Emerson Micro Motion 1000 Series, Micro Motion 1700, Micro Motion 2500, Micro Motion 2000 Series, Micro Motion 2700 Configuration And Use Manual

...
Page 1
Configuration and Use Manual
P/N 20001715, Rev. BA September 2009
Micro Motion
®
Series 1000 and Series 2000 Transmitters
Configuration and Use Manual
• Model 1700 with intrinsically safe outputs
• Model 2500 with configurable input/outputs
• Model 2700 with intrinsically safe outputs
• Model 2700 with configurable input/outputs
Page 2
© 2009 Micro Motion, Inc. All rights reserved. The Micro Motion and Emerson logos are trademarks and service marks of Emerson Electric Co. Micro Motion, ELITE, MVD, ProLink, MVD Direct Connect, and PlantWeb are marks of one of the Emerson Process Management family of companies. All other trademarks are property of their respective owners.
Page 3

Contents

Chapter 1 Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3 Determining your transmitter type and version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3.1 Transmitter type, installation type, and outputs option board. . . . . . . . . . . 2
1.3.2 Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 Flowmeter documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.5 Using this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.5.1 Component versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.5.2 Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.5.3 Communication tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.6 Planning the configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.7 Pre-configuration worksheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.8 Micro Motion customer service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 2 Using the Transmitter Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2 Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3 Using the optical switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4 Using the display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4.1 Display language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4.2 Viewing process variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4.3 Display menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.4.4 Display password. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.4.5 Entering floating-point values with the display . . . . . . . . . . . . . . . . . . . . . 12
Chapter 3 Connecting with ProLink II or Pocket ProLink Software . . . . . . . . . . 15
3.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2 Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.3 ProLink II configuration upload/download . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.4 Connecting from a PC to a Model 1700 or Model 2700 transmitter . . . . . . . . . . . . . 16
3.4.1 Connecting to the service port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.4.2 Connecting to the RS-485 terminals or an RS-485 network . . . . . . . . . . 18
3.4.3 Connecting to the primary mA output terminals or to a
HART multidrop network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.5 Connecting from a PC to a Model 1500 or Model 2500 transmitter . . . . . . . . . . . . . 23
3.5.1 Connecting to the RS-485 terminals or an RS-485 network . . . . . . . . . . 23
3.5.2 HART/Bell 202 connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.6 ProLink II language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Configuration and Use i
Page 4
Contents
Chapter 4 Connecting with the 275 HART Communicator or
375 Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.2 Communicator models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.2.1 Viewing the device descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.2.2 Using the 275 HART Communicator with the Model 2500 . . . . . . . . . . . 30
4.3 Connecting to a transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.3.1 Connecting to communication terminals . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.3.2 Connecting to a multidrop network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.4 Conventions used in this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.5 HART Communicator safety messages and notes . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Chapter 5 Flowmeter Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.2 Applying power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.2.1 Communication methods after power-up . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.3 Performing a loop test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.4 Trimming the milliamp outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.5 Zeroing the flowmeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.5.1 Preparing for zero . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.5.2 Zero procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Chapter 6 Required Transmitter Configuration . . . . . . . . . . . . . . . . . . . . . . . 43
6.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.2 Characterizing the flowmeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.2.1 When to characterize. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.2.2 Characterization parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.2.3 How to characterize . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
6.3 Configuring the channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
6.4 Configuring the measurement units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
6.4.1 Mass flow units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
6.4.2 Volume flow units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.4.3 Density units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
6.4.4 Temperature units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
6.4.5 Pressure units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
6.5 Configuring the mA output(s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
6.6 Configuring the frequency output(s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
6.7 Configuring the discrete output(s). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
6.8 Configuring the discrete input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.9 Establishing a meter verification baseline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Chapter 7 Using the Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
7.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
7.2 Special applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
7.3 Recording process variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
7.4 Viewing process variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
7.4.1 With the display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
7.4.2 With ProLink II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
7.4.3 With a Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
ii Micro Motion Series 1000 and Series 2000 Transmitters
Page 5
Contents
7.5 Viewing transmitter status and alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
7.5.1 Using the status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
7.5.2 Using the display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
7.5.3 Using ProLink II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
7.5.4 Using the Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
7.6 Acknowledging alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
7.7 Using the totalizers and inventories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
7.7.1 Viewing the totalizers and inventories . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
7.8 Controlling totalizers and inventories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Chapter 8 Optional Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
8.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
8.2 Configuration map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
8.3 How to access a parameter for configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
8.4 Configuring standard volume flow measurement for gas . . . . . . . . . . . . . . . . . . . . . 67
8.4.1 Using the Gas Wizard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
8.5 Creating special measurement units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
8.5.1 About special measurement units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
8.5.2 Special measurement unit procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
8.6 Configuring the petroleum measurement application (API feature) . . . . . . . . . . . . . 70
8.6.1 About the petroleum measurement application . . . . . . . . . . . . . . . . . . . . 70
8.7 Configuring cutoffs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
8.7.1 Cutoffs and volume flow. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
8.7.2 Interaction with the AO cutoffs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
8.8 Configuring the damping values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
8.8.1 Damping and volume measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
8.8.2 Interaction with the added damping parameter . . . . . . . . . . . . . . . . . . . . 74
8.8.3 Interaction with the update rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
8.9 Configuring the update rate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
8.9.1 Effects of Special mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
8.10 Configuring the flow direction parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
8.11 Configuring events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
8.11.1 Changing event setpoints from the display . . . . . . . . . . . . . . . . . . . . . . . 79
8.12 Configuring slug flow limits and duration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
8.13 Configuring fault handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
8.13.1 Status alarm severity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
8.13.2 Fault timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
8.14 Configuring the display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
8.14.1 Update period . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
8.14.2 Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
8.14.3 Enabling and disabling display functions . . . . . . . . . . . . . . . . . . . . . . . . . 85
8.14.4 Changing the scroll rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
8.14.5 Changing the display password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
8.14.6 Changing the display variables and display precision . . . . . . . . . . . . . . . 86
8.14.7 Fixing Display Variable 1 to the primary mA output . . . . . . . . . . . . . . . . . 86
8.15 Configuring digital communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
8.16 Configuring device settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
8.17 Configuring sensor parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
8.18 Configuring write-protect mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Configuration and Use iii
Page 6
Contents
Chapter 9 Pressure Compensation, Temperature Compensation,
and Polling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
9.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
9.2 Pressure compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
9.2.1 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
9.2.2 Pressure correction factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
9.2.3 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
9.3 External temperature compensation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
9.3.1 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
9.4 Configuring polling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Chapter 10 Measurement Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
10.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
10.2 Meter verification, meter validation, and calibration . . . . . . . . . . . . . . . . . . . . . . . . . 97
10.2.1 Meter verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
10.2.2 Meter validation and meter factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
10.2.3 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
10.2.4 Comparison and recommendations. . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
10.3 Performing meter verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
10.3.1 Preparing for the meter verification test . . . . . . . . . . . . . . . . . . . . . . . . . 101
10.3.2 Running the meter verification test, original version . . . . . . . . . . . . . . . 101
10.3.3 Running Smart Meter Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
10.3.4 Reading and interpreting meter verification test results . . . . . . . . . . . . 109
10.3.5 Setting up automatic or remote execution of the meter verification test 115
10.4 Performing meter validation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
10.5 Performing density calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
10.5.1 Preparing for density calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
10.5.2 Density calibration procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
10.6 Performing temperature calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Chapter 11 Custody Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
11.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
11.2 Locale-specific commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
11.3 Configuring the weights and measures approval agency . . . . . . . . . . . . . . . . . . . . 125
11.4 Special restrictions when using custody transfer transmitters . . . . . . . . . . . . . . . . 126
11.5 Switching between security breach and secure mode . . . . . . . . . . . . . . . . . . . . . . 126
11.6 Security breach mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
11.6.1 Transmitter outputs in security breach mode. . . . . . . . . . . . . . . . . . . . . 127
11.6.2 Configuring the totalizers in security breach mode . . . . . . . . . . . . . . . . 127
11.7 Secure mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
11.7.1 Transmitter outputs in secure mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
11.7.2 Operating the totalizers in secure mode . . . . . . . . . . . . . . . . . . . . . . . . 128
11.7.3 Displaying totalizer and inventory values. . . . . . . . . . . . . . . . . . . . . . . . 128
Chapter 12 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
12.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
12.2 Guide to troubleshooting topics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
12.3 Micro Motion customer service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
12.4 Transmitter does not operate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
12.5 Transmitter does not communicate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
iv Micro Motion Series 1000 and Series 2000 Transmitters
Page 7
Contents
12.6 Zero or calibration failure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
12.7 Fault conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
12.8 HART output problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
12.9 I/O problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
12.10 Simulation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
12.11 Transmitter status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
12.11.1 Model 1500/2500 transmitters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
12.11.2 Model 1700/2700 transmitters with displays . . . . . . . . . . . . . . . . . . . . . 135
12.12 Status alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
12.13 Checking process variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
12.14 Diagnosing wiring problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
12.14.1 Checking the power supply wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
12.14.2 Checking the sensor-to-transmitter wiring . . . . . . . . . . . . . . . . . . . . . . . 145
12.14.3 Checking grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
12.14.4 Checking for RF interference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
12.14.5 Checking the HART communication loop . . . . . . . . . . . . . . . . . . . . . . . 146
12.15 Checking the communication device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
12.16 Checking the output wiring and receiving device . . . . . . . . . . . . . . . . . . . . . . . . . . 147
12.17 Checking slug flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
12.18 Checking output saturation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
12.19 Setting the Loop Current Mode parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
12.20 Checking the flow measurement unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
12.21 Checking the upper and lower range values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
12.22 Checking the frequency output scale and method . . . . . . . . . . . . . . . . . . . . . . . . . 149
12.23 Checking the characterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
12.24 Checking the calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
12.25 Checking the test points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
12.25.1 Obtaining the test points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
12.25.2 Evaluating the test points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
12.25.3 Excessive drive gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
12.25.4 Erratic drive gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
12.25.5 Low pickoff voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
12.26 Checking the core processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
12.26.1 Checking the core processor LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
12.26.2 Core processor resistance test (standard core processor only) . . . . . . 155
12.27 Checking sensor coils and RTD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
12.27.1 9-wire remote or remote core processor with
remote transmitter installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
12.27.2 4-wire remote or integral installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Appendix A Default Values and Ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
A.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
A.2 Most frequently used defaults and ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Configuration and Use v
Page 8
Contents
Appendix B Flowmeter Installation Types and Components. . . . . . . . . . . . . . . 169
B.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
B.2 Model 1500/2500 transmitters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
B.2.1 Installation diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
B.2.2 Component diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
B.2.3 Wiring and terminal diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
B.3 Model 1700/2700 transmitters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
B.3.1 Installation diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
B.3.2 Component diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
B.3.3 Wiring and terminal diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
Appendix C Menu Flowcharts – Model 1500 AN Transmitters . . . . . . . . . . . . . 181
C.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
C.2 Model 1500 output board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
C.3 Version information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
C.4 ProLink II menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
C.5 Communicator menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
Appendix D Menu Flowcharts – Model 2500 CIO Transmitters . . . . . . . . . . . . . 191
D.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
D.2 Version information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
D.3 ProLink II menus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
D.4 Communicator menus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Appendix E Menu Flowcharts – Model 1700/2700 AN Transmitters. . . . . . . . . . 201
E.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
E.2 Version information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
E.3 ProLink II menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
E.4 Communicator menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
E.5 Display menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Appendix F Menu Flowcharts – Model 1700/2700 IS Transmitters . . . . . . . . . . 219
F.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
F.2 Version information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
F.3 ProLink II menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
F.4 Communicator menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
F.5 Display menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Appendix G Menu Flowcharts – Model 2700 CIO Transmitters . . . . . . . . . . . . . 237
G.1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
G.2 Version information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
G.3 ProLink II menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
G.4 Communicator menus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
G.5 Display menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
vi Micro Motion Series 1000 and Series 2000 Transmitters
Page 9
Contents
Appendix H Display Codes and Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . 257
H.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
H.2 Codes and abbreviations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
Appendix I NE53 History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
I.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
I.2 Software change history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
Configuration and Use vii
Page 10
viii Micro Motion Series 1000 and Series 2000 Transmitters
Page 11
Chapter 1

Before You Begin

1.1 Overview

This chapter provides an orientation to the use of this manual, and includes a pre-configuration worksheet. This manual describes the procedures required to start, configure, use, maintain, and troubleshoot the following Series 1000 and Series 2000 transmitters:
Model 1500 with analog outputs option board
Model 1700 with analog outputs option board
Model 1700 with intrinsically safe outputs option board
Model 2500 with configurable input/outputs option board
Model 2700 with analog outputs option board
Model 2700 with intrinsically safe outputs option board
Model 2700 with configurable input/outputs option board
If you do not know what transmitter you have, see Section 1.3 for instructions on identifying the transmitter type from the model number on the transmitter’s tag.
Note: Information on configuration and use of Model 2700 transmitters with F Model 2700 transmitters with Profibus-PA, and Model 1500 transmitters with the Filling and Dosing application is provided in separate manuals. See the manual for your transmitter.
OUNDATION fieldbus
Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin
,

1.2 Safety

Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully before proceeding to the next step.

1.3 Determining your transmitter type and version

To configure, use, and troubleshoot the transmitter, you must know your transmitter type, installation type, outputs option board, and several different types of version information. This section provides instructions for this information. Record this information in the pre-configuration worksheet in Section 1.7.
Configuration and Use Manual 1
Page 12
Before You Begin

1.3.1 Transmitter type, installation type, and outputs option board

To determine your transmitter type, installation type, and outputs option board:
1. Obtain the transmitter's model number, which is provided on a tag attached to the side of the transmitter.
Model 1500 transmitters have a model number of the form
Model 2500 transmitters have a model number of the form
1500xxxxxxxxxx.
2500xxxxxxxxxx.
Model 1700 transmitters have a model number of the form
Model 2700 transmitters have a model number of the form
2. The fifth character in the model number (
xxxxXxxxxxxxxx) represents the installation type
that was ordered:
R = remote (4-wire remote installation)
I = integral (transmitter mounted on sensor)
C = transmitter/core processor assembly (9-wire remote installation)
B = remote core processor with remote transmitter
D = DIN rail (for Model 1500 or 2500 transmitters in 4-wire remote installations)
Note: For more information on installation type, see Appendix B.
3. The eighth character in the model number (
xxxxxxxXxxxxxx) represents the outputs option
board:
A = transmitter with analog outputs option board (one mA, one frequency, one RS-485)
B = transmitter with configurable input/outputs option board, default output configuration
(two mA, one frequency)
C = transmitter with configurable input/outputs option board, customized output
configuration
D = transmitter with intrinsically safe outputs option board
1700xxxxxxxxxx.
2700xxxxxxxxxx.
Note: The remaining characters in the model number describe options that do not affect transmitter configuration or use.
The following examples illustrate use of the model number to determine transmitter type, installation type, and output board type:
1700RxxAxxxxxx = Model 1700 remote transmitter with analog outputs option board
2700CxxDxxxxxx = Model 2700 transmitter/core processor assembly with intrinsically safe
outputs option board
2 Micro Motion Series 1000 and Series 2000 Transmitters
Page 13
Before You Begin
• Model 1500 AN
• Model 1700 AN
• Model 1700 IS
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO

1.3.2 Version

Different configuration options are available with different versions of the components. Table 1-1 lists the version information that you may need and describes how to obtain the information.
Table 1-1 Obtaining version information
Component With ProLink II With Communicator With Display
Transmitter software View>Installed Options>
Software Revision
Core processor software
ProLink II Help>About ProLink II Not applicable Not applicable
Communicator device description
Not available Review/Device info>
Not applicable See Section 4.2.2 Not applicable

1.4 Flowmeter documentation

Table 1-2 lists documentation sources for additional information.
Table 1-2 Flowmeter documentation resources
Review>Device info> Software rev
Hardware rev
OFF-LINE MAINT>VER
OFF-LINE MAINT>VER
Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin
Topic Document
Installing the sensor Sensor installation manual
Installing a Model 1500/2500 transmitter Model 1500 and 2500 Transmitters: Installation Manual
Installing a Model 1700/2700 transmitter Model 1700 and 2700 Transmitters: Installation Manual
Supplementary configuration and use information for the v6.0 update

1.5 Using this manual

• Model 1500 Transmitters with Analog Outputs: Configuration and Use Manual Supplement
• Model 1700 Transmitters with Analog Outputs: Configuration and Use Manual Supplement
• Model 1700 Transmitters with Intrinsically Safe Outputs: Configuration and Use Manual Supplement
• Model 2500 Transmitters with Configurable Input/Outputs: Configuration and Use Manual Supplement
• Model 2700 Transmitters with Analog Outputs: Configuration and Use Manual Supplement
• Model 2700 Transmitters with Intrinsically Safe Outputs: Configuration and Use Manual Supplement
• Model 2700 Transmitters with Configurable Input/Outputs: Configuration and Use Manual Supplement
This manual describes features and procedures that apply to most or all of the Series 1000 and 2000 transmitters. To help you identify the topics that apply to your transmitter, a list of transmitters is supplied with topic headings (see the example to the left of this paragraph). If no list is supplied with the topic heading, the topic is applicable to all transmitters.
Configuration and Use Manual 3
Page 14
Before You Begin

1.5.1 Component versions

In general, this manual documents transmitters with transmitter software rev5.0, connected to either a standard core processor (v2.5) or an enhanced core processor (v3.21). Earlier versions of transmitter and core processor software are similar but not identical. Significant differences between versions are noted in the manual; however, not all differences are noted.

1.5.2 Terminology

Table 1-3 lists definitions for the terms and codes that are used in this manual.
Table 1-3 Terms and codes used in this manual
Term Definition
Series 1000 Refers to the following transmitters:
Series 2000 Refers to the following transmitters:
Model 1500 Refers to the following transmitter:
Model 1700 Refers to the following transmitters:
Model 2500 Refers to the following transmitter:
Model 2700 Refers to the following transmitters:
AN Analog outputs option board. Available with the following transmitters:
IS Intrinsically safe outputs option board. Available with the following transmitters:
CIO Configurable input/outputs option board. Available with the following transmitters:
• Model 1500
• Model 1700
• Model 2500
• Model 2700
• Model 1500 with the analog outputs option board
• Model 1700 with the analog outputs option board
• Model 1700 with the intrinsically safe outputs option board
• Model 2500 with the configurable input/outputs option board
• Model 2700 with the analog outputs option board
• Model 2700 with the intrinsically safe outputs option board
• Model 2700 with the configurable input/outputs option board
• Model 1500 with the analog outputs option board
• Model 1700 with the analog outputs option board
• Model 2700 with the analog outputs option board
• Model 1700 with the intrinsically safe outputs option board
• Model 2700 with the intrinsically safe outputs option board
• Model 2500 with the configurable input/outputs option board
• Model 2700 with the configurable input/outputs option board
4 Micro Motion Series 1000 and Series 2000 Transmitters
Page 15
Before You Begin

1.5.3 Communication tools

Most of the procedures described in this manual require the use of a communication tool. Table 1-4 lists the transmitters discussed in this manual, and the communication tools that can be used with them.
Table 1-4 Transmitters and communication tools
display
Model 1500
Model 1700 with analog outputs option board ✓✓✓
Model 1700 with intrinsically safe outputs option board ✓✓✓
Model 2500 with configurable input/outputs option board ✓✓
Model 2700 with analog outputs option board ✓✓✓
Model 2700 with intrinsically safe outputs option board ✓✓✓
Model 2700 with configurable input/outputs option board ✓✓✓
(1) Model 1700 and 2700 transmitters may be ordered with or without a display. (2) Requires ProLink II v2.1 or later. (3) Requires 375 Field Communicator. (4) Partial support available with 275 HART Communicator; requires 375 Field Communicator for full support.
(1)
ProLink II software Communicator
(2)
(3)
(4)
In this manual:
Basic information on using the display is provided in Chapter 2.
Basic information on ProLink II and connecting ProLink II to your transmitter is provided in Chapter 3. For more information, refer to the ProLink II manual, available on the Micro Motion web site (www.micromotion.com).
Basic information on the 275 HART Communicator, the 375 Field Communicator, and connecting the Communicator to your transmitter is provided in Chapter 4. For more information, refer to the HART Communicator or Field Communicator documentation available on the Micro Motion web site (www.micromotion.com).
You may be able to use other tools from Emerson Process Management, such as AMS. Use of AMS is not discussed in this manual; however, the user interface that AMS provides is similar to the ProLink II user interface.

1.6 Planning the configuration

The pre-configuration worksheet in Section 1.7 provides a place to record information about your flowmeter (transmitter and sensor) and your application. This information will affect your configuration options as you work through this manual. Fill out the pre-configuration worksheet and refer to it during configuration. You may need to consult with transmitter installation or application process personnel to obtain the required information.
If you are configuring multiple transmitters, make copies of this worksheet and fill one out for each individual transmitter.
Configuration and Use Manual 5
Page 16
Before You Begin

1.7 Pre-configuration worksheet

Note: Not all options are available for all transmitters.
Item Configuration data
Sensor type
Transmitter model number
Transmitter model
Installation type
Outputs option board
Transmitter software version
Core processor software version
Outputs Terminals 1 & 2
Terminals 21 & 22 or Channel A
Terminals 3 & 4 Terminals 23 & 24 or Channel B
Terminals 5 & 6 Terminals 31 & 32 or Channel C
Process variable or assignment
Measurement units Mass flow
Terminals 1 & 2 or Terminals 21 & 22 or Channel A ______________________________________
Terminals 3 & 4 or Terminals 23 & 24 or Channel B ______________________________________
Terminals 5 & 6 Terminals 31 & 32 or Channel C ______________________________________
Volume flow
Density
Pressure
Temperature
or
or
or
or
T- S e r i e s
Other
______________________________________
1500
1700
2500
2700
Integral
4-wire remote
9-wire remote
Remote core processor with remote transmitter
Analog (AN)
Intrinsically safe (IS)
Configurable input/outputs (CIO)
______________________________________
______________________________________
Milliamp (no options)
Used for HART/Bell202 digital communications
Milliamp
Frequency
Discrete output
Milliamp
Frequency
RS-485
Discrete output
Discrete input
Internal power
External power
Internal power
External power
______________________________________
______________________________________
______________________________________
______________________________________
______________________________________
6 Micro Motion Series 1000 and Series 2000 Transmitters
Page 17
Before You Begin
Item Configuration data
Installed applications and options
ProLink II version
Communicator device description version ______________________________________

1.8 Micro Motion customer service

For customer service, phone the support center nearest you:
In the U.S.A., phone
800-522-MASS (800-522-6277) (toll-free)
In Canada and Latin America, phone +1 303-527-5200
•In Asia:
- In Japan, phone 3 5769-6803
- In other locations, phone +65 6777-8211 (Singapore)
Petroleum measurement (API)
Enhanced density
Custody transfer
Micro Motion Smart Meter Verification
Meter verification application, original version
______________________________________
Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin
•In Europe:
- In the U.K., phone 0870 240 1978 (toll-free)
- In other locations, phone +31 (0) 318 495 555 (The Netherlands)
Customers outside the U.S.A. can also email Micro Motion customer service at flow.support@emerson.com.
Configuration and Use Manual 7
Page 18
8 Micro Motion Series 1000 and Series 2000 Transmitters
Page 19
Chapter 2
• Model 1700 AN
• Model 1700 IS
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO
Current value
Units of measure
Process variable
Scroll optical switch Select optical switch
Optical switch indicator
Status LED

Using the Transmitter Display

2.1 Overview

The transmitter display provides basic configuration and management functionality. This chapter describes the user interface of the transmitter display. The following topics are discussed:
Display components (see Section 2.2)
•Using the
Using the display (see Section 2.4)
Note that the Model 1500 and 2500 transmitters do not have displays, and the Model 1700 and 2700 transmitters can be ordered with or without displays. Not all configuration and use functions are available through the display. If you need the added functionality, or if your transmitter does not have a display, you must use either ProLink II or a Communicator.
Scroll and Select optical switches (see Section 2.3)
Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin

2.2 Components

Figure 2-1 illustrates the display components.
Figure 2-1 Display components
Configuration and Use Manual 9
Page 20
Using the Transmitter Display
WARNING

2.3 Using the optical switches

Scroll and Select optical switches are used to navigate the transmitter display. To activate an
The optical switch, touch the glass in front of the optical switch or move your finger over the optical switch close to the glass. The optical switch indicator will be solid red when a single switch is activated, and will flash red when both switches are activated simultaneously.
Removing the display cover in an explosive atmosphere can cause an explosion.
When using the optical switches, do not remove the display cover. To activate an optical switch, touch the glass of the display cover or move your finger over the switch close to the glass.

2.4 Using the display

The display can be used to view process variable data or to access the transmitter menus for configuration or maintenance.

2.4.1 Display language

The display can be configured for the following languages:
English
•French
Spanish
•German
Due to software and hardware restrictions, some English words and terms may appear in the non-English display menus. For a list of the codes and abbreviations used on the display, see Appendix H.
For information on configuring the display language, see Section 8.14.2.
In this manual, English is used as the display language.

2.4.2 Viewing process variables

In ordinary use, the
Units of measure line shows the measurement unit for that process variable.
the
Process variable line on the display shows the configured display variables, and
See Section 8.14.6 for information on configuring the display variables.
See Appendix H for information on the codes and abbreviations used on the display (e.g.,
SrC).
If more than one line is required to describe the display variable, the
Units of measure line alternates
between the measurement unit and the additional description. For example, if the display is showing a mass inventory value, the name of the inventory (
Units of measure line alternates between the measurement unit (G) and the
MASSI). For enhanced density or petroleum measurement variables, the
reference temperature is also shown.
10 Micro Motion Series 1000 and Series 2000 Transmitters
Page 21
Using the Transmitter Display
Auto Scroll may or may not be enabled:
If Auto Scroll is enabled, each configured display variable will be shown for the number of seconds specified for Scroll Rate. At any time, you can interrupt the automatic scrolling (e.g., to control the display manually) by activating either optical switch. The display reverts to auto scrolling after 30 seconds of inactivity.
Whether Auto Scroll is enabled or not, the operator can manually scroll through the configured display variables by activating
For more information on using the display to view process variables or manage totalizers and inventories, see Chapter 7.

2.4.3 Display menus

Scroll.
To enter the display menus, activate will flash. Hold
Scroll and Select until the words SEE ALARM or OFF-LINE MAINT appear.
To move through a list of options, activate
To select from a list, scroll to the desired option, then activate
Scroll and Select simultaneously. The optical switch indicator
Scroll.
Select.
For entry into certain sections of the display menu:
If a password has been enabled, you will be prompted to enter it. See Section 2.4.4.
If a display password is not required, you will be prompted to activate the optical switches in a pre-defined sequence (
Scroll-Select-Scroll). This feature is designed to prevent unintentional
entry to the menu caused by variations in ambient lighting or other environmental factors.
To exit a display menu without making any changes:
•Use the
If the
EXIT option if available.
EXIT option is not available, activate Scroll and Select simultaneously, and hold until
the screen returns to the previous display.

2.4.4 Display password

A password can be used to control access to either the off-line maintenance menu, the alarm menu, or both. The same code is used for both:
If both passwords are enabled, the user must enter the password to access the top-level off-line menu. The user can then access either the alarm menu or the off-line maintenance menu without re-entering the password.
If only one password is enabled, the user can access the top-level off-line menu, but will be prompted for the password when he or she attempts to access the alarm menu or the off-line maintenance menu (depending on which password is enabled). The user can access the other menu without a password.
If neither password is enabled, the user can access all parts of the off-line menu without a password.
For information about enabling and setting the display password, see Section 8.14.
Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin
Note: If the petroleum measurement application is installed on your transmitter, the display password is always required to start, stop, or reset a totalizer, even if neither password is enabled. If the petroleum measurement application is not installed, the display password is never required for these functions, even if one of the passwords is enabled.
Configuration and Use Manual 11
Page 22
Using the Transmitter Display
SX.XXXX
Sign
For positive numbers, leave this space blank. For negative numbers, enter a minus sign (–).
Digits
Enter a number (maximum length: eight digits, or seven digits and a minus sign). Maximum precision is four.
If a password is required, the word CODE? appears at the top of the password screen. Enter the digits of the password one at a time by using digit.
If you encounter the display password screen but do not know the password, wait 30 seconds without activating any of the display optical switches. The password screen will timeout automatically and you will be returned to the previous screen.

2.4.5 Entering floating-point values with the display

Certain configuration values, such as meter factors or output ranges, are entered as floating-point values. When you first enter the configuration screen, the value is displayed in decimal notation (as shown in Figure 2-2) and the active digit is flashing.
Figure 2-2 Numeric values in decimal notation
Scroll to choose a number and Select to move to the next
To change the value:
Select to move one digit to the left. From the leftmost digit, a space is provided for a sign. The
1. sign space wraps back to the rightmost digit.
2.
Scroll to change the value of the active digit: 1 becomes 2, 2 becomes 3, ..., 9 becomes 0, 0
becomes 1. For the rightmost digit, an E option is included to switch to exponential notation.
To change the sign of a value:
1.
Select to move to the space that is immediately left of the leftmost digit.
2. Use
Scroll to specify a minus sign (–) for a negative value or a blank space for a positive value.
In decimal notation, you can change the position of the decimal point up to a maximum precision of four (four digits to the right of the decimal point). To do this:
1.
Select until the decimal point is flashing.
2.
Scroll. This removes the decimal point and moves the cursor one digit to the left.
3.
Select to move one digit to the left. As you move from one digit to the next, a decimal point
will flash between each digit pair.
4. When the decimal point is in the desired position,
Scroll. This inserts the decimal point and
moves the cursor one digit to the left.
12 Micro Motion Series 1000 and Series 2000 Transmitters
Page 23
Using the Transmitter Display
SX.XXXEYY
Sign
Digits
Enter a four-digit number; three digits must fall to the right of the decimal point.
E
Exponent indicator
Sign or Digit (0–3)
Digit (0–9)
To change from decimal to exponential notation (see Figure 2-3):
Select until the rightmost digit is flashing.
1.
2.
Scroll to E, then Select. The display changes to provide two spaces for entering the exponent.
3. To enter the exponent:
a.
Select until the desired digit is flashing.
b.
Scroll to the desired value. You can enter a minus sign (first position only), values
between 0 and 3 (for the first position in the exponent), or values between 0 and 9 (for the second position in the exponent).
c.
Select.
Notes: When switching between decimal and exponential notation, any unsaved edits are lost. The system reverts to the previously saved value.
While in exponential notation, the positions of the decimal point and exponent are fixed.
Figure 2-3 Numeric values in exponential notation
Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin
To change from exponential to decimal notation:
1.
Select until the E is flashing.
Scroll to d.
2.
3.
Select. The display changes to remove the exponent.
To exit the menu:
If the value has been changed,
Select and Scroll simultaneously until the confirmation screen
is displayed.
-
Select to apply the change and exit.
-
Scroll to exit without applying the change.
If the value has not been changed,
Select and Scroll simultaneously until the previous screen
is displayed.
Configuration and Use Manual 13
Page 24
14 Micro Motion Series 1000 and Series 2000 Transmitters
Page 25
Chapter 3
• Model 1500 AN
• Model 1700 AN
• Model 1700 IS
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO

Connecting with ProLink II or Pocket ProLink Software

3.1 Overview

ProLink II is a Windows-based configuration and management tool for Micro Motion transmitters. It provides complete access to transmitter functions and data. Pocket ProLink is a version of ProLink II that runs on a Pocket PC.
This chapter provides basic information for connecting ProLink II or Pocket ProLink to your transmitter. The following topics and procedures are discussed:
Requirements (see Section 3.2)
Configuration upload/download (see Section 3.3)
Connecting to a Model 1700 or 2700 transmitter (see Section 3.4)
Connecting to a Model 1500 or 2500 transmitter (see Section 3.5)
Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin
The instructions in this manual assume that users are already familiar with ProLink II or Pocket ProLink software. For more information on using ProLink II, see the ProLink II manual. For more information on using Pocket ProLink, see the Pocket ProLink manual. Instructions in this manual will refer only to ProLink II.

3.2 Requirements

To use ProLink II with a Series 1000 or 2000 transmitter, the following are required:
ProLink II v2.0 or later for most basic functions
ProLink II v2.5 or later for access to many advanced functions, such as meter verification
Signal converter(s), to convert the PC port’s signal to the signal used by the transmitter
- For RS-485 connections, an RS-485 to RS-232 signal converter. The Black Box IC521A-F RS-232 to RS-485 converter is recommended. For computers without serial ports, the Black Box IC138A USB to RS-232 converter can be used in conjunction with the IC521A-F. Both converters are available from Micro Motion.
- For Bell 202 connections, a HART interface. The MACTek Interface (for serial port) or USB HART Interface Model 010031 (for USB) are recommended. Both converters are available from Micro Motion.
25-pin to 9-pin adapter (if required by your PC)
Note: If you are using the enhanced core processor and you connect directly to the core processor’s RS-485 terminals (see Figure B-4 or Figure B-14) instead of to the transmitter, ProLink II v2.4 or later is required. This connection type is sometimes used for troubleshooting.
®
®
Viator® RS232 HART
Async
Configuration and Use Manual 15
Page 26
Connecting with ProLink II or Pocket ProLink Software

3.3 ProLink II configuration upload/download

ProLink II provides a configuration upload/download function which allows you to save configuration sets to your PC. This allows:
Easy backup and restore of transmitter configuration
Easy replication of configuration sets
Micro Motion recommends that all transmitter configurations be downloaded to a PC as soon as the configuration is complete.
To access the configuration upload/download function:
1. Connect ProLink II to your transmitter as described in this chapter.
2. Open the
File menu.
To save a configuration file to a PC, use the
Load from Xmtr to File option.
To restore or load a configuration file to a transmitter, use the option.

3.4 Connecting from a PC to a Model 1700 or Model 2700 transmitter

Depending on your transmitter, there are several options for connecting ProLink II to your transmitter. See Table 3-1.
Notes: Service port connections use standard settings, do not require transmitter configuration, and are always available. Therefore, they are easy and convenient. However, service port connections require opening the power supply compartment. Accordingly, service port connections should be used only for temporary connections, and may require extra safety precautions.
Due to the design of HART protocol, connections made using HART protocol are slower than connections that use Modbus protocol. If you use HART protocol, you cannot open more than one ProLink II window at a time.
Table 3-1 Connection options for Model 1700 or Model 2700 transmitters
Connection Physical layer Protocol
Service port (see Section 3.4.1)
RS-485 terminals or RS-485 network (see Section 3.4.2)
Primary mA terminals or HART network (see Section 3.4.3)
RS-485 Modbus
RS-485 Modbus
RS-485 HART
Bell 202 HART
1700/2700 AN 1700/2700 IS 2700 CIO
Send to Xmtr from File
Transm itter
16 Micro Motion Series 1000 and Series 2000 Transmitters
Page 27
Connecting with ProLink II or Pocket ProLink Software
WARNING
WARNING
WARNING
• Model 1700 AN
• Model 1700 IS
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO

3.4.1 Connecting to the service port

To connect to the service port, which is located in the non-intrinsically safe power supply compartment (see Figure 3-1):
1. Attach the signal converter to the serial or USB port of your PC, using a 25-pin to 9-pin adapter if required.
2. Open the cover to the wiring compartment.
Opening the wiring compartment in a hazardous area can cause an explosion.
Because the wiring compartment must be open to make this connection, the service port should be used only for temporary connections, for example, for configuration or troubleshooting purposes.
When the transmitter is in an explosive atmosphere, use a different method to connect to your transmitter.
Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin
3. Open the power supply compartment.
Opening the power supply compartment in explosive atmospheres while the power is on can cause an explosion.
Before using the service port to communicate with the transmitter in a hazardous area, make sure the atmosphere is free from explosive gases.
Opening the power supply compartment can expose the operator to electric shock.
To avoid the risk of electric shock, do not touch the power supply wires or terminals while using the service port.
4. Connect the signal converter leads to the service port terminals. See Figure 3-1.
Configuration and Use Manual 17
Page 28
Connecting with ProLink II or Pocket ProLink Software
Service port
RS-485 to RS-232 signal converter
25-pin to 9-pin serial port adapter (if necessary)
Model 1700 or 2700 transmitter
terminal compartment
RS-485/A
RS-485/B
PC
• Model 1700 AN
• Model 2700 AN
Figure 3-1 Service port connections to Model 1700 or 2700
5. Start ProLink II. Choose
Connection > Connect to Device. In the screen that appears,
specify:
Protocol: Service Port
COM Port: as appropriate for your PC
All other parameters are set to service port required values and cannot be changed.
6. Click
Connect.
7. If an error message appears:
a. Swap the leads between the two service port terminals and try again.
b. Ensure that you are using the correct COM port.
c. Check all the wiring between the PC and the transmitter.

3.4.2 Connecting to the RS-485 terminals or an RS-485 network

To connect a PC to the RS-485 terminals or an RS-485 network:
1. Attach the signal converter to the serial or USB port of your PC, using a 25-pin to 9-pin adapter if required.
2. To connect to the RS-485 terminals, open the cover to the wiring compartment and connect the signal converter leads to the transmitter terminals labeled Figure 3-2.
5 and 6, or to the output wires from these terminals. See
3. To connect to an RS-485 network, connect the signal converter leads to any point in the network. See Figure 3-3.
4. For long-distance communication, or if noise from an external source interferes with the signal, install 120 Ω, 1/2 watt resistors in parallel with the output at both ends of the communication segment.
18 Micro Motion Series 1000 and Series 2000 Transmitters
Page 29
Connecting with ProLink II or Pocket ProLink Software
RS-485 to RS-232
signal converter
25-pin to 9-pin serial port
adapter (if necessary)
Model 1700 or 2700 transmitter
terminal compartment
(transmitters with analog outputs
option boards only)
PC
DCS or PLC
Add resistance if necessary (see Step 4)
RS-485 to RS-232 signal converter
25-pin to 9-pin serial port adapter (if necessary)
PC
Figure 3-2 RS-485 terminal connections to Model 1700 or 2700 AN
Figure 3-3 RS-485 network connections to Model 1700 or 2700 AN
Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin
Note: If you do not know the transmitter’s RS-485 configuration, you can connect through the service port, which always uses default settings, or you can use the Communicator or the display to view or change the transmitter’s RS-485 configuration.
Configuration and Use Manual 19
5. Start ProLink II. Choose
6. Set
Protocol, Baud Rate, Stop Bits, and Parity to the RS-485 values configured in the
Connection > Connect to Device.
transmitter. See Section 8.15.
7. Set the
Address/Tag value to the Modbus or HART polling address configured for the
transmitter. The default Modbus address is 1; the default HART polling address is 0. See Section 8.15.
8. Set the
9. Click
COM Port value to the PC COM port assigned to this connection.
Connect.
Page 30
Connecting with ProLink II or Pocket ProLink Software
CAUTION
• Model 1700 AN
• Model 1700 IS
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO
10. If an error message appears:
a. Swap the leads and try again.
b. You may be using incorrect connection parameters.
- Ensure you are using the correct COM port.
- Connect using the service port and check the RS-485 configuration. If required, change the configuration or change your RS-485 connection parameters to match the existing configuration.
- If you are unsure of the transmitter’s address. use the window to return a list of all devices on the network.
- Check all the wiring between the PC and the network. You may need to add resistance. See Figure 3-3.

3.4.3 Connecting to the primary mA output terminals or to a HART multidrop network

Connecting a HART device to the transmitter’s primary mA output terminals could cause transmitter output error.
Poll button in the Connect
If the primary mA output is being used for flow control, connecting a HART device to the output loop could cause the transmitter’s 4–20 mA output to change, which would affect flow control devices.
Set control devices for manual operation before connecting a HART device to the transmitter’s primary mA output loop.
To connect a PC to the primary mA output terminals or to a HART multidrop network:
1. If you are connecting to an AN or CIO transmitter, see Figure 3-4. If you are connecting to an IS transmitter, see Figure 3-5.
2. Attach the HART interface to the serial or USB port of your PC.
3. To connect to the primary mA output terminals, open the cover to the intrinsically safe wiring compartment and connect the HART interface leads to the terminals labeled
1 and 2, or to the
output wires from these terminals.
4. To connect to a HART multidrop network, connect the HART interface leads to any point on the network.
20 Micro Motion Series 1000 and Series 2000 Transmitters
Page 31
Connecting with ProLink II or Pocket ProLink Software
VIATOR
1 (+)
2 (–)
Model 1700/2700 AN Model 2700 CIO
R2 See Step 5
R3 See Step 5
DCS or
PLC
R1 See Step 5
+
VIATOR
VIATOR
or
+ –
DCS or
PLC
R2 See Step 5
R3 See Step 5
R1 See Step 5
Primary mA output terminals See Step 3
Transmitter
External power supply
See Step 5
USB plug
Figure 3-4 HART/Bell 202 connections to Model 1700/2700 AN or Model 2700 CIO
Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin
Figure 3-5 HART/Bell 202 connections to Model 1700/2700 IS
Configuration and Use Manual 21
Page 32
Connecting with ProLink II or Pocket ProLink Software
R
max
= (V
supply
– 12)/0.023
A minimum of 250 ohms and 17.5 volts is required
Supply voltage VDC (Volts)
External resistance (Ohms)
Operating range
12 3014 16 18 20 22 24 26 28
0
1000
900
800
700
600
500
400
300
200
100
5. Add resistance as required. The Viator HART interface must be connected across a resistance of 250–600 Ω. In addition, if you are using an IS transmitter, the primary mA output requires an external power supply with a minimum of 250 Ω and 17.5 volts (see Figure 3-6). To meet the resistance requirements, you may use any combination of resistors R1, R2, and R3 (see Figure 3-4 or 3-5).
Figure 3-6 Model 1700/2700 IS: Resistance and voltage requirements for HART/Bell 202 connections
Connection > Connect to Device.
6. Start ProLink II. Choose
Protocol to HART Bell 202. Baud rate, Stop bits, and Parity are automatically set to the
7. Set values required by HART protocol.
8. Set the
Address/Tag value to the HART polling address configured for the transmitter. The
default HART polling address is 0. See Section 8.15 for information on the HART polling
22 Micro Motion Series 1000 and Series 2000 Transmitters
Note: The 275 HART Communicator or 375 Field Communicator is not a host.
address.
9. Set the
10. Set
COM Port value to th e PC COM port assigned to this connection.
Master as appropriate:
If another host such as a DCS is on the network, set
If no other host is on the network, set
11. Click
Connect.
Master to Primary.
Master to Secondary.
Page 33
Connecting with ProLink II or Pocket ProLink Software
• Model 1500 AN
• Model 2500 CIO
12. If an error message appears:
a. You may be using incorrect connection parameters.
- Ensure you are using the correct COM port.
- If you are unsure of the transmitter’s address, use the window to return a list of all devices on the network.
b. Check all the wiring between the PC and the transmitter.
c. Increase or decrease resistance.

3.5 Connecting from a PC to a Model 1500 or Model 2500 transmitter

ProLink II software can communicate with a Model 1500 or Model 2500 transmitter using:
Poll button in the Connect
Modbus/RS-485 protocol (see Section 3.5.1
)
- Configurable connection
- SP (service port) standard connection
A HART/Bell 202 connection (see Section 3.5.2
)
Note: Service port connections use standard settings and do not require transmitter configuration. Therefore, they are easy and convenient. However, service port connections can be established only during a 10-second interval after power-up. See Step 5 in the following section.
Note: Due to the design of HART protocol, connections made using HART protocol are slower than connections that use Modbus protocol. If you use HART protocol, you cannot open more than one ProLink II window at a time.

3.5.1 Connecting to the RS-485 terminals or an RS-485 network

To connect a PC to the RS-485 terminals or an RS-485 network:
1. Attach the signal converter to the serial or USB port of your PC, using a 25-pin to 9-pin adapter if required.
2. To connect to the RS-485 terminals, connect the signal converter leads to terminals 33 and 34. See Figure 3-7.
3. To connect to an RS-485 network, connect the signal converter leads to any point in the network. See Figure 3-8.
4. For long-distance communication, or if noise from an external source interferes with the signal, install 120 ohm, 1/2 watt resistors in parallel with the output at both ends of the communication segment.
Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin
Configuration and Use Manual 23
Page 34
Connecting with ProLink II or Pocket ProLink Software
RS-485/B
RS-485/A
RS-485 to RS-232 signal converter
25-pin to 9-pin serial port adapter (if necessary)
PC
DCS or PLC
Add resistance if necessary (see Step 4)
RS-485 to RS-232 signal converter
25-pin to 9-pin serial port adapter (if necessary)
PC
RS-485/B
RS-485/A
Figure 3-7 RS-485 terminal connections to Model 1500 or 2500
Figure 3-8 RS-485 network connections to Model 1500 or 2500
24 Micro Motion Series 1000 and Series 2000 Transmitters
Page 35
Connecting with ProLink II or Pocket ProLink Software
5. Start ProLink II. Choose Connection > Connect to Device. In the screen that appears, specify connection parameters appropriate to your connection type:
Service port mode – Immediately after the transmitter is powered up, terminals 33 and 34
are available in service port mode for 10 seconds. To connect during this period, set
Protocol to Service Port, and set COM port to the appropriate value for your PC. Baud rate
, Stop bits, and Parity are set to standard values and cannot be changed (see Table 3-2). If a connection is made during this period, the port will remain in service port mode until power is cycled.
RS-485 mode – If no connection is made during the 10-second period, the terminals are automatically reset to the configured RS-485 communication parameters. To connect, set the connection parameters to the values configured in your transmitter (see Table 3-2).
Table 3-2 Modbus connection parameters for ProLink II
Connection type
Connection parameter Configurable (RS-485 mode) SP standard (service port mode)
Protocol As configured in transmitter
(default = Modbus RTU) Baud rate As configured in transmitter (default = 9600) 38,400 Stop bits As configured in transmitter (default = 1) 1 Parity As configured in transmitter (default = odd) none Address/Tag Configured Modbus address (default = 1) 111 COM port COM port assigned to PC serial port COM port assigned to PC serial port
(1) Required value; cannot be changed by user.
6. Click
Connect.
Modbus RTU
(1)
(1)
(1)
(1)
(1)
7. If an error message appears:
a. Swap the leads between the two terminals and try again.
b. Ensure you are using the correct COM port.
c. If you are in RS-485 mode, you may be using incorrect connection parameters.
Connect using the service port and check the RS-485 configuration. If required, change the configuration or change your RS-485 connection parameters to match the existing configuration.
If you are unsure of the transmitter’s address. use the
Poll button in the Connect
window to return a list of all devices on the network.
Check all the wiring between the PC and the transmitter.
Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin
Configuration and Use Manual 25
Page 36
Connecting with ProLink II or Pocket ProLink Software
CAUTION
VIATOR
250–600 Ω

3.5.2 HART/Bell 202 connections

Connecting a HART device to the transmitter’s primary mA output terminals could cause transmitter output error.
If the primary mA output is being used for flow control, connecting a HART device to the output loop could cause the transmitter’s 4–20 mA output to change, which would affect flow control devices.
Set control devices for manual operation before connecting a HART device to the transmitter’s primary mA output loop.
Follow the instructions below to make the connection.
1. Connect the HART interface to your PC’s serial or USB port. Then connect the leads of the HART interface to terminals 21 and 22 on the transmitter (see Figure 3-9).
Figure 3-9 HART/Bell 202 connections to Model 1500 or 2500
2. Add 250–600 Ω resistance to the connection, as required.
3. Start ProLink II. Choose
4. In the screen that appears, set
Connection > Connect to Device.
Protocol to HART Bell 202. Baud rate, Stop bits, and Parity
are automatically set to the values required by HART protocol. Specify the remaining connection parameters as shown in Table 3-3.
Table 3-3 HART connection parameters for ProLink II
Connection parameter HART setting
Address/Tag Configured HART polling address (default = 0)
COM port COM port assigned to PC serial port
26 Micro Motion Series 1000 and Series 2000 Transmitters
Page 37
Connecting with ProLink II or Pocket ProLink Software
5. Click Connect.
6. If an error message appears:
a. Ensure that you are using the correct COM port.
b. Check all the wiring between the PC and the transmitter.
c. Increase or decrease the resistance.

3.6 ProLink II language

ProLink II can be configured for several different languages. To configure the ProLink II language, choose
Tools > Options.
In this manual, English is used as the ProLink II language.
Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin
Configuration and Use Manual 27
Page 38
28 Micro Motion Series 1000 and Series 2000 Transmitters
Page 39
Chapter 4
• Model 1500 AN
• Model 1700 AN
• Model 1700 IS
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO

Connecting with the 275 HART Communicator or 375 Field Communicator

4.1 Overview

The 275 HART Communicator and the 375 Field Communicator are handheld configuration and management tools for HART-compatible devices, including Micro Motion transmitters.
This chapter provides basic information for connecting the 275 HART Communicator or 375 Field Communicator to your transmitter. The following topics and procedures are discussed:
Communicator models (see Section 4.2)
Connecting to a transmitter (see Section 4.3)
Conventions used in this manual (see Section 4.4)
The instructions in this manual assume that users are already familiar with the Communicator and can perform the following tasks:
Turn on the Communicator
Navigate the Communicator menus
Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin

4.2 Communicator models

Configuration and Use Manual 29
Establish communication with HART-compatible devices
Transmit and receive configuration information between the Communicator and HART-compatible devices
Use the alpha keys to type information
If you are unable to perform the tasks listed above, consult the Communicator manual before attempting to use the Communicator. The documentation is available on the Micro Motion web site (www.micromotion.com).
Two models of the Communicator – the 275 HART Communicator and the 375 Field Communicator – can be used with Series 1000 and Series 2000 transmitters. However, the 275 HART Communicator does not have device descriptions for all models. In some cases, you can communicate with a transmitter using a device description that provides partial support for the new transmitter’s features.
Some features of the Series 1000 and 2000 transmitters, e.g., gas standard volume flow, are not supported by the device descriptions for either the 275 or 375 Communicator.
Table 4-1 lists the Communicator device descriptions that are available for Series 1000 and 2000 transmitters, and the type of support they provide.
Page 40
Connecting with the 275 HART Communicator or 375 Field Communicator
• Model 2500 CIO
HART Communicator Notice: Upgrade 275 Software to access new Xmtr functions. Continue with old description?
Table 4-1 Communicator models, device descriptions, and transmitter support
275 HART Communicator 375 Field Communicator
Transm itter
Model 1500 AN Not available None 1500 Mass Flow Full
Model 1700 AN 1000 Mass Flow Full 1000 Mass Flow Full
Model 1700 IS 1000I Mass Flow Full 1000I Mass Flow Full
Model 2500 CIO 2000C Mass Flow
Model 2700 AN 2000 Mass Flow Full 2000 Mass Flow Full
Model 2700 IS 2000I Mass Flow Full 2000I Mass Flow Full
Model 2700 CIO 2000C Mass Flow Full 2000C Mass Flow Full
(1) “Full” support does not include all functionality (e.g., gas standard volume flow). (2) See Section 4.2.2 for information on using the 275 HART Communicator with this transmitter.
Device description Support
(2)
Partial 2000C Mass Flow Full
(1)
Device description Support

4.2.1 Viewing the device descriptions

HART Communicator 275
(1)
To view the device descriptions that are installed on your 275 HART Communicator:
1. Turn on the HART Communicator, but do not connect it to the transmitter.
2. When the words
3. Select
4. Select
5. Select
OFFLINE.
New Configuration.
Micro Motion.
No device found appear, press OK.
375 Field Communicator
To view the device descriptions that are installed on your 375 Field Communicator:
1. At the HART application menu, select
2. Select
3. Select
Available Device Descriptions.
Micro Motion.
Utility.

4.2.2 Using the 275 HART Communicator with the Model 2500

To use the 275 HART Communicator with the Model 2500 transmitter:
1. Turn on the HART Communicator and connect it to the transmitter. The following warning message is displayed:
30 Micro Motion Series 1000 and Series 2000 Transmitters
2. Press
Yes to continue using the 275 HART Communicator. Do not upgrade the 275 HART
Communicator.
Page 41
Connecting with the 275 HART Communicator or 375 Field Communicator
CAUTION
WARNING
• Model 1500 AN
• Model 1700 AN
• Model 1700 IS
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO
Note: This procedure allows you to use the device description for the Model 2700 transmitter with the configurable input/outputs option board. You will not be able to configure the RS-485 parameters using this device description. To configure the RS-485 parameters, use the 375 Field Communicator or ProLink II.

4.3 Connecting to a transmitter

You can connect the Communicator directly to the transmitter’s mA/HART terminals or to a point on a HART network.
Note: If you are using the mA/HART terminals to report a process variable and also for HART communication, see the transmitter installation manual for wiring diagrams.

4.3.1 Connecting to communication terminals

To connect the Communicator directly to the transmitter’s mA/HART terminals:
Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin
Connecting a HART device to the transmitter’s primary mA output terminals could cause transmitter output error.
If the primary mA output is being used for flow control, connecting a HART device to the output loop could cause the transmitter’s 4–20 mA output to change, which would affect flow control devices.
Set control devices for manual operation before connecting a HART device to the transmitter’s primary mA output loop.
1. If you are connecting to a Model 1700/2700 transmitter, open the cover to the wiring compartment.
Opening the wiring compartment in a hazardous area can cause an explosion.
Because the wiring compartment must be open to make this connection, connections to the mA terminals should be used only for temporary connections, for example, for configuration or troubleshooting purposes.
When the transmitter is in an explosive atmosphere, use a different method to connect to your transmitter.
Configuration and Use Manual 31
2. Connect the Communicator leads to the transmitter’s primary mA output terminals:
Model 1700/2700 transmitters: terminals 1 and 2 (see Figure 4-1)
Model 1500/2500 transmitters: terminals 21 and 22 (see Figure 4-2)
Page 42
Connecting with the 275 HART Communicator or 375 Field Communicator
Communicator
250–600 Ω
resistance
VDC (IS transmitters only)
See the transmitter installation manual
for voltage and resistance values
1
2
+
250–600 Ω resistance
+–
Communicator
3. The Communicator must be connected across a resistance of 250–600 Ω. Add resistance to the connection. See Figure 4-1.
Figure 4-1 Connecting to communication terminals – Model 1700/2700 transmitters
Figure 4-2 Connecting to communication terminals – Model 1500/2500 transmitters
32 Micro Motion Series 1000 and Series 2000 Transmitters
Page 43
Connecting with the 275 HART Communicator or 375 Field Communicator
Tr an s m it t ers
Communicator
Master
device
250–600 Ω resistance (if necessary)

4.3.2 Connecting to a multidrop network

The Communicator can be connected to any point in a multidrop network. See Figure 4-3.
Note: The Communicator must be connected across a resistance of 250–600 connection if necessary.
Figure 4-3 Connecting to a multidrop network

4.4 Conventions used in this manual

Ω . Add resistance to the
Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin
All Communicator procedures assume that you are starting at the on-line menu. “Online” appears on the top line of the Communicator main menu when the Communicator is at the on-line menu. Figure 4-4 shows the 275 HART Communicator on-line menu for the Model 2700 transmitter with the intrinsically safe outputs option board.
Figure 4-4 275 HART Communicator on-line menu

4.5 HART Communicator safety messages and notes

Users are responsible for responding to safety messages (e.g., warnings) and notes that appear on the Communicator. Safety messages and notes that appear on the Communicator are not discussed in this manual.
Configuration and Use Manual 33
Page 44
34 Micro Motion Series 1000 and Series 2000 Transmitters
Page 45
Chapter 5

Flowmeter Startup

5.1 Overview

This chapter describes the procedures you should perform the first time you install the flowmeter. Performing these steps will help verify that all the flowmeter components are installed and wired correctly. It is usually necessary to perform some additional first-time configuration of the transmitter, which is described in Chapter 6.
The following procedures are discussed:
Applying power to the flowmeter (see Section 5.2) – This step is required.
Performing a loop test on the transmitter outputs (see Section 5.3) – Although this is not a requirement, performing a loop test is strongly recommended as a way to verify that the flowmeter is properly installed and wired.
Trimming the mA outputs (see Section 5.4) – This step may be necessary depending on the results of a loop test.
Zeroing the flowmeter (see Section 5.5) – Zeroing is not generally necessary, but you may need to zero to meet local requirements or if you are instructed to do so by Micro Motion Customer Service.
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
This chapter provides only basic information for each procedure. For more details about how to perform each procedure, see the flowcharts for your transmitter and communication tool, provided in the appendices to this manual.
Notes: All ProLink II procedures provided in this chapter assume that your computer is already connected to the transmitter and you have established communication. All ProLink II procedures also assume that you are complying with all applicable safety requirements. See Chapter 3 for more information.
If you are using AMS, the AMS interface will be similar to the ProLink II interface described in this chapter.
All Communicator procedures provided in this chapter assume that you are starting from the “Online” menu. See Chapter 4 for more information.
Configuration and Use Manual 35
Page 46
Flowmeter Startup
WARNING
WARNING

5.2 Applying power

Before you apply power to the flowmeter, close and tighten all housing covers.
Operating the flowmeter without covers in place creates electrical hazards that can cause death, injury, or property damage.
Make sure safety barrier partition and covers for the field-wiring, circuit board compartments, electronics module, and housing are all in place before applying power to the transmitter.
Using the service port to communicate with a Model 1700/2700 transmitter in a hazardous area can cause an explosion.
Before using the service port to communicate with the transmitter in a hazardous area, make sure the atmosphere is free from explosive gases.
Turn on the electrical power at the power supply. The flowmeter will automatically perform diagnostic routines. When the flowmeter has completed its power-up sequence:
For Model 1700/2700 transmitters under normal conditions, the status LED on the display will turn green and begin to flash.
For Model 1500/2500 transmitters under normal conditions, the status LED will turn green.
If the status LED exhibits different behavior, an alarm condition is present or transmitter zero is in progress. See Section 7.5.
Note: The flowmeter is ready to receive process fluid approximately one minute after power-up (time varies with models). However, approximately ten minutes are required for the electronics to warm up to equilibrium. During this ten-minute period, the transmitter may exhibit minor instability or inaccuracy.

5.2.1 Communication methods after power-up

For Model 1700/2700 transmitters, all communication methods supported by the transmitter are available immediately after power-up.
For Model 1500/2500 transmitters:
If you are using the Communicator, or ProLink II with HART/Bell 202, you can establish communication with the transmitter immediately after power-up, using terminals 21 and 22. See Chapter 3 for more information on using ProLink II and Chapter 4 for more information on using the Communicator.
If you are using ProLink II via the RS-485 physical layer, terminals 33 and 34 are available to establish a connection in service port mode for 10 seconds immediately after power-up. If no service port connection is made during this period, the terminals are automatically reset to the configured Modbus communication parameters. Be sure to set the ProLink II connection parameters appropriately. See Chapter 3.
36 Micro Motion Series 1000 and Series 2000 Transmitters
Page 47
Flowmeter Startup
Fix Milliamp
1 or 2
Fix Discrete Output
1 or 2
Read Discrete Input
Enter mA value ON or OFF
Read output at
receiving device
Verify state at
receiving device
Toggle remote input
device
Verify state
at transmitter
Correct? Correct? Correct?
Check output wiring Troubleshoot receiving device
Loop test successful
Check input wiring Troubleshoot input device
Yes No Yes No
Fix Freq Out
Read output at
receiving device
Correct?
Enter Hz value
Unfix output
Note: Not all inputs and outputs shown here will be available on every device.

5.3 Performing a loop test

A loop test is a means to:
Verify that analog outputs (mA and frequency) are being sent by the transmitter and received accurately by the receiving devices
Determine whether or not you need to trim the mA outputs
Select and verify the discrete output voltage
Read the discrete input
Perform a loop test on all inputs and outputs available on your transmitter. Before performing the loop tests, ensure that your transmitter’s channels are configured for the input/outputs that will be used in your application (see Section 6.3).
You can perform a loop test with the display, with ProLink II, or the Communicator. The general procedure for performing a loop test is shown in Figure 5-1.
Notes: If you are using the display, dots will traverse the top line of the display when an output is fixed, and the status LED will blink yellow.
If the custody transfer application is enabled on the transmitter, it is not possible to perform a loop test of the frequency output, even when in security breach mode.
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
If you are using either a Communicator or ProLink II via HART/Bell 202, the HART signal will affect the primary mA reading. While testing the primary mA output, disconnect the Communicator or ProLink II before reading the output, then reconnect the Communicator or ProLink II and resume the loop test after taking the reading.
Milliamp readings do not need to be exact. You will correct differences when you trim the mA output(s).
Figure 5-1 Loop test procedure
Configuration and Use Manual 37
Page 48
Flowmeter Startup
Read mA output at
receiving device
Read mA output at
receiving device
Equal?
Enter receiving device
value
Done
No
Yes
Perform the procedure for each mA output at both 4 mA and 20 mA.

5.4 Trimming the milliamp outputs

Trimming the mA output creates a common measurement range between the transmitter and the device that receives the mA output. For example, a transmitter might send a 4 mA signal that the receiving device reports incorrectly as 3.8 mA. If the transmitter output is trimmed correctly, it will send a signal appropriately compensated to ensure that the receiving device actually indicates a 4 mA signal.
You must trim the mA output at both the 4 mA and 20 mA points to ensure appropriate compensation across the entire output range.
Perform a milliamp trim on all mA outputs available on your transmitter. Before performing the trim, ensure that your transmitter’s channels are configured for the input/outputs that will be used in your application (see Section 6.3).
You can trim the outputs with ProLink II or a Communicator. The general procedure for performing a milliamp trim is shown in Figure 5-2.
Notes: If you are using either a Communicator or ProLink II via HART/Bell 202, the HART signal will affect the primary mA reading. While trimming the primary mA output, disconnect the Communicator or ProLink II before reading the output, then reconnect the Communicator or ProLink II and resume the trim procedure after taking the reading.
Any trimming performed on the output should not exceed ±200 microamps. If more trimming is required, contact Micro Motion customer support.
Figure 5-2 Trimming the milliamp output
38 Micro Motion Series 1000 and Series 2000 Transmitters
Page 49
Flowmeter Startup
CAUTION

5.5 Zeroing the flowmeter

Zeroing the flowmeter establishes the flowmeter’s point of reference when there is no flow. The meter was zeroed at the factory, and should not require a field zero. However, you may wish to perform a field zero to meet local requirements or to confirm the factory zero.
When you zero the flowmeter, you may need to adjust the zero time parameter. Zero time is the amount of time the transmitter takes to determine its zero-flow reference point. The default zero time is 20 seconds.
•A long zero time may produce a more accurate zero reference but is more likely to result in a zero failure. This is due to the increased possibility of noisy flow, which causes incorrect calibration.
•A short zero time is less likely to result in a zero failure but may produce a less accurate zero reference.
For most applications, the default zero time is appropriate.
Note: In some menus, a convergence limit parameter is displayed. Micro Motion recommends that you use the default value for convergence limit.
Note: Do not zero the flowmeter if a high severity alarm is active. Correct the problem, then zero the flowmeter. You may zero the flowmeter if a low severity alarm is active. See Section 7.5 for information on viewing transmitter status and alarms.
If the zero procedure fails, see Section 12.6 for troubleshooting information. Additionally, if you have the enhanced core processor:
You can restore the factory zero. This procedure returns the zero value to the value obtained at the factory. The factory zero can be restored with ProLink II or the display (if the transmitter has a display).
If you are using ProLink II to zero the flowmeter, you can also restore the prior zero immediately after zeroing (e.g., an “undo” function), as long as you have not closed the Calibration window or disconnected from the transmitter. Once you have closed the Calibration window or disconnected from the transmitter, you can no longer restore the prior zero.

5.5.1 Preparing for zero

To prepare for the zero procedure:
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
1. Apply power to the flowmeter. Allow the flowmeter to warm up for approximately 20 minutes.
2. Run the process fluid through the sensor until the sensor temperature reaches the normal process operating temperature.
3. Close the shutoff valve downstream from the sensor.
4. Ensure that the sensor is completely filled with fluid.
5. Ensure that the process flow has completely stopped.
If fluid is flowing through the sensor, the sensor zero calibration may be inaccurate, resulting in inaccurate process measurement.
To improve the sensor zero calibration and measurement accuracy, ensure that process flow through the sensor has completely stopped.
Configuration and Use Manual 39
Page 50
Flowmeter Startup
Status LED
Status LED flashes
yellow
Done
Solid Green or
Solid Yellow
Troubleshoot
Solid
Red
Press ZERO button
Modify zero time
if required
Calibration
Failure LED
Calibration in Progress
LED turns red
Green
Troubleshoot
Red
Perform Auto Zero
Done
ProLink > Calibration > Zero Calibration
Wait until Calibration in
Progress LED turns green

5.5.2 Zero procedure

To zero the flowmeter, refer to the procedures shown in Figures 5-3 through 5-6. Note the following:
The zero button is available only on Model 1500 or Model 2500 transmitters. It is located on
If the off-line menu has been disabled, you will not be able to zero the transmitter with the
You cannot change the zero time with the zero button or the display. If you need to change the
Figure 5-3 Zero button – Flowmeter zero procedure
the front panel of the transmitter. To press the zero button, use a fine-pointed object that will fit into the opening (0.14 in [3.5 mm]). Hold the button down until the status LED begins to flash yellow.
display.
zero time, you must use the Communicator or ProLink II.
40 Micro Motion Series 1000 and Series 2000 Transmitters
Figure 5-4 ProLink II – Flowmeter zero procedure
Page 51
Flowmeter Startup
………………….
OFF-LINE MAINT
Scroll and Select simultaneously
for 4 seconds
Scroll
Select
Select
CAL ZERO
ZERO/YES?
CAL PASSCAL FAIL
EXIT
Scroll
Scroll
Select
ZERO
Troubleshoot
Select
RESTORE ZERO
(1)
Scroll
Select
xxxx CUR Z
Scroll
yyyy FAC Z
Scroll
EXIT
RESTORE/YES?
Select
Select
Scroll
RESTORE ZERO
Scroll
YesNo
Scroll
RESTORE EXIT
(1) Available only on systems with the enhanced core processor.
Figure 5-5 Display menu – Flowmeter zero procedure
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
Configuration and Use Manual 41
Page 52
Flowmeter Startup
Modify zero time if
required
Perform auto zero
Auto Zero Failed Auto Zero Complete
OK
1 Auto zero
Calibration in Progress
message
OK
On-Line Menu > 3 Diag/Service > 3 Calibration
Troubleshoot
Figure 5-6 Communicator – Flowmeter zero procedure
42 Micro Motion Series 1000 and Series 2000 Transmitters
Page 53
Chapter 6
Characterize the
flowmeter
Configure the channels
(Section 6.3)
Configure measurement
units (Section 6.4)
Configure mA outputs
(Section 6.5)
Configure frequency
output (Section 6.6)
(1)
Configure discrete
outputs (Section 6.7)
(1)
Configure discrete input
(Section 6.8)
(1)
Model 2500 Model 2700
Model 1500 Model 1700
Model 2500 Model 2700
Model 1500 Model 1700
Model 2500 CIO Model 2700 CIO
Model 1500 Model 1700
Model 2700 AN
Model 2700 IS
Done
(2)
(1) Only the input or outputs that have been assigned to a channel need to be configured. (2) If the meter verification option has been purchased, the final configuration step should be to
establish a meter verification baseline (Section 6.9).

Required Transmitter Configuration

6.1 Overview

This chapter describes the configuration procedures that are usually required when a transmitter is installed for the first time. The procedures in this chapter should be performed in the order shown in Figure 6-1.
Figure 6-1 Required configuration procedures in order
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
Configuration and Use Manual 43
Page 54
Required Transmitter Configuration
• Model 1500 AN
• Model 1700 AN
• Model 1700 IS
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO
This chapter provides basic information and procedural flowcharts for each configuration step. For more details about how to perform each procedure, see the flowcharts for your transmitter and communication tool, provided in the appendices to this manual.
Default values and ranges for the parameters described in this chapter are provided in Appendix A. Optional configuration procedures are described in Chapter 8.
Notes: All ProLink II procedures provided in this chapter assume that your computer is already connected to the transmitter and you have established communication. All ProLink II procedures also assume that you are complying with all applicable safety requirements. See Chapter 3 for more information.
If you are using AMS, the AMS interface will be similar to the ProLink II interface described in this chapter.
All Communicator procedures provided in this chapter assume that you are starting from the “Online” menu. See Chapter 4 for more information.

6.2 Characterizing the flowmeter

Characterizing the flowmeter adjusts the transmitter to compensate for the unique traits of the sensor it is paired with. The characterization parameters, or calibration parameters, describe the sensor’s sensitivity to flow, density, and temperature.

6.2.1 When to characterize

If the transmitter, core processor, and sensor were ordered together, then the flowmeter has already been characterized. You need to characterize the flowmeter only if the core processor and sensor are being paired together for the first time.

6.2.2 Characterization parameters

The characterization parameters that must be configured depend on your flowmeter’s sensor type: “T-Series” or “Other” (also referred to as “Straight Tube” and “Curved Tube,” respectively), as listed in Table 6-1. The “Other” category includes all Micro Motion sensors except T-Series.
The characterization parameters are provided on the sensor tag. The format of the sensor tag varies depending on your sensor’s date of purchase. See Figures 6-2 and 6-3 for illustrations of newer and older sensor tags.
44 Micro Motion Series 1000 and Series 2000 Transmitters
Page 55
Required Transmitter Configuration
Newer tag Older tag
19.0005.13
19.0005.13
0.0010
0.9980
12502.000
14282.000
4.44000
310
12502142824.44
12500142864.44
Table 6-1 Sensor calibration parameters
Sensor type
Parameter
K1 ✓✓
K2 ✓✓
FD ✓✓
D1 ✓✓
D2 ✓✓
Temp coeff (DT)
Flowcal
FCF and FT
FCF
FTG
FFQ
DTG
DFQ1
DFQ2
(1) See the section entitled “Density calibration factors.” (2) On some sensor tags, shown as TC. (3) See the section entitled “Flow calibration values.” (4) Older T-Series sensors. See the section entitled “Flow calibration values.” (5) Newer T-Series sensors. See the section entitled “Flow calibration values.”
(2)
T- S eri e s O t her
(1)
(1)
(1)
(1)
(1)
✓✓
(4)
(5)
(1)
(3)
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
Figure 6-2 Sample calibration tags – All sensors except T-Series
Configuration and Use Manual 45
Page 56
Required Transmitter Configuration
Newer tag Older tag
Flow FCF X.XXXX FT X.XX
Figure 6-3 Sample calibration tags – T-Series sensors
Density calibration factors
If your sensor tag does not show a D1 or D2 value:
For D1, enter the Dens A or D1 value from the calibration certificate. This value is the line-condition density of the low-density calibration fluid. Micro Motion uses air.
For D2, enter the Dens B or D2 value from the calibration certificate. This value is the line-condition density of the high-density calibration fluid. Micro Motion uses water.
If your sensor tag does not show a K1 or K2 value:
For K1, enter the first 5 digits of the density calibration factor. In the sample tag in Figure 6-2, this value is shown as
12500.
For K2, enter the second 5 digits of the density calibration factor. In the sample tag in Figure 6-2, this value is shown as
14286.
If your sensor does not show an FD value, contact Micro Motion customer service.
If your sensor tag does not show a DT or TC value, enter the last 3 digits of the density calibration factor. In the sample tag in Figure 6-2, this value is shown as
4.44.
Flow calibration values
Two separate values are used to describe flow calibration: a 6-character FCF value and a 4-character FT value. Both values contain decimal points. During characterization, these are entered as a single 10-character string that includes two decimal points. In ProLink II, this value is called the Flowcal parameter; in the Communicator, it is called the FCF for T-Series sensors, and Flowcal for other sensors.
To obtain the required value:
For older T-Series sensors, concatenate the FCF value and the FT value from the sensor tag, as shown below.
For newer T-Series sensors, the 10-character string is represented on the sensor tag as the FCF value. The value should be entered exactly as shown, including the decimal points. No concatenation is required.
For all other sensors, the 10-character string is represented on the sensor tag as the Flow Cal value. The value should be entered exactly as shown, including the decimal points. No concatenation is required.
46 Micro Motion Series 1000 and Series 2000 Transmitters
Page 57
Required Transmitter Configuration
Device
·Sensor type
Flow
T Series Config
Straight
tube
Curved
tube
Sensor type?
Density
Flow
Density
ProLink > Configuration
ProLink II
Device Sensor t ype
Flow
T Seri es Confi g
Straight
tube
Curved
tube
Sensor type?
Density
Flow
Density
ProLink > Configuration
Sensor selection
Flow
Density
On-Line Menu > Detailed Setup
Chari ze sensor
ProLink II Communicator
Communicator
• Model 1500 AN
• Model 1700 AN
• Model 1700 IS
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO

6.2.3 How to characterize

To characterize the flowmeter:
Refer to Figure 6-4.
Ensure that the correct sensor type is configured.
Set required parameters, as listed in Table 6-1.
Figure 6-4 Characterizing the flowmeter
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup

6.3 Configuring the channels

See the Configuration and Use Manual Supplement for your transmitter for information and instructions on channel configuration.

6.4 Configuring the measurement units

For the following process variables, the transmitter must be configured to use the measurement unit appropriate to your application:
Mass flow
•Volume flow
Density
Pressure (optional)
The measurement units used for totalizers and inventories are assigned automatically, based on the measurement unit configured for the corresponding process variable. For example, if per hour) is configured for mass flow, the unit used for the mass totalizer and mass inventory is (kilograms).
To configure measurement units, refer to the flowcharts in Figure 6-5.
Configuration and Use Manual 47
kg/hr (kilograms
kg
Page 58
Required Transmitter Configuration
Density
Temperature
Flow
Pressure
ProLink > Configuration
Units
Off-line maint > Off-line config
Vol (or GSV)
Density
Mass
Temperature
Pressure
Density
Temperature
Flow
Pressure
On-Line Menu > Detailed Setup
Config field dev var
Communicator DisplayProLink II
Figure 6-5 Configuring measurement units
Table 6-2 Mass flow measurement units
G/S g/s g/s Grams per second
G/MIN g/min g/min Grams per minute
G/H g/hr g/h Grams per hour
KG/S kg/s kg/s Kilograms per second
KG/MIN kg/min kg/min Kilograms per minute
KG/H kg/hr kg/h Kilograms per hour
KG/D kg/day kg/d Kilograms per day
T/MIN mTon/min MetTon/min Metric tons per minute
T/H mTon/hr MetTon/h Metric tons per hour
T/D mTon/day MetTon/d Metric tons per day
LB/S lbs/s lb/s Pounds per second
LB/MIN lbs/min lb/min Pounds per minute
LB/H lbs/hr lb/h Pounds per hour
LB/D lbs/day lb/d Pounds per day
ST/MIN sTon/min STon/min Short tons (2000 pounds) per minute
ST/H sTon/hr STon/h Short tons (2000 pounds) per hour
ST/D sTon/day STon/d Short tons (2000 pounds) per day

6.4.1 Mass flow units

The default mass flow measurement unit is
g/s. See Table 6-2 for a complete list of mass flow
measurement units.
If the mass flow unit you want to use is not listed, you can define a special measurement unit for mass flow (see Section 8.5).
Mass flow unit
Unit descriptionDisplay ProLink II Communicator
48 Micro Motion Series 1000 and Series 2000 Transmitters
Page 59
Required Transmitter Configuration
Table 6-2 Mass flow measurement units continued
Mass flow unit
Unit descriptionDisplay ProLink II Communicator
LT/H lTon/hr LTon/h Long tons (2240 pounds) per hour
LT/D lTon/day LTon/d Long tons (2240 pounds) per day
SPECL special Spcl Special unit (see Section 8.5)

6.4.2 Volume flow units

Two different sets of volume flow measurement units are provided:
Units typically used for liquid volume – see Table 6-3
Units typically used for gas volume – see Table 6-4
The default liquid volume flow measurement unit is measurement unit is
SCFM.
L/s. The default gas standard volume flow
By default, only liquid volume flow units are listed. To access the gas volume flow units, you must first use ProLink II to configure Vol Flow Type. See Section 8.4.
Note: The Communicator cannot be used to configure gas volume flow units. If a volume flow unit for gas is configured, the Communicator will display “Unknown Enumerator” for the units label.
If the volume flow unit you want to use is not listed, you can define a special measurement unit for volume flow (see Section 8.5).
Table 6-3 Volume flow measurement units – Liquids
Volume flow unit
Display ProLink II Communicator Unit description
CUFT/S ft3/sec Cuft/s Cubic feet per second
CUF/MN ft3/min Cuft/min Cubic feet per minute
CUFT/H ft3/hr Cuft/h Cubic feet per hour
CUFT/D ft3/day Cuft/d Cubic feet per day
M3/S m3/sec Cum/s Cubic meters per second
M3/MIN m3/min Cum/min Cubic meters per minute
M3/H m3/hr Cum/h Cubic meters per hour
M3/D m3/day Cum/d Cubic meters per day
USGPS US gal/sec gal/s U.S. gallons per second
USGPM US gal/min gal/min U.S. gallons per minute
USGPH US gal/hr gal/h U.S. gallons per hour
USGPD US gal/d gal/d U.S. gallons per day
MILG/D mil US gal/day MMgal/d Million U.S. gallons per day
L/S l/sec L/s Liters per second
L/MIN l/min L/min Liters per minute
L/H l/hr L/h Liters per hour
MILL/D mil l/day ML/d Million liters per day
UKGPS Imp gal/sec Impgal/s Imperial gallons per second
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
Configuration and Use Manual 49
Page 60
Required Transmitter Configuration
Table 6-3 Volume flow measurement units – Liquids continued
Volume flow unit
Display ProLink II Communicator Unit description
UKGPM Imp gal/min Impgal/min Imperial gallons per minute
UKGPH Imp gal/hr Impgal/h Imperial gallons per hour
UKGPD Imp gal/day Impgal/d Imperial gallons per day
BBL/S barrels/sec bbl/s Barrels per second
BBL/MN barrels/min bbl/min Barrels per minute
BBL/H barrels/hr bbl/h Barrels per hour
BBL/D barrels/day bbl/d Barrels per day
BBBL/S Beer barrels/sec bbbl/s Beer barrels per second
BBBL/MN Beer barrels/min bbbl/min Beer barrels per minute
BBBL/H Beer barrels/hr bbbl/h Beer barrels per hour
BBBL/D Beer barrels/day bbbl/d Beer barrels per day
SPECL special Spcl Special unit (see Section 8.5)
(1) Unit based on oil barrels (42 U.S gallons). (2) Unit based on beer barrels (31 U.S gallons).
(1)
(1)
(1)
(1)
(2)
(2)
(2)
(2)
Table 6-4 Volume flow measurement units – Gas
Volume flow unit
Display ProLink II Communicator Unit description
NM3/S Nm3/sec Not available Normal cubic meters per second
NM3/MN Nm3/min Not available Normal cubic meters per minute
NM3/H Nm3/hr Not available Normal cubic meters per hour
NM3/D Nm3/day Not available Normal cubic meters per day
NLPS NLPS Not available Normal liter per second
NLPM NLPM Not available Normal liter per minute
NLPH NLPH Not available Normal liter per hour
NLPD NLPD Not available Normal liter per day
SCFS SCFS Not available Standard cubic feet per second
SCFM SCFM Not available Standard cubic feet per minute
SCFH SCFH Not available Standard cubic feet per hour
SCFD SCFD Not available Standard cubic feet per day
SM3/S Sm3/S Not available Standard cubic meters per second
SM3/MN Sm3/min Not available Standard cubic meters per minute
SM3/H Sm3/hr Not available Standard cubic meters per hour
SM3/D Sm3/day Not available Standard cubic meters per day
SLPS SLPS Not available Standard liter per second
SLPM SLPM Not available Standard liter per minute
50 Micro Motion Series 1000 and Series 2000 Transmitters
Page 61
Required Transmitter Configuration
Table 6-4 Volume flow measurement units – Gas continued
Volume flow unit
Display ProLink II Communicator Unit description
SLPH SLPH Not available Standard liter per hour
SLPD SLPD Not available Standard liter per day
SPECL special Spcl Special unit (see Section 8.5)

6.4.3 Density units

The default density measurement unit is
g/cm3. See Table 6-2 for a complete list of density
measurement units.
Table 6-5 Density measurement units
Density unit
Unit descriptionDisplay ProLink II Communicator
SGU SGU SGU Specific gravity unit (not temperature corrected)
G/CM3 g/cm3 g/Cucm Grams per cubic centimeter
G/L g/l g/L Grams per liter
G/mL g/ml g/mL Grams per milliliter
KG/L kg/l kg/L Kilograms per liter
KG/M3 kg/m3 kg/Cum Kilograms per cubic meter
LB/GAL lbs/Usgal lb/gal Pounds per U.S. gallon
LB/CUF lbs/ft3 lb/Cuft Pounds per cubic foot
LB/CUI lbs/in3 lb/CuIn Pounds per cubic inch
D API degAPI degAPI API gravity
ST/CUY sT/yd3 STon/Cuyd Short ton per cubic yard

6.4.4 Temperature units

The default temperature measurement unit is
degC. See Table 6-6 for a complete list of temperature
measurement units.
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
Table 6-6 Temperature measurement units
Temperature unit
Unit descriptionDisplay ProLink II Communicator
°C degC degC Degrees Celsius
°F degF degF Degrees Fahrenheit
°R degR degR Degrees Rankine
°K degK Kelvin Kelvin
Configuration and Use Manual 51
Page 62
Required Transmitter Configuration

6.4.5 Pressure units

The flowmeter does not measure pressure, but the transmitter can poll an external pressure measurement device. The default pressure measurement unit is
PSI. See Table 6-7 for a complete list
of pressure measurement units. It is not necessary to match units between the transmitter and the external pressure device – the transmitter will convert units for you.
Table 6-7 Pressure measurement units
Pressure unit
Unit descriptionDisplay ProLink II Communicator
FTH2O Ft Water @ 68°F ftH2O Feet water @ 68 °F
INW4C In Water
INW60 In Water @ 60°F inH2O @60DegF Inches water @ 60 °F
INH2O In Water @ 68°F inH2O Inches water @ 68 °F
mmW4C mm Water
mmH2O mm Water
mmHG mm Mercury
INHG In Mercury @ 0°C inHg Inches mercury @ 0 °C
PSI PSI psi Pounds per square inch
BAR bar bar Bar
mBAR millibar mbar Millibar
G/SCM g/cm2 g/Sqcm Grams per square centimeter
KG/SCM kg/cm2 kg/Sqcm Kilograms per square centimeter
PA pascals Pa Pascals
KPA Kilopascals kPa Kilopascals
MPA megapascals MPa Megapascals
TORR Torr
ATM atms atms Atmospheres
@ 4°C inH2O @4DegC Inches water @ 4 °C
@ 4°C mmH2O @4DegC Millimeters water @ 4 °C
@ 68°F mmH2O Millimeters water @ 68 °F
@ 0°C mmHg Millimeters mercury @ 0 °C
@ 0 °C torr Torr @ 0 °C

6.5 Configuring the mA output(s)

See the Configuration and Use Manual Supplement for your transmitter for information and instructions on configuring the mA output(s).

6.6 Configuring the frequency output(s)

See the Configuration and Use Manual Supplement for your transmitter for information and instructions on configuring the frequency output(s).

6.7 Configuring the discrete output(s)

See the Configuration and Use Manual Supplement for your transmitter for information and instructions on configuring the discrete output(s).
52 Micro Motion Series 1000 and Series 2000 Transmitters
Page 63
Required Transmitter Configuration

6.8 Configuring the discrete input

See the Configuration and Use Manual Supplement for your transmitter for information and instructions on configuring the discrete input.

6.9 Establishing a meter verification baseline

Note: This procedure applies only if your transmitter is connected to an enhanced core processor and you have ordered the meter verification application. In addition, ProLink II v2.5 or later is required.
Meter verification is a method of establishing that the flowmeter is performing within factory specifications. See Chapter 10 for more information about Smart Meter Verification.
Micro Motion recommends performing metere verification several times over a range of process conditions after the transmitter’s required configuration procedures have been completed. This will establish a baseline for how widely the verification measurement varies under normal circumstances. The range of process conditions should include the expected variations in flow rate, temperature, density, and pressure.
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
Configuration and Use Manual 53
Page 64
54 Micro Motion Series 1000 and Series 2000 Transmitters
Page 65
Chapter 7

Using the Transmitter

7.1 Overview

This chapter describes how to use the transmitter in everyday operation. The following topics and procedures are discussed:
Special applications on your transmitter (see Section 7.2)
Viewing process variables (see Sections 7.4)
Viewing transmitter status and alarms (see Section 7.5)
Acknowledging alarms (see Section 7.6)
Viewing and using the totalizers and inventories (see Section 7.7)
Notes: All ProLink II procedures provided in this section assume that your computer is already connected to the transmitter and you have established communication. All ProLink II procedures also assume that you are complying with all applicable safety requirements. See Chapter 3 for more information.
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
If you are using AMS, the AMS interface will be similar to the ProLink II interface described in this chapter.
All Communicator key sequences in this section assume that you are starting from the “Online” menu. See Chapter 4 for more information.

7.2 Special applications

Your transmitter may support one of the following special applications:
Petroleum measurement (API feature)
Enhanced density
Either Smart Meter Verification or the original version of the meter verification application
Custody transfer
The special application must be enabled at the factory or by a Micro Motion field service engineer.
Configuration of the petroleum measurement application is discussed in Section 8.6. For information on configuring and using the enhanced density application, see the manual entitled Micro Motion Enhanced Density Application: Theory, Configuration, and Use. Smart Meter Verification is discussed in Chapter 10. For information on configuring the custody transfer application, see Chapter 11.
Configuration and Use Manual 55
Page 66
Using the Transmitter

7.3 Recording process variables

Micro Motion suggests that you make a record of the process variables listed below, under normal operating conditions. This will help you recognize when the process variables are unusually high or low, and may help in fine-tuning transmitter configuration.
Record the following process variables:
Flow rate
Density
•Temperature
Tube frequency
Pickoff voltage
•Drive gain
For information on using this information in troubleshooting, see Section 12.13.

7.4 Viewing process variables

Process variables include measurements such as mass flow rate, volume flow rate, mass total, volume total, temperature, and density.
You can view process variables with the display (Model 1700 and 2700 transmitters only), ProLink II, or the Communicator.

7.4.1 With the display

Process variable values are displayed using either standard decimal notation or exponential notation:
•Values < 100,000,000 are displayed in decimal notation (e.g., 123456.78).
•Values ≥ 100,000,000 are displayed using exponential notation (e.g., 1.000E08).
- If the value is less than the precision configured for that process variable, the value is
displayed as 0 (i.e., there is no exponential notation for fractional numbers).
- If the value is too large to be displayed with the configured precision, the displayed
precision is reduced (i.e., the decimal point is shifted to the right) as required so that the value can be displayed.
See the Configuration and Use Manual Supplement for your transmitter for additional information and instructions on viewing process variables with the display.

7.4.2 With ProLink II

The Process Variables window opens automatically when you first connect to the transmitter. This window displays current values for the standard process variables (mass, volume, density, temperature, external pressure, and external temperature).
To view the standard process variables with ProLink II, if you have closed the Process Variables window, click
To view API process variables (if the petroleum measurement application is enabled), click
API Process Variables
ProLink > Process Variables.
ProLink >
.
To view enhanced density process variables (if the enhanced density application is enabled), click
ProLink > ED Process Variables. Different enhanced density process variables are displayed,
depending on the configuration of the enhanced density application.
56 Micro Motion Series 1000 and Series 2000 Transmitters
Page 67
Using the Transmitter
• Model 1500 AN
• Model 2500 CIO
• Model 1700 AN
• Model 1700 IS
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO

7.4.3 With a Communicator

To view process variables with a Communicator:
1. Press
1, 1.
2. Scroll through the list of process variables by pressing
3. Press the number corresponding to the process variable you wish to view, or highlight the process variable in the list and press

7.5 Viewing transmitter status and alarms

You can view transmitter status using the status LED or display, ProLink II, or the Communicator.
The transmitter broadcasts alarms whenever a process variable exceeds its defined limits or the transmitter detects a fault condition. You can view alarms with the display, ProLink II, or the Communicator. For information regarding all the possible alarms, see Table 12-5.
You can use the display or ProLink II to acknowledge alarms.

7.5.1 Using the status LED

For these transmitters, the status LED is located on the front panel. This LED shows transmitter status as described in Table 7-1.
Down Arrow.
Right Arrow.
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
Table 7-1 Transmitter status reported by the Model 1500/2500 status LED
Status LED state Alarm priority Definition
Green No alarm Normal operating mode
Flashing yellow No alarm Zero in progress
Yellow Low severity alarm • Alarm condition: will not cause measurement error
• Outputs continue to report process data
Red High severity (critical fault) alarm • Alarm condition: will cause measurement error
• Outputs go to configured fault indicators

7.5.2 Using the display

The display reports alarms in two ways:
With the status LED, which reports only that one or more alarms has occurred
Through the alarm list, which reports each specific alarm
Note: If access to the alarm menu from the display has been disabled (see Section 8.14.3), then the display will not list active alarms.
For these transmitters, the status LED is located at the top of the display (see Figure 7-1). It can be in one of six possible states, as listed in Table 7-1.
Configuration and Use Manual 57
Page 68
Using the Transmitter
Status LED
Scroll optical
switch
Select optical switch
Figure 7-1 Display status LED
Table 7-2 Priorities reported by the Model 1700/2700 status LED
Status LED state Alarm priority
Green No alarm – normal operating mode
Flashing green
Yellow Acknowledged low severity alarm
Flashing yellow
Red Acknowledged high severity alarm
Flashing red
(1) If the LED blinking option is turned off (see Section 8.14), the status LED will flash only during calibration. It will not
flash to indicate an unacknowledged alarm..
(1)
(1)
(1)
Unacknowledged corrected condition
Unacknowledged low severity alarm
Unacknowledged high severity alarm
Alarms in the alarm list are listed by number. To view specific alarms in the list:
1. Activate and hold
Scroll and Select simultaneously until the words SEE ALARM appear on
the screen. See Figure 7-1.
2.
Select.
3. If the alternating words
4. If the words
Scroll to view each alarm in the list. See Section 12.12 for an explanation of the alarm codes
5.
NO ALARM appear, go to Step 6.
ACK ALL appear, Scroll.
reported by the display. The status LED changes color to reflect the severity of the current alarm, as described in Table 7-2.
6.
Scroll until the word EXIT appears.
Select.
7.
58 Micro Motion Series 1000 and Series 2000 Transmitters
Page 69
Using the Transmitter
• Model 1700 AN
• Model 1700 IS
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO

7.5.3 Using ProLink II

ProLink II provides two ways to view alarm information:
Choose independent of configured alarm severity. The alarms are divided into three categories: Critical, Informational, and Operational. To view the indicators in a category, click on the associated tab. A tab is red if one or more status indicators in that category is active. On each tab, currently active alarms are shown by red indicators.
Choose unacknowledged Fault and Informational alarms. (The transmitter automatically filters out Ignore alarms.) A green indicator means “inactive but unacknowledged” and a red indicator means “active.” Alarms are organized into two categories: High Priority and Low Priority.
Notes: The location of alarms in the Status window is not affected by the configured alarm severity (see Section 8.13.1). Alarms in the Status window are predefined as Critical, Informational, or Operational.
The alarm log in ProLink II is similar to but not the same as the alarm log in the Communicator.

7.5.4 Using the Communicator

ProLink > Status. This window shows the current status of all possible alarms,
ProLink > Alarm Log. This window lists all active alarms, and all inactive but
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
To view status and alarms with a Communicator:
1. Press
2. Press
2, 1, 1.
OK to scroll through the list of current alarms.
This view will show all Fault and Informational alarms. (The transmitter automatically filters out Ignore alarms.)

7.6 Acknowledging alarms

You can acknowledge alarms using ProLink II or the display.
For transmitters with a display, access to the alarm menu can be enabled or disabled, and a password may or may not be required. If access to the alarm menu is enabled, the operator may or may not be allowed to acknowledge all alarms simultaneously (the functions.
If the LED blinking option has been turned off, the status LED will not flash to indicate unacknowledged alarms. Alarms can still be acknowledged.
To acknowledge alarms using the display:
1. Activate and hold the screen. See Figure 7-1.
2.
Select.
Ack All? function). See Section 8.14.3 for information on controlling these
Scroll and Select simultaneously until the words SEE ALARM appear on
Configuration and Use Manual 59
3. If the words
NO ALARM appear, go to Step 8.
4. If you want to acknowledge all alarms:
a.
Scroll until the word ACK appears by itself. The word ACK begins to alternate with the
ALL?.
word
b.
Select.
Note: If the “acknowledge all alarms” feature has been disabled (see Section 8.14.1, then you must acknowledge each alarm individually. See Step 5.
Page 70
Using the Transmitter
5. If you want to acknowledge a single alarm:
a.
b.
c.
6. If you want to acknowledge another alarm, go to Step 3.
7. If you do NOT want to acknowledge any more alarms, go to Step 8.
8.
Scroll until the word EXIT appears.
Select.
9.
To acknowledge alarms using ProLink II:
1. Click
Scroll until the alarm you want to acknowledge appears.
Select. The word ALARM begins to alternate with the word ACK.
Select to acknowledge the alarm.
ProLink.
2. Select
Alarm log. Entries in the alarm log are divided into two categories: High Priority and
Low Priority, corresponding to the default Fault and Information alarm severity levels. Within each category:
All active alarms are listed with a red status indicator.
All alarms that are “cleared but unacknowledged” are listed with a green status indicator.
3. For each alarm that you want to acknowledge, check the

7.7 Using the totalizers and inventories

The totalizers keep track of the total amount of mass or volume measured by the transmitter over a period of time. The totalizers can be viewed, started, stopped, and reset.
The inventories track the same values as the totalizers but can be reset separately. Because the inventories are reset separately, you can keep a running total of mass or volume across multiple totalizer resets.
The transmitter can store totalizer and inventory values up to 2 internal totalizer to go into overflow.

7.7.1 Viewing the totalizers and inventories

You can view the current value of the totalizers and inventories with the display (if the transmitter is equipped with a display), ProLink II, or the Communicator.
ACK checkbox.
64
. Values larger than this cause the
With the display
You cannot view totalizers or inventories with the display unless the display has been configured to show them. See Section 8.14.6.
1. To view totalizer values,
Scroll until the word TOTAL appears and the units of measure are:
For the mass totalizer, mass units (e.g., kg, lb)
For the volume totalizer, volume units (e.g., gal, cuft)
For petroleum measurement or enhanced density totalizers, the mass or volume unit displayed cyclically with the name of the process variable (e.g.,
TCORR or NET M), and
the reference temperature
See Figure 7-2. Read the current value from the top line of the display.
60 Micro Motion Series 1000 and Series 2000 Transmitters
Page 71
Using the Transmitter
Current value
Units of measure
Process variable
Scroll optical switch
Select optical switch
2. To view inventory values, Scroll until the word TOTAL appears and:
For the mass inventory, the word units of measure
For the volume inventory, the word with the units of measure
For petroleum measurement or enhanced density inventories, the mass or volume unit displayed cyclically with the name of the process variable (e.g., Appendix H) and the reference temperature
See Figure 7-2. Read the current value from the top line of the display.
Figure 7-2 Display totalizer
MASSI (Mass Inventory) begins to alternate with the
LVO LI (Line Volume Inventory) begins to alternate
TCORI or NET VI) (see
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
With ProLink II software
To view current totals for the totalizers and inventories with ProLink II:
1. Click
2. Select
ProLink.
Process Variables, API Process Variables, or ED Process Variables.
With a Communicator
To view the current value of the totalizers and inventories with a Communicator:
1. Press
2. Select

7.8 Controlling totalizers and inventories

1, 1.
Mass totl, Mass inventory, Vol t otl , or Vol inventory.
Table 7-3 shows all of the totalizer and inventory functions and which configuration tools you can use to control them.
Configuration and Use Manual 61
Page 72
Using the Transmitter
Table 7-3 Totalizer and inventory control methods
Function name Communicator ProLink II Display
Stop all totalizers and inventories (mass, volume, ED, and API) Yes Yes Yes
Start all totalizers and inventories (mass, volume, ED, and API) Yes Yes Yes
Reset mass totalizer only Yes Yes Yes
Reset volume totalizer only Yes Yes Yes
Reset API totalizer only Yes No Yes
Reset ED totalizer only Yes Yes Yes
(2)
(2)
(2)
(2)
Simultaneously reset all totalizers (mass, volume, and API) Yes Yes No
Simultaneously reset all inventories (mass, volume, and API) No Yes
Individually reset inventories No Yes
(3)
(3)
No
No
(1) These actions are available only if the associated display function is enabled. See Section 8.14. (2) This function is available only if the corresponding totalizer is configured as a display variable (see Section 8.14.6). (3) If enabled in the ProLink II preferences.
With the display
You can use the display to start and stop all totalizers and inventories simultaneously, or to reset individual totalizers. See the flowchart in Figure 7-3. You cannot reset any inventories with the display.
The display must be configured to show the appropriate totalizer (see Section 8.14.6), and the corresponding display function must be enabled (see Section 8.14).
(1)
62 Micro Motion Series 1000 and Series 2000 Transmitters
Page 73
Using the Transmitter
RESET
(6)(7)
Select
Scroll
STOP/START
(4)(5)
RESET YES?
Process variable
display
STOP/START YES?
Scroll
Mass total
(1)
Volume total
(1)
Scroll
Select
Yes No
Select Scroll
EXIT
Select
Yes No
Select Scroll
ED total
(1)(2)
Scroll
API total
(1)(2)
Scroll
E1--SP
(3)
E2--SP
(3)
Scroll Scroll
(1) Displayed only if configured as a display variable (see Section 8.14.6). (2) The petroleum measurement application or enhanced density application must be enabled. (3) The Event Setpoint screens can be used to define or change Setpoint A for Event 1 or Event 2 (from the single-setpoint event
model). These screens are displayed only for events defined on mass total or volume total. See Section 8.11 for more information. To change the setpoint for an event defined on mass total, you must enter the totalizer management menu from the mass total screen. To change the setpoint for an event defined on volume total, you must enter the totalizer management menu from the volume total screen.
(4) The display must be configured to allow stopping and starting (see Section 8.14). (5) All totalizers and inventories will be stopped and started together, including API and enhanced density totalizers and inventories. (6) The display must be configured to allow totalizer resetting (see Section 8.14). (7) Only the totalizer currently shown on the display will be reset. No other totalizers will be reset, and no inventories will be reset.
Be sure that the totalizer you want to reset is displayed before performing this reset.
Figure 7-3 Controlling totalizers and inventories with the display
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
With ProLink II software
Using ProLink II, you can:
Start and stop all totalizers and inventories together
Reset all totalizers and inventories simultaneously, including API and ED totalizers
Reset each totalizer and inventory separately (except API totalizers)
To control ED totalizers and inventories, choose totalizer and inventory functions, choose
ProLink > Totalizer Control.
To reset inventories using ProLink II, you must first enable this capability. To enable inventory reset
ProLink > ED Totalizer Control. To control all other
using ProLink II:
Configuration and Use Manual 63
1. Choose
2. Select the
3. Click
With a Communicator
You can start and stop all totalizers and inventories, or reset individual (or all) totalizers with a Communicator. All of these functions are accessed from the Process Variables menu.
View > Preferences.
Enable Inventory Totals Reset checkbox.
Apply.
Page 74
64 Micro Motion Series 1000 and Series 2000 Transmitters
Page 75
Chapter 8

Optional Configuration

8.1 Overview

This chapter describes transmitter configuration parameters that may or may not be used, depending on your application requirements. For required transmitter configuration, see Chapter 6.
For information about how to perform the procedures described in this chapter, see the flowcharts for your transmitter and communication tool, provided in the appendices to this manual.
Note: If you are using AMS, the AMS interface will be similar to the ProLink II interface.

8.2 Configuration map

Different transmitters support different parameters and features. Additionally, different configuration tools allow you to configure different features. Table 8-1 lists the optional configuration parameters. For each parameter, the table also lists the transmitters that support that parameter and a reference to the section where the parameter is discussed.
In general, all parameters discussed in this chapter can be configured either with ProLink II or the Communicator, but cannot be configured with the display. Exceptions are noted in the configuration map.
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
Default values and ranges for the most commonly used parameters are provided in Appendix A.

8.3 How to access a parameter for configuration

For information on the menu structure for each transmitter, and how to access a particular parameter, see the appendix for your transmitter, as listed below. Within that appendix, refer to the menu flowcharts for the communication tool you are using: ProLink II, the Communicator, or the display.
Model 1500 AN – see Appendix C
Model 2500 CIO – see Appendix D
Model 1700/2700 AN – see Appendix E
Model 1700/2700 IS – see Appendix F
Model 2700 CIO – see Appendix G
Configuration and Use Manual 65
Page 76
Optional Configuration
Table 8-1 Configuration map
Transmitter
1500 1700 2500 2700
Topic Subtopic AN AN IS CIO AN IS CIO Section
Gas standard volume measurement
Special measurement units
Petrol eum measurement application (API feature)
Cutoffs ✓✓✓✓✓✓8.7
Damping ✓✓✓✓✓✓8.8
Update rate ✓✓✓✓✓✓8.9
Flow direction ✓✓✓✓✓✓8.10
Events ✓✓✓✓✓✓8.11
Slug flow ✓✓✓✓✓✓8.12
Fault handling Status alarm
severity
Fault timeout ✓✓✓✓✓✓8.13.2
Display functionality Update period
Language
Enable and disable functions
Scroll rate
Password
Display variables and precision
Digital communications settings
Device settings ✓✓✓✓✓✓8.16
Sensor parameters ✓✓✓✓✓✓8.17
Write-protect mode
✓✓✓✓✓✓8.4
✓✓✓✓✓✓8.5
✓✓✓✓8.6
✓✓✓✓✓✓8.13.1
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
8.14.1
8.14.2
8.14.3
8.14.4
8.14.5
✓✓ ✓ ✓ ✓ 8.14.6
✓✓✓✓✓✓8.15
(1)
(1)
(1)
(1)
(1)
(1)
(1)
8.18
(1) Can be configured with ProLink II, the Communicator, or the display.
66 Micro Motion Series 1000 and Series 2000 Transmitters
Page 77
Optional Configuration
• Model 1500 AN
• Model 1700 AN
• Model 1700 IS
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO

8.4 Configuring standard volume flow measurement for gas

Special functionality is provided for measuring the standard volume flow of gases.
ProLink II is required to access this functionality. Other tools provide only limited support:
The Communicator cannot be used to configure volume flow meaurement for gas or to select a standard gas volume flow measurement unit. If standard gas volume flow measurement has been configured, the Communicator will display the correct volume flow value, but will display “Unknown Enumerator” for the units label.
The local display cannot be used to change the volume flow type. However, after the transmitter has been configured for standard gas volume flow measurement, the display can be used to select a standard gas volume flow measurement unit.
Standard gas volume flow and liquid volume flow are mutually exclusive settings. When the Vol Flow Type is set to Std Gas Volume, the units list contains the units that are most frequently used for gas measurement. If Liquid Volume is configured, gas measurement units are not available.
To configure the transmitter to use gas standard volume flow:
1. Choose
ProLink > Configure > Flow.
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
Vol Flow Type to Std Gas Volume.
2. Set
3. Select the measurement unit you want to use from the default is
4. Configure the
SCFM.
Std Gas Vol Flow Cutoff (see Section 8.7). The default is 0.
Std Gas Vol Flow Units list. The
You have two choices for entering the standard density of the gas you are going to measure (i.e., the density of the gas at reference conditions):
If you know the standard density, you can enter that value in the
Std Gas Density field. For
optimal standard volume measurement accuracy, be sure the standard density you enter is correct and fluid composition is stable.
If you do not know the standard density of the gas, you can use the Gas Wizard (see Section 8.4.1). The Gas Wizard can calculate the standard density of the gas that you are measuring.

8.4.1 Using the Gas Wizard

The Gas Wizard is a tool provided in ProLink II for calculating the standard density of the gas that you are measuring.
To use the Gas Wizard:
1. Choose
2. Click
ProLink > Configure > Flow.
Gas Wizard.
Configuration and Use Manual 67
3. If your gas is listed in the
a. Select the
Choose Gas radio button.
b. Select your gas.
Choose Gas list:
Page 78
Optional Configuration
• Model 1500 AN
• Model 1700 AN
• Model 1700 IS
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO
4. If your gas is not listed, you must describe its properties.
a. Select the
Enter Other Gas Property radio button.
b. Select the method that you will use to describe its properties:
Gravity Compared to Air
c. Provide the required information. Note that if you selected
value in the configured density units and you must provide the temperature and pressure at which the density value was determined, using the configured temperature and pressure units.
5. Click
Next.
6. Verify the reference temperature and reference pressure. If these are not appropriate for your application, click
Change Reference Conditions and enter new values for reference
temperature and reference pressure.
7. Click
Next. The calculated standard density value is displayed.
If the value is correct, click configuration.
If the value is not correct, click
Note: The Gas Wizard displays density, temperature, and pressure in the configured units. If required, you can configure the transmitter to use different units. See Section 6.4.

8.5 Creating special measurement units

If you need to use a non-standard unit of measure, you can create one special measurement unit for mass flow, and one special measurement unit for liquid volume flow, and one special measurement unit for gas standard volume flow.
Molecular Weight, Specific
, or Density.
Density, you must enter the
Finish. The value will be written to transmitter
Back and modify input values as required.
68 Micro Motion Series 1000 and Series 2000 Transmitters
Note the following:
You can create all special measurement units with ProLink II.
Using the Communicator, you can create special measurement units for mass flow and liquid volume flow, but not for gas standard volume flow.
You cannot create any special measurement units with the display.
Special measurement units can be viewed normally with the display and with ProLink II. The Communicator will display special measurement units for mass flow and liquid volume flow. For special measurement units for gas standard voume flow, the Communicator will display the correct value but will display “Spcl” for the units label.

8.5.1 About special measurement units

Special measurement units consist of:
Base unit – A combination of:
- Base mass or base volume unit – A measurement unit that the transmitter already recognizes (e.g.,
kg, m3, l, SCF)
- Base time unit – A unit of time that the transmitter already recognizes (e.g., seconds, days)
Conversion factor – The number by which the base unit will be divided to convert to the special unit
Special unit – A non-standard volume flow or mass flow unit of measure that you want to be reported by the transmitter
Page 79
Optional Configuration
ConversionFactor
x BaseUnit(s)[]
y SpecialUnit(s)[]
---------------------------------------------=
x BaseUnit(s)[]y SpecialUnit(s)[]=
1 (gallon per minute)
8 (pints per minute)
------------------------------------------------------- 0.125 (conversion factor)=
The preceding terms are related by the following formula:

8.5.2 Special measurement unit procedure

To create a special measurement unit:
1. If necessary, set Volume Flow Type to match the type of special measurement unit you will create.
2. Identify the simplest base volume or mass and base time units for your special mass flow or volume flow unit. For example, to create the special volume flow unit pints per minute, the simplest base units are gallons per minute:
Base volume unit: gallon
Base time unit: minute
3. Calculate the conversion factor using the formula below:
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
Note: 1 gallon per minute = 8 pints per minute
4. Name the new special mass flow or volume flow measurement unit and its corresponding totalizer measurement unit:
Special volume flow measurement unit name: Pint/min
Volume totalizer measurement unit name: Pints
Note: Special measurement unit names can be up to 8 characters long (i.e., 8 numbers or letters), but only the first 5 characters appear on the display.
5. To apply the special measurement unit to mass flow or volume flow measurement, select
Special from the list of measurement units (see Section 6.4.1 or 6.4.2).
Configuration and Use Manual 69
Page 80
Optional Configuration
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO

8.6 Configuring the petroleum measurement application (API feature)

The API parameters determine the values that will be used in API-related calculations. The API parameters are available only if the petroleum measurement application is enabled on your transmitter.

8.6.1 About the petroleum measurement application

The petroleum measurement enables Correction of Temperature on volume of Liquids, or CTL. In other words, some applications that measure liquid volume flow or liquid density are particularly sensitive to temperature factors, and must comply with American Petroleum Institute (API) standards for measurement.
Terms and definitions
The following terms and definitions are relevant to the petroleum measurement application:
API – American Petroleum Institute
CTL – Correction of Temperature on volume of Liquids. The CTL value is used to calculate the VCF value
TEC – Thermal Expansion Coefficient
VCF – Volume Correction Factor. The correction factor to be applied to volume process variables. VCF can be calculated after CTL is derived
CTL derivation methods
There are two derivation methods for CTL:
Method 1 is based on observed density and observed temperature.
Method 2 is based on a user-supplied reference density (or thermal expansion coefficient, in some cases) and observed temperature.
API parameters
The API parameters are listed and defined in Table 8-2.
Table 8-2 API parameters
Variable Description
Table type Specifies the table that will be used for reference temperature and reference density unit. Select
the table that matches your requirements. See API reference tables.
User defined TEC
Temperature units
Density units Read-only. Displays the unit used for reference density in the reference table.
Reference temperature
(1)
Thermal expansion coefficient. Enter the value to be used in CTL calculation.
(2)
Read-only. Displays the unit used for reference temperature in the reference table.
Read-only unless Table type is set to 53x or 54x. If configurable:
• Specify the reference temperature to be used in CTL calculation.
• Enter reference temperature in °C.
(1) Configurable if Table Type is set to 6C, 24C, or 54C. (2) In most cases, the temperature unit used by the API reference table should also be the temperature unit configured for the transmitter
to use in general processing. To configure the temperature unit, see Section 6.4.4.
70 Micro Motion Series 1000 and Series 2000 Transmitters
Page 81
Optional Configuration
API reference tables
Reference tables are organized by reference temperature, CTL derivation method, liquid type, and density unit. The table selected here controls all the remaining options.
Reference temperature:
- If you specify a 5x, 6x, 23x, or 24x table, the default reference temperature is 60
- If you specify a 53x or 54x table, the default reference temperature is 15 °C. However, you
CTL derivation method:
- If you specify an odd-numbered table (5, 23, or 53), CTL will be derived using method 1
- If you specify an even-numbered table (6, 24, or 54), CTL will be derived using method 2
The letters A, B, C, or D that are used to terminate table names define the type of liquid that the table is designed for:
- A tables are used with generalized crude and JP4 applications.
- B tables are used with generalized products.
°F, an d
cannot be changed.
can change the reference temperature, as recommended in some locations (for example, to
14.0 or 14.5 °C).
described above.
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
described above.
- C tables are used with liquids with a constant base density or known thermal expansion
coefficient.
- D tables are used with lubricating oils.
Different tables use different density units:
-Degrees API
- Relative density (SG)
- Base density (kg/m
3
)
Table 8-3 summarizes these options.
Table 8-3 API reference temperature tables
CTL derivation
Table
5A Method 1 60 °F, non-configurable 0 to 100
5B Method 1 60 °F, non-configurable 0 to 85
5D Method 1 60 °F, non-configurable –10 to +40
23A Method 1 60 °F, non-configurable 0.6110 to 1.0760
23B Method 1 60 °F, non-configurable 0.6535 to 1.0760
23D Method 1 60 °F, non-configurable 0.8520 to 1.1640
53A Method 1 15 °C, configurable 610 to 1075 kg/m
53B Method 1 15 °C, configurable 653 to 1075 kg/m
53D Method 1 15 °C, configurable 825 to 1164 kg/m
method Base temperature
Degrees API Base density Relative density
Density unit and range
3
3
3
Configuration and Use Manual 71
Page 82
Optional Configuration
• Model 1500 AN
• Model 1700 AN
• Model 1700 IS
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO
Table 8-3 API reference temperature tables continued
CTL
Density unit and range
derivation
Table
method Base temperature
Degrees API Base density Relative density
Reference temperature Supports
6C Method 2 60 °F, non-configurable 60 °F Degrees API
24C Method 2 60 °F, non-configurable 60 °F Relative density
54C Method 2 15 °C, configurable 15 °C Base density in kg/m
Temperature data
For the temperature value to be used in CTL calculation, you can use the temperature data from the sensor, or you can poll an external temperature device:
To use temperature data from the sensor, no action is required.
To poll an external temperature device, configure polling for temperature as described in Section 9.4. When polling is enabled, the transmitter will automatically use the external temperature value for CTL calculation.

8.7 Configuring cutoffs

Cutoffs are user-defined values below which the transmitter reports a value of zero for the specified process variable. Cutoffs can be set for mass flow, volume flow, or density.
3
Note: The density cutoff is available only with core processor software v2.0 or above and transmitter software rev3.0 or above.
See Table 8-4 for cutoff default values and related information. See Sections 8.7.1 and 8.7.2 for information on how the cutoffs interact with other transmitter measurements.
Table 8-4 Cutoff default values
Cutoff type Default Comments
Mass flow 0.0 g/s Recommended setting:
• Standard use: 0.5–1.0% of the sensor’s rated maximum flow rate
• Empty-full-empty batching: 2.5% of the sensor’s rated maximum flow rate
Volume flow 0.0 L/s Lower limit: 0
Gas standard volume flow
Density 0.2 g/cm
0.0 No limit
Upper limit: the sensor’s flow calibration factor, in units of L/s, multiplied by 0.2
3
Range: 0.0–0.5 g/cm
3
72 Micro Motion Series 1000 and Series 2000 Transmitters
Page 83
Optional Configuration
• Model 1500 AN
• Model 1700 AN
• Model 1700 IS
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO

8.7.1 Cutoffs and volume flow

If you are using liquid volume flow units (
Vol F low Ty pe is set to Liquid):
The density cutoff is applied to the volume flow calculation. Accordingly, if the density drops below its configured cutoff value, the volume flow rate will go to zero.
The mass flow cutoff is not applied to the volume flow calculation. Even if the mass flow drops below the cutoff, and therefore the mass flow indicators go to zero, the volume flow rate will be calculated from the actual mass flow process variable.
If you are using gas standard volume flow units (
Vol Flow Type is set to Std Gas Volume), neither
the mass flow cutoff nor the density cutoff is applied to the volume flow calculation.

8.7.2 Interaction with the AO cutoffs

Both the primary mA output and the secondary mA output (if it is available on your transmitter) have cutoffs (the AO cutoffs). If the mA outputs are configured for mass flow, volume flow, or gas standard volume flow:
And the AO cutoff is set to a greater value than the mass, volume, or gas standard volume cutoff, the mA output will report zero flow when the AO cutoff is reached.
And the AO cutoff is set to a lower value than the mass, volume, or gas standard volume cutoff, when the mass, volume, or gas standard volume cutoff is reached, all outputs representing that process variable will report zero flow.
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup

8.8 Configuring the damping values

A damping value is a period of time, in seconds, over which the process variable value will change to reflect 63% of the change in the actual process. Damping helps the transmitter smooth out small, rapid measurement fluctuations.
A high damping value makes the output appear to be smoother because the output must change slowly.
A low damping value makes the output appear to be more erratic because the output changes more quickly.
When you specify a new damping value, it is automatically rounded down to the nearest valid damping value. Flow, density, and temperature have different valid damping values. Valid damping values are listed in Table 8-5.
Before setting the damping values, review Sections 8.8.1 through 8.8.3 for information on how the damping values interact with other transmitter measurements and parameters.
Table 8-5 Valid damping values
Process variable Update rate
Flow (mass and volume) Normal (20 Hz) 0, .2, .4, .8, ... 51.2
Density Normal (20 Hz) 0, .2, .4, .8, ... 51.2
Temperature Not applicable 0, .6, 1.2, 2.4, 4.8, ... 76.8
(1)
Special (100 Hz) 0, .04, .08, .16, ... 10.24
Special (100 Hz) 0, .04, .08, .16, ... 10.24
Valid damping values
Configuration and Use Manual 73
(1) See Section 8.8.3.
Page 84
Optional Configuration
• Model 1500 AN
• Model 1700 AN
• Model 1700 IS
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO

8.8.1 Damping and volume measurement

When configuring damping values, note the following:
Liquid volume flow is derived from mass and density measurements; therefore, any damping applied to mass flow and density will affect liquid volume measurement.
Gas standard volume flow is derived from mass flow measurement, but not from density measurement. Therefore, only damping applied to mass flow will affect gas standard volume measurement.
Be sure to set damping values accordingly.

8.8.2 Interaction with the added damping parameter

Both the primary mA output and the secondary mA output (if it is available on your transmitter) have a damping parameter (added damping). If damping is configured for flow, density, or temperature, the same process variable is assigned to an mA output, and added damping is also configured for the mA output, the effect of damping the process variable is calculated first, and the added damping calculation is applied to the result of that calculation.

8.8.3 Interaction with the update rate

Flow and density damping values depend on the configured Update Rate (see Section 8.9). If you change the update rate, the damping values are automatically adjusted. Damping rates for Special are 20% of Normal damping rates. See Table 8-5.
Note: The specific process variable selected for the 100 Hz update rate is not relevant; all damping values are adjusted as described.

8.9 Configuring the update rate

The update rate is the rate at which the transmitter polls the sensor for process data. Update Rate affects the transmitter’s response time to changes in the process.
There are two settings for Update Rate:
When
When
If you set the update rate to 100 Hz. Different 100 Hz variables are available, depending on which special applications are installed on your transmitter.
Note: For transmitters with transmitter software rev5.0 running the enhanced density application, the Special update rate is not available.
Normal and Special.
Normal is configured, most process variables are polled at the rate of
20 times per second (20 Hz).
Special is configured, a single, user-specified process variable is
polled 100 times per second (100 Hz). Polling for some process variables and diagnostic/calibration data is dropped (see Section 8.9.1), and the remaining process variables are polled a minimum of 6 times per second (6.25 Hz).
Special, you must also specify which process variable will be polled at
74 Micro Motion Series 1000 and Series 2000 Transmitters
Note: Most users should select the Normal update rate. Use the Special update rate only if required by your application. See Section 8.9.1.
Note: If you change the update rate, the setting for damping is automatically adjusted. See Section 8.8.3.
Page 85
Optional Configuration

8.9.1 Effects of Special mode

In Special mode:
Not all process variables are updated. The process variables listed below are always updated:
- Mass flow
-Volume flow
- Gas standard volume flow
- Density
- Temperature
-Drive gain
- LPO amplitude
- Status (contains Event 1 and Event 2)
- Raw tube frequency
- Mass total
- Volume total
- Gas standard volume total
- API temperature-corrected volume total
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
- API temperature-corrected density
- API temperature-corrected volume flow
- API batch weighted average temperature
- API batch weighted average density
The process variables listed below are updated only when the petroleum measurement application is not enabled:
- RPO amplitude
-Board temperature
- Core input voltage
- Mass inventory
- Volume inventory
- Gas standard volume inventory
All other process variables are not polled at all. The omitted process variables will remain at the values they held before Special mode was implemented.
Calibration data is not refreshed.
Discrete event status is not polled.
The enhanced density application is not available.
Micro Motion recommends the following:
Do not use Special mode unless required by your application. Contact Micro Motion before setting Update Rate to Special.
If Special mode is required, ensure that all required data is being updated.
Do not perform any calibrations while in Special mode.
Do not restore the factory zero or prior zero.
Do not use discrete events (the dual-setpoint event model) while in Special mode. Instead, use Event 1 and Event 2 from the single-setpoint event model. See Section 8.11.
Configuration and Use Manual 75
Page 86
Optional Configuration
• Model 1500 AN
• Model 1700 AN
• Model 1700 IS
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO
Reverse
flow
(1)
20
12
4
x0
20
12
4
-x x0
mA output configuration:
• 20 mA value = x
• 4 mA value = 0 To set the 4 mA and 20 mA values, see Section .
Forward flow
(2)
Zero flow
Reverse
flow
(1)
Forward flow
(2)
Zero flow
Flow direction parameter:
•Forward
Flow direction parameter:
• Reverse
• Negate Forward
20
12
4
-x x0
Reverse
flow
(1)
Forward flow
(2)
Zero flow
Flow direction parameter:
• Absolute value
• Bidirectional
• Negate Bidirectional
(1) Process fluid flowing in opposite direction from flow direction arrow on sensor. (2) Process fluid flowing in same direction as flow direction arrow on sensor.
-x
mA output
mA output
mA output

8.10 Configuring the flow direction parameter

The flow direction parameter controls how the transmitter reports flow rate and how flow is added to or subtracted from the totalizers, under conditions of forward flow, reverse flow, or zero flow.
Forward (positive) flow moves in the direction of the arrow on the sensor.
Reverse (negative) flow moves in the direction opposite of the arrow on the sensor.
Options for flow direction include:
•Forward
•Reverse
Absolute Value
Bidirectional
Negate Forward
Negate Bidirectional
For the effect of flow direction on mA outputs:
See Figure 8-1 if the 4 mA value of the mA output is set to 0.
See Figure 8-2 if the 4 mA value of the mA output is set to a negative value.
For a discussion of these figures, see the examples following the figures.
For the effect of flow direction on frequency outputs, totalizers, and flow values reported via digital communication, see Table 8-6.
Figure 8-1 Effect of flow direction on mA outputs: 4mA value = 0
76 Micro Motion Series 1000 and Series 2000 Transmitters
Page 87
Optional Configuration
Reverse
flow
(1)
mA output
20
12
4
–x x0
20
12
–x x0
mA output configuration:
• 20 mA value = x
• 4 mA value = –x
• –x < 0 To set the 4 mA and 20 mA values, see Section .
Forward flow
(2)
Zero flow
Reverse
flow
(1)
Forward flow
(2)
Zero flow
Flow direction parameter:
•Forward
Flow direction parameter:
• Reverse
• Negate Forward
20
12
4
–x x0
Reverse
flow
(1)
Forward flow
(2)
Zero flow
Flow direction parameter:
• Absolute value
• Bidirectional
• Negate Bidirectional
(1) Process fluid flowing in opposite direction from flow direction arrow on sensor. (2) Process fluid flowing in same direction as flow direction arrow on sensor.
mA output
mA output
4
Figure 8-2 Effect of flow direction on mA outputs: 4mA value < 0
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
Example 1
Configuration:
Flow direction = Forward
mA output: 4 mA = 0 g/s; 20 mA = 100 g/s
(See the first graph in Figure 8-1.)
As a result:
Under conditions of reverse flow or zero flow, the mA output level is 4 mA.
Under conditions of forward flow, up to a flow rate of 100 g/s, the mA output level varies between 4 mA and 20 mA in proportion to (the absolute value of) the flow rate.
Under conditions of forward flow, if (the absolute value of) the flow rate equals or exceeds 100 g/s, the mA output will be proportional to the flow rate up to 20.5 mA, and will be level at 20.5 mA at higher flow rates.
Configuration and Use Manual 77
Page 88
Optional Configuration
Example 2
Example 3
Configuration:
Flow direction = Reverse
mA output: 4 mA = 0 g/s; 20 mA = 100 g/s
(See the second graph in Figure 8-1.)
As a result:
Under conditions of forward flow or zero flow, the mA output level is 4 mA.
Under conditions of reverse flow, up to a flow rate of 100 g/s, the mA output level varies between 4 mA and 20 mA in proportion to the absolute value of the flow rate.
Under conditions of reverse flow, if the absolute value of the flow rate equals or exceeds 100 g/s, the mA output will be proportional to the absolute value of the flow rate up to 20.5 mA, and will be level at 20.5 mA at higher absolute values.
Configuration:
Flow direction = Forward
mA output: 4 mA = –100 g/s; 20 mA = 100 g/s
(See the first graph in Figure 8-2.)
As a result:
Under conditions of zero flow, the mA output is 12 mA.
Under conditions of forward flow, up to a flow rate of 100 g/s, the mA output varies between 12 mA and 20 mA in proportion to (the absolute value of) the flow rate.
Under conditions of forward flow, if (the absolute value of) the flow rate equals or exceeds 100 g/s, the mA output is proportional to the flow rate up to 20.5 mA, and will be level at 20.5 mA at higher flow rates.
Under conditions of reverse flow, up to a flow rate of 100 g/s, the mA output varies between 4 mA and 12 mA in inverse proportion to the absolute value of the flow rate.
Under conditions of reverse flow, if the absolute value of the flow rate equals or exceeds 100 g/s, the mA output is inversely proportional to the flow rate down to 3.8 mA, and will be level at
3.8 mA at higher absolute values.
78 Micro Motion Series 1000 and Series 2000 Transmitters
Page 89
Optional Configuration
Table 8-6 Effect of flow direction on frequency output, discrete output, totalizers, and digital
communications
Forward flow
Frequency
Flow direction value
Forward Increase OFF Increase Positive
Reverse 0 Hz OFF No change Positive
Bidirectional Increase OFF Increase Positive
Absolute value Increase OFF Increase Positive
Negate Forward Zero
Negate Bidirectional Increase ON Decrease Negative
output Discrete output
(3)
ON No change Negative
(2)
(1)
Flow totals
Flow values via digital comm.
Zero flow
Frequency
Flow direction value
All 0 Hz OFF No change 0
output Discrete output Flow totals
Reverse flow
(4)
Frequency
Flow direction value
Forward 0 Hz ON No change Negative
Reverse Increase ON Increase Negative
Bidirectional Increase ON Decrease Negative
Absolute value Increase OFF Increase Positive
Negate Forward Increase OFF Increase Positive
Negate Bidirectional Increase OFF Increase Positive
output Discrete output Flow totals
Flow values via digital comm.
Flow values via digital comm.
(3)
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
(3)
(1) Process fluid flowing in same direction as flow direction arrow on sensor. (2) Applies only if the discrete output has been configured to indicate flow direction. (3) Refer to the digital communications status bits for an indication of whether flow is positive or negative. (4) Process fluid flowing in opposite direction from flow direction arrow on sensor.

8.11 Configuring events

See the Configuration and Use Manual Supplement for your transmitter for information and instructions on configuring events.

8.11.1 Changing event setpoints from the display

For Event 1 or Event 2 from the single-setpoint event model only, the value of Setpoint A can be changed from the display, under the following circumstances:
Mass total or volume total (gas or liquid) must be assigned to the event.
Mass total or volume total must be configured as a display variable (see Section 8.14.6).
Then, to reset Setpoint A from the display:
Configuration and Use Manual 79
Page 90
Optional Configuration
• Model 1500 AN
• Model 1700 AN
• Model 1700 IS
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO
1. Referring to the totalizer management flowchart in Figure 7-3, Scroll to the appropriate display screen:
To change the setpoint for an event defined on mass total,
Scroll to the mass total screen.
To change the setpoint for an event defined on volume total,
screen.
2.
Select.
3. Enter the new setpoint value. See Section 2.4.5 for instructions on entering floating-point values with the display.

8.12 Configuring slug flow limits and duration

Slugs – gas in a liquid process or liquid in a gas process – occasionally appear in some applications. The presence of slugs can significantly affect the process density reading. The slug flow parameters can help the transmitter suppress extreme changes in process variables, and can also be used to identify process conditions that require correction.
Slug flow parameters are as follows:
Low slug flow limit – the point below which a condition of slug flow will exist. Typically, this is the lowest density point in your process’s normal density range. Default value is 0.0 g/cm
3
range is 0.0–10.0 g/cm
.
High slug flow limit – the point above which a condition of slug flow will exist. Typically, this is the highest density point in your process’s normal density range. Default value is 5.0 g/cm
3
range is 0.0–10.0 g/cm
.
Slug flow duration – the number of seconds the transmitter waits for a slug flow condition (outside the slug flow limits) to return to normal (inside the slug flow limits). Default value is
0.0 seconds; range is 0.0–60.0 seconds
If the transmitter detects slug flow:
A slug flow alarm is posted immediately.
Scroll to the volume total
3
;
3
;
80 Micro Motion Series 1000 and Series 2000 Transmitters
During the slug duration period, the transmitter holds the mass flow rate at the last measured pre-slug value, independent of the mass flow rate measured by the sensor. All outputs that report mass flow rate and all internal calculations that include mass flow rate will use this value.
If slugs are still present after the slug duration period expires, the transmitter forces the mass flow rate to 0, independent of the mass flow rate measured by the sensor. All outputs that report mass flow rate and all internal calculations that include mass flow rate will use 0.
When process density returns to a value within the slug flow limits, the slug flow alarm is cleared and the mass flow rate reverts to the actual measured value.
Note: This functionality is not available via the display menus.
Note: The slug flow limits must be entered in g/cm
3
, even if another unit has been configured for
density. Slug flow duration is entered in seconds.
Note: Raising the low slug flow limit or lowering the high slug flow limit will increase the possibility of slug flow conditions. Conversely, lowering the low slug flow limit or raising the high slug flow limit will decrease the possibility of slug flow conditions.
Page 91
Optional Configuration
• Model 1500 AN
• Model 1700 AN
• Model 1700 IS
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO
Note: If slug flow duration is set to 0, the mass flow rate will be forced to 0 as soon as slug flow is detected.

8.13 Configuring fault handling

There are three ways that the transmitter can report faults:
By setting outputs to their configured fault levels
By configuring a discrete output to indicate fault status
By posting an alarm to the active alarm log
Status alarm severity controls which of these methods is used. For some faults only, fault timeout controls when the fault is reported.

8.13.1 Status alarm severity

Status alarms are classified into three levels of severity. The severity level controls transmitter behavior when the alarm condition occurs. See Table 8-7.
Table 8-7 Alarm severity levels
Severity level Transmitter action
Fault If this condition occurs, an alarm will be generated and all outputs go to their
Informational If this condition occurs, an alarm will be generated but output levels are not affected.
Ignore If this condition occurs, no alarm will be generated (no entry is added to the active
configured fault levels. Output configuration is described in Chapter 6.
alarm log) and output levels are not affected.
Some alarms can be reclassified. For example:
The default severity level for Alarm A020 (calibration factors unentered) is
reconfigure it to either
The default severity level for Alarm A102 (drive over-range) is
reconfigure it to either
Informational or Ignore.
Informational, but you can
Ignore or Fault.
Fault, but you can
For a list of all status alarms and default severity levels, see Table 8-8. (For more information on status alarms, including possible causes and troubleshooting suggestions, see Table 12-5.)
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
Table 8-8 Status alarms and severity levels
Alarm code
A001 EEprom Checksum Error (Core Processor) Fault No No
A002 RAM Test Error (Core Processor) Fault No No
Configuration and Use Manual 81
To configure alarm severity, refer to the ProLink II and Communicator menu trees in the appropriate appendix for your transmitter model (Appendices C through G).
Note: You cannot set status alarm severity via the display menus.
Communicator message
(E)EEPROM Checksum Error (CP)
RAM Error (CP)
Default severity Configurable
Affected by fault timeoutProLink II message
Page 92
Optional Configuration
Table 8-8 Status alarms and severity levels continued
Communicator message
Alarm code
A003 Sensor Not Responding (No Tube Interrupt) Fault Yes Yes
Sensor Failure
A004 Temperature Sensor Out-of-Range Fault No Yes
Temperature Sensor Failure
A005 Input Over-Range Fault Yes Yes
Input Overrange
A006 Transmitter Not Characterized Fault Yes No
Not Configured
A008 Density Outside Limits Fault Yes Yes
Density Overrange
A009 Transmitter Initializing/Warming Up Fault Yes No
Transmitter Initializing/Warming Up
A010 Calibration Failure Fault No No
Calibration Failure
A011 Excess Calibration Correction, Zero too Low Fault Yes No
Zero Too Low
A012 Excess Calibration Correction, Zero too High Fault Yes No
Zero Too High
A013 Process too Noisy to Perform Auto Zero Fault Yes No
Zero Too Noisy
A014 Transmitter Failed Fault No No
Transmitter Failed
A016 Line RTD Temperature Out-Of-Range Fault Yes Yes
Line RTD Temperature Out-of-Range
A017 Meter RTD Temperature Out-Of-Range Fault Yes Yes
Meter RTD Temperature Out-of-Range
A018 EEprom Checksum Error Fault No No
(E)EPROM Checksum Error
A019 RAM Test Error Fault No No
RAM or ROM TEST ERROR
A020 Calibration Factors Unentered Fault Yes No
Calibration Factors Unentered (FlowCal)
A021 Unrecognized/Unentered Sensor Type Fault No No
Incorrect Sensor Type (K1)
A022
A023
(1)
(1)
(E)EPROM Config. DB Corrupt (Core Processor)
(E)EPROM Config. CB Corrupt (CP)
(E)EPROM Totals Corrupt (Core Processor) Fault No No
(E)EPROM Powerdown Totals Corrupt (CP)
Default severity Configurable
Fault No No
Affected by fault timeoutProLink II message
82 Micro Motion Series 1000 and Series 2000 Transmitters
Page 93
Optional Configuration
Table 8-8 Status alarms and severity levels continued
Alarm code
(1)
A024
Communicator message
(E)EPROM Program Corrupt (Core Processor) Fault No No
Default severity Configurable
Affected by fault timeoutProLink II message
(E)EPROM Program Corrupt (CP)
A025
(1)
Protected Boot Sector Fault Fault No No
Protected Boot Sector Fault (CP)
A026 Sensor/Xmtr Communication Error Fault No No
Sensor/Transmitter Communication Error
A027 Security Breach Fault No No
Security Breach
A028 Sensor/Xmtr Communication Failure Fault No No
Core Processor Write Failure
A031
(2)
Undefined Fault No No
Low Power
(3)
A032
Meter Verification Fault Alarm Fault No No
Meter Verification/Outputs In Fault
A032
(4)
Outputs Fixed during Meter Verification Varies
(5)
No No
Meter Verification In Progress and Outputs Fixed
(2)
A033
Sensor OK / Tubes Stopped by Process Fault Yes Yes
Sensor OK/Tubes Stopped by Process
A034
(4)
Meter Verification Failed Info Yes No
Meter Verification Failed
A035
(4)
Meter Verification Aborted Info Yes No
Meter Verification Aborted
A100 Primary mA Output Saturated Info Yes
(6)
No
Primary mA Output Saturated
A101 Primary mA Output Fixed Info Yes
(6)
No
Primary mA Output Fixed
A102 Drive Over-Range / Partially Full Tube Info Yes No
Drive Overrange
A103
(1)
Data Loss Possible Info Yes No
Data Loss Possible (Tot and Inv)
A104 Calibration-In-Progress Info Yes
(6)
No
Calibration in Progress
A105 Slug Flow Info Yes No
Slug Flow
A106 Burst Mode Enabled Info Yes
(6)
No
Burst Mode Enabled
A107 Power Reset Occurred Info Yes No
Power Reset Occurred
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
Configuration and Use Manual 83
Page 94
Optional Configuration
Table 8-8 Status alarms and severity levels continued
Alarm code
(7)
A108
Communicator message
Event #1 Triggered Info Yes No
Default severity Configurable
Affected by fault timeoutProLink II message
Event 1 Triggered
A109
(7)
Event #2 Triggered Info Yes No
Event 2 Triggered
A110
Frequency Output Saturated
Info Yes
(6)
No
Frequency Output Saturated
A111 Frequency Output Fixed Info Yes
(6)
No
Frequency Output Fixed
A112
(8)
Software Upgrade Recommended Info Yes No
S/W Upgrade Recommended
A113 Secondary mA Output Saturated Info Yes
(6)
No
Secondary mA Output Saturated
A114 Secondary mA Output Fixed Info Yes
(6)
No
Secondary mA Output Fixed
A115 External Input Error Info Yes No
External Input Error
A116 API Temperature Out-of-Limits Info Yes No
API: Temperature Outside Standard Range
A117 API Density Out-of-Limits Info Yes No
API: Density Outside Standard Range
A118 Discrete Output 1 Fixed Info Yes
(6)
No
Discrete Output 1 Fixed
A119 Discrete Output 2 Fixed Info Yes
(6)
No
Discrete Output 2 Fixed
A120 ED: Unable to fit curve data Info No No
ED: Unable to Fit Curve Data
A121 ED: Extrapolation alarm Info Yes No
ED: Extrapolation Alarm
A131
(3)
Meter Verification Info Alarm Info Yes No
Meter Verification/Outputs at Last Value
A131
(4)
Meter Verification in Progress Info Yes No
Meter Verification In Progress
A132
(2)
Simulation Mode Active Info Yes
(6)
No
Simulation Mode Active
(1) Applies only to systems with the standard core processor. (2) Applies only to systems with the enhanced core processor. (3) Applies only to systems with the original version of the meter verification application. (4) Applies only to systems with Smart Meter Verification. (5) If outputs are set to Last Measured Value, severity is Info. If outputs are set to Fault, severity is Fault. (6) Can be set to either Info or Ignore, but cannot be set to Fault. (7) Applies only to events configured using the single-setpoint event model. (8) Applies only to systems with transmitter software earlier than rev5.0.
84 Micro Motion Series 1000 and Series 2000 Transmitters
Page 95
Optional Configuration
• Model 1700 AN
• Model 1700 IS
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO

8.13.2 Fault timeout

If a fault is detected, the transmitter always sets the “alarm active” status bit immediately. Fault actions for the transmitter outputs and digital communications may be implemented immediately or may be delayed until the fault timeout expires. During the fault timeout, outputs continue to report their last measured value.
The default fault timeout value is
The fault timeout is not applicable to all faults. See Table 8-8 for information about which faults are affected.

8.14 Configuring the display

If your transmitter has a display, you can enable or disable specific display functions, specify the process variables to be shown on the display, and set a variety of parameters that control display behavior.

8.14.1 Update period

0, meaning that fault actions will be implemented immediately.
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
Table 8-9 Display parameters
Parameter Enabled Disabled
Totalizer start/stop
Totalizer reset
Auto scroll The display automatically scrolls through each
Off-line menu Operators can access the off-line menu (zero,
Off-line password
Alarm menu Operators can access the alarm menu
Configuration and Use Manual 85
The update period (or display rate) parameter controls how often the display is refreshed with current data. The default is 0.2 seconds. The range is 0.10 seconds to 10 seconds. The Update Period value applies to all process variables.

8.14.2 Language

The display can be configured to use any of the following languages for data and menus:
English
•French
•German
Spanish

8.14.3 Enabling and disabling display functions

Table 8-9 lists the display functions and describes their behavior when enabled or disabled.
(1)(2)
Operators can start or stop totalizers using the display.
(1)
(3)
Operators can reset the mass and volume totalizers.
process variable at a configurable rate.
simulation, and configuration).
Operators must enter the display password to access the off-line menu.
(viewing and acknowledging alarms).
Operators cannot start or stop totalizers using the display.
Operators cannot reset the mass and volume totalizers.
Operators must variables.
Operators cannot access the off-line menu.
Operators can access the off-line menu without the display password.
Operators cannot access the alarm menu.
Scroll to view process
Page 96
Optional Configuration
Table 8-9 Display parameters continued
Parameter Enabled Disabled
Acknowledge all alarms
Backlight on/off Display backlight is on. Display backlight is off.
Alarm screen password
LED blinking The status LED will flash when there are
(1) If the petroleum measurement application is installed on your transmitter, the display password is always required to start, stop, or
(2) This feature is available only with rev3.3 or higher of the transmitter software. For all other transmitters, totalizer reset and totalizer
(3) See Section 2.4.4 for detailed information on the display password function.
(3)
reset a totalizer, even if neither password is enabled. If the petroleum measurement application is not installed, the display password is never required for these functions, even if one of the display passwords is enabled.
start/stop from the display cannot be disabled.
Operators are able to acknowledge all current alarms at once.
Operators must enter the display password to access the alarm menu.
unacknowledged alarms.
Operators must acknowledge alarms individually.
Operators can access the alarm menu without the display password.
The status LED will not flash to indicate unacknowledged alarms. It will still flash to indicate calibration in progress.

8.14.4 Changing the scroll rate

The scroll rate is used to control the speed of scrolling when Auto Scroll is enabled. Scroll Rate defines how long each display variable (see Section 8.14.6) will be shown on the display. The time period is defined in seconds; e.g., if Scroll Rate is set to 10, each display variable will be shown on the display for 10 seconds.
If you are using the Communicator to configure the transmitter, you must enable Auto Scroll before you can configure Scroll Rate (see Section 8.14.3).

8.14.5 Changing the display password

The display password is a numeric code that can contain up to four digits. It is used for both the off-line password and the alarm screen password. See Section 2.4.4 for information on how the two passwords are implemented.
If you are using the Communicator or the display, you must enable either the off-line password or the alarm screen password before you can configure the password (see Section 8.14.3).
Note: If the petroleum measurement application is installed on your transmitter, the display password is always required to start, stop, or reset a totalizer, even if neither password is enabled. If the petroleum measurement application is not installed, the display password is never required for these functions, even if one of the passwords is enabled.

8.14.6 Changing the display variables and display precision

See the Configuration and Use Manual Supplement for your transmitter for information and instructions on configuring display variables and display precision.

8.14.7 Fixing Display Variable 1 to the primary mA output

See the Configuration and Use Manual Supplement for your transmitter for information and instructions on fixing Display Variable 1 to the primary mA output.
86 Micro Motion Series 1000 and Series 2000 Transmitters
Page 97
Optional Configuration
• Model 1500 AN
• Model 1700 AN
• Model 1700 IS
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO
• Model 1500 AN
• Model 1700 AN
• Model 1700 IS
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO

8.15 Configuring digital communications

See the Configuration and Use Manual Supplement for your transmitter for information and instructions on configuring digital communications parameters.

8.16 Configuring device settings

The device settings are used to describe the flowmeter components. Table 8-10 lists and defines the device settings.
Note: The HART device ID, which is displayed in some menus, can be set only once, and is usually set at the factory to the device serial number. If the HART device ID has not been set, its value is 0.
Table 8-10 Device settings
Parameter Description
HART tag
Descriptor Any user-supplied description. Not used in transmitter processing, and not required.
Message Any user-supplied message. Not used in transmitter processing, and not required.
Date Any user-selected date. Not used in transmitter processing, and not required.
(1)
Also called the “software tag.” Used by other devices on the network to identify and communicate with this transmitter via HART protocol. The HART tag must be unique on the network. If the transmitter will not be accessed using HART protocol, the HART tag is not required. Maximum length: 8 characters.
Maximum length: 16 characters.
Maximum length: 32 characters.
Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup Required Configuration Optional ConfigurationUsing the TransmitterFlowmeter Startup
(1) Devices using HART protocol to communicate with the transmitter may use either the HART address or the HART tag. You may
configure either or both, as required by your other HART devices.
If you are entering a date:
With ProLink II, use the left and right arrows at the top of the calendar to select the year and
month, then click on a date
With a Communicator, enter a value in the form mm/dd/yyyy

8.17 Configuring sensor parameters

The sensor parameters are used to describe the sensor component of your flowmeter. They are not used in transmitter processing, and are not required. The following sensor parameters can be changed:
Serial number
Model number
Sensor material
Liner material
•Flange
Configuration and Use Manual 87
Page 98
Optional Configuration
• Model 1500 AN
• Model 1700 AN
• Model 1700 IS
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO

8.18 Configuring write-protect mode

When the transmitter is in write-protect mode, the configuration data stored in the transmitter and core processor cannot be changed until write-protect mode is disabled.
88 Micro Motion Series 1000 and Series 2000 Transmitters
Page 99
Chapter 9
• Model 1500 AN
• Model 1700 AN
• Model 1700 IS
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO

Pressure Compensation, Temperature Compensation, and Polling

9.1 Overview

This chapter describes the following procedures:
Configuring pressure compensation (see Section 9.2)
Configuring external temperature compensation (see Section 9.3)
Configuring polling (see Section 9.4)
Note: All ProLink II procedures provided in this section assume that your computer is already connected to the transmitter and you have established communication. All ProLink II procedures also assume that you are complying with all applicable safety requirements. See Chapter 3 for more information.
Note: All Communicator key sequences in this section assume that you are starting from the “Online” menu. See Chapter 4 for more information.

9.2 Pressure compensation

Series 1000/2000 transmitters can compensate for the effect of pressure on the sensor flow tubes. Pressure effect is defined as the change in sensor flow and density sensitivity due to process pressure change away from calibration pressure.
Note: Pressure compensation is an optional procedure. Perform this procedure only if required by your application.
Measurement Performance TroubleshootingCustody TransferCompensation
Configuration and Use Manual 89

9.2.1 Options

There are two ways to configure pressure compensation:
If the operating pressure is a known static value, you can enter the external pressure in the
software, and not poll a pressure measurement device.
If the operating pressure varies significantly, you configure the transmitter to poll for an
updated pressure value from an external pressure measurement device. Polling requires HART/Bell 202 communications over the primary mA output.
Note: If you configure a static pressure value, ensure that it is accurate. If you configure polling for pressure, ensure that the pressure measurement device is accurate and reliable.
Page 100
Pressure Compensation, Temperature Compensation, and Polling
Enter Flow factor
Configure
Enter Density factor
Enter Cal pressure
Enter External
Pressure
Enable External Pressure
Compensation
Enable
Enter Pressure units
Set measurement unit
Dynamic
Static
View > Preferences
ProLink > Configuration > Pressure
ProLink > Configuration > Pressure
Apply
Apply
Apply
Apply
Done
Dynamic or static?
(1) Setting the pressure measurement unit is optional. (2) See Section 9.4. (3) If previously configured. Polling for temperature is allowed. See
Section 9.4.

9.2.2 Pressure correction factors

When configuring pressure compensation, you must provide the flow calibration pressure – the pressure at which the flowmeter was calibrated (which therefore defines the pressure at which there will be no effect on the calibration factor). Refer to the calibration document shipped with your sensor. If the data is unavailable, use 20 psi.
Two additional pressure correction factors may be configured: one for flow and one for density. These are defined as follows:
Flow factor – the percent change in the flow rate per psi
Density factor – the change in fluid density, in g/cm
Not all sensors or applications require pressure correction factors. For the pressure correction values to be used, obtain the pressure effect values from the product data sheet for your sensor, then reverse the signs (e.g., if the flow factor is 0.000004 % per PSI, enter a pressure correction flow factor of –0.000004 % per PSI).

9.2.3 Configuration

To enable and configure pressure compensation:
With ProLink II, see Figure 9-1.
With the Communicator, see Figure 9-2.
3
/psi
Figure 9-1 Configuring pressure compensation with ProLink II
90 Micro Motion Series 1000 and Series 2000 Transmitters
Loading...