Micro Motion® Model 1500 Transmitters with
Analog Outputs
Configuration and Use Manual
Page 2
Safety messages
Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully
before proceeding to the next step.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration
manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government
transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept
your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion Customer
Service department.
Emerson Flow customer service
Email:
•Worldwide: flow.support@emerson.com
•Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South AmericaEurope and Middle EastAsia Pacific
United States800-522-6277U.K.0870 240 1978Australia800 158 727
Appendix ENE 53 history ..............................................................................................................181
ivMicro Motion Model 1500 Transmitters with Analog Outputs
Page 7
Part I
Getting started
Chapters covered in this part:
Before you begin
•
Quick start
•
Getting started
Configuration and Use Manual1
Page 8
Getting started
2Micro Motion Model 1500 Transmitters with Analog Outputs
Page 9
1Before you begin
Topics covered in this chapter:
About this manual
•
Transmitter model code
•
Communications tools and protocols
•
Additional documentation and resources
•
1.1About this manual
This manual helps you configure, commission, use, maintain, and troubleshoot the
Model 1500 transmitter.
Important
This manual assumes that the following conditions apply:
•The transmitter has been installed correctly and completely according to the instructions in
the transmitter installation manual
•The installation complies with all applicable safety requirements
•The user is trained in local and corporate safety standards
Before you begin
1.2
Transmitter model code
You can verify that this manual pertains to your transmitter by ensuring the model code on
the transmitter tag matches the format.
Example:
The transmitter has a model number of the following form: 1500DEB**A******
D
4-wire remote DIN rail–mount
E
4-wire remote DIN rail transmitter with 9-wire remote enhanced core processor
B
4-wire remote DIN rail transmitter with 9-wire remote core processor
A
Analog outputs option board
1.3Communications tools and protocols
You must have a communications tool to interface with the transmitter. Several different
communications tools and protocols are supported. You may use different tools in
different locations or for different tasks.
Configuration and Use Manual3
Page 10
Before you begin
Communications toolSupported protocols
ProLink III• HART/Bell 202
• Modbus/RS-485
• Service port
Field Communicator• HART/Bell 202
Tip
You may be able to use other communications tools, such as AMS Suite: Intelligent Device Manager,
or the Smart Wireless THUM™ Adapter. Use of AMS or the Smart Wireless THUM Adapter is not
discussed in this manual. For more information on the Smart Wireless THUM Adapter, refer to the
documentation available at www.emerson.com.
1.4Additional documentation and resources
The following additional documentation supports the installation and operation of the
transmitter.
Topic
Hazardous area installationSee the approval documentation shipped with the transmit-
Product Data Sheet
Production Volume Reconciliation
(PVR), Transient Bubble Remediation (TBR), and Transient Mist Remediation (TMR) applications
SensorSensor documentation
Transmitter installation
Document
ter, or download the appropriate documentation at
www.emerson.com.
Micro Motion Series 1000 and Series 2000 Transmitters with
MVD™ Technology Product Data Sheet (PDS)
Micro Motion Oil and Gas Production Supplement
Micro Motion Model 1500 and Model 2500 Transmitters: Instal‐
lation Manual
All documentation resources are available at www.emerson.com or on the user
documentation DVD.
4Micro Motion Model 1500 Transmitters with Analog Outputs
Page 11
2Quick start
Topics covered in this chapter:
Power up the transmitter
•
Check meter status
•
Make a startup connection to the transmitter
•
(Optional) Adjust digital communications settings
•
Verify mass flow measurement
•
Verify the zero
•
2.1Power up the transmitter
The transmitter must be powered up for all configuration and commissioning tasks, or for
process measurement.
Quick start
The Model 1500:
•Is DC powered only
•Has a minimum 19.2 to 28.8 VDC, 6.3 watts
•At startup, the transmitter power source must provide a minimum of 1.0 amperes of
short-term current per transmitter
•The length and conductor diameter of the power cable must be sized to provide
19.2 VDC minimum at the power terminals, at a load current of 330 mA
Procedure
1.Ensure that all transmitter and sensor covers and seals are closed.
WARNING!
To prevent ignition of flammable or combustible atmospheres, ensure that all covers
and seals are tightly closed. For hazardous area installations, applying power while
housing covers are removed or loose can cause an explosion.
2.Turn on the electrical power at the power supply.
The transmitter will automatically perform diagnostic routines. During this period,
Alert 009 is active. The diagnostic routines should complete in approximately
30 seconds. The status LED will turn green when the startup diagnostics are
complete. If the status LED exhibits different behavior, an alert is active.
Postrequisites
Although the sensor is ready to receive process fluid shortly after power-up, the electronics
can take up to 10 minutes to reach thermal equilibrium. Therefore, if this is the initial
startup, or if power has been off long enough to allow components to reach ambient
Configuration and Use Manual5
Page 12
Quick start
temperature, allow the electronics to warm up for approximately 10 minutes before
relying on process measurements. During this warm-up period, you may observe minor
measurement instability or inaccuracy.
2.2Check meter status
Check the meter for any error conditions that require user action or that affect
measurement accuracy.
1.Wait approximately 10 seconds for the power-up sequence to complete.
Immediately after power-up, the transmitter runs through diagnostic routines and
checks for error conditions. During the power-up sequence, Alert A009 is active.
This alert should clear automatically when the power-up sequence is complete.
2.Check the status LED on the transmitter.
Related information
View and acknowledge status alerts
2.2.1Transmitter status reported by LED
Status LED statesTable 2-1:
LED stateAlarm conditionDescription
Solid greenNo alarmNormal operation
Flashing yellowNo alarm• Zero calibration procedure is in progress
• Loop test is in progress
Solid yellowLow-severity alarmAlarm condition that will not cause measure-
ment error (outputs continue to report process data)
Solid redHigh-severity alarmAlarm condition that will cause measurement
error (outputs in fault)
2.3Make a startup connection to the transmitter
To configure the transmitter, you must have an active connection from a communications
tool. Follow this procedure to make your first connection to the transmitter.
Identify the connection type to use, and follow the instructions for that connection type in
the appropriate appendix. Use the default communications parameters shown in the
appendix.
6Micro Motion Model 1500 Transmitters with Analog Outputs
Page 13
Communications toolConnection type to useInstructions
ProLink IIIModbus/RS-485Appendix A
Field CommunicatorHARTAppendix B
2.4(Optional) Adjust digital communications
settings
Change the communications parameters to site-specific values.
Important
If you are changing communications parameters for the connection type that you are using, you will
lose the connection when you write the parameters to the transmitter. Reconnect using the new
parameters.
Procedure
Quick start
2.5
1.To change the communications parameters using ProLink III, choose Device Tools >
Configuration > Communications.
2.To change the communications parameters using the Field Communicator, choose
Check to see that the mass flow rate reported by the transmitter is accurate. You can use
any available method.
•Connect to the transmitter with ProLink III and read the value for Mass Flow Rate in
the Process Variables panel.
•Connect to the transmitter with the Field Communicator and read the value for Mass
Flow Rate.
On-Line Menu > Overview > Primary Purpose Variables
Postrequisites
If the reported mass flow rate is not accurate:
•Check the characterization parameters.
•Review the troubleshooting suggestions for flow measurement issues.
2.6
Configuration and Use Manual7
Verify the zero
Verifying the zero helps you determine if the stored zero value is appropriate to your
installation, or if a field zero can improve measurement accuracy.
Page 14
Quick start
The zero verification procedure analyzes the Live Zero value under conditions of zero flow,
and compares it to the Zero Stability range for the sensor. If the average Live Zero value is
within a reasonable range, the zero value stored in the transmitter is valid. Performing a
field calibration will not improve measurement accuracy.
Important
In most cases, the factory zero is more accurate than the field zero. Do not zero the meter unless one
of the following is true:
•The zero is required by site procedures.
•The stored zero value fails the zero verification procedure.
Procedure
1.Allow the flowmeter to warm up for at least 20 minutes after applying power.
2.Run the process fluid through the sensor until the sensor temperature reaches the
normal process operating temperature.
3.Stop flow through the sensor by shutting the downstream valve, and then the
upstream valve if available.
4.Verify that the sensor is blocked in, that flow has stopped, and that the sensor is
completely full of process fluid.
5.From ProLink III, choose Device Tools > Calibration > Zero Verification and
Calibration > Verify Zero and wait until the procedure completes.
6.Observe the drive gain, temperature, and density readings. If they are stable, check
the Live Zero or Field Verification Zero value. If the average value is close to 0, you
should not need to zero the meter.
7.If the zero verification procedure fails:
a. Confirm that the sensor is completely blocked in, that flow has stopped, and that
the sensor is completely full of process fluid.
b. Verify that the process fluid is not flashing or condensing, and that it does not
contain particles that can settle out.
c. Remove or reduce sources of electromechanical noise if appropriate.
d. Repeat the zero verification procedure.
e. If it fails again, zero the meter.
Postrequisites
Restore normal flow through the sensor by opening the valves.
Related information
Zero the meter
8Micro Motion Model 1500 Transmitters with Analog Outputs
Page 15
2.6.1Terminology used with zero verification and zero
calibration
TermDefinition
ZeroIn general, the offset required to synchronize the left pickoff and the right
pickoff under conditions of zero flow. Unit = microseconds.
Factory ZeroThe zero value obtained at the factory, under laboratory conditions.
Field ZeroThe zero value obtained by performing a zero calibration outside the fac-
tory.
Prior ZeroThe zero value stored in the transmitter at the time a field zero calibration
is begun. May be the factory zero or a previous field zero.
Manual ZeroThe zero value stored in the transmitter, typically obtained from a zero
calibration procedure. It may also be configured manually. Also called
“mechanical zero” or “stored zero”.
Live ZeroThe real-time bidirectional mass flow rate with no flow damping or mass
flow cutoff applied. An adaptive damping value is applied only when the
mass flow rate changes dramatically over a very short interval. Unit = configured mass flow measurement unit.
Zero StabilityA laboratory-derived value used to calculate the expected accuracy for a
sensor. Under laboratory conditions at zero flow, the average flow rate is
expected to fall within the range defined by the Zero Stability value (0 ±
Zero Stability). Each sensor size and model has a unique Zero Stability value. Statistically, 95% of all data points should fall within the range defined
by the Zero Stability value.
Zero CalibrationThe procedure used to determine the zero value.
Zero TimeThe time period over which the Zero Calibration procedure is performed.
Unit = seconds.
Field Verification ZeroA 3-minute running average of the Live Zero value, calculated by the
transmitter. Unit = configured mass flow measurement unit.
Zero VerificationA procedure used to evaluate the stored zero and determine whether or
not a field zero can improve measurement accuracy.
Quick start
Configuration and Use Manual9
Page 16
Quick start
10Micro Motion Model 1500 Transmitters with Analog Outputs
Page 17
Configuration and commissioning
Part II
Configuration and commissioning
Chapters covered in this part:
Introduction to configuration and commissioning
•
Configure process measurement
•
Configure device options and preferences
•
Integrate the meter with the control system
•
Complete the configuration
•
Configuration and Use Manual11
Page 18
Configuration and commissioning
12Micro Motion Model 1500 Transmitters with Analog Outputs
Page 19
Introduction to configuration and commissioning
3Introduction to configuration and
commissioning
Topics covered in this chapter:
Configuration flowchart
•
Default values and ranges
•
Disable write‐protection on the transmitter configuration
•
Restore the factory configuration
•
3.1Configuration flowchart
Use the following flowchart as a general guide to the configuration and commissioning
process.
Some options may not apply to your installation. Detailed information is provided in the
remainder of this manual.
Configuration and Use Manual13
Page 20
Introduction to configuration and commissioning
Configuration flowchartFigure 3-1:
Configure process measurement
Configure mass flow
measurement
Configure volume flow
meaurement
Volume flow type
Liquid
Configure flow direction
Configure density
measurement
Configure temperature
measurement
Gas
Define gas properties
Configure device options and
preferences
Configure fault handling
parameters
Configure sensor
parameters
Configure device
parameters
Integrate device with control system
Configure the channel(s)
Configure the mA
output(s)
Test and move to production
Test or tune transmitter
using sensor simulation
Back up transmitter
configuration
Enable write-protection on
transmitter configuration
Done
Configure pressure
compensation (optional)
Configure PVR, TMR,
or TBR (if available)
Configure the frequency
output(s)
Configure the discrete
output(s)
Configure events
Configure digital
communications
14Micro Motion Model 1500 Transmitters with Analog Outputs
Page 21
Introduction to configuration and commissioning
3.2Default values and ranges
See Appendix C to view the default values and ranges for the most commonly used
parameters.
3.3Disable write-protection on the transmitter
configuration
Field Communicator Configure > Manual Setup > Info Parameters > Transmitter Info > Write Protect
Overview
If the transmitter is write-protected, the configuration is locked and you must unlock it
before you can change any configuration parameters. By default, the transmitter is not
write-protected.
3.4
Tip
Write-protecting the transmitter prevents accidental changes to configuration. It does not prevent
normal operational use. You can always disable write-protection, perform any required configuration
changes, then re-enable write-protection.
Restore the factory configuration
ProLink IIIDevice Tools > Configuration Transfer > Restore Factory Configuration
Field Communicator Service Tools > Maintenance > Reset/Restore > Restore Factory Configuration
Overview
Restoring the factory configuration returns the transmitter to a known operational
configuration. This may be useful if you experience problems during configuration.
Important
You cannot restore factory configurations with a 700 core.
Tip
Restoring the factory configuration is not a common action. You may want to contact customer
support to see if there is a preferred method to resolve any issues.
Configuration and Use Manual15
Page 22
Introduction to configuration and commissioning
16Micro Motion Model 1500 Transmitters with Analog Outputs
Page 23
Configure process measurement
4Configure process measurement
Topics covered in this chapter:
Configure mass flow measurement
•
Configure volume flow measurement for liquid applications
•
Configure GSV flow measurement
•
Configure Flow Direction
•
Configure density measurement
•
Configure temperature measurement
•
Configure pressure compensation
•
4.1Configure mass flow measurement
The mass flow measurement parameters control how mass flow is measured and reported.
4.1.1Configure Mass Flow Measurement Unit
ProLink IIIDevice Tools > Configuration > Process Measurement > Flow
Field Communicator Configure > Manual Setup > Measurements > Flow > Mass Flow Unit
Overview
Mass Flow Measurement Unit specifies the unit of measure that will be used for the mass
flow rate. The unit used for mass total and mass inventory is derived from this unit.
Any selected measurement unit, (mass, volume or gas standard volume), is automatically
applied to both the mA and Frequency Outputs.
Procedure
Set Mass Flow Measurement Unit to the unit you want to use.
The default setting for Mass Flow Measurement Unit is g/sec (grams per second).
Tip
If the measurement unit you want to use is not available, you can define a special measurement unit.
Options for Mass Flow Measurement Unit
The transmitter provides a standard set of measurement units for Mass Flow Measurement
Unit, plus one user-defined special measurement unit. Different communications tools
may use different labels for the units.
Configuration and Use Manual17
Page 24
Configure process measurement
Label
Unit description
Grams per second
Grams per minute
Grams per hour
Kilograms per second
Kilograms per minute
Kilograms per hour
Kilograms per day
Metric tons per minute
Metric tons per hour
Metric tons per day
Pounds per second
Pounds per minute
Pounds per hour
Pounds per day
Short tons (2000 pounds) per minute
Short tons (2000 pounds) per hour
Short tons (2000 pounds) per day
Long tons (2240 pounds) per hour
Long tons (2240 pounds) per day
Special unit
ProLink IIIField Communicator
g/secg/s
g/ming/min
g/hrg/h
kg/seckg/s
kg/minkg/min
kg/hrkg/h
kg/daykg/d
mTon/minMetTon/min
mTon/hrMetTon/h
mTon/dayMetTon/d
lbs/seclb/s
lbs/minlb/min
lbs/hrlb/h
lbs/daylb/d
sTon/minSTon/min
sTon/hrSTon/h
sTon/daySTon/d
lTon/hrLTon/h
lTon/dayLTon/d
specialSpcl
Define a special measurement unit for mass flow
ProLink III
Field Communicator Configure > Manual Setup > Measurements > Special Units > Mass Special Units
Overview
A special measurement unit is a user-defined unit of measure that allows you to report
process data, totalizer data, and inventory data in a unit that is not available in the
transmitter. A special measurement unit is calculated from an existing measurement unit
using a conversion factor.
Procedure
1.Specify Base Mass Unit.
Base Mass Unit is the existing mass unit that the special unit will be based on.
18Micro Motion Model 1500 Transmitters with Analog Outputs
Device Tools > Configuration > Process Measurement > Flow > Special Units
Page 25
Configure process measurement
2.Specify Base Time Unit.
Base Time Unit is the existing time unit that the special unit will be based on.
3.Calculate Mass Flow Conversion Factor as follows:
a. x base units = y special units
b. Mass Flow Conversion Factor = x ÷ y
The original mass flow rate value is divided by this value.
4.Enter Mass Flow Conversion Factor.
5.Set Mass Flow Label to the name you want to use for the mass flow unit.
6.Set Mass Total Label to the name you want to use for the mass total and mass
inventory unit.
The special measurement unit is stored in the transmitter. You can configure the
transmitter to use the special measurement unit at any time.
Example: Defining a special measurement unit for mass flow
You want to measure mass flow in ounces per second (oz/sec).
4.1.2
1.Set Base Mass Unit to Pounds (lb).
2.Set Base Time Unit to Seconds (sec).
3.Calculate Mass Flow Conversion Factor:
a. 1 lb/sec = 16 oz/sec
b. Mass Flow Conversion Factor = 1 ÷ 16 = 0.0625
4.Set Mass Flow Conversion Factor to 0.0625.
5.Set Mass Flow Label to oz/sec.
6.Set Mass Total Label to oz.
Configure Flow Damping
ProLink IIIDevice Tools > Configuration > Process Measurement > Flow
Damping is used to smooth out small, rapid fluctuations in process measurement.
Damping Value specifies the time period (in seconds) over which the transmitter will
spread changes in the process variable. At the end of the interval, the internal value will
reflect 63% of the change in the actual measured value.
Procedure
Set Flow Damping to the value you want to use.
Configuration and Use Manual19
Page 26
Configure process measurement
The default value is 0.8 seconds. The range depends on the core processor type and the
setting of Update Rate, as shown in the following table.
Update Rate settingDamping range
Normal
Special
The value you enter is automatically rounded off to the nearest valid value. For example, if
the damping is currently set to 0.8 seconds, any value entered up to 1.2 seconds will be
rounded down to 0.8 seconds, and any value entered from 1.21 to 1.59 seconds will be
rounded up to 1.6 seconds.
Flow damping affects volume measurement for liquid volume data. Flow damping also
affects volume measurement for gas standard volume data. The transmitter calculates
volume data from the damped mass flow data.
Interaction between Flow Damping and mA Output
Damping
In some circumstances, both Flow Damping and mA Output Damping are applied to the
reported mass flow value.
Flow Damping controls the rate of change in flow process variables. mA Output Damping
controls the rate of change reported via the mA Output. If mA Output Process Variable is
set to Mass Flow Rate, and both Flow Damping and mA Output Damping are set to non-zero
values, flow damping is applied first, and the added damping calculation is applied to the
result of the first calculation.
4.1.3
20Micro Motion Model 1500 Transmitters with Analog Outputs
Configure Mass Flow Cutoff
ProLink IIIDevice Tools > Configuration > Process Measurement > Flow
Field Communicator Configure > Manual Setup > Measurements > Flow > Mass Flow Cutoff
Page 27
Configure process measurement
Overview
Mass Flow Cutoff specifies the lowest mass flow rate that will be reported as measured. All
mass flow rates below this cutoff will be reported as 0.
Procedure
Set Mass Flow Cutoff to the value you want to use.
The default value for Mass Flow Cutoff is 0.0 g/sec or a sensor-specific value set at the
factory. The recommended value is 0.5% of the nominal flow rate of the attached sensor.
See the sensor specifications. Leaving Mass Flow Cutoff at 0.0 g/sec is not recommended.
Effect of Mass Flow Cutoff on volume measurement
Mass Flow Cutoff does not affect volume measurement. Volume data is calculated from
the actual mass data rather than the reported value.
Volume flow has a separate Volume Flow Cutoff that is not affected by the Mass Flow
Cutoff value.
Interaction between Mass Flow Cutoff and mA Output Cutoff
Mass Flow Cutoff defines the lowest mass flow value that the transmitter will report as
measured. mA Output Cutoff defines the lowest flow rate that will be reported via the mA
output. If mA Output Process Variable is set to Mass Flow Rate, the mass flow rate reported
via the mA Output is controlled by the higher of the two cutoff values.
Mass Flow Cutoff affects all reported values and values used in other transmitter behavior
(e.g., events defined on mass flow).
mA Output Cutoff affects only mass flow values reported via the mA Output.
Example: Cutoff interaction with mA Output Cutoff lower than Mass Flow Cutoff
Configuration:
•mA Output Process Variable: Mass Flow Rate
•Frequency Output Process Variable: Mass Flow Rate
•mA Output Cutoff: 10 g/sec
•Mass Flow Cutoff: 15 g/sec
Result: If the mass flow rate drops below 15 g/sec, mass flow will be reported as 0, and 0
will be used in all internal processing.
Example: Cutoff interaction with mA Output Cutoff higher than Mass Flow Cutoff
Configuration:
•mA Output Process Variable: Mass Flow Rate
•Frequency Output Process Variable: Mass Flow Rate
•mA Output Cutoff: 15 g/sec
Configuration and Use Manual21
Page 28
Configure process measurement
•Mass Flow Cutoff: 10 g/sec
Result:
•If the mass flow rate drops below 15 g/sec but not below 10 g/sec:
-The mA Output will report zero flow.
-The Frequency Output will report the actual flow rate, and the actual flow rate
will be used in all internal processing.
•If the mass flow rate drops below 10 g/sec, both outputs will report zero flow, and 0
will be used in all internal processing.
4.2Configure volume flow measurement for liquid
applications
The volume flow measurement parameters control how liquid volume flow is measured
and reported.
Restriction
You cannot implement both liquid volume flow and gas standard volume flow at the same time.
Choose one or the other.
4.2.1
Note
If you need to switch from gas standard volume to liquid volume, polling for base density will
automatically be disabled.
Configure Volume Flow Type for liquid applications
ProLink IIIDevice Tools > Configuration > Process Measurement > Flow
Field Communicator Configure > Manual Setup > Measurements > GSV > Volume Flow Type > Liquid
Overview
Volume Flow Type controls whether liquid or gas standard volume flow measurement will
be used.
Restriction
Gas standard volume measurement is incompatible with some applications. Set Volume Flow Type
to Liquid if you are using any of the following applications:
•Production Volume Reconciliation (PVR)
Procedure
Set Volume Flow Type to Liquid.
22Micro Motion Model 1500 Transmitters with Analog Outputs
Page 29
Configure process measurement
4.2.2Configure Volume Flow Measurement Unit for liquid
applications
ProLink IIIDevice Tools > Configuration > Process Measurement > Flow
Field Communicator Configure > Manual Setup > Measurements > Flow > Volume Flow Unit
Overview
Volume Flow Measurement Unit specifies the unit of measurement that will be displayed
for the volume flow rate. The unit used for the volume total and volume inventory is based
on this unit.
Prerequisites
Before you configure Volume Flow Measurement Unit, be sure that Volume Flow Type is
set to Liquid.
Procedure
Set Volume Flow Measurement Unit to the unit you want to use.
The default setting for Volume Flow Measurement Unit is l/sec (liters per second).
Tip
If the measurement unit you want to use is not available, you can define a special measurement unit.
Options for Volume Flow Measurement Unit for liquid
applications
The transmitter provides a standard set of measurement units for Volume Flow
Measurement Unit, plus one user-defined measurement unit. Different communications
tools may use different labels for the units.
Label
Unit description
Cubic feet per second
Cubic feet per minute
Cubic feet per hour
Cubic feet per day
Cubic meters per second
Cubic meters per minute
Cubic meters per hour
Cubic meters per day
U.S. gallons per second
ProLink IIIField Communicator
ft3/secCuft/s
ft3/minCuft/min
ft3/hrCuft/h
ft3/dayCuft/d
m3/secCum/s
m3/minCum/min
m3/hrCum/h
m3/dayCum/d
US gal/secgal/s
Configuration and Use Manual23
Page 30
Configure process measurement
Label
Unit description
U.S. gallons per minute
U.S. gallons per hour
U.S. gallons per day
Million U.S. gallons per day
Liters per second
Liters per minute
Liters per hour
Million liters per day
Imperial gallons per second
Imperial gallons per minute
Imperial gallons per hour
Imperial gallons per day
Barrels per second
Barrels per minute
Barrels per hour
Barrels per day
Beer barrels per second
Beer barrels per minute
Beer barrels per hour
Beer barrels per day
(1)
(1)
(1)
(1)
(2)
(2)
(2)
(2)
Special unit
(1) Unit based on oil barrels (42 U.S. gallons).
(2) Unit based on U.S. beer barrels (31 U.S. gallons).
ProLink IIIField Communicator
US gal/mingal/min
US gal/hrgal/h
US gal/daygal/d
mil US gal/dayMMgal/d
l/secL/s
l/minL/min
l/hrL/h
mil l/dayML/d
Imp gal/secImpgal/s
Imp gal/minImpgal/min
Imp gal/hrImpgal/h
Imp gal/dayImpgal/d
barrels/secbbl/s
barrels/minbbl/min
barrels/hrbbl/h
barrels/daybbl/d
Beer barrels/secbbbl/s
Beer barrels/minbbbl/min
Beer barrels/hrbbbl/h
Beer barrels/daybbbl/d
specialSpcl
Define a special measurement unit for volume flow
ProLink III
Field Communicator Configure > Manual Setup > Measurements > Special Units > Volume Special Units
Overview
A special measurement unit is a user-defined unit of measure that allows you to report
process data, totalizer data, and inventory data in a unit that is not available in the
transmitter. A special measurement unit is calculated from an existing measurement unit
using a conversion factor.
24Micro Motion Model 1500 Transmitters with Analog Outputs
Device Tools > Configuration > Process Measurement > Flow > Special Units
Page 31
Configure process measurement
Procedure
1.Specify Base Volume Unit.
Base Volume Unit is the existing volume unit that the special unit will be based on.
2.Specify Base Time Unit.
Base Time Unit is the existing time unit that the special unit will be based on.
3.Calculate Volume Flow Conversion Factor as follows:
a. x base units = y special units
b. Volume Flow Conversion Factor = x ÷ y
4.Enter Volume Flow Conversion Factor.
The original volume flow rate value is divided by this conversion factor.
5.Set Volume Flow Label to the name you want to use for the volume flow unit.
6.Set Volume Total Label to the name you want to use for the volume total and
volume inventory unit.
The special measurement unit is stored in the transmitter. You can configure the
transmitter to use the special measurement unit at any time.
4.2.3
Example: Defining a special measurement unit for volume flow
You want to measure volume flow in pints per second (pints/sec).
1.Set Base Volume Unit to Gallons (gal).
2.Set Base Time Unit to Seconds (sec).
3.Calculate the conversion factor:
a. 1 gal/sec = 8 pints/sec
b. Volume Flow Conversion Factor = 1 ÷ 8 = 0.1250
4.Set Volume Flow Conversion Factor to 0.1250.
5.Set Volume Flow Label to pints/sec.
6.Set Volume Total Label to pints.
Configure Volume Flow Cutoff
ProLink IIIDevice Tools > Configuration > Process Measurement > Flow
Volume Flow Cutoff specifies the lowest volume flow rate that will be reported as
measured. All volume flow rates below this cutoff are reported as 0.
Configuration and Use Manual25
Page 32
Configure process measurement
Procedure
Set Volume Flow Cutoff to the value you want to use.
The default value for Volume Flow Cutoff is 0.0 l/sec (liters per second). The lower limit is
0.
Interaction between Volume Flow Cutoff and mAO Cutoff
Volume Flow Cutoff defines the lowest liquid volume flow value that the transmitter will
report as measured. mAO Cutoff defines the lowest flow rate that will be reported via the
mA Output. If mA Output Process Variable is set to Volume Flow Rate, the volume flow rate
reported via the mA Output is controlled by the higher of the two cutoff values.
Volume Flow Cutoff affects both the volume flow values reported via the outputs and the
volume flow values used in other transmitter behavior (e.g., events defined on the volume
flow).
mAO Cutoff affects only flow values reported via the mA Output.
Example: Cutoff interaction with mAO Cutoff lower than Volume Flow Cutoff
Configuration:
•mA Output Process Variable: Volume Flow Rate
•Frequency Output Process Variable: Volume Flow Rate
•AO Cutoff: 10 l/sec
•Volume Flow Cutoff: 15 l/sec
Result: If the volume flow rate drops below 15 l/sec, volume flow will be reported as 0, and
0 will be used in all internal processing.
Example: Cutoff interaction with mAO Cutoff higher than Volume Flow Cutoff
Configuration:
•mA Output Process Variable: Volume Flow Rate
•Frequency Output Process Variable: Volume Flow Rate
•AO Cutoff: 15 l/sec
•Volume Flow Cutoff: 10 l/sec
Result:
•If the volume flow rate drops below 15 l/sec but not below 10 l/sec:
-The mA Output will report zero flow.
-The Frequency Output will report the actual flow rate, and the actual flow rate
will be used in all internal processing.
•If the volume flow rate drops below 10 l/sec, both outputs will report zero flow, and
0 will be used in all internal processing.
26Micro Motion Model 1500 Transmitters with Analog Outputs
Page 33
Configure process measurement
4.3Configure GSV flow measurement
The gas standard volume (GSV) flow measurement parameters control how volume flow is
measured and reported in a gas application.
Restriction
You cannot implement both liquid volume flow and gas standard volume flow at the same time.
Choose one or the other.
4.3.1Configure Volume Flow Type for gas applications
ProLink IIIDevice Tools > Configuration > Process Measurement > Flow
Field Communicator Configure > Manual Setup > Measurements > GSV > Volume Flow Type
Overview
Volume Flow Type controls whether liquid or gas standard volume flow measurement is
used.
4.3.2
Restriction
Gas standard volume measurement is incompatible with some applications. Set Volume Flow Type
to Liquid if you are using any of the following applications:
•Production Volume Reconciliation (PVR)
Procedure
Set Volume Flow Type to Gas Standard Volume.
Configure Standard Density of Gas
ProLink IIIDevice Tools > Configuration > Process Measurement > Flow
Field Communicator Configure > Manual Setup > Measurements > GSV > Gas Ref Density
Overview
The Standard Density of Gas value is the gas density at standard reference conditions. Use
it to convert the measured mass flow data to volume flow at reference conditions.
Prerequisites
Ensure that Density Measurement Unit is set to the measurement unit you want to use for
Standard Density of Gas.
Configuration and Use Manual27
Page 34
Configure process measurement
Procedure
From the Source field, choose the method to supply gas base density data and perform the
required setup.
OptionDescription
Fixed Value or Digital
Communications
Poll for external value The meter polls an external HART device for gas base density data in order
Configure fixed value or digital communications
Prerequisites
Section 4.3.2
A host writes gas base density data to the meter at appropriate intervals.
Continue to Configure fixed value or digital communications.
to then compute gas standard volume from the mass flow and gas base
density.
Continue to Poll for external value.
Procedure
1.Set Standard Density of Gas to the standard reference density of the gas you are
measuring.
Note
ProLink III provides a guided method that you can use to calculate your gas base density, if
you do not know it.
2.Continue to Section 4.3.3.
Poll for external value
Prerequisites
Section 4.3.2
Procedure
1.Set Polling Slot to an available slot.
2.Set Polling Control n as one of the following options:
The n is the value you selected in the Polling Slot field.
If there is another master, and if that master is primary, then set this field to
secondary. If the other master is secondary, then set this field to primary.
Option
Poll as Primary
Description
No other HART masters will be on the network.
28Micro Motion Model 1500 Transmitters with Analog Outputs
Page 35
Configure process measurement
OptionDescription
Poll as Secondary
3.Set External Device Tag n to the HART tag of the device being polled.
The n is the value you selected in the Polling Slot field.
• The device being polled (slave) cannot have special units set for density.
Otherwise, the master will reject the base density and report the following alarm:
A115: No External Input or Polled Data Alert
• On the slave side, setup the HART Primary Variable for Base Density. The master
will reject anything other than Base Density for the HART Primary Variable and
trigger an A115 alarm.
• The density units on the transmitter and the polled device can be different as
long as they can be classified as density units; for example, kg/m3 and g/cm3.
The transmitter converts the polled units into compatible specified units.
For wiring and setup instructions for a polled device, refer to the Micro Motion Gas
Density Meters (GDM) Installation manual or the Micro Motion Specific Gravity Meters
(SGM) Installation manual.
4.Continue to Section 4.3.3.
Other HART masters will be on the network.
4.3.3
Configure Gas Standard Volume Flow Unit
ProLink IIIDevice Tools > Configuration > Process Measurement > Flow
Field Communicator Configure > Manual Setup > Measurements > GSV > GSV Flow Unit
Overview
Gas Standard Volume Flow Unit specifies the unit of measure that will be displayed for the
gas standard volume flow. The measurement unit used for the gas volume total and the
gas volume inventory is derived from this unit.
Prerequisites
Before you configure Gas Standard Volume Flow Unit, be sure that Volume Flow Type is set
to Gas Standard Volume.
For polling, the first transmitter (master) requests density from a second transmitter
(slave) via HART communications. Special units for GSV are allowed on the master side,
but the device being polled (slave) cannot have special units set for density, otherwise the
master will reject the base density and report an A115: No External Input or Polled Data
Alert.
Procedure
Set Gas Standard Volume Flow Unit to the unit you want to use.
Configuration and Use Manual29
Page 36
Configure process measurement
The default setting for Gas Standard Volume Flow Unit is SCFM (Standard Cubic Feet per
Minute).
Tip
If the measurement unit you want to use is not available, you can define a special measurement unit.
Options for Gas Standard Volume Flow Unit
The transmitter provides a standard set of measurement units for Gas Standard Volume
Flow Unit, plus one user-defined special measurement unit. Different communications
tools may use different labels for the units.
Label
Unit description
Normal cubic meters per second
Normal cubic meters per minute
Normal cubic meters per hour
Normal cubic meters per day
Normal liters per second
Normal liters per minute
Normal liters per hour
Normal liters per day
Standard cubic feet per second
Standard cubic feet per minute
Standard cubic feet per hour
Standard cubic feet per day
Standard cubic meters per second
Standard cubic meters per minute
Standard cubic meters per hour
Standard cubic meters per day
Standard liters per second
Standard liters per minute
Standard liters per hour
Standard liters per day
Special measurement unit
ProLink IIIField Communicator
Nm3/secNm3/sec
Nm3/secNm3/min
Nm3/hrNm3/hr
Nm3/dayNm3/day
NLPSNLPS
NLPMNLPM
NLPHNLPH
NLPDNLPD
SCFSSCFS
SCFMSCFM
SCFHSCFH
SCFDSCFD
Sm3/secSm3/sec
Sm3/minSm3/min
Sm3/hrSm3/hr
Sm3/daySm3/day
SLPSSLPS
SLPMSLPM
SLPHSLPH
SLPDSLPD
specialSpecial
30Micro Motion Model 1500 Transmitters with Analog Outputs
Page 37
Configure process measurement
Define a special measurement unit for gas standard volume
flow
ProLink IIIDevice Tools > Configuration > Process Measurement > Flow > Special Units
Field Communicator Configure > Manual Setup > Measurements > Special Units > Special GSV Units
Overview
A special measurement unit is a user-defined unit of measure that allows you to report
process data, totalizer data, and inventory data in a unit that is not available in the
transmitter. A special measurement unit is calculated from an existing measurement unit
using a conversion factor.
Procedure
1.Specify Base Gas Standard Volume Unit.
Base Gas Standard Volume Unit is the existing gas standard volume unit that the
special unit will be based on.
2.Specify Base Time Unit.
Base Time Unit is the existing time unit that the special unit will be based on.
3.Calculate Gas Standard Volume Flow Conversion Factor as follows:
a. x base units = y special units
b. Gas Standard Volume Flow Conversion Factor = x ÷ y
4.Enter the Gas Standard Volume Flow Conversion Factor.
The original gas standard volume flow value is divided by this conversion factor.
5.Set Gas Standard Volume Flow Label to the name you want to use for the gas
standard volume flow unit.
6.Set Gas Standard Volume Total Label to the name you want to use for the gas
standard volume total and gas standard volume inventory unit.
The special measurement unit is stored in the transmitter. You can configure the
transmitter to use the special measurement unit at any time.
Example: Defining a special measurement unit for gas standard volume flow
You want to measure gas standard volume flow in thousands of standard cubic feet per
minute.
1.Set Base Gas Standard Volume Unit to SCF.
2.Set Base Time Unit to minutes (min).
3.Calculate the conversion factor:
a. 1 thousands of standard cubic feet per minute = 1000 cubic feet per minute
b. Gas Standard Volume Flow Conversion Factor = 1 ÷ 1000 = 0.001 standard
Configuration and Use Manual31
Page 38
Configure process measurement
4.Set Gas Standard Volume Flow Conversion Factor to 0.001.
5.Set Gas Standard Volume Flow Label to MSCFM.
6.Set Gas Standard Volume Total Label to MSCF.
4.3.4Configure Gas Standard Volume Flow Cutoff
ProLink IIIDevice Tools > Configuration > Process Measurement > Flow
Gas Standard Volume Flow Cutoff specifies the lowest gas standard volume flow rate that
will reported as measured. All gas standard volume flow rates below this cutoff will be
reported as 0.
Procedure
Set Gas Standard Volume Flow Cutoff to the value you want to use.
The default value for Gas Standard Volume Flow Cutoff is 0.0. The lower limit is 0.0. There
is no upper limit.
Interaction between Gas Standard Volume Flow Cutoff and
mA Output Cutoff
Gas Standard Volume Flow Cutoff defines the lowest Gas Standard Volume flow value that
the transmitter will report as measured. mA Output Cutoff defines the lowest flow rate
that will be reported via the mA Output. If mA Output Process Variable is set to GasStandard Volume Flow Rate, the volume flow rate reported via the mA Output is controlled by
the higher of the two cutoff values.
Gas Standard Volume Flow Cutoff affects both the gas standard volume flow values
reported via outputs and the gas standard volume flow values used in other transmitter
behavior (e.g., events defined on gas standard volume flow).
mA Output Cutoff affects only flow values reported via the mA Output.
Example: Cutoff interaction with mA Output Cutoff lower than Gas Standard Volume
Flow Cutoff
Configuration:
•mA Output Process Variable for the primary mA Output: Gas Standard Volume Flow
Rate
•Frequency Output Process Variable: Gas Standard Volume Flow Rate
•mA Output Cutoff for the primary mA Output: 10 SLPM (standard liters per minute)
•Gas Standard Volume Flow Cutoff: 15 SLPM
32Micro Motion Model 1500 Transmitters with Analog Outputs
Page 39
Configure process measurement
Result: If the gas standard volume flow rate drops below 15 SLPM, the volume flow will be
reported as 0, and 0 will be used in all internal processing.
Example: Cutoff interaction with mA Output Cutoff higher than Gas Standard Volume
Flow Cutoff
Configuration:
•mA Output Process Variable for the primary mA Output: Gas Standard Volume Flow
Rate
•Frequency Output Process Variable: Gas Standard Volume Flow Rate
•mA Output Cutoff for the primary mA Output: 15 SLPM (standard liters per minute)
•Gas Standard Volume Flow Cutoff: 10 SLPM
Result:
•If the gas standard volume flow rate drops below 15 SLPM but not below 10 SLPM:
-The primary mA Output will report zero flow.
-The Frequency Output will report the actual flow rate, and the actual flow rate
will be used in all internal processing.
•If the gas standard volume flow rate drops below 10 SLPM, both outputs will report
zero flow, and 0 will be used in all internal processing.
4.4
Configure Flow Direction
ProLink IIIDevice Tools > Configuration > Process Measurement > Flow
Field Communicator Configure > Manual Setup > Measurements > Flow > Flow Direction
Overview
Flow Direction controls how forward flow and reverse flow affect flow measurement and
reporting.
Flow Direction is defined with respect to the flow arrow on the sensor:
•Forward flow (positive flow) moves in the direction of the flow arrow on the sensor.
•Reverse flow (negative flow) moves in the direction opposite to the flow arrow on
the sensor.
Tip
Micro Motion sensors are bidirectional. Measurement accuracy is not affected by actual flow
direction or the setting of the Flow Direction parameter.
Procedure
Set Flow Direction to the value you want to use.
Configuration and Use Manual33
Page 40
Configure process measurement
The default setting is Forward.
4.4.1Options for Flow Direction
Flow Direction setting
ForwardForward
ReverseReverse
Absolute ValueAbsolute Value
BidirectionalBi directional
Negate ForwardNegate/Forward Only
Negate BidirectionalNegate/Bi-directional
Relationship to Flow Direction arrow
on sensorProLink IIIField Communicator
Appropriate when the Flow Direction arrow is in the same direction as the majority of flow.
Appropriate when the Flow Direction arrow is in the opposite direction from the
majority of flow.
Flow Direction arrow is not relevant.
Appropriate when both forward and reverse flow are expected, and forward
flow will dominate, but the amount of reverse flow will be significant.
Appropriate when the Flow Direction arrow is in the opposite direction from the
majority of flow.
Appropriate when both forward and reverse flow are expected, and reverse flow
will dominate, but the amount of forward flow will be significant.
Effect of Flow Direction on mA Outputs
Flow Direction affects how the transmitter reports flow values via the mA Outputs. The mA
Outputs are affected by Flow Direction only if mA Output Process Variable is set to a flow
variable.
Flow Direction and mA Outputs
The effect of Flow Direction on the mA Outputs depends on Lower Range Value configured
for the mA Output:
•If Lower Range Value is set to 0, see Figure 4‐1.
•If Lower Range Value is set to a negative value, see Figure 4‐2.
34Micro Motion Model 1500 Transmitters with Analog Outputs
Page 41
Configure process measurement
Effect of Flow Direction on the mA Output: Lower Range Value = 0Figure 4-1:
Flow Direction = Forward
20
12
mA output
4
-x0x
Reverse flowForward flow
•Lower Range Value = 0
•Upper Range Value = x
Effect of Flow Direction on the mA Output: Lower Range Value < 0Figure 4-2:
Flow Direction = Forward
20
Flow Direction = Reverse, Negate Forward
20
12
mA output
4
-x0x
Reverse flowForward flow
Flow Direction = Reverse, Negate Forward
20
Flow Direction = Absolute Value, Bidirectional,
Negate Bidirectional
20
12
mA output
4
-x0x
Reverse flowForward flow
Flow Direction = Absolute Value, Bidirectional,
Negate Bidirectional
20
12
mA output
4
-x0x
Reverse flowForward flow
12
mA output
4
-x0x
Reverse flowForward flow
12
mA output
4
-x0x
Reverse flowForward flow
•Lower Range Value = −x
•Upper Range Value = x
Example: Flow Direction = Forward and Lower Range Value = 0
Configuration:
•Flow Direction = Forward
•Lower Range Value = 0 g/sec
•Upper Range Value = 100 g/sec
Configuration and Use Manual35
Page 42
Configure process measurement
Result:
•Under conditions of zero flow, the mA Output is 4 mA.
•Under conditions of forward flow, up to a flow rate of 100 g/sec, the mA Output
•Under conditions of forward flow, if the flow rate equals or exceeds 100 g/sec, the
Example: Flow Direction = Forward and Lower Range Value < 0
Configuration:
•Flow Direction = Forward
•Lower Range Value = −100 g/sec
•Upper Range Value = +100 g/sec
Result:
•Under conditions of zero flow, the mA Output is 12 mA.
•Under conditions of forward flow, for flow rates between 0 and +100 g/sec, the mA
•Under conditions of forward flow, if (the absolute value of) the flow rate equals or
•Under conditions of reverse flow, for flow rates between 0 and −100 g/sec, the mA
•Under conditions of reverse flow, if the absolute value of the flow rate equals or
varies between 4 mA and 20 mA in proportion to the flow rate.
mA Output will be proportional to the flow rate up to 20.5 mA, and will be level at
20.5 mA at higher flow rates.
Output varies between 12 mA and 20 mA in proportion to (the absolute value of)
the flow rate.
exceeds 100 g/sec, the mA Output is proportional to the flow rate up to 20.5 mA,
and will be level at 20.5 mA at higher flow rates.
Output varies between 4 mA and 12 mA in inverse proportion to the absolute value
of the flow rate.
exceeds 100 g/sec, the mA Output is inversely proportional to the flow rate down to
3.8 mA, and will be level at 3.8 mA at higher absolute values.
Example: Flow Direction = Reverse
Configuration:
•Flow Direction = Reverse
•Lower Range Value = 0 g/sec
•Upper Range Value = 100 g/sec
Result:
•Under conditions of zero flow, the mA Output is 4 mA.
•Under conditions of reverse flow, for flow rates between 0 and +100 g/sec, the mA
Output level varies between 4 mA and 20 mA in proportion to the absolute value of
the flow rate.
•Under conditions of reverse flow, if the absolute value of the flow rate equals or
exceeds 100 g/sec, the mA Output will be proportional to the absolute value of the
flow rate up to 20.5 mA, and will be level at 20.5 mA at higher absolute values.
36Micro Motion Model 1500 Transmitters with Analog Outputs
Page 43
Configure process measurement
Effect of flow direction on Frequency Outputs
Flow direction affects how the transmitter reports flow values via the Frequency Outputs.
The Frequency Outputs are affected by flow direction only if Frequency Output Process
Variable is set to a flow variable.
Table 4-1:
Effect of the flow direction parameter and actual flow direction on
Frequency Outputs
Actual flow direction
Flow Direction setting
Forward
Reverse
Bidirectional
Absolute Value
Negate Forward
Negate Bidirectional
ForwardZero flowReverse
Hz > 00 Hz0 Hz
0 Hz0 HzHz > 0
Hz > 00 HzHz > 0
Hz > 00 HzHz > 0
0 Hz0 HzHz > 0
Hz > 00 HzHz > 0
Effect of flow direction on Discrete Outputs
The flow direction parameter affects the Discrete Output behavior only if Discrete Output
Source is set to Flow Direction.
Table 4-2:
Discrete Outputs
Effect of the flow direction parameter and actual flow direction on
Actual flow direction
Flow Direction setting
Forward
Reverse
Bidirectional
Absolute Value
Negate Forward
Negate Bidirectional
ForwardZero flowReverse
OFFOFFON
OFFOFFON
OFFOFFON
OFFOFFON
ONOFFOFF
ONOFFOFF
Effect of flow direction on digital communications
Flow direction affects how flow values are reported via digital communications. The
following table describes the effect of the flow direction parameter and actual flow
direction on flow values reported via digital communications.
Configuration and Use Manual37
Page 44
Configure process measurement
Effect of the flow direction on flow valuesTable 4-3:
Actual flow direction
Flow Direction setting
Forward
Reverse
Bidirectional
Absolute Value
Negate Forward
Negate Bidirectional
(1) Refer to the digital communications status bits for an indication of whether flow is positive or negative.
ForwardZero flowReverse
Positive0Negative
Positive0Negative
Positive0Negative
Positive
Negative0Positive
Negative0Positive
(1)
0Positive
Effect of flow direction on flow totals
Flow direction affects how flow totals and inventories are calculated.
Actual flow direction
Flow Direction setting
Forward
Reverse
Bidirectional
Absolute Value
Negate Forward
Negate Bidirectional
ForwardZero flowReverse
Totals increaseTotals do not changeTotals do not change
Totals do not changeTotals do not changeTotals increase
Totals increaseTotals do not changeTotals decrease
Totals increaseTotals do not changeTotals increase
Totals do not changeTotals do not changeTotals increase
Totals decreaseTotals do not changeTotals increase
(1)
4.5Configure density measurement
The density measurement parameters control how density is measured and reported.
4.5.1
38Micro Motion Model 1500 Transmitters with Analog Outputs
Configure Density Measurement Unit
ProLink IIIDevice Tools > Configuration > Process Measurement > Density
Field Communicator Configure > Manual Setup > Measurements > Density > Density Unit
Overview
Density Measurement Unit controls the measurement units that will be used in density
calculations and reporting.
Page 45
Configure process measurement
Procedure
Set Density Measurement Unit to the option you want to use.
The default setting for Density Measurement Unit is g/cm3 (grams per cubic centimeter).
Options for Density Measurement Unit
The transmitter provides a standard set of measurement units for Density Measurement
Unit. Different communications tools may use different labels.
Label
Unit description
Specific gravity unit
Grams per cubic centimeter
Grams per liter
Grams per milliliter
Kilograms per liter
Kilograms per cubic meter
Pounds per U.S. gallon
Pounds per cubic foot
Pounds per cubic inch
Degrees API
Short ton per cubic yard
(1) Non‐standard calculation. This value represents line density divided by the density of water at 60 °F.
4.5.2
(1)
Configure two-phase flow parameters
ProLink IIIDevice Tools > Configuration > Process Measurement > Density
Field Communicator • Configure > Manual Setup > Measurements > Density > Slug Low Limit
• Configure > Manual Setup > Measurements > Density > Slug High Limit
The two-phase flow parameters control how the transmitter detects and reports twophase flow (gas in a liquid process or liquid in a gas process).
Note
Two-phase flow is also referred to as slug flow.
Configuration and Use Manual39
Page 46
Configure process measurement
Procedure
1.Set Two-Phase Flow Low Limit to the lowest density value that is considered normal
2.Set Two-Phase Flow High Limit to the highest density value that is considered
in your process.
Values below this will cause the transmitter to post Alert A105 (Two-Phase Flow).
Tip
Gas entrainment can cause your process density to drop temporarily. To reduce the
occurrence of two-phase flow alerts that are not significant to your process, set Two-Phase
Flow Low Limit slightly below your expected lowest process density.
You must enter Two-Phase Flow Low Limit in g/cm³, even if you configured another
unit for density measurement.
The default value for Two-Phase Flow Low Limit is 0.0 g/cm³. The range is 0.0 to
10.0 g/cm³.
normal in your process.
Micro Motion recommends leaving Two-Phase Flow High Limit at the default value.
Values above this will cause the transmitter to post Alert A105 (Two-Phase Flow).
You must enter Two-Phase Flow High Limit in g/cm³, even if you configured another
unit for density measurement.
The default value for Two-Phase Flow High Limit is 5.0 g/cm³. The range is 0.0 to
10.0 g/cm³.
3.Set Two-Phase Flow Timeout to the number of seconds that the transmitter will wait
for a two-phase flow condition to clear before posting the alert.
The default value for Two-Phase Flow Timeout is 0.0 seconds, meaning that the alert
will be posted immediately. The range is 0.0 to 60.0 seconds.
Detecting and reporting two-phase flow
Two-phase flow (gas in a liquid process or liquid in a gas process) can cause a variety of
process control issues. By configuring the two-phase flow parameters appropriately for
your application, you can detect process conditions that require correction.
Micro Motion recommends leaving Two-Phase Flow High Limit at the default value.
A two-phase flow condition occurs whenever the measured density goes below Two-Phase
Flow Low Limit or above Two-Phase Flow High Limit. If this occurs:
•A two-phase flow alert is posted to the active alert log.
•All outputs that are configured to represent flow rate hold their last pre‐alert value
for the number of seconds configured in Two-Phase Flow Timeout.
If the two-phase flow condition clears before Two-Phase Flow Timeout expires:
•Outputs that represent flow rate revert to reporting actual flow.
40Micro Motion Model 1500 Transmitters with Analog Outputs
Page 47
•The two-phase flow alert is deactivated, but remains in the active alert log until it is
acknowledged.
If the two-phase flow condition does not clear before Two-Phase Flow Timeout expires, the
outputs that represent flow rate report a flow rate of 0.
If Two-Phase Flow Timeout is set to 0.0 seconds, the outputs that represent flow rate will
report a flow rate of 0 as soon as two-phase flow is detected.
4.5.3Configure Density Damping
ProLink IIIDevice Tools > Configuration > Process Measurement > Density
Field Communicator Configure > Manual Setup > Measurements > Density > Density Damping
Overview
Density Damping controls the amount of damping that will be applied to the line density
value.
Configure process measurement
Damping is used to smooth out small, rapid fluctuations in process measurement.
Damping Value specifies the time period (in seconds) over which the transmitter will
spread changes in the process variable. At the end of the interval, the internal value will
reflect 63% of the change in the actual measured value.
Tip
Density damping affects all process variables that are calculated from line density.
Procedure
Set Density Damping to the value you want to use.
The default value is 1.6 seconds. The range depends on the core processor type and the
setting of Update Rate, as shown in the following table:
Update Rate setting
Normal
Special
Tips
• A high damping value makes the process variable appear smoother because the reported value
changes slowly.
• A low damping value makes the process variable appear more erratic because the reported value
changes more quickly.
• Whenever the damping value is non-zero, the reported measurement will lag the actual
measurement because the reported value is being averaged over time.
Damping range
0 to 51.2 seconds
0 to 40.96 seconds
Configuration and Use Manual41
Page 48
Configure process measurement
• In general, lower damping values are preferable because there is less chance of data loss, and less
lag time between the actual measurement and the reported value.
The value you enter is automatically rounded off to the nearest valid value. The valid values
for Density Damping depend on the setting of Update Rate.
Update Rate settingValid damping values
Normal
Special
Effect of Density Damping on volume measurement
Density Damping affects liquid volume measurement. Liquid volume values are calculated
from the damped density value rather than the measured density value. Density Damping
does not affect gas standard volume measurement.
Interaction between Density Damping and Added Damping
When the mA Output is configured to report density, both Density Damping and Added
Damping are applied to the reported density value.
Density Damping controls the rate of change in the value of the process variable in
transmitter memory. Added Damping controls the rate of change reported via the mA
Output.
If mA Output Process Variable is set to Density, and both Density Damping and Added
Damping are set to non-zero values, density damping is applied first, and the added
damping calculation is applied to the result of the first calculation. This value is reported
over the mA Output.
Configure Density Cutoff
Density Cutoff specifies the lowest density value that will be reported as measured. All
density values below this cutoff will be reported as 0.
Procedure
Set Density Cutoff to the value you want to use.
For most applications, the default setting (0.2 g/cm³) is sufficient. The range is 0.0 g/cm³
to 0.5 g/cm³.
Effect of Density Cutoff on volume measurement
Density Cutoff affects liquid volume measurement. If the density value goes below Density
Cutoff, the volume flow rate is reported as 0. Density Cutoff does not affect gas standard
volume measurement. Gas standard volume values are always calculated from the value
configured for Standard Gas Density or polled value if configured for polled base density.
42Micro Motion Model 1500 Transmitters with Analog Outputs
Page 49
Configure process measurement
4.6Configure temperature measurement
The temperature measurement parameters control how temperature data from the
sensor is reported.
4.6.1Configure Temperature Measurement Unit
ProLink IIIDevice Tools > Configuration > Process Measurement > Temperature
Field Communicator Configure > Manual Setup > Measurements > Temperature > Temperature Unit
Overview
Temperature Measurement Unit specifies the unit that will be used for temperature
measurement.
Procedure
Set Temperature Measurement Unit to the option you want to use.
The default setting is Degrees Celsius.
Options for Temperature Measurement Unit
The transmitter provides a standard set of units for Temperature Measurement Unit.
Different communications tools may use different labels for the units.
Unit description
Degrees Celsius
Degrees Fahrenheit
Degrees Rankine
Kelvin
ProLink IIIField Communicator
°CdegC
°FdegF
°RdegR
°KKelvin
4.6.2Configure Temperature Damping
ProLink IIIDevice Tools > Configuration > Temperature
Field Communicator Configure > Manual Setup > Measurements > Temperature > Temp Damping
Label
Overview
Temperature Damping controls the amount of damping that will be applied to the line
temperature value, when the on-board temperature data is used (RTD).
Configuration and Use Manual43
Page 50
Configure process measurement
Damping is used to smooth out small, rapid fluctuations in process measurement.
Damping Value specifies the time period (in seconds) over which the transmitter will
spread changes in the process variable. At the end of the interval, the internal value will
reflect 63% of the change in the actual measured value.
Tip
Temperature Damping affects all process variables, compensations, and corrections that use
temperature data from the sensor.
Procedure
Enter the value you want to use for Temperature Damping.
The default value is 4.8 seconds. The range is 0.0 to 38.4 seconds.
Tips
• A high damping value makes the process variable appear smoother because the reported value
changes slowly.
• A low damping value makes the process variable appear more erratic because the reported value
changes more quickly.
• Whenever the damping value is non-zero, the reported measurement will lag the actual
measurement because the reported value is being averaged over time.
• In general, lower damping values are preferable because there is less chance of data loss, and less
lag time between the actual measurement and the reported value.
4.6.3
4.7
The value you enter is automatically rounded off to the nearest valid value. Valid values for
Temperature Damping are 0, 0.6, 1.2, 2.4, 4.8, … 38.4.
Effect of Temperature Damping on process
measurement
Temperature Damping affects all processes and algorithms that use temperature data
from the internal sensor RTD.
Temperature compensation
Temperature compensation adjusts process measurement to compensate for the effect of
temperature on the sensor tubes.
Configure pressure compensation
Pressure compensation adjusts process measurement to compensate for the pressure
effect on the sensor. The pressure effect is the change in the sensor’s sensitivity to flow
and density caused by the difference between the calibration pressure and the process
pressure.
44Micro Motion Model 1500 Transmitters with Analog Outputs
Page 51
Configure process measurement
Tip
Not all sensors or applications require pressure compensation. The pressure effect for a specific
sensor model can be found in the product data sheet located at www.emerson.com. If you are
uncertain about implementing pressure compensation, contact customer service.
Prerequisites
You will need the flow factor, density factor, and calibration pressure values for your
sensor.
•For the flow factor and density factor, see the product data sheet for your sensor.
•For the calibration pressure, see the calibration sheet for your sensor. If the data is
unavailable, use 20 PSI.
4.7.1Configure pressure compensation using ProLink III
If you will use an external pressure value, set Pressure Unit to match the pressure
unit used by the external pressure device.
4.Enter Flow Calibration Pressure for your sensor.
The calibration pressure is the pressure at which your sensor was calibrated, and
defines the pressure at which there is no pressure effect. If the data is unavailable,
enter 20 PSI.
5.Enter Flow Factor for your sensor.
The flow factor is the percent change in the flow rate per PSI. When entering the
value, reverse the sign.
Example: If the flow factor is 0.000004 % per PSI, enter −0.000004 % per PSI.
6.Enter Density Factor for your sensor.
The density factor is the change in fluid density, in g/cm3/PSI. When entering the
value, reverse the sign.
Example:
If the density factor is 0.000006 g/cm3/PSI, enter −0.000006g/cm3/PSI.
7.Set Pressure Source to the method that the transmitter will use to obtain pressure
data.
Option
Poll for external value
Description
The transmitter will poll an external pressure device, using
HART protocol over the primary mA Output.
Configuration and Use Manual45
Page 52
Configure process measurement
8.If you chose to poll for pressure data:
OptionDescription
Fixed Value or Digital Communications
a. Select the Polling Slot to use.
b. Set Polling Control to Poll as Primary or Poll as Secondary, and click Apply.
Tip
• Poll as Primary: No other HART masters will be on the network.
• Poll as Secondary: Other HART masters will be on the network. The Field Communicator
is not a HART master.
c. Set External Device Tag to the HART tag of the external pressure device, and click
Apply.
d. Ensure that the primary mA Output is wired to support HART communications
with the external pressure device.
The transmitter will use the pressure value that it reads from
memory.
• Fixed Value: The configured value is used.
• Digital Communications: A host writes transmitter data
to transmitter memory.
4.7.2
9.If you chose to use a fixed pressure value:
a. Set Fixed Value to the value to use, and click Apply
10.If you want to use digital communications, click Apply, then perform the necessary
host programming and communications setup to write pressure data to the
transmitter at appropriate intervals.
Postrequisites
If you are using an external pressure value, verify the setup by checking the External
Pressure value displayed in the Inputs area of the main window.
Configure pressure compensation using the Field
Communicator
The calibration pressure is the pressure at which your sensor was calibrated, and
defines the pressure at which there is no pressure effect. If the data is unavailable,
enter 20 PSI.
4.Enter Flow Press Factor for your sensor.
46Micro Motion Model 1500 Transmitters with Analog Outputs
Page 53
Configure process measurement
The flow factor is the percent change in the flow rate per PSI. When entering the
value, reverse the sign.
Example:
If the flow factor is 0.000004 % per PSI, enter −0.000004 % per PSI.
5.Enter Dens Press Factor for your sensor.
The density factor is the change in fluid density, in g/cm3/PSI. When entering the
value, reverse the sign.
Example:
If the density factor is 0.000006 g/cm3/PSI, enter −0.000006g/cm3/PSI.
6.Determine how the transmitter will obtain pressure data, and perform the required
setup.
Option
A user-configured
static pressure value
Polling for pressurea. Ensure that the primary mA Output has been wired to support
A value written by
digital communications
Setup
a. Set Pressure Unit to the desired unit.
b. Set Compensation Pressure to the desired value.
External Pressure/Temperature > External Polling .
c. Set Poll Control to Poll As Primary Host or Poll as Secondary Host.
d. Choose an unused polling slot.
e. Set External Tag to the HART tag of the external pressure device.
f. Set Polled Variable to Pressure.
Tip
• Poll as Primary: No other HART masters will be on the network.
• Poll as Secondary: Other HART masters will be on the network.
The Field Communicator is not a HART master.
a. Set Pressure Unit to the desired unit.
b. Perform the necessary host programming and communications
setup to write pressure data to the transmitter at appropriate in-
tervals.
Postrequisites
If you are using an external pressure value, verify the setup by choosing Service Tools >
Variables > External Variables and checking the value displayed for External Pressure.
Configuration and Use Manual47
Page 54
Configure process measurement
4.7.3Options for Pressure Measurement Unit
The transmitter provides a standard set of measurement units for Pressure Measurement
Unit. Different communications tools may use different labels for the units. In most
applications, Pressure Measurement Unit should be set to match the pressure
measurement unit used by the remote device.
Label
Unit description
Feet water @ 68 °F
Inches water @ 4 °C
Inches water @ 60 °F
Inches water @ 68 °F
Millimeters water @ 4 °C
Millimeters water @ 68 °F
Millimeters mercury @ 0 °C
Inches mercury @ 0 °C
Pounds per square inch
Bar
Millibar
Grams per square centimeter
Kilograms per square centimeter
Pascals
Kilopascals
Megapascals
Torr @ 0 °C
Atmospheres
ProLink IIIField Communicator
Ft Water @ 68°FftH2O
In Water @ 4°CinH2O @4DegC
In Water @ 60°FinH2O @60DegF
In Water @ 68°FinH2O
mm Water @ 4°CmmH2O @4DegC
mm Water @ 68°FmmH2O
mm Mercury @ 0°CmmHg
In Mercury @ 0°CinHG
PSIpsi
barbar
millibarmbar
g/cm2g/Sqcm
kg/cm2kg/Sqcm
pascalsPa
KilopascalskPa
MegapascalsMPa
Torr @ 0°Ctorr
atmsatms
48Micro Motion Model 1500 Transmitters with Analog Outputs
Page 55
Configure device options and preferences
5Configure device options and
preferences
Topics covered in this chapter:
Configure response time parameters
•
Configure alert handling
•
Configure informational parameters
•
5.1Configure response time parameters
You can configure the rate at which process data is polled and process variables are
calculated.
Update Rate controls the rate at which process data is polled and process variables are
calculated. Update Rate = Special produces faster and “noisier” response to changes in the
process. Do not use Special mode unless required by your application.
Tip
For systems with a standard core processor, Special mode can improve performance for applications
with entrained air or Empty-Full-Empty conditions. This does not apply to systems with an enhanced
core processor.
Prerequisites
Before setting Update Rate to Special:
•Check the effects of Special mode on specific process variables.
•Contact customer support.
Procedure
1.Set Update Rate as desired.
Configuration and Use Manual49
Page 56
Configure device options and preferences
Option Description
Normal
Special
If you change Update Rate, the settings for Flow Damping, Density Damping, and
Temperature Damping are automatically adjusted.
2.If you set Update Rate to Special, select the process variable to be polled at 100 Hz.
Effects of Update Rate = Special
All process data is polled at the rate of 20 times per second (20 Hz).
All process variables are calculated at 20 Hz.
This option is appropriate for most applications.
A single, user-specified process variable is polled at the rate of 100 times per second (100 Hz). Other process data is polled at 6.25 Hz. Some process, diagnostic,
and calibration data is not polled.
All available process variables are calculated at 100 Hz.
Use this option only if required by your application.
Incompatible features and functions
Special mode is not compatible with the following features and functions:
•Enhanced events. Use basic events instead.
•All calibration procedures.
•Zero verification.
•Restoring the factory zero or the prior zero.
If required, you can switch to Normal mode, perform the desired procedures, and then
return to Special mode.
Process variable updates
Some process variables are not updated when Special mode is enabled.
50Micro Motion Model 1500 Transmitters with Analog Outputs
Page 57
Special mode and process variable updatesTable 5-1:
Always polled and updated
• Mass flow
• Volume flow
• Gas standard volume flow
• Density
• Temperature
• Drive gain
• LPO amplitude
• Status [contains Event 1 and Event
2 (basic events)]
• Mass total
• Volume total
• Live zero
• Gas standard volume total
Configure device options and preferences
Updated only when the petroleum
measurement application is disabledNever updated
• RPO amplitude
• Core input voltage
• Mass inventory
• Volume inventory
• Gas standard volume inventory
All other process variables and calibration data. They retain the values held
at the time you enabled Special mode.
5.1.2Configure Response Time
ProLink IIIDevice Tools > Configuration > Process Measurement > Response > Response Time
Field Communicator Not available
Overview
Response Time is used to apply a different algorithm to the calculation of process variables
from the raw process data.
Restriction
Response Time is available only on systems with the enhanced core processor.
Procedure
Set Response Time as desired.
Option
Normal (Legacy)
Special (Legacy)
Normal - Optimal Filtering
Description
Transmitter calculates process variables at the standard speed. This option is selected if this parameter was configured on an earlier version of
ProLink III software.
Transmitter calculates process variables at a faster speed. This option is
selected if this parameter was configured on an earlier version of ProLink
III software.
Transmitter calculates process variables at standard filtering and speed.
Configuration and Use Manual51
Page 58
Configure device options and preferences
OptionDescription
Low Filtering - Fastest Response
High Filtering - Smoothest
Output
Service
Transmitter calculates process variables at the fastest speed.
Transmitter calculates process variables at the smoothest (least noisy)
response to changes in the process.
For factory use only.
5.2Configure alert handling
The alert handling parameters control the transmitter’s response to process and device
conditions.
Fault Timeout controls the delay before fault actions are performed.
Restriction
Fault Timeout is applied only to the following alerts (listed by Status Alert Code): A003, A004, A005,
A008, A016, A017, A033. For all other alerts, fault actions are performed as soon as the alert is
detected.
Procedure
Set Fault Timeout as desired.
The default value is 0 seconds. The range is 0 to 60 seconds.
If you set Fault Timeout to 0, fault actions are performed as soon as the alert condition is
detected.
The fault timeout period begins when the transmitter detects an alert condition. During
the fault timeout period, the transmitter continues to report its last valid measurements.
If the fault timeout period expires while the alert is still active, the fault actions are
performed. If the alert condition clears before the fault timeout expires, no fault actions
are performed.
52Micro Motion Model 1500 Transmitters with Analog Outputs
Field Communicator Configure > Manual Setup > Info Parameters > Sensor Information > Sensor Serial Num-
ber
Overview
Sensor Serial Number lets you store the serial number of the sensor component of your
flowmeter in transmitter memory. This parameter is not used in processing and is not
required.
Procedure
1.Obtain the sensor serial number from your sensor tag.
2.Enter the serial number in the Sensor Serial Number field.
56Micro Motion Model 1500 Transmitters with Analog Outputs
Field Communicator Configure > Manual Setup > Info Parameters > Sensor Information > Tube Wetted Mate-
rial
Overview
Sensor Material lets you store the type of material used for your sensor’s wetted parts in
transmitter memory. This parameter is not used in processing and is not required.
Procedure
1.Obtain the material used for your sensor’s wetted parts from the documents
shipped with your sensor, or from a code in the sensor model number.
To interpret the model number, refer to the product data sheet for your sensor.
Field Communicator Configure > Manual Setup > Info Parameters > Sensor Information > Tube Lining
Overview
Sensor Liner Material lets you store the type of material used for your sensor liner in
transmitter memory. This parameter is not used in processing and is not required.
Procedure
1.Obtain your sensor’s liner material from the documents shipped with your sensor, or
from a code in the sensor model number.
To interpret the model number, refer to the product data sheet for your sensor.
2.Set Sensor Liner Material to the appropriate option.
Field Communicator Configure > Manual Setup > Info Parameters > Transmitter Info > Date
Overview
Date lets you store a static date (not updated by the transmitter) in transmitter memory.
This parameter is not used in processing and is not required.
Procedure
Enter the date you want to use, in the form mm/dd/yyyy.
Tip
ProLink III provides a calendar tool to help you select the date.
Configure device options and preferences
Configuration and Use Manual59
Page 66
Configure device options and preferences
60Micro Motion Model 1500 Transmitters with Analog Outputs
Field Communicator Configure > Manual Setup > Inputs/Outputs > Channels > Channel C
Overview
You can configure Channel C on your transmitter to operate as a Frequency Output or a
Discrete Output. The channel configuration must match the wiring at the transmitter
terminals.
Prerequisites
To avoid causing process errors:
•Configure the channels before configuring the outputs.
•Before changing the channel configuration, ensure that all control loops affected by
the channel are under manual control.
Procedure
Set Channel C as desired.
Option
Frequency OutputChannel C will operate as a Frequency Output.
Discrete OutputChannel C will operate as a Discrete Output.
Description
Configuration and Use Manual61
Page 68
Integrate the meter with the control system
Postrequisites
For each channel that you configured, perform or verify the corresponding input or output
configuration. When the configuration of a channel is changed, the channel’s behavior will
be controlled by the configuration that is stored for the selected input or output type, and
the stored configuration may not be appropriate for your process.
After verifying channel and output configuration, return the control loop to automatic
control.
6.2Configure the mA Output
The mA Output is used to report the configured process variable. The mA Output
parameters control how the process variable is reported.
Your transmitter has one mA Output: Channel A.
Restriction
The process variable assigned to the primary mA Output is automatically assigned to the Frequency
Output. You cannot assign a different process variable.
6.2.1
Important
Whenever you change an mA Output parameter, verify all other mA Output parameters before
returning the meter to service. In some situations, the transmitter automatically loads a set of stored
values, and these values may not be appropriate for your application.
Field Communicator Configure > Manual Setup > Inputs/Outputs > mA Output > Primary Variable
Overview
Use mA Output Process Variable to select the variable that is reported over the mA Output.
This variable is applied automatically to the Frequency Output.
Prerequisites
•If you plan to configure the output to report volume flow, ensure that you have set
Volume Flow Type as desired: Liquid or Gas Standard Volume.
•If you are using the HART variables, be aware that changing the configuration of mA
Output Process Variable will change the configuration of the HART Primary Variable
(PV) and the HART Tertiary Variable (TV).
Procedure
Set mA Output Process Variable as desired.
62Micro Motion Model 1500 Transmitters with Analog Outputs
Page 69
Integrate the meter with the control system
The default setting is Mass Flow Rate.
Postrequisites
If you changed the setting of mA Output Process Variable, verify the settings of Lower
Range Value (LRV) and Upper Range Value (URV).
Options for mA Output Process Variable
The transmitter provides a basic set of options for mA Output Process Variable, plus
several application-specific options. Different communications tools may use different
labels for the options.
Standard mA Output process variablesTable 6-1:
Label
Process variable
Gas standard volume flow rate
Mass flow rate
Volume flow rate
PVR mA Output process variablesTable 6-2:
Process variable
Uncorrected oil flow
Uncorrected water cut
Uuncorrected water flow
Corrected oil flow
Corrected water cut
Corrected water flow
Shrinkage factor corrected net oil at
line
Shrinkage factor corrected net oil at
60F
Shrinkage factor corrected volume of
mix at 60F
ProLink IIIField Communicator
Gas Standard Volume Flow RateGas vol flo
Mass Flow RateMass flo
Volume Flow RateVol flo
Label
ProLink IIIField Communicator
Oil Flow Rate At LineOil Flow Rate at Line
Water Cut At LineWater Cut at Line
Water Flow Rate At LineWater Flow Rate at Line
Oil Flow Rate At ReferenceOil Flow Rate at Reference
Water Cut At ReferenceWater Cut at Reference
Water Flow Rate At ReferenceWater Flow Rate at Reference
SF Oil Flow Rate At LineShrinkage Factor Oil Flow Rate at Line
SF Oil Flow Rate At ReferenceShrinkage Factor Oil Flow Rate at Reference
SF Volume Flow Rate At ReferenceShrinkage Factor Volume Flow Rate at Ref-
erence
Configuration and Use Manual63
Page 70
Integrate the meter with the control system
6.2.2Configure Lower Range Value (LRV) and Upper Range
Value (URV)
Field Communicator • Configure > Manual Setup > Inputs/Outputs > mA Output > mA Output Settings >
LRV
• Configure > Manual Setup > Inputs/Outputs > mA Output > mA Output Settings >
URV
Overview
The Lower Range Value (LRV) and Upper Range Value (URV) are used to scale the mA
Output, that is, to define the relationship between mA Output Process Variable and the
mA Output level.
Prerequisites
Ensure that mA Output Process Variable is set to the desired process variable. Each process
variable has its own set of LRV and URV values. When you change the values of LRV and
URV, you are configuring values for the currently assigned mA Output process variable.
Ensure that the measurement unit for the configured process variable has been set as
desired.
Procedure
Set LRV and URV as desired.
• LRVis the value of mA Output Process Variable represented by an output of 4 mA. The
default value for LRV depends on the setting of mA Output Process Variable. Enter LRV
in the measurement units that are configured for mA Output Process Variable.
• URV is the value of mA Output Process Variable represented by an output of 20 mA.
The default value for URV depends on the setting of mA Output Process Variable. Enter
URV in the measurement units that are configured for mA Output Process Variable.
Tip
For best performance:
• Set LRV ≥ LSL (lower sensor limit).
• Set URV ≤ USL (upper sensor limit).
• Set these values so that the difference between URV and LRV is ≥ Min Span (minimum span).
Defining URV and LRV within the recommended values for Min Span, LSL, and USL ensures that the
resolution of the mA Output signal is within the range of the bit precision of the D/A converter.
64Micro Motion Model 1500 Transmitters with Analog Outputs
Page 71
Integrate the meter with the control system
The mA Output uses a range of 4–20 mA to represent mA Output Process Variable.
Between LRV and URV, the mA Output is linear with the process variable. If the process
variable drops below LRV or rises above URV, the transmitter posts an output saturation
alert.
Default values for Lower Range Value (LRV) and Upper Range
Value (URV)
Each option for mA Output Process Variable has its own LRV and URV. If you change the
configuration of mA Output Process Variable, the corresponding LRV and URV are loaded
and used.
Default values for Lower Range Value (LRV) and Upper Range Value (URV)Table 6-3:
Process variableLRVURV
All mass flow variables–200.000 g/sec200.000 g/sec
All liquid volume flow variables –0.200 l/sec0.200 l/sec
Field Communicator Configure > Manual Setup > Inputs/Outputs > mA Output > mA Output Settings > PV
MAO Cutoff
AO Cutoff (Analog Output Cutoff) specifies the lowest mass flow rate, volume flow rate, or
gas standard volume flow rate that will be reported through the mA Output. Any flow rates
below AO Cutoff will be reported as 0.
Restriction
AO Cutoff is applied only if mA Output Process Variable is set to Mass Flow Rate, Volume Flow Rate, or
Gas Standard Volume Flow Rate. If mA Output Process Variable is set to a different process variable, AO
Cutoff is not configurable, and the transmitter does not implement the AO cutoff function.
Procedure
Set AO Cutoff as desired.
The default value for AO Cutoff is 0.0 g/sec.
Tip
For most applications, the default value of AO Cutoff should be used. Contact customer service
before changing AO Cutoff.
Configuration and Use Manual65
Page 72
Integrate the meter with the control system
Interaction between AO Cutoff and process variable cutoffs
When mA Output Process Variable is set to a flow variable (for example, mass flow rate or
volume flow rate), AO Cutoff interacts with Mass Flow Cutoff or Volume Flow Cutoff. The
transmitter puts the cutoff into effect at the highest flow rate at which a cutoff is
applicable.
Example: Cutoff interaction
Configuration:
•mA Output Process Variable = Mass Flow Rate
•Frequency Output Process Variable = Mass Flow Rate
•AO Cutoff = 10 g/sec
•Mass Flow Cutoff = 15 g/sec
Result: If the mass flow rate drops below 15 g/sec, all outputs representing mass flow will
report zero flow.
Example: Cutoff interaction
6.2.4
Configuration:
•mA Output Process Variable = Mass Flow Rate
•Frequency Output Process Variable = Mass Flow Rate
•AO Cutoff = 15 g/sec
•Mass Flow Cutoff = 10 g/sec
Result:
•If the mass flow rate drops below 15 g/sec but not below 10 g/sec:
-The mA Output will report zero flow.
-The Frequency Output will report the actual flow rate.
•If the mass flow rate drops below 10 g/sec, both outputs will report zero flow.
Field Communicator Configure > Manual Setup > Inputs/Outputs > mA Output > mA Output Settings > PV
Added Damping
Overview
Added Damping controls the amount of damping that will be applied to the mA Output.
66Micro Motion Model 1500 Transmitters with Analog Outputs
Page 73
Integrate the meter with the control system
Damping is used to smooth out small, rapid fluctuations in process measurement.
Damping Value specifies the time period (in seconds) over which the transmitter will
spread changes in the process variable. At the end of the interval, the internal value will
reflect 63% of the change in the actual measured value.
Added Damping affects the reporting of mA Output Process Variable through the mA
Output only. It does not affect the reporting of that process variable via any other method
(e.g., a Frequency Output or digital communications), or the value of the process variable
used in calculations.
Note
Added Damping is not applied if the mA Output is fixed (for example, during loop testing) or if the
mA Output is reporting a fault. Added Damping is applied while sensor simulation is active.
Procedure
Set Added Damping to the desired value.
The default value is 0.0 seconds. The range is 0.0 to 440 seconds.
When you specify a value for Added Damping, the transmitter automatically rounds the
value down to the nearest valid value.
Note
Added Damping values are affected by the setting of Update Rate and 100 Hz Variable.
100 Hz variable (if not assigned to the mA Output)
All other process variables
Interaction between mA Output Damping and process
variable damping
When mA Output Source is set to a flow rate variable, mA Output Damping interacts with
Flow Damping. If multiple damping parameters are applicable, the effect of damping the
process variable is calculated first, and the mA output damping calculation is applied to
the result of that calculation.
Update rate
in effectValid values for Added Damping
Result: A change in the mass flow rate will be reflected in the mA Output over a time
period that is greater than 3 seconds. The exact time period is calculated by the
transmitter according to internal algorithms which are not configurable.
6.2.5Configure mA Output Fault Action and mA Output Fault
Level
Field Communicator Configure > Manual Setup > Inputs/Outputs > mA Output > mA Fault Settings
Overview
mA Output Fault Action controls the behavior of the mA Output if the transmitter
encounters an internal fault condition.
Note
For some faults only: If Fault Timeout is set to a non-zero value, the transmitter will not implement
the fault action until the timeout has elapsed.
Procedure
1.Set mA Output Fault Action to the desired value.
The default setting is Downscale.
Restriction
If Digital Communications Fault Action is set to NAN (not a number), you cannot set mA
Output Fault Action or Frequency Output Fault Action to None. If you try to do this, the
transmitter will not accept the configuration.
2.If you set mA Output Fault Action to Upscale or Downscale, set mA Output Fault Level
as desired.
68Micro Motion Model 1500 Transmitters with Analog Outputs
Page 75
Integrate the meter with the control system
Postrequisites
CAUTION!
If you set mA Output Fault Action or Frequency Output Fault Action to None, be sure to set
Digital Communications Fault Action to None. If you do not, the output will not report actual
process data, and this may result in measurement errors or unintended consequences for your
process.
Options for mA Output Fault Action and mA Output Fault
Level
Option
Upscale
Downscale (default)Goes to the configured fault levelDefault: 2.0 mA
Internal Zero
None
mA Output behaviormA Output Fault Level
Goes to the configured fault levelDefault: 22.0 mA
Goes to the mA Output level associated
with a process variable value of 0 (zero),
as determined by Lower Range Value and
Upper Range Value settings
Tracks data for the assigned process variable; no fault action
6.3Configure the Frequency Output
The Frequency Output is used to report a process variable. The Frequency Output
parameters control how the process variable is reported. Your transmitter has one
Frequency Output: Channel C.
Restriction
The process variable assigned to the primary mA Output is automatically assigned to the Frequency
Output. You cannot assign a different process variable.
Range: 21.0 to 24.0 mA
Range: 1.0 to 3.6 mA
Not applicable
Not applicable
Important
Whenever you change a Frequency Output parameter, verify all other Frequency Output parameters
before returning the flowmeter to service. In some situations, the transmitter automatically loads a
set of stored values, and these values may not be appropriate for your application.
Field Communicator Configure > Manual Setup > Inputs/Outputs > Frequency Output > FO Settings > FO Po-
larity
Overview
Frequency Output Polarity controls how the output indicates the ON (active) state. The
default value, Active High, is appropriate for most applications. Your receiving device might
require an Active Low setting.
Procedure
Set Frequency Output Polarity as desired.
The default setting is Active High.
Options for Frequency Output Polarity
Polarity option
Active High
Active Low
Reference voltage (OFF)Pulse voltage (ON)
0As determined by power supply,
pull-up resistor, and load. See
the installation manual for your
transmitter.
As determined by power supply,
pull-up resistor, and load. See
the installation manual for your
transmitter.
Field Communicator Configure > Manual Setup > Inputs/Outputs > Frequency Output > FO Scaling
Overview
Frequency Output Scaling Method defines the relationship between output pulse and flow
units. Set Frequency Output Scaling Method as required by your frequency receiving
device.
Procedure
1.Set Frequency Output Scaling Method.
70Micro Motion Model 1500 Transmitters with Analog Outputs
Page 77
Integrate the meter with the control system
OptionDescription
Frequency=Flow (default)Frequency calculated from flow rate
Pulses/Unit
Units/Pulse
A user-specified number of pulses represents one flow unit
A pulse represents a user-specified number of flow units
2.Set additional required parameters.
• If you set Frequency Output Scaling Method to Frequency=Flow, set Rate Factor
and Frequency Factor.
• If you set Frequency Output Scaling Method to Pulses/Unit, define the number of
pulses that will represent one flow unit.
• If you set Frequency Output Scaling Method to Units/Pulse, define the number of
units that each pulse will indicate.
For all scaling methods, the transmitter puts out a fixed number of pulses per unit,
and at the same time, the Frequency Output signal varies in proportion to flowrate.
Calculate frequency from flow rate
The Frequency=Flow option is used to customize the Frequency Output for your application
when you do not know appropriate values for Units/Pulse or Pulses/Unit.
If you specify Frequency=Flow, you must provide values for Rate Factor and Frequency
Factor:
Rate Factor
Frequency
Factor
The maximum flow rate that you want the Frequency Output to report.
A value calculated as follows:
FrequencyFactor =x N
RateFactor
T
where:
T
Factor to convert selected time base to seconds
N
Number of pulses per flow unit, as configured in the receiving
device
The resulting Frequency Factor must be within the range of the Frequency Output ( :
•If Frequency Factor is less than1 Hz, reconfigure the receiving device for a higher
pulses/unit setting.
•If Frequency Factor is greater than 10,000 Hz, reconfigure the receiving device for a
lower pulses/unit setting.
Configuration and Use Manual71
Page 78
Integrate the meter with the control system
6.3.3Configure Frequency Output Fault Action and Frequency
Output Fault Level
Frequency Output Fault Action controls the behavior of the Frequency Output if the
transmitter encounters an internal fault condition.
Note
For some faults only: If Fault Timeout is set to a non-zero value, the transmitter will not implement
the fault action until the timeout has elapsed.
Procedure
1.Set Frequency Output Fault Action as desired.
The default value is Downscale (0 Hz).
2.If you set Frequency Output Fault Action to Upscale, set Frequency Fault Level to the
desired value.
The default value is 15000 Hz. The range is 10 to 15000 Hz.
Options for Frequency Output Fault Action
Options for Frequency Output Fault Action Table 6-5:
LabelFrequency Output behavior
Upscale
Downscale
Internal Zero
None (default)Tracks data for the assigned process variable; no fault action
Goes to configured Upscale value:
• Range: 10 Hz to 15000 Hz
• Default: 15000 Hz
0 Hz
0 Hz
72Micro Motion Model 1500 Transmitters with Analog Outputs
Page 79
Integrate the meter with the control system
CAUTION!
If you set mA Output Fault Action or Frequency Output Fault Action to None, be sure to set
Digital Communications Fault Action to None. If you do not, the output will not report actual
process data, and this may result in measurement errors or unintended consequences for your
process.
Restriction
If Digital Communications Fault Action is set to NAN (not a number), you cannot set mA Output Fault
Action or Frequency Output Fault Action to None. If you try to do this, the transmitter will not accept
the configuration.
6.4Configure the Discrete Output
The Discrete Output is used to report specific meter or process conditions. The Discrete
Output parameters control which condition is reported and how it is reported.
Restriction
Before you can configure the Discrete Output, you must configure a channel to operate as a Discrete
Output.
6.4.1
Important
Whenever you change a Discrete Output parameter, verify all other Discrete Output parameters
before returning the meter to service. In some situations, the transmitter automatically loads a set of
stored values, and these values may not be appropriate for your application.
Flow Switch is used to indicate that the flow rate (measured by the configured flow variable)
has moved past the configured setpoint, in either direction. The flow switch is
implemented with a user-configurable hysteresis.
Procedure
1.Set Discrete Output Source to Flow Switch, if you have not already done so.
2.Set Flow Switch Variable to the flow variable that you want to use to control the flow
switch.
3.Set Flow Switch Setpoint to the value at which the flow switch will be triggered
(after Hysteresis is applied).
• If the flow rate is below this value, the Discrete Output is ON.
• If the flow rate is above this value, the Discrete Output is OFF.
4.Set Hysteresis to the percentage of variation above and below the setpoint that will
operate as a deadband.
Hysteresis defines a range around the setpoint within which the flow switch will not
change. The default is 5%. The valid range is 0.1% to 10%.
6.4.2
Example: If Flow Switch Setpoint = 100 g/sec and Hysteresis = 5%, and the first
measured flow rate is above 100 g/sec, the Discrete Output is OFF. It will remain OFF
unless the flow rate drops below 95 g/sec. If this happens, the Discrete Output will
turn ON, and remain ON until the flow rate rises above 105 g/sec. At this point it
turns OFF and will remain OFF until the flow rate drops below 95 g/sec.
Field Communicator Configure > Manual Setup > Inputs/Outputs > Discrete Output > DO Polarity
Overview
Discrete Outputs have two states: ON (active) and OFF (inactive). Two different voltage
levels are used to represent these states. Discrete Output Polarity controls which voltage
level represents which state.
Field Communicator Configure > Manual Setup > Inputs/Outputs > Discrete Output > DO Fault Action
Overview
Discrete Output Fault Action controls the behavior of the Discrete Output if the
transmitter encounters an internal fault condition.
Note
For some faults only: If Fault Timeout is set to a non-zero value, the transmitter will not implement
the fault action until the timeout has elapsed.
CAUTION!
Do not use Discrete Output Fault Action as a fault indicator. If you do, you may not be able to
distinguish a fault condition from a normal operating condition. If you want to use the Discrete
Output as a fault indicator, set Discrete Output Source to Fault and set Discrete Output Fault
Action to None.
Procedure
Set Discrete Output Fault Action as desired.
The default setting is None.
Related information
Fault indication with the Discrete Output
76Micro Motion Model 1500 Transmitters with Analog Outputs
Page 83
Integrate the meter with the control system
Options for Discrete Output Fault Action
LabelDiscrete Output behavior
Upscale
Downscale
None (default)Discrete Output is controlled by its assignment
• Fault: Discrete Output is ON (site-specific voltage)
• No fault: Discrete Output is controlled by its assign-
ment
• Fault: Discrete Output is OFF (0 V)
• No fault: Discrete Output is controlled by its assign-
ment
Fault indication with the Discrete Output
To indicate faults via the Discrete Output, set Discrete Output Source to Fault. Then, if a
fault occurs, the Discrete Output is always ON and the setting of Discrete Output Fault
Action is ignored.
6.5Configure events
An event occurs when the real-time value of a user-specified process variable moves past a
user-defined setpoint. Events are used to provide notification of process changes or to
perform specific transmitter actions if a process change occurs.
A basic event is used to provide notification of process changes. A basic event occurs (is
ON) if the real-time value of a user-specified process variable moves above (HI) or below
(LO) a user-defined setpoint. You can define up to two basic events. Event status can be
queried via digital communications, and a Discrete Output can be configured to report
event status.
Procedure
1.Select the event that you want to configure.
Configuration and Use Manual77
Page 84
Integrate the meter with the control system
2.Specify Event Type.
OptionDescription
HI
LO
x > A
The event occurs when the value of the assigned process variable (x) is
greater than the setpoint (Setpoint A), endpoint not included.
x < A
The event occurs when the value of the assigned process variable (x) is
less than the setpoint (Setpoint A), endpoint not included.
3.Assign a process variable to the event.
4.Set a value for Setpoint A.
5.(Optional) Configure a Discrete Output to switch states in response to the event
status.
Field Communicator Configure > Alert Setup > Discrete Events
Overview
An enhanced event is used to provide notification of process changes and, optionally, to
perform specific transmitter actions if the event occurs. An enhanced event occurs (is ON)
if the real-time value of a user-specified process variable moves above (HI) or below (LO) a
user-defined setpoint, or in range (IN) or out of range (OUT) with respect to two userdefined setpoints. You can define up to five enhanced events.
Procedure
1.Select the event that you want to configure.
2.Specify Event Type.
Option
HI
LO
IN
Description
x > A
The event occurs when the value of the assigned process variable (x) is
greater than the setpoint (Setpoint A), endpoint not included.
x < A
The event occurs when the value of the assigned process variable (x) is
less than the setpoint (Setpoint A), endpoint not included.
A ≤ x ≤ B
The event occurs when the value of the assigned process variable (x) is inrange, that is, between Setpoint A and Setpoint B, endpoints included.
78Micro Motion Model 1500 Transmitters with Analog Outputs
Page 85
Integrate the meter with the control system
OptionDescription
OUT
x ≤ A or x ≥ B
The event occurs when the value of the assigned process variable (x) is
out of range, that is, less than Setpoint A or greater than Setpoint B, endpoints included.
3.Assign a process variable to the event.
4.Set values for the required setpoints.
• For HI and LO events, set Setpoint A.
• For IN and OUT events, set Setpoint A and Setpoint B.
5.(Optional) Configure a Discrete Output to switch states in response to the event
status.
6.(Optional) Specify the action or actions that the transmitter will perform when the
event occurs.
• With the Field Communicator: Configure > Alert Setup > Discrete Events > Assign
Discrete Action
Options for Enhanced Event Action
Action
Standard
None (default)
Start sensor zero
Start/stop all totalizers
Reset mass total
Reset volume total
Reset gas standard volume total
Reset all totals
Meter verification
Start meter verification test
Note
Before assigning actions to an enhanced event, check the status of the event. If it is ON, all assigned
actions will be performed when the new configuration is implemented. If this is not accepatable,
wait until an appropriate time to assign actions to the event.
Label
ProLink IIIField Communicator
NoneNone
Start Sensor ZeroPerform auto zero
Start/Stop All TotalizationStart/stop totals
Reset Mass TotalReset mass total
Reset Volume TotalReset volume total
Reset Gas Std Volume TotalReset gas standard volume total
Reset All TotalsReset totals
Start Meter Verification
Not available
Configuration and Use Manual79
Page 86
Integrate the meter with the control system
6.6Configure digital communications
The digital communications parameters control how the transmitter will communicate
using digital communications.
Your transmitter supports the following types of digital communications:
•HART/Bell 202 over the primary mA terminals
•Modbus/RS-485 over the RS-485 terminals
•Modbus RTU via the service port
The Model 1500 has only a single Modbus port.
Procedure
You have the following digital communication options:
• During the first 10 seconds after a power cycle, connect to the service port using
address 111 and the service port communication parameters.
• After the initial startup period, you can connect using Modbus with the configured
Modbus address and communication parameters.
6.6.1Configure HART/Bell 202 communications
HART/Bell 202 communications parameters support HART communications with the
transmitter's primary mA terminals over a HART/Bell 202 network.
Configure basic HART parameters
ProLink III
Field CommunicatorConfigure > Manual Setup > Inputs/Outputs > Com-
Overview
Basic HART parameters include the HART address, HART tags, and the operation of the
primary mA Output.
HART/Bell 202 communications parameters support HART communication with the
transmitter's primary mA terminals over a HART/Bell 202 network. The HART/Bell 202
communications parameters include:
80Micro Motion Model 1500 Transmitters with Analog Outputs
Page 87
Integrate the meter with the control system
Procedure
1.Set HART Address to a value that is unique on your network.
• Default: 0
• Range: 0 to 15
Tips
• The default address is typically used unless you are in a multidrop environment.
• Devices using HART protocol to communicate with the transmitter may use either HART
Address or HART Tag (Software Tag) to identify the transmitter. Configure either or both,
as required by your other HART devices.
2.Ensure that mA Output Action is configured appropriately.
Option
Enabled (Live)
Disabled (Fixed)
Important
If you use ProLink III to set HART Address to 0, the program automatically enables mA Output
Action. If you use ProLink III to set HART Address to any other value, the program
automatically disables mA Output Action. This is designed to make it easier to configure the
transmitter for legacy behavior. Always verify mA Output Action after setting HART Address.
Description
The primary mA Output reports process data as configured.
The primary mA Output is fixed at 4 mA and does not report process
data.
Configure burst parameters
ProLink III
Field Communicator Configure > Manual Setup > Inputs/Outputs > Communications > Set Up Burst Mode
Overview
Burst mode is a mode of communication during which the transmitter regularly
broadcasts HART digital information over the mA Output. The burst parameters control
the information that is broadcast when burst mode is enabled.
In typical installations, burst mode is disabled. Enable burst mode only if you are using a HART
Triloop.
Procedure
1.Enable Burst Mode.
Configuration and Use Manual81
Page 88
Integrate the meter with the control system
2.Set Burst Mode Output as desired.
Label
Source (Primary Variable)PV
Primary Variable (Percent
Range/Current)
Process Variables/CurrentProcess variables/current
Transmitter variablesFld dev var
% range/current
3.Ensure that the burst output variables are set appropriately.
DescriptionProLink IIIField Communicator
The transmitter sends the primary variable (PV) in the configured measurement units in each burst (e.g., 14.0 g/sec,
13.5 g/sec, 12.0 g/sec.
The transmitter sends the PV’s percent of range and the
PV’s actual mA level in each burst (e.g., 25%, 11.0 mA.
The transmitter sends PV, SV, TV, and QV values in measurement units and the PV’s actual milliamp reading in each
burst (e.g., 50 g/sec, 23 °C, 50 g/sec, 0.0023 g/cm3,
11.8 mA.
The transmitter sends four user-specified process variables
in each burst.
• If you set Burst Mode Output to send four user-specified variables, set the four
process variables to be sent in each burst.
• If you set Burst Mode Output to any other option, ensure that the HART variables
The HART variables are a set of four variables predefined for HART use. The HART variables
include the Primary Variable (PV), Secondary Variable (SV), Tertiary Variable (TV), and
Quaternary Variable (QV). You can assign specific process variables to the HART variables,
and then use standard HART methods to read or broadcast the assigned process data.
Restriction
The TV is automatically set to match the PV and cannot be configured independently.
Tip
The Tertiary Variable and Quaternary Variable are also called the Third Variable (TV) and Fourth
Variable (FV).
82Micro Motion Model 1500 Transmitters with Analog Outputs
Page 89
Integrate the meter with the control system
Options for HART variables
Standard HART process variablesTable 6-6:
Process variablePrimary Varia-
ble (PV)
Gas Standard Volume Flow Rate✓✓✓✓
Gas Standard Volume Inventory✓
Gas Standard Volume Total✓
Line (Gross) Volume Flow Rate✓✓✓✓
Line (Gross) Volume Inventory✓
Line (Gross) Volume Total✓
Mass Flow Rate✓✓✓✓
Mass Inventory✓
Mass Total✓
Secondary
Variable (SV)
Third Variable
(TV)
PVR-only HART process variablesTable 6-7:
Process variablePrimary Varia-
ble (PV)
Corrected Oil Flow✓✓✓
Corrected Oil Total✓
Corrected Water Cut✓
Corrected Water Flow✓✓✓
Corrected Water Total✓
Density of Oil @ Line Fixd degAPI✓
Density of Oil @ Line Fixd SGU✓
Oil Total @ Line✓
Shrinkage Factor Corrected Oil Flow @ 60F✓✓✓
Shrinkage Factor Corrected Oil Flow @ Line✓✓✓
Shrinkage Factor Corrected Oil Total @ 60F✓
Shrinkage Factor Corrected Oil Total @ Line✓
Shrinkage Factor Corrected Total of Mix @ 60F✓
Shrinkage Factor Corrected Volume Of Mix @ 60F✓✓✓
Uncorrected Oil Flow✓✓✓
Uncorrected Water Cut✓
Uncorrected Water Flow✓✓✓
Volume Flow of Mix at Line✓✓✓
Volume Total Of Mix @ Line✓
Secondary
Variable (SV)
Third Variable
(TV)
Fourth Variable (QV )
Fourth Variable (QV )
Configuration and Use Manual83
Page 90
Integrate the meter with the control system
PVR-only HART process variables (continued)Table 6-7:
Process variablePrimary Varia-
ble (PV)
Water Total @ Line✓
Secondary
Variable (SV)
Third Variable
(TV)
TMR-only HART process variablesTable 6-8:
Process variablePrimary Varia-
ble (PV)
Remediated Mass Flow✓✓✓
Remediated Mass Total✓
Remediated Mass Inventory✓
Secondary
Variable (SV)
Third Variable
(TV)
PVR- and TBR-only HART process variablesTable 6-9:
Process variablePrimary Varia-
ble (PV)
Unremediated Density✓
Secondary
Variable (SV)
Third Variable
(TV)
PVR, TBR, and TMR HART process variablesTable 6-10:
Fourth Variable (QV )
Fourth Variable (QV )
Fourth Variable (QV )
Process variablePrimary Varia-
ble (PV)
Total Remediated Time✓
Secondary
Variable (SV)
Third Variable
(TV)
Fourth Variable (QV )
Interaction of HART variables and transmitter outputs
The HART variables are automatically reported through specific transmitter outputs. They
may also be reported through HART burst mode, if enabled on your transmitter.
HART variables and transmitter outputsTable 6-11:
HART variableReported viaComments
Primary Variable (PV)Primary mA outputIf one assignment is changed, the other is changed auto-
matically, and vice versa.
Secondary Variable (SV)Not associated with an out-
put
Tertiary Variable (TV)Frequency OutputIf one assignment is changed, the other is changed auto-
Quaternary Variable (QV)Not associated with an out-
put
The SV must be configured directly, and the value of the
SV is available only via digital communications.
matically, and vice versa.
The QV must be configured directly, and the value of the
QV is available only via digital communications.
84Micro Motion Model 1500 Transmitters with Analog Outputs
Field Communicator Configure > Manual Setup > Inputs/Outputs > Communications > Set Up RS-485 Port
Overview
Modbus/RS-485 communications parameters control Modbus communication with the
transmitter's RS-485 terminals.
Procedure
1.Set Disable Modbus ASCII as desired.
Support for Modbus ASCII limits the set of addresses that are available for the
transmitter's Modbus address.
Modbus ASCII support
Disabled1–127, excluding 111 (111 is reserved to the service port)
Enabled1–15, 32–47, 64–79, and 96–110
Available Modbus addresses
2.Set Protocol to match the protocol used by your Modbus/RS-485 host.
Option
Modbus RTU (default)8–bit communications
Modbus ASCII7–bit communications
Description
If support for Modbus ASCII is disabled, you must use Modbus RTU.
3.Set Modbus Address to a unique value on the network.
4.Set Parity, Stop Bits, and Baud Rate as appropriate for your network.
5.Set Floating-Point Byte Order to match the byte order used by your Modbus host.
Code
01–2 3–4
13–4 1–2
22–1 4–3
34–3 2–1
Byte order
See the following table for the bit structure of bytes 1 through 7.
Configuration and Use Manual85
Page 92
Integrate the meter with the control system
ByteBitsDefinition
1SEEEEEEES=Sign
2EMMMMMMME=Exponent
3MMMMMMMMM=Mantissa
4MMMMMMMMM=Mantissa
6.(Optional) Set Additional Communications Response Delay in delay units.
A delay unit is 2/3 of the time required to transmit one character, as calculated for
the port currently in use and the character transmission parameters. Valid values
range from 1 to 255.
Additional Communications Response Delay is used to synchronize Modbus
communications with hosts that operate at a slower speed than the transmitter. The
value specified here will be added to each response the transmitter sends to the
host.
Bit structure of floating-point bytesTable 6-12:
E=Exponent
M=Mantissa
6.6.3
Tip
Do not set Additional Communications Response Delay unless required by your Modbus host.
Field Communicator Configure > Alert Setup > I/O Fault Actions > Comm Fault Action
Overview
Digital Communications Fault Actionspecifies the values that will be reported via digital
communications if the device encounters an internal fault condition.
Procedure
Set Digital Communications Fault Action as desired.
The default setting is None.
Restrictions
• If mA Output Fault Action or Frequency Output Fault Action is set to None, Digital
Communications Fault Action should also be set to None. If you do not, the output will not report
actual process data, and this may result in measurement errors or unintended consequences for
your process.
86Micro Motion Model 1500 Transmitters with Analog Outputs
Page 93
Integrate the meter with the control system
• If you set Digital Communications Fault Action to NAN, you cannot set mA Output Fault Action or
Frequency Output Fault Action to None. If you try to do this, the transmitter will not accept the
configuration.
Options for Digital Communications Fault Action
Label
DescriptionProLink IIIField Communicator
UpscaleUpscale
DownscaleDownscale
ZeroIntZero-All 0
Not a NumberNot-a-Number
Flow to ZeroIntZero-Flow 0
None
None (default)• All process variables are reported as meas-
• Process variable values indicate that the val-
ue is greater than the upper sensor limit.
• Totalizers stop incrementing.
• Process variable values indicate that the val-
ue is lower than the lower sensor limit.
• Totalizers stop incrementing.
• Flow rate variables go to the value that rep-
resents a flow rate of 0 (zero).
• Density is reported as 0.
• Temperature is reported as 0 °C , or the
equivalent if other units are used (e.g.,
32 °F .
• Drive gain is reported as measured.
• Totalizers stop incrementing.
• Process variables are reported as IEEE
NAN.
• Drive gain is reported as measured.
• Modbus scaled integers are reported as Max
Int.
• Totalizers stop incrementing.
• Flow rates are reported as 0.
• Other process variables are reported as
measured.
• Totalizers stop incrementing.
ured.
• Totalizers increment if they are running.
CAUTION!
If you set mA Output Fault Action or Frequency Output Fault Action to None, be sure to set
Digital Communications Fault Action to None. If you do not, the output will not report actual
process data, and this may result in measurement errors or unintended consequences for your
process.
Configuration and Use Manual87
Page 94
Integrate the meter with the control system
Restriction
If Digital Communications Fault Action is set to NAN (not a number), you cannot set mA Output Fault
Action or Frequency Output Fault Action to None. If you try to do this, the transmitter will not accept
the configuration.
88Micro Motion Model 1500 Transmitters with Analog Outputs
Page 95
7Complete the configuration
Topics covered in this chapter:
Test or tune the system using sensor simulation
•
Back up transmitter configuration
•
Enable write‐protection on the transmitter configuration
•
7.1Test or tune the system using sensor
simulation
Use sensor simulation to test the system's response to a variety of process conditions,
including boundary conditions, problem conditions, or alert conditions, or to tune the
loop.
Complete the configuration
Restriction
Sensor simulation is available only on flowmeters with the enhanced core processor.
Prerequisites
Before enabling sensor simulation, ensure that your process can tolerate the effects of the
simulated process values.
Field CommunicatorService Tools > Simulate > Simulate Sensor
2.Enable sensor simulation.
3.For mass flow, set Wave Form as desired and enter the required values.
Option
Fixed
Sawtooth
Sine
Menu path
Required values
Fixed Value
Period
Minimum
Maximum
Period
Minimum
Maximum
Configuration and Use Manual89
Page 96
Complete the configuration
4.For density, set Wave Form as desired and enter the required values.
5.For temperature, set Wave Form as desired and enter the required values.
OptionRequired values
Fixed
Sawtooth
Sine
Fixed Value
Period
Minimum
Maximum
Period
Minimum
Maximum
7.1.1
Option
Fixed
Sawtooth
Sine
Required values
Fixed Value
Period
Minimum
Maximum
Period
Minimum
Maximum
6.Observe the system response to the simulated values and make any appropriate
changes to the transmitter configuration or to the system.
7.Modify the simulated values and repeat.
8.When you have finished testing or tuning, disable sensor simulation.
Sensor simulation
Sensor simulation allows you to test the system or tune the loop without having to create
the test conditions in your process. When sensor simulation is enabled, the transmitter
reports the simulated values for mass flow, density, and temperature, and takes all
appropriate actions. For example, the transmitter might apply a cutoff, activate an event,
or post an alert.
When sensor simulation is enabled, the simulated values are stored in the same memory
locations used for process data from the sensor. The simulated values are then used
throughout transmitter functioning. For example, sensor simulation will affect:
•All mass flow rate, temperature, and density values displayed or reported via
outputs or digital communications
•The mass total and mass inventory values
•All volume calculations and data, including reported values, volume totals, and
volume inventories
90Micro Motion Model 1500 Transmitters with Analog Outputs
Page 97
•All mass, temperature, density, or volume values logged to Data Logger
Sensor simulation does not affect any diagnostic values.
Unlike actual mass flow rate and density values, the simulated values are not temperaturecompensated (adjusted for the effect of temperature on the sensor’s flow tubes).
7.2Back up transmitter configuration
ProLink III provides a configuration upload/download function which allows you to save
configuration sets to your PC. This allows you to back up and restore your transmitter
configuration. This is also a convenient way to replicate a configuration across multiple
devices.
Restriction
This function is not available with any other communications tools.
Procedure
Complete the configuration
7.3
To back up the transmitter configuration using ProLink III:
1. Choose Device Tools > Configuration Transfer > Save or Load Configuration Data.
2. In the Configuration groupbox, select the configuration data you want to save.
3. Click Save, then specify a file name and location on your computer.
4. Click Start Save.
The backup file is saved to the specified name and location. It is saved as a text file and can
be read using any text editor.
Enable write-protection on the transmitter
configuration
Field Communicator Configure > Manual Setup > Info Parameters > Transmitter Info > Write Protect
Overview
If the transmitter is write-protected, the configuration is locked and nobody can change it
until it is unlocked. This prevents accidental or unauthorized changes to the transmitter
configuration parameters.
Configuration and Use Manual91
Page 98
Complete the configuration
92Micro Motion Model 1500 Transmitters with Analog Outputs
Page 99
Operations, maintenance, and troubleshooting
Part III
Operations, maintenance, and
troubleshooting
Chapters covered in this part:
Transmitter operation
•
Measurement support
•
Troubleshooting
•
Configuration and Use Manual93
Page 100
Operations, maintenance, and troubleshooting
94Micro Motion Model 1500 Transmitters with Analog Outputs
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.