Table 5-3: Active Line LEDs and Branch Voltage Phasing by Plug Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
ivEmerson® MPH2™ User Manual
Page 6
Important Safety Instructions
!
!
!
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This safety sheet contains important safety instructions. Read all safety, installation and operating
instructions before installing the Emerson Network Power MPH2 rack power-distribution unit (PDU).
Adhere to all warnings on the unit and in this safety sheet. Follow all instructions.
• The MPH2 Rack PDU is designed for information technology equipment. The MPH2 Rack PDU is not
intended for use with life support or other designated critical devices. If uncertain about its intended
application, consult your local dealer or Emerson representative.
• Maximum load must not exceed the rating shown on the MPH2 Rack PDU nameplate.
• The rated line voltage must not exceed 240VAC for connection to AC power distribution systems with
an isolated or high-impedance ground.
• Operate the MPH2 Rack PDU in an indoor environment only in the appropriate ambient temperature
range:
• 32°F to 140°F (0°C to 60°C) for 24A or less input models.
• 32°F to 122°F (0°C to 50°C) for 40A and 48A input models without case ventilation.
• 32°F to 140°F (0°C to 60°C) for 40A and 48A input models with case ventilation.
• Install the MPH2 Rack PDU in a clean environment, free of conductive contaminants, moisture,
flammable liquids, gases and corrosive substances.
• The MPH2 Rack PDU must be installed in a restricted-access location. A restricted-access location is
an area where access is possible only through the use of a tool or lock and key or other means of
security, and is controlled by the authority responsible for the location.
• The MPH2 Rack PDU has no user-serviceable parts. Under no circumstances attempt to gain internal
access due to the risk of electric shock or burn.
• Refer any unexpected behavior or unusual fault conditions to your local dealer, Emerson
representative or Emerson Network Power Applications Engineering.
• Emerson recommends powering only devices with safety agency approval from the MPH2 Rack PDU.
• For permanently connected MPH2 Rack PDUs (hard-wired versions), a readily accessible disconnect
device must be incorporated external to the equipment.
• For MPH2 Rack PDUs with integral plugs, the socket/ outlet must be installed near the equipment and
must be easily accessible.
WARNING
Opening or removing end caps from an MPH2 Rack PDU may expose personnel to lethal voltages
within the rack PDU. Observe all cautions and warnings. Failure to do so may result in serious
injury or death. MPH2 Rack PDU units contain no user-serviceable parts. For service or technical
support, contact Emerson Network Power Applications Engineering or your local Emerson
representative. Do not attempt to service this product yourself.
CAUTION
Connecting an MPH2 Rack PDU to a power supply with an incorrect rating in voltage or amperes
may damage the connected equipment and your MPH2 Rack PDU. For questions about the power
supply connections, contact Emerson Network Power Applications Engineering or your local
Emerson representative.
CAUTION
Ensure that the ratings of the electric circuit of each connected device meets the specified rating at
each branch and receptacle.
Emerson® MPH2™ User Manual1
Page 7
Important Safety Instructions
!
!
CAUTION
All configuration steps must be completed before attempting to start equipment connected to the
MPH2 Rack PDU.
NOTE
For power management purposes, record the receptacle where each piece of equipment is
connected. Receptacles on the MPH2 Rack PDU have a numeric designation. The MPH2 Rack
PDU identifies the receptacles with numbers and are grouped by branch with a letter referring to
the proper circuit breaker.
EUROPEAN UNION
Notice to European Union Customers: Disposal of Old Appliances
This product uses components that are dangerous for the environment, such as
electronic cards and other electronic components. Any component that is removed
must be taken to specialized collection and disposal centers. If this unit must be
dismantled, this must be done by a specialized center for collection and disposal
of electric and electronics appliances or other dangerous substances. This product
has been supplied from an environmentally aware manufacturer that complies with
the Waste Electrical and Electronic Equipment (WEEE) Directive 2002/96/EC. The
“crossed-out wheelie bin” symbol at right is placed on this product to encourage
you to recycle wherever possible.
Please be environmentally responsible and recycle this product through your
recycling facility at its end of life. Do not dispose of this product as unsorted municipal waste. Follow local
municipal waste ordinances for proper disposal provisions to reduce the environmental impact of waste
electrical and electronic equipment (WEEE).
For information regarding the scrapping of this equipment, go to http://www.eu.emersonnetworkpower.com
(“Products session” or “Contact us” session) or call Emerson’s worldwide technical support at:
• 00 80011554499 (toll free number)
• +39 0298250222 (toll number based in Italy)
ROHS Compliance
The MPH2 Rack PDU modules comply with the Restriction of Hazardous Substances directive (ROHS),
prohibiting use of six hazardous materials manufacturing of electronics, including lead-free solder.
FCC Compliance
This unit complies with the limits for a Class A device pursuant to Part 15 of the FCC Rules. Operation is
subject to the following two conditions:
This device may not cause harmful interference, and
This device must accept any interference received, including interference that may cause undesired
operation.
NOTE
This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference when the equipment is operated in a commercial environment. This
equipment generates, uses and can radiate radio frequency energy and, if not installed and used
in accordance with the instruction manual, may cause harmful interference to radio
communications.
Operation of this equipment in a residential area is likely to cause harmful interference that the
user must correct, including the expense of all corrective modifications.
2Emerson
®
MPH2™ User Manual
Page 8
Safety Symbols
Safety Symbols
The following symbols may appear within the documentation or on the product.
SymbolMeaning
High Temperature
Alerts the user where the enclosure temperature may exceed 158°F (70°C) while operating under highambient temperature and at maximally rated load.
Instructions
Signifies the presence of important operating and maintenance (servicing) instructions in the literature
accompanying the appliance.
Dangerous Voltage
Warns about the presence of uninsulated dangerous voltage within the product’s enclosure that may be
of sufficient magnitude to constitute a risk of electric shock to persons.
Power On
Indicates the principal On/Off switch is in the On position.
Power Off
Indicates the principal On/Off switch is in the Off position.
Protective Grounding Terminal
Indicates a terminal that must be connected to earth ground before any other connections to the
equipment may be made.
Emerson® MPH2™ User Manual3
Page 9
1.0Introduction
The Emerson Network Power® MPH2™ is the most intelligent, high-availability line of managed rack PDUs.
It offers remote monitoring and control capabilities as well as environmental sensors with multiple power
input selections and output configurations.
Metering Levels
Four types of MPH2 are available that offer metering of all electrical information including input, branch
and receptacle levels, as well as integration with environmental sensors. The available information varies
by type of MPH2. See 1.2 - Model Types, page 7 for descriptions.
Mounting
Rack PDUs are available for mounting in vertical and horizontal configurations in standard racks or
network enclosures.
Because the power cord is connected at the end of the vertical-mount (0-U) MPH2 models, the rack PDUs
may be oriented to accommodate top or bottom cable-entry into the rack.
Locking Receptacles - IEC Type Only
Locking receptacles are available on models with IEC receptacles. The locking feature requires optional
locking power cords to be installed on devices powered by the MPH2.
Introduction
The receptacles require no modification to function properly with non-locking power cords.
Overcurrent Protection
All MPH2 Rack PDU units with input current rating of 30 A and higher feature 100% rated
hydraulic-magnetic breakers. For all UL-listed models, the maximum cord and plug-connected loading is
limited to 80% continuous loading, as required by UL in accordance with the National Electric Code.
Low-profile circuit breakers are used on all MPH2 0-U Rack PDUs with two or three branch circuits.
Standard-profile circuit breakers are used on MPH2 horizontal models and on certain vertical models that
have 6 branch circuits or have a 240 VAC rating. Each type of circuit breaker is a flush-mount, rocker style
(see Figure 3-17).
Integrated Monitoring and Management
The factory-installed Emerson RPC2™ communications module permits managing the MPH2 Rack PDU
over a secure Web page and SNMP-based network management system. The RPC2 permits
interconnecting up to 4 rack PDUs in a Rack-PDU array configuration for monitoring and management.
NOTE
Do not interconnect RPC-1000 with RPC2 Rack PDUs in an array. They are incompatible and will
not interoperate.
NOTE
Refer to the RPC2 communications module user manual, SL-20841, for detailed instructions on
installing and using the RPC2 module. The document is available at Emerson’s Web site:
http://www.emersonnetworkpower.com
4Emerson
®
MPH2™ User Manual
Page 10
Introduction
A rack PDU can be monitored locally through its on-board LCD, through a Web interface or through an
optional display module, either the RPC BDM (Part# RPCBDM-1000). The display module connects
directly to the RPC2 communications module and may be moved between operating MPH2 units. It can be
hand-held, mounted in or on the rack or mounted on a wall near the rack PDU it is monitoring.
Multiple MPH2 Rack PDUs can be managed with these software applications:
• Input ampacities include 16 A or 32 A for European Union versions and 12 A to 48 A for
North-American versions.
• Single-phase and three-phase.
• Input voltages include 100-120 VAC, 120/208 VAC, 200-240/415 VAC.
• Receptacle types include NEMA 5-20, IEC 60320 C13 and IEC 60320 C19
• Input connection supports a highly flexible fixed power cord or hard-wired connection to user
accessible terminal block.
6Emerson
®
MPH2™ User Manual
Page 12
Introduction
1.2Model Types
There are four types of MPH2 Rack PDU. All models provide power distribution and include input and
branch metering.
• Type B—Rack PDU metered: Provides metering of input and branches.
• Type C—Rack PDU metered, receptacle-switched: Provides metering of input and branches and
individual on/off control of each receptacle.
• Type M—Receptacle-metered: Provides metering of input, branches and receptacles.
• Type R—Receptacle-metered, receptacle-switched: Provides metering of input, branches and
receptacles. Provides individual on/off control of each receptacle.
1.3Appearance and Components
1.3.1Controls and Indicators—RPC2
The MPH2 Rack PDU is monitored and managed by the factory-installed RPC2 communications module.
This manual presents information about the MPH2’s functions and features. For details on operating the
MPH2 through the RPC2 communications module, refer to the RPC2 user manual, SL-20841. The
document is available at Emerson’s Web site: http://www.emersonnetworkpower.com
The RPC2 is installed near the middle of the MPH2 Rack PDU. The central location eases connections
whichever orientation is required for network cabling.
The RPC2’s Web-based interface provides system-operating measurements, sensor readings (optional)
and basic unit information including firmware version, unit rating, model number and serial number.
Figure 1-3 MPH2 major monitoring and management features
™
NumberDescriptionNumberDescription
1Serial port5Array link/management port
2USB port6Network port
3Sensor port7Access to Reset button
4Display port
Emerson® MPH2™ User Manual7
Page 13
Introduction
1.3.2LED Indicators
The MPH2 Rack PDU also has LEDs that indicate receptacle and branch status and system information.
The LEDs flash, pulse or change colors to indicate an event or alarm condition (for details on how LEDs
respond to events and alarms, refer to 5.0 - Troubleshooting.
NOTE
Units with a “B” as the fourth character in the model name (MPHBxxxx) do not have LEDs at their
receptacles. The branch and receptacle LED behavior in 5.0 - Troubleshooting and elsewhere in
this document does not apply to these units.
Receptacles on units with an “M” as the fourth character in the model name (MPHMxxxx) cannot
be turned off. Refer to the description of branch and receptacle LED behavior in 5.0 - Troubleshooting.
1.3.3On-board LCD Controls and Indicators
Emerson’s MPH2 has an integrated, on-board LCD that can be used to view information about the rack
PDU. The information available depends on the type of MPH2. For additional information about the
on-board LCD, refer to 3.0 - Operation.
1.3.4Power Components
The component location and type depend on the model of the MPH2 Rack PDU. For example, units
with a “B” as the fourth character in the model name do not have LEDs at their receptacles; see Figures 1-
4, 1-5 and 1-6.
Figure 1-4 Branch and receptacle identification—Units with no monitoring (Type B models)
NumberDescription
1Branch identification
2Receptacle identification
8Emerson
®
MPH2™ User Manual
Page 14
Introduction
Figure 1-5 Branch and receptacle identification—Units with individually-monitored
and managed receptacles (Type C, R and M models)
NumberDescription
1Branch identification
2Receptacle identification
3
Receptacle-status LED (See 5.0 -
Troubleshooting, page 42.)
1.3.4.1Branch Overcurrent Protection
Models having more than 16-A input-current rating are equipped with branch overcurrent protection. The
branch circuit breaker is a UL 489-listed breaker with a flush-mount, rocker-style actuator. This protects
each receptacle group against overload and short circuit by interrupting the fault current flowing in the
line-to-line, line-to-neutral and line-to-PE conductors of the branch circuits. The branch circuit breaker
ratings apply over the full, rated operating temperature and frequency.
The flush-mount breakers guard against accidental trips that could interrupt power to the connected load.
Manually tripping a breaker requires a small, flat blade, such as a screw driver (see Figure 3-17).
Low-profile circuit breakers are used on all MPH2 Rack PDUs with two or three branch circuits less than
240-V rating in a line-neutral configuration. Standard-profile circuit breakers are used on MPH2 Rack
PDUs with six branch circuits or have a 240-VAC rating. Each type of circuit breaker is a rocker style (see
Figure 1-6).
The branch circuit breaker labeling (A, B, C and so on) shows which receptacles are protected by each
specific breaker. Receptacles on Branch A are protected by the circuit breaker labeled A. Three-phase
PDUs may also have labeling showing the phase associated with each circuit breaker.
NOTE
The branch circuit breaker is not designed to be used as a disconnect device for the connected
load.
Emerson’s MPH2 Rack PDU may be equipped with either a factory-installed input power cord or
hard-wired connections. The hard-wired connection will be at one end of the unit. A terminal block in the
hard-wired connection compartment is coded to aid in making the connections. A collar secures the input
wire, keeping the strain off the terminal block connections. See Figure 2-1.
10Emerson® MPH2™ User Manual
Page 16
Installation
2.0Installation
An MPH2 Rack PDU can be installed in an Emerson rack on the frame members using factory-supplied
hardware. The unit can be installed on the face or the side of frame members. The unit can be mounted so
that the power cord exits either the top or bottom of the rack.
NOTE
Follow all local and national electrical codes, standards and recommended practices.
Disconnect Required for Hard-Wired MPH2 Units
A readily-accessible input-power disconnect device must be installed near the MPH2 Rack PDU.
Input Power Location for MPH2 Units with Factory-Installed Power Cords
The input-power socket or outlet must be installed near the MPH2 and must be easily accessible.
2.1Attaching Input Power Cords—Hard-wired Models Only
MPH2s with integral power cords need no assembly before installation. Units with hard-wired input power
require attachment of input-power cords. See Table 2-1 for wire sizing.
Hard-wired models may be wired with or without conduit.
2.1.1Attaching Input-power Cords without Conduit
1. Remove the end cap. It is held in place with two T10 Torx screws.
2. Slide the terminal block cover off.
3. Loosen the strain-relief collar. It is held in place with two Phillips head PH1 screws.
4. Strip the insulation from the individual wires as required to fit into the terminal block.
Recommended stripping length for MPH2 units rated less than 32 A is 9 mm; for MPH2s rated 40 A or
higher, 11 mm.
5. Slip the power cord through the hole in the end cap and through the strain-relief collar.
6. Loosen the terminal block screws.
7. Insert the wires into the terminal block according to the labeling inside the MPH2; tighten each terminal
block screw after inserting a wire. Refer to Table 2 -2 for tightening torque.
8. Tighten the strain-relief collar around the input power cord. The cord’s outer insulation covering should
extend through the bracket.
Emerson® MPH2™ User Manual11
Page 17
9. Replace the terminal block cover by either sliding it on or snapping it into place.
10. Reattach the end cap to the MPH2 with the two screws removed in Step 1.
Figure 2-1 Disassembly to install an input-power cable
Installation
NumberDescriptionNumberDescription
1Cover plate4Terminal-block labels
2Terminal-block screws5Strain-relief collar w/Phillips-head screws
3Terminal blocks6End cap (attached with 2 screws)
2.1.2Attaching Input-power Cords with Conduit
1. Remove the end cap. It is held in place with two T10 Torx screws.
2. Slide the terminal block cover off.
3. Loosen the strain-relief collar. It is held in place with four nuts (see Figure 2-1).
4. Strip the insulation from the individual wires as required to fit into the terminal block.
Recommended stripping length for MPH2 units rated less than 32 A is 9 mm; for MPH2s rated 40 A or
higher, 11 mm.
5. Slip the stripped wires through the conduit connector, through the metal end plate and into the terminal
block connection box.
6. Loosen the terminal block screws.
7. Insert the wires into the terminal block according to the labeling inside the MPH2; tighten each terminal
block screw after inserting a wire. Refer to Table 2 -2 for tightening torque.
8. Install the cover plate, by either sliding it on or snapping it into place and sliding it firmly against the
main body of the MPH2.
9. Install the cover plate, by either sliding it on or snapping it into place and pressing it against the cover
plate.
10. Attach the metal end plate to the MPH2 with four screws provided in the kit.
12Emerson® MPH2™ User Manual
Page 18
Installation
11. Slide the conduit into the conduit connector.
12. Tighten the conduit connector until it grips the conduit and crimps it securely.
Figure 2-2 Re-assembly to install an input power cable in conduit
NumberDescriptionNumberDescription
1Cover plate5Strain-relief collar w/Phillips-head screws
2Terminal-block screws6Metal end plate (attached with 4 screws)
3Terminal blocks7Conduit connector (field-supplied)
4Terminal-block labels8Conduit (cable not shown)
For tool-less mounting, attach the mounts to the rear of the MPH2 Rack PDU, then hang it in the rack as
shown in Figure 2-3. Torque the screw attaching the mounting button 17 lb-in. (2 Nm).
NOTE
Brackets are not supplied. A range of brackets for Emerson and other manufacturers’ racks are
available as accessories.
Figure 2-3 Tool-less mounting
Installation
MPH2 Rating
≤32 A>32 A
NumberDescription
1
2Button mount
3Insert button mount into keyhole slot.
Torx screw
(tighten torque 17 lb-in. (2 Nm)
14Emerson® MPH2™ User Manual
Page 20
Installation
2.3Installing a MPH2 in an Emerson® Rack
2.3.1Mounting Hardware and Tools Required
Factory-supplied
• 2 mounting brackets
• 2 mounting buttons
•4 spring nuts
Field-supplied
For mounting a vertical MPH2
• Phillips #2 screwdriver
For mounting a horizontal MPH2:
• Flat-blade screwdriver
• Torx screwdriver TX30
• Torque wrench
2.3.2Mounting the Vertical MPH2
The vertical MPH2 can be installed on a vertical or horizontal frame member in the rack.
1. Determine where in the Emerson rack the PDU will be installed.
2. Attach a bracket to each end of the PDU.
3. If mounting on horizontal frame members, attach the brackets in-line, Figure 2-4.
- or -
If mounting on a vertical frame member, attach the brackets at a right angle to the PDU.
4. Insert two spring nuts into the appropriate T-slot on the frame member, Figure 2-4. Position the spring
nuts to accommodate screws inserted through slots in the brackets. To move the spring nuts, press
down on each with a small, pointed object and slide each into position.
5. Hold the PDU in place and attach the top of the unit to the rack with tool-less fasteners, Figure 2-4.
Emerson® MPH2™ User Manual15
Page 21
6. Tighten the screws, applying 46 lb-in (5.2 Nm).
7. Repeat Steps 4 through 6 for the lower bracket on the lower end of the PDU.
Figure 2-4 Installing vertical MPH2 in an Emerson rack
2.3.3Mounting the Horizontal MPH2
The horizontal MPH2 is installed on a vertical frame member in the rack.
1. Choose a position in the rack for the PDU and install 4 cage nuts into the respective slots, Figure 2-5.
Installation
2. Hold the MPH2 PDU over the desired mounting holes (now with the cage nuts), and route the input
cable through the rack as desired.
3. Insert screws and use a Torx T30 screwdriver to tighten all of them. Leave the screws slightly loose for
the time being, Figure 2-5.
4. Once all the screws are installed, tighten them completely using 35.4 lb-in (5.2 Nm).
Figure 2-5 Installing horizontal MPH2 in an Emerson rack
16Emerson® MPH2™ User Manual
Page 22
Installation
2.3.4Mounting Horizontal MPH2
on Vertical Frame Member with Aluminum Extrusions
1. Choose a position in the rack for the PDU and install 4 spring nuts into the groove, Figure 2-6.
2. Use a level to check if the horizontal plane is maintained.
3. Set the distance to match the holes on the PDU, and hold the MPH2 PDU over the desired position
(now with the spring nuts).
4. Route the input cable through the rack as desired.
5. Insert screws and use a Torx T30 screwdriver to tighten all of them, Figure 2-6. Leave the screws
slightly loose for the time being.
6. Once all the screws are installed, tighten them completely using 35.4 lb-in (5.2 Nm).
Figure 2-6 Installing horizontal MPH2 in a rack with aluminum extrusions
Emerson® MPH2™ User Manual17
Page 23
Installation
2.3.5Rack Grounding strap
NOTE
Ensure that the safety-earth connection at the input-power-source receptacle
is made before any equipment is connected to Emerson’s MPH2 Rack PDU.
Units with factory-attached input-power cords have an grounding conductor internal to the case. The rack
grounding strap establishes the same ground reference between the MPH2 Rack PDU and the rack.
NOTE
The grounding strap may be used with MPH2 Rack PDUs that have integral input-power cords and
units that have hard-wired input-power cords. The strap supplements the internal grounding
conductor of the integral power-supply cord.
The grounding strap may be particularly useful when the rack is on a raised floor.
Table 2-3Ground-strap wire gauge by
Wire Size
Rating
12 A14 AWG——
16 A12 AWG
24 A10 AWG——
32 A—
40 A6 AWG——
48 A6 AWG——
NA, UL ListedEU, CE MarkedWW
2
4.0 mm
2
6.0 mm
MPH2 rating
12 AWG or 4.0 mm
—
2
1. Insert a spring nut into the rack frame near the grounding point on the MPH2 (see Figure 2-3 for
inserting the spring nut).
2. Attach a ground wire to the rack with a screw, washer and lock washer. The screw is secured to the
rack’s frame with a spring nut.
3. Use a second field-supplied screw, washer and lock washer to secure the ground wire to the MPH2.
The connection point is marked with an earth-ground symbol (see Figure 2-7).
18Emerson® MPH2™ User Manual
Page 24
Installation
Figure 2-7 Rack grounding-strap connection
NumberDescriptionNumberDescription
1Ground-wire connection screw, M6 x 124Lock washer
Ground-wire connection on MPH2
(location may vary)
Emerson® MPH2™ User Manual19
Page 25
2.3.6Recommended Electrical-backup Protection
A field-provided external circuit breaker must be installed upstream of the MPH2 Rack PDU. The circuit
breaker must be sized according to the input rating of the PDU. The circuit breaker rating must meet the
values in Tab le 2-4.
The external circuit breaker serves as the primary input power disconnect for the MPH2.
Table 2-4Upstream circuit breaker rating
Maximum Input
Current Per Pole
12 A15 A (NA)
16 A
24 A30 A (NA)
32 A32 A (EU, WW)
40 A50 A (NA)
48 A60 A (NA)
63 A63 A (EU, WW)
Rated Current
of Upstream CB
20 A (NA)
16 A (EU, WW)
2.4Connecting Rack Equipment
Installation
NOTE
Circuit breakers on Emerson’s MPH2 Rack PDU are opened at the factory. The open circuit
breakers help protect against high inrush current when input power is first connected.
To mitigate in-rush currents:
• Close the branch circuit breakers after all receptacle loads are connected.
–or –
• For MPH2-C and MPH2-R models, turn the receptacle off before connecting the load.
Once the MPH2 Rack PDU has been installed in the rack, the unit is ready for connection of equipment
that will be powered by the unit or used for monitoring.
Verify that the equipment to be connected meet these requirements:
• Input power requirements of each load do not exceed the MPH2 receptacle ratings.
• Input power cords meet or exceed the rating of the MPH2 receptacles and are fully-engaged.
• Total equipment power consumption will not overload the MPH2 Rack PDU.
To connect devices to an MPH2 Rack PDU:
1. Make sure that input power is installed in accordance with national and local electric codes.
2. Verify that all devices to be connected are shut down and unplugged from input power sources.
3. If the MPH2 Rack PDU will be monitored over a network, connect an Ethernet cable to the LAN port on
the RPC2.
4. Route the devices’ power cables to the MPH2 Rack PDU, following proper procedures and good
practices, such as segregating power cables from control cables and keeping cable bends to
recommended angles.
5. Verify that the branch circuit breakers on the MPH2 Rack PDU are open.
20Emerson® MPH2™ User Manual
Page 26
Installation
6. Connect the devices’ input power cables to the MPH2 Rack PDU.
7. Record where each piece of rack equipment is connected, using the branch and receptacle numbers
8. Post the connection information on or near the rack and at any remote monitoring location.
9. Connect input power to the MPH2 Rack PDU. On Types R, C and M models, the receptacle LEDs
10. Verify that input power is present and the line-status LEDs are illuminated green and steady state. If
11. Close the branch circuit breakers. The receptacle LEDs are lit green and steady-state. If any LEDs are
12. Turn on the connected devices one at a time and verify that each is operating properly.
13. Ensure that the specified ratings found on the MPH2 Rack PDUs name plate are not exceeded.
NOTE
All C13 and C19 receptacles on MPH2 Rack PDUs are locking receptacles. Locking requires use
of special power cords, which may be factory-installed on the equipment or is available from
Emerson.
If non-locking power cords are used, the power cords should be secured through other methods to
prevent unintended power interruption.
on the MPH2 Rack PDU.
pulse RED indicating that the branch circuit breakers are open.
any LEDs are not lit or are blinking, refer to Table 5-2 - Line LED Troubleshooting, page 39.
not lit or are blinking, refer to Table 5-1 - Receptacle LED Troubleshooting, page 38.
14. Monitor and control the MPH2 Rack PDU as detailed in the RPC2 user manual, SL-20841, available at
www.emersonnetworkpower.com
2.5Installing Optional Items
The following items may be added to an MPH2 Rack PDU system but are not required.
• RPC Basic Display Module
• Liebert
2.5.1RPC Basic Display Module Installation
The RPC Basic Display Module (BDM) provides local display of parametric data, including electrical status,
temperature and humidity for all connected MPH2 Rack PDUs. Display information is accessed via a
navigation switch on the BDM. The RPC BDM is connected by cable to the MPH2 Rack PDU, allowing the
user to install the display to suit the local reading requirements. A 6.5-ft. (2-m) cable and general mounting
provisions are provided. A single display can be used for up to four rack PDUs connected in a Rack PDU
Array
The RPC BDM can be mounted in the rack with either the included hardware or with a cable tie through the
slot on the back of the module. Either method permits moving the BDM to a different place in the same
rack or to another rack.
2.5.1.1Included Hardware
• RPC BDM, 1
®
SN temperature/humidity sensors
™
.
• Spring Nut M5, 1
• Spacer Sleeve, 1
• Mounting Button, 1
•M5 Screw, 1
• Cable Clip, 1
Emerson® MPH2™ User Manual21
Page 27
Figure 2-8 RPC BDM
Installation
NumberDescription
1Scan switch
2RJ-45 communication and power input port
To install an RPC BDM in a rack:
1. Determine the mounting location on the frame member where the RPC BDM will be installed.
2. Insert a spring nut into a T-slot and flip it so that it is square in the slot as shown in Figure 2-9.
Figure 2-9 Inserting the spring nut into a T-slot
3. Insert the MPH2 Rack PDU screw into the spacer sleeve.
4. Insert the MPH2 Rack PDU screw into the spring nut and tighten securely with a flat-head screwdriver.
5. Hang the RPC BDM on the screw with the hooded mounting slot on the back of the RPC BDM.
6. Connect the RPC BDM to the RPC2 with an Ethernet cable.
7. Be certain to connect the cable to the correct port on the RPC2.
22Emerson® MPH2™ User Manual
Page 28
Installation
2.5.2Temperature/Humidity Sensor Installation
Optional Liebert® SN temperature/humidity sensors are available to assist in monitoring conditions in the
rack. Liebert SN sensors are designed for installation in Emerson racks without tools, but each may be
placed in any area to monitor temperature and humidity levels. Each connects to the RPC2
communications module, which makes readings available to other monitoring methods.
To install a sensor in a rack:
1. Insert the sensor bracket base into one end of the sensor support.
2. Snap the sensor into the other end of the sensor support.
3. Choose where in the rack to install the sensor assembly.
NOTE
Emerson recommends placing the sensor in the area of the rack that is likely to be warmest. That
location helps determine extreme conditions that can cause equipment damage.
4. Hold the sensor bracket on a T-slot on the Emerson rack frame where the sensor will be placed.
5. Insert the included quarter-turn fastener through the rectangular hole in the sensor bracket base and
into the T-slot.
6. Turn the fastener clockwise 90 degrees, a quarter of a turn.
7. Route the sensor cable to the RPC2 communications module and insert it into the card’s external
sensor port.
NOTE
For more information, see the RPC2 user manual, SL-20841, available at Emerson’s Web site,
http://www.emersonnetworkpower.com
Emerson® MPH2™ User Manual23
Page 29
3.0Operation
Emerson’s MPH2 Rack PDU may be monitored and managed by the factory-installed RPC2
communications module. This manual presents information about the MPH2’s functions and features.
Refer to the RPC2 user manual, SL-20841, for details on using the RPC2 communications module to
monitor and manage the MPH2. The document shipped with the MPH2 Rack PDU and is available at
Emerson’s Web site, http://www.emersonnetworkpower.com
The MPH2’s on-board LCD and the Web-based interface display system operating measurements, as well
as readings from optional Liebert SN temperature or temperature/humidity sensors. The RPC2
communications module and on-board LCD also display basic information about the MPH2 Rack PDU,
such as firmware version, unit rating, model number and serial number.
LEDs on the MPH2 and an audible alarm also assist in monitoring performance with alerts about events
and alarm conditions. The keys under the on-board LCD are used to navigate to various information and to
silence alarms.
3.1Controls and Indicators
The MPH2 Rack PDU also has LEDs that indicate receptacle and branch status and system information.
LEDs flash, pulse or change colors to indicate an event or alarm condition (for details on how LEDs
respond to events and alarms, refer to 5.0 - Troubleshooting.
Operation
NOTE
Units with a “B” as the fourth character in the model name (MPHBxxxx) do not have LEDs at their
receptacles. The branch and receptacle LED behavior in 5.0 - Troubleshooting and elsewhere in
this document does not apply to these units.
Receptacles on units with an “M” as the fourth character in the model name (MPHMxxxx) cannot
be turned Off. LEDs at receptacles on these models are always either on continuously or flashing
when input power is present.
The MPH2’s main screen is displayed by the on-board LCD when the rack PDU is first powered up. The
input-level information is the main screen, Figure 3-2.
NOTE
After 5 minutes of no activity (no key pressed), the on-board LCD returns to
the main screen.
NOTE
During a firmware upgrade:
• The Line-input status LEDs flash red and green, and the rack PDU
continues receiving and distributing power without interruption.
Figure 3-2 Input-level information (main screen)
NumberDescriptionNumberDescription
1Input-level metered information icon7Receptacle icon
2Bar graph of input current8Sensor icon
3Link icon9Alarm icon
4Input voltage10% Amperes used until alarm threshold.
5Voltage phase11Unit identification (always shows unit 1)
6Information icon
Emerson® MPH2™ User Manual25
Page 31
3.2.1Communication Link with RPC2
When power is cycled to the MPH2, it takes a few moments to establish communication and load the
configuration information from RPC2, such as receptacle labels and IP and MAC addresses.
When configuration changes (such as turning-on/off a receptacle) require that the LCD screen update, the
configuration wheel appears and spins, Figure 3-3, to indicate that navigation is unavailable while
configuration is in-progress.
Figure 3-3 Configuration in-progress wheel
Operation
NumberDescription
1Configuration wheel
26Emerson® MPH2™ User Manual
Page 32
Operation
3.3View MPH2 System Information
1. Use the arrow keys to highlight the information icon, .
2. Press .
The MPH2 model number, serial number, firmware version, power rating and number of receptacles
display, Figure 3-4.
Figure 3-4 System information
NOTE
The firmware version and other information in the figure are an examples only.
3.3.1System and Screen Options
On the system-information screen is a menu of icons that provides access to further system options,
network information, and LCD-screen options, Figure 3-5.
1. Use the arrow keys to highlight the information icon, , and press .
2. Use an arrow key to highlight the reboot/restore-defaults icon, , and press .
The Reboot Options display, Figure 3-6.
Figure 3-6 Reboot Options
Operation
3. Use the arrow keys to highlight an up/down arrow at the bottom-left, and pressto highlight Reboot.
4. Use the arrow keys to highlight the play button, , and press .
The Reboot? confirmation displays.
5. Use the arrow keys to highlight an up/down arrow, and pressto highlight Yes / Reboot Now.
6. Press .
The system reboots.
28Emerson® MPH2™ User Manual
Page 34
Operation
3.3.3Restore System Defaults
Table 3 -1 describes the factory-default settings.
1. Use the arrow keys to highlight the information icon, , and press .
2. Use an arrow key highlight the reboot/restore-defaults icon, , and press .
The Reboot Options display, Figure 3-6.
Figure 3-7 Restore Defaults selected on Reboot Options
3. Use the arrow keys to highlight an up/down arrow at the bottom-left, and press
to highlight Restore Defaults.
4. Use the arrow keys to highlight the play button, , and press .
The Restore Defaults? confirmation displays, Figure 3-8.
5. Use the arrow keys to highlight an up/down arrow, and pressto highlight Yes/ Reboot to Default.
6. Press .
The system-default settings are restored.
Figure 3-8 Restore Defaults? confirmation
Emerson® MPH2™ User Manual29
Page 35
The default settings described in Table 3-1 apply only to MPH2, are set at time of manufacture and are
applied when “Restore to Factory Defaults” is initiated via RPC2 clients.
NOTE
For detailed information about settings and about network- and protocolrelated default settings for RPC2, see SL-20841. The document is available at
Emerson’s Web site: http://www.emersonnetworkpower.com
Table 3-1Factory-default settings
LevelSettingsDefault ValueUnits
MPH2 or
PDU
Branch
User Assigned Label
Asset Tag 1<empty>—All
Asset Tag 2<empty>—All
Overcurrent Alarm Threshold45%All
Overcurrent Warning
Protection (SWOCP)
User Assigned LabelBranch <alpha>—All
Asset Tag 1<empty>—All
Asset Tag 2<empty>—All
Overcurrent Alarm Threshold95%All
Overcurrent Warning
Threshold
Undercurrent Alarm Threshold 0%All
SWOCPDisabled—R
Rack PDU
<alpha>
40%All
0%
Disabled—R
90%All
Models
AffectedNotes
—All
All
3-phase
• RackPDU is default value the first time
only.
• Allowed characters include
alphanumeric, space,
and ~!#$_+`-={}|[]\\:;'?,.\/%^&*()@
• % calculated from maximum inputcurrent rating on nameplate.
• Default values are recommended for
dual-corded server applications.
% difference calculated between any two
phases.
Conditionally applies to unlocked and
unloaded receptacles only.
Allowed characters include
alphanumeric, space,
and ~!#$_+`-={}|[]\\:;'?,.\/%^&*()@
% calculated from CB rating. Refer to
nameplate for maximum branch current
rating.
Conditionally applies to all unlocked and
unloaded receptacles only for this
branch.
Operation
30Emerson® MPH2™ User Manual
Page 36
Operation
Table 3-1Factory-default settings (continued)
LevelSettingsDefault ValueUnits
Receptacle
<number>
90%M,R
Disabled—C,R
Receptacle
User Assigned Label
Asset Tag 1<empty>—All
Asset Tag 2<empty>—All
Overcurrent Alarm Threshold95%M,R
Overcurrent Warning
Threshold
Undercurrent Alarm Threshold 0%M,R
Power Up StateRestore—C,R
Power On Delay0secondsC,R
Power Cycle Delay8secondsC,R
Post On Delay0secondsC,R
Post Off Delay0secondsC,R
Software Over Temperature
Protection (SWOTP)
SWOTP Delay10secondsC,R
SWOTP ScopeLocal—C,R
CriticalityCritical—C,R
Locked/UnlockedUnlocked—C,R
Models
AffectedNotes
—All
Allowed characters include
alphanumeric, space,
and ~!#$_+`-={}|[]\\:;'?,.\/%^&*()@
Configurable per receptacle.
% calculated from maximum receptacle
current rating on nameplate.
Restore returns receptacle power state
to last programmed state after expiration
of Power On Delay.
The delay timing begins after
measurement stability is achieved.
A Power Cycle turns off power to the
receptacle for the specified delay.
Delay before RPC2 issues command to
power on receptacle.
Delay before RPC2 issues command to
power off receptacle.
• Unconditionally applies regardless of
locked/unlocked and loaded/unloaded
status.
• At least one temperature sensor is
required.
Delay required for persistent overtemperature alarm condition before
SWOTP triggered.
• Local = affects only PDU connected to
the temperature sensor that triggered
SWOTP.
• Array = affects all PDUs regardless of
temperature sensor that triggered
SWOTP.
Affects power control when a member of
a receptacle group.
Affects authorization to manage power
control and behavior of SWOCP.
Emerson® MPH2™ User Manual31
Page 37
3.3.4Determine IP Address, MAC Address and Firmware Version
1. Use the arrow keys to highlight the information icon, , and press .
2. Use an arrow key to highlight the network icon, , and press .
The IP address, MAC address, firmware, date and time display, Figure 3-9.
Figure 3-9 IP address, MAC address, and firmware information
Operation
NumberDescription
1IP address
2MAC address
3Agent firmware type and version
NOTE
The firmware version and other information in the figure are examples only.
32Emerson® MPH2™ User Manual
Page 38
Operation
3.3.5Adjust the Contrast of the On-board LCD
NOTE
Contrast adjustment may help improve LCD-screen legibility in a
high-temperature environment.
The on-board LCD is factory-set to be easily viewed in lighting conditions found in most work places. The
contrast can be changed.
1. Press any key to activate the LCD.
2. Use the arrow keys to highlight the information icon, , and press
3. Use the arrow keys to highlight the contrast icon, , and press .
4. Use the arrow keys to highlight an up/down arrow, and pressto increase or decrease contrast.
Refer to the pattern, Figure 3-10, to determine when the contrast is acceptable.
5. When the contrast is satisfactory, highlight and press to return to the system-information
screen.
NOTE
These steps also apply to the RPC BDM.
Figure 3-10 Adjust LCD contrast
Emerson® MPH2™ User Manual33
Page 39
3.3.6Adjust the Orientation of the On-board LCD
Because mounting of the MPH2 in the rack may vary, the on-board LCD may be “flipped” to change the
screen orientation for viewing ease.
1. Press any key to activate the LCD.
2. Use the arrow keys to highlight the information icon, , and press .
3. Use the arrow keys to highlight the flip-orientation icon, , and press .
The screen “flips” orientation.
4. Highlight and press to return to the input-level screen.
NOTE
These steps also apply to the RPC BDM.
3.4View Active Alarms
NOTE
The most-recent alarms are at the top of the list.
Operation
1. Use the arrow keys to highlight the alarm icon, , and press .
A list of active alarms on the MPH2 displays, Figure 3-11.
2. Use the arrow keys to highlight an up/down arrow, and pressto highlight an alarm.
3. Highlight the play button, , and press .
The alarm details display.
Figure 3-11 Alarm list
3.4.1Silence an Audible Alarm
To silence an audible alarm, press any of the three navigation keys below the LCD.
See 5.0 - Troubleshooting for details about how the LED interface signifies events and alarms.
34Emerson® MPH2™ User Manual
Page 40
Operation
3.5View Branch-level Information
1. At the input-level (main) screen, highlight the unit-identification number, , and press .
The branch letters display along the bottom-left, Figure 3-12.
2. Use the arrow keys to highlight the letter of the branch to view, and press .
Information about the selected branch displays, Figure 3-12.
• To display more details about the selected branch, highlight the information icon, , and press.
• To return to the previous level view, highlight and press.
Figure 3-12 Branch information
NumberDescription
1Branch-level information icon
Branch circuit-breaker status icon
2
3Branches (two shown, A and B)
I = closed circuit breaker
O = open circuit breaker
Emerson® MPH2™ User Manual35
Page 41
3.6View Receptacle-level Information
1. At the input-level (main) screen, highlight the receptacle icon, , and press .
The receptacle list displays, Figure 3-13.
Figure 3-13 Receptacle list
Operation
2. Use the arrow keys to highlight an up/down arrow at the bottom-left, and pressto highlight a
receptacle.
3. Highlight the play button, , and press .
The receptacle information displays, Figure 3-14. The receptacle numbers display along the bottomleft, and the number of the selected receptacle number flashes.
4. To view a different receptacle, highlight the number of the receptacle, and press .
• To display more details about the selected receptacle,
highlight the information icon, , and press.
• To return to the previous level view, highlight and press.
36Emerson® MPH2™ User Manual
Page 42
Operation
Figure 3-14 Receptacle information
NumberDescription
1Receptacle-level information icon
2
3
Receptacle identification:
1 = MPH2 #1
A = Branch A
1 = Receptacle #1
Receptacle list (receptacle #1 of 5 is
selected)
Emerson® MPH2™ User Manual37
Page 43
3.7View Sensor Information
1. At the input-level (main) screen, highlight the sensor icon, , and press .
A list of the sensors, in the order of their identification number, displays, Figure 3-15.
NOTE
The default label is the sensor’s serial number, but can be changed through
the Web interface.
Figure 3-15 Sensor list
Operation
NumberDescription
Sensors connected to the MPH2. (two
1
temperature sensors and one humidity
sensor in the example)
2. Use the arrow keys to highlight an up/down arrow at the bottom-left, and pressto highlight a
receptacle.
38Emerson® MPH2™ User Manual
Page 44
Operation
3. Highlight the play button, , and press .
The sensor information displays, similar to that shown in Figure 3-16, which shows
humidity-sensor information:
• Percentage and severity of humidity.
• Sensor identification and label (serial number).
NOTE
The default label is the sensor’s serial number, but can be changed through
the Web interface.
Figure 3-16 Sensor information
Emerson® MPH2™ User Manual39
Page 45
3.8Opening and Closing Circuit Breakers
MPH2 Rack PDU feature circuit breakers to protect either branches or individual receptacles, depending
on the model. Low-profile circuit breakers are used on all MPH2 Rack PDUs with two or three branch
circuits. Standard-profile circuit breakers are used on MPH2 Rack PDUs with six branch circuits or have a
240VAC rating.
Both types of circuit breakers are flush-mount, rocker-style breakers. The circuit breakers are designed to
prevent accidental trips. To manually trip a circuit breaker to the Off position, insert a flat-blade screwdriver
or similar tool into the slot on the breaker as shown in Figure 3-17. To reset the breaker, press the end
nearest ON until it clicks into place.
Figure 3-17 Turning Off or resetting a circuit breaker
Input Wiring Options10-ft. (3-m) Non-Detachable Power
Supply Cord
Hard-Wired Terminal Block
Receptacle OptionsNEMA 5-15; NEMA 5-20; IEC 320C13; IEC 320 C19
Number of Receptacles, Maximum481224
Power Consumption, Maximum7.5 W
Measurement Accuracy
Current: ±1.5% + 0.01 A from 1% to 10% of unit rating;
EN55022:2006+A1:2007, Class A, Industrial
EN55024:1998+A1:2001+A2:2003, Class A, Industrial
IEC61000-3-2:2014 (ed.3), IEC61000-3-3:2013 (ed.3)
IEC61000-4-2/3/4/5/6/8/11
UL, cUL, CE, BV, CB, RoHS, REACH, WEEE
10-ft. (3-m) Non-Detachable Power Supply Cord
Voltage: ±1% +0.1 VAC
Class I, Reinforced SELV
Tested up to 4242 VDC
20 A, 5000 A A.I.C
10 to 90 non-condensing
6562 (2000)
Factory-installed, Right-angle Mounting Brackets
1.73 x 9.84 (44 x 250)3.46 x 9.84 (88 x 250)
Emerson® MPH2™ User Manual41
Page 47
5.0Troubleshooting
NOTE
Per UL 60950-1 2nd Ed. ITE safety-standard requirements, the current ratings of UL Listed
models are 80% of input-plug, branch-circuit-breaker and receptacle maximum current ratings.
Table 5-1Receptacle LED Troubleshooting
LED Indication
(One or All LEDs)
State/
Flash Speed
GreenSteady On—
GreenFast—Receptacle Identification
OffNA—Voltage OffCheck receptacle power control settings.
GreenSlow—Overcurrent Warning
RedFast
Red
(All LEDs)
Green
(All LEDs)
Red
(All LEDs)
Pulse—Branch Circuit Breaker Open
Slow—Branch Overcurrent Warning
FastBranch Overcurrent Alarm
Audible
AlarmConditionStatus/Recommended ActionColor
Input-voltage-supported
Receptacle Powered-on
Overcurrent Alarm
Undercurrent Alarm
Normal Operation
Remote user is requesting receptacle identification.
The LED should stop flashing after 10 seconds.
Check for changing load conditions.
Check overcurrent warning threshold settings.
Check for changing load conditions.
Check overcurrent alarm threshold settings.
Check for removal of load.
Check undercurrent alarm threshold settings.
Check for changing load conditions; confirm circuit
breaker actuator is closed. If open, correct loading
condition before pressing circuit breaker actuator
closed again.
Note: On single-phase, switched-receptacle models,
this may indicate that the input-power line and
neutral are swapped if there is no power to the unit.
Check for changing load conditions.
Check overcurrent warning threshold settings.
Check for changing load conditions.
Check overcurrent alarm threshold settings.
Troubleshooting
42Emerson® MPH2™ User Manual
Page 48
Troubleshooting
Table 5-2Line LED Troubleshooting
LED Indication
(One or All LEDs)
State/
Flash Speed
GreenSteady On—None
OffNA—Voltage Off
RedSteady OnLine Undervoltage Alarm
RedFastOvercurrent Alarm
GreenSlow—Overcurrent Warning
RedFastUndercurrent Alarm
Green/RedFast—Firmware Update
Audible
AlarmConditionStatus/Recommended ActionColor
Normal Operation
Note: Depending on plug type, not all LEDs may be lit,
see Table 5-3.
Confirm that the LED is active per Table 5-3.
Check power source and input plug’s receptacle
wiring.
Check receptacle power control settings.
Check power source for power quality problem. If the
MPH2 uses 3-phase power, a single low-voltage
phase may cause one or more undervoltage alarms.
The undervoltage alarm is factory-set to -10% of the
minimum input voltage range on the nameplate; it
cannot be changed.
Check for changing load conditions.
Check overcurrent alarm threshold settings.
Check for changing load conditions.
Check overcurrent warning threshold settings.
Check for removal of load.
Check undercurrent alarm threshold settings.
Firmware updated in-progress. LCD does not display
information. If the update fails or aborts, the indication
continues until firmware update is successful.
Emerson® MPH2™ User Manual43
Page 49
Troubleshooting
5.1Additional Troubleshooting by Plug Type
Table 5 -3 describes the line LEDs active by plug type. Depending on the type of plug, not all of the line
LEDs may be lit. The table also describes the branch circuits/receptacle-type and corresponding
input-power voltage phases
Table 5-3Active Line LEDs and Branch Voltage Phasing by Plug Type
Pole/Wire
Plug Type
NEMA 5-15P1P3W L1-N
NEMA 5-20P1P3W L1-N
NEMA L5-20P1P3W L1-N
NEMA L5-30P1P3W L1-NL1-N
NEMA L6-20P2P3WL1-L2
NEMA L6-30P2P3WL1-L2L1-L2
NEMA L14-30P2P4WL1-NL1-L2L1-L2
NEMA L15-20P3P4WL1-L2L2-L3L3-L1
NEMA L15-30P3P4WL1-L2L2-L3L3-L1
liebert.monitoring@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
liebert.upstech@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
852 2572220
Fax: 852 28029250
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims
all liability for damages resulting from use of this information or for any errors or omissions.