This chapter provides an orientation to the use of this manual. This manual describes the procedures
required to install the following Model 1700 and 2700 transmitters:
•Model 1700 or Model 2700 with analog outputs option board
•Model 1700 or Model 2700 with intrinsically safe analog outputs option board
•Model 2700 with configurable input/outputs option board
•Model 2700 with F
•Model 2700 with PROFIBUS-PA option board
If you do not know what transmitter you have, see Section 1.4 for instructions on identifying the
transmitter type from the model number on the transmitter’s tag.
Note: Installation information for Model 1500 transmitters or Model 2500 transmitters is provided in
a separate manual. See the manual for your transmitter.
OUNDATION fieldbus
™
option board
Installing the TransmitterOutput Wiring – AnalogSensor WiringBefore You Begin
1.2Safety
Safety messages are provided throughout this manual to protect personnel and equipment. Read each
safety message carefully before proceeding to the next step.
Improper installation in a hazardous area can cause an explosion.
For information about hazardous applications, refer to the approval documentation,
shipped with the transmitter or available from the Micro Motion web site.
Hazardous voltage can cause severe injury or death.
Make sure power is disconnected before installing transmitter.
Improper installation could cause measurement error or flowmeter failure.
Follow all instructions to ensure transmitter will operate correctly.
Installation Manual1
Before You Begin
1.3Flowmeter components
The Model 1700 or 2700 transmitter is one component in your Micro Motion flowmeter. Other major
components include:
•The sensor, which provides measurement functions
•The core processor, which provides memory and processing functions
1.4Transmitter type, installation type, and outputs option board
To install the transmitter, you must know your transmitter type, installation type, and outputs option
board. This section provides information on obtaining this information. The codes described below
match the codes that were used to order your transmitter.
1. Obtain the transmitter's model number, which is provided on a tag attached to the side of the
transmitter.
•Model 1700 transmitters have a model number of the form
1700xxxxxxxxxx.
•Model 2700 transmitters have a model number of the form
•C = transmitter with configurable input/outputs option board, customized output
configuration
•D = transmitter with intrinsically safe analog outputs option board
•E = transmitter with intrinsically safe (FISCO compliant) F
option board
•N = transmitter with non-incendive (FNICO compliant) F
option board
•G = transmitter with PROFIBUS-PA outputs option board
2700xxxxxxxxxx.
OUNDATION fieldbus outputs
OUNDATION fieldbus outputs
Note: The remaining characters in the model number describe options that do not affect transmitter
installation.
The following examples illustrate use of the model number to determine transmitter type, installation
type, and output board type:
•
1700RxxAxxxxxx = Model 1700 remote transmitter with analog outputs option board
•
2700CxxDxxxxxx = Model 2700 transmitter/core processor assembly with intrinsically safe
outputs option board
2Micro Motion® Model 1700 and 2700 Transmitters
Before You Begin
1.5Transmitter installation procedures
To install the transmitter, the following procedures are required:
•Install the transmitter – see Chapter 2
•Wire the transmitter to the sensor – see Chapter 3
•Wire the transmitter outputs:
-For Model 1700 or 2700 analog outputs transmitters, see Chapter 4.
-For Model 1700 or 2700 intrinsically safe analog outputs transmitters, see Chapter 5.
-For Model 2700 configurable I/O transmitters, see Chapter 6.
-For Model 2700 F
Chapter 7.
1.6Flowmeter documentation
Table 1-1 lists documentation sources for other required information. Documents can be obtained in
PDF form from the Micro Motion web site (www.micromotion.com/documentation).
Table 1-1Flowmeter documentation resources
TopicDocument
Sensor installationInstallation manual shipped with sensor
Core processor installation (if mounted
remotely from sensor and transmitter)
Transmitter configuration, transmitter
startup and use, and transmitter
troubleshooting
OUNDATION fieldbus and PROFIBUS-PA outputs transmitters, see
This document
Series 1000 and 2000 Transmitter Configuration and
Use Manual
or
Model 2700 Transmitter with F
Installation and Operation Manual
or
Model 2700 Transmitter with PROFIBUS-PA
Installation and Operation Manual
OUNDATION Fieldbus
Installing the TransmitterOutput Wiring – AnalogSensor WiringBefore You Begin
Installation Manual3
Before You Begin
1.7Micro Motion customer service
For technical assistance, phone the Micro Motion Customer Service department:
•In the U.S.A., phone 800-522-MASS (800-522-6277) (toll free)
•In Canada and Latin America, phone +1 303-527-5200 (U.S.A.)
•In Asia:
-In Japan, phone 3 5769-6803
-In other locations, phone +65 6777-8211 (Singapore)
•In Europe:
-In the U.K., phone 0870 240 1978 (toll-free)
-In other locations, phone +31 (0) 318 495 555 (The Netherlands)
Customers outside the U.S.A. can also email Micro Motion customer service at
International.MMISupport@EmersonProcess.com.
4Micro Motion® Model 1700 and 2700 Transmitters
Chapter 2
Installing the Transmitter
2.1Overview
This chapter describes how to install Micro Motion Model 1700 and 2700 transmitters. The following
general steps are required:
•Determine the location of the transmitter and other flowmeter components (see Section 2.3)
•Mount the transmitter (see Section 2.4)
•Mount the core processor, if required (see Section 2.5)
•Ground the flowmeter components (see Section 2.6)
•Supply power to the flowmeter (see Section 2.7)
•Rotate the display, if desired and the transmitter has a display (see Section 2.8)
Installing the TransmitterOutput Wiring – AnalogSensor WiringBefore You Begin
2.2Installation architecture
Your flowmeter installation will match one of the architectures shown in Figure 2-1. Mounting, sensor
wiring, and grounding requirements depend on this architecture. Your installation type should be
consistent with the installation type specified in your transmitter model number (see Section 1.4).
Installation Manual5
Transmitter
Sensor
Junction box
9-wire cable
9-wire remote
Core
processor
4-wire remote
Transmitter
Sensor
Core processor
4-wire cable
Transmitter
Sensor
Core processor
Integral
Remote core processor with
remote transmitter
4-wire cable
9-wire cable
Sensor
Junction box
Transmitter
Core
processor
Installing the Transmitter
Figure 2-1Installation types
6Micro Motion® Model 1700 and 2700 Transmitters
Installing the Transmitter
2.3Determining an appropriate location
To determine an appropriate location for the transmitter, you must consider the environmental
requirements of the transmitter and core processor, hazardous area classification, location of power
source, cable lengths, accessibility for maintenance, and visibility of the display (if the transmitter is
equipped with a display).
2.3.1Environmental requirements
The transmitter’s environmental requirements include temperature, humidity, and vibration.
Temperature limits
Install the transmitter in an environment where ambient temperature is between –40 and +140 °F
(–40 and +60 °C). If possible, install the transmitter in a location that will prevent direct exposure to
sunlight.
Different ambient temperature requirements may apply when installing the transmitter in a hazardous
area. Refer to the approval documentation shipped with the transmitter or available on the Micro
Motion web site.
Humidity limits
Installing the TransmitterOutput Wiring – AnalogSensor WiringBefore You Begin
Install the transmitter in an environment where relative humidity is between 5 and 95%,
non-condensing at 140 °F (60 °C).
Vibration limits
The transmitter meets IEC 68.2.6, endurance sweep, 5 to 2000 Hz, 50 sweep cycles at 1.0 g.
2.3.2Hazardous area classifications
If you plan to mount the transmitter in a hazardous area:
•Verify that the transmitter has the appropriate hazardous area approval. Each transmitter has a
hazardous area approval tag attached to the transmitter housing.
•Ensure that any cable used between the transmitter and the sensor meets the hazardous area
requirements.
For more information about hazardous area classifications and requirements, see Section A.2.
2.3.3Power source
Connect the transmitter to an AC or DC voltage source. The transmitter automatically recognizes the
source voltage.
AC power requirements
If you are using AC power, the following requirements apply:
Note: These requirements assume a single transmitter per cable. Connecting multiple transmitters to
a single cable should be avoided.
If you are using DC power, the following requirements apply:
•18–100 VDC
•6 watts typical, 11 watts maximum
•At startup, the transmitter power source must provide a minimum of 1.5 amps of short-term
current per transmitter.
•Length and conductor diameter of the power cable must be sized to provide 18 VDC minimum
at the power terminals, at a load current of 0.5 amps. To size the cable, refer to Table 2-1 and
use the following formula as a guideline:
Table 2-1Typical power cable resistances at 68 °F (20 °C)
GaugeResistance
14 AWG0.0050 Ω/foot
16 AWG0.0080 Ω/foot
18 AWG0.0128 Ω/foot
20 AWG0.0204 Ω/foot
2,5 mm
1,5 mm
1 mm
0,75 mm
0,5 mm
(1) These values include the resistance of both high and low conductors in a cable.
Example
(1)
2
2
2
2
2
0,0136 Ω/meter
0,0228 Ω/meter
0,0340 Ω/meter
0,0460 Ω/meter
0,0680 Ω/meter
The transmitter is mounted 350 feet from a DC power supply. If you want to use 16 AWG
cable, calculate the required voltage at the DC power supply as follows:
8Micro Motion® Model 1700 and 2700 Transmitters
Installing the Transmitter
CAUTION
2.3.4Maximum cable lengths
This requirement does not apply to integral installations (see Figure 2-1). For other installation types
(see Figure 2-1), maximum cable length between flowmeter components depends on the installation
type and the cable type. Refer to Figure 2-1, then see Table 2-2.
• Signal wires (RS-485)22 AWG (0,35 mm2) or larger1000 feet (300 meters)
2.3.5Accessibility for maintenance
Ensure that the transmitter is mounted in a location and orientation that will allow easy access to the
terminals and to the display (if your transmitter has a display).
2
)300 feet (90 meters)
2
20 AWG (0,5 mm
18 AWG (0,8 mm2)1000 feet (300 meters)
)500 feet (150 meters)
Installing the TransmitterOutput Wiring – AnalogSensor WiringBefore You Begin
2.4Mounting the transmitter
You can mount the transmitter in any orientation as long as the conduit and wiring openings do not
point upward. If possible, mount the transmitter so that there is at least 8–10″ (200–250 mm)
clearance at the rear of the housing to enable operator access to the wiring and power compartments.
For transmitter dimensions, see Appendix A.
Condensation or excessive moisture entering the transmitter could damage
the transmitter and result in measurement error or flowmeter failure.
To reduce the risk of measurement error or flowmeter failure:
• Ensure the integrity of gaskets and O-rings.
• Grease the O-rings every time the transmitter housing or core processor
housing is opened and closed.
• Do not mount the transmitter with the conduit openings pointing upward.
• Install drip legs on conduit or cable.
• Seal the conduit openings.
• Fully tighten the transmitter cover.
Installation Manual9
Installing the Transmitter
CAUTION
Base
Core processor
Transmitter
Sensor
Transition ring
4 X Cap screws (4 mm)
2.4.1Integral installations
If you chose an integral installation (see Figure 2-1), there are no special mounting instructions for the
transmitter.
You can rotate an integrally mounted transmitter up to 360° in 90° increments, to one of four possible
positions on the core processor base. See Figure 2-2.
Figure 2-2Rotating the transmitter
Damaging the wires that connect the transmitter to the core processor can
cause measurement error or flowmeter failure.
To reduce the risk of damaging the wires, do not move the transmitter more than a
few inches from the core processor. When reassembling the flowmeter, ensure that
the wires will not be bent or pinched in the housing.
To rotate the transmitter on the core processor:
1. Loosen each of the four cap screws (4 mm) that fasten the transmitter to the base.
2. Rotate the transmitter counter-clockwise so that the cap screws are in the unlocked position.
3. Gently lift the transmitter straight up, disengaging it from the cap screws. Do not disconnect or
damage the wires that connect the transmitter to the core processor.
4. Rotate the transmitter to the desired orientation, and align the slots with the cap screws. Do not
pinch or stress the wires.
5. Gently lower the transmitter onto the base, inserting the cap screws into the slots.
6. Rotate the transmitter clockwise so that the cap screws are in the locked position.
7. Tighten the cap screws, torquing to 20 to 30 in-lbs (2,3 to 3,4 N-m).
10Micro Motion® Model 1700 and 2700 Transmitters
Installing the Transmitter
CAUTION
Mounting bracket
(wall mount)
Mounting bracket
(pipe mount)
Note: If possible, maintain 8–10″ (200–250 mm) clearance
at the rear of the transmitter.
Twisting the core processor will damage the sensor.
To reduce the risk of damaging the sensor, do not allow the core processor
to rotate.
2.4.24-wire remote or remote core processor with remote transmitter installations
If you chose the 4-wire remote or the remote core processor with remote transmitter installation (see
Figure 2-1), see Figure 2-3 for a diagram of the mounting bracket supplied with the transmitter. Both
pipe mounting and wall mounting are shown. Ensure that the transmitter is mounted and oriented in a
way that will allow easy access to the terminals and to the display (if your transmitter has a display).
Figure 2-34-wire remote – Wall mount or pipe mount
Installing the TransmitterOutput Wiring – AnalogSensor WiringBefore You Begin
To mount the transmitter:
1. Identify the components shown in Figure 2-4. For dimensions, see Appendix A.
2. If desired, re-orient the transmitter on the bracket.
a. Remove the junction end-cap from the junction housing.
b. Loosen each of the four cap screws (4 mm) inside the junction housing.
c. Rotate the bracket so that the transmitter is oriented as desired.
d. Tighten the cap screws, torquing to 30 to 38 in-lbs (3 to 4 N-m).
e. Replace the junction end-cap.
3. Attach the mounting bracket to an instrument pole or wall. For pipe mount, two user-supplied
U-bolts are required. Contact Micro Motion to obtain a pipe-mount installation kit if required.
Installation Manual11
Installing the Transmitter
Ground screw
Mounting bracket
Main enclosure
Junction housing
Mating connector
socket
Mating connector
Junction end-cap
4 X Cap screws
(4 mm)
Conduit opening
for 4-wire cable
Mounting bracket
(wall mount)
Mounting bracket
(pipe mount)
Note: If possible, maintain 8–10″ (200–250 mm) clearance
at the rear of the transmitter.
Figure 2-4Transmitter components – 4-wire remote or remote core processor with
remote transmitter installations
2.4.39-wire remote installations
If you chose a 9-wire remote installation (see Figure 2-1), see Figure 2-5 for a diagram of the
mounting bracket supplied with the transmitter/core processor assembly. Ensure that the transmitter is
mounted and oriented in a way that will allow easy access to the terminals and to the display (if your
transmitter has a display).
Figure 2-59-wire remote – Wall mount or pipe mount
12Micro Motion® Model 1700 and 2700 Transmitters
Installing the Transmitter
End-cap
Mounting bracket
Core processor housing
Transmitter
Core processor
4 × Cap screws (4 mm)
Conduit opening
for 9-wire cable
To mount the transmitter/core processor assembly:
1. Identify the components shown in Figure 2-6. For dimensions, see Appendix A.
2. If desired, re-orient the transmitter on the bracket.
a. Loosen each of the four cap screws (4 mm).
b. Rotate the bracket so that the transmitter is oriented as desired.
c. Tighten the cap screws, torquing to 30 to 38 in-lbs (3 to 4 N-m).
3. Attach the mounting bracket to an instrument pole or wall. For pipe mount, two user-supplied
U-bolts are required. Contact Micro Motion to obtain a pipe-mount installation kit if required.
Installing the TransmitterOutput Wiring – AnalogSensor WiringBefore You Begin
2.5Mounting the remote core processor
Note: This step is required only for remote core processor with remote transmitter installations (see
Figure 2-1). If you have an integral installation, 4-wire remote installation, or 9-wire remote
installation, go to Section 2.6.
If you chose the remote core processor with remote transmitter installation (see Figure 2-1), see
Figure 2-3 for a diagram of the mounting bracket supplied with the transmitter. Both pipe mounting
and wall mounting are shown.
Installation Manual13
Installing the Transmitter
Mounting bracket
(wall mount)
Mounting bracket
(pipe mount)
End-cap
Mounting bracket
Core processor lid
Core processor housing
Conduit opening
for 4-wire cable
Conduit opening
for 9-wire cable
4 × Cap screws (4 mm)
Figure 2-7Remote core processor – Wall mount or pipe mount
To mount the core processor:
1. Identify the components shown in Figure 2-8. For dimensions, see Appendix A.
2. If desired, reorient the core processor housing on the bracket.
a. Loosen each of the four cap screws (4 mm).
b. Rotate the bracket so that the core processor is oriented as desired.
c. Tighten the cap screws, torquing to 30 to 38 in-lbs (3 to 4 N-m).
3. Attach the mounting bracket to an instrument pole or wall. For pipe mount, two user-supplied
U-bolts are required. Contact Micro Motion to obtain a pipe-mount installation kit if required.
Figure 2-8Remote core processor components
14Micro Motion® Model 1700 and 2700 Transmitters
Installing the Transmitter
CAUTION
2.6Grounding the flowmeter components
Grounding requirements depend on the installation type (see Figure 2-1
each flowmeter component are listed in Table 2-3.
Improper grounding could cause measurement error.
To reduce the risk of measurement error:
• Ground the transmitter to earth, or follow ground network requirements for the
facility.
• For installation in an area that requires intrinsic safety, refer to Micro Motion
approval documentation, shipped with the transmitter or available from the Micro
Motion web site.
• For hazardous area installations in Europe, refer to standard EN 60079-14 if
national standards do not apply.
If national standards are not in effect, follow these grounding guidelines:
•Use copper wire, 14 AWG (2,5 mm
). Grounding methods for
2
) or larger wire size, for grounding.
Installing the TransmitterOutput Wiring – AnalogSensor WiringBefore You Begin
•Keep all ground leads as short as possible, less than 1 Ω impedance.
•Connect ground leads directly to earth, or follow plant standards.
Table 2-3Grounding methods for flowmeter components
TransmitterGround according to applicable local standards, using either the
Transmitter / core
processor assembly
SensorSee sensor documentation.
Core processorGround according to applicable local standards, using either the internal
TransmitterGround according to applicable local standards, using either the
Ground via piping, if possible (see sensor documentation). Otherwise,
ground according to applicable local standards using either the
transmitter’s internal or external ground screw.
See sensor documentation.
transmitter’s internal or external ground screw.
Ground according to applicable local standards, using either the
transmitter’s internal or external ground screw, or the core processor’s
internal ground screw.
or external ground screw.
transmitter’s internal or external ground screw.
Installation Manual15
Installing the Transmitter
WARNING
Equipment
ground
9
10
Warning flap
2.7Supplying power
In all installations, power must be provided to the transmitter. Refer to Section 2.3.3 for information
on the transmitter’s power supply requirements.
A user-supplied switch may be installed in the power supply line. For compliance with low-voltage
directive 2006/95/EC (European installations), a switch in close proximity to the transmitter is
required.
Connect the power supply to terminals 9 and 10, under the Warning flap. Terminate the positive (line)
wire on terminal 10 and the return (neutral) wire on terminal 9. Ground the power supply using the
equipment ground, also under the Warning flap. See Figure 2-9.
Figure 2-9Wiring the transmitter power supply
2.8Rotating the display
If your transmitter has a display, you can rotate the display on the transmitter up to 360° in
90° increments.
Removing the display cover in explosive atmospheres while the power is on
can cause an explosion.
To reduce the risk of an explosion, before removing the display cover in explosive
atmospheres, be sure to shut off the power and wait five minutes.
16Micro Motion® Model 1700 and 2700 Transmitters
Installing the Transmitter
WARNING
Using a dry cloth to clean the display cover can cause static discharge,
which could result in an explosion in an explosive atmosphere.
To reduce the risk of an explosion, always use a damp cloth to clean the display
cover in an explosive atmosphere.
To rotate the display, follow the instructions below:
1. Power down the transmitter.
2. Remove the end-cap clamp by removing the cap screw. See Figure 2-10.
3. Turn the display cover counterclockwise to remove it from the main enclosure.
4. Carefully loosen (and remove if necessary) the semicaptive display screws while holding the
display module in place.
5. Carefully pull the display module out of the main enclosure until the sub-bezel pin terminals
are disengaged from the display module.
Note: The display pins may come out of the board stack with the display module. If this happens,
simply remove the pins and reinstall them.
Installing the TransmitterOutput Wiring – AnalogSensor WiringBefore You Begin
6. Rotate the display module to the desired position.
7. Insert the sub-bezel pin terminals into the display module pin holes to secure the display in its
new position.
8. If you have removed the display screws, line them up with the matching holes on the
sub-bezel, then reinsert and tighten them.
9. Place the display cover onto the main enclosure. Turn the display cover clockwise until it is
snug.
10. Replace the end-cap clamp by reinserting and tightening the cap screw.
11. Restore power to the transmitter.
Installation Manual17
Installing the Transmitter
Display cover
Display screws
Display module
Main enclosure
Sub-bezel
Pin terminals
Cap screw
End-cap clamp
Figure 2-10 Display components
18Micro Motion® Model 1700 and 2700 Transmitters
Chapter 3
CAUTION
Wiring the Transmitter to the Sensor
3.1Overview
This chapter describes how to connect Micro Motion Model 1700 and 2700 transmitters to a Micro
Motion sensor.
Note: If you have an integral installation, this step is not required. Continue with wiring the
transmitter outputs (Chapters 4–7).
Wiring requirements between the sensor and transmitter depend on the installation type (see
Figure 2-1
).
•If you have a 4-wire remote transmitter installation, review the information on 4-wire cable in
Section 3.2, then follow the instructions in Section 3.3.
•If you have a 9-wire remote transmitter installation, review the information on 9-wire cable in
Section 3.2, then follow the instructions in Section 3.4.
•If you have a remote core processor with remote transmitter installation, review the
information on both 4-wire and 9-wire cable in Section 3.2, then follow the instructions in
Section 3.5.
Large electromagnetic fields can interfere with flowmeter communication
signals.
Improper installation of cable or conduit can cause measurement error or flowmeter
failure. To reduce the risk of measurement error or flowmeter failure, keep cable or
conduit away from devices such as transformers, motors, and power lines which
produce large electromagnetic fields.
Installing the TransmitterOutput Wiring – AnalogSensor WiringBefore You Begin
3.2Cable types
This section describes the types of 4-wire cable and 9-wire cable that can be used for wiring the
transmitter to the sensor.
Installation Manual19
Wiring the Transmitter to the Sensor
Core processor
terminals
4-wire cable Mating connector
(transmitter)
Maximum cable length: see Table 2-2
VDC+
VDC–
RS-485A
RS-485B
User-supplied or
factory-supplied cable
VDC+ (Red)
VDC– (Black)
RS-485A (white)
RS-485B (Green)
3.2.14-wire cable
Micro Motion offers two types of 4-wire cable: shielded and armored. Both types contain shield
drain wires.
User-supplied 4-wire cable must meet the following requirements:
•Twisted pair construction
•The gauge requirements as described in Table 2-2
•The applicable hazardous area requirements, if the core processor is installed in a hazardous
area (see the approval documentation shipped with the transmitter or available on the Micro
Motion web site)
3.2.29-wire cable
Micro Motion offers three types of 9-wire cable: jacketed, shielded, and armored. Refer to Micro
Motion’s 9-Wire Flowmeter Cable Preparation and Installation Guide for detailed descriptions of
these cable types and for assistance in selecting the appropriate cable for your installation.
3.3Wiring for 4-wire remote installations
To connect the cable, follow the steps below.
1. Prepare the cable as described in the sensor documentation.
2. Connect the cable to the core processor as described in the sensor documentation.
3. To connect the cable to the transmitter:
a. Identify the wires in the 4-wire cable. The 4-wire cable supplied by Micro Motion consists
of one pair of 18 AWG (0,75 mm
VDC connection, and one pair of 22 AWG (0,35 mm
2
) wires (red and black), which should be used for the
2
) wires (green and white), which
should be used for the RS-485 connection.
b. Connect the four wires from the core processor to terminals 1–4 on the mating connector
of the transmitter. See Figures 3-1, 3-2, and 3-3. Never ground the shield, braid, or drain
wire(s) at the transmitter.
Figure 3-14-wire cable between enhanced core processor and transmitter
Figure 3-24-wire cable between standard core processor and transmitter
Figure 3-3Wiring to the mating connector
Installing the TransmitterOutput Wiring – AnalogSensor WiringBefore You Begin
Installation Manual21
Wiring the Transmitter to the Sensor
CAUTION
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Ye l l o w
Black
(Drains from all
wire sets)
Plug and
socket
Mounting screw
Blue
Gray
Orange
Red
Green
White
Brown
Violet
Yellow
Ground screw
Black
9-wire cable from sensorCore processor (on transmitter)
3.4Wiring for 9-wire remote installations
If you chose a 9-wire remote installation (see Figure 2-1), a 9-wire cable must be used to connect the
junction box on the sensor to the core processor on the transmitter/core processor assembly.
Allowing the shield drain wires to contact the sensor junction box can cause
flowmeter errors.
Do not allow the shield drain wires to contact the sensor junction box.
To connect the cable, follow the steps below:
1. Refer to Micro Motion’s 9-Wire Flowmeter Cable Preparation and Installation Guide for
instructions on cable shielding and preparation:
•At the sensor end, follow the instructions for your cable type.
•At the transmitter end, follow the instructions for your cable type with an MVD
transmitter.
2. To connect the wires, refer to Micro Motion’s 9-Wire Flowmeter Cable Preparation and Installation Guide and follow the instructions for your sensor with an MVD transmitter.
Additional information for connecting the wires at the transmitter is provided below:
a. Identify the components shown in Figure 2-6.
b. Remove the end-cap.
c. Insert the 9-wire cable through the conduit opening.
d. Connect the wires to the plugs supplied with the transmitter.
e. Insert the plugs into the sockets inside the lower conduit ring. See Figure 3-4.
Figure 3-49-wire cable between sensor and core processor (on transmitter)
3. Ground the cable.
22Micro Motion® Model 1700 and 2700 Transmitters
Wiring the Transmitter to the Sensor
CAUTION
If using jacketed cable:
a. Ground the shield drain wires (the black wire) only on the core processor end, by
connecting it to the ground screw inside the lower conduit ring. Never ground to the core
processor’s mounting screw. Never ground the shield drain wires at the sensor junction
box.
If using shielded or armored cable:
a. Ground the shield drain wires (the black wire) only on the core processor end, by
connecting it to the ground screw inside the lower conduit ring. Never ground to the core
processor’s mounting screw. Never ground the shield drain wires at the sensor junction
box.
b. Ground the cable braid on both ends, by terminating it inside the cable glands.
4. Ensure integrity of gaskets, grease all O-rings, then close the junction box housing and core
processor end-cap, and tighten all screws.
Damaging the wires that connect the transmitter to the sensor can cause
measurement error or flowmeter failure.
Installing the TransmitterOutput Wiring – AnalogSensor WiringBefore You Begin
To reduce the risk of measurement error or flowmeter failure, when closing the
housings on the sensor and core processor, make sure that the wires are not
caught or pinched.
3.5Wiring for remote core processor with remote transmitter installations
This task includes two subtasks:
•Subtask 1: Wiring the remote core processor to the transmitter (4-wire cable)
•Subtask 2: Wiring the sensor to the remote core processor (9-wire cable)
Subtask 1: Wire the remote core processor to the transmitter
1. Use one of the following methods to shield the wiring from the core processor to the
transmitter:
•If you are installing unshielded wiring in continuous metallic conduit that provides
360° termination shielding for the enclosed wiring, go to Subtask 1, Step 6.
•If you are installing a user-supplied cable gland with shielded cable or armored cable,
terminate the shields in the cable gland. Terminate both the armored braid and the shield
drain wires in the cable gland. Go to Subtask 1, Step 6.
•If you are installing a Micro Motion-supplied cable gland at the core processor housing:
-Refer to Figure 3-5 to identify the cable gland to use for the 4-wire cable conduit
opening.
-Prepare the cable and apply shielded heat shrink to the cable (see Figure 3-6). The
shielded heat shrink provides a shield termination suitable for use in the gland when
using cable whose shield consists of foil and not a braid. Proceed to Subtask 1, Step 2.
-With armored cable, where the shield consists of braid, prepare the cable as described
below, but do not apply heat shrink. Proceed to Subtask 1, Step 2.
Installation Manual23
Wiring the Transmitter to the Sensor
Cable gland
• Used with 4-wire conduit
opening
Cable gland
•3/4″–14 NPT
• Used with 9-wire conduit opening
Cable glands
•1/2″–14 NPT or M20 × 1.5
• Used with transmitter
4 1/2 in
(114 mm)
3/4 in
(19 mm)
7/8 in
(22 mm)
7/8 in
(22 mm)
Shielded heat shrink
Gland body
Gland nut
Gland clamping insert
Figure 3-5Cable glands
2. Remove the cover from the core processor housing.
3. Slide the gland nut and the clamping insert over the cable.
Figure 3-6Micro Motion cable gland and heat shrink
4. For connection at the core processor housing, prepare shielded cable as follows (for armored
cable, omit steps d, e, f, and g):
a. Strip 4 1/2 inches (114 mm) of cable jacket.
b. Remove the clear wrap that is inside the cable jacket, and remove the filler material
between the wires.
c. Remove the foil shield or braid and drain wires from the insulated wires, leaving 3/4 inch
(19 mm) of foil or braid exposed, and separate the wires.
d. Wrap the shield drain wire(s) around the exposed foil twice. Cut off the excess wire. See
Figure 3-7.
24Micro Motion® Model 1700 and 2700 Transmitters
Wiring the Transmitter to the Sensor
Figure 3-7Wrapping the shield drain wires
e. Place the shielded heat shrink over the exposed shield drain wire(s). The tubing should
completely cover the drain wires. See Figure 3-8.
f.Without burning the cable, apply heat (250 °F or 120 °C) to shrink the tubing.
Figure 3-8Applying the heat shrink
Installing the TransmitterOutput Wiring – AnalogSensor WiringBefore You Begin
g. Position gland clamping insert so the interior end is flush with the heat shrink.
h. Fold the cloth shield or braid and drain wires over the clamping insert and approximately
1/8 inch (3 mm) past the O-ring. See Figure 3-9.
Figure 3-9Folding the cloth shield
i.Install the gland body into the core processor housing conduit opening. See Figure 3-10.
Installation Manual25
Wiring the Transmitter to the Sensor
CAUTION
Power supply +
(Red wire)
Power supply –
(Black wire)
RS-485A
(White wire)
RS-485B
(Green wire)
Core processor housing internal ground screw
• For connections to earth ground (if core processor cannot be grounded via sensor
piping and local codes require ground connections to be made internally)
• Do not connect shield drain wires to this terminal
Figure 3-10 Gland body and core processor housing
5. Insert the wires through the gland body and assemble the gland by tightening the gland nut.
6. Identify the wires in the 4-wire cable. The 4-wire cable supplied by Micro Motion consists of
one pair of 18 AWG (0,75 mm
2
) wires (red and black), which should be used for the VDC
connection, and one pair of 22 AWG (0,35 mm
used for the RS-485 connection. Connect the four wires to the numbered slots on the core
processor, matching corresponding numbered terminals on the transmitter. See Figure 3-11.
Figure 3-11 Connecting the wires at the core processor
2
) wires (green and white), which should be
7. Reinstall and tighten the core processor housing cover.
26Micro Motion® Model 1700 and 2700 Transmitters
Twisting the core processor will damage the equipment.
Do not twist the core processor.
Wiring the Transmitter to the Sensor
CAUTION
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Ye l l o w
Black
(Drains from all
wire sets)
Plug and
socket
Mounting screw
Blue
Gray
Orange
Red
Green
White
Brown
Violet
Yellow
Ground screw
Black
9-wire cable from sensorCore processor
8. At the transmitter, connect the four wires from the core processor to terminals 1–4 on the
mating connector of the transmitter. See Figure 3-2. Never ground the shield, braid, or shield
drain wire(s) at the transmitter. Refer to Figure 2-4.
Subtask 2: Wiring the sensor to the remote core processor
Allowing the shield drain wires to contact the sensor junction box can cause
flowmeter errors.
Do not allow the shield drain wires to contact the sensor junction box.
1. Refer to Micro Motion’s 9-Wire Flowmeter Cable Preparation and Installation Guide for
instructions on cable shielding and preparation:
•At the sensor end, follow the instructions for your cable type.
•At the core processor end, follow the instructions for your cable type with an MVD
transmitter.
2. To connect the wires, refer to Micro Motion’s 9-Wire Flowmeter Cable Preparation and Installation Guide and follow the instructions for your sensor with an MVD transmitter.
Additional information for connecting the wires at the core processor is provided below:
a. Identify the components shown in Figure 2-8.
b. Remove the end-cap.
c. Insert the 9-wire cable through the conduit opening.
d. Connect the wires to the plugs supplied with the core processor.
e. Insert the plugs into the sockets inside the lower conduit ring. See Figure 3-12.
Figure 3-12 9-wire cable between sensor and core processor
Installing the TransmitterOutput Wiring – AnalogSensor WiringBefore You Begin
3. Ground the cable.
Installation Manual27
Wiring the Transmitter to the Sensor
CAUTION
If using jacketed cable:
a. Ground the shield drain wires (the black wire) only on the core processor end, by
connecting it to the ground screw inside the lower conduit ring. Never ground to the core
processor’s mounting screw. Never ground the cable at the sensor junction box.
If using shielded or armored cable:
a. Ground the shield drain wires (the black wire) only on the core processor end, by
connecting it to the ground screw inside the lower conduit ring. Never ground to the core
processor’s mounting screw. Never ground the cable at the sensor junction box.
b. Ground the cable braid on both ends, by terminating it inside the cable glands.
4. Ensure integrity of gaskets, grease all O-rings, then close the junction box housing and core
processor end-cap, and tighten all screws.
Damaging the wires that connect the transmitter to the sensor can cause
measurement error or flowmeter failure.
To reduce the risk of measurement error or flowmeter failure, when closing the
housings on the sensor and core processor, make sure that the wires are not
caught or pinched.
28Micro Motion® Model 1700 and 2700 Transmitters
Chapter 4
Output Wiring – Model 1700/2700
Analog Transmitters
4.1Overview
This chapter explains how to wire outputs for Model 1700 or 2700 transmitters with the analog
outputs option board (output option code A).
Note: If you do not know what outputs option board is in your transmitter, see Section 1.4.
It is the user’s responsibility to verify that the specific installation meets the local and national safety
requirements and electrical codes.
4.2Output terminals and output types
Table 4-1 describes the outputs and communication protocols available for the Model 1700 or 2700
analog transmitter.
Installing the TransmitterOutput Wiring – AnalogSensor WiringBefore You Begin
(1) The Bell 202 signal is superimposed on the mA output.
4.3Output wiring
Output wiring requirements depend on how you will use the analog functionality and the HART or
Modbus protocol. This chapter describes several possible configurations:
•Figure 4-1 shows the wiring requirements for the mA output (terminals 1 and 2) and the
frequency output (terminals 3 and 4).
•Figure 4-2 shows the wiring requirements for the mA output (terminals 1 and 2) if it will be
used for HART communications in addition to the mA signal.
•Figure 4-3 shows the wiring requirements for RS-485 communications using the RS-485
output (terminals 5 and 6).
•Figure 4-4 shows the wiring requirements for connecting the transmitter to a HART multidrop
network.
(1)
Milliamp/Bell 202
• Discrete
(1)
HART
None
• Modbus
Installation Manual29
Output Wiring – Model 1700/2700 Analog Transmitters
+
–
mA output loop
820 Ω maximum loop resistance
Frequency receiving device
+
–
00042
Output voltage level is +24 VDC ± 3%
Note: If you will configure the transmitter to poll an external temperature or pressure device, you
must wire the mA output to support HART communications. You may use either HART/analog
single-loop wiring or HART multidrop wiring.
It is the user’s responsibility to verify that the specific installation meets the local and national safety
requirements and electrical codes.
Figure 4-1Basic analog wiring
30Micro Motion® Model 1700 and 2700 Transmitters
Output Wiring – Model 1700/2700 Analog Transmitters
820 Ω maximum loop resistance
For HART communications:
• 600 Ω maximum loop resistance
• 250 Ω minimum loop resistance
+
–
HART-
compatible host
or controller
Note: The RS-485 communication wires must be shielded.
Other devices
RS-485A
RS-485B
Primary
controller
Multiplexer
Figure 4-2HART/analog single-loop wiring
Installing the TransmitterOutput Wiring – AnalogSensor WiringBefore You BeginInstalling the TransmitterOutput Wiring – AnalogSensor WiringBefore You BeginInstalling the TransmitterOutput Wiring – AnalogSensor WiringBefore You BeginInstalling the TransmitterOutput Wiring – AnalogSensor WiringBefore You Begin
Figure 4-3RS-485 point-to-point wiring
Installation Manual31
Output Wiring – Model 1700/2700 Analog Transmitters
HART-compatible
host or controller
HART-compatible
transmitters
SMART FAMILY
™
transmitters
Note: For optimum HART communication, make sure the output
loop is single-point-grounded to an instrument-grade ground.
24 VDC loop power
supply required for
passive transmitters
600 Ω maximum resistance
250 Ω minimum resistance
Model 1700 or 2700
analog transmitter
Figure 4-4HART multidrop wiring with SMART FAMILY™ transmitters and a configuration tool
32Micro Motion® Model 1700 and 2700 Transmitters
Chapter 5
Output Wiring – Model 1700/2700 Intrinsically
Safe Transmitters
5.1Overview
This chapter explains how to wire outputs for Model 1700 or 2700 transmitters with the intrinsically
safe outputs option board (output option code D).
Note: If you do not know what outputs option board is in your transmitter, see Section 1.4.
Intrinsically safe outputs require external power. “External power” means that the terminals must be
connected to an independent power supply. The output wiring instructions include power setup and
power wiring.
Note: The term “passive” is sometimes used to describe externally powered outputs.
Output wiring requirements depend on whether the transmitter will be installed in a safe area or a
hazardous area. This chapter describes several possible configurations:
•Section 5.3 describes wiring requirements for the outputs if the transmitter will be installed in
a safe area.
•Section 5.4 describes wiring requirements for the outputs if the transmitter will be installed in
a hazardous area.
It is the user’s responsibility to verify that the specific installation meets the local and national safety
requirements and electrical codes.
5.2Output terminals and output types
Table 5-1 describes the outputs and communication protocols available for the Model 1700 or 2700
intrinsically safe transmitter.
(1) The Bell 202 signal is superimposed on the mA output.
Note: If you will configure the transmitter to poll an external temperature or pressure device, you
must wire the mA output to support HART communications. You may use either HART/analog
single-loop wiring or HART multidrop wiring.
Installation Manual33
(1)
Milliamp/Bell 202
• Discrete
(1)
HART
None
Output Wiring – Model 1700/2700 Intrinsically Safe Transmitters
Note: See Figure 5-2 for voltage and resistance values.
VDC
VDC
R
load
R
load
+
–
+
–
+
–
+
–
mA1
mA2
5.3Safe area output wiring
The following notes and diagrams are designed to be used as a guide for wiring the Model 1700 or
Model 2700 outputs for safe area applications.
5.3.1Safe area mA output wiring
The following 4–20 mA wiring diagrams are examples of proper basic wiring for the Model 1700 mA
output or Model 2700 primary and secondary mA outputs.
Note: This diagram shows the Model 2700, which has a secondary mA output. If you are using the
Model 1700, the secondary mA output does not exist.
Figure 5-1Safe area basic mA output wiring
34Micro Motion® Model 1700 and 2700 Transmitters
Output Wiring – Model 1700/2700 Intrinsically Safe Transmitters
0
100
200
300
400
500
600
700
800
900
1000
12141618202224262830
R
max
= (V
supply
– 12)/0.023
If communicating with HART, a minimum of 250 Ω and 17.5 V is required
Supply voltage VDC (Volts)
External resistor R
load
(Ohms)
OPERATING REGION
Note: See Figure 5-2 for voltage and resistance values.
VDC
R
load
(250–600 Ω
resistance)
+
–
+
–
HART-
compatible host
or controller
mA1
Figure 5-2Safe area mA output load resistance values
Figure 5-3Safe area HART/analog single-loop wiring
Installation Manual35
Output Wiring – Model 1700/2700 Intrinsically Safe Transmitters
HART-compatible
host or controller
HART-compatible
transmitters
SMART FAMILY™
transmitter
Note: For optimum HART communication, make sure the output loop
is single-point-grounded to an instrument-grade ground.
24 VDC loop power
supply required for
HART 4–20 mA
passive transmitters
600 Ω maximum resistance
250 Ω minimum resistance
Model 1700 or 2700
I.S. transmitter
+
–
Note: See Figure 5-6 for voltage and resistance values.
Counter
VDC
R
load
+
–
+
–
00042
Figure 5-4Safe area HART multidrop wiring with SMART FAMILY™ transmitters and a configuration tool
5.3.2Safe area frequency/discrete output wiring
The following frequency/discrete output wiring diagram is an example of proper basic wiring for the
Model 1700 transmitter’s frequency output or the Model 2700 transmitter’s frequency/discrete output.
Figure 5-5Safe area frequency/discrete output wiring
36Micro Motion® Model 1700 and 2700 Transmitters
Output Wiring – Model 1700/2700 Intrinsically Safe Transmitters
WARNING
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
57911131517192123252729
R
max
= (V
supply
– 4)/0.003
R
min
= (V
supply
– 25)/0.006
Absolute minimum = 100 ohms for supply voltage less than 25.6 Volts
Supply voltage VDC (Volts)
External pull-up resistor R
load
range (Ohms)
OPERATING REGION
Figure 5-6Safe area frequency/discrete output load resistance values
The following notes and diagrams are designed to be used as a guide for wiring the Model 1700 or
Model 2700 outputs for hazardous area applications.
5.4.1Hazardous area safety parameters
The proper barrier selection will depend on what output is desired, which approval is applicable, and
many installation-specific parameters. The information that is provided about I.S. barrier selection is
intended as an overview. Refer to barrier manufacturers for more detailed information regarding the
use of their products. Application-specific questions should be addressed to the barrier manufacturer
or to Micro Motion.
Hazardous voltage can cause severe injury or death.
To reduce the risk of hazardous voltage, shut off the power before wiring the
transmitter outputs.
Installation Manual37
Output Wiring – Model 1700/2700 Intrinsically Safe Transmitters
WARNING
A transmitter that has been improperly wired or installed in a hazardous area
could cause an explosion.
To reduce the risk of an explosion:
• Make sure the transmitter is wired to meet or exceed local code requirements.
• Install the transmitter in an environment that complies with the classification tag
on the transmitter. See Appendix A.
Table 5-2Safety parameters
Parameter4–20 mA outputFrequency/discrete output
Voltage (Ui)30 V30 V
Current (I
Power (Pi)1.0 W0.75 W
Capacitance (Ci)0.0005 μF0.0005 μF
Inductance (L
)300 mA100 mA
i
)0.0 mH0.0 mH
i
Val ue
Hazardous area voltage
The Model 1700 or 2700 transmitter’s safety parameters require the selected barrier’s open-circuit
voltage to be limited to less than 30 VDC (Vmax = 30 VDC). This voltage is the combination of the
maximum safety barrier voltage (typically 28 VDC) plus an additional 2 VDC for HART
communications when communicating in the hazardous area.
Hazardous area current
The Model 1700 or 2700 transmitter’s safety parameters require the selected barrier’s short-circuit
currents to sum to less than 300 mA (Imax = 300 mA) for the milliamp outputs and 100 mA
(Imax = 100 mA) for the frequency/discrete output.
Hazardous area capacitance
The capacitance (Ci) of the Model 1700 or 2700 transmitter is 0.0005 μF. This value added to the
wire capacitance (Ccable) must be lower than the maximum allowable capacitance (Ca) specified by
the I.S. barrier. Use the following equation to calculate the maximum length of the cable between the
transmitter and the barrier:
Ci + Ccable ≤ Ca
Hazardous area inductance
The inductance (Li) of the Model 1700 or 2700 transmitter is 0.0 mH. This value plus the field wiring
inductance (Lcable), must be lower than the maximum allowable inductance (La) specified by the I.S.
barrier. The following equation can then be used to calculate the maximum cable length between the
transmitter and the barrier:
Li + Lcable ≤ La
38Micro Motion® Model 1700 and 2700 Transmitters
Output Wiring – Model 1700/2700 Intrinsically Safe Transmitters
Note: R
barrier
and R
load
should be added together to
determine the proper V
in
. Refer to Figure 5-2.
V
out
Hazardous areaSafe area
V
in
Ground
R
load
4-20 mA
R
barrier
5.4.2Hazardous area mA output wiring
Figure 5-7 provides an example of basic hazardous area wiring for the Model 1700 transmitter’s mA
output or the Model 2700 transmitter’s primary mA output.
5.4.3Hazardous area frequency/discrete output wiring
The following frequency/discrete output wiring diagrams are examples of proper hazardous area
wiring for the Model 1700 transmitter’s frequency output or the Model 2700 transmitter’s
frequency/discrete output:
•The diagram in Figure 5-8 utilizes a galvanic isolator that has an internal 1000 Ω resistor used
for sensing current:
-ON > 2.1 mA
-OFF < 1.2 mA
•The diagram in Figure 5-9 utilizes a barrier with external load resistance.
Installation Manual39
Output Wiring – Model 1700/2700 Intrinsically Safe Transmitters
External power supply
R
load
V
out
Galvanic isolator
Hazardous areaSafe area
COUNTER
Note: R
barrier
and R
load
should be added together to
determine the proper V
in
. Refer to Figure 5-6.
Hazardous areaSafe area
Ground
V
out
V
in
R
barrier
R
load
COUNTER
Figure 5-8Hazardous area frequency/discrete output wiring using galvanic isolator
Figure 5-9Hazardous area frequency/discrete output wiring using barrier with external load resistance
40Micro Motion® Model 1700 and 2700 Transmitters
Chapter 6
Output Wiring – Model 2700 Configurable I/O
Transmitters
6.1Overview
This chapter explains how to wire outputs for Model 2700 transmitters with the configurable
input/outputs board (output option code B or C).
Note: If you don’t know what outputs option board is in your transmitter, see Section 1.4.
Output wiring requirements depend on how you will configure the transmitter terminals. The
configuration options are shown in Table 6-1 and Figure 6-1.
If Channel B is configured as a frequency output or discrete output, it can also be configured to use
either internal or external power. Channel C can be configured to use either internal or external power,
independent of its output configuration.
•“Internal power” means that the terminals are powered automatically by the transmitter. The
output wiring instructions do not include power setup and power wiring.
•“External power” means that the terminals must be connected to an independent power supply.
The output wiring instructions include power setup and power wiring.
Note: The terms “active” and “passive” are sometimes used to describe internally and externally
powered outputs.
It is the user’s responsibility to verify that the specific installation meets the local and national safety
requirements and electrical codes.
6.2Channel configuration
The six terminals are divided into three pairs, and called Channels A, B, and C. Channel A is
terminals 1 and 2; Channel B is terminals 3 and 4; and Channel C is terminals 5 and 6. Variable
assignments are governed by channel configuration. Table 6-1 and Figure 6-1 show how each channel
may be configured, and the power options for each channel.
You can use a HART Communicator or ProLink II software to configure channels. To configure
channels, see the manual entitled Series 1000 and 2000 Transmitters Configuration and Use Manual.
Note: You cannot configure the following combination: Channel B = discrete output, Channel
C = frequency output. If you need both a frequency output and a discrete output, use the following:
Channel B = frequency output, Channel C = discrete output. For more information, see the manual
entitled Series 1000 and 2000 Transmitters Configuration and Use Manual.
Installation Manual41
Output Wiring – Model 2700 Configurable I/O Transmitters
Terminals 1 and 2 (Channel A)
mA1 output
Internal power only
HART (Bell 202) communications
Terminals 3 and 4 (Channel B)
mA2 output or FO or DO1
Power:
• mA – internal only
• FO or DO – internal or external
No communications
Terminals 5 and 6 (Channel C)
FO or DO2 or DI
Power: internal or external
No communications
mA = milliamp
FO = frequency output
DO = discrete output
DI = discrete input
+
–
+
–
+
–
Table 6-1Channel configuration
ChannelTerminalsConfiguration optionsPower
A1 & 2mA output with HART/Bell 202
B3 & 4• mA output (default)Internal
• Frequency outputInternal or external
• Discrete outputInternal or external
C5 & 6• Frequency output (default)
• Discrete outputInternal or external
• Discrete inputInternal or external
(1) The Bell 202 signal is superimposed on the mA output.
(2) You must provide power to the outputs when a channel is set to external power.
(3) When configured for two frequency outputs (dual pulse), frequency output 2 is generated from the same signal that is sent
to the first frequency output. Frequency output 2 is electrically isolated but not independent.
Figure 6-1Configuration of configurable I/O terminals
(1)
(3)
Internal
(2)
Internal or external
6.3mA output wiring
The following 4–20 mA wiring diagrams are examples of proper basic wiring for the Model 2700
primary and secondary mA outputs. The following options are shown:
•Basic mA wiring (Figure 6-2)
•HART/analog single-loop wiring (Figure 6-3)
•HART multidrop wiring (Figure 6-4)
Note: If you will configure the transmitter to poll an external temperature or pressure device, you
must wire the mA output to support HART communications. You may use either HART/analog
42Micro Motion® Model 1700 and 2700 Transmitters
single-loop wiring or HART multidrop wiring.
Output Wiring – Model 2700 Configurable I/O Transmitters
Output Wiring – Model 2700 Configurable I/O Transmitters
HART-compatible
host or controller
HART-compatible
transmitters
SMART FAMILY™
transmitters
Note: For optimum HART communication,
make sure the output loop is
single-point-grounded to an
instrument-grade ground.
24 VDC loop power
supply required for
HART 4–20 mA
passive transmitters
Model 2700
configurable I/O
transmitter
(internally powered
outputs)
600 Ω maximum resistance
250 Ω minimum resistance
Figure 6-4HART multidrop wiring with SMART FAMILY™ transmitters and a configuration tool
6.4Frequency output wiring
Frequency output wiring depends on whether you are wiring terminals 3 and 4 (Channel B) or
terminals 5 and 6 (Channel C), and also on whether you have configured the terminals for internal or
external power. The following diagrams are examples of proper wiring for these configurations:
•Channel B, internal power – Figure 6-5
•Channel B, external power – Figure 6-6
•Channel C, internal power – Figure 6-7
•Channel C, external power – Figure 6-8
Note: If both Channel B and Channel C are configured for frequency output, the Channel C signal is
generated from the Channel B signal, with a user-specified phase shift. The signals are electrically
isolated but not independent. This configuration is used to support dual-pulse and quadrature modes.
For more information, see the manual entitled Series 1000 and 2000 Transmitters Configuration and Use Manual.
44Micro Motion® Model 1700 and 2700 Transmitters
Output Wiring – Model 2700 Configurable I/O Transmitters
Note: See Figure 6-13 for output voltage versus load resistance.
Counter
+
–
Output voltage level is +15 VDC ± 3%
00042
Note: See Figure 6-15 for recommended resistor versus supply voltage.
CAUTION
Excessive current will damage the transmitter.
Do not exceed 30 VDC input. Terminal current must be less than 500 mA.
Counter
Pull-up
resistor
3–30 VDC
+
–
+
–
000042
Figure 6-5Frequency output – Terminals 3 & 4 (Channel B) – Internal power
Figure 6-6Frequency output – Terminals 3 & 4 (Channel B) – External power
Installation Manual45
Output Wiring – Model 2700 Configurable I/O Transmitters
Output voltage level is +15 VDC ± 3%
Note: See Figure 6-14 for output voltage versus load resistance.
Counter
+
–
00042
Counter
Pull-up
resistor
3–30 VDC
+
–
Note: Refer to Figure 6-15 for
recommended resistor versus supply
voltage.
CAUTION
Excessive current will damage the transmitter.
Do not exceed 30 VDC input. Terminal current must be less than 500 mA.
+
–
000042
Figure 6-7Frequency output – Terminals 5 & 6 (Channel C) – Internal power
Figure 6-8Frequency output – Terminals 5 & 6 (Channel C) – External power
46Micro Motion® Model 1700 and 2700 Transmitters
Output Wiring – Model 2700 Configurable I/O Transmitters
Total load
Note: See Figure 6-13 for output
voltage versus load information.
+
–
3–30 VDC
Note: See Figure 6-15 for recommended
resistor versus supply voltage.
CAUTION
Excessive current will damage the transmitter.
Do not exceed 30 VDC input. Terminal current must be less than 500 mA.
+
–
+
–
Pull-up resistor or DC relay
6.5Discrete output wiring
Discrete output (DO) wiring depends on whether you are wiring terminals 3 and 4 (Channel B) or
terminals 5 and 6 (Channel C), and also on whether you have configured the terminals for internal or
external power. The following diagrams are examples of proper wiring for these configurations:
•Channel B, internal power – Figure 6-9
•Channel B, external power – Figure 6-10
•Channel C, internal power – Figure 6-11
•Channel C, external power – Figure 6-12
Figure 6-9Discrete output 1 – Terminals 3 & 4 (Channel B) – Internal power
Note: When using a discrete output to drive a relay, choose
external pull-up to limit current to less than 500 mA.
Figure 6-15 Recommended pull-up resistor versus supply voltage – External power
6.6Discrete input wiring
Discrete input wiring depends on whether you have configured terminals 5 and 6 (Channel C) for
internal or external power. The following diagrams are examples of proper wiring for these
configurations.
If external power is configured, power may be supplied by a PLC or other device, or by direct DC
input. See Table 6-2 for input voltage ranges.
Table 6-2Input voltage ranges for external power
VDCRange
3–30High level
0–0.8Low level
0.8–3Undefined
50Micro Motion® Model 1700 and 2700 Transmitters
Output Wiring – Model 2700 Configurable I/O Transmitters
+
–
Switch
PLC or
other device
ORVDC
(see Table 6-2)
Direct DC input
(see Table 6-2)
+
–
+
–
Figure 6-16 Discrete input – Terminals 5 & 6 (Channel C) – Internal power
Figure 6-17 Discrete input – Terminals 5 & 6 (Channel C) – External power
Installation Manual51
52Micro Motion® Model 1700 and 2700 Transmitters
Chapter 7
Fieldbus
power
supply
F
OUNDATION fieldbus per FOUNDATION
fieldbus wiring specification
Spur to fieldbus per
F
OUNDATION fieldbus
wiring specification
Terminals 3–6
Terminals 1–2
{
Note: Terminals 3 through 6 are not used.
Note: The fieldbus communication terminals (1 and 2) are polarity insensitive.
Output Wiring – Model 2700 FOUNDATION fieldbus
and PROFIBUS-PA Transmitters
7.1Overview
This chapter explains how to wire outputs for Model 2700 transmitters with the F
and PROFIBUS-PA output boards (output option code E, N, or G).
Note: If you don’t know what outputs option board is in your transmitter, see Section 1.4.
It is the user’s responsibility to verify that the specific installation meets the local and national safety
requirements and electrical codes.
7.2F
OUNDATION fieldbus wiring
Wire the transmitter to the fieldbus segment according to the diagram in Figure 7-1. Follow all local
safety regulations. The transmitter is either FISCO or FNICO approved (see Section A.1.1). For
FISCO-approved transmitters, a barrier is required. Refer to the F
specification.
Figure 7-1Connecting the fieldbus communication wires
Output Wiring – Model 2700 FOUNDATIONFIELDBUS and PROFIBUS-PA Transmitters
Bus
power
supply
PROFIBUS-PA segment per
PROFIBUS-PA User and Installation
Guideline published by PNO
Spur to PROFIBUS-PA segment
per PROFIBUS-PA User and
Installation Guideline published
by PNO
Terminals 3–6
Terminals 1–2
{
Note: Terminals 3 through 6 are not used.
Note: The PROFIBUS communication terminals (1 and 2) are polarity
insensitive.
Note: If you want intrinsically safe wiring, see the PROFIBUS-PA User and Installation Guide published by PNO.
7.3PROFIBUS-PA wiring
Wire the transmitter to the PROFIBUS-PA segment according to the diagram in Figure 7-2. Follow all
local safety regulations. The transmitter is FISCO approved — see Section A.1.1.
Figure 7-2Connecting the PROFIBUS-PA communication wires
54Micro Motion® Model 1700 and 2700 Transmitters
Appendix A
Specifications
A.1Functional specifications
The Model 1700 or 2700 transmitter’s functional specifications include:
The transmitter has two (Model 1700) or three (Model 2700) pairs of wiring terminals for
transmitter outputs.
•The Model 1700/2700 with analog outputs option board has one pair of wiring terminals for
digital communications (Modbus or HART protocol on RS-485)
•On the Model 2700 with F
Screw terminals accept one or two solid conductors, 14 to 12 AWG (2,5 to 4,0 mm
stranded conductors, 22 to 14 AWG (0,34 to 2,5 mm
Power connection
The transmitter has two pairs of wiring terminals for the power connection:
•One pair of wiring terminals accepts AC or DC power
•One internal ground lug for power-supply ground wiring
Screw terminals accept one or two solid conductors, 14 to 12 AWG (2,5 to 4,0 mm
stranded conductors, 22 to 14 AWG (0,34 to 2,5 mm
Service port connection
The transmitter has two clips for temporary connection to the service port.
OUNDATION fieldbus or PROFIBUS-PA, terminals 3–6 are not used.
2
2
).
2
).
), or one or two
2
), or one or two
Installation Manual55
Specifications
Core processor connection
The transmitter has two pairs of wiring terminals for the 4-wire connection to the core processor:
Plug connectors accept stranded or solid conductors, 24 to 12 AWG (0,2 to 2,5 mm
FISCO and FNICO approval
•One pair is used for the RS-485 connection
•One pair is used to supply power to the core processor
2
).
Model 2700 transmitters with F
OUNDATION fieldbus and PROFIBUS-PA are either FISCO or FNICO
approved depending on their output code:
•Transmitters with output code E (intrinsically safe F
OUNDATION fieldbus) or output code G
(PROFIBUS-PA) are FISCO approved with the following entity parameters:
-Ui = 30 V
-Ii = 380 mA
-Pi = 5.32 W
-Ci = 0.0002 µF
-Li = 0.0 mH
•Transmitters with output code N (non-incendive F
OUNDATION fieldbus) are FNICO approved
A.1.2Input/output signals
Input signal from sensor
•4-wire remote: one intrinsically safe 4-wire mating connector
•9-wire remote: two intrinsically safe terminal blocks with 3 sockets and one intrinsically safe
terminal block with 4 sockets (only 3 sockets are used)
•Remote core processor with remote transmitter:
-Core processor: two intrinsically safe terminal blocks with 3 sockets and one intrinsically
safe terminal block with 4 sockets (only 3 sockets are used)
-Transmitter: one intrinsically safe 4-wire mating connector
Model 1700/2700 transmitters with non-intrinsically safe analog outputs option board
(output option code A)
One 4–20 mA output
•Not intrinsically safe
•Internally powered (active)
•Isolated to ±50 VDC from all other outputs and earth ground
•Maximum load limit: 820 Ohms
•Model 1700 can report mass flow or volume flow; Model 2700 can report mass flow, volume
flow, density, temperature, or drive gain; transmitters with the petroleum measurement
application (API) or enhanced density application can also report standard volume flow and
density at reference temperature
•Linear with process from 3.8 to 20.5 mA, per NAMUR NE43 (June 1994)
56Micro Motion® Model 1700 and 2700 Transmitters
Specifications
One frequency/pulse output (Model 1700 transmitters) or frequency/pulse/discrete output (Model
2700 transmitters):
•Not intrinsically safe
•Internally powered (active)
•Maximum current: 100 mA
•Output voltage: +24 VDC ±3%, with a 2.2 kohm internal pull-up resistor
•Frequency/pulse output (Model 1700/2700):
-Can be used to indicate either flow rate or total; Model 1700 output reports the same flow
variable as the mA output, Model 2700 output is independent from mA output
-Scalable to 10,000 Hz
-Linear with flow rate to 12,500 Hz
-Configurable polarity: active high or active low
•Discrete output (Model 2700 only):
-Can report event 1, event 2, event 1 or 2, flow direction, flow switch, calibration in
progress, or fault
Model 1700/2700 transmitters with intrinsically safe outputs option board (output option code D)
Model 1700 has one 4–20 mA output; Model 2700 has two 4–20 mA outputs:
•Intrinsically safe
•Externally powered (passive)
•Isolated to ±50 VDC from all other outputs and earth ground
•Maximum input voltage: 30 VDC, 1 watt maximum
•Model 1700 can report mass flow or volume flow; Model 2700 can report mass flow, volume
flow, density, temperature, or drive gain; transmitters with the petroleum measurement
application (API) or enhanced density application can also report standard volume flow and
density at reference temperature
•Linear with process from 3.8 to 20.5 mA, per NAMUR NE43 (June 1994)
•Maximum load limits: see following chart
Installation Manual57
Specifications
0
100
200
300
400
500
600
700
800
900
1000
12141618202224262830
mA Output Load Resistance Value
R
max
= (V
supply
- 12)/0.023*
*If communicating with HART a minimum of 250 Ohms
and 17.75 V supply is needed
Supply voltage (volts)
External resistor (Ohms)
Operating
Region
One frequency/pulse output (Model 1700 transmitters) or frequency/pulse/discrete output (Model
2700 transmitters):
•Intrinsically safe
•Externally powered (passive)
•Maximum input voltage: 30 VDC, 0.75 watt maximum
•Frequency/pulse output (Model 1700/2700):
-Can be used to indicate either flow rate or total; Model 1700 output reports the same flow
variable as the mA output, Model 2700 output is independent from mA output
-Can report event 1, event 2, event 1 or 2, flow direction, flow switch, calibration in
progress, or fault
-Configurable polarity: active high or active low
Model 2700 transmitters with non-intrinsically safe configurable input/outputs option board
(output option code B or C)
One or two 4–20 mA outputs:
•Channel A is always an mA output; Channel B is configurable as an mA output
•Not intrinsically safe
•Internally powered (active)
•Isolated to ±50 VDC from all other outputs and earth ground
•Maximum load limit:
-Channel A (mA1): 820 Ohms
-Channel B (mA2): 420 Ohms
•Can report mass flow, volume flow, density, temperature, or drive gain; transmitters with the
petroleum measurement application (API) or enhanced density application can also report
standard volume flow and density at reference temperature
•Linear with process from 3.8 to 20.5 mA, per NAMUR NE43 (June 1994)
Installation Manual59
Specifications
One or two frequency/pulse outputs:
•Channels B and C are configurable as frequency/pulse outputs
•If both are configured for frequency/pulse:
-The channels function as a dual-pulse output which reports a single process variable.
Channels are electrically isolated but not independent
-Output on channel C can be phase-shifted 0, 90, or 180 degrees from the output on channel
B, or the dual-pulse output can be set to quadrature mode
•Not intrinsically safe
•Configurable for internal or external power (active or passive):
-If internally powered, output voltage is 15 VDC ±3%, internal 2.2 kohm pull-up
-If externally powered, output voltage is 3–30 VDC maximum, sinking up to 500 mA at
30 VDC maximum
•Scalable to 10,000 Hz
•Can report mass flow rate or volume flow rate, which can be used to indicate flow rate or total
flow
•Linear with flow rate to 12,500 Hz
•Configurable polarity: active high or active low
One or two discrete outputs:
•Channels B and C are configurable as discrete outputs
•Can report event 1, event 2, event 1 & 2, flow direction, flow switch, calibration in progress, or
fault
•Maximum sink capability: 500 mA
•Configurable for internal or external power (active or passive):
-If internally powered, output voltage is 15 VDC ±3%, internal 2.2 kohm pull-up
-If externally powered, output voltage is 3–30 VDC maximum, sinking up to 500 mA at
30 VDC maximum
•Configurable polarity: active high or active low
One discrete input:
•Channel C is configurable as a discrete input
•Not intrinsically safe
•Configurable for internal or external power:
-Internal power: 15 VDC, 7 mA maximum source current
-External power: 3–30 VDC maximum
•Can be used to start flowmeter zeroing procedure, reset mass total, reset volume total, reset
corrected volume total, or reset all totals
Model 2700 transmitters with intrinsically safe F
OUNDATION fieldbus outputs option board (output
option code E)
One F
OUNDATION fieldbus H1 output:
-F
OUNDATION fieldbus wiring is intrinsically safe with an intrinsically safe power supply
-Manchester-encoded digital signal conforms to IEC 1158-2
60Micro Motion® Model 1700 and 2700 Transmitters
Specifications
Model 2700 transmitters with non-incendive FOUNDATION fieldbus outputs option board (output option
code N)
One F
Model 2700 transmitters with PROFIBUS-PA outputs option board (output option code G)
One PROFIBUS-PA output:
OUNDATION fieldbus H1 output:
OUNDATION fieldbus wiring is non-incendive
-F
-Manchester-encoded digital signal conforms to IEC 1158-2
-PROFIBUS-PA wiring is intrinsically safe with an intrinsically safe PROFIBUS-PA
network power supply
-Manchester-encoded digital signal conforms to IEC 1158-2
A.1.3Digital communication
Model 1700/2700 transmitters support the following digital communications:
Service port
•One service port can be used for temporary connection only
•Address 111
•Uses RS-485 Modbus RTU signal, 38.4 kilobaud, one stop bit, no parity
HART/Bell202
A HART/Bell202 signal can be superimposed on the primary mA output and used for interface with a
host system:
•Frequency: 1.2 and 2.2 kHz
•Amplitude: 0.8 mA peak-to-peak
•1200 baud
•Requires 250 to 600 Ohms load resistance
HART/RS485 or Modbus/RS485 (transmitters with analog outputs option board only)
One pair of terminals provides RS-485 communications:
•Can be used for direct connection to a HART or Modbus host system
•Accepts baud rates between 1200 baud and 38.4 kilobaud
F
OUNDATION fieldbus or PROFIBUS-PA transmitters
One pair of terminals provides F
•Resource, transducer, and function blocks per F
Installation Manual61
OUNDATION fieldbus or PROFIBUS-PA communications:
OUNDATION or PROFIBUS specification
Specifications
A.1.4Power supply
The Model 1700/2700 transmitter’s power supply:
AC power requirements
85 to 265 VAC, 50/60 Hz, 6 watts typical, 11 watts maximum
DC power requirements
•Has a self-switching AC/DC input
•Complies with low voltage directive 2006/95/EC per EN 61010-1 (IEC 61010-1) with
amendment 2
•Meets Installation (Overvoltage) Category II, Pollution Degree 2 requirements
•Has an IEC 127–1.25 slowblow fuse
•18 to 100 VDC, 6 watts typical, 11 watts maximum
•At startup, transmitter power source must provide a minimum of 1.5 amps of short-term
current at a minimum of 18 volts at the transmitter power input terminals
•Minimum 22 VDC with 1000 feet (300 meters) of 18 AWG (0,8 mm
2
) power supply cable
A.1.5Environmental requirements
Ambient temperature limits
•Operation: –40 to +140 °F (–40 to +60 °C)
•Storage: –40 to +140 °F (–40 to +60 °C)
Display responsiveness decreases, and display may become difficult to read, below –4 °F (–20 °C).
Above 131 °F (55 °C), some darkening of display may occur.
If possible, install the transmitter in a location that will prevent direct exposure to sunlight.
Different ambient temperature requirements may apply when installing the transmitter in a hazardous
area. Refer to the approval documentation shipped with the transmitter or available on the Micro
Motion web site.
Humidity limits
Relative humidity between 5 and 95%, non-condensing at 140 °F (60 °C)
Vibration limits
The transmitter meets IEC 68.2.6, endurance sweep, 5 to 2000 Hz, 50 sweep cycles at 1.0 g
A.1.6Ambient temperature effect
On analog outputs ±0.005% of span per °C
A.1.7EMC compliance
The transmitter complies with the following EMI effects standards:
•NAMUR NE21 (May 1999) with the exception of Voltage Dip when powered by 24 VDC
•Complies with EMC directive 2004/108/EC per EN 61326 Industrial
62Micro Motion® Model 1700 and 2700 Transmitters
Specifications
A.2Hazardous area classifications
The transmitter may have a tag listing hazardous area classifications, which indicate suitability for
installation in the hazardous areas described in this section.
A.2.1UL and CSA
Ambient temperature is limited to –40 to +131 °F (–40 to +55 °C) for UL compliance.
Ambient temperature is limited to –40 to +140 °F (–40 to +60 °C) for CSA compliance.
Transmitter
Class I, Division 1, Groups C and D. Class II, Division 1, Groups E, F, and G explosion proof (when
installed with approved conduit seals). Otherwise, Class I, Division 2, Groups A, B, C, and D.
Outputs
Provides nonincendive sensor outputs for use in Class I, Division 2, Groups A, B, C, and D; or
intrinsically safe sensor outputs for use in Class I, Division 1, Groups C and D or Class II, Division 1,
Groups E, F, and G.
Ambient temperature is limited to below 131 °F (55 °C) for ATEX and IECEx compliance. Table A-1
lists the classification codes for each transmitter output option.
Table A-1ATEX and IECEx classifications
Output optionClassificationATEXIECEx
Analog,
non-incendive
FOUNDATION fieldbus,
and configurable I/O
(output options A, N, B, and C)
Intrinsically safe analog,
intrinsically safe F
fieldbus, and PROFIBUS-PA
(output options D, E, and G)
OUNDATION
Flameproof when installed with
approved cable glands:
• With displayEEx d [ib] IIB+H2 T5Ex d [ib] IIB+H2 T5
• Without displayEEx d [ib] IIC T5Ex d [ib] IIC T5
Increased safety when installed
with approved cable glands:
• With displayEEx de [ib] IIB+H2 T5Ex de [ib] IIB+H2 T5
• Without displayEEx de [ib] IIC T5Ex de [ib] IIC T5
Flameproof when installed with
approved cable glands:
• With displayEEx d [ia/ib] IIB+H2 T5Ex d [ia/ib] IIB+H2 T5
• Without displayEEx d [ia/ib] IIC T5Ex d [ia/ib] IIC T5
Increased safety when installed
with approved cable glands:
• With displayEEx de [ia/ib] IIB+H2 T5 Ex de [ia/ib] IIB+H2 T5
• Without displayEEx de [ia/ib] IIC T5Ex de [ia/ib] IIC T5
Installation Manual63
Specifications
A.3Performance specifications
For performance specifications, refer to the sensor specifications.
A.4Physical specifications
The physical specifications of the transmitter include:
•Housing
•Mounting
•Interface/display (optional)
•Weight
•Dimensions
A.4.1Housing
NEMA 4X (IP67) epoxy painted cast aluminum housing.
Terminal compartment contains output terminals, power terminals and service-port terminals. The
output terminals are physically separated from the power- and service-port terminals.
•The electronics compartment contains all electronics and the standard display.
•The sensor compartment contains the wiring terminals for connection to the core processor on
the sensor.
Screw-terminal on housing for chassis ground.
Cable gland entrances are either 1/2″–14 NPT or M20 × 1.5 female conduit ports.
A.4.2Mounting
Model 1700/2700 transmitters are available integrally mounted to some Micro Motion sensors, or in
two remote-mount configurations.
•Remote-mount transmitters include a mounting bracket, and require 4-wire or 9-wire signal
cables between the sensor and the transmitter. Maximum distance from other flowmeter
components depends on the installation type and cable type, as described in Table A-2.
•The transmitter can be rotated on the sensor or the mounting bracket, up to 360° in
90° increments.
Figures A-1 through A-5 show the dimensions of the Model 1700 or 2700 transmitter with and
without a display, the transmitter/core processor assembly with and without a display, and the standalone core processor. For dimensions of integrally mounted transmitters and sensors, refer to the
product data sheet for your sensor.
Installation Manual65
Specifications
6 13/16
(174)
1
(25)
2 1/4
(57)
4 5/16
(110)
8 7/16
(214)
9 5/16
(237)
3 × 1/2″–14 NPT
or M20 × 1.5
Note: These dimensions apply to the transmitter in 4-wire remote installations or remote core
processor with remote transmitter installations. See Figure 2-1.
3 15/16
(99)
2 11/16 (69)
1 7/8 (47)
Ø 4 11/16
(119)
2 7/16
(62)
4 11/16
(119)
4 3/4
(120)
1 3/4
(45)
2 1/4
(57)
To 1/2–NPT
or M20
4 1/2
(114)
2 13/16
(71)
4 × Ø3/8
(10)
3 11/16
(93)
2 13/16
(71)
Wall mount
To centerline of
2″ pipe (pipe mount)
Dimensions in
inches
(mm)
4 1/2
(114)
Figure A-1Dimensions – Model 1700/2700 transmitter with display
66Micro Motion® Model 1700 and 2700 Transmitters
Specifications
5 13/16
(148)
1
(25)
2 1/4
(57)
4 5/16
(110)
7 7/16
(188)
8 5/16
(211)
3 × 1/2″–14 NPT
or M20 × 1.5
Note: These dimensions apply to the transmitter in 4-wire remote installations or remote core
processor with remote transmitter installations. See Figure 2-1.
2 11/16 (69)
2 7/16
(62)
1 7/8 (47)
Ø 4 1/16
(104)
4 7/16
(113)
4 3/4
(120)
1 3/4
(45)
2 1/4
(57)
To 1/2–NPT
or M20
4 1/2
(114)
2 13/16
(71)
4 × Ø3/8
(10)
Wall mountTo centerline of
2″ pipe (pipe mount)
4 1/2
(114)
2 15/16
(74)
13/16
(21)
3 11/16
(93)
2 13/16
(71)
Dimensions in
inches
(mm)
Figure A-2Dimensions – Model 1700/2700 transmitter without display