Emerson NetSure 4015 DC Application Guide

Home

SYSTEM OVERVIEW

Description: 400V DC Output @ up to 30kW Power System
The NetSure™ 4015, 30kW DC Power System is a complete integrated power system containing rectifiers, intelligent control, metering, monitoring, and distribution. The individual system sub-racks can be factory integrated into a standard 19” IT rack or provided separately for customer integration into an existing IT rack.
This power system is capable of operating either with or without batteries online. This system consists of the following components.
Power and Control Sub-Rack (List 11, 12)
SAG584000300
System Application Guide
NetSure 4015 30kW 400V DC Power System
Spec. No. 584000300 (Model 4015-X003)
Issue AB, April 5, 2013
The system contains one (1) “power and control sub-rack”, which houses up to two (2) rectifiers and the system control and monitoring components.
Rectifier(s)
The system contains one (1) or two (2) rectifiers, which provide load power, battery float current, and battery recharge current during normal operating conditions. Refer to the rectifier instructions (UM1R40015000e) for more information.
Controls
ACU+ (Advanced Control Unit Plus) Controller The system controller provides power system control, rectifier control (including a
charge control function), metering functions, monitoring functions, and local/remote alarm functions. Power system control includes battery low voltage disconnect (BLVD) functionality to remotely trip battery circuit breakers which protects batteries against over-discharge. The system can also be equipped with one (1) or two (2) temperature probe(s). Any combination of the two (2) temperature probes can be programmed to monitor ambient air temperature and/or battery temperature. A temperature probe set to monitor battery temperature can also be used for the rectifier battery charge temperature compensation feature and/or BTRM (battery thermal runaway management) feature. The controller also provides data acquisition, system alarm management, and advanced battery and energy management. The controller contains an LCD display and keypad for local access. The controller provides Ethernet connection and supports software upgrade via its USB port. It also comes with a comprehensive web page and SNMP capability for remote system management. Refer to the ACU+ controller instructions (UM1M820NNB-1) for more information.
System Shutdown
A “System Shutdown” pushbutton is
located on the front of the power and control sub-rack. When momentarily
depressed, the rectifier’s AC input circuit
breakers and the Emerson provided
battery trays’ battery disconnect circuit
breakers are tripped open to isolate the system from all electrical sources. Manual intervention is required to restart the system.
Page 1 of 32
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG584000300 System Application Guide
Home
Complete Solution
(components factory installed
in an Emerson Network
Power DCM IT Rack)
Individual Components
Issue AB, April 5, 2013 NetSure 4015 30kW 400V DC Power System Spec. No. 584000300 (Model 4015-X003)
Load Distribution Sub-Rack(s) (List 21-24)
The system may contain up to two (2) load distribution sub-racks, which provide DC distribution through circuit breakers. Optional main row breaker required for UL applications. Distribution can also be bulk with no “distribution sub-rack”.
Battery Tray(s) (List 91, 92)
The system may contain up to five (5) battery trays, each housing one (1) 400V battery string consisting of twenty-eight (28) 12V battery blocks (336V nominal). Customer supplied external battery strings can be connected to the system. The total number of internal and external battery strings cannot exceed five (5).
IT Rack Integration (List R1, R2)
Choice of 24U or 42U rack, also includes factory installation, integration, and testing of all selected components.
Available Grounding Configurations
HRMG (High Resistance Midpoint Ground) Configuration (+/- 200V DC) The HRMG configuration provides system voltages to ground at half of the output
system voltage, for additional personnel safety. That is, the HRMG version of 400V DC produces +/-200V DC to ground potentials. This configuration is used in applications where an internal high resistance path is required between the positive output busbar and site ground and also the negative output busbar and site ground.
The DC bus is continuously monitored for ground fault conditions. If the insulation resistance between the +BUS or -BUS to ground goes below a set value, a ground fault alarm is generated. (Refer to UM584000300 [Operation Instructions] for additional information on this topic.)
NPG (Negative Pole Ground) Configuration (+400V, -0V DC) This configuration is used in applications where the negative output busbar is
required to be connected to site ground.
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 2 of 32
System Application Guide SAG584000300
Home
NetSure 4015 30kW 400V DC Power System Issue AB, April 5, 2013 Spec. No. 584000300 (Model 4015-X003)
General Specifications Family: NetSure System Spec. No.: 584000300 System Model: 4015-X003 System AC Input Voltage Nominal 380/400/480 volts AC, three phase, 50/60 Hz, with an
operating range of 260 to 530 volts. Acceptable input frequency range is 45 to 65 Hz. A single 4-wire (no neutral) AC input feed
supplies both rectifiers. System Output Voltage (max.): 400V DC Output Capacity:
System: 89A, 30kW (maximum) Rectifier: 44.6A @ 336V DC to 37.5A @ 400V DC, 15kW (maximum)
System Agency Approval: UL Listed per UL60950-1 (cUL for Canada). CE Marking per low
voltage directive (EN60950) and the EMC directive.
(See 1.5.1 Safety Compliance” on page 27.) EMI: EN 300 386, Class A and FCC Part 15, Class A Framework Type: Rack Mounting in an IT Rack (EIA-310-D Compliant) Mounting Width: 19 Inches (483mm), nominal Mounting Depth:
Power and Control Sub-Rack: 724mm (28.5 inches) Load Distribution Sub-Rack: 257mm (10 inches), HRMG Configuration
317mm (12.5 inches), NPG Configuration
Battery Tray: 838mm (33 inches) 24U Rack Dimensions: 1194mmH x 600mmW x 1000mmD (47"H x 24"W x 40"D) 42U Rack Dimensions: 2000mmH x 600mmW x 1000mmD (79"H x 24"W x 40"D) Access: Front and rear for installation and maintenance.
Front for operation. Control: Microprocessor Color: Black Environment: -5°C to +45°C (+23°F to +113°F).
Full Rating: -5°C to +35°C (+23°F to +95°F).
Note: Battery manufacturers recommend an operating temperature
of 25°C (77°F). Ambient temperatures higher than this reduce
battery life; temperatures lower than this reduce battery capacity.
For optimal battery performance and service life, battery temperature
should be maintained between +20°C to +25°C (+68°F to +77°F).
See detailed specifications on page 26. Customer Supplied IT Rack Guidelines
If you plan to assemble / configure your own system, note that the NetSure 4000 Series components (power and control sub-rack / load distribution sub-rack / battery tray) were evaluated as a UL Listed system in an Emerson Network Power DCM IT Rack in an ambient of +35°C (95°F), with a front and rear door free area ratio of 83%.
Page 3 of 32
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG584000300 System Application Guide Issue AB, April 5, 2013 NetSure 4015 30kW 400V DC Power System Spec. No. 584000300 (Model 4015-X003)

TABLE OF CONTENTS

SYSTEM OVERVIEW................................................................................................................................................. 1
TABLE OF CONTENTS ............................................................................................................................................. 4
MAIN COMPONENTS ILLUSTRATIONS .................................................................................................................. 6
Factory System Integration – Lists R1 and R2 (Assembled System) ............................................................ 6
Customer System Integration – Installed in Customer IT Rack ..................................................................... 6
Power and Control Sub-Rack - Lists 11 (HRMG) and List 12 (NPG) .............................................................. 7
Load Distribution Sub-Rack – List 21-24 .......................................................................................................... 8
Battery Tray - List 91 (HRMG) and List 92 (NPG) ............................................................................................. 9
LIST DESCRIPTIONS .............................................................................................................................................. 10
Power and Control Sub-Rack ........................................................................................................................... 11
List 11: Power and Control Sub-Rack – HRMG (High Resistance Midpoint Grounded) Systems ............... 11
List 12: Power and Control Sub-Rack – NPG (Negative Pole Grounded) Systems ..................................... 11
Load Distribution Sub-Rack ............................................................................................................................. 12
List 21: Load Distribution Sub-Rack with Row Breaker – HRMG (High Resistance Midpoint
Grounded) Systems ....................................................................................................................................... 12
List 22: Load Distribution Sub-Rack with Row Breaker – NPG (Negative Pole Grounded) Systems .......... 12
List 23: Load Distribution Sub-Rack without Row Breaker – HRMG (High Resistance Midpoint
Grounded) Systems ....................................................................................................................................... 13
List 24: Load Distribution Sub-Rack without Row Breaker – NPG (Negative Pole Grounded)
Systems .......................................................................................................................................................... 13
Battery Tray ........................................................................................................................................................ 14
List 91: Battery Tray – HRMG (High Resistance Midpoint Grounded) Systems .......................................... 14
List 92: Battery Tray – NPG (Negative Pole Grounded) Systems ................................................................ 14
Temperature Probes ......................................................................................................................................... 15
List 98: Temperature Probe, 12 Feet (4m) Total Cable Length ..................................................................... 15
List 99: Temperature Probe, 33 Feet (10m) Total Cable Length ................................................................... 15
Rack Integration (Factory Integrated System) ............................................................................................... 16
List R1: 24U, 19” ........................................................................................................................................... 16
List R2: 42U, 19” ........................................................................................................................................... 16
ACCESSORY DESCRIPTIONS ............................................................................................................................... 17
DC Load Distribution Devices .......................................................................................................................... 17
DIN-Rail Type Load Circuit Breakers ............................................................................................................. 17
Load Circuit Breaker Lockout/Tagout Assembly ............................................................................................ 18
User Replaceable Components ....................................................................................................................... 19
ONE LINE DIAGRAM............................................................................................................................................... 20
RECOMMENDED WIRING SIZES, BRANCH CIRCUIT PROTECTION, AND CRIMP LUGS ............................... 21
Equipment Grounding ...................................................................................................................................... 21
Factory Furnished IT Rack Frame Grounding ............................................................................................... 21
Sub-Rack Frame Grounding (for systems installed in a customer furnished IT rack) ................................... 21
Return Busbar (-Bus) Grounding (NPG Configurations Only) ....................................................................... 22
AC Input (Power and Control Sub-Rack) ........................................................................................................ 23
DC Load Distribution (Distribution Sub-Rack) ............................................................................................... 24
DC Load Distribution (Bulk Output from Power and Control Sub-Rack) .................................................... 25
External Controller Interface (Distribution Sub-Rack)................................................................................... 25
Battery (Power and Control Sub-Rack) ........................................................................................................... 25
SPECIFICATIONS .................................................................................................................................................... 26
1. System ........................................................................................................................................................... 26
1.1 System DC Output Ratings...................................................................................................................... 26
1.2 System AC Input Ratings......................................................................................................................... 26
1.3 System Environmental Ratings ............................................................................................................... 26
Page 4 of 32
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG584000300 NetSure 4015 30kW 400V DC Power System Issue AB, April 5, 2013 Spec. No. 584000300 (Model 4015-X003)
1.4 Physical.................................................................................................................................................... 26
1.5 System Compliance Information .............................................................................................................. 27
2. Rectifier .......................................................................................................................................................... 27
3. ACU+ Controller ............................................................................................................................................ 27
MECHANICAL SPECIFICATIONS .......................................................................................................................... 28
Rack Integrated System (24U) (List R1) .......................................................................................................... 28
Rack Integrated System (42U) (List R2) .......................................................................................................... 28
Dimensions and Weights .................................................................................................................................. 29
RELATED DOCUMENTATION ................................................................................................................................ 31
BATTERY MANUFACTURER INFORMATION ...................................................................................................... 31
Page 5 of 32
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG584000300 System Application Guide
Home
Complete Solution
(components factory installed
in Emerson Network Power
DCM 24U IT rack)
Complete Solution (components factory installed in Emerson Network Power DCM 42U IT rack)
Doors/Sides Removed in Illustration for Clarity
Load Distribution Sub-Rack(s) (6U each)
Power and Control Sub-Rack (6U)
Optional Battery Tray(s) (4U each)
(List 21, 22, 23, 24)
(List 11 and 12)
(List 91 and 92)
List R1:
List R2:
Issue AB, April 5, 2013 NetSure 4015 30kW 400V DC Power System Spec. No. 584000300 (Model 4015-X003)
MAIN COMPONENTS ILLUSTRATIONS Factory System Integration – Lists R1 and R2 (Assembled System)
Note: Also order individual sub-racks List 11, 12, 21, 22, 23, 24, 91, 92;
not to exceed 24U for List R1 and 42U for List R2. See List Descriptions on page 10.

Customer System Integration – Installed in Customer IT Rack

Note: Order List 11, 12, 21, 22, 23, 24, 91, 92.
See List Descriptions on page 10.
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 6 of 32
System Application Guide SAG584000300
Home
Front
Rectifier Module AC Input Circuit Breakers (40A, 380V/400V/480V AC)
ACU+ Interface Board (IB2)
(behind cover)
ACU+ Controller
Rectifier Modules
Adjustable Rear Mounting Brackets
Front Mounting Flanges
System Shutdown Button
AC Input Leads Opening for 25mm (1) Conduit
Alarm Leads Opening for 25mm (1) Conduit
DC Output Leads Openings
for 32mm (1.25) Conduit
Battery Leads Openings for
19mm (0.75) Conduit
(top and bottom)
AC Surge
Protectors
Removable Panels
(for installation)
Battery
Shunt
Battery Terminals (5 sets of studs for double hole lugs, each polarity)
External and Internal Battery Tray Control/Alarm Connectors
Sub-Rack Grounding Stud
DC Output Terminals (2 sets of studs for double hole lugs, each polarity)
AC Input
Terminals
Rear
HRMG Ground Connection (HRMG Configurations Only) (MUST BE PROPERLY CONNECTED TO GROUND)
NetSure 4015 30kW 400V DC Power System Issue AB, April 5, 2013 Spec. No. 584000300 (Model 4015-X003)

Power and Control Sub-Rack - Lists 11 (HRMG) and List 12 (NPG)

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 7 of 32
SAG584000300 System Application Guide
Home
Rear
HRMG Configuration NPG Configuration
Sub-Rack Grounding Stud
Sub-Rack
Grounding Stud
DC Distribution Leads Openings
for 25mm (1) Conduit
(snap bushings are furnished
for use without conduit)
Removable Panel
Rear
Return Bar
Grounding Point
(opening for 19mm [0.75"]
conduit provided)
Front
Front
Conduit Grounding Points (opposite side also) (both HRMG and NPG)
Distribution Blocks hold factory wiring in unused breaker locations for ease of adding future circuit breakers. (both HRMG and NPG)
Customer Load Connections to DC Distribution Circuit Breakers
Removable Panel (for installation) (both HRMG and NPG)
Customer
Load Connections
to DC Distribution
Circuit Breakers
Customer Load Return Connections to Return Bar
List Row Breaker HRMG NPG
21 X X 22 X X 23 X 24 X
Front
DC Distribution Circuit Breakers - 9 positions (4A, 6A, 8A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A)
Future Circuit Breaker Mounting Positions
Optional (List 21, 22)
Row DC Distribution
Circuit Breaker (125A)
DC Distribution
Input Leads
(from Power and
Control Sub-Rack)
Front Mounting Flanges
Issue AB, April 5, 2013 NetSure 4015 30kW 400V DC Power System Spec. No. 584000300 (Model 4015-X003)

Load Distribution Sub-Rack – List 21-24

Page 8 of 32
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG584000300
Home
Six (6) Removable Battery Sub-Trays Four (4) trays equipped with five (5) 12V DC battery blocks. Two(2) trays equipped with four (4) 12V DC battery blocks. Battery blocks in each tray are factory wired.
Battery Breaker (40A)
Front
Rear
Adjustable Rear Mounting Brackets
Front Mounting Flanges
Tray Grounding Stud
Battery Sub-Trays
Battery Tray
View of Individual Battery Sub-Tray
Battery Retaining Bracket
(shipped installed, remove to
install battery sub-trays)
Battery Sub-Tray Connector
Battery wiring connectorized for easy installation.
Battery Tray Connector
Battery Tray Power Cables
Battery Tray Control/Alarm Harness
NetSure 4015 30kW 400V DC Power System Issue AB, April 5, 2013 Spec. No. 584000300 (Model 4015-X003)

Battery Tray - List 91 (HRMG) and List 92 (NPG)

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 9 of 32
SAG584000300 System Application Guide
Home
List
Number
Part
Number
Description
Rack Unit
Height
11
58400030011
Power and Control Sub-Rack – HRMG (High Resistance Midpoint Grounded) Systems
6U
12
58400030012
Power and Control Sub-Rack – NPG (Negative Pole Grounded) Systems
6U
21
58400030021
Load Distribution Sub-Rack with Row Breaker – HRMG (High Resistance Midpoint Grounded) Systems
6U
22
58400030022
Load Distribution Sub-Rack with Row Breaker – NPG (Negative Pole Grounded) Systems
6U
23
58400030023
Load Distribution Sub-Rack without Row Breaker – HRMG (High Resistance Midpoint Grounded) Systems
6U
24
58400030024
Load Distribution Sub-Rack without Row Breaker – NPG (Negative Pole Grounded) Systems
6U
91
58400030091
Battery Tray – HRMG (High Resistance Midpoint Grounded) Systems
4U
92
58400030092
Battery Tray – NPG (Negative Pole Grounded) Systems
4U
R1
584000300R1
Rack Integration (Factory Integrated System) 24U, 19”
24U
R2
584000300R2
Rack Integration (Factory Integrated System) 42U, 19”
42U
98
58400030093
Temperature Probe, 12 Feet (4m)
--
99
58400030094
Temperature Probe, 33 Feet (10m)
--
Issue AB, April 5, 2013 NetSure 4015 30kW 400V DC Power System Spec. No. 584000300 (Model 4015-X003)

LIST DESCRIPTIONS

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Page 10 of 32