Emerson Micro Motion Installation Manual

Installation Manual
20001700, Rev CG
December 2019
Micro Motion™ 1700 and 2700 Transmitters
Installation Manual
Safety messages
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The EU declaration of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available on the internet at www.emerson.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at
www.emerson.com.
For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion Customer Service department.
Emerson Flow customer service
Email:
Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America
United States 800-522-6277 U.K. 0870 240 1978 Australia 800 158 727
Canada +1 303-527-5200 The Netherlands +31 (0) 704 136
Mexico +41 (0) 41 7686
111
Argentina +54 11 4837 7000 Germany 0800 182 5347 Pakistan 888 550 2682
Brazil +55 15 3413 8000 Italy 8008 77334 China +86 21 2892 9000
Europe and Middle East Asia Pacific
666
France 0800 917 901 India 800 440 1468
Central & Eastern +41 (0) 41 7686
111
Russia/CIS +7 495 995 9559 South Korea +82 2 3438 4600
Egypt 0800 000 0015 Singapore +65 6 777 8211
Oman 800 70101 Thailand 001 800 441 6426
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudi Arabia 800 844 9564
UAE 800 0444 0684
New Zealand 099 128 804
Japan +81 3 5769 6803
2
Installation Manual Contents
20001700 December 2019

Contents

Chapter 1 Before you begin............................................................................................................5
1.1 About this document........................................................................................................................5
1.2 Hazard messages..............................................................................................................................5
1.3 Related documentation....................................................................................................................5
Chapter 2 Planning........................................................................................................................ 7
2.1 Meter components...........................................................................................................................7
2.2 Installation types.............................................................................................................................. 7
2.3 Maximum cable lengths between sensor and transmitter...............................................................11
2.4 Output options...............................................................................................................................12
2.5 Electrical connections.....................................................................................................................13
2.6 Environmental limits...................................................................................................................... 13
2.7 Hazardous area classifications........................................................................................................ 14
2.8 Power requirements....................................................................................................................... 14
Chapter 3 Mounting.....................................................................................................................17
3.1 Mounting for integral installations..................................................................................................17
3.2 Orientation.....................................................................................................................................17
3.3 Accessibility for maintenance......................................................................................................... 17
3.4 Mounting options...........................................................................................................................17
3.5 Rotate the transmitter on the sensor (optional)..............................................................................23
3.6 Rotate the user interface on the transmitter (optional)...................................................................24
Chapter 4 Preparing the wires......................................................................................................27
4.1 Prepare the 4-wire cable.................................................................................................................27
4.2 Prepare the 9-wire cable.................................................................................................................30
Chapter 5 Wiring the transmitter to the sensor............................................................................37
5.1 Wire the transmitter to the sensor (4-wire).....................................................................................37
5.2 Wire the transmitter to the remote core processor (4-wire)............................................................38
5.3 Wire the remote core processor to the sensor using jacketed cable (9-wire)...................................40
5.4 Wire the remote core processor to the sensor using shielded or armored cable (9-wire).................42
5.5 Sensor and remote core processor/transmitter terminals...............................................................45
Chapter 6 Grounding....................................................................................................................49
6.1 Ground the meter components...................................................................................................... 49
Chapter 7 Wiring the power supply..............................................................................................51
7.1 Wire the power supply....................................................................................................................51
Chapter 8 I/O wiring for transmitters with analog outputs........................................................... 53
8.1 Basic analog wiring......................................................................................................................... 53
Installation Manual iii
Contents Installation Manual
December 2019 20001700
8.2 HART®/analog single loop wiring.................................................................................................... 53
8.3 RS-485 point-to-point wiring..........................................................................................................54
8.4 HART multidrop wiring................................................................................................................... 55
Chapter 9 I/O wiring for transmitters with intrinsically safe outputs.............................................57
9.1 Safe area mA Output wiring (2700)................................................................................................ 57
9.2 Safe area HART/analog single-loop wiring...................................................................................... 58
9.3 Safe area HART multidrop wiring.................................................................................................... 59
9.4 Safe area Frequency Output/Discrete Output wiring...................................................................... 60
9.5 Hazardous area wiring.................................................................................................................... 61
Chapter 10 I/O wiring for 2700 with configurable input/outputs.................................................... 69
10.1 Channel configuration..................................................................................................................69
10.2 Basic mA Output wiring................................................................................................................ 70
10.3 HART/analog single loop wiring....................................................................................................70
10.4 HART multidrop wiring.................................................................................................................71
10.5 Internally powered Frequency Output wiring on Channel B.......................................................... 72
10.6 Externally powered Frequency Output wiring on Channel B..........................................................73
10.7 Internally powered FO wiring on Channel C.................................................................................. 74
10.8 Externally powered Frequency Output wiring on Channel C..........................................................75
10.9 Internally powered Discrete Output wiring on Channel B..............................................................76
10.10 Externally powered Discrete Output wiring on Channel B........................................................... 77
10.11 Internally powered Discrete Output wiring on Channel C............................................................78
10.12 Externally powered Discrete Output wiring on Channel C........................................................... 79
10.13 Internally powered Discrete Input wiring.................................................................................... 80
10.14 Externally powered Discrete Input wiring................................................................................... 80
Chapter 11 I/O wiring for 2700 with FOUNDATION fieldbus or PROFIBUS-PA...................................81
11.1 FOUNDATION fieldbus wiring........................................................................................................... 81
11.2 PROFIBUS-PA wiring..................................................................................................................... 81
iv Micro Motion 1700 and 2700 Transmitters
Installation Manual Before you begin
20001700 December 2019

1 Before you begin

1.1 About this document

This manual provides information on planning, mounting, wiring, and initial setup of the 1700-2700 transmitter. For information on full configuration, maintenance, troubleshooting, or service of the transmitter, see the configuration and use manual.
The information in this document assumes that users understand basic transmitter and sensor installation, configuration, and maintenance concepts and procedures.

1.2 Hazard messages

This document uses the following criteria for hazard messages based on ANSI standards Z535.6-2011 (R2017).
DANGER
Serious injury or death will occur if a hazardous situation is not avoided.
WARNING
Serious injury or death could occur if a hazardous situation is not avoided.
CAUTION
Minor or moderate injury will or could occur if a hazardous situation is not avoided.
NOTICE
Data loss, property damage, hardware damage, or software damage can occur if a situation is not avoided. There is no credible risk of physical injury.
Physical access
NOTICE
Unauthorized personnel can potentially cause significant damage and/or misconfiguration of end users' equipment. Protect against all intentional or unintentional unauthorized use.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access to protect users' assets. This is true for all systems used within the facility.

1.3 Related documentation

You can find all product documentation on the product documentation DVD shipped with the product or at www.emerson.com.
See any of the following documents for more information:
Micro Motion Series 1000 and Series 2000 Transmitters with MVD Technology Product Data
Sheet
Installation Manual 5
Before you begin Installation Manual
December 2019 20001700
1700 documentsMicro Motion Model 1700 Transmitters with Analog Outputs Configuration and Use
Manual
Micro Motion Model 1700 Transmitters with Intrinsically Safe Outputs Configuration
and Use Manual
2700 documentsMicro Motion Model 2700 Transmitters with Analog Outputs Configuration and Use
Manual
Micro Motion Model 2700 Transmitters with Configurable Input/Outputs Configuration
and Use Manual
Micro Motion Model 2700 Transmitters with Intrinsically Safe Outputs Configuration
and Use Manual
Micro Motion Model 2700 Transmitters with FOUNDATION™ Fieldbus Configuration and
Use Manual
Micro Motion Model 2700 Transmitters with PROFIBUS-PA Configuration and Use
Manual
Micro Motion Fuel Consumption Application for Transmitters Installation and Operation
Guide
Micro Motion 9-Wire Flowmeter Cable Preparation and Installation Guide
Micro Motion Enhanced Density Application Manual
Sensor installation manual
6 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700 December 2019
Planning

2 Planning

2.1 Meter components

A meter consists of the following components:
A transmitter
A sensor
A core processor that provides additional memory and processing functions

2.2 Installation types

The transmitter was ordered and shipped for one of up to eight installation types. The fifth character of the transmitter model number indicates the installation type.
Figure 2-1: Installation type indication for 1700 and 2700 transmitters
The model number is located on the device tag on the side of the transmitter.
Table 2-1: Installation types for 1700 and 2700 transmitters
Model code Description
R Remote mount 4-wire
I Integral
E Remote enhanced core processor (painted aluminum housing) with remote
transmitter
C Remote mount 9-wire (painted aluminum housing with integral core)
B Remote core processor with remote transmitter
M Remote mount 4-wire (stainless steel housing)
P Remote mount 9-wire (stainless steel housing)
(1)
H
(1) This option is available only with the 2700 FOUNDATION™ fieldbus transmitter
The transmitter is mounted directly to the sensor. Integral installations do not require separate transmitter installation. Power supply and I/O must be field wired to the transmitter.
Remote mount 4-wire (painted aluminum housing) for connecting to Compact Density Meter (CDM), Fork Density Meter (FDM), Fork Viscosity Meter (FVM)
Installation Manual 7
STATUS
SCROLL SELECT
Planning Installation Manual
December 2019 20001700
Figure 2-2: Integral installation (model code I)
Note
If replacing an integral 1700/2700 transmitter with a spare transmitter, retain the transition ring. The replacement does not include a new transition ring.
Figure 2-3: High-temperature meters with factory connection (model code I)
A
B
C
The transmitter is shipped with a flexible connection factory installed between the sensor and the transmitter. The transmitter must be dismounted from its shipping location (spot­welded to the sensor case) and then mounted separately. Power supply and I/O must be field wired to the transmitter.
A. Sensor
B. Transmitter or core processor
C. Factory-installed flexible connection
8 Micro Motion 1700 and 2700 Transmitters
Installation Manual
Planning
20001700 December 2019
Figure 2-4: 4-wire remote installation for Coriolis meters (model code R or M)
A
B
C
D
A
The transmitter is installed remotely from the sensor. The 4-wire connection between the sensor and transmitter must be field wired. Power supply and I/O must be field wired to the transmitter.
A. Transmitter
B. Field-wired 4-wire connection C. Core processor D. Sensor
Figure 2-5: 4-wire remote installation for density and viscosity meters (CDM, FDM, or FVM with fieldbus only model code H)
The transmitter is installed remotely from the Compact Density Meter (CDM), Fork Density Meter (FDM), or Fork Viscosity Meter (FVM). The 4-wire connection between the sensor and transmitter must be field wired. Power supply and I/O must be field wired to the transmitter.
A. Transmitter
B. Field-wired 4-wire connection C. Meter electronics
Installation Manual 9
Planning Installation Manual
December 2019 20001700
Figure 2-6: 9-wire remote installation (model code P)
A
B
C
D
A
The transmitter and core processor are combined in a single unit that is installed remotely from the sensor. The 9-wire connection between the transmitter/core processor and the sensor must be field wired. Power supply and I/O must be field wired to the transmitter.
A. Transmitter
B. Field-wired 9-wire connection C. Junction box D. Sensor
10 Micro Motion 1700 and 2700 Transmitters
Installation Manual Planning
20001700 December 2019
Figure 2-7: Remote core processor with remote sensor installation (model code B or E)
C
D
A
B
E
F
The transmitter, core processor, and sensor are all mounted separately. The 4-wire connection between the transmitter and core processor must be field wired. The 9-wire connection between the core processor and the sensor must be field wired. Power supply and I/O must be field wired to the transmitter. This configuration is sometimes called
double-hop.
A. Junction box
B. Sensor C. Transmitter D. Field-wired 4-wire connection
E. Core processor
F. Field-wired 9-wire connection

2.3 Maximum cable lengths between sensor and transmitter

The maximum cable length between the sensor and transmitter that are separately installed is determined by cable type.
Cable type
Micro Motion 4-wire remote mount
Micro Motion 9-wire remote mount
Installation Manual 11
Wire gauge Maximum length
Not applicable 1,000 ft (305 m) without
Ex-approval
500 ft (152 m) with IIC
rated sensors
1,000 ft (305 m) with IIB
rated sensors
Not applicable 60 ft (18 m)
Planning Installation Manual
December 2019 20001700
Cable type Wire gauge Maximum length
User-supplied 4-wire VDC 22 AWG (0.326 mm²) 300 ft (91 m)
VDC 20 AWG (0.518 mm²) 500 ft (152 m)
VDC 18 AWG (0.823 mm²) 1,000 ft (305 m)

2.4 Output options

The transmitter was ordered and shipped for one of up to 10 output options. You must know your transmitter output option to correctly install the transmitter. The eighth character of the transmitter model number indicates the output option.
Figure 2-8: Output option indication for 1700 and 2700 transmitters
The model number is located on the device tag on the side of the transmitter.
Table 2-2: Output options for 1700 transmitters
Letter Description
A Analog outputs – one mA, one frequency, one RS-485
D Intrinsically safe analog outputs – one mA, one frequency
RS-485 22 AWG (0.326 mm²) or larger
1,000 ft (305 m)
Table 2-3: Output options for 2700 transmitters
Letter Description
A Analog outputs – one mA, one frequency, one RS-485
B Configurable I/O channels (default configuration of two mA, one frequency)
C Configurable I/O channels (custom configuration )
D Intrinsically safe analog outputs – two mA, one frequency
E Intrinsically safe FOUNDATION fieldbus H1 with standard function blocks
G PROFIBUS-PA
N Non-incendive FOUNDATION fieldbus H1 with standard function blocks
2 WirelessHART® – one mA, one frequency, one RS-485
3 WirelessHART – one mA, two configurable I/O channels (custom
configuration)
4 Intrinsically safe WirelessHART – two mA, one frequency
12 Micro Motion 1700 and 2700 Transmitters
Installation Manual Planning
20001700 December 2019

2.5 Electrical connections

Table 2-4: 1700 and 2700 transmitters
Connection type 1700 2700
Input/Output Intrinsically safe
version: Two pairs of wiring terminals for transmitter outputs
Non-intrinsically
safe analog outputs (output option A): Three pairs of wiring terminals for transmitter outputs
Power One pair of wiring terminals accepts AC or DC power
One internal ground lug for power-supply ground wiring
Service port Two clips for temporary connection to the service port
Three pairs of wiring terminals for transmitter I/O and communications
Notes
Each screw terminal connection accepts one or two solid conductors, 14 AWG
(2.08 mm²) to 12 AWG (3.31 mm²) or one or two stranded conductors, 22 AWG (0.326 mm²) to 14 AWG (2.08 mm²). Each plug type connector accepts one stranded or solid conductor, 24 AWG (0.205 mm²) to 12 AWG (3.31 mm²).
For 1700/2700 transmitters with an integral core processor (mounting code C), the 4-
wire connection between the transmitter and core processor is not normally accessed.

2.6 Environmental limits

1700 and 2700
Type
Ambient temperature limits
Humidity limits 5 to 95% relative humidity, non-condensing at
Installation Manual 13
(1)
Value
Operating:
-40 °F (-40.0 °C) to 140 °F (60.0 °C)
Storage:
-40 °F (-40.0 °C) to 140 °F (60.0 °C)
140 °F (60.0 °C)
Planning Installation Manual
December 2019 20001700
Type Value
Vibration limits Meets IEC 60068-2-6,endurance sweep, 5 to
2000 Hz up to 1.0 g
Housing rating NEMA 4X [IP66/67/69(K)]
(1) Display responsiveness decreases, and display may become difficult to read below -4 °F
(-20.0 °C). Above 131 °F (55.0 °C), some darkening of display might occur.
(2) The protection is IP69K-based NEN-ISO 20653:2013 and IP69 when using standard IEC/EN
60529.
(2)

2.7 Hazardous area classifications

If you plan to mount the transmitter in a hazardous area:
Verify that the transmitter has the appropriate hazardous area approval. Each
transmitter has a hazardous area approval tag attached to the housing.
Ensure that any cable used between the transmitter and the sensor meets the
hazardous area requirements.

2.8 Power requirements

Self-switching AC/DC input, automatically recognizes supply voltage
85 to 265 VAC, 50/60 Hz, 6 watts typical, 11 watts maximum
18 to 100 VDC, 6 watts typical, 11 watts maximum
Complies with low voltage directive 2006/95/EC per EN 61010-1 (IEC 61010-1) with
amendment 2, and Installation (Overvoltage) Category II, Pollution Degree 2
Notes
For DC power:
Power requirements assume a single transmitter per cable.
At startup, the power source must provide a minimum of 1.5 amps of short-term
current per transmitter.
Length and conductor diameter of the power cable must be sized to provide 18 VDC
minimum at the power terminals, at a load current of 0.5 amps.
M = 18V + R × L × 0.5A
M: Minimum supply voltage R: Cable resistance L: Cable length
Table 2-5: Typical power cable resistance at 68 °F (20.0 °C)
Wire gauge Resistance
14 AWG 0.0050 Ω/ft
16 AWG 0.0080 Ω/ft
14 Micro Motion 1700 and 2700 Transmitters
Installation Manual Planning
20001700 December 2019
Table 2-5: Typical power cable resistance at 68 °F (20.0 °C) (continued)
Wire gauge Resistance
18 AWG 0.0128 Ω/ft
20 AWG 0.0204 Ω/ft
2.5 mm
1.5 mm
1.0 mm
0.75 mm
0.50 mm
2
2
2
2
2
0.0136 Ω/m
0.0228 Ω/m
0.0340 Ω/m
0.0460 Ω/m
0.0680 Ω/m
Installation Manual 15
Planning Installation Manual
December 2019 20001700
16 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700 December 2019
Mounting

3 Mounting

3.1 Mounting for integral installations

There are no separate mounting requirements for integral transmitters.

3.2 Orientation

You can mount the transmitter in any orientation as long as the conduit openings do not point upward.
NOTICE
Upward-facing conduit openings risk condensation moisture entering the transmitter housing that could damage the transmitter.

3.3 Accessibility for maintenance

Mount the transmitter in a location and orientation that satisfies the following conditions:
Allows sufficient clearance to open the transmitter housing cover. Micro Motion
recommends 8 in (203 mm) – 10 in (254 mm) clearance at the rear of the transmitter.
Provides clear access for installing cabling to the transmitter.

3.4 Mounting options

There are two options available for mounting the transmitter:
Mount the transmitter to a wall or flat surface.
Mount the transmitter to an instrument pole.
3.4.1

Mount the transmitter to a wall

Prerequisites
Use two 0.31 in (7.9 mm) U-bolts for a 2 in (51 mm) pipe, and four matching nuts that
can withstand the process environment. Appropriate bolts and nuts are shipped with remote mount transmitters in the ship kit. The pipe mount kit can be ordered as part of the 1700/2700 part number.
Ensure that the surface is flat and rigid, does not vibrate, or move excessively.
Confirm that you have the necessary tools, and the mounting kit shipped with the
transmitter.
Procedure
1. If desired, re-orient the transmitter on the mounting bracket.
Installation Manual 17
B
D
C
A
Mounting Installation Manual
December 2019 20001700
a) Remove the junction end-cap from the junction housing.
b) Loosen each of the four 0.16 in (4.1 mm) cap screws.
c) Rotate the bracket so that the transmitter is oriented as desired.
d) Tighten the cap screws, torquing to 30 in lbf (3.39 N m) to 38 in lbf (4.29 N
m).
e) Replace the junction end-cap.
Figure 3-1: Components of 4-wire remote mount transmitter (aluminum housing)
A. Transmitter B. Mounting bracket C. Cap screws
D. End-cap
18 Micro Motion 1700 and 2700 Transmitters
Installation Manual Mounting
20001700 December 2019
Figure 3-2: Components of a 4-wire remote mount transmitter (stainless steel housing)
A. Transmitter B. Mounting bracket C. Cap screws
D. End-cap
Installation Manual 19
A
B
C
Mounting
December 2019 20001700
Figure 3-3: Components of 9-wire remote mount transmitter
Installation Manual
A. Transmitter B. Cap screws C. Mounting bracket
2. Attach the mounting bracket to the wall.
3.4.2

Mount the transmitter to an instrument pole

Prerequisites
Use two 0.3125 in (8 mm) U-bolts for 2 in (51 mm) pipe, and four matching nuts, that
can withstand the process environment. Micro Motion does not supply U-bolts or nuts (appropriate bolts and nuts are available as an option).
Ensure the instrument pole extends at least 12 in (305 mm) from a rigid base, and is no
more than 2 in (51 mm) in diameter.
Procedure
1. If desired, re-orient the transmitter on the mounting bracket.
a) For 4-wire remote mount transmitters, remove the junction end-cap from
the junction housing.
b) Loosen each of the four 0.16 in (4.1 mm) cap screws.
c) Rotate the bracket so that the transmitter is oriented as desired.
d) Tighten the cap screws, torquing to 30 in lbf (3.39 N m) to 38 in lbf (4.29 N
m).
20 Micro Motion 1700 and 2700 Transmitters
B
D
C
A
Installation Manual Mounting
20001700 December 2019
e) If applicable, replace the junction end-cap.
Figure 3-4: Components of 4-wire remote mount transmitter (aluminum housing)
A. Transmitter B. Mounting bracket C. Cap screws
D. End-cap
Installation Manual 21
A
B
C
Mounting Installation Manual
December 2019 20001700
Figure 3-5: Components of 9-wire remote mount transmitter
A. Transmitter and integral core B. Cap screws C. Mounting bracket
2. Attach the mounting bracket to an instrument pole.
22 Micro Motion 1700 and 2700 Transmitters
A
B
C
D
Installation Manual
Mounting
20001700 December 2019

3.5 Rotate the transmitter on the sensor (optional)

In integral installations, you can rotate the transmitter on the sensor up to 360º in 90º increments.
Figure 3-6: Components of an integral transmitter
A. Transmitter
B. Transition ring C. Cap screws D. Sensor
Procedure
1. Loosen each of the four cap screws 0.16 in (4.1 mm) that fasten the transmitter to
the base.
2. Rotate the transmitter counter-clockwise so that the cap screws are in the unlocked
position.
3. Gently lift the transmitter straight up, disengaging it from the cap screws.
NOTICE
Do not disconnect or damage the wires that connect the transmitter to the core processor.
4. Rotate the transmitter to the desired orientation.
NOTICE
Do not pinch or stress the wires.
The slots on the transition ring should be aligned with the cap screws.
5. Gently lower the transmitter onto the base, inserting the cap screws into the slots.
Installation Manual 23
A
B
C
G
E
F
D
Mounting
Installation Manual
December 2019 20001700
6. Rotate the transmitter clockwise so that the cap screws are in the locked position.
7. Tighten the cap screws, torquing to 1.70 ft lbf (2 N m) to 2.51 ft lbf (3 N m).

3.6 Rotate the user interface on the transmitter (optional)

The user interface on the transmitter electronics module can be rotated 90º or 180° from the original position. .
Figure 3-7: Display components
A. Transmitter housing
B. Sub-bezel C. Display module D. Display screws
E. End-cap clamp
F. Cap screw
G. Display cover
Notes
When using the touch buttons, you must cover at least a 0.31 in (7.9 mm) diameter
circle over the surface above the touch button: using your thumb may be more effective because it has a greater surface area.
When the housing cover is removed, the touch buttons do not function.
Procedure
1. Shut off power to the unit.
2. Remove the end-cap clamp by removing the cap screw.
3. Turn the display cover counterclockwise to remove it from the main enclosure.
24 Micro Motion 1700 and 2700 Transmitters
Installation Manual Mounting
20001700 December 2019
4. Carefully loosen (and remove if necessary) the semicaptive display screws while
holding the display module in place.
5. Carefully pull the display module out of the main enclosure until the sub-bezel pin
terminals are disengaged from the display module.
Note
If the display pins come out of the board stack with the display module, remove the pins and reinstall them.
6. Rotate the display module to the desired position.
7. Insert the sub-bezel pin terminals into the display module pin holes to secure the
display in its new position.
8. If you have removed the display screws, line them up with the matching holes on
the sub-bezel, then reinsert and tighten them.
9. Place the display cover onto the main enclosure.
10. Turn the display cover clockwise until it is snug.
11. Replace the end-cap clamp by reinserting and tightening the cap screw.
12. Restore power to the transmitter.
Installation Manual 25
Mounting Installation Manual
December 2019 20001700
26 Micro Motion 1700 and 2700 Transmitters
Loading...
+ 58 hidden pages