Emerson MP2-115HW User Manual

POWER AVAILABILITY
2U Hardwire POD™
USER MANUAL
Power Output
Distribution
120 Volt
TABLE OF CONTENTS
GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INTRODUCTION AND SYSTEM DESCRIPTION . . . . . . . . . . . . . . . 4
System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
RACK MOUNT INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . 5
INSTALLATION ON GXT 2U UPS. . . . . . . . . . . . . . . . . . . . . . . 6
HARDWIRE CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical Installation Considerations . . . . . . . . . . . . . . . . . . . . 7
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Properly Grounded (Earthed) Equipment Provides Multiple
Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Wiring Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
APPLY FEED POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
START EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
INDICATOR LAMPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Utility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
UPS Available . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Transfer to Maintenance Bypass . . . . . . . . . . . . . . . . . . . . . . . 13
Transfer to UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Product Warranty Registration. . . . . . . . . . . . . . . . . . . . . . . . . 15
i
FIGURES
Figure 1 UPS mode of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 2 Utility/maintenance bypass mode . . . . . . . . . . . . . . . . . . . 4
Figure 3 2U Hardwire POD with rack mounting brackets . . . . . . . 5
Figure 4 Attaching POD securing brackets to rear of UPS . . . . . . . 6
Figure 5 Conduit entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 6 Removing wiring access doors . . . . . . . . . . . . . . . . . . . . . . 8
Figure 7 Attaching POD to securing brackets . . . . . . . . . . . . . . . . 10
Figure 8 Indicator lamps on 2U Hardwire POD . . . . . . . . . . . . . . . 12
TABLES
Table 1 Breaker specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS
WARNING
!
Do not attempt to service this product yourself. Opening or removing the cover may expose you to dangerous voltages, even when the AC cord is disconnected from the electrical receptacle. Refer all servicing to qualified service personnel.
This manual contains important instructions that should be followed during installation and operation of the 2U Hardwire POD™. This product is designed for commercial / industrial use only, with Liebert UPS systems. It is not intended for use with life support and other designated “critical” devices. Do not exceed POD or UPS rating labels.
Read all safety and operating instructions before operating the 2U Hardwire POD and the connected UPS system. Adhere to all warnings on the unit and in this manual. Follow all operating and user instruc­tions.
Turn the UPS off and unplug the 2U Hardwire POD before cleaning. Use only a soft cloth, never liquid or aerosol cleaners.
The UPS and 2U Hardwire POD are designed for data processing equipment. Do not connect laser printers or appliances, such as hair dryers, heaters, vacuum cleaners, or electric drills, into the POD.
WARNING
!
Do not modify the cables in any way. The POD receptacles should match the UPS input plugs. The 2U Hardwire POD must be grounded at all times while in use. Turn off the UPS before unplugging it.
The UPS and the 2U Hardwire POD are equipped with grounded plugs (plug types vary depending on model). Do not defeat the safety purpose of this plug. If unable to fully insert the plug into the desig­nated socket, contact a qualified electrician or your local dealer or Lie­bert representative for assistance.
1
CAUTION
!
This device receives power from multiple sources. Before servicing this device, remove all connections and cut power from the utility branch input. Before servicing the UPS, follow “Maintenance of UPS” instructions in the user manual for your UPS.
CAUTION
!
This device is for use in a clean, temperature-controlled, indoor environment that is free of conductive contaminants. Route power supply cords so they are not walked on or pinched in any way. Refer to Specifications on page 15 for environmental conditions.
WARNING
!
When the 2U Hardwire POD is in utility position (maintenance bypass mode) the power to the connected load is not filtered or conditioned by the UPS. The Liebert UPS connected equipment guarantee is not valid while in this mode of operation.
2

GLOSSARY OF SYMBOLS

Equipment grounding conductor
Bonded to ground
Electric phase
Indicates AC input
Indicates AC output
3

INTRODUCTION AND SYSTEM DESCRIPTION

Congratulations on your choice of the Liebert 2U Hardwire POD™. The 2U Hardwire POD provides maintenance bypass capability as well as power output distribution. The Liebert 2U Hardwire POD can be used on UPS in the rack mount or tower configuration.
The Liebert 2U Hardwire POD provides an isolated path of power for your UPS system for preventive maintenance or service. While UTIL­ITY and LOAD connections are hardwired, connections to and from the UPS are plug-in to allow easy connection of the UPS.

System Description

The 2U Hardwire POD has two modes of operation: UPS (UPS avail­able) and UTILITY (maintenance bypass).
•During the UPS mode, the power is routed through the UPS sys­tem delivering conditioned power to the load, as shown in Figure 1.
Figure 1 UPS mode of operation
Utility
•During the UTILITY mode, the power is routed around (bypass- ing) the UPS system (see Figure 2). UTILITY power is supplied directly to the load through the 2U Hardwire POD.
CAUTION
!
Battery back-up and conditioned power are NOT available during the UTILITY mode of operation.
Figure 2 Utility/maintenance bypass mode
Utility
• The UPS may be turned off and removed without affecting the load.
POD
UPS
POD
UPS
Connected loads
Connected loads
4

RACK MOUNT INSTALLATION

1. Rack mount installation of the 2U POD is possible with the use of
the rack mounting brackets (shipped with the POD). See Figure 3.
2. The rack mount brackets allow you to rack mount the POD in a
19" enclosure (23" to 19" rack adapters are available as options from Liebert if you are using 23" Foundation or equivalent cabi­net).
3. The POD can be mounted to face one of four directions depending
on your application, and utilizing the rack mount brackets pro­vided.
4. Conduit entry is possible on two sides of the POD. Plan POD ori-
entation to allow for wiring. Determine the desired position and direction for the POD, face it in that direction, and then attach the brackets to the POD with the screws provided.
5. Consult your rack/enclosure manufacturer’s recommendations for
specific rack mounting hardware that will be required.
6. The holes on the rack mount bracket are notched for easy installa-
tion. Tighten the POD securely to the rails and then follow the startup directions for the POD in Installation on GXT 2U UPS.
Figure 3 2U Hardwire POD with rack mounting brackets
LOAD
CAUTION
IF UTILITY LAMP IS ILLUMINATED MAINTENANCE BYPASS POSITION MAY BE SELECTED
SWITCH TO UPS POSITION ONLY WHEN UPS LAMP IS ILLUMINATED
AVAILABLE
UPS
UPS
UTILITY
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
UPS
UTILITY
5

INSTALLATION ON GXT 2U UPS

NOTE
This manual provides instructions for the 2U POD only. Refer to your UPS manual for UPS operation and installation instructions.
1. Unpack the 2U POD carefully, noting the packing method. Retain
the box and packing material for possible future shipments.
2. Visually inspect the 2U POD for freight damage. Report damage
to the carrier and your local dealer or Liebert representative.
3. Verify that the 2U POD UPS input cord and receptacle for the
UPS are the same type of configuration as the UPS to be con­nected.
4. If you already have a UPS installed, turn off all connected UPS
loads. Turn off the UPS and disconnect the input cord.
Figure 4 Attaching POD securing brackets to rear of UPS
5. Attach the two POD securing brackets (this is optional for GXT 2U
UPS) to the rear of the UPS (see Figure 4). You will need a 7-in. (177.8mm) long #1 Phillips head screwdriver for this procedure (torque is 7 in-lb, or 0.8 Nm). The POD brackets have a hole to allow the screwdriver to reach the screw.
6

HARDWIRE CONNECTIONS

Electrical Installation Considerations

CAUTION
!
This UPS must be installed by competent electrical personnel and wired in accordance with local/national electrical codes.
CAUTION
!
The utility input supply to the POD must be protected by a branch rated circuit breaker. The UPS output must also be protected with a circuit breaker connected to the load, rated to carry the input current, and be capable of breaking the maximum expected short circuit current of this branch circuit. The breaker is to be mounted within 6 feet of the POD and be readily accessible to the operator. Refer to
Table 1 for breaker specification.
CAUTION
!
Before installing, open all branch circuit power at the nearest disconnect, turn UPS off, and disconnect all cords to and from the UPS.
The front and bottom of the POD provide alternate conduit entry points for both the UTILITY and LOAD connections.
Figure 5 Conduit entry
FRONT VIEW
CAUTION
LOAD
BOTTOM VIEW
IF UTILITY LAMP IS ILLUMINATED MAINTENANCE BYPASS POSITION MAY BE SELECTED
SWITCH TO UPS POSITION ONLY WHEN UPS LAMP IS ILLUMINATED
Conduit Entry Knockouts
AVAILABLE
UPS
UPS
UTILITY
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
UPS
UTILITY
7
Wiring access doors on each end of the POD allow access to the wiring compartments by opening the top and rear of the POD. Each access door is retained using two Phillips head screws.
The center screw and center panel should not be removed.
Figure 6 Removing wiring access doors
REAR VIEW
CAUTION
- RISK OF ELECTRIC SHOCK, SO NOT REMOVE COVER. NO USER
SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL.
CAUTION
- RISK OF ELECTRIC SHOCK, THIS UPS RECEIVES POWER FROM MORE THAN ONE SOURCE-DISCONNECTION OF THE AC SOURCES IS REQUIRED TO DE-ENERGIZE THIS UNIT BEFORE SERVICING.
CAUTION
- FOR USE IN A CONTROLLED ENVIRONMENT. REFER TO MANUAL FOR ENVIRONMENTAL CONDITION.
Model No. : MP2-115HW Desc. : Micro Pod
C US
Input : 120VAC 12A 50/60Hz, 10 Ouptut : 120VAC 12A 50/60Hz, 10
U.P.S. Accessory
MADE IN TAIWAN 612-XXXXX-00
U L
LISTED
91N6
Remove
Screws
INSTALLATION OF UPS
1.) MAKE LINE CORD CONNECTION TO UPS SIDE OF POD.
2.) TURN ON UPS BY ITS START INSTRUCTIONS.
3.) ENSURE UPS LAMP IS ILLUMINATED.
4.) SWITCH TO UPS POSITION (LOAD IS NOW PROTECTED BY UPS!)
Access
Door
Do NOT remove the
center screw
POWER OUTPUT DISTRIBUTION
Access
Door
MAINTENANCE OF UPS
1.) ENSURE MAINTENANCE BYPASS LAMP IS ILLUMINATED.
2.) SWITCH TO MAINTENANCE BYPASS POSITION. (LOAD IS NOW UNPROTECTED!)
3.) TURN UPS OFF AND DISCONNECT UPS CORDS FROM POD.
4.) UPS IS NOW AVAILABLE FOR MAINTENANCE
Remove
Screws
TOP VIEW

Electrical Connections

The wiring compartments provide terminal blocks to connect Line, Neutral, and Ground for both the UTILITY input and LOAD output.
The cable sizes and distribution methods used during installation are subject to local/national electrical codes of practice, and therefore are not detailed here. Table 1 details the standard current ratings.

Properly Grounded (Earthed) Equipment Provides Multiple Benefits

High quality Ground (Earth) connections are required for the equip­ment ground conductors (Protective Earth) (power system earth con­nection) to provide for safe operation of the UPS and connected loads and to reduce electrical noise. Conduit used alone without a grounding conductor wire is not an acceptable connection. Size Ground (Protec­tive Earth) conductors equal in size to circuit conductors.
For wiring information, please refer to Table 1.
8

Wiring Instructions

1. Remove the wiring access doors by removing the two Phillips head screws that secure them.
2. Determine which of the two available conduit entry points are to be used. Knock out the conduit entry hole for the location and size of conduit to be used.
3. Connect conduit bushing and conduit and run utility load wiring. Inspect wiring to ensure it is not pinched. Make connections to the terminal blocks as labeled. The wiring terminals are labeled.
4. Close the wiring access doors and install the retaining screws.
CAUTION - RISK OF ELECTRIC SHOCK, SO NOT REMOVE COVER. NO USER
SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL.
CAUTION - RISK OF ELECTRIC SHOCK, THIS UPS RECEIVES POWER FROM
MORE THAN ONE SOURCE-DISCONNECTION OF THE AC SOURCES IS REQUIRED
Left Side of POD
CAUTION:
To
circuit provided w
branch circuit overcurrent prote
accordance w
A
reduce the risk of fire, connect o
NSI/N
FPA 70.
ith the Nationa
14-12AWG 8Kgf-cm
ith 15 am
pe res m
l Electric Code
ction
axim
in
um
L
nly to a
Input
N
TO DE-ENERGIZE THIS UNIT BEFORE SERVICING.
CAUTION - FOR USE IN A CONTROLLED ENVIRONMENT. REFER TO MANUAL FOR
ENVIRONMENTAL CONDITION.
Extract screws to remove
wiring access doors
Model No. : MP2-115HW Desc. : Micro Pod
U
C US
Input : 120VAC 12A
L
50/60Hz, 10
LISTED
Ouptut : 120VAC 12A
91N6
50/60Hz, 10
U.P.S. Accessory
MADE IN TAIWAN 612-XXXXX-00
Right Side of POD
m
L
f-c g
N
8K G
Output
W
A
-12 14
Knockouts for Conduit
Input Terminal Block Connections
Output Terminal Block Connections
9
Knockouts for Conduit

APPLY FEED POWER

1. Next attach the POD to the securing brackets (see Figure 7). The POD can be installed to face one of three different directions utiliz­ing the same mounting procedures. Select the direction of mount­ing to accommodate the conduit entry connections.
Figure 7 Attaching POD to securing brackets
2. Make sure the 2U POD rotary switch is in the UTILITY position. Close the branch circuit breaker providing UTILITY input power.
WARNING
!
The 2U POD is now electrically live. The UTILITY lamp (amber) should now be illuminated.
3. Plug the UPS input cord into the receptacle on the front of the 2U POD labeled “CONNECT UPS LINE CORD HERE.”
WARNING
!
The UPS system is now electrically live.
4. Connect the 2U POD UPS output cord (labeled “CONNECT TO UPS OUTPUT RECEPTACLE”) to the output of the UPS system.
10

START EQUIPMENT

1. Turn on all loads hardwired to the output of the POD. The 2U POD now powers your equipment in the UTILITY mode.
2. Turn ON the loads and ensure all are up and operating properly.
3. Start the UPS according to its specific user manual.
4. Verify that the UPS lamp (green) on the 2U POD is illuminated. If so, transfer the rotary switch from UTILITY to UPS. The load is now being supplied with conditioned power through the UPS.
5. Before any operation or procedure, always verify that both the UPS lamp (green) and the UTILITY lamp (amber) are illuminated before changing the status of the rotary switch.
11

INDICATOR LAMPS

Utility

This amber lamp is illuminated when utility power is present. It sig­nals that you may transfer the loads to maintenance bypass (UTILITY mode) operation via the rotary switch. During a utility power outage, this light will be off and the UPS will supply battery back-up power to the connected loads if in UPS position.

UPS Available

This green lamp is illuminated when there is output power available from the UPS. It signals that it is safe to transfer the connected loads from utility power back to UPS output power.
Figure 8 Indicator lamps on 2U Hardwire POD
Green lamp: Output power available from UPS
Amber lamp: Utility power present
Input from UPS Connect to load socket
LOAD
Hardwired connection to LOAD
CAUTION
IF UTILITY LAMP IS ILLUMINATED MAINTENANCE BYPASS POSITION MAY BE SELECTED
SWITCH TO UPS POSITION ONLY WHEN UPS LAMP IS ILLUMINATED
Rotary switch
UPS
AVAILABLE
UPS
UTILITY
Connect UPS input cord here
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
UPS
UTILITY
Hardwired connection from UTILITY
12

OPERATION

Transfer to Maintenance Bypass

To transfer to maintenance bypass (UTILITY) from UPS, follow the following steps:
1. Ensure the Utility lamp (amber lamp) is illuminated. If the lamp is not illuminated, refer to the Troubleshooting section.
2. Transfer the rotary switch from UPS to UTILITY.
3. Turn the UPS off.
4. Disconnect the two cables connecting the UPS to the 2U Hardwire POD.
5. You may now service/remove the UPS.

Transfer to UPS

To transfer to UPS from maintenance bypass (UTILITY), use the fol­lowing steps:
1. Reconnect the UPS to the 2U Hardwire POD. Start the UPS according to the instructions in the UPS user manual.
2. Verify that UPS lamp (green lamp) on the 2U Hardwire POD is illuminated. If so, transfer the rotary bypass switch from UTIL­ITY to UPS. If the lamp does not illuminate, refer to the Trouble- shooting section.
13

TROUBLESHOOTING

Problem Cause Solution
UTILITY lamp (amber) not illuminated.
UPS Available lamp (green) not illuminated.
2U Hardwire POD will not start some / all connected loads.
Utility or UPS circuit protectors trip after resetting.
UTILITY not present.
Utility Branch Circuit Breaker may be open.
2U Hardwire POD input power not connected to UTILITY.
UPS output power not present.
UPS input and/or output cord not connected to 2U Hardwire POD.
Input power cannot support load.
Overcurrent protection on 2U Hardwire POD connected load.
Call qualified service personnel to restore power.
Verify that the branch circuit breaker is closed.
Refer to 2U Hardwire POD installation instructions in this manual:
Installation on GXT 2U UPS and
Rack Mount Installation.
Turn on UPS. Refer to UPS user manual.
Refer to 2U Hardwire POD installation instructions in this manual:
Installation on GXT 2U UPS and
Rack Mount Installation.
Verify that utility and UPS are on, all circuit protectors are closed, and load is within the rating of the power source.
Recalculate load requirements.
14

SPECIFICATIONS

Transfer Time (to and from maintenance bypass)
Operating Ambient Temperature
Storage Ambient Temperature
Dimensions with brackets W x D x H: in. (mm)
Humidity
Agency/Standards
Electrical Rating
< 6 milliseconds
32°F to 104°F (0°C to +40°C)
-4°F to 140°F (-20°C to +60°C)
3.5 x 3.0 x 15.5 (88.0 x 77.0 x 394.0)
0 to 95% non-condensing
UL1778, c-UL, ISTA Procedure 1A
See Model Label on POD
Table 1 Breaker specifications
Model
VA - Vol t
Rating
MP2-115HW 12A 15A 14 AWG 8 AWG 20 in-lb
MP2-120HW 16A 20A 12 AWG 8 AWG 20 in-lb
MP2-130HW 24A 30A 10 AWG 8 AWG 20 in-lb
* See POD Rating Plate for Alternate Output Voltages
Input
Current
Rating
120V*
Recommended
at
(Maximum)
External
Overcurrent
Protection
Recommended Wire (including
ground wire)
(75°C
copper wire)
Maximum
Wire
Accepted
by Terminal
Block
Ter minal
Tightening
Tor que
This POD is intended for use with a UPS meeting all of the following requirements:
• UPS input cord is compatible with the rating and type of receptacle on the POD labeled “CONNECT UPS LINE CORD HERE.”
• UPS output receptacle is compatible with the POD input power con­nector labeled “UPS.”
• Available utility is compatible with the POD input connection and an appropriately sized branch circuit breaker has been provided.

Product Warranty Registration

To register for warranty protection:
•Visit the Quick Links section of our Web site at:
http://www.liebert.com
• Click on Product Warranty Registration and fill in the form.
If you have any questions, please contact us at:
US: 800-222-5877 Outside the US: 614-841-6755
upstech@liebert.com
15
16
POWER AVAILABILITY
2U Hardwire POD™
USER MANUAL
The Company Behind the Products
With over a million installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics:
Environmental systems—close-control air conditioning from 1 to 60 tons
Power conditioning and UPS with power ranges from 300 VA to more than 1000 kVA
Integrated systems that provide both environmental and power protection in a single, flexible package
Monitoring and control—from systems of any size or location, on-site or remote
Service and support through more than 100 service centers around the world and a 24/7 Customer Response Center
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2003 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-23159 (3/03) Rev. 0
Technical Support/ Service
Web Site
www.liebert.com
Monitoring
monitoring@liebert.com
Outside the US: 614-841-6755
Outside the US: 614-841-6755
powertech@liebert.com
Environmental Systems
Outside the United States
800-222-5877
Single-Phase UPS
800-222-5877
upstech@liebert.com
Three-Phase UPS
800-543-2378
800-543-2778
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
+39 049 9719 111
Fax: +39 049 5841 257
23F, Allied Kajima Bldg.
138 Gloucester Road
+852 2 572 2201
Fax: +852 2 831 0114
Italy
Asia
Wanchai
Hong Kong
Loading...