Emerson MPH2 Technical Documents

Emerson Network Power® MPH2™ Rack PDU
MPH2
2.96A
2kWh
i
TX
MPH2
Managed Rack
Power Distribution
RX
L1 L2
L3
1
User Manual
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY SYMBOLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.1 General Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Model Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Appearance and Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3.1 Controls and Indicators—RPC2™ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3.2 Controls and Indicators—LED’s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3.3 Controls and Indicators—Onboard LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3.4 Power Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3.5 Hard-Wired Connection Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.0 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
2.1 Attaching Input Power Cords—Hard-Wired Models Only. . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.1.1 Attaching Input Power Cords Without Conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.1.2 Attaching Input Power Cords With Conduit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.2 Tool-less Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.3 Installing an MPH2 in an Emerson
2.3.1 Mounting Hardware and Tools Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.3.2 Safety Earth Ground Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.3.3 Recommended Electrical Backup Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.4 Connecting Rack Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.5 Installing Optional Items. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.5.1 RPC Basic Display Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.5.2 Temperature/Humidity Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
®
Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.0 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
3.1 Controls and Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.1.1 Getting Information Through the Onboard LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.1.2 Adjusting the Onboard LCD’s Contrast . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.1.3 Adjusting the Onboard LCD’s Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.1.4 Obtain MPH2 System Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.1.5 Determine IP or MAC Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.1.6 View Input Level Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.1.7 View Active Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.1.8 View Branch Level Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.1.9 View Outlet Level Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.1.10 View Sensor List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.1.11 View Sensor Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.1.12 Opening and Closing Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.1.13 Silence an Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.0 EMERSON® MPH2 RACK PDU SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
5.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
i
FIGURES
Figure 1 Vertical MPH2 rack PDU Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 2 MPH2 major monitoring and management features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 3 MPH2 LCD and LED’s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 4 Branch and outlet identification—Units with no monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 5 Branch and outlet identification—Units with individually monitored and managed outlets . . . . 7
Figure 6 Circuit breaker branch identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 7 Hard-wired connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 8 Disassembling the MPH2 for installing an input power cable in conduit . . . . . . . . . . . . . . . . . . . 11
Figure 9 Disassembling the MPH2 for installing an input power cable in conduit . . . . . . . . . . . . . . . . . . . 11
Figure 10 Tool-less mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 11 Installing in an Emerson rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 12 Earth-ground connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 13 RPC BDM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 14 Inserting the spring nut into a T-slot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 15 MPH2 onboard LCD and control keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 16 MPH2 onboard LCD layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 17 Adjust LCD contrast . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 18 Flip LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 19 MPH2 rack PDU information screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 20 IP address in MPH2 Onboard LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 21 Input level screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 22 Alarm icon . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 23 Alarm list screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 24 Branch level information screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 25 Outlet level information screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 26 Sensor list screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 27 Sensor information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 28 Configuration in progress screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 29 Turning Off or resetting a circuit breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 30 Silence an alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
TABLES
Table 1 Hard-wired models—Connection terminal ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Table 2 Terminal tightening torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Table 3 Upstream circuit breaker rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
ii
IMPORTANT SAFETY INSTRUCTIONS
!
!
!
!

SAVE THESE INSTRUCTIONS

This safety sheet contains important safety instructions. Read all safety, installation and operating instructions before installing the Emerson Network Power MPH2 rack power distribution unit (PDU). Adhere to all warnings on the unit and in this safety sheet. Follow all operating and user instructions.
• The MPH2 rack PDU is designed for information technology equipment. The MPH2 rack PDU is not intended for use with life support or other designated critical devices. If uncertain about its intended application, consult your local dealer or Emerson representative.
• Maximum load must not exceed the rating shown on the MPH2 rack PDU nameplate.
• The rated line voltage must not exceed 240VAC for connection to AC power distribution systems with an isolated or high-impedance ground.
• Operate the MPH2 rack PDU in an indoor environment only in an ambient temperature range of 32°F to 140°F (0°C to 60°C) for 24A or less input models and 32°F to 122°F (0°C to 50°C) for 40A and 48A input models.
• Install the MPH2 rack PDU in a clean environment, free of conductive contaminants, moisture, flammable liquids, gases and corrosive substances.
• The MPH2 rack PDU must be installed in a restricted-access location. A restricted-access location is an area where access is possible only through the use of a tool or lock and key or other means of security, and is controlled by the authority responsible for the location.
• The MPH2 rack PDU has no user-serviceable parts. Under no circumstances attempt to gain internal access due to the risk of electric shock or burn.
• Refer any unexpected behavior or unusual fault conditions to your local dealer, Emerson representative or Emerson Network Power Applications Engineering.
• Emerson recommends powering only devices with safety agency approval from the MPH2 rack PDU.
• For permanently connected MPH2 rack PDU’s (hard-wired versions), a readily accessible disconnect device must be incorporated external to the equipment.
• For MPH2 rack PDU’s with integral plugs, the socket/ outlet must be installed near the equipment and must be easily accessible.

Important Safety Instructions

WARNING
Opening or removing end caps from an MPH2 rack PDU may expose personnel to lethal voltages within the rack PDU. Observe all cautions and warnings. Failure to do so may result in serious injury or death. MPH2 rack PDU units contain no user-serviceable parts. For service or technical support, contact Emerson Network Power Applications Engineering or your local Emerson representative. Do not attempt to service this product yourself.
CAUTION
Connecting an MPH2 rack PDU to a power supply with an incorrect rating in voltage or amperes may damage the connected equipment and your MPH2 rack PDU. For questions about the power supply connections, contact Emerson Network Power Applications Engineering or your local Emerson representative.
CAUTION
Ensure that the ratings of the electric circuit of each connected device meets the specified rating at each branch and outlet.
NOTE
For power management purposes, record the outlet where each piece of equipment is connected. Outlets on the MPH2 rack PDU have a numeric designation. The MPH2 rack PDU identifies the outlets with numbers and are grouped by branch with a letter referring to the proper circuit breaker.
1 Emerson® MPH2
Important Safety Instructions
!
CAUTION
All configuration steps must be completed before attempting to start equipment connected to the MPH2 rack PDU.

EUROPEAN UNION

Notice to European Union Customers: Disposal of Old Appliances
This product uses components that are dangerous for the environment, such as electronic cards and other electronic components. Any component that is removed must be taken to specialized collection and disposal centers. If this unit must be dismantled, this must be done by a specialized center for collection and disposal of electric and electronics appliances or other dangerous substances. This product has been supplied from an environmentally aware manufacturer that complies with the Waste Electrical and Electronic Equipment (WEEE) Directive 2002/96/EC. The “crossed-out wheelie bin” symbol at right is placed on this product to encourage you to recycle wherever possible.
Please be environmentally responsible and recycle this product through your recycling facility at its end of life. Do not dispose of this product as unsorted municipal waste. Follow local municipal waste ordinances for proper disposal provisions to reduce the environmental impact of waste electrical and electronic equipment (WEEE).
For information regarding the scrapping of this equipment, go to http://www.eu.emersonnetworkpower.com
(“Products session” or “Contact us” session) or call Emerson’s worldwide technical support at:
• 00 80011554499 (toll free number)
• +39 0298250222 (toll number based in Italy)

ROHS Compliance

The MPH2 rack PDU modules comply with the Restriction of Hazardous Substances directive (ROHS), prohibiting use of six hazardous materials manufacturing of electronics, including lead-free solder.

FCC Compliance

This unit complies with the limits for a Class A device pursuant to Part 15 of the FCC Rules. Operation is subject to the following two conditions:
This device may not cause harmful interference, and
This device must accept any interference received, including interference that may cause undesired operation.
NOTE
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications.
Emerson® MPH2
Operation of this equipment in a residential area is likely to cause harmful interference that the user must correct, including the expense of all corrective modifications.
2
SAFETY SYMBOLS
The following symbols may appear within the documentation or on the product.
Symbol Meaning
High Temperature
Alerts the user where the enclosure temperature may exceed 158°F (70°C) while operating under high-ambient temperature and at maximally rated load.
Instructions
Signifies the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.
Dangerous Voltage
Warns about the presence of uninsulated dangerous voltage within the product’s enclosure that may be of sufficient magnitude to constitute a risk of electric shock to persons.
Power On
Indicates the principal On/Off switch is in the On position.

Safety Symbols

Power Off
Indicates the principal On/Off switch is in the Off position.
Protective Grounding Terminal
Indicates a terminal that must be connected to earth ground before any other connections to the equipment may be made.
3 Emerson® MPH2

1.0 INTRODUCTION

The Emerson Network Power® MPH2™ is the most intelligent, high-availability line of managed rack PDU’s. It offers remote monitoring and control capabilities as well as environmental sensors with multiple power input selections and output configurations.

Metering Levels

Four types of MPH2 are available that offer metering of all electrical information including input, branch and outlet levels, as well as integration with environmental sensors. The available information varies by type of MPH2.

Mounting

Rack PDU’s are available for mounting in vertical configuration in standard or network enclosures.
Power cords on MPH2 models that mount vertically in a zero-U configuration may be switched from one end to the other to accommodate top or bottom cable entry into the rack.

Locking Outlets - IEC Type Only

Locking outlets are available on models with IEC outlets. The locking feature requires optional power cords to be installed on devices powered by the MPH2.
The outlets require no modification to function properly with non-locking power cords.

Overcurrent Protection

Introduction
All MPH2 rack PDU units with input current rating of 30A and higher feature 100% rated hydraulic-magnetic breakers. For all UL-listed models, the maximum cord and plug-connected loading is limited to 80% continuous loading, as required by UL in accordance with the National Electric Code.
Low-profile circuit breakers are used on all MPH2 rack PDU’s with two or three branch circuits. Standard-profile circuit breakers are used on MPH2 rack PDU’s that have six branch circuits or have a 240VAC rating. Each type of circuit breaker is a flush-mount, rocker style (see Figure 29).

Integrated Monitoring and Management

The factory-installed Emerson RPC2™ communications module permits managing the MPH2 rack PDU over a secure Web page and SNMP-based network management system. The RPC2 permits interconnecting up to four rack PDU’s for monitoring and management.
NOTE
Refer to the RPC2 communications module user manual, SL-20841, for detailed instructions on installing and using the RPC2 module. The document is available at Emerson’s Web site:
http://www.emersonnetworkpower.com
A rack PDU can be monitored locally through its onboard LCD, through a Web interface or through an optional display module, either the RPC BDM (Part# RPCBDM-1000). The display module connects directly to the RPC2 communications module. It can be handheld, mounted in or on the rack or mounted on a wall near the rack PDU it is monitoring.
Multiple MPH2 rack PDU’s can be managed with these software applications:
•Avocent
•Avocent DSView
• Emerson’s Trellis
•Liebert
• Liebert SiteScan
®
Rack Power Manager software
management software
Real-Time Infrastructure Optimization platform software
®
Nform®, which adds group-based outlet management
®
Emerson® MPH2
4

Figure 1 Vertical MPH2 rack PDU Configuration

Network
Connection
(10MB/100M
B/1GB)
Monitoring Station
RPC™ Basic
Display Module
Serial Appliance
Vertical
MPH2
rack PDU
Connected Equipment
Rack PDU Array
Sensors
Integrated and
Modular
Introduction

1.1 General Characteristics

• Input ampacities include 16A or 32A for European Union versions and 16A to 48A for North American versions.
• Single-phase and three-phase.
• Input voltages include 100-120VAC, 120/208VAC, 200-240/415VAC.
• Outlets types include NEMA 5-20, IEC 320 C13 and IEC 320 C19
• Input connection supports a highly flexible fixed power cord or hard-wired connection to user accessible terminal block.

1.2 Model Types

There are four types of MPH2 rack PDU.
Type R—Outlet Metered, Outlet Switched: Supports metering of the overall input, individual branches and individual outlets; also supports individual On/Off control of each outlet.
Type M—Outlet Metered: Supports metering of the overall input, individual branches and individual outlets.
Type C—Rack PDU Metered, Outlet Switched: Supports metering of the overall input and of individual branches and supports individual On/Off control of each outlet.
Type B—Rack PDU Metered: Provides basic power distribution and supports metering of the overall input and of the individual branches.
5 Emerson® MPH2

1.3 Appearance and Components

Serial Port
USB Port
Display Port
Link Port
Network Port
Sensor Port
Reset Button Access
1.3.1 Controls and Indicators—RPC2
The MPH2 rack PDU is monitored and managed by the factory-installed RPC2 communications module. This manual presents information about the MPH2’s functions and features. For details on operating the MPH2 through the RPC2 communications module, refer to the RPC2 user manual, SL-20841. The document is available at Emerson’s Web site:
http://www.emersonnetworkpower.com
The RPC2 is installed near the middle of the MPH2 rack PDU. The central location eases connections whichever orientation is required for power cabling.
The RPC2’s Web-based interface provides system operating measurements, as well as readings from optional SN temperature or temperature/humidity sensors. The RPC2 provides basic information about the MPH2 rack PDU, such as firmware version, unit rating, model number and serial number.
Figure 2 MPH2 major monitoring and management features
Introduction

1.3.2 Controls and Indicators—LED’s

The MPH2 rack PDU also has LED’s that indicate outlet and branch status and system information. The LED’s flash, pulse or change colors to indicate an event or alarm condition (for details on how LED’s respond to events and alarms, refer to 5.0 - Troubleshooting.
NOTE
Units with a “B” as the fourth character in the model name (MPHBxxxx) do not have LED’s at their outlets. The branch and outlet LED behavior in 5.0 - Troubleshooting and elsewhere in this document does not apply to these units.
Outlets on units with an “M” as the fourth character in the model name (MPHMxxxx) cannot be turned Off. LED’s at outlets on these models are always either on continuously or flashing when input power is present.

1.3.3 Controls and Indicators—Onboard LCD

Emerson’s MPH2 has an integrated, onboard LCD that can be used to view information about the rack PDU. The information available depends on the type of MPH2. For additional information about the onboard LCD, refer to 3.1.1 - Getting Information Through the Onboard LCD.
Emerson® MPH2
6
Figure 3 MPH2 LCD and LED’s
MPH2
121. 1V 359W
2.96A
2kWh
i
TX
MPH2
Managed Rack
Power Distribution
RX
L1 L2
L3
1
Onboard LCD
Left Arrow Key Right Arrow KeySelect Key
Line Input Status LED’s
Typ e B M odels
Branch B Outlets
Not shown
Branch Identification
Outlet Identification
Type C, R and M Models
LED’s at Each Outlet
(Denote Outlet Status)
Outlet
Identification
Outlet
Identification
Branch
Identification
Branch
Identification

1.3.4 Power Components

Introduction
The component location and type depend on the model of the MPH2 rack PDU. For example, units with a “B” as the fourth character in the model name do not have LED’s at their outlets; see Figures 4, 5, 6 and 7.
Figure 4 Branch and outlet identification—Units with no monitoring
Figure 5 Branch and outlet identification—Units with individually monitored and managed outlets
7 Emerson® MPH2
Branch Overcurrent Protection
Branch Circuit Breakers
Standard Profile
Branch Identification
Branch Circuit Breakers
Low Profile
Branch Identification
Models having more than 16A input current rating are equipped with branch overcurrent protection. This protects each outlet group against overload and short circuit. The branch circuit breaker is a UL 489-listed breaker with a flush-mount, rocker-style actuator. The circuit breaker interrupts the fault current flowing in the line-to-line, line-to-neutral and line-to-PE conductors of the branch circuits. The branch circuit breaker ratings apply over the full rated operating temperature and frequency.
The flush-mount breakers guard against accidental trips that could interrupt power to the connected load. Manually tripping a breaker requires a small, flat blade, such as a screw driver (see Figure 29).
Low-profile circuit breakers are used on all MPH2 rack PDU’s with two or three branch circuits less than 240V rating in a line-neutral configuration. Standard-profile circuit breakers are used on MPH2 rack PDU’s with six branch circuits or have a 240VAC rating. Each type of circuit breaker is a rocker style (see Figure 29).
The branch circuit breaker labeling (A, B, C and so on) shows which outlets are protected by each specific breaker. Outlets on Branch A are protected by the circuit breaker labeled A. Three-phase PDU’s may also have labeling showing the phase associated with each circuit breaker.
NOTE
The branch circuit breaker is not designed to be used as a disconnect device for the connected load.
Figure 6 Circuit breaker branch identification
Introduction

1.3.5 Hard-Wired Connection Features

Emerson’s MPH2 rack PDU may be equipped with either a factory-installed input power cord or hard-wired connections. The hard-wired connection will be at one end of the unit. A terminal block in the hard-wired connection compartment is coded to aid in making the connections. A collar secures the input wire, keeping the strain off the terminal block connections. See Figure 7.
Emerson® MPH2
8

2.0 INSTALLATION

An MPH2 rack PDU can be installed in an Emerson rack on the frame members using field-supplied hardware. The unit can be installed on the face or the side of frame members. The unit can be mounted so that the power cord exits either the top or bottom of the rack.
NOTE
Follow all local and national electrical codes, standards and recommended practices.

Disconnect Required for Hard-Wired MPH2 Units

A readily accessible input power disconnect device must be installed near the MPH2 rack PDU.

Input Power Location for MPH2 Units with Factory-Installed Power Cords

The input power socket or outlet must be installed near the MPH2 and must be easily accessible.
Installation
9 Emerson® MPH2

2.1 Attaching Input Power Cords—Hard-Wired Models Only

L2
L1
PE
L3
Terminal Blocks
Labels
Strain-Relief Collar
Terminal Blocks
Input Power Wiring Entry Through End Cap
Hard-Wired Connections
(Faceplate and End Cap Removed)
Faceplate
Terminal Block Screws
Phillips Head Screws
Nuts Attaching Cable Clamp Assembly: 4
MPH2’s with integral power cords need no assembly before installation. Units with hard-wired input power require attachment of input power cords. See Table 1 for wire sizing.
Hard-wired models may be wired with or without conduit.

2.1.1 Attaching Input Power Cords Without Conduit

1. Remove the end cap. It is held in place with two T10 Torx screws.
2. Slide the terminal block cover off.
3. Loosen the strain-relief collar. It is held in place with two Phillips head PH1 screws.
4. Strip the insulation from the individual wires as required to fit into the terminal block. Recommended stripping length for MPH2 units rated less than 32A is 9mm; for MPH2’s rated or
higher, 11mm.
5. Slip the power cord through the hole in the end cap and through the strain-relief collar.
6. Loosen the terminal block screws.
7. Insert the wires into the terminal block according to the labeling inside the MPH2; tighten each terminal block screw after inserting a wire. Refer to Table 2 for tightening torque.
8. Tighten the strain-relief collar around the input power cord. The cord’s outer insulation covering should extend through the bracket.
9. Replace the terminal block cover by either sliding it on or snapping it into place.
10. Reattach the end cap to the MPH2 with the two screws removed in Step 1.
Figure 7 Hard-wired connections
Installation
Emerson® MPH2
10

2.1.2 Attaching Input Power Cords With Conduit

Cover Plate Spacer
Cover Plate
Conduit (Cable Not Shown)
End Cover (4 screws)
Conduit Connector (field-supplied)
1. Remove the end cap. It is held in place with two T10 Torx screws.
2. Slide the terminal block cover off.
3. Remove the cable clamp assembly. It is held in place with four nuts (see Figure 7).
4. Strip the insulation from the individual wires as required to fit into the terminal block. Recommended stripping length for MPH2 units rated less than 32A is 9mm; for MPH2’s rated or
higher, 11mm.
5. Slip the stripped wires through the seal-tight conduit connector, through the metal end plate and into the terminal block connection box.
6. Loosen the terminal block screws.
7. Insert the wires into the terminal block according to the labeling inside the MPH2; tighten each terminal block screw after inserting a wire. Refer to Table 2 for tightening torque.
8. Install the cover plate spacer, by either sliding it on or snapping it into place and sliding it firmly against the main body of the MPH2.
9. Install the cover plate, by either sliding it on or snapping it into place and pressing it against the cover plate spacer.
10. Attach the metal end plate to the MPH2 with four screws provided in the kit.
11. Slide the conduit into the seal-tight conduit connector.
12. Tighten the seal-tight conduit connector until it grips the conduit and crimps it securely.
Figure 8 Disassembling the MPH2 for installing an input power cable in conduit
Cable Clamp Assembly (Individual parts shown; may be removed as a unit)
Cover Plate
Installation
Figure 9 Disassembling the MPH2 for installing an input power cable in conduit
End Cap; attaches with two screws
11 Emerson® MPH2
Table 1 Hard-wired models—Connection terminal ratings
Insert the Button Mount into the Keyhole Slot
Torque screw 17 lb-in (2Nm)
Button Mount
MPH2 Rating
32A >32A
Conductor Cross-Section Solid, Minimum 0.2mm
Conductor Cross-Section Solid, Maximum 6mm
Conductor Cross-Section Stranded, Minimum 0.2mm
²
0.5mm
²
²
16mm
0.5mm
Conductor Cross-Section Stranded, Maximum 4mm² 10mm
Conductor Cross-Section, AWG/kcmil, Minimum 24 20
Conductor Cross-Section, AWG/kcmil, Maximum 10 6
Conductor Cross-Section Stranded, With Ferrule Without Plastic Sleeve, Minimum
Conductor Cross-Section Stranded, With Ferrule Without Plastic Sleeve, Maximum
Conductor Cross-Section Stranded, With Ferrule With Plastic Sleeve, Minimum
Conductor Cross-Section Stranded, With Ferrule With Plastic Sleeve, Maximum
0.25mm
0.25mm²²0.5mm
4mm
4mm
²
0.5mm
²
²
10mm
10mm
Table 2 Terminal tightening torque
MPH2 Rating
Tightening Torque
Minimum 0.6 Nm 1.5Nm
Maximum 0.8Nm 1.8Nm
32A >32A
Installation
²
²
²
²
²
²
²
²

2.2 Tool-less Mounting

Figure 10 Tool-less mounting

For tool-less mounting, attach the mounts to the rear of the MPH2 rack PDU, then hang it in the rack as shown in Figure 10. Torque the screw attaching the mounting button 17 lb-in (2Nm).
NOTE
Brackets are not supplied. A range of brackets for Emerson and other manufacturers’ racks are available as accessories.
Emerson® MPH2
12

2.3 Installing an MPH2 in an Emerson® Rack

2.3.1 Mounting Hardware and Tools Required

Factory-Supplied
•Two brackets
• Mounting buttons
Field-Supplied
• Spring nuts (supplied with Emerson rack)
• Phillips #2 screwdriver
Determine where in the Emerson rack the PDU will be installed and follow the instructions below. Installation requires attaching two brackets to the PDU, inserting four spring nuts into the rack and using the brackets to attach the PDU to the rack.
To install a PDU in a rack:
1. Attach a bracket to each end of the PDU.
2. If mounting on horizontal frame members, attach the brackets in-line.
- or -
If mounting on a vertical frame member, attach the brackets at a right angle to the PDU.
3. Insert two spring nuts into the appropriate T-slot on the frame member. Position the spring nuts to accommodate screws inserted through slots in the brackets. To move the spring nuts, press down on each with a small, pointed object and slide each into position.
4. Hold the PDU in place and attach the top of the unit to the rack with tool-less fasteners.
5. Tighten the screws, applying 46 lb-in (5.2Nm).
6. Repeat Steps 3 through 5 for the lower bracket on the lower end of the PDU.
Installation
Figure 11 Installing in an Emerson rack
13 Emerson® MPH2

2.3.2 Safety Earth Ground Connection

A
L1
OFF
20
ON
Ground wire connection on the MPH2 Rack PDU (location may vary)
Ground Wire
Ground Wire Connection Screw M6 x 12
Washer
Ground wire connection on an Emerson rack
Ground wire connection on the MPH2 Rack PDU (location may vary)
Lock Washer
COMPLETED GROUND WIRE CONNECTION
Ground wire and hardware are available as an option from Emerson.
Ensure that the safety earth connection is made before any equipment is connected to Emerson’s MPH2 rack PDU. Units with factory-attached input power cords have an internal grounding conductor. The ground wire establishes the same ground reference between the MPH2 rack PDU and the rack. The ground-wire and hardware are available as an option from Emerson.
NOTE
The grounding strap may be used with MPH2 rack PDU’s that have integral input power cords and units that have hard-wired input power cords. The strap supplements the internal grounding conductor of the integral power supply cord.
The grounding strap may be particularly useful when the rack is on a raised floor.
1. Insert a spring nut into the rack frame near the grounding point on the MPH2 (see Figure 10 for inserting the spring nut).
2. Attach a ground wire to the rack with a screw, washer and lock washer. The screw is secured to the rack’s frame with a spring nut. The ground wire and hardware are available as an option from Emerson.
3. Use a second field-supplied screw, washer and lock washer to secure the ground wire to the MPH2. The connection point is marked with an earth-ground symbol (see Figure 12).
Figure 12 Earth-ground connection
Installation
Emerson® MPH2
14

2.3.3 Recommended Electrical Backup Protection

A field-provided external circuit breaker must be installed upstream of the MPH2 rack PDU. The circuit breaker must be sized according to the input rating of the PDU. The circuit breaker rating must meet the values in Table 3.
The external circuit breaker serves as the primary input power disconnect for the MPH2.
Table 3 Upstream circuit breaker rating
Maximum Input
Current Per Pole
16A
24A 30A (NA)
32A 32A (EU, WW)
40A 50A (NA)
48A 60A (NA)
63A 63A (EU, WW)
Rated Current
of Upstream CB
20A (North America)
16A (EU, WW)
Installation
15 Emerson® MPH2

2.4 Connecting Rack Equipment

NOTE
Circuit breakers on Emerson’s MPH2 rack PDU are opened at the factory. The open circuit breakers help protect against damage to the connected load from high inrush current when input power is connected.
The circuit breakers must be closed before the unit will supply power to the connected load. Do not close the breakers until after all rack equipment is connected to the MPH2 rack PDU.
Once the MPH2 rack PDU has been installed in the rack, the unit is ready for connection of equipment that will be powered by the unit or used for monitoring.
Verify that the equipment to be connected meet these requirements:
• Input power requirements of each device match the MPH2 output
• Equipment will not overload the MPH2 rack PDU
• Input power cords match the MPH2 outlets
• Equipment is ready for input power (properly installed and prepared)
To connect devices to an MPH2 rack PDU:
1. Verify that all devices to be connected are shut down and unplugged from input power sources.
2. If the MPH2 rack PDU will be monitored over a network, connect an Ethernet cable to the network port on the factory-installed RPC2.
3. Route the devices’ power cables to the MPH2 rack PDU, following proper procedures and good practices, such as segregating power cables from control cables and keeping cable bends to recommended angles.
4. Verify that the branch circuit breakers on the MPH2 rack PDU are open.
5. Connect the devices’ input power cables to the MPH2 rack PDU.
Installation
NOTE
All C13 and C19 outlets on MPH2 rack PDU’s are locking outlets. Locking requires use of special power cords, which may be factory-installed on the equipment or is available from Emerson.
If non-locking power cords are used, the power cords should be secured through other methods to prevent unintended power interruption.
6. Record where each piece of rack equipment is connected, using the branch and outlet numbers on the MPH2 rack PDU.
7. Post the connection information on or near the rack and at any remote monitoring location.
8. Connect input power to the MPH2 rack PDU. On Types R, C and M models, all LED’s will begin pulsing.
9. Verify that input power is present and the line status LED’s are illuminated.
10. Close the branch circuit breakers. The receptacle LED’s will glow green.
11. Turn on the connected devices one at a time and verify that each is operating properly.
12. Ensure that the specified values found on the MPH2 rack mount PDU’s serial tag are not exceeded.
13. Monitor and control the MPH2 rack PDU as detailed in the RPC2 user manual, SL-20841, available at www.emersonnetworkpower.com
Emerson® MPH2
16

2.5 Installing Optional Items

Scan-Switch
RJ-45 Input
The following items may be added to an MPH2 rack PDU system but are not required.
• RPC Basic Display Module
•Liebert

2.5.1 RPC Basic Display Module

The RPC Basic Display Module (BDM) provides local display of parametric data, including electrical status, temperature and humidity for all connected MPH2 rack PDU’s. Display information is accessed via a navigation switch on the BDM. The RPC BDM is connected by cable to the MPH2 rack PDU, allowing the user to install the display to suit the local reading requirements. A 6.5ft. (2m) cable and general mounting provisions are provided. A single display can be used for up to four rack PDU’s connected in a Rack PDU Array
The RPC BDM can be mounted in the rack with either the included hardware or with a cable tie through the slot on the back of the module. Either method permits moving the BDM to a different place in the same rack or to another rack.
Included Hardware
•RPC BDM, 1
• Spring Nut M5, 1
• Spacer Sleeve, 1
• Mounting Button, 1
• M5 Screw, 1
• Cable Clip, 1
Figure 13 RPC BDM
®
SN temperature/humidity sensors
Installation
.
17 Emerson® MPH2
To install an RPC BDM in a rack:
Insert a spring nut into a T-slot...
... then flip it so that it is square in the slot
1. Determine the mounting location.
2. Insert a spring nut into a T-slot on the frame member where the RPC BDM will be installed.
Figure 14 Inserting the spring nut into a T-slot
3. Insert the MPH2 rack PDU screw into the spacer sleeve.
4. Insert the MPH2 rack PDU screw into the spring nut and tighten securely with a flat-head screwdriver.
5. Hang the RPC BDM on the screw with the hooded mounting slot on the back of the RPC BDM.
6. Connect the RPC BDM to the RPC2 with an Ethernet cable.
7. Be certain to connect the cable to the correct port on the RPC2.
Installation

2.5.2 Temperature/Humidity Sensor

Optional Liebert® SN temperature/humidity sensors are available to assist in monitoring conditions in the rack. Liebert SN sensors are designed for installation in Emerson racks without tools, but each may be placed in any area to monitor temperature and humidity levels. Each connects to the RPC2 communications module, which makes readings available to other monitoring methods.
To install a sensor in a rack:
1. Insert the sensor bracket base into one end of the sensor support.
2. Snap the sensor into the other end of the sensor support.
3. Choose where in the rack to install the sensor assembly.
NOTE
Emerson recommends placing the sensor in the area of the rack that is likely to be warmest. That location helps determine extreme conditions that can cause equipment damage.
4. Hold the sensor bracket on a T-slot on the Emerson rack frame where the sensor will be placed.
5. Insert the included quarter-turn fastener through the rectangular hole in the sensor bracket base and into the T-slot.
6. Turn the fastener clockwise 90 degrees, a quarter of a turn.
7. Route the sensor cable to the RPC2 communications module and insert it into the card’s external sensor port.
NOTE
For more information, see the RPC2 user manual, SL-20841, available at Emerson’s Web site,
http://www.emersonnetworkpower.com
Emerson® MPH2
18

3.0 OPERATION

Emerson’s MPH2 rack PDU may be monitored and managed by the factory-installed RPC2 communi­cations module. This manual presents information about the MPH2’s functions and features. Refer to the RPC2 user manual, SL-20841, for details on using the RPC2 communications module to monitor and manage the MPH2. The document shipped with the MPH2 rack PDU and is available at Liebert’s Web site, http://www.emersonnetworkpower.com
The MPH2’s onboard LCD and the Web-based interface display system operating measurements, as well as readings from optional Liebert SN temperature or temperature/humidity sensors. The RPC2 communications module and onboard LCD also display basic information about the MPH2 rack PDU, such as firmware version, unit rating, model number and serial number.
LED’s on the MPH2 and an audible alarm also assist in monitoring performance with alerts about events and alarm conditions. The keys under the onboard LCD are used to navigate to various information and to silence alarms.

3.1 Controls and Indicators

The MPH2 rack PDU also has LED’s that indicate outlet and branch status and system information. LED’s flash, pulse or change colors to indicate an event or alarm condition (for details on how LED’s respond to events and alarms, refer to 5.0 - Troubleshooting.
NOTE
Units with a “B” as the fourth character in the model name (MPHBxxxx) do not have LED’s at their outlets. The branch and outlet LED behavior in 5.0 - Troubleshooting and elsewhere in this document does not apply to these units.
Operation
Outlets on units with an “M” as the fourth character in the model name (MPHMxxxx) cannot be turned Off. LED’s at outlets on these models are always either on continuously or flashing when input power is present.
19 Emerson® MPH2

3.1.1 Getting Information Through the Onboard LCD

MPH2
121. 1V 359W
2.96A
2kWh
i
TX
MPH2
Managed Rack
Power Distribution
RX
L1 L2
L3
1
LCD
Left Arrow Key Right Arrow KeySelect Key
Line
Input
Status
LED’s
MPH2 LCD Keys
and LED’s
(Main Screen Example)
MPH2
121.1V 359W
2.96
A
2kWh
1
i
!
Power Consumption by Connected Load in Watts
Input Current Level in Amperes
Bar Graph of Input Current
MPH2 Unit Identification (Always shows numeral 1)
Energy used in kWh
MPH2 Rack PDU Information
Input Level Metered Information
Phase or Line Voltage
Alarm Indication
Link to Receptacle Level
The MPH2’s main screen is displayed when the rack PDU is first powered up; see Figure 3. The onboard LCD returns to the main screen from any other view after 5 minutes of inactivity (no keys being pressed).
The Left and Right arrow keys below the onboard LCD move the cursor across the bottom of the screen. When the cursor is over the desired symbol, press the Select key to display information about that portion of the MPH2. The keys permit moving one level at a time through the levels of the MPH2 menus.
Example: Use the arrow keys to move the cursor over branch names (A or B) or outlet names (numbers 1 - 8). Press the Select key and the screen displays information about the selected branch or outlet. The screen retains the view if no key is pressed for 5 minutes. After 5 minutes of inactivity, the onboard LCD returns to the main screen.
Figure 15 MPH2 onboard LCD and control keys
Operation
Figure 16 MPH2 onboard LCD layout
Emerson® MPH2
20

3.1.2 Adjusting the Onboard LCD’s Contrast

The onboard LCD is factory-set to be easily viewed in lighting conditions found in most work places. The contrast can be changed. To change the contrast:
1. Press any key to activate the LCD.
2. Press either the Right or Left arrow key to highlight the contrast icon, a circle half dark and half white.
3. Press the Select key.
4. Use the Right or Left arrow key to highlight the Up or Down contrast icon (each is an arrow). Use the pattern to determine when the contrast is acceptable.
5. Press Select until the screen’s contrast is satisfactory
NOTE
The same steps apply to the RPC BDM.
Figure 17 Adjust LCD contrast
Operation
21 Emerson® MPH2

3.1.3 Adjusting the Onboard LCD’s Orientation

Model: MPHM3141 S/N: 4FEB030033 MPHM3 FW Ver: 0.4.1.2 Ratings: 1P3W 120V 16A Receptacles : 16
Model: MPHM3141 S/N: 4FEB030033 MPHM3 FW Ver: 0.4.1.2 Ratings: 1P3W 120V 16A Receptacles : 16
The onboard LCD may be flipped for viewing ease. To flip the screen:
1. Press any key to activate the LCD.
2. Press either the Right or Left arrow key to highlight the information icon (
3. Press the Select key.
4. Use the Right or Left arrow key to highlight the orientation icon .
5. Press Select to the flip the screen’s orientation.
NOTE
The same steps apply to the RPC BDM.
Figure 18 Flip LCD
Operation
i).

3.1.4 Obtain MPH2 System Information

1. Use the Left or Right arrow key to move the cursor to the information icon (the letter i) in the lower right corner.
2. Press the Select key. The onboard LCD shows information about the MPH2: model number, serial number, firmware
version, power rating and number of outlets. See Figure 19. After 5 minutes of no activity (no key pressed), the onboard LCD returns to the main screen.
Figure 19 MPH2 rack PDU information screen
Emerson® MPH2
22

3.1.5 Determine IP or MAC Address

IP: 162.1.30.57 MAC ID: 00:00:84:47:31:49 RPC2 FW Ver: 7.0.0.1
MPH2 IP Address
MPH2 MAC Address
Firmware version installed on RPC2
MPH2
119.7V
0kWh
i
1.98
A
204W
1
1. Use the Left or Right arrow key to move the cursor to the information icon (the letter i) in the lower right corner.
2. Press the Select key.
3. Use an arrow key to scroll to the Network icon .
4. Press the Select key. The onboard LCD will display the MPH2 rack PDU’s IP address and MAC address as shown in
Figure 20.
Figure 20 IP address in MPH2 Onboard LCD
Operation

3.1.6 View Input Level Information

The input level is the main screen shown by the onboard LCD. The LCD will show the input level screen if the cursor and arrow keys are not used for 5 minutes. The input screen is shown in Figure 21.
Figure 21 Input level screen
23 Emerson® MPH2

3.1.7 View Active Alarms

MPH2
121.1V 359W
2.96
A
2kWh
1
i
!
Alarm Indication
Low Humidity Sensor
!
The most-recent alarms will be at the top of the list.
1. Use the Left or Right arrow key to move the cursor to the information icon (the letter i on a black box) in the lower right corner.
2. Press the Select key.
3. Use the Left or Right arrow key to scroll to the Alarm icon, a large exclamation point.
Figure 22 Alarm icon
Operation
4. Press the Select key. The onboard LCD will display a list of active alarms on the MPH2 rack PDU as shown in
Figure 23.
5. Moving the cursor to an alarm and pressing the select key displays information about the alarm.
Figure 23 Alarm list screen
Emerson® MPH2
24

3.1.8 View Branch Level Information

1-A
119.6V 202W
1.98
A
237VA
i
BA
Branches A and B
Branch Level Indicator
Indicates Branch Circuit Breaker is Closed (O indicates open Branch Circuit Breaker
1-A-7
119.7V
237VA
i
1.98
A
203W
1 2 3 4 5 6 7 8
Outlet Level
Outlet Identification: MPH2 #1 Branch A Outlet #7 (Cursor is over Outlet #7 at bottom of screen)
Cursor over Outlet #7
1. Use the Left or Right arrow key to move the cursor to the information icon (the letter i on a black box) in the lower right corner.
2. Press the Select key.
3. Use the Left or Right arrow key to scroll to the letter of the branch to be viewed.
4. Press the Select key. The onboard LCD will display information about the selected branch of the MPH2 rack PDU as
shown in Figure 24.
Figure 24 Branch level information screen
Operation

3.1.9 View Outlet Level Information

Figure 25 Outlet level information screen
1. Use the Left or Right arrow key to move the cursor to the outlet icon in the lower right corner of the screen.
2. Press the Select key.
3. Use the Left or Right arrow key to scroll to the number of the outlet to be viewed.
4. Press the Select key. The outlet number will begin flashing and remain flashing until a new outlet is selected.
The onboard LCD will display information about the outlet as shown in Figure 25.
25 Emerson® MPH2

3.1.10 View Sensor List

Sensor: 1-2-1
T 7B0000024241431 H 8A000095173G6B62 T C3000000122 G6431
Two temperature and one humidity sensors are connected to the MPH2
The sensors’ default names are their serial numbers. This can be changed through the Web interface.
Sensor: 1-2-1
33.8% : High ID: 8A000095173 G6B62 Label: 8A000095173 G6B62
!
Humidity sensor information: Percentage and severity followed by identification and label (serial number). The default label is the sensor’s serial number. This can be changed through the Web interface.
Humidity sensor triggers high humidity alarm
1. Use the Left or Right arrow key to move the cursor to the outlet icon in the lower right corner of the screen.
2. Press the Select key. The onboard LCD will display a list of the sensors as shown in Figure 26. The sensors will be
listed in order of their identification number.
Figure 26 Sensor list screen
Operation

3.1.11 View Sensor Information

1. Use the Left or Right arrow key to move the cursor to the outlet icon in the lower right corner of the screen.
2. Press the Select key.
3. Use the Left or Right arrow key to scroll to the sensor to be viewed.
4. Press the Select key. The onboard LCD will display information about the sensor, similar to that shown in Figure 27.
Figure 27 Sensor information
Emerson® MPH2
26
Figure 28 Configuration in progress screen
MPH2
--V
--kWh
i
A
--W
The onboard LCD will shift to the main menu during a configuration update. The keys below the LCD will be inoperable during the update.
Low-Profile Breaker Switch
Standard-Profile Breaker Switch
Press here to reset the breaker
Push top of breaker in to reset this breaker
Press flat-blade screwdriver into slot to trip breaker

3.1.12 Opening and Closing Circuit Breakers

MPH2 rack PDU feature circuit breakers to protect either branches or individual outlets, depending on the model. Low-profile circuit breakers are used on all MPH2 rack PDU’s with two or three branch circuits. Standard-profile circuit breakers are used on MPH2 rack PDU’s with six branch circuits or have a 240VAC rating.
Operation
Both types of circuit breakers are flush-mount, rocker-style breakers. The circuit breakers are designed to prevent accidental trips. To manually trip a circuit breaker to the Off position, insert a flat-blade screwdriver or similar tool into the slot on the breaker as shown in Figure 29. To reset the breaker, press the end nearest ON until it clicks into place.
Figure 29 Turning Off or resetting a circuit breaker
27 Emerson® MPH2

3.1.13 Silence an Alarm

IP: 10.301.36.28 MAC ID: 00:00:40:86:68:70
1
Press any of the navigation keys momentarily to silence an audible alarm.
To silence an audible alarm, press any of the three navigation keys below the LCD.
Figure 30 Silence an alarm
Operation
5.0 - Troubleshooting tells how the LED interface signifies events and alarms.
NOTE
During a firmware upgrade, the Line Input Status LED’s on the MPH2 will flash red and green, but the rack PDU will continue receiving and distributing power without interruption.
Emerson® MPH2
28
Emerson® MPH2 Rack PDU Specifications

4.0 EMERSON® MPH2 RACK PDU SPECIFICATIONS

Input Power Configurations; Vary by Model and Region
Single-Phase Input; CE-Mark
240VAC, 16A; also UL-listed 3.7kW
230V, 32A 7.3kW
Three-Phase Input; CE-Mark
230/400V, 16A 11kW
230/400V, 32A 22kW
Single-Phase Input; UL-Listed
120VAC 16A 1.9kW
120VAC 24A 2.9kW
208VAC 24A 4.9kW
Three-Phase Input; UL-Listed
120/208VAC, 24A 8.6kW
120/208VAC, 40A 14.4kW
120/208VAC 48A; 240/415VAC, 24A 17.3kW
Input Wiring Options
Outlet Options NEMA 5-15; NEMA 5-20; IEC 320C13; IEC 320 C19
Number of Outlets, Maximum 48
Power Consumption, Maximum 7.5W
Measurement Accuracy
Insulation Class I, Reinforced SELV
Dielectric Electric Strength Tested up to 4242VDC
Overcurrent Protection
Operating Temperature Range, °F (°C)
Storage Temperature Range, °F (°C) -13 to 185 (-25 to 85)
Humidity, % 10 to 90 non-condensing
Altitude, ft. (m) 6562 (2000)
Mounting
Zero-U Units, Width x Depth, in. (mm)
Zero-U Units, Length, in. (mm) 13.1 - 72.2 (333 - 1833)
Safety Standards (Vary by Model and Region)
EMC Standards (Vary by Model and Region)
Agency Approvals (Vary by Model and Region)
8 to 10 ft. (2.4 to 3m) Non-Detachable Power Supply Cord
Hard-Wired Terminal Block
Voltage: ±1% +0.1VAC
Current: ±1.5% + 0.01A from 1% to 10% of unit rating;
±1% +0.01A from >10% to 125% of unit rating
UL489-Listed, CSA, TUV, CCC Overcurrent Circuit Breaker,
20A, 5000A A.I.C
32A or Less Input Models: 32 to 140 (0 to 60)
40A and 48A Input Models: 32 to 122 (0 to 50)
Factory-Installed Toolless Brackets
Universal Mounting Bracket
Low-profile: 2.2 x 1.96 (56x50)
Standard: 2.2 x 2.7 (56 x 70)
IEC 60950-1:2005 (Second Edition) + Amendment 1:2009
CSA C22.2 NO. 60950-1-07 (2nd Edition) + Amendment 1:2009
UL 60950-1 (2nd Edition) + Amendment 1:2009
IECEE CB Full Certification Scheme
FCC Class A, Part 15, Industrial
EN55022:2006+A1:2007, Class A, Industrial
EN55024:1998+A1:2001+A2:2003, Class A, Industrial
IEC61000-3-2:2006, IEC61000-3-3:1995+A1:2001+A1:2005
IEC61000-4-2/3/4/5/6/8/11
UL, cUL, CE, BV, CB, RoHS, REACH, WEEE
29 Emerson® MPH2

5.0 TROUBLESHOOTING

LED Indication
(One or All LED’s)
Color
Green Fast
Green Steady On
Off NA Voltage Off
Red Steady On
Red Fast
Green Slow
Red Fast
Red
(All Receptacle
LED’s)
Green
(All Receptacle
LED’s)
Red
(All Receptacle
LED’s)
State/Flash
Speed
Pulse
Slow
Fast
Audible
Alarm
Condition Status/Recommended Action
Receptacle Identification
Input Voltage Supported Receptacle Powered On
Line Undervoltage Alarm
Line or Receptacle Overcurrent Alarm
Line or Receptacle Overcurrent Warning
Line or Receptacle Undercurrent Alarm
Branch Circuit Breaker Open
Branch Overcurrent Warning
Branch Overcurrent Alarm
Remote user is requesting outlet identification. The LED should stop flashing after 10 seconds.
Normal Operation
Check power source and input plug’s receptacle wiring.
Check receptacle power control settings.
Check power source for power quality problem. If the MPH2 uses 3-phase power, a single low­voltage phase may cause one or more undervoltage alarms. The undervoltage alarm is factory-set to -10% of the minimum input voltage range on the nameplate; it cannot be changed.
Check for changing load conditions. Check overcurrent alarm threshold settings.
Check for changing load conditions. Check overcurrent warning threshold settings.
Check for removal of load. Check undercurrent alarm threshold settings.
Check for changing load conditions; confirm circuit breaker actuator is closed. If open, correct loading condition before pressing circuit breaker actuator closed again.
Check for changing load conditions. Check overcurrent warning threshold settings.
Check for changing load conditions. Check overcurrent alarm threshold settings.
Troubleshooting
Emerson® MPH2
30
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2014 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Lieber t is a registered t rademark of Lieber t Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL -20860_REV1_10-14
Technical Support / Service
Web Site
www.liebert.com
Monitoring
liebert.monitoring@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
liebert.upstech@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
Fax: +63 2 730 9572
Emerson Network Power
Liebert www.emerson.com
Loading...