Emerson Ma1200-1, Ma1200 Owner's Manual

Page 1
Part No. SP6550 Printed in Canada
CAUTION: READ ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLATION.
SAVE THIS OWNER’S MANUAL FOR FUTURE REFERENCE.
Model No.
MA 1200 0
MA 1200 Evaporative Console Humidifier Owner’s Manual
MA1200 Manual - 71233 7/12/05 2:36 PM Page 1
Page 2
Safety Signal Words
DANGER: means if the safety information is
not followed someone will be seriously injured or killed. WARNING: means if the safety information is not followed someone could be seriously injured or killed. CAUTION: means if the safety information is not followed someone may be injured.
1. To reduce the risk of fire or shock hazard, plug humidifier directly into a 120V, A.C. electrical outlet. Do not use extension cords.
2. Keep the electric cord out of traffic areas. To reduce the risk of fire hazard, never put the electric cord under rugs, near heat reg­isters, radiators, stoves or heaters.
3. Always unplug the humidifier before mov­ing it, removing the fan assembly section, before cleaning, or whenever the humidifi­er is not in service.
4. Keep the humidifier clean.
5. Do not put foreign objects inside the humidifier.
6. Never use your humidifier while any part is missing or damaged in any manner.
7. To reduce the risk of electrical hazard or damage to humidifier, do not tilt, jolt or tip humidifier over while unit is running.
8. To reduce the risk of damage to humidifier, unplug humidifier when water bottles are empty or when the humidifier is not in use.
9. To reduce the risk of accidental electrical shock, do not touch the cord or controls with wet hands.
10.Note the warning label shown below.
WARNING: To reduce the risk of fire, electric shock, or injury always unplug before filling, servicing or cleaning.
GENERAL SAFETY INSTRUCTIONS
2
Limited Warranty
All products covered by this Owner’s Manual are warranted against defects in work­manship and materials for one year from the date of sale except for motors, which are warranted for two years. This warranty does not apply to damage from accident, misuse or alteration nor where the connected voltage is more than 5% above the nameplate voltage, nor to the equipment improperly installed or wired or maintained in violation of this Owner’s Manual. No other written or oral warranty applies. No employee, agent, dealer or other person is authorized to give any warranties on behalf of Emerson. The customer shall be responsible for all costs incurred in the removal or reinstallation and shipping of the product for repairs. Within the limitations of this warranty, inoperative units should be returned, with a copy of the sales receipt, freight prepaid to a local repair service center and we will repair or replace, at our option, at no charge to you with return freight paid by Emerson. It is agreed that such repair or replacement is the exclusive remedy available from Emerson and that
Emerson Is Not Responsible For Damages Of Any Kind, Including Incidental
And Consequential Damage. Some states or provinces do not allow the exclusion
or limitation of incidental or consequential damages, so the above exclusion or lim­itation may not apply to you. The warranty gives you specific legal rights, and you may also have other rights which vary from state to state or province to province.
Sales receipt required as proof of purchase for warranty claims.
MA1200 Manual - 71233 7/12/05 2:36 PM Page 2
Page 3
Description MA1200
* Gallon Output/24 hrs 12
Capacity of Bottle 1.9 Gallons Capacity of Base 2.0 Gallons
* Sq. Ft. Coverage 2500
Fan Speeds 3 Replacement Filter MAF-1 Power Light Yes Fill Light Yes Auto Humidistat Yes Auto Shut Off Yes Controls
Electronic (Push Button)
Casters Yes (4) CUL Listed Yes Volts 120 A.C. Hertz 60 Amps 0.80 Watts 80
Know Your Humidifier
3
* Based on an area with average insulation
and an 8 foot ceiling height ANSI/AHAM HU-1-1997, SEC. 8.1
Bottle Handles
Speed Control
Bottle
Base
Filter: Replacement No. MAF-1
Housing Assembly
Fan Assembly
Humidistat (On power cord)
Casters
MA1200 Manual - 71233 7/12/05 2:36 PM Page 3
Page 4
Your new Emerson MoistAir humidifier is designed to satisfy home humidity requirements through the principle of evaporation of water in the air. After water is added to the humidifier, the filter begins to soak up the water and will become saturated in approximately 30 minutes. Air drawn in through the open­ings in the lower housing passes through the filter by means of a circulation fan. As air passes through the filter, moisture is absorbed into the air and then released in the form of vapor. No water droplets will enter the home. All evapora­tion into the air takes place in the humidi­fier, which means that the residue left by evaporating water is not passed into the home, but remains in the filter. This natural process of evaporation helps eliminate the chance of white dust in the humidified output air.
CAUTION: Use only liquid EPA Registered Bacteriostat available from your local retail store. Under no circumstances should you use water treatment products designed for Roto belt or Ultrasonic humidifiers.
CAUTION: To reduce the risk of injury, fire or damage to humidifier, use only cleaners specifically recom­mended for humidifiers. Never use flammable, combustible or poisonous materials to clean your humidifier. To reduce the risk of scalds and dam­age to humidifier, never put hot water in humidifier.
Your new Emerson MoistAir humidifier is supplied with four swivel casters for ease of maneuverability. Remove the casters from the top of the packing material inside the carton. The casters press into the bottom of the base at the locations shown. To make assembly easier remove the water bottle, housing assembly and filter and flip the base upside to install. See steps 2-4 of "Replacement and Care of Filters" section on page 12 for proce­dure. Take care not to damage the floats or base assembly if choosing this method of assembly. Press casters into location beside X.
Note: Casters should be installed manu­ally. Do not use any tools to install them. Once installed return the unit to its origi­nal state and proceed to "Location Instructions.
Humidifier Operation
Unpacking and Assembly
4
Humidified air is then released through the top
Dry air enters through the louvers in the housing
X
X
X
X
MA1200 Manual - 71233 7/12/05 2:36 PM Page 4
Page 5
Location Instructions
WARNING: For your own safety, do not use humidifier if any parts are damaged or missing.
Step 1
Place humidifier on a flat level surface in an area of house where most humidity is needed, or one which would likely result in moist air being circulated throughout the house such as near a cold air return. Placing the unit level is very important. Special attention should be given to unit’s level if the humidifier is located on car­peting. Moist air (humidity) produced will disperse into the whole house, but the area closest to the unit will have the high­est humidity. If the unit is positioned close to a window, condensation may form on the window pane. If this is not appropri­ate the unit should be repositioned in another location. NOTE: Due to release of cool, moist air from humidifier, it is best to direct air away from home thermostat and hot air registers. It is best to position humidifier next to an inside wall. Hot air registers and cold air from outside walls can affect the efficiencies of the controls. Unit should not be placed where warm air from a hot air register blows directly on unit.
Step 2
The humidifier should be positioned with the back (cord exit side) and left side, at least 2 inches away from the wall. Air needs to enter through all of the louvers in the housing assembly in order for the humidifier to operate at peak efficiency.
Locate nearest 120V A.C. wall socket in the location desired, preferably on inside wall. With the humidifier in the desired location, route the electrical cord safely so no one will trip or upset the humidifier. Plug in the electrical cord.
WARNING: To reduce the risk of fire or shock hazard, humidifier should be plugged into a 120V A.C. outlet. Do not use extension cords.
To reduce the risk of electrical shock, this humidifier has a polarized plug (one blade is wider than the other). This plug will fit in a polarized outlet only one way.
If the plug does not fit fully in the outlet, reverse plug. If it still does not fit, contact a qualified electrician to install the proper outlet. Do not change the plug in any way.
Electrical Hook-Up
5
Note: Be sure humidistat located approximately 4 inches outside humidi­fier body on power cord is free from obstruction and away from any hot air register.
At least 2" from wall
MA1200 Manual - 71233 7/12/05 2:36 PM Page 5
Page 6
WARNING: To reduce the risk of shock, always unplug humidifier before cleaning or servicing.
WARNING: To reduce the risk of fire or shock hazard, do not pour or spill water into control or motor area. If controls get wet, let them dry completely and have unit checked by authorized service personnel before plugging in.
This humidifier is designed for use with the water bottle located to the right of the upper grill. The water bottle holds 1.9 gal­lons of water. The humidifier should be positioned where it will be operating.
To fill the whole house humidifier, grasp the bottle handle at the top of the bottle and lift it straight up and away from humidifier base. Take care not to bump or damage spring valve assembly on bottom of bottle.
NOTE: If it is desired to use approved bacteriostat, follow directions correctly.
The bottle of the whole house humidifier will hold 1.9 gallons of water.
The water bottle is designed with a Side Fill Cap. Remove the “Side Fill Cap” on the side of the water bottle by twisting counterclockwise.
Place the opening of the water bottle under a water faucet and fill. If desired, add liquid bacteriostat to help control the build up of bacteria and algae. Do not use solid water treatments. Solid debris could make the lower valve leak.
Install the “Side Fill Cap” by twisting clockwise. Hand tighten only.
Check for possible leaks by perform­ing the following:
1. Grasp bottle handle and hold the bottle upright over a sink.
2. Press up on valve plunger for about one second to let out a little water.
3. Release the plunger.
Water Fill
6
Turn Counterclockwise to Remove “Side Fill Cap”
Spring Valve Assembly
Base
Bottle
MA1200 Manual - 71233 7/12/05 2:36 PM Page 6
Page 7
7
4. Listen for air bubbles. Look for leaks around the “Side Fill Cap” and valve plunger.
5. If you hear air bubbles or see leaks, retighten the “Side Fill Cap” and repeat steps 1-4.
Wipe off excess water from the bottle. Position the water bottle back into the
humidifier base to the right of the grille. The “Side Fill Cap” must be facing out­ward. When positioned properly, the plunger will open and water will flow into the base. The base will hold the entire contents of the water bottle. Allow up to one minute for the water to flow into the base. Once the bottle is empty, remove it and refill it as mentioned earlier. Return it to the right side of the grille. The humidifi­er is now filled to capacity.
The water bottle may be filled at anytime as necessary during operation. To benefit from less frequent filling let the humidifier exhaust both the water from the bottle and base before filling. The unit is now ready for operation.
The operating controls of your MoistAir Quiet Comfort whole house humidifier are located towards the front of the humidifier.
Familiarize yourself with the controls. Refer to the diagram of the control area for the correct nomenclature used in this manual.
To Operate the Controls
Power Button / Light
When the unit is plugged in and the power button is pressed once the red power light will come on. The power light will stay on until the power button is pressed again turning the unit off or until the unit is unplugged.
Digital Display
The digital display will also show readouts when the unit is turned on. Initially there is a slight delay while the electronics cali­brate. Two bars (- -) flash during this time. Once calibration is complete a ROOM humidity reading between 25% ­95% will be displayed. Aflashing 25 dis-
play indicates that the room humidity is less than 25 %.
Note: The default settings at initial start­up are LOW fan speed and 65% SET humidity. After desired settings are selected by the user, they remain as defaults as long as the unit remains plugged in and there is no power interruption. If the unit is unplugged the
original default settings are employed.
IMPORTANT: Water damage may result if condensation starts to form on windows or walls. Humidity SET point should be lowered until condensation no longer forms.
Operating Humidifier Controls
Base
Bottle
Digital Display
Refill Light
On Light
Function Buttons
MA1200 Manual - 71233 7/12/05 2:36 PM Page 7
Page 8
Speed Button
This humidifier is equipped with a 3­speed fan control. Each push of the speed button advances the mode through the settings of HIGH, MEDIUM, and LOW. The selected setting is displayed on the digital readout. The higher the set­ting, the faster water is evaporated and released into the air. LOW is the quietest setting and is provid­ed for conditions that do not require a rapid evaporation rate.
Humidity Control
The +/- buttons allows you to adjust the humidity to suit your needs. This humidi­fier will automatically cycle on and off as required to maintain the selected setting. The readout displays both actual (ROOM) and desired (SET) humidity percentage (%) settings. The ROOM reading is the larger display of the two. The ROOM readout is displayed in 1% increments and has a range of 25% to 95%. If the room humidity level is equal to or less than 25% the display will show a flashing
25. The SET readout has a range of 30% to
65% and is adjusted in increments of 5%. Each press of the
(+) button increases the setting by 5% and conversely each press of the ( – ) button decreases the setting by 5%. A SET point of 65% operates the humidifier continuously regardless of the ROOM reading. The humidistat that senses the readings is located on the power cord. Insure that it is free from obstruction.
8
Operating Humidifier Controls (cont’d)
Speed
Humidity Buttons
Constant On Setting
MA1200 Manual - 71233 7/12/05 2:36 PM Page 8
Page 9
9
Refill Light
The humidifier base and bottle hold approxi­mately 2 gallons of water each. The bottle empties into the base during operation. When the base empties the red REFILL light will illuminate informing additional water is required. Also at this time the unit will auto­matically switch into “DRY OUT MODE” and continue to run on LOW speed until the filter is dry. The message “DRY OUT MODE” will appear on the digital display and the fan speed will switch to LOW speed. Note: The digital display will still show the speed the humidifier was operating in before the REFILL light turned on even though the fan is operating at LOW speed. During this time the room humidity level will continue to be monitored and the humidifier will cycle the fan on and off as required. If DRY OUT MODE is not desired, refill the humidifier with water. Note: Once the dry out cycle is complete the fan will shut off and the REFILL light will stay illuminated. The humidifier will automatically start again when it is refilled.
Operating Humidifier Controls (cont’d)
Refill Light
MA1200 Manual - 71233 7/12/05 2:36 PM Page 9
Page 10
10
Check Filter
Indicator
The ability of any humidifier to efficiently sup­ply humidity output relies heavily on the condi­tion of the filter. As the filter loads with trapped impurities found in water it gradually loses its wicking capability. When this happens mois­ture output is reduced and the humidifier has to work longer to satisfy the selected setting. When such a condition occurs, a flashing “CHECK FILTER” message will be displayed, disconnect the power and check the condition of the filter. If a buildup of deposits and severe discol­oration is evident replace the filter to restore maximum efficiency.
Humidistat
The humidistat located on the power cord senses the percentage of humidity in the air. It causes the humidifier to cycle on and off to maintain the selected humidity SET point. The fan will turn on if the “ROOM” reading falls 3% below the SET point and will continue to run the humidifi­er until a reading of 1% above the SET point is achieved. At this point the fan will stop. The fan will remain off until the ROOM reading falls 3% below the SET point again.
Dry Out Mode
When both the water bottle and the base are empty the red REFILL light will illuminate and the humidifier will automat­ically switch into DRY OUT MODE. The message DRY OUT MODE will appear on the digital display and the fan speed will automatically switch to LOW speed. Note: The digital display will show the speed the humidifier was operating in before the REFILL light turned on even though the fan is operating on LOW speed. During this time the humidifier will continue to cycle the fan on and off as required until the filter is completely dry thus producing no moisture output. Once dry, the fan will shut off leaving you with a dry humidifier that is less prone to mold
and mildew growth. The red REFILL light will be illuminated and the humidifier is ready for cleaning or refilling as desired.
Humidifier Operations
Note: Be sure humidistat located approxi­mately 4 inches outside humidifier body on power cord is free from obstruction and away from any hot air register.
Note: Fan automatically switches to "LOW" speed during "DRY OUT MODE" Display will still show programmed speed. i.e: HIGH
Dry Out Mode
Check Filter
MA1200 Manual - 71233 7/12/05 2:36 PM Page 10
Page 11
1. Place the humidifier where you intend to run it and be sure it is plugged in and full of water.
2. Press the POWER button once to turn the humidifier on. The red power light will illuminate.
The fan will immediately operate on LOW speed and the SET humidity percentage will read 65 on the digital display.
NOTE: Humidifier fan should operate at initial start up. If it does not, refer to the “Trouble Shooting” section on page 16 of this manual.
3. Wait a few seconds while the humidifier takes a ROOM humidity reading. During this time two bars (- -) will flash on the display.
4. Once a ROOM reading has registered proceed to adjust the desired humidity percentage by pressing the + or ­button. It will change the desired SET humidity level in increments of 5%.
If the room reading is a flashing 25, the humidity level is low. A SET point of 30% ­40% is recommended but there may be conditions that require a different setting. Depending on your particular environment it could take 24 hours and in some cases longer for the humidifier to reach your desired humidity. It may take several
fillings to bring the ROOM humidity level up to the SET point. A faster fan speed will accomplish this quicker. Once estab­lished adjust the fan speed to suit your needs.
IMPORTANT: Water damage may result if condensation starts to form on windows or walls. Humidity SET point should be lowered until condensation no longer forms.
5 If the humidifier stops running and the
red REFILL light is not illuminated, the humidity level is at the normal require­ments for that SET point. The table below shows recommended indoor humidity levels as it relates to outdoor temperatures.
Using Your Humidifier
Operating Tips for Best Performance
1. Position the humidifier next to an
inside wall at least 2 inches from the wall and away from any heat regis­ters.
2. Do not restrict airflow from entering or
exiting the humidifier.
3. Use EPAapproved bacteriostat
(available at your local retail store) to retard bacteria growth that may cause odors and may be harmful to your health.
4. Regular cleaning as instructed in “Cleaning Your Humidifier” section of this manual is recommended.
5. Replace the evaporative wicking filter at least once per humidification sea­son or more depending on water con­ditions in your area.
6. Ensure humidistat located on power cord is free from any obstruction and is away from heating vents or other sources of heat.
11
-10° F 2° F
10° F
20° F*
-24° C
-18° C
-12° C
-6° C*
20% 25% 30% 35%
When Outdoor Recommended Indoor
Temperature is: Relative Humidity is:
* and above
MA1200 Manual - 71233 7/12/05 2:36 PM Page 11
Page 12
WARNING: To reduce the risk of shock or injury from moving parts, always unplug humidifier before removing or replacing any parts.
CAUTION: To help retard bacteria growth and keep maximum efficien­cy, the filter should be replaced at least once per season, or more often under hard water conditions. Use Emerson (MAF-1) recommended replacement filter.
To replace the filter in your MoistAir Whole House humidifier, follow the instructions below.
1. Unplug humidifier. Before removing the filters, we recom­mend moving the humidifier to an area where floor coverings are not susceptible to water damage. (i.e. kitchen or bath areas.)
2. Remove the water bottle and set aside. Be sure not to bump or damage the lower spring valve.
3. Grasp the housing assembly and lift straight up and away from the base and set aside. The filter is now acces­sible.
4. Take note of the filter position. Remove the filter and dispose of prop­erly. You may want to clean the base at this time. See the "Cleaning Your Humidifier" section of this manual.
Replacement and Care of Filters
12
Grasp
Housing
Assembly
Securely
and Lift OFF
Filter
Base
MA1200 Manual - 71233 7/12/05 2:36 PM Page 12
Page 13
5. Install a new filter (MAF-1) into the base. Coil the filter and position it between the uprights in the bottom of the base. The start and finish of the coil should be captured at the centre of the base (see diagram) and the filter should be resting on the floor of the base.
6. Return the housing assembly to the top of the base. Return the water bottle to the right of the housing assembly and reposition the humidifier to its operating position.
7. The humidifier is now ready to be filled for operation.
Replacement and Care of Filters (continued)
13
Base
Position start and finish of coiled filter at center of base.
Align housing assembly bottom with top of base and reposition securely.
Return bottle to right side of humidifier.
Base Uprights
MA1200 Manual - 71233 7/12/05 2:36 PM Page 13
Page 14
WARNING: To reduce the risk of injury, fire or damage to humidifier, use only cleaners specifically rec­ommended for humidifiers. Never use flammable, combustible or poi­sonous materials to clean your humidifier. To reduce the risk of scalds and damage to humidifier, never put hot water in humidifier.
CAUTION: Local water purity varies from area to area and under certain conditions water impurities and air­borne bacteria may promote the growth of microorganisms in the reservoir of the humidifier.
To retard bacteria growth that may cause odors and be harmful to your health, use only MoistAir replace­ment filters. We also recommend using EPA approved bacteriostat, and humidifier cleaner, available at your local store.
Step 1
To make cleaning easier, the humidifier base should be empty and completely dried out. To accomplish this, use the fol­lowing method:
a. Allow the humidifier to run until the
red Refill light illuminates and the automatic shutoff has stopped the humidifier fan.
b. Unplug humidifier.
WARNING: If humidifier is not un­plugged, fan could start after housing is removed.
Step 2
To Remove Parts
1. Remove the water bottle and set aside. Be sure not to bump or dam­age the lower spring valve.
2. Grasp the housing assembly and lift straight up and away from the base and set aside. The filter is now accessible.
3. Take note of the filter position. Remove the filter and set aside or dispose of properly.
NOTE: There may be a little water still in the base. Carefully dump the water out or remove with a sponge.
Cleaning Your Humidifier
14
Note: Remove excess water before cleaning
MA1200 Manual - 71233 7/12/05 2:36 PM Page 14
Page 15
Step 3
Bi-Weekly Maintenance Removing Scale
1. Fill the humidifier base with one 8 oz. cup of undiluted white vinegar. Let solution stay 20 minutes.
2. Clean all interior surfaces with a soft brush. Dampen a soft cloth with undi­luted white vinegar and wipe out the base to remove scale.
3. Rinse thoroughly with clean warm water to remove scale and cleaning solution.
Disinfecting Base
1. Pour 1 gallon of water and 1 teaspoon chlorine bleach into the base. Let solution stay for 20 minutes, carefully swishing every few minutes. Wet all surfaces normally exposed to water.
2. Empty base after 20 minutes. Rinse with water until bleach smell is gone. Allow unit to dry out completely.
NOTE: The water bottle should be cleaned in the same manner as the base. Rinse thoroughly with clean water after all steps are complete.
Step 4
Replacing Parts
1. Install a new filter (MAF-1) or the filter previously set aside if it is in good condition into the base. Coil the filter and position it between the uprights in the bottom of the base. The start and finish of the coil should be captured in the center of the base (see diagram) and the filter should be resting on the floor of the base.
2. Return the housing assembly to the top of the base. Return the water bot­tle to the right of the housing assem­bly and reposition the humidifier to its operating position.
3. The humidifier is now ready to be filled for operation.
End of Season Maintenance
1. Follow “Bi-Weekly Maintenance” instructions at end of humidification season.
2. Remove filter and dispose of properly.
3. Let humidifier dry completely before storing. Do not store with water inside base or bottle.
4. Store in cool, dry location.
5. Install a new filter in clean humidifier before next season begins.
Note: “Bi-Weekly Maintenance” is also recommended if you do not plan to run the humidifier for one week or more.
Cleaning of Humidifier (continued)
15
Position start and finish of coiled filter at center of base.
Align housing assembly bottom with top of base and reposition securely.
MA1200 Manual - 71233 7/12/05 2:36 PM Page 15
Page 16
Troubleshooting
Trouble
Red power light and digital display not illuminated.
Fan not operating (Red power light and digital display is illuminated).
Fan running continuously.
Poor evaporation of water.
Bottle empties completely.
Bottle continues to empty after initial filling.
Bottle not emptying.
Probable Cause
• No Power.
• Power button has not been depressed.
• ROOM humidity level is 1% or more above SET humidity level.
• SET humidity level is 65%.
• ROOM humidity level is 3% or more below SET humidity level.
• CHECK FILTER message flashing.
.
• This is normal for initial filling.
• Air is entering water bottle.
• Spring Valve Assembly damaged or missing post in bottom of base.
• Base full of water.
Remedy
• Check 120 volt power source.
• Press power button once to turn on.
• Raise SET humidity level if desired.
• A SET humidity percentage of 65% operates fan continuously. Adjust SET level between 30% - 60%.
• Continue to run until desired humidity level is achieved. This may take up to 48 hours initially.
• Change to a fresh new filter.
• Refill bottle for maximum run time.
• Ensure fill cap is tightened securely.
• Ensure gasket on fill cap is in place.
• Check for leak in water bottle.
• Check orientation of bottle. Reposition so that spring valve on bottom of bottle is depressed by post in bottom of base.
• The base will hold the con­tents of water bottle (2.0 gal­lons). Continue to run humidifier to deplete water from base.
16
CAUTION: Use only liquid EPA Registered Bacteriostat available from local Retail store.
Use of other water treatment products may damage the filter component.
Under no circumstances should you use water treatment products designed for Roto belt or Ultrasonic humidifiers.
MA1200 Manual - 71233 7/12/05 2:36 PM Page 16
Page 17
17
Troubleshooting
Trouble
Display blinks or fan moves slightly when humidifier is plugged in.
“CHECK FILTER” message does not appear even when fil­ter is dirty or humidifier perfor­mance is clearly reduced.
Fan operating slower than speed registered on digital dis­play.
Humidifier not shutting off dur­ing “DRY OUT MODE”.
Probable Cause
• Normal
• Humidistat on power cord is being heated.
• Humidifier in “DRY OUT MODE”.
• Filter not dry.
Remedy
• No action required.
• Move power cord away from any source of heat or obstruc­tion.
• Humidifier automatically switches fan speed to “LOW” when “DRY OUT MODE” message is displayed.
• During “DRY OUT MODE” the humidifier will continue to run on “LOW” speed as required for up to 2 hours or until the filter is completely dry.
MA1200 Manual - 71233 7/12/05 2:36 PM Page 17
Page 18
Repair Parts
Parts List for MoistAir Humidifier
Model No. MA 1200 0
18
MA1200 Manual - 71233 7/12/05 2:36 PM Page 18
Page 19
Repair Parts
Parts List for MoistAir Humidifier
Model No. MA 1200 0
Always order by part number - Not by key number
* Standard Hardware Item - May be purchased locally † Stock item - Purchase locally or call 1-800-654-3545 from the USA or
1-866-808-6500 from Canada to order
NOTE: Any attempt to repair the control assembly or motor may create a hazard unless repair is done by a qualified service technician.
To order parts call: USA 1-800-654-3545 Canada 1-866-808-6500
19
Key No Part No. Description
1 830488 Housing, Upper 2 829806 Assembly, Control 3 829821 Blade, Fan 4 830778 Motor 5 828854 Switch, Micro 6 830489 Housing, Lower 7 MAF-1 † Filter 8 829815 * Screw, Pan Hd. Ty. AB #6 x 1/2 SS
9 830496 Support, Float 10 829816 Float, Reservoir 11 830484 Base 12 829812 Casters (Includes 4) 13 830537
Bottle, Includes Key # 14 14 824690-3 Cap, Fill 15 829805 Screw, Pan Hd. Trx Hi-Lo #6 x 3/4 16 830587 Cap, Screw 17 SP6550 Owner’s Manual (not shown)
MA1200 Manual - 71233 7/12/05 2:36 PM Page 19
Page 20
© 2004 Emerson Part No. SP6550 Form No. SP6550 Printed in Canada 11/04
FOR TECHNICAL HELP, CALL
(800) 654-3545 FROM USA OR (888) 744-4687 FROM CANADA
(Please have complete model number)
Emerson Tool Company
For more information about MoistAir® humidifiers visit our website at
www.moistair.com
MA1200 Manual - 71233 7/12/05 2:36 PM Page 20
Loading...