The outdoor site solution includes the NetSure™ 211 power system
and the NetXtend
Compact 2416 is a small single sided low-cost outdoor rated
aluminum enclosure with a heat exchanger cooling system.
n NEMA 3R design protects equipment from water and dust,
while maintaining a cool operating environment
n NetSure
+75 °C, providing 400 W output at 65 °C, suitable for harsh
environmental conditions
n UL and cUL listing
ensures documented
performance
n GR-487-CORE Issue 3
design ensures
system reliability
and durability
Application
The Outdoor Solution With DC Power is ideal for inconspicuous
deployment of Alternative Access Vendor (AAV) applications,
mobile 2G/3G/4G cellular base stations, DAS nodes, mobile backhaul, remote power solutions, fiber (FTTx) nodes, advanced
metering management (AMM) nodes or hybrid controller
systems (solar, wind, etc.).
™
Compact 2416 cabinet. The NetXtend™
™
rectifiers are designed to operate from -40 °C to
Technical Specifications
Electrical
System Voltage
Output Voltage-42 VDC to -58 VDC
System Capacity19" 1 RU up to 8 A
Rectifier Capacity0.4 kW @ 120 VAC
DC DistributionWallmount GMT fuse panel with (10) fuses, up to 15 A
ControllerSCU+ controller
Physical Characteristics
Framework Type
Available Space
Dimensions
(H x W x D)
Mounting
Weight, Equipped
Access
Environmental
Climate SystemHeat Exchanger
Operating Temp.-40 °C to +52 °C
Storage Temp.-40 °C to +75 °C
Relative Humidity100%
EMI/RFIConforms to FCC rules Part 15, Subpart B, Class B and EN55022
See rectifier specification for any derating. Operating and storage temperatures for
*
batteries installed in the battery cabinet are provided by the battery manufacturer.
120 VAC single phase (nominal)
™
NetXtend
Up to 14 RU, 19" W
Enclosure: 24" x 24" x 16"
Battery tray: 22" W x 13" D
Wall or H-frame, pole mount (wall-mount kit included)
Enclosure: 64 lb., w/out batteries
Four (4) batteries: 36 lb. total
Front
Class B, radiated and conducted
Enclosure: cULus Listed GR-487
Compact Enclosure
Ordering Information
Dimensions
8.57"
16.67"
24.00"
16.00"
24.00"
Emerson
Number Description
F2013074 Outdoor Solution w/DC Power F2014025 Outdoor Solution w/DC Power
Equipped with the following:Equipped with the following:
1 EANetXtend
1 EANetSure
2 EA500 W rectifiers2 EA500 W rectifiers
1 EA19" rack-mount, slide-out tray1 EAAC outlet mounting bracket
1 EAAC outlet mounting bracket2 EA20 A, 120 VAC outlets
2 EA20 A, 120 VAC outlets1 EAWall-mounting kit
1 EAWall-mounting kit
Accessories
547681 Battery, EnerSys NP12-12,12 AH bat mod, 4 EA
524855 Battery, GNB Marathon, M12V30NT, 30 AH bat mod, 4 EA
140454 Battery, C&D 12-45, 45 AH bat mod, 4 EA
™
exchanger,
and slide-out shelf
Compact with heat
NXC2416AAV1H05BB3
™
211 power system1 EANetSure™ 211 power system
Emerson
Number Description
1 EANetXtend
™
exchanger,
(no slide-out shelf)
Compact with heat
NXC2416AAV1H05BB3
1095ORB-GMCSS / 0614
Compact Indoor and Outdoor Cell Site Solutions
Indoor Solution With DC Power
The indoor site solution combines a NetSure™ 211 -48 VDC
power system with reliable rectifiers, an advanced Ethernetaccessible controller, flexible distribution and high power
density. An enclosed battery cabinet is included that can be
mounted on the wall or in a relay rack. A 40 A battery disconnect
is included with the battery cabinet and can be connected in
parallel with other cabinets to provide additional backup time.
n Supports Ethernet and
SNMP communication
interfaces, enabling remote
control and monitoring
n NetSure
™
rectifiers are
designed to operate from
-40 °C to +75 °C, providing
500 W output at 45 °C, suitable
Indoor Solution
(shown without cover)
for harsh environmental conditions
n Extremely wide AC voltage range
window, 85 VAC to 300 VAC
Application
The Indoor Solution With DC Power is designed for deployment
in wireless sites, central office, POP sites, co-location sites,
customer premises, outdoor cabinets, CEVs, vaults or portable
shelters. Specific applications include: Alternative Access Vendor
(AAV), wireless backhaul and other site solutions such as, DAS,
DLC, xDSL, DSLAM, FTTx electronics, broadband communications, multiplexers, LTE, WiMAX, microwave and PBX.
Dimensions
17.7"
Technical Specifications
Electrical
System Voltage
Output Voltage-42 VDC to -58 VDC
System Capacity19" 1 RU up to 10 A
Rectifier Capacity0.5 kW @ 120 VAC
DC DistributionWallmount GMT fuse panel with (10) fuses, up to 15 A
ControllerSCU+ controller
Physical Characteristics
Framework Type
Available Space
Dimensions
(H x W x D)
Mounting
Weight, Equipped
Access
Environmental
Climate SystemFan-cooled front to rear
Operating Temp.-40 °C to +75 °C*
Storage Temp.-40 °C to +75 °C
Relative Humidity0% to 95% non-condensing
EMI/RFIConforms to FCC rules Part 15, Subpart B, Class B and EN55022
See rectifier specification for any derating. Operating and storage temperatures for
*
batteries installed in the battery cabinet are provided by the battery manufacturer.
120 VAC single phase (nominal)
Relay rack
1 RU 19" W
DC power system: 1.7" x 19" x 12"
Solution: 10.5" x 19" x 15.6"
Rack or wall mount
System: 35.5 lb., w/out batteries
Four (4) batteries: 36 lb. total
Front for batteries, control and distribution, rear for AC
Class B, radiated and conducted
Ordering Information
Emerson
Part Number
582136600SK010 Indoor Solution w/DC Power
Equipped with the following:
1 EANetSure
2 EA500 W rectifiers
1 EA19" rack-mount, slide-out tray
1 EABattery cabinet
1 EAWall mount bracket
Accessories
547681Battery, EnerSys NP12-12, 12 AH bat mod, 4 EA
Description
™
211 power system
1.9"
1.7"
6.9"
17.5"
2095ORB-GMCSS / 0614
5.0"
10.5"
15.6"
Compact Indoor and Outdoor Cell Site Solutions
631-205-411
VersionC, July 29, 2013
Outdoor Solution Without DC Power
The outdoor site solution (without DC power) is a small single
sided low-cost outdoor rated aluminum enclosure with a heat
exchanger cooling system, equipment rack and fused
terminal blocks.
n NEMA 3R design protects equipment from water and dust,
while maintaining a cool operating environment
n UL and cUL listing ensures documented performance
n GR-487-CORE Issue 3 design ensures system reliability
and durability
n Aluminum construction provides superior protection for
panels, cables and splices, offering a long, corrosion resistant,
problem-free service life
NetXtend
deployment of Alternative Access Vendor (AAV) applications,
mobile 2G/3G/4G cellular base stations, DAS nodes, mobile
backhaul, remote power solutions, fiber (FTTx) nodes, advanced
metering management (AMM) nodes or hybrid controller
systems (solar, wind, etc.).
™
Compact enclosures are ideal for inconspicuous
Technical Specifications
Physical Characteristics
Framework Type
Available Space
Dimensions
Mounting
Weight
Access
Environmental
Climate System500 W heat exchanger
Operating Temp.-40 °C to +52 °C
Storage Temp.-40 °C to +75 °C
Relative Humidity 100%
EMI/RFIConforms to FCC rules Part 15, Subpart B, Class B and
Safety Compliance UL Listed, cUL, GR-487
NetXtend
Up to 13 RU, 19" W
Enclosure: 24" H x 24" W x 16" D
Wall/H-frame or pole mount
64 lb.
Front
EN55022 Class B, radiated and conducted
™
Compact Enclosure
Diagrams
Wall Mounting
Ordering Information
Emerson
Part Number Description
F2014020NetXtend
equipped with:
F2014015NetXtend
equipped with:
F2014016NetXtend
equipped with:
Accessories
F1010408(1) Wall mount kit
F1010409(1) Pole mount kit
Business-Critical Continuity™, Emerson Network Power™, the Emer son Net work Power l ogo, Emer son™ and Consi der it Solv ed are ser vice mark s and
tradem arks of Eme rson Elec tric Co. En ergyMas ter
Netw ork Power, Ener gy Systems , North Am erica, In c. Any other p roduct , brand, or co mpany names o r logos are t he proper ty of the r especti ve owner.
™
, eSure™, NetPerform™, NetReach™, NetSpan™, NetSu re™ and NetXtend™ are trad emarks of E merson
While ev ery prec aution has b een taken to e nsure accur acy and
completeness herein, Emerson Electric Co. assumes no responsibility,
and disc laims all liab ility, for da mages resul ting from u se of this
information or for any errors or omissions. Specifications subject to
change without notice.
4095ORB-GMCSS / 0614
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.