Emerson NetSure 211, NetSure 211BC Ordering Guides

Compact Indoor and Outdoor Cell Site Solutions
Outdoor Solution With DC Power
The outdoor site solution includes the NetSure™ 211 power system and the NetXtend Compact 2416 is a small single sided low-cost outdoor rated aluminum enclosure with a heat exchanger cooling system.
n NEMA 3R design protects equipment from water and dust,
while maintaining a cool operating environment
n NetSure
+75 °C, providing 400 W output at 65 °C, suitable for harsh environmental conditions
n UL and cUL listing
ensures documented performance
n GR-487-CORE Issue 3
design ensures system reliability and durability
Application
The Outdoor Solution With DC Power is ideal for inconspicuous deployment of Alternative Access Vendor (AAV) applications, mobile 2G/3G/4G cellular base stations, DAS nodes, mobile back­haul, remote power solutions, fiber (FTTx) nodes, advanced metering management (AMM) nodes or hybrid controller systems (solar, wind, etc.).
Compact 2416 cabinet. The NetXtend™
rectifiers are designed to operate from -40 °C to
Technical Specifications
Electrical
System Voltage Output Voltage -42 VDC to -58 VDC System Capacity 19" 1 RU up to 8 A Rectifier Capacity 0.4 kW @ 120 VAC DC Distribution Wallmount GMT fuse panel with (10) fuses, up to 15 A Controller SCU+ controller
Physical Characteristics
Framework Type Available Space Dimensions
(H x W x D) Mounting Weight, Equipped
Access
Environmental
Climate System Heat Exchanger Operating Temp. -40 °C to +52 °C Storage Temp. -40 °C to +75 °C Relative Humidity 100% EMI/RFI Conforms to FCC rules Part 15, Subpart B, Class B and EN55022
Safety Compliance cULus 60950 Recognized, NEBS Level 3 Compliance
See rectifier specification for any derating. Operating and storage temperatures for
*
batteries installed in the battery cabinet are provided by the battery manufacturer.
120 VAC single phase (nominal)
NetXtend Up to 14 RU, 19" W Enclosure: 24" x 24" x 16"
Battery tray: 22" W x 13" D Wall or H-frame, pole mount (wall-mount kit included) Enclosure: 64 lb., w/out batteries
Four (4) batteries: 36 lb. total Front
Class B, radiated and conducted
Enclosure: cULus Listed GR-487
Compact Enclosure
Ordering Information
Dimensions
8.57"
16.67"
24.00"
16.00"
24.00"
Emerson Number Description
F2013074 Outdoor Solution w/DC Power F2014025 Outdoor Solution w/DC Power
Equipped with the following: Equipped with the following:
1 EA NetXtend
1 EA NetSure 2 EA 500 W rectifiers 2 EA 500 W rectifiers 1 EA 19" rack-mount, slide-out tray 1 EA AC outlet mounting bracket 1 EA AC outlet mounting bracket 2 EA 20 A, 120 VAC outlets 2 EA 20 A, 120 VAC outlets 1 EA Wall-mounting kit 1 EA Wall-mounting kit
Accessories
547681 Battery, EnerSys NP12-12,12 AH bat mod, 4 EA 524855 Battery, GNB Marathon, M12V30NT, 30 AH bat mod, 4 EA 140454 Battery, C&D 12-45, 45 AH bat mod, 4 EA
exchanger, and slide-out shelf
Compact with heat
NXC2416AAV1H05BB3
211 power system 1 EA NetSure™ 211 power system
Emerson Number Description
1 EA NetXtend
exchanger,
(no slide-out shelf)
Compact with heat
NXC2416AAV1H05BB3
1095ORB-GMCSS / 0614
Compact Indoor and Outdoor Cell Site Solutions
Indoor Solution With DC Power
The indoor site solution combines a NetSure™ 211 -48 VDC power system with reliable rectifiers, an advanced Ethernet­accessible controller, flexible distribution and high power density. An enclosed battery cabinet is included that can be mounted on the wall or in a relay rack. A 40 A battery disconnect is included with the battery cabinet and can be connected in parallel with other cabinets to provide additional backup time.
n Supports Ethernet and
SNMP communication interfaces, enabling remote control and monitoring
n NetSure
rectifiers are
designed to operate from
-40 °C to +75 °C, providing 500 W output at 45 °C, suitable
Indoor Solution
(shown without cover)
for harsh environmental conditions
n Extremely wide AC voltage range
window, 85 VAC to 300 VAC
Application
The Indoor Solution With DC Power is designed for deployment in wireless sites, central office, POP sites, co-location sites, customer premises, outdoor cabinets, CEVs, vaults or portable shelters. Specific applications include: Alternative Access Vendor (AAV), wireless backhaul and other site solutions such as, DAS, DLC, xDSL, DSLAM, FTTx electronics, broadband communica­tions, multiplexers, LTE, WiMAX, microwave and PBX.
Dimensions
17.7"
Technical Specifications
Electrical
System Voltage Output Voltage -42 VDC to -58 VDC System Capacity 19" 1 RU up to 10 A Rectifier Capacity 0.5 kW @ 120 VAC DC Distribution Wallmount GMT fuse panel with (10) fuses, up to 15 A Controller SCU+ controller
Physical Characteristics
Framework Type Available Space Dimensions
(H x W x D) Mounting Weight, Equipped
Access
Environmental
Climate System Fan-cooled front to rear Operating Temp. -40 °C to +75 °C* Storage Temp. -40 °C to +75 °C Relative Humidity 0% to 95% non-condensing EMI/RFI Conforms to FCC rules Part 15, Subpart B, Class B and EN55022
Safety Compliance cULus 60950 recognized NEBS Level 3 Compliance
See rectifier specification for any derating. Operating and storage temperatures for
*
batteries installed in the battery cabinet are provided by the battery manufacturer.
120 VAC single phase (nominal)
Relay rack 1 RU 19" W DC power system: 1.7" x 19" x 12"
Solution: 10.5" x 19" x 15.6" Rack or wall mount System: 35.5 lb., w/out batteries
Four (4) batteries: 36 lb. total Front for batteries, control and distribution, rear for AC
Class B, radiated and conducted
Ordering Information
Emerson Part Number
582136600SK010 Indoor Solution w/DC Power
Equipped with the following:
1 EA NetSure 2 EA 500 W rectifiers 1 EA 19" rack-mount, slide-out tray 1 EA Battery cabinet 1 EA Wall mount bracket
Accessories
547681 Battery, EnerSys NP12-12, 12 AH bat mod, 4 EA
Description
211 power system
1.9"
1.7"
6.9"
17.5"
2 095ORB-GMCSS / 0614
5.0"
10.5"
15.6"