Emerson MCR Portable Schematics

50 Hz Mini/Micro
Computer Regulator (MCR) Series
Installation and Operation Manual
Operating & Service Instructions
Sola Minicomputer Regulators UL White Card Listed – Power Supply Classification CSA Certified – Transformer Classif icat ion
Contact Technical Services at (800) 377-4384 with any questions.
Fax-on-Demand: (877) 888-9329, Document #: 8412
50 Hz Mini/Micro
Computer Regulator (MCR) Series
Installation and Operation Manual

General Description and Specifications

The Sola Micro/Minicomputer regulator provides voltage regulation and isolation from both transverse and common mode noises for any type of load. It also suppresses transients, protects from overloads and serves as a portable dedicated line. It is the ultimate in AC power conditioning equipment.
Two types of units are manufactured. Hardwired units, rated 125 to 1500VA, should be permanently installed by competent electricians. Portable units, rated 150 to 2000VA, are designed for office type environments and have a low 43dB sound level.
Operating Temperature Range: Phase: Input Voltage (Hardwired Models): Input Voltage (Portable Models): Output Voltage (Hardwired models): Output Voltage (Portable models): Output Voltage Regulation:
Output Harmonic Distortion:
Efficiency: Dropout:
Common Mode Noise Rejection: Transverse Mode Noise Rejection: Safety Approvals:
* The unit must not be powered while operating this switch. Unplug the unit
from the power source before using this switch.
-20°C to + 50°C Single Refer to Table 4 220/240 VAC 110/120/220/240 VAC 220 or 240 VAC, switch selectable* +/-5% for an input line variation
of +/-15%. Less than 3% total RMS content at
full load with rated input voltage 85% at full load. No loss of output for line loss of
3msec. Greater than 120dB Greater than 60dB Designed and built per VDE 0550
and 0806. Specifications (compatible with IEC 380/435)
Contact Technical Services at (800) 377-4384 with any questions.
Fax-on-Demand: (877) 888-9329, Document #: 8412
2
50 Hz Mini/Micro
Computer Regulator (MCR) Series
Installation and Operation Manual
Safety Notice
High voltages are present inside all regulators. Do not reach inside a unit when it is energized. To measure voltage, de-energize the unit, connect the meter, and then re-energize the unit.

Hardwired Units

Installation – Mechanical
Table 1 shows the physical dimensions of the hardwired units. These units can be mounted with the “This Side Up” designation upwards, or they can be mounted horizontally. Allow 60cm above and 30cm on either side of the regulator during installation.
Contact Technical Services at (800) 377-4384 with any questions.
Fax-on-Demand: (877) 888-9329, Document #: 8412
3
Computer Regulator (MCR) Series
Installation and Operation Manual
Table 1. Hardwired Regulator Dimensions
50 Hz Mini/Micro
VA
125 63-23-612-8 A 23,11 18,90 11,43 13,67 8,08 250 63-23-625-8 A 26,92 18,90 11,43 13,67 12,24
500 63-23-650-8 A 33,66 16,21 19,69 22.86 18,14 1000 63-23-710-8 A 45,57 16,21 19,69 22,86 28,12 2000 63-23-720-8 B 44,65 23,72 26,82 32,38 50,81 3000 63-23-730-8 B 67,72 23,81 26,90 32,38 72,59 5000 63-23-750-8 B 76,20 23,81 26,90 32,38 109,79 7500 63-23-775-8 C 71,12 23,81 62,23 65,55 176,94
10000 63-23-810-8 C 76,20 23,81 62,23 65,55 220,50 15000 63-28-815-8 * 76,20 23,81 91,44 97,15 349,35
VA
125 63-23-612-8 A 12,07 10,48 5,53 0,79 X 1,75 8,08
250 63-23-625-8 A 12,07 10,48 5,53 0,79 X 1,75 12,24
500 63-23-650-8 A 20,64 14,30 9,12 0,79 X 2,06 18,14 1000 63-23-710-8 A 20,64 14,30 14,83 0,79 X 2,06 28,12 2000 63-23-720-8 B 29,84 10,69 12,70 1,12 X 1,75 50,81 3000 63-23-730-8 B 29,84 15,39 9,29 1,12 X 1,75 72,59 5000 63-23-750-8 B 29,84 23,79 9,37 1,12 X 1,75 109,79 7500 63-23-775-8 C 63,02 18,71 9,37 1,12 X 1,75 176,94
10000 63-23-810-8 C 63,02 23,80 9,37 1,12 X 1,75 220,50 15000 63-28-815-8 * 94,56 23,80 9,37 1,42 X 1,75 349,35
Catalog Number
Catalog Number
Outline
Drawing
Outline
Drawing
Dim.
A
(cm)
Dim.
E
(cm)
Dim.
B
(cm)
Dim.
F
(cm)
Dim.
C
(cm)
Dim.
G
(cm)
Dim.
D
(cm)
Dim.
H
(cm)
Approx.
Shipping
Weight (kg)
Approx.
Shipping
Weight (kg)
Same as (c), but is a triplex assembly.
Note:
Dimension C includes heat shield around core for all units
except 125, 250 and 500VA, which have no shield.
Contact Technical Services at (800) 377-4384 with any questions.
Fax-on-Demand: (877) 888-9329, Document #: 8412
4
50 Hz Mini/Micro
Computer Regulator (MCR) Series
Installation and Operation Manual
Figure 1: Hardwired Regulator Dimensions (Refer to Table 1).
Knockout locations are typical.
Outline A Outline B Outline C
Table 2 shows the recommended bolt size for mounting the hardwired units.
Table 2. Bolt Sizes
Rated VA
of Unit
125/250 M6
500/1000 M7
1500 to 10000 M8
150000 M12
Minimum Recommended Size
of Steel Mounting Hardware

Portable Units

Installation – Mechanical
These units may be installed in any protected environment. Allow 60 cm above and 30 cm on either side of the installation. Dimensions of the portable regulators are given in Table 3.
Contact Technical Services at (800) 377-4384 with any questions.
Fax-on-Demand: (877) 888-9329, Document #: 8412
5
50 Hz Mini/Micro
Computer Regulator (MCR) Series
Installation and Operation Manual
Table 3. Portable Regulator Dimensions
Catalog Number
63-13-625-9 250 33,66 19,56 17,93 15,5 63-13-650-9 500 41,27 21,60 21,59 20,0
63-13-710-9 1000 41,27 21,60 21,59 28,63
63-13-720-9 2000 41,91 27,94 26,34 53,18
VA
Figure 2: Dimensions - Portable Regulators (Refer to Table 3)
Dim. A
(cm)
Dim. B
(cm)
Dim. C
(cm)
Weight (kg)
Approx.
Shipping

Hardwired Models

Installation – Electrical
These regulators may be jumpered for different input and output voltages. The terminal block is at the top of the unit in units 2kVA and smaller. Larger units (3kVA and up) have the terminal block located in the capacitor compartment. Table 4 gives the proper jumper configurations for needed input and output voltages. Figure 3 shows the schematic diagrams of the units.
Contact Technical Services at (800) 377-4384 with any questions.
Fax-on-Demand: (877) 888-9329, Document #: 8412
6