vi • MRLDS-450 Refrigerant Gas Detection I&O Manual 026-1316 Rev 2
1Introduction
1.1.About this Manual
Thank you for investing in an MRLDS-450 Gas Detector. To ensure operator safety
and the proper use of the gas detector, please read the contents of this manual for
important information about the operation and maintenance of the instrument.
IMPORTANT: Before installing this product, carefully read and strictly follow the
instructions in the manual.
1.2.Iconography
AlertIconDescription
DangerImminently hazardous situation which, if not avoided,
will result in serious injury or death.
WarningPotentially hazardous situation which, if not avoided,
could result in serious injury or death.
Potential electrical shock hazard which, if not avoided,
could result in serious injury or death.
CautionPotentially hazardous situation which, if not avoided,
could result in physical injury or damage to the product
or environment. It may also be used to alert against
unsafe practices.
ImportantAdditional information on how to use the product.
Table 1-1 - Icons
About this ManualIntroduction • 1
1.3.General Safety Requirements
IMPORTANT: Before using this product, carefully read and strictly follow the instructions
in the manual. Ensure that all product documentation is retained and available to anyone
operating the instrument.
DANGER! This instrument is neither certified nor approved for operation in
oxygen-enriched atmospheres. Failure to comply may result in personal injury or death.
DANGER! This instrument has not been designed to be intrinsically safe for use in areas
classified as being hazardous locations. For your safety, DO NOT use it in hazardous
(classified) locations.
WARNING! Use this product only for the purposes specified in this document and under
the conditions listed.
CAUTION! In the event of an alarm or over-range condition, the sensor must be
re-calibrated to ensure continued accuracy.
CAUTION! This product must be re-calibrated if installed in a non-room condition
environment (For example, temperature or humidity extremes).
CAUTION! The gas diffusion path can become occluded (moisture, dust, debris, frozen
condensation) over time resulting in reduced or complete lack of gas detection and
alarming function. Routine visual inspection of the gas detector and bump testing are
suggested to ensure proper gas detection and alarm function.
CAUTION! Except for maintenance detailed in this manual, these products should only be
opened and/or serviced by authorized Emerson Technical Support personnel.
Failure to comply may void the warranty.
CAUTION! Operator assumes responsibility for complying with all laws, rules and
regulations governing the use of this product.
CAUTION! Use only genuine Emerson parts and accessories. Failure to comply may
impair the operation of the product and/or void the warranty.
CAUTION! Only operate the product within the framework of a risk-based alarm signaling
concepts.
WARNING! The gas diffusion path can become occluded (moisture, dust, debris, frozen
condensation) over time, resulting in reduced or complete lack of gas detection and
alarming function. Routine visual inspection of the gas detector and bump testing are
recommended to ensure proper gas detection and alarm function. For information on
calibrating the sensor, refer to the “Care and Maintenance” section of this manual.
1.4.Safe Connection of Electrical Devices
WARNING! Before connecting this instrument to electrical devices not mentioned in this
manual, consult the manufacturer or a qualified professional. Failure to comply may result
in personal injury and/or damage to the product.
Safe Connection of Electrical DevicesIntroduction • 3
2Product Description
2.1.Intended Uses/Applications
MRLDS-450 Gas Detection Series instruments continuously monitor ambient air
(indoor or outdoor) for the following gas types:
• Refrigerants
• Oxygen
• Toxic and combustible gases
The MRLDS-450 refrigerant gas detector is designed for use in refrigeration
applications and with the integrated audio-visual alarm indication, can be operated
as a stand-alone unit (with additional local alarm signaling as required), or it may be
connected to a facility's building management system (BMS). It enables compliance
with refrigerant safety codes (ASHRAE 15 and EN378) and alarms to alert
personnel in the event of a refrigerant leak.
DANGER! This instrument is neither certified nor approved for operation in
oxygen-enriched atmospheres. Failure to comply may result in EXPLOSION.
DANGER! This instrument has not been designed to be intrinsically safe for use in areas
classified as being hazardous locations. For your safety, DO NOT use it in hazardous
(classified) locations.
2.2.MRLDS-450
2.2.1. MRLDS-450 Product Overview
The Emerson MRLDS-450 continuously monitors indoor or outdoor ambient air for
the following gases:
With the integrated Modbus communication, analog output and relays, the
instrument can be operated as a stand-alone unit or as a third-party device capable
of accepting digital and/or analog outputs from the gas detectors, such as a Building
Management System (BMS) or a Supervisory Controller. The instrument is
designed to be installed in non-classified, non-hazardous, permanent locations.
Figure 2-1 - MRLDS-450
2.2.2. MRLDS-450 Design Features
• Transmitter: IP66 rated ABS enclosure
• Power options:
• 24VAC
• 19.5 to 28.5VDC
• Diagnostic/Status LED (3 color): Green, Orange, and Red
• Configurable output signal options
• 3× Relays (high alarm/low alarm/fault)
• 1× Analog Output (4 to 20mA, 0 to 5V, 0 to 10V, 1 to 5V, 2 to 10V)
• Digital Output (Modbus RTU signal)
Bluetooth communication allows for full instrument configuration, initiation of
calibration, bump test and functional test mode, and viewing of status information
via the corresponding MRLDS-450 iOS/Android app.
Non-intrusive magnetic wand can be used to initiate calibration of the device.
CAUTION! The manufacturer of this product requires that a bump test or calibration be
performed following installation to verify instrument functionality.
3.1.General Information
Every detail of installation site selection is critical to ensure overall system
performance and effectiveness. Strict compliance and considerable thought must be
given to every detail of the installation process, including, but not limited to the
following:
• Regulations as well as local, state, and national codes that govern the installation of
gas monitoring equipment.
• Electrical codes that govern the routing and connection of electrical
cables to gas monitoring equipment.
• The full range of environmental conditions to which the instruments
• The physical characteristics of the gas or vapor to be detected.
• The specifics of the application (For example, possible leaks, air movement/draft,
etc.)
• The degree of accessibility required for maintenance purposes.
• The types of optional equipment and accessories that will be used with the system.
• Any limiting factors or regulations that would affect system performance or
installations.
• Wiring details, including:
• The MRLDS-450 enclosure provides the following cable gland openings:
• 2×, M20, supports 10-14mm cable outer diameter
• 6×, M16, supports 4-8mm cable outer diameter
• Secondary circuit must be supplied from an isolating source.
• The wiring for the relays must be selected and fused according to the rated
voltages, currents, and environmental conditions.
• If stranded conductions are used, ferrule should be used.
• To comply with RFI immunity regulations, it is necessary to ground the shield of
the communications cable at the PLC, GDA controller, front-end controller or
Building Management System (For example, the chassis, the ground bus-bar,
etc.).
power and signal
will be exposed.
General InformationInstallation • 7
3.2.Restrictions
The installation location must have appropriate supply power available for the
instrument (For example, 19.5 to 28.5VDC or 24VAC). This ultimately determines
the distance the instrument can be mounted from the controller or power supply.
3.3.Mechanical Installation
WARNING! DO NOT allow the lid/sensor to hang from the ribbon cable. Failure to
comply may result in damage to the product.
1. Using the provided hardware, securely mount the MRLDS-450 Gas Detector
according to the product dimensions, maximum wiring lengths and following
considerations:
a. Environment: the full range of environmental conditions when selecting a
location.
b. Application: the specifics of the application (possible leaks,
etc.) when selecting a location.
c. Accessibility: the degree of accessibility required for maintenance purposes
when selecting a location.
d. Target Gas: the specific gravity of the target gas when selecting
instrument.
2. Using a 5/32” (4mm) hex key/allen wrench (not included) remove the lid and
disconnect the ribbon cable from the base.
3. Set the lid and rubber gasket aside to be reinstalled later.
air movement/draft,
the height of the
3.4.Electrical Installation
3.4.1. Preparations
IMPORTANT: If analog output is configured for 4 to 20mA output, ensure that the current
loop is connected to a sinking current loop monitor before powering on the instrument.
Otherwise, a fault may be displayed indicating an open loop condition. If analog output is
unused, ensure it is configured as a voltage output (1-5V) to prevent an open loop fault
condition. The analog output is designed as sourcing.
WARNING! Ensure wiring for relays and connections for sensor(s) are made before
applying power.
CAUTION! This product uses semiconductors which can be damaged by electrostatic
discharge (ESD). When handling the printed circuit boards (PCBs), observe proper ESD
precautions so that the electronics are not damaged.
3.4.2. Power and Signal Wiring
The product comes with cable glands and plugs pre-installed. The power entry cable
gland is without a gland plug. Use the appropriate cable glands to insert and connect
the wires for power and signal to the appropriate terminals as indicated in the figure
and wiring table that follow. The PCB terminal blocks are a pluggable type and may
be removed to aid termination.
IMPORTANT:
• For 24VAC installations sharing a transformer in a daisy-chain configuration, neutral
polarity must be maintained for all instruments.
• 24VAC power polarity must not be reversed.
• For a more robust system, a dedicated transformer for each MRLDS is recommended to
prevent damage caused by wiring errors.
• Fasten terminal screws.
PowerDescriptionLabelWiring Termination
24VDC/VAC IN
Power
Digital Output
Analog
Output
Table 3-1 - Power and Signal Wiring
24VDC/VAC OUT
(power daisy chain
terminal)
MODBUS Network
Communications
Voltage or Current
Output
24V IN: -24VDC/VAC neutral/ground
24V IN: +24VAC neutral
24V OUT: -24VDC/VAC neutral/ground
24V OUT: +24VAC neutral
MODBUS: BRS-485 “B” (inverted)
MODBUS: ARS-485 “A” (non-inverted)
MODBUS: GNDRS-485 GND
MODBUS: SHRS-485 Shield
ANALOG: -Analog output ground
ANALOG: +Analog output signal (+)
3.4.3. Relay Wiring
WARNING! Relays are rated for 0 to 30V AC/DC. DO NOT apply main power onto these
relays.
Electrical InstallationInstallation • 9
Using appropriate cable glands, connect the wires for relay 1, relay 2, and relay 3 to
the terminals as indicated in Table 3-2.
RelayFunction
1Low Alarm
2High Alarm
3Fault Alarm
Table 3-2 - Relay Wiring Configuration
When configured according to the factory default settings, the relays are
de-energized during normal operation (not fail-safe). Fail-safe mode can be
configured. When configured for Failsafe operation, relays are energized during
normal operation. Failsafe operation ensures relays are triggered in cases of power
failure at the instrument. In Failsafe operation, normally open and normally closed
terminals are reversed as indicated in Table 3-3
TerminalNormal OperationFailsafe Operation
NCNormally ClosedNormally Open
COMCommonCommon
NONormally OpenNormally Closed
Table 3-3 - Relay Wiring Terminal Configuration
3.4.4. Modbus RTU RS-485 Interface
For the Modbus RS-485 network use a 16 to 24 AWG (0.5 to 1mm2) 3-core,
2 twisted pair + ground, shielded cable with 120Ω characteristic impedance.
The Modbus address, baud rate, stop bit, parity and slave termination is configured
through the setup menu. No jumpers or hardware switch settings are required.
Ensure that the communication parameters within the network, including the BMS,
are configured identically.
To ensure optimal performance of the Modbus network ensure the following
guidelines are implemented:
• Ensure instruments are configured in a single bus topology, connecting multiple buses in
parallel or branching multiple units from the main bus, may introduce impedance mismatches,
reflections and/or signal distortions.
• Avoid long stubs when connecting instruments to the bus, stubs should be less than one (1)
meter in length.
• Ensure A/B signal polarity is maintained throughout RS-485 network.
• Connect cable shield drain to physical earth or ground at the controller only.
• Ensure cable shield integrity is maintained throughout RS-485 network.
For Modbus end-of-line termination, use 150Ω ohm resistor or termination block
P/N 537-2711. Do not use MRLDS 120Ω ohm on-board termination with Site
Supervisor or E2.
Site Supervisor Setup - Device and COMM
Figure 3-1 - Site Supervisor Network Setup
Electrical InstallationInstallation • 11
E2 Setup - Device and COMM
Figure 3-2 - E2 Network Setup
3.4.5. Conclusion
After all wiring is completed, power the transmitter and confirm operation, and then
prepare to seal the enclosure.
Align the enclosure gasket (primary transmitter and remote sensor if equipped),
replace the lid, and tighten the six (6) screws. Tightening torque should be limited to
tightening by hand, and should be uniform in pattern.