Emerson M820D, M820B User Manual

NetSure™ ACU+ (Advanced Control Unit Plus)
User Instructions, UM1M820BNA (Issue AH, March 4, 2013)
Specification Number: 1M820BNA, 1M820DNA Model Number: M820B, M820D
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
TABLE OF CONTENTS
Chapter 1. Introduction .......................................................................................................... 1
1.1 Preface ......................................................................................................................................................... 1
1.2 Overview....................................................................................................................................................... 1
1.3 Function Descriptions ................................................................................................................................... 2
1.3.1 Rectifier Control ................................................................................................................................ 2
1.3.2 Converter Control ............................................................................................................................. 2
1.3.3 System Components Monitoring and System Alarms Generation ................................................... 3
1.3.4 Operating Data Acquisition and Data Logs ...................................................................................... 3
1.3.5 Battery Management ........................................................................................................................ 4
1.3.6 Intelligent Power Matching (Energy Optimization Mode) ................................................................. 8
1.3.7 Power Split Feature .......................................................................................................................... 9
1.3.8 Diesel Management Feature ............................................................................................................ 9
1.3.9 PLC (Programmable Logic Controller) Function ............................................................................ 10
1.3.10 Supervisory Module (SM Modules) Monitoring .............................................................................. 10
1.3.11 Hybrid Control Function .................................................................................................................. 10
1.3.12 Maximum Current Limit Function.................................................................................................... 15
Chapter 2. Operation ............................................................................................................ 16
2.1 Local Indicators .......................................................................................................................................... 16
2.2 Passwords and Access Levels ................................................................................................................... 17
2.3 Local Keypad and Display Access ............................................................................................................. 18
2.3.1 Local Menu Navigation Keys and LCD Display .............................................................................. 18
2.3.2 Local Display Menus ...................................................................................................................... 18
2.4 WEB Interface Access ................................................................................................................................ 19
2.4.1 Overview ......................................................................................................................................... 19
2.4.3 WEB Interface Menus ..................................................................................................................... 19
2.4.4 Connecting the Controller Locally (via the Ethernet Port) .............................................................. 19
2.4.5 Disabling Proxy Server Settings to Enable a Connection to the Controller over an Intranet
Network (if required) ....................................................................................................................... 20
2.4.6 Logging into the Controller ............................................................................................................. 21
2.5 Common Tasks Performed via the Local Keypad and/or Web Interface ................................................... 22
2.5.1 Backing Up the Configuration ......................................................................................................... 22
2.5.2 Reloading a Backed-Up Configuration ........................................................................................... 22
2.5.3 Reloading the Configuration File Stored in the ACU+ Controller ................................................... 22
2.5.4 Downloading a Configuration or an Application ("All") Package into the ACU+ Controller ............ 23
2.5.5 Rebooting the Controller ................................................................................................................. 24
2.5.6 Changing the Local LCD Display Contrast ..................................................................................... 24
2.5.7 Disabling the Local Keypad Sound ................................................................................................ 24
2.5.8 Changing the Date .......................................................................................................................... 24
2.5.9 Changing the Time ......................................................................................................................... 24
2.5.10 Adding, Deleting, and Modifying Users .......................................................................................... 24
2.5.11 Assigning Severity Level to Alarms ................................................................................................ 24
Table of Contents i
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
2.5.12 Assigning Relays to Alarms ............................................................................................................ 25
2.5.13 Changing the Names of Items Displayed in the LCD and Web-Interface Menus .......................... 25
2.5.14 Viewing Alarms ............................................................................................................................... 25
2.5.15 Clearing Rectifier Lost, Rectifier Communication Fail, Converter Lost, Converter
Communication Fail, and All Converter Comm Fail Alarms ........................................................... 25
2.5.16 Clearing SMTemp Lost and SMTemp Probe Alarms ..................................................................... 25
2.5.17 Clearing Battery Alarms .................................................................................................................. 25
2.5.18 Clearing Logs.................................................................................................................................. 25
2.5.19 Clearing the Maintenance Alarm .................................................................................................... 26
2.5.20 Viewing the ACU+ Controller’s Device Inventory ........................................................................... 26
2.5.21 Updating the ACU+ Controller’s Device Inventory ......................................................................... 26
2.5.22 Programming the Audible Alarm Feature ....................................................................................... 26
2.5.23 Blocking Alarms .............................................................................................................................. 26
2.5.24 Configuring the ACU+ Identification of Rectifiers and Assigning which Input Phase is
Connected to the Rectifiers ............................................................................................................ 27
2.5.25 Configuring the ACU+ Identification of Converters ........................................................................ 28
2.5.26 Viewing/Changing the Float Voltage Setting .................................................................................. 29
2.5.27 Viewing/Changing the Equalize Voltage Setting ............................................................................ 29
2.5.28 Setting Digital Inputs ....................................................................................................................... 29
2.5.29 Setting Temperature Sensors ......................................................................................................... 29
2.5.30 Setting Battery Charge Temperature Compensation ..................................................................... 30
2.5.31 Setting Auto Equalize ..................................................................................................................... 30
2.5.32 Setting Battery Parameters ............................................................................................................ 31
2.5.34 Setting Battery Block and Battery Midpoint Monitoring (if equipped with an EIB Assembly) ......... 31
2.5.35 Setting IP Communications Parameters ........................................................................................ 31
2.5.36 Setting External Shunts (connected to the EIB Assembly) ............................................................ 31
2.5.37 Setting External Shunts (connected to the SM-DU+ Assembly) .................................................... 31
2.5.38 Setting the Load Current Alarm ...................................................................................................... 32
2.5.39 Placing the System in Float or Equalize Charge Mode .................................................................. 32
2.5.40 Manually Forcing Relays ................................................................................................................ 32
2.5.41 Manually Forcing LVDs .................................................................................................................. 32
2.5.42 Using the Relay Test Feature ......................................................................................................... 33
2.5.43 Spec. No. 588820300 Battery Rack System (Lithium Ion Battery Configuration) .......................... 34
2.6 Available Alarms ......................................................................................................................................... 35
2.7 Power Split Feature .................................................................................................................................... 73
2.7.1 Overview ......................................................................................................................................... 73
2.7.2 How Power Split Works .................................................................................................................. 73
2.7.3 Operating Modes ............................................................................................................................ 74
2.7.4 Requirements and Conditions ........................................................................................................ 74
2.7.5 Paralleling the Existing and ACU+ Power Systems ....................................................................... 75
2.7.6 Programming the ACU+ Power Split Feature ................................................................................ 77
2.7.7 Verifying the Operation of the Power Split Feature ........................................................................ 79
Chapter 3. Local Display Menus .......................................................................................... 80
3.1 Overview..................................................................................................................................................... 80
ii Table of Contents
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
3.2 Menus ......................................................................................................................................................... 80
3.2.1 Adjustment Range Restrictions ...................................................................................................... 81
3.3 Description of Local Display (and Web Interface) Menus Line Items ........................................................ 92
3.3.1 Settings Menu ................................................................................................................................. 92
3.3.2 ECO Mode (Energy Optimization) Menu ...................................................................................... 106
3.3.3 Manual Menu ................................................................................................................................ 106
3.3.4 Quick Setting Menu ...................................................................................................................... 109
Chapter 4. WEB Interface Menus ....................................................................................... 113
4.1 Overview................................................................................................................................................... 113
4.2 Homepage ................................................................................................................................................ 113
4.3 Menu Navigation Window......................................................................................................................... 115
4.3.1 Alarms ........................................................................................................................................... 116
4.4 Device Information Menu ......................................................................................................................... 118
4.4.1 Rectifier Group.............................................................................................................................. 118
4.4.2 Battery Group (except Li-Ion Battery Configuration) .................................................................... 123
4.4.3 Battery Group (Li-Ion Battery Configuration) ................................................................................ 128
4.5 Quick Settings Menu ................................................................................................................................ 130
4.6 Query Menu .............................................................................................................................................. 131
4.6.1 Alarm History Log Sub-Menu ....................................................................................................... 131
4.6.2 Data History Log Sub-Menu ......................................................................................................... 132
4.6.3 Control/System/Diesel Log Sub-Menu ......................................................................................... 133
4.6.4 Battery Test Log Sub-Menu .......................................................................................................... 134
4.7 Maintenance Menu ................................................................................................................................... 135
4.7.1 Network Configuration Sub-Menu ................................................................................................ 135
4.7.2 NMS (Network Management System) Configuration Sub-Menu .................................................. 136
4.7.3 HLMS (High Level Management System) Configuration Sub-Menu ............................................ 137
4.7.4 Edit PowerSplit Sub-Menu ............................................................................................................ 138
4.7.5 User Information Settings Sub-Menu ........................................................................................... 139
4.7.6 Clear Data Sub-Menu ................................................................................................................... 141
4.7.7 Restore Factory Defaults Sub-Menu ............................................................................................ 142
4.7.8 Download Sub-Menu .................................................................................................................... 143
4.7.9 Retrieve ‘SettingParam.run’ File Sub-Menu ................................................................................. 145
4.7.10 Time Sync Sub-Menu ................................................................................................................... 146
4.7.11 System Inventory Sub-Menu ........................................................................................................ 147
4.8 Configuration Menu .................................................................................................................................. 148
4.8.1 Auto Configuration Sub-Menu ...................................................................................................... 148
4.8.2 Site Information Modification Sub-Menu ...................................................................................... 149
4.8.3 Equipment Information Modification Sub-Menu ........................................................................... 150
4.8.4 Signal Information Modification Sub-Menu ................................................................................... 151
4.8.5 Alarm Suppressing Sub-Menu...................................................................................................... 153
4.8.6 PLC Sub-Menu ............................................................................................................................. 155
4.8.7 Alarm Relay Sub-Menu ................................................................................................................ 158
Table of Contents iii
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
Chapter 5. Accessing the Controller via a Network Management System (NMS) ......... 159
5.1 General ..................................................................................................................................................... 159
5.2 NMS Supported by SNMP Agent ............................................................................................................. 159
5.3 MIB Installation ......................................................................................................................................... 159
5.3.1 Installation ..................................................................................................................................... 159
5.3.2 Contents of the Controller’s MIB................................................................................................... 159
5.4 Accessing the Controller through an NMS ............................................................................................... 163
5.4.1 Apply Administrative Authority ...................................................................................................... 163
Chapter 6. Replacement Procedures ................................................................................ 164
6.1 ACU+ Controller Replacement ................................................................................................................. 164
Chapter 7. Specifications ................................................................................................... 166
Revision Record ................................................................................................................... 168
iv Table of Contents
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)

CHAPTER 1. INTRODUCTION

1.1 Preface

These instructions describe the complete functionality of the ACU+ Controller. Some functionality is dependent on hardware connected to the ACU+ Controller. Your system may not utilize all the functionality described.
Refer also to the ACU+ Configuration Drawing (C-drawing) furnished with your system for a list of factory default settings.

1.2 Overview

The ACU+ Controller performs the following functions.
Rectifier Control, including an Energy Optimization Mode Converter Control System Components Monitoring and System Alarms Generation
(including recording alarms in logs) Operating Data Acquisition and Data Logs Battery Management Intelligent Power Matching (Energy Optimization Mode) Power Split Feature Diesel Management Feature PLC (Programmable Logic Controller) Function Supervisory Module (SM Modules) Monitoring Hybrid Control Function Maximum Current Limit Function
The ACU+ controls the system automatically via configured parameters. A User interfaces with the ACU+ Controller locally using the local keypad and LCD display or
locally/remotely using the WEB Interface. The ACU+ Controller can also be accessed via SNMP (v1 and v2).
Chapter 1. Introduction 1
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
Figure 1 illustrates the various methods to interface with the ACU+ Controller remotely.
Figure 1
ACU+ Remote Communications

1.3 Function Descriptions

1.3.1 Rectifier Control

Rectifiers are automatically controlled by the ACU+ Controller. The ACU+ Controller provides an Energy Optimization Mode function. Energy Optimization permits an installation to only operate rectifiers as needed to maintain the load and keep batteries in a fully charged condition. As load increases, Energy Optimization turns on additional rectifiers as needed to maintain the load. As load decreases, Energy Optimization places rectifiers in standby to conserve energy usage. Rectifiers which are always operating to maintain any load requirements are cycled through the group of rectifiers controlled by this feature to provide uniform operating times for each rectifier.

1.3.2 Converter Control

Converters are automatically controlled by the ACU+ Controller.
2 Chapter 1. Introduction
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Alarm
Severity Level
ACU+ Red
Alarm Indicator
ACU+ Yellow
Alarm Indicator
ACU+
Audible Alarm
Critical Alarm (CA)
ON
OFF
ON
Major Alarm (MJ)
ON
OFF
ON
Minor Alarm (MN)
OFF
ON
OFF
No Alarm
OFF
OFF
OFF
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)

1.3.3 System Components Monitoring and System Alarms Generation

The ACU+ Controller monitors the components comprising the system (such as the rectifiers, converters, and supervisory modules) and generates alarms if a fault condition occurs. The ACU+ Controller also maintains an alarm history log.
The available system alarms are programmed with an Alarm Severity Level. Each Alarm Severity Level has different visual/audible alarm attributes. Available Alarm Severity Levels and their attributes are listed in Table 1.
Table 1
Alarm Severity Levels
The alarm indicator turns OFF if the fault(s) that triggered the alarm clears. The audible alarm can be silenced by pressing any key on the ACU+ Controller local interface pad.
The audible alarm is also silenced if the fault(s) that triggered the alarm clears. An audible alarm cutoff feature can be programmed that silences the audible alarm after a pre-set
programmable time period. The audible alarm can also be disabled.
The available system alarms can also be mapped to alarm relays (located on ACU+ interface boards) that can be wired to external alarm circuits.

1.3.4 Operating Data Acquisition and Data Logs

The ACU+ Controller acquires and analyses real time data from the system’s components such as the rectifiers, converters, and supervisory modules.
The ACU+ Controller uses this data to process alarms and also records data in logs. The logs are viewed using the WEB Interface and consists of...
Alarm History Log: records 600 latest alarms. Data History Log: records 60000 latest history data. Control Log: records 500 latest control events. System Log: records 3000 latest system events. Diesel Test Log: records 500 latest diesel test results. Battery Test Log: up to twelve (12) battery discharge tests can be performed and recorded per year.
Note: Once maximum number of log entries is reached, new entries overwrite oldest entries.
Logs can be saved in the text (.txt) format.
Chapter 1. Introduction 3
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)

1.3.5 Battery Management

General Battery Management
The ACU+ Controller provides the following battery management functions (except Lithium Ion Battery Configuration).
Battery Charge Temperature Compensation Battery Equalize Charge Battery Charge Current Limit High and Low Battery Temperature Alarms Battery Thermal Runaway Management (BTRM) Feature
(Reduces Voltage during a High Battery Temperature Condition) Battery Discharge Tests Battery Test Logs (maximum twelve [12] logs, maximum eighteen [18] battery strings per log) Battery LVD (Low Voltage Disconnect) Battery Capacity Prediction Battery Block and Battery Midpoint Monitoring Enhanced Battery Monitoring with SM-BRC Thermal Runaway Detection/Management
Spec. No. 588820300 Battery Rack System (Lithium Ion Battery Configuration)
When the ACU+ is equipped with the Lithium Ion Battery Configuration for use with Spec. No. 588820300 NetSure Battery Rack System, the battery management functions are as follows.
The configuration only provides the battery float charge voltage (equalize charging is not applicable). The only adjustable battery setting (besides the float voltage level) is the ABCL (Active Battery
Charge Current Limit) Point. Active Battery Charge Current Limit (ABCL): This feature controls the amount of charge current
supplied to the lithium-ion batteries installed in the power plant to prevent failure of the batteries. Battery status and alarms sent by the batteries to the ACU+ are displayed in the ACU+ interfaces. Refer also to the instructions provided by the battery manufacturer for battery management functions
built into the battery itself.
NOTE THAT THE FOLLOWING DESCRIPTIONS ARE FOR THE GENERAL BATTERY MANAGEMENT FUNCTIONS AND DO NOT APPLY TO THE LITHIUM ION BATTERY CONFIGURATION.
4 Chapter 1. Introduction
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
TempCompCoeff setting (mV/°C).
nom
T
nom
T
V
nom
V
high
V
low
Upper voltage level where temperature compensation clamps the voltage. Limitedto the TEMP COMP MAX V setting.
Nominal voltage (voltage at nominal temperature).
Lower voltage level where temperature compensation clamps the voltage. Limitedto the TEMP COMP MIN V setting.
Nominal temperature (no temperature compensation is done at this temperature). This is the Temp Comp setting.
1V Max (24V System) 2V Max (48V System)
1V Max (24V System) 2V Max (48V System)
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Battery Charge Temperature Compensation
The ACU+ Controller can be programmed to automatically increase or decrease system output voltage to maintain battery float current as battery temperature decreases or increases, respectively. Battery life can be extended when an optimum charge voltage to the battery with respect to temperature is maintained. Temperature is monitored by a sensor mounted on the battery. See your power system documentation for temperature sensor information. You can also set High2, High1, and Low compensation temperature alarms.
Functional Description (See Figure 2): Battery charge temperature compensation adds a correction term, related to the temperature of the batteries, to the nominal value of the system voltage. The degree of regulation (TempComp Coeff), expressed in mV/°C/battery string, can be set per battery manufacturer recommendations.
To protect batteries and voltage-sensitive loads, compensation is automatically limited to a maximum of two volts (48V systems) or one volt (24 volt systems) above or below the nominal output level (float setting).
Temperature compensation will also clamp if the voltage reaches either the TEMP COMP MAX V setting or the TEMP COMP MIN V setting. This feature can also be disabled.
Temperature compensation is automatically disabled if communication between the Controller and all rectifiers is lost, a DC over or under voltage alarm activates, a low voltage disconnection occurs, manual mode is entered, or the system enters the boost or test modes.
Figure 2
Temperature Compensated Voltage Control
Chapter 1. Introduction 5
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
Battery Equalize Charge and Battery Charge Current Limit
The ACU+ Controller can increase system output voltage for equalizing the charge on all battery cells of a conventional flooded cell battery, or for recharging the battery following a commercial power failure.
The charging function can be initiated cyclically (scheduled), automatically, or manually. Refer to the battery manufacturer's instructions for equalize charging instructions.
Functional Description (See Figure 3):
Start of Charging: When the battery charge current exceeds a preset value for 3 minutes or if the
calculated battery capacity has decreased to a preset value (after a commercial AC failure, for
example), the charging function of the ACU+ is activated. A charging signal is sent from the ACU+ to
the rectifiers to increase the voltage up to the battery charging level V
equalize
Battery Current Limitation: After a commercial AC failure or when some battery cells are
permanently damaged, the current to the batteries can be quite extensive. To avoid overheating or
further damages to the battery, the ACU+ limits the battery current to a preset level by limiting the
charging voltage of the rectifiers. Should the battery current still exceed a higher preset value, an
alarm is issued. End of Charging: When the charging current drops below a preset value, a defined prolonged
charging time is started before the charging is stopped and the voltage of the rectifiers return to the
float charging level (V
). For safety, there is a equalize charging limit time that stops the charging
nom
after a preset time.
Figure 3
Voltage Characteristics on Commercial AC Failure and Automatic Equalize Charging
High and Low Battery Temperature Alarms
The ACU+ Controller can monitor battery temperature via a temperature sensor mounted on a battery cell. Values for high battery temperature and low battery temperature alarms can then be programmed into the ACU+ Controller.
Battery Thermal Runaway Management (BTRM) Feature
You can designate a temperature sensor as the BTRM sensor. The BTRM sensor has High2 and High1 BTRM temperature alarm limits. If battery temperature exceeds the “BTRM Temp High2” setting, system voltage is lowered to the BTRM voltage setting. This feature can also be disabled.
6 Chapter 1. Introduction
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Battery Discharge Test and Battery Test Logs
The ACU+ Controller can perform battery discharge tests to check the condition of the battery. There are (3) types of battery discharge tests.
Short Time Test Time Test Stable Current Test
A User can manually start a battery discharge test or program the ACU+ Controller to automatically start battery discharge tests at scheduled intervals (cyclic battery tests). During a battery discharge test, the ACU+ Controller controls the rectifiers output to place the entire load or partial load on the batteries. The ACU+ Controller monitors the discharge of the battery and saves the results in a battery test log.
Functional Description: For manual battery discharge tests as well as for cyclic battery discharge tests, the following parameters must be set: End Voltage, Test Time, and Battery Capacity Discharge Limit. See Figure 4.
Battery Discharge Test Sequence:
In time test modes, the output voltage of the rectifiers is reduced so that only the batteries power the
load. If the batteries fail, the rectifiers power the load. In stable current test mode, the output voltage of the rectifiers is reduced so that the batteries supply
the preset test current to the load. The battery test continues until one of the following occurs:
The preset test time, see Figure 4, expires. The battery has passed the test. The battery voltage drops below the preset end voltage level (V
) (Figure 4). The battery has not
end
passed the test and the test is interrupted. A battery test alarm is activated.
The battery capacity drops below the preset test end battery capacity. The battery has not passed
the test and the test is interrupted. A battery test alarm is activated.
After the battery discharge test, the output voltage of the rectifiers increase so that the rectifiers supply
the system and charge the batteries.
Figure 4
Battery Test Diagram
Chapter 1. Introduction 7
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
Battery LVD (Low Voltage Disconnect)
To prevent serious damage to the batteries during a commercial AC power failure, the batteries can be disconnected by voltage or time control.
The batteries are reconnected automatically when commercial AC power is restored and a predetermined DC voltage level is reached.
Voltage Controlled Disconnection: When the set voltage level is reached, the batteries are
disconnected. Time Controlled Disconnection: When the set time has elapsed, the batteries are disconnected.
Battery Capacity Prediction
The ACU+ can predict battery capacity.
Battery Block and Battery Midpoint Monitoring
The ACU+ can monitor battery blocks (12V blocks) or midpoint battery voltage of battery strings connected to the EIB assembly. An alarm is issued when either battery block voltage or battery midpoint voltage is abnormal.
Enhanced Battery Monitoring with SM-BRC
When connected to an SM-BRC, the ACU+ provides enhanced battery monitoring.
Thermal Runaway Detection and Management Functional Description: The system uses several control mechanisms to avoid thermal runaway.
First: During a short high rate discharge, the batteries will normally get hot. The ACU+ takes this into consideration. After completion of the discharge duty, the batteries are recharged with a limited current to avoid heating the batteries any further.
Second: The temperature of the batteries can be monitored, and the ACU+ sets the charge voltage appropriately, as previously described under Battery Charge Temperature Compensation.
Third: In addition to battery temperature compensation, if battery temperature rises above a set temperature limit, the system stops battery charging completely by lowering the output voltage to the “BTRM Voltage” setting. This allows the batteries to cool down. The system also provides alarm notification of this occurrence. Power supplied to customer equipment is not interrupted.
Fourth: The battery LVD circuits can be programmed to open (disconnect) if a high temperature event occurs (HTD – High Temperature Disconnect). The contactor(s) open when battery temperature rises above a programmable value and close again when battery temperature falls below another programmable value.

1.3.6 Intelligent Power Matching (Energy Optimization Mode)

With Energy Optimization Mode (ECO):
The Controller monitors load current versus system capacity. The Controller commands some rectifiers to standby in rotation.
Refer to 1.3.1 Rectifier Controlfor further description.
8 Chapter 1. Introduction
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)

1.3.7 Power Split Feature

The Power Split feature allows you to connect the power system controlled via the ACU+ to an existing DC power system instead of extending or completely replacing the existing DC power system.
The power system controlled via the ACU+ functions as a slave system to share load (split output) with the existing system (master system) that requires expansion. The ACU+ does not require communication with the master system’s Controller.
The Power Split feature provides for the sharing of total load in a controlled manner between the paralleled power systems.
When Power Split is programmed, the ACU+ adjusts rectifier output voltage per load demands to ensure proper sharing between the slave and master power systems. See Figure 5.
Figure 5
Power Split Feature

1.3.8 Diesel Management Feature

The Diesel Management feature is available when an SM-AC supervisory module is connected to the ACU+ Controller. The Diesel Management feature consists of a Diesel Test. The Diesel Test can be performed at specific intervals or a User can manually start the Diesel Test. The ACU+ records the test results.
Chapter 1. Introduction 9
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Logical Component
Description
Logic NOT
NOT; Returns the inverted value of the input signal/parameter.
Logic OR
OR; Returns active (true) if any of the two signals/parameters are active (true).
Logic AND
AND; Returns active (true) if both of the two signals/parameters are active (true).
AndOr
XOR; Returns active (true) if one and only one of the two signals/parameters are active (true).
Greater Than (>)
GREATER THAN; Returns active (true) if the analog input signal goes above the set threshold. Returns inactive (false) if the input signal goes below the set threshold minus hysteresis value.
Less Than (<)
LESS THAN; Returns active (true) if the analog input signal goes below the set threshold. Returns inactive (false) if the input signal goes above the set threshold plus hysteresis value.
Delay
DELAY in seconds; Delays the applied signal/parameter with the defined time in seconds before applying it to the output.
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)

1.3.9 PLC (Programmable Logic Controller) Function

The PLC function allows a User to create "control program lines" by combining equipment analog signals, parameters, and alarms in a sequence that controls equipment and/or operates relays.
Control program lines are created using the WEB Interface. See 4.8.6. PLC Sub-Menu. Available logical components are:

1.3.10 Supervisory Module (SM Modules) Monitoring

Various devices (supervisory modules) can be connected to the ACU+ Controller to extend its monitoring capabilities.

1.3.11 Hybrid Control Function

Hybrid Control is designed for use in new installations or as an upgrade of existing sites powered by a diesel generator(s) when grid power is not available. The Hybrid Control is also applicable to sites with highly unreliable or frequently unavailable grid power connection. The primary power source is still considered to be the diesel generator(s).
Note: The Hybrid Control function requires a specific configuration. Hybrid Control menus will not
normally be displayed unless your ACU+ has been configured by Emerson for this function. Contact Emerson for a Hybrid Control configuration.
General
Hybrid Control allows the option of selecting one of the following: Fixed Daily Time based operation or Capacity Discharge based operation.
10 Chapter 1. Introduction
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Fixed Daily Time based operation is intended to be used with a combination of AC powered active cooling (air conditioners) and DC powered cooling (heat exchangers, etc). The cycle period is synchronized to the 24hr day-night cycle. It makes optimum use of the different temperature conditions during the day and the night in order to facilitate Hybrid fuel saving operation.
Capacity Discharge based operation is intended for sites utilizing only DC powered cooling (heat exchangers, etc). The cycle period is determined by User selectable depth of discharge (DOD) of the batteries per cycle and associated recharge time. It provides optimum Hybrid fuel saving operation.
Operation from Grid Power is performed with both Fixed Daily Time and Capacity Discharge modes of operation. Grid power is always given priority when available.
As the two types of control are specific to the hardware configuration of the site, the Fixed Daily Time or Capacity Discharge is a User selectable option on installation.
Hybrid Operation Generator Control: Potential free relay contact output from the ACU+ interface board controls the start
and stop of the diesel generator. The signal is generated by the ACU+ Controller and operates according to the Hybrid software mode of operation. The control logic is as follows:
Energized output relay – Generator OFF. De-energized output relay – Generator ON.
This is a fail-safe logic to ensure generator operation in all cases where power or control to the relay is lost.
Further to that, the type of signal to the generator can be selected as N/O (Normally Open) or N/C (Normally Closed) by selecting the relevant output pins of the control relay.
Number of Generator Control Outputs: The ACU+ Hybrid software can control one or two generators. Each generator control is designated as DG1 or DG2 output. A User selectable menu will allow selecting DG1, DG2, or DG1 and DG2. When both are selected they will be alternatively used (two generator operation).
Diesel Fail Alarm: A diesel fail alarm will be generated if the Diesel Generator ON signal fails to bring the generator to operation and provide the system with AC power. Alarm will be triggered after 60 seconds (default value, settable) from ON signal. If two generator operations are selected simultaneously with the alarm, the second Diesel Generator ON signal will be activated.
Battery Fuse Trip Alarm: In the event of a Battery Fuse trip condition an alarm will be generated. Under Voltage Alarms:
Under Voltage Alarm 1: An Under Voltage Alarm 1 is set. If voltage decreases below this setting, an
alarm is raised. Under Voltage Alarm 2: An Under Voltage Alarm 2 is set. If voltage decreases below this setting, the
Diesel Generator is started and an alarm is raised.
LVD 1: Normal loads are disconnected. LVD 2: Priority loads are disconnected. Charge Voltage:
Refer to Figure 6.
Chapter 1. Introduction 11
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
Figure 6
Charge Voltage
Equalize Charge: The battery will be recharged at equalize voltage. This is the voltage set in the initial phase of battery recharge. See Figure 6.
As the voltage limit is reached, the charge current is gradually reduced – effect known as current tail. When the current tail falls below a set of threshold levels, additional equalize charge time is added.
The equalize charge current tail threshold is settable from 0.01 to 0.05. Default setting is 0.02 (2A per 100Ah). The additional equalize charge time is settable from 0 hours to 7 hours (settable in minutes from 0 to 720), default setting is 4 hours. The duration of the equalize charge is determined as the time from the start of the recharge to the end of the additional time. (Maximum charge time, determined from the time charge starts, is settable in the range of 5-24h.)
The end of recharge is determined by a three (3) step approach:
Step1 - calculated battery capacity exceeds 90%. Calculation is performed by measurement of battery current and time, in Ah.
Step 2 - charge current tail threshold is reached.
Step 3 - additional charge time is added. Float Charge: Default float voltage is 54.0V at 20°C with a temperature compensation of -72mV per °C. If battery temperature exceeds 38°C, the charge voltage is reduced to 51V to reduce gassing and prevent
thermal runaway. The same is applicable as well for equalizing charge. Equalizing Charge: As the cyclic use does not ensure complete battery recharge after every cycle, an
equalizing charge cycle is added. The equalizing cycle will occur up to four times a month, settable for every 7 to 60 days intervals. Start date and time is settable. Equalizing charge time is 20 hours independent of discharge time setting. Equalizing charge is performed at equalize voltage until end of additional equalize time and thereafter at float voltage for the remaining time. Also see Figure 6.
Equalize charge independently settable 0-720 min (already set in equalize charge).
12 Chapter 1. Introduction
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Early Termination of the Discharge Periods During discharge, over temperature and under voltage conditions will interrupt the discharge and
change the operation to charge – Diesel Generator ON. Over Temperature: The diesel generator will start and run for a period before it is stopped again. The run
time is User selectable in the range 30 to 120 minutes, default setting is 60 minutes. Temperature is referenced to cabinet/shelter ambient temperature sensor connected to the Controller, not battery temperature. Over temperature start can be disabled completely from User settings menu.
Under Voltage: The under voltage start is triggered by under voltage alarm 2 voltage settings. The diesel generator will start and run until the normal recharge cycle is due to finish depending on
selected mode of operation. Example for Fixed Daily Time: If the normal recharge cycle is from 7am until 7pm and under voltage has
started the diesel generator at 5:30am, the effective recharge will be from 5:30am until 7pm.
Example for Capacity Discharge: If this mode is selected, the recharge will terminate. Operation with Grid Power
Grid power is always prioritized when available. If grid power becomes available during battery discharge, the discharge cycle is terminated and recharge cycle is initiated. If grid power becomes available during diesel generator operation, the diesel generator is switched OFF and operations continue on grid power.
Battery Recharge with Grid Power: Battery recharge with grid power can start from the beginning (case of grid power becoming available during battery discharge) or can continue over from diesel generator recharge depending on the timing. In both cases, the recharge process will follow the recharge profile shown in Figure 6. If battery becomes fully recharged and grid power is still present, the operations will continue to be powered from grid and no battery discharge will be initiated for the duration of grid availability. In this case battery voltage will revert back to Float voltage.
Battery Discharge after Grid Failure: At the point of grid power failure, the battery capacity is unknown as these events occur in random manner. For the purpose of maximizing the use of grid power and in anticipation of grid power becoming available again, the Hybrid operation will continue with battery discharge cycle. Discharge will continue until:
The preset discharge time elapses (Fixed Daily Time). The preset DOD is reached (Capacity Discharge).
In both cases, the discharge can be terminated earlier as described in Early Termination of the Discharge Periods.
Relay Assignment – when in Hybrid Mode Relay 1: Generator Alarm
No Generator Voltage Alarm. No AC supply, 60 sec delay.
Relay 2: Battery Alarms
Logic alarm generated from: under voltage 1, under voltage 2, LVD1, LVD2, battery high temp,
battery very high temp, overvoltage 1, overvoltage 2, battery temp sensor fail, battery fuse alarms, and high load alarm.
Relay 3: Rectifier Alarms
Logic alarm generated from: multiple rectifier fail, rectifier fail, rectifier fan failure, rectifier HVSD,
rectifier AC failure, and rectifier not responding.
Chapter 1. Introduction 13
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
Relay 4: System Alarms
Logic alarm generated from: load fuse alarms, high ambient temperature, ambient temp sensor fail,
smoke detected, and water detection.
Relay 5: Generator Run At High Temp
Output to intelligent cooling devices linked to AC supply (DG run).
Relay 6: Intruder Alarm
Alarm triggered by dry contact door/motion sensor.
Relay 7: Diesel 1 in Operation
Output to DG1 on site. DG is set on for the duration of the signal.
Relay 8: Diesel 2 in Operation
Output to DG2 on site. DG is set on for the duration of the signal.
Fixed Daily
In this mode of operation the total duration of a complete cycle is 24hr. Such duration is necessary as the operation is synchronized with day-night temperature pattern. When an extended recharge cycle is required, the termination of it will still follow the 24hr schedule.
Cycle Duration: A complete cycle consists of discharge and charge periods to the combined total of 24hrs. The discharge period starts at 7pm. It is then followed by recharge period (Diesel Generator ON) for the remaining of the 24hrs. The discharge time is User selectable in the range 1hrs to 22hrs, default setting is 12hrs.
Discharge: The discharge start time and duration are settable. Discharge period starts at 7pm. The discharge time is User selectable in the range 1hrs to 22hrs, default setting is 12hrs.
Recharge: Recharge period (Diesel Generator ON) follows after discharge for the remaining of the 24hrs. Recharge is performed at equalize voltage until added equalize time elapses and at float voltage for the remaining charge time.
High Load Alarm: In order to identify conditions where the load requirements are exceeding the dimensioning of the Hybrid site, an alarm must be generated. The alarm will be triggered upon exceeding the maximum capacity per discharge cycle. The threshold value will be set as default to 40% of battery capacity. It will require capacity measurement per cycle. The alarm will be set once the high load threshold value is reached and is reset at the beginning of the next discharge period. This alarm will also allow distinguishing the root cause of under voltage conditions: is it high load demand or is it a battery ageing and associated loss of capacity issue or insufficient charge capacity.
Capacity Discharge
The cycle period is determined by User selectable capacity discharge of the batteries and associated recharge times. After that the cycle repeats itself. It does not follow a 24hr pattern.
Capacity Discharge and Recharge: The battery discharge period is determined by the percentage of the nominal battery capacity [Ah] that will be discharged per cycle.
The depth of discharge [DOD] per cycle is User selectable in the range 20% to 80%. Default setting is 60%. The value is set as battery capacity at the end of each discharge period. Therefore, if a 60% discharge is chosen, the discharge value is set to 40%.
The time to recharge to full battery capacity depends on battery capacity at the start of the charge cycle and available recharge current.
When the additional charge time has been reached; the generator will be stopped, the recharge cycle will end, and discharge cycle will be initiated.
14 Chapter 1. Introduction
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
For practical purposes, the battery capacity at the end of every recharge period is set to 100% as long as Step1, Step 2, and Step 3 have elapsed.
If end of charge is not reached within the set maximum hrs, the recharge will be terminated anyway and discharge cycle will be initiated.

1.3.12 Maximum Current Limit Function

The current available from the rectifiers can be programmed (in AMPS) from 10% to 121% of combined rectifier capacity. The factory setting is 121% unless otherwise specified. The current available from the converters can be programmed (in AMPS) from 50% to 116% of combined converter capacity. The factory setting is 116% unless otherwise specified. Refer to the ACU+ Configuration Drawing (C-drawing) supplied with your system documentation for your system’s settings.
If a rectifier or converter is added, the respective current limit point will automatically increase by the percentage each existing rectifier or converter was set to provide prior to the addition.
If a rectifier or converter is removed from the system (and the Rect Comm Fail or Conv Comm Fail alarm is reset), the respective current limit point will remain unchanged unless the capacity of the remaining rectifiers or converters is not sufficient to maintain the present current limit point. If that happens, the current limit point will automatically increase to the maximum (121% of the remaining rectifiers or 116% of the remaining converters).
Chapter 1. Introduction 15
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Indicator
Normal State
Fault State
Fault Cause
Status
(Green)
On
Off
No input power to the ACU+ Controller.
Minor Alarm
(Yellow)
Off
On
The system has one or more active Minor alarms. Alarm conditions are programmable.
Critical/Major
Alarm (Red)
Off
On
The system has one or more active Critical or Major alarms. Alarm conditions are programmable.
ESC
ENT
USB
Port
10/100M Ethernet Port (RJ-45)
M820B
Critical or Major Alarm Indicator (Red)
MinorAlarm Indicator (Yellow)
Status Indicator (Green)
Menu
Navigation
Keys
Status
Indicator
(Green)
MinorAlarm
Indicator (Yellow)
Critical or Major Alarm Indicator (Red)
ESC ENT
Menu Navigation Keys
USB
Port
10/100M Ethernet
Port (RJ-45)
M820D
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)

CHAPTER 2. OPERATION

2.1 Local Indicators

Location and Identification: Refer to Figure 7. Description: There are three (3) indicators located on the ACU+ Controller’s front panel. Refer to Table 2
for the function of the indicators.
16 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Local Indicators and Menu Navigation Keys Locations
Figure 7
Table 2
Local Indicators
User Instructions UM1M820BNA
Access Level
(Authority Level)
Default User Name
and Password
Authority
Level A (Browser)
none set
The User can only read (browse) information in the menus.
Level B (Operator)
none set
The User has access to the system "Control" menus.
Level C (Engineer)
none set
The User has access to the system "Setting" menus and can download the configuration file.
Level D (Administrator)
Admin, 1
The User has full access to all menus; including update the OS application and modifying, adding, and deleting Users.
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)

2.2 Passwords and Access Levels

Users (for local and Web access to the ACU+ Controller) are set via the Web Interface.
Note that anyone can browse the ACU+ via the local keypad and display. A password is required to change settings. Web access always requires a User Name and password to be entered to gain access.
Users are configured with a User Name, password, and access level.
User Name: Maximum 13 Characters (0-9, a-z, A-Z, _ ). Password: Maximum 13 Characters (0-9, a-z, A-Z, _ ).
Once a password is entered, it remains in effect for a preset time period to allow navigating between menus without re-entering the password.
Access Level: Refer to the following table. A User has access to his/her level menus, plus all menus of the lesser access levels.
Chapter 2. Operation 17
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Key Symbol
Key Name
Function
ESC
Escape
Press this key to go back to a previous menu or to cancel setting a parameter.
Press ESC and ENT together to reset the ACU+ Controller, then press ENT to accept or ESC to cancel.
ENT
Enter
Press this key to go forward to the next menu, to select a parameter to edit, or to validate a parameter setting change.
Up
Press or to scroll through the menus or to change the value of a parameter.
--
Down
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)

2.3 Local Keypad and Display Access

2.3.1 Local Menu Navigation Keys and LCD Display

Location and Identification: Refer to Figure 7. Description: There are four (4) menu navigation keys and an LCD display located on the ACU+
Controller’s front panel. Refer to Table 3 for the function of the menu navigation keys.
Note: When the LCD is lit, if no button is pushed for 8 minutes, the backlight of the LCD display
extinguishes and the ACU+ Controller returns to the Main Screen. Press any key to re-activate the LCD display.
Press any key to silence an audible alarm.

2.3.2 Local Display Menus

Refer to Chapter 3. Local Display Menus.
Note: A valid password is required to access menus that allow changing any power system parameter.
Navigating the Menus To Select a Sub-Menu:
Press the up or down arrow keys to move the cursor up and down the list of sub-menus in the menu screen (selects the sub-menu), then press ENT to enter the selected sub-menu.
To Enter a Password: If a password screen opens, a password must be entered to allow the User to make adjustments. To enter a password, with the cursor at the User Name field (default is “Admin”), press the down arrow key to move cursor down to the password line. Press ENT. “0” is highlighted. Press the up arrow key once to change
the “0” to”1” (default password is “1”), then press ENT twice. (Note: If you have been assigned a unique User Name and password, follow this procedure to enter these.)
To Change a Parameter:
Press the up or down arrow keys to move the cursor up and down the list of parameters in the menu screen (selects the parameter to change), then press ENT to change the selected parameter. The parameter field highlights. Press the up or down arrow keys to change the parameter value. Press ENT to confirm the change.
Table 3
Local Menu Navigation Keys
18 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)

2.4 WEB Interface Access

Note: The ACU+ supports a 10/100M Ethernet connection.

2.4.1 Overview

Via the WEB Interface, a User (with proper access level) can:
View real-time operating information (rectifiers, converters, AC, DC, Batteries, etc.). View and download information recorded in logs. Send control commands. Set programmable parameters. Download and upload configuration files. Download firmware to the Controller.

2.4.2 Setting IP Communications Parameters

The Controller’s IP parameters (IP, subnet mask, and gateway addresses) must be set to match your
company’s network settings. The default settings for these parameters are shown below.
IP Address: 192.168.1.2 Subnet Mask Address: 255.255.255.0 Gateway Address: 192.168.1.1
Local Menu Navigation: Main Menu / Settings / Communication / enter parameters. WEB Menu Navigation: Maintenance / Network Configuration / enter parameters.

2.4.3 WEB Interface Menus

Refer to Chapter 4. WEB Interface Menus.

2.4.4 Connecting the Controller Locally (via the Ethernet Port)

Before connecting your computer directly to the Controller’s Ethernet Port, record your current network
settings as outlined below, then change these settings to match the communications settings programmed into the Controller.
Procedure
1) Record your computer’s network settings by launching Control Panel in your computer. Navigate through Network Connections  Local Area Connection  Properties  Internet Protocol (TCP/IP)  Properties.
2) Record whether the "Obtain an IP address automatically" or "Use the following IP address" button is selected. If "Use the following IP address" button is selected, also record the following:
IP Address: Subnet Mask: Default Gateway:
3) Record your Controller’s network settings by navigating the Controller’s local display panel to Main Menu  Settings  Communication.
4) Record the following information:
IP Address: Subnet Mask: Default Gateway:
Example: IP Address: 192.168.1.2
Chapter 2. Operation 19
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
Subnet Mask: 255.255.255.0 Default Gateway: 192.168.1.1
5) Change your local computer’s network settings using the information you acquired in Step 4), except that the last part of the IP address needs to be replaced with any different number.
IP Address: Subnet Mask: Default Gateway:
Example: IP Address: 192.168.1.3 Subnet Mask: 255.255.255.0 Default Gateway: 192.168.1.1
6) Select OK. Note that you may have to reboot your local computer for the settings to take effect. Follow any instruction you see on the screen.

2.4.5 Disabling Proxy Server Settings to Enable a Connection to the Controller over an Intranet Network (if required)

Note: This procedure needs to be performed only when the Controller is connected to an Intranet and the
User’s computer is set to access the Intranet through a proxy server. Note that if the Controller is
connected to the Internet and the User’s computer is connected to an Intranet, the User may not
be able to disable the proxy server and access the Controller.
If the Controller’s Ethernet Port is connected to your company’s Intranet Network and your computer is
also connected to the Intranet Network but requires access via a proxy server, you must disable the proxy server settings to access the Controller. Follow the procedure below to disable the proxy server settings.
Procedure
1) Launch “Internet Explorer”.
2) Select Internet Options from the Tools menu. The “Internet Options” window opens. In the “Internet Options” window, select the Connections Tab.
3) Click on the LAN Settings... button. The following window opens. In the LAN Settings window, uncheck the Proxy Server box and click OK.
20 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)

2.4.6 Logging into the Controller

Procedure
1) Internet Explorer, version 5.5 or newer, is required. It is best to view the WEB Interface at 1280 x 1024 resolution. In newer versions of Internet Explorer, you may need to turn Compatibility View On (Tools Menu / Compatibility View).
2) In Internet Explorer, enter the IP address programmed into the Controller and press ENTER. The following WEB Interface window opens. Enter a valid User Name and Password then click LOGIN.
Note: By default, the “User Name” is "admin" and the “Password” is “1”.
3) After entering a valid User Name and Password and clicking LOGIN, the "HOMEPAGE" window opens. Refer to Chapter 4. WEB Interface Menus.
Chapter 2. Operation 21
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)

2.5 Common Tasks Performed via the Local Keypad and/or Web Interface

Refer also to Chapter 3. Local Display Menus and Chapter 4. WEB Interface Menus.

2.5.1 Backing Up the Configuration

A file named SettingParam.run is automatically created/appended by the Controller whenever a User makes changes to any parameter settings via the LCD or WEB interface. This file can be saved to your computer so you can restore any custom settings you may have made.
Prior to changing settings, ensure the current “SettingParam.run” file is backed up. After making changes, create a new backup file. Note that you may change the name of a SettingParam.run file to differentiate it from other files saved. The new name can use alpha and numeric characters preceding the original SettingParam.run name (the end of the new file name must always be “SettingParam.run; for example, an acceptable filename would be seville4SettingParam.run).
Local Menu Navigation: none. WEB Menu Navigation: See also 4.7.9. Retrieve ‘SettingParam.run’ File Sub-Menu.
1) Log onto the Controller using the WEB Interface.
2) Click on “Retrieve SettingParam.run” in the MAINTENANCE MENU.
3) Click on the “Retrieve File” button to save the file named "SettingParam.run" to you hard drive.
Note: Ensure Internet Explorer security settings are set to enable a file to be downloaded.
4) Select where you want the file to be copied to on your computer.

2.5.2 Reloading a Backed-Up Configuration

Reload the ACU+ configuration by restoring the “SettingParam.run” file previously saved. Refer to 2.5.1 Backing Up the Configuration for a procedure to save the “SettingParam.run” file.
Local Menu Navigation: none. WEB Menu Navigation: See also 4.7.8 Download Sub-Menu.
1) Log onto the Controller using the WEB Interface.
2) Click on “Download” in the MAINTENANCE MENU.
3) The "Stop Controller" window opens. Click on the “Stop Controller” button.
4) A Download window opens.
Warning: Never navigate from this web page without first clicking on "Start Controller". If
you do, you will not have web access. A manual system reset is required to restore web access.
5) Click the “Browse….” button and navigate to the folder where the file is located. Select the file and
then click the “Download” button. Click “Start Controller” to restart the Controller with the
downloaded file installed.

2.5.3 Reloading the Configuration File Stored in the ACU+ Controller

Note: When this procedure is performed, the “SettingParam.run” file (see 2.5.1) is deleted.
Local Menu Navigation: Main Menu / Settings / Controller / Reload Config. The only selection for "Reload Config" is Yes. Once Yes is selected and confirmed, the configuration file
stored in the ACU+ Controller is reloaded into memory. All settings WILL BE restored to the factory defaults of the configuration file.
WEB Menu Navigation: Maintenance / Restore Factory Defaults / select “Restore Defaults”.
22 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)

2.5.4 Downloading a Configuration or an Application ("All") Package into the ACU+ Controller

The name of the Configuration or Application "All" Package file must end in .tar or .tar.gz. An Application “All” package file has both the application (software) and configuration files and is usually supplied for an application upgrade.
Local Menu Navigation: A User can copy a Configuration or an Application ("All") Package from your computer to a USB memory device. You can then place the USB memory device into the ACU+ USB port and then download the file into the ACU+ Controller.
To Download a Configuration Locally:
1) Copy the file to a USB memory device. The file must be in the root directory of the USB memory device. The file must be named app_cfg.tar or app_cfg.tar.gz.
2) Connect the USB memory device to the USB port on the front of the Controller.
3) Navigate to Main Menu / Settings / Controller / Download Config.
4) The only selection for "Download Config" is Yes. Once Yes is selected and confirmed, the configuration file located on the memory device located in the Controller’s USB port is loaded into the Controller.
5) After the file is downloaded, remove the memory device from the Controller’s USB port.
6) Return to the Main Screen, then reboot the Controller (press ENT and ESC at the same time).
7) The screen displays "System Is Rebooting" then "App Exited".
8) The Controller enters an initialization routine, which takes a few minutes. The routine is complete and the Controller is operational when normal system voltage is displayed on the screen.
To Download an Application ("All") Package Locally:
1) Copy the file to a USB memory device. The file must be in the root directory of the USB memory device. The file must be named app.tar.gz.
2) Connect the USB memory device to the USB port on the front of the Controller.
3) With the Controller displaying the Main Screen, reboot the Controller (press ENT and ESC at the same time).
4) The screen displays "Acknowledge Info. Reboot System."
5) Press ENT to confirm.
6) The screen displays "System Is Rebooting" "App Exited" then the Emerson Network Power logo appears followed by… Press the key ENT to Download the Application."
7) Press ENT.
8) The screen displays "Please Wait".
9) The Controller enters an initialization routine, which takes a few minutes. The routine is complete and the Controller is operational when normal system voltage is displayed on the screen.
10) Remove the memory device.
WEB Menu Navigation: See also 4.7.8 Download Sub-Menu.
1) Log onto the Controller using the WEB Interface.
2) Click on “Download” in the MAINTENANCE MENU.
Chapter 2. Operation 23
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
3) The "Stop Controller" window opens. Click on the “Stop Controller” button.
4) A Download window opens.
Warning: Never navigate from this web page without first clicking on "Start Controller". If
you do, you will not have web access. A manual system reset is required to restore web access.
5) Click the “Browse….” button and navigate to the folder where the file is located. Select the file and
then click the “Download” button. Click “Start Controller” to restart the Controller with the
downloaded file installed.

2.5.5 Rebooting the Controller

Local Menu Navigation: Press ENT and ESC at the same time to reset the ACU+ Controller. WEB Menu Navigation: Maintenance / Restore Factory Defaults / select “Reboot Controller”.

2.5.6 Changing the Local LCD Display Contrast

Local Menu Navigation: Press ENT and UP ARROW or ENT and DOWN ARROW while in the Main
Screen to change the contrast of the LCD display.
WEB Menu Navigation: none.

2.5.7 Disabling the Local Keypad Sound

Local Menu Navigation: Main Menu / Settings / Controller / Keypad Voice.
To disable the keypad sound, set "Keypad Voice" to "Off".
WEB Menu Navigation: none.

2.5.8 Changing the Date

Local Menu Navigation: Main Menu / Settings / Controller / Date.
After selecting Date (by pressing ENT when the cursor is in the Date field), use  and to select the year then press ENT, next use and to select the month then press ENT, and finally use  and  to select the day then press ENT.
WEB Menu Navigation: Maintenance / Time Sync.

2.5.9 Changing the Time

Local Menu Navigation: Main Menu / Settings / Controller / Time.
After selecting Time (by pressing ENT when the cursor is in the Time field), use and to select the hour then press ENT, next use  and  to select the minute then press ENT, and finally use and to select the second then press ENT.
WEB Menu Navigation: Maintenance / Time Sync.

2.5.10 Adding, Deleting, and Modifying Users

Local Menu Navigation: none. WEB Menu Navigation: Refer to 4.7.5 User Information Settings Sub-Menu.

2.5.11 Assigning Severity Level to Alarms

Local Menu Navigation: Main Menu / Settings / Alarm Setting / Alm Severity. WEB Menu Navigation: Configuration / Signal Information Modification / select entry from “Query Device
Type” list / select “Alarm Signal” from Signal Type” list / select entry from “New Level” list / press “Set”.
24 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)

2.5.12 Assigning Relays to Alarms

Local Menu Navigation: Main Menu / Settings / Alarm Setting / Alarm Relay. WEB Menu Navigation: Configuration / Alarm Relays / select entry from “Standard Equipment” list /
select entry from “New Relay Number” list / press “Modify”.

2.5.13 Changing the Names of Items Displayed in the LCD and Web-Interface Menus

Note: Only relay names and digital input names are recommended to be changed for troubleshooting
purposes.
Local Menu Navigation: none. WEB Menu Navigation: Configuration / Equipment Information Modification.
Configuration / Signal Information Modification.

2.5.14 Viewing Alarms

Local Menu Navigation: Main Menu / Status / Active Alarms. WEB Menu Navigation: Active alarms are listed in the lower right window pane. If the window pane is
collapsed, click the "arrow" icon to expand the alarm list.

2.5.15 Clearing Rectifier Lost, Rectifier Communication Fail, Converter Lost, Converter Communication Fail, and All Converter Comm Fail Alarms

Navigate to the menus to clear the respective alarm as indicated below. Local Menu Navigation: Main Menu / Manual / Rectifier / All Rect Ctrl.
Main Menu / Manual / Converter / All Conv Ctrl. WEB Menu Navigation: Device Information / Rectifier Group / Control Tab.
Device Information / Converter Group / Control Tab.

2.5.16 Clearing SMTemp Lost and SMTemp Probe Alarms

Navigate to the menus to clear the respective alarm as indicated below. Local Menu Navigation: Main Menu / Manual / SMTemp / SMTemp Group.
Main Menu / Manual / SMTemp / SMTemp #. WEB Menu Navigation: Device Information / SM Temp Group / Control Tab.
Device Information / SM Temp Group / SM Temp # / Control Tab.

2.5.17 Clearing Battery Alarms

Navigate to the menus to clear the respective alarm as indicated below.
Local Menu Navigation: Main Menu / Manual / Batt Group. WEB Menu Navigation: Device Information / Battery Group / Control Tab.

2.5.18 Clearing Logs

Local Menu Navigation: Main Menu / Settings / Alarm Setting / Alarm Param / Clr Alm Hist.
The only selection for "Clr Alm Hist" is Yes. Once Yes is selected and confirmed, the alarm history log is cleared.
WEB Menu Navigation: Maintenance / Clear Data.
Select which log to clear (“Alarm History”, “Data History”, “Control Command Log”, “Battery Test Log”,
“System Runtime Log”, or “Diesel Test Log”). Select “Clear”.
Chapter 2. Operation 25
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)

2.5.19 Clearing the Maintenance Alarm

A maintenance time can be set which, once expires, issues a maintenance alarm. When the maintenance alarm is issued, perform the routine maintenance and reset the maintenance timer. To reset the maintenance timer and clear the Maintenance Alarm, clear the Maintenance Run Time.
Local Menu Navigation: Place Controller in Manual Mode, then Main Menu / Manual / Power System / Clr MtncRunTime.
The only selection for "Clr MtncRunTime" is Yes. Once Yes is selected and confirmed, the maintenance timer is reset and the maintenance alarm is cleared.
Place Controller back to Auto mode. WEB Menu Navigation: Quick Settings / “Auto/Manual” Setting / change to Manual.
then Device Information / Power System / select the Control Tab and clear the maintenance timer. then Quick Settings / “Auto/Manual” Setting / change to Auto.

2.5.20 Viewing the ACU+ Controller’s Device Inventory

Local Menu Navigation: Main Menu / Status / Sys Inventory. WEB Menu Navigation: Maintenance / System Inventory.

2.5.21 Updating the ACU+ Controller’s Device Inventory

Local Menu Navigation: Main Menu / Settings / Controller / Auto Config.
The only selection for "Auto Config" is Yes. Once Yes is selected and confirmed, the ACU+ Controller will auto-configure for the devices connected to it.
WEB Menu Navigation: Configuration / Auto Configuration.

2.5.22 Programming the Audible Alarm Feature

Local Menu Navigation: Main Menu / Settings / Alarm Setting / Alarm Param / Alarm Voice. Set "Alarm Voice" to:
On: When a new alarm occurs, the audible alarm sounds. Press any key to silence the audible alarm. Off: Disables the audible alarm. 3 minutes / 10 minutes / 1 hour / 4 hours: When a new alarm occurs, the audible alarm sounds.
The audible alarm automatically silences after the selected time period.
WEB Menu Navigation: none.

2.5.23 Blocking Alarms

Local Menu Navigation: Main Menu / Settings / Alarm Setting / Alarm Param / Block Alarm.
or
Local Menu Navigation: Main Menu / Settings / Power System / General / Alarm Blocked. WEB Menu Navigation: Device Information / Power System / Settings Tab / Outgoing Alarms Blocked. Set to:
Normal: Alarms are processed normally. Blocked: Forces the alarm relays in the "off" state and blocks alarms from changing the relay state.
26 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)

2.5.24 Configuring the ACU+ Identification of Rectifiers and Assigning which Input Phase is Connected to the Rectifiers

When rectifiers are all installed prior to applying power and starting the system, the order in which the ACU+ identifies the rectifiers is by serial number (lowest serial number is Rect 1, next lowest is Rect 2, etc.). If you prefer the ACU+ to identify the rectifiers by position in the system, perform the following procedure.
Upon power up, the ACU+ arbitrarily assigns Phase A, B, or C to each rectifier. This assignment is used to display rectifier AC input phase voltage(s). The User may reassign the phase to each rectifier per your specific installation by following the procedure below.
Local Menu Navigation: Main Menu / Settings / Rectifier / Rect #1 / Rectifier ID and Rect Phase. (repeat for every rectifier) then Main Menu / Manual / Rectifier / All Rect Ctrl / Confirm ID/PH.
WEB Menu Navigation: Device Information / Rectifier Group / Rectifier #1 / Settings Tab / Rectifier ID and Rectifier Phase. (repeat for every rectifier) then Device Information / Rectifier Group / Control Tab / Confirm Rectifier “ID/Phase.
Local Procedure
1) With the Main screen displayed, press ENT to go to the Main Menu. Navigate to and select
Settings” (ENT).
2) If a password screen opens, a password must be entered to allow the User to make adjustments. If a password was previously entered and has not yet timed out, skip this step and proceed to step 3). Otherwise, to enter a password, with the cursor at the User Name field (default is “Admin”), press the down arrow key to move cursor down to the password line. Press ENT. “0” is highlighted. Press the up arrow key once to change the “0” to”1” (default password is “1”), then press ENT twice.
(Note: If you have been assigned a unique User Name and password, follow this procedure to enter these.)
3) With the Settings menu screen displayed, navigate to and select Rectifier” (ENT).
4) Navigate to Rect #” (# is used here to represent the rectifier identification number). Press ENT. The rectifier # menu screen is displayed, and the green LED on one rectifier starts flashing. This is the rectifier currently identified by the ACU+ as rectifier #. (If this is not the rectifier you want, press ESC to return to rectifier menu screen and select a different rectifier.)
5) If you wish to change the Rectifier IDs, navigate to and select “Rectifier ID”. Press ENT. Use the up or down keys to change the ACU+ identification number for the flashing rectifier. Press ENT.
6) If you wish to change the Rectifier Phase Assignment, navigate to and select “Rect Phase”. Press ENT. Use the up or down keys to change the phase connected to the flashing rectifier. Press ENT.
7) Press ESC to return to rectifier menu screen.
8) Navigate to and select the next rectifier.
9) Repeat steps 4) through 8) for each of the remaining rectifiers in the system.
10) When you have finished selecting identification numbers and phases for all rectifiers, repeatedly press ESC to return to the Main Menu.
11) Navigate to and select Manual” (ENT) / “Rectifier” (ENT) / “All Rect Ctrl (ENT).
12) Navigate to “Confirm ID/PH”. Press ENT. Yes highlights.
Chapter 2. Operation 27
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
13) Press ENT to select the operation. Press ENT again to confirm.
Note: Check you numbering to be sure it is correct. If there were conflicts in your numbering, rectifiers
with conflicts will be assigned the next available sequential number.
14) Return to the Main screen by repeatedly pressing ESC (escape).

2.5.25 Configuring the ACU+ Identification of Converters

When converters are all installed prior to applying power and starting the system, the order in which the ACU+ identifies the converters is by serial number (lowest serial number is Conv 1, next lowest is Conv 2, etc.).
If you prefer the ACU+ to identify the converters by position in the system, perform the following procedure.
Local Menu Navigation: Main Menu / Settings / Converter / Conv #1 / Set Conv ID. (repeat for every converter) then Main Menu / Manual / Converter / All Conv Ctrl / Confirm ID.
WEB Menu Navigation: Device Information / Converter Group / Converter #1 / Settings Tab / Set Converter ID. (repeat for every converter) then Device Information / Converter Group / Control Tab / Confirm Converters ID.
Local Procedure
1) With the Main screen displayed, press ENT to go to the Main Menu. Navigate to and select
Settings” (ENT).
2) If a password screen opens, a password must be entered to allow the User to make adjustments. If a password was previously entered and has not yet timed out, skip this step and proceed to step 3). Otherwise, to enter a password, with the cursor at the User Name field (default is “Admin”), press the down arrow key to move cursor down to the password line. Press ENT. “0” is highlighted. Press the up arrow key once to change the “0” to”1” (default password is “1”), then press ENT twice.
(Note: If you have been assigned a unique User Name and password, follow this procedure to enter these.)
3) With the Settings menu screen displayed, navigate to and select Converter” (ENT).
4) Navigate to Conv #” (# is used here to represent the converter identification number). Press ENT. The converter # menu screen is displayed, and the green LED on one converter starts flashing. This is the converter currently identified by the ACU+ as converter #. (If this is not the converter you want, press ESC to return to converter menu screen and select a different converter.)
5) Navigate to and select “Set Conv ID”. Press ENT. Use the up or down keys to change the ACU+ identification number for the flashing converter. Press ENT.
6) Press ESC to return to converter menu screen.
7) Navigate to and select the next converter.
8) Repeat steps 4) through 7) for each of the remaining converters in the system.
9) When you have finished selecting identification numbers for all converters, repeatedly press ESC to return to the Main Menu.
10) Navigate to and select Manual” (ENT) / “Converter” (ENT) / “All Conv Ctrl (ENT).
11) Navigate to “Confirm ID”. Press ENT. Yes highlights.
12) Press ENT to select the operation. Press ENT again to confirm.
28 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Note: Check you numbering to be sure it is correct. If there where conflicts in your numbering,
converters with conflicts will be assigned the next available sequential number.
13) Return to the Main screen by repeatedly pressing ESC (escape).

2.5.26 Viewing/Changing the Float Voltage Setting

Local Menu Navigation: Main Menu / Settings / Battery / Charge / Float Voltage. Local Menu Navigation: Main Menu / Quick Setting / “FLT/EQ” Voltag / Float Voltage. WEB Menu Navigation: Device Information / Battery Group / Settings Tab / Float Charge Voltage. WEB Menu Navigation: Quick Settings / “Float/Equalize” Charge Voltage.

2.5.27 Viewing/Changing the Equalize Voltage Setting

Local Menu Navigation: Main Menu / Settings / Battery / Charge / EQ Voltage. Local Menu Navigation: Main Menu / Quick Setting / “FLT/EQ” Voltag / EQ Voltage. WEB Menu Navigation: Device Information / Battery Group / Settings Tab / Equalize Charge Voltage. WEB Menu Navigation: Quick Settings / “Float/Equalize” Charge Voltage.

2.5.28 Setting Digital Inputs

Local Menu Navigation: Main Menu / Settings / Power System / General / DI[number] Alarm State. WEB Menu Navigation: Device Information / Power System / Settings Tab / DI[number] Alarm State.

2.5.29 Setting Temperature Sensors

Temperature sensors may be connected to the…
Temp1 and Temp2 ports on an IB2 Interface Board, Temp1 and Temp2 ports on an EIB Interface Board, and
Temp1 through Temp8 ports of up to eight (8) SM-Temp modules. Each port (sensor) may be set as None, Battery, or Ambient. A temperature sensor set as an ambient temperature sensor may also be set as the sensor which displays
the ambient temperature on the Web Interface’s Homepage. A temperature sensor set as a battery temperature sensor may also be set as the temperature
compensation sensor (in addition, the temperature compensation sensor is the sensor which displays the battery temperature on the Web Interface’s Homepage).
A temperature sensor set as a battery temperature sensor may also be set as the BTRM (Battery Thermal Runaway Management) sensor (in addition, the BTRM sensor is the sensor which is used for the High Temperature Disconnect [HTD] Feature.)
First, set each temperature sensor in the system to None, Battery, or Ambient.
Local Menu Navigation: Main Menu / Settings / Power System / General / IB2 Temp#. Main Menu / Settings / Power System / General / EIB Temp#. Main Menu / Settings / SMTemp / SMTemp # / T# Assign Equip.
WEB Menu Navigation: Device Information / Power System / Settings Tab / IB2 Temp #. Device Information / Power System / Settings Tab / EIB Temp #. Device Information / SM Temp Group / SM Temp # / Settings Tab / Temperature# Assign Equipment.
Chapter 2. Operation 29
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
Note: Also set High2, High1, and Low temperature alarms for each temperature sensor (from the
Web Interface). Note that you cannot set high and low temperature alarms for individual temperature sensors from the Local Menus. High and low temperature alarm settings for the temperature sensors set as ambient are found in the Device Information / Power System / Settings tab. High and low temperature alarm settings for the probes set as battery are found in the Device Information / Battery Group / Settings tab.
Second, if desired, set a temperature sensor set as an ambient temperature sensor as the sensor
which displays the ambient temperature on the Web Interface’s Homepage. Then set High2, High1, and Low ambient temperature alarms (from the same menu).
Local Menu Navigation: Main Menu / Settings / Power System / Amb Temp Sensor. WEB Menu Navigation: Device Information / Power System / Settings Tab / Ambient Temp Sensor.
Third, if desired, set a temperature sensor set as a battery temperature sensor as the battery
temperature compensation sensor. Then set High2, High1, and Low compensation temperature alarms (from the same menu).
Local Menu Navigation: Main Menu / Settings / Battery / Temp Comp / TempComp Sensor. WEB Menu Navigation: Device Information / Battery Group / Settings Tab / Temp Compensation
Probe Number.
Fourth, if desired, set a temperature sensor set as a battery temperature sensor as the BTRM sensor.
Then set High2 and High1 BTRM temperature alarms (from the same menu). If battery temperature exceeds the “BTRM Temp High2” setting, system voltage is lowered to the BTRM voltage setting (set from the same menu). Note, you must first enable this feature (from the same menu).
Local Menu Navigation: Main Menu / Settings / Battery / Basic / BTRM TempSensor. WEB Menu Navigation: Device Information / Battery Group / Settings Tab / BTRM Temp Sensor.

2.5.30 Setting Battery Charge Temperature Compensation

The following need to be set for the Battery Charge Temperature Compensation feature. See above for selecting the battery temperature compensation temperature sensor; or select maximum,
average, or Average SMBRC.
Local Menu Navigation: Main Menu / Settings / Battery / Temp Comp.
Enter values for the following parameters: Temp CompCenter, Temp Comp Coeff, TempComp Sensor, Comp Temp High2, Comp Temp High1, Comp Temp Low, Temp Comp Max V, Temp Comp Clamp, and Temp Comp Min V (note that you have to enable Temp Comp Clamp to set the Temp Comp Max V and Min V values).
WEB Menu Navigation: Quick Settings / Temp Compensation Setting. Enter values for the following parameters: Temperature Compensation Center, Temp Comp Coefficient (slope), Temp Compensation Probe Number, Comp Temp High2, Comp Temp High1, Comp Temp Low, Temp Comp Voltage Clamp, Temp Comp Max Voltage, and Temp Comp Min Voltage (note that you have to enable Temp Comp Clamp to set the Temp Comp Max V and Min V values).

2.5.31 Setting Auto Equalize

Local Menu Navigation: Main Menu / Settings / Battery / Charge / Auto EQ / once enabled, additional
parameters appear. Local Menu Navigation: Main Menu / Settings / Battery / Charge / Cyc EQ / once enabled, additional
parameters appear. Local Menu Navigation: Main Menu / Quick Setting / “FLT/EQ” Set.
30 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Also set “Maximum EQ Time” in same menu. WEB Menu Navigation: Device Information / Battery Group / Settings Tab / Automatic Equalize.
Once Automatic Equalize is enabled, additional parameters appear. WEB Menu Navigation: Device Information / Battery Group / Settings Tab / Cyclic Equalize.
Once Cyclic Equalize is enabled, additional parameters appear. WEB Menu Navigation: Quick Settings / “Float/Equalize” Settings / once Automatic Equalize and/or
Cyclic Equalize is enabled, additional parameters appear. Also set “Maximum Equalize Charge Time” in same menu.

2.5.32 Setting Battery Parameters

Local Menu Navigation: Main Menu / Settings / Battery / Battery # / enter parameters. WEB Menu Navigation: Device Information / Battery Group / Battery # / select the Settings Tab and enter
parameters.

2.5.33 Setting Battery Capacity Parameters

Local Menu Navigation: Main Menu / Settings / Battery / Battery # / Rated Capacity. WEB Menu Navigation: Device Information / Battery Group / Battery # / select the Settings Tab and enter
the Battery Rating parameter.

2.5.34 Setting Battery Block and Battery Midpoint Monitoring (if equipped with an EIB Assembly)

Local Menu Navigation: Main Menu / Settings / EIB / EIB 1 / enter the following parameters. WEB Menu Navigation: Device Information / EIB Group / EIB 1 / select the Settings Tab and enter the
following parameters.
Parameters
Voltage Type Blk V Diff(12V) or Blk V Diff(Mid) Block In-Use

2.5.35 Setting IP Communications Parameters

Local Menu Navigation: Main Menu / Settings / Communication / enter parameters. WEB Menu Navigation: Maintenance / Network Configuration / enter parameters.

2.5.36 Setting External Shunts (connected to the EIB Assembly)

Local Menu Navigation: Main Menu / Settings / EIB / EIB1 / enter the following parameters. WEB Menu Navigation: Device Information / EIB Group / EIB 1 / select the Settings Tab and enter the
following parameters.
Parameters
Shunt # Current Shunt # Voltage Num Batt Shunts Num Load Shunts

2.5.37 Setting External Shunts (connected to the SM-DU+ Assembly)

Local Menu Navigation: none. WEB Menu Navigation: Device Information / SMDUP Group / SMDUP 1 / select the Settings Tab and
enter the following parameters.
Chapter 2. Operation 31
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
Parameters
Current1 Break Value (A) (Device rating.) Current1 High Current Limit (% of Current# Break Value.) Current1 Very High Current Limit (% of Current# Break Value.) Shunt # Current (Rating of Shunt.) Shunt # Voltage (Rating of Shunt.)

2.5.38 Setting the Load Current Alarm

Local Menu Navigation: Main Menu / Settings / Power System / General / Load Curr Alarm. WEB Menu Navigation: Device Information / Power System / Settings Tab / Load Current Alarm.
Enter a value (in AMPS). If load current exceeds this value, a load current alarm is issued.

2.5.39 Placing the System in Float or Equalize Charge Mode

Local Menu Navigation: Main Menu / Manual / Batt Group / “EQ/FLT Control”. WEB Menu Navigation: Device Information / Battery Group / Control Tab / “Equalize/Float” Charge
Control.

2.5.40 Manually Forcing Relays

See also “2.5.42 Using the Relay Test Feature”. Place Controller in Manual Mode, then... Local Menu Navigation: Main Menu / Manual / Power System / Relay Output [number].
Main Menu / Manual / EIB / EIB1 / Relay Output [number].
Select the other state for an alarm relay (active / not active). After confirming the change, the alarm relay will momentarily toggle to the chosen state. The alarm
relay then reverts back to being controlled by the ACU+.
WEB Menu Navigation: Device Information / Power System / Control Tab. Device Information / EIB Group / EIB1 / Control Tab.
The Control Tab allows you to change the state of an alarm relay.
In the "Set value" box, select the other state for an alarm relay (active / not active). Click on "set". After confirming the change, the alarm relay will momentarily toggle to the chosen state. The alarm
relay then reverts back to being controlled by the ACU+.

2.5.41 Manually Forcing LVDs

Place Controller in Manual Mode, then... Local Menu Navigation: Main Menu / Manual / LVD / LVD Unit.
Select the other state for an LVD (connected/disconnected). After confirming the change, the LVD will momentarily toggle to the chosen state. The LVD then
reverts back to being controlled by the ACU+. WEB Menu Navigation: Device Information / LVD Group / LVD Unit / select the Control Tab. The Control Tab allows you to change the state of an LVD.
In the "Set value" box, select the other state for an LVD (connected/disconnected). Click on "set".
32 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
After confirming the change, the LVD will momentarily toggle to the chosen state. The LVD then
reverts back to being controlled by the ACU+.

2.5.42 Using the Relay Test Feature

Note: The relay test can only be performed when no alarms are present.
Automatic Test
When placed in Relay Automatic Test Mode, all relays on the IB2 board deenergize (when set for Fail Safe), then one-by-one each relay energizes for the time period selected and then deenergizes. If the system is equipped with an EIB board, after the IB2 relays are tested, one-by-one each relay on the EIB board deenergizes for the time period selected and then re-energizes. At the end of the test, all relays are returned to their normal state (if no alarms are present).
Local Menu Navigation: Main Menu / Settings / Power System / General / set the Relay Test Time. then Main Menu / Settings / Power System / General / Relay Test / set to Automatic.
Note: The relay test can be exited at any time by setting the Relay Test to Disabled.
WEB Menu Navigation: Device Information / Power System / Settings Tab / set the Relay Test Time. then Device Information / Power System / Settings Tab / Relay Test / set to Automatic.
Note: The relay test can be exited at any time by setting the Relay Test to Disabled.
Individual Test
When placed in Relay Individual Test Mode, relays can be tested individually. This is the same procedure as “2.5.40 Manually Forcing Relays” except you do not place the Controller in Manual Mode.
Local Menu Navigation: Main Menu / Settings / Power System / General / Relay Test / set to Individual. then Main Menu / Manual / Power System / Relay Output [number] (individually you can set the state of the relays on the IB2 Board). Main Menu / Manual / EIB / EIB1 / Relay Output [number] (individually you can set the state of the relays on the EIB Board).
Select the other state for an alarm relay (active / not active). After confirming the change, the alarm relay will momentarily toggle to the chosen state. The alarm
relay then reverts back to being controlled by the ACU+.
When done, set “Relay Test” to “Disabled”. Note that if there is no User interaction for 10 minutes, the
Relay Test will automatically revert to the “disabled” state. WEB Menu Navigation: Device Information / Power System / Settings Tab / Relay Test /
set to Individual. then Device Information / Power System / Control Tab. (individually you can set the state of the relays on the IB2 Board). Device Information / EIB Group / EIB 1 / Control Tab (individually you can set the state of the relays on the EIB Board).
The Control Tab allows you to change the state of an alarm relay.
In the "Set value" box, select the other state for an alarm relay (active / not active). Click on "set". After confirming the change, the alarm relay will momentarily toggle to the chosen state. The alarm
relay then reverts back to being controlled by the ACU+.
Chapter 2. Operation 33
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
When done, set “Relay Test” to “Disabled”.

2.5.43 Spec. No. 588820300 Battery Rack System (Lithium Ion Battery Configuration)

When the ACU+ is equipped with the Lithium Ion Battery Configuration for use with Spec. No. 588820300 NetSure Battery Rack System, the only required settings for battery functions is the float voltage and ABCL (Active Battery Charge Current Limit) point.
Note: The maximum value that the ABCL point can be adjusted to is 60A, which is below the maximum
current the battery can handle.
The batteries communicate their status and alarms to the ACU+. The ACU+ displays these via the LCD and WEB interfaces.
Batteries are added to the ACU+ inventory as they are detected. If a battery communications cable is removed, a Li-Ion Battery Communication Fail alarm is generated. If the controller resets while a Li-Ion Battery Communication Fail alarm is active, the alarm changes to a Li-Ion Battery Lost alarm. If you clear any of these alarms, that battery is removed from the ACU+ inventory.
34 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
Power System Alarms (Power System)
Supervision Unit Fault (SelfDetect Fail)
Controller self detection test fails.
Replace the Controller.
CAN Communication Failure (CAN Comm Fail)
CAN bus communications failure.
Check communications cables.
Outgoing Alarms Blocked (Alarm Blocked)
Alarm relays are forced in the "off" state and alarms are blocked from changing the relay state.
Verify why Controller setting was changed before changing back.
Maintenance Time Limit Alarm (Mtnc Time Alarm)
Controller issues a maintenance alarm.
Perform routine maintenance and reset maintenance timer.
Config Error (Backup Config)” (Config Error 1)
Configuration error 1.
Reload configuration file.
Config Error (Default Config)”
(Config Error 2)
Configuration error 2.
Imbalance System Current (Imbalance Curr)
Current sharing imbalance.
Check to see why current sharing is imbalanced.
Over Load (Over Load)
Output overload condition.
Check to see why output is overloaded.
SPD (SPD)
Surge protection device needs attention.
Check surge protection device.
EStop/EShutdown (EStop/EShutdown)
System in emergency stop or emergency shutdown mode.
Check to see why the system was placed in this mode.
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)

2.6 Available Alarms

Table 4 lists the alarms that you can scroll through in the Alarm Severity and Alarm Relay submenus. These are also the possible alarms that display in the Active Alarms sub-menu. Table 4 also provides guidelines for alarm correction.
Note: These instructions describe the complete functionality of the ACU+. Some functionality is
dependent on hardware connected to the ACU+. Some alarms listed may not display in your system or may be named differently. Refer to the ACU+ Configuration Drawing (C-drawing) furnished with your system.
Chapter 2. Operation 35
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
System Temp1 Not Used (System T1 Not U)
Temperature sensor port #1 is not used.
(Note: This alarm is not used at this time.)
System Temp2 Not Used (System T2 Not U)
Temperature sensor port #2 is not used.
System Temp3 Not Used (System T3 Not U)
Temperature sensor port #3 is not used.
IB2 Temp1 Not Used (IB2 T1 Not Used)
Temperature sensor port #1 (on IB2 Board) is empty.
--
IB2 Temp2 Not Used (IB2 T2 Not Used)
Temperature sensor port #2 (on IB2 Board) is empty.
EIB Temp1 Not Used (EIB T1 Not Used)
Temperature sensor port #1 (on EIB Board) is empty.
--
EIB Temp2 Not Used (EIB T2 Not Used)
Temperature sensor port #2 (on EIB Board) is empty.
System Temp1 Sensor Fault (System T1 Senso)
Temperature sensor #1 failure.
(Note: This alarm is not used at this time.)
System Temp2 Sensor Fault (System T2 Senso)
Temperature sensor #2 failure.
System Temp3 Sensor Fault (System T3 Senso)
Temperature sensor #3 failure.
IB2 Temp1 Sensor Fault (IB2 T1 Sensor F)
Temperature sensor #1 (connected to IB2 Board) failure.
Replace temperature sensor. IB2 Temp2 Sensor Fault
(IB2 T2 Sensor F)
Temperature sensor #2 (connected to IB2 Board) failure.
EIB Temp1 Sensor Fault (EIB T1 Sensor F)
Temperature sensor #1 (connected to EIB Board) failure.
Replace temperature sensor. EIB Temp2 Sensor Fault
(EIB T2 Sensor F)
Temperature sensor #2 (connected to EIB Board) failure.
DHCP Failure (DHCP Failure)
The DHCP function is enabled, but effective IP address cannot be acquired.
Verify DHCP IP address.
PLC Config Error (PLC Config Err)
PLC configuration error.
Re-enter the PLC logic functions.
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
36 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
485 Communication Failure (485 Comm Fail)
485 communications failure.
--
Minor Summary (MN Summary)
Minor alarm summary (one or more alarms designated as minor is active).
Check additional alarms.
Major Summary (MJ Summary)
Major alarm summary (one or more alarms designated as major is active).
Check additional alarms.
Critical Summary (CR Summary)
Critical alarm summary (one or more alarms designated as critical is active).
Check additional alarms.
Rectifier Group Lost (Rect Group Lost)
A rectifier group cannot be detected by the Controller.
Check communications cables. Check additional alarms.
Over Voltage 1 (Over Voltage 1)
Output voltage is higher than the Over Voltage 1 Alarm threshold.
Check to see why system voltage is high. Check the alarm setting.
Over Voltage 2 (Over Voltage 2)
Output voltage is higher than the Over Voltage 2 Alarm threshold.
Under Voltage 1 (Under Voltage 1)
Output voltage is lower than the Under Voltage 1 Alarm threshold.
Check to see why system voltage is low. If there is a mains failure, check if some load could be switched off in order to prolong the operating time of the plant. If the system load is too high related to rectifier capacity, install additional rectifiers. If the batteries are being recharged, the alarm will cease by itself when battery voltage has increased to the charging level.
Under Voltage 2 (Under Voltage 2)
Output voltage is lower than the Under Voltage 2 Alarm threshold.
Over Voltage 1 (24V) (24V Over Volt1)
Output voltage is higher than the Over Voltage 1 Alarm threshold.
Check to see why system voltage is high. Check the alarm setting.
Over Voltage 2 (24V) (24V Over Volt2)
Output voltage is higher than the Over Voltage 2 Alarm threshold.
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 2. Operation 37
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
Under Voltage 1 (24V) (24V Under Volt1)
Output voltage is lower than the Under Voltage 1 Alarm threshold.
Check to see why system voltage is low. If there is a mains failure, check if some load could be switched off in order to prolong the operating time of the plant. If the system load is too high related to rectifier capacity, install additional rectifiers. If the batteries are being recharged, the alarm will cease by itself when battery voltage has increased to the charging level.
Under Voltage 2 (24V) (24V Under Volt2)
Output voltage is lower than the Under Voltage 2 Alarm threshold.
Diesel Run Over Temp (DG Run OverTemp)
Diesel generator run over temperature alarm.
Check diesel generator.
DG1 is Running (DG1 is Running)
Diesel generator 1 is running.
--
DG2 is Running (DG2 is Running)
Diesel generator 2 is running.
--
Hybrid is High Load (High Load)
Diesel generator high load alarm.
Check load on diesel generator.
DG1 Failure (DG1 Failure)
Diesel generator 1 has failed.
Check diesel generator.
DG2 Failure (DG2 Failure)
Diesel generator 2 has failed.
Check diesel generator.
Grid is on (Grid is on)
AC is on grid.
--
Ambient Temp High 1 (Amb Temp High1)
High diesel generator ambient temperature alarm1.
Check why temperature is high or low.
Ambient Temp Low (Amb Temp Low)
Low diesel generator ambient temperature alarm.
Ambient Temp High 2 (Amb Temp High2)
High diesel generator ambient temperature alarm2.
Ambient Sensor Fault (AmbSensor Fault)
Diesel generator temperature sensor failure.
Replace temperature sensor.
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
38 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
DI1Alarm (DI1 Alarm)
Digital input #1 alarm is active.
Check why alarm is active.
DI7Alarm (DI7 Alarm)
Digital input #7 alarm is active.
DI8 ESTOP (DI8 ESTOP)
Digital input #8 alarm is active.
IB Communication Fail (IB Comm Fail)
ACU+ Interface Board communications failure.
Check communications cables.
Relay Testing (Relay Testing)
Relay Test in progress.
--
Testing Relay 1 (Testing Relay 1)
Testing Relay 1 (on IB2 Board).
--
Testing Relay 8 (Testing Relay 8)
Testing Relay 8 (on IB2 Board).
System Temp1 High 2 (System T1 Hi2)
Temperature sensor #1 sensing temperature higher than high temperature threshold 2.
Note: This alarm is not used at this time.)
System Temp1 High 1 (System T1 Hi1)
Temperature sensor #1 sensing temperature higher than high temperature threshold 1.
System Temp1 Low (System T1 Low)
Temperature sensor #1 sensing temperature lower than low temperature threshold.
System Temp2 High 2 (System T2 Hi2)
Temperature sensor #2 sensing temperature higher than high temperature threshold 2.
Note: This alarm is not used at this time.)
System Temp2 High 1 (System T2 Hi1)
Temperature sensor #2 sensing temperature higher than high temperature threshold 1.
System Temp2 Low (System T2 Low)
Temperature sensor #2 sensing temperature lower than low temperature threshold.
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 2. Operation 39
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
System Temp3 High 2 (System T3 Hi2)
Temperature sensor #3 sensing temperature higher than high temperature threshold 2.
Note: This alarm is not used at this time.)
System Temp3 High 1 (System T3 Hi1)
Temperature sensor #3 sensing temperature higher than high temperature threshold 1.
System Temp3 Low (System 31 Low)
Temperature sensor #3 sensing temperature lower than low temperature threshold.
IB2 Temp1 High 2 (IB2 T1 Hi2)
Temperature sensor #1 (connected to IB2 board and set as Ambient) sensing temperature higher than high temperature threshold 2.
Check why temperature is high or low.
IB2 Temp1 High 1 (IB2 T1 Hi1)
Temperature sensor #1 (connected to IB2 board and set as Ambient) sensing temperature higher than high temperature threshold 1.
IB2 Temp1 Low (IB2 T1 Low)
Temperature sensor #1 (connected to IB2 board and set as Ambient) sensing temperature lower than low temperature threshold.
IB2 Temp2 High 2 (IB2 T2 Hi2)
Temperature sensor #2 (connected to IB2 board and set as Ambient) sensing temperature higher than high temperature threshold 2.
Check why temperature is high or low.
IB2 Temp2 High 1 (IB2 T2 Hi1)
Temperature sensor #2 (connected to IB2 board and set as Ambient) sensing temperature higher than high temperature threshold 1.
IB2 Temp2 Low (IB2 T2 Low)
Temperature sensor #2 (connected to IB2 board and set as Ambient) sensing temperature lower than low temperature threshold.
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
40 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
EIB Temp1 High 2 (EIB T1 Hi2)
Temperature sensor #1 (connected to EIB board and set as Ambient) sensing temperature higher than high temperature threshold 2.
Check why temperature is high or low.
EIB Temp1 High 1 (EIB T1 Hi1)
Temperature sensor #1 (connected to EIB board and set as Ambient) sensing temperature higher than high temperature threshold 1.
EIB Temp1 Low (EIB T1 Low)
Temperature sensor #1 (connected to EIB board and set as Ambient) sensing temperature lower than low temperature threshold.
EIB Temp2 High 2 (EIB T2 Hi2)
Temperature sensor #2 (connected to EIB board and set as Ambient) sensing temperature higher than high temperature threshold 2.
Check why temperature is high or low.
EIB Temp2 High 1 (EIB T2 Hi1)
Temperature sensor #2 (connected to EIB board and set as Ambient) sensing temperature higher than high temperature threshold 1.
EIB Temp2 Low (EIB T2 Low)
Temperature sensor #2 (connected to EIB board and set as Ambient) sensing temperature lower than low temperature threshold.
SMTemp1 Temp1 High 2 (SMTemp1 T1 Hi2)
Temperature sensor #1 (connected to SM-Temp 1 and set as Ambient) sensing temperature higher than high temperature threshold 2.
Check why temperature is high or low.
SMTemp1 Temp1 High 1 (SMTemp1 T1 Hi1)
Temperature sensor #1 (connected to SM-Temp 1 and set as Ambient) sensing temperature higher than high temperature threshold 1.
SMTemp1 Temp1 Low (SMTemp1 T1 Low)
Temperature sensor #1 (connected to SM-Temp 1 and set as Ambient) sensing temperature lower than low temperature threshold.
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 2. Operation 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
SMTemp1 Temp8 High 2 (SMTemp1 T8 Hi2)
Temperature sensor #8 (connected to SM-Temp 1 and set as Ambient) sensing temperature higher than high temperature threshold 2.
Check why temperature is high or low.
SMTemp1 Temp8 High 1 (SMTemp1 T8 Hi1)
Temperature sensor #8 (connected to SM-Temp 1 and set as Ambient) sensing temperature higher than high temperature threshold 1.
SMTemp1 Temp8 Low (SMTemp1 T8 Low)
Temperature sensor #8 (connected to SM-Temp 1 and set as Ambient) sensing temperature lower than low temperature threshold.
SMTemp8 Temp1 High 2 (SMTemp8 T1 Hi2)
Temperature sensor #1 (connected to SM-Temp 8 and set as Ambient) sensing temperature higher than high temperature threshold 2.
Check why temperature is high or low.
SMTemp8 Temp1 High 1 (SMTemp8 T1 Hi1)
Temperature sensor #1 (connected to SM-Temp 8 and set as Ambient) sensing temperature higher than high temperature threshold 1.
SMTemp8 Temp1 Low (SMTemp8 T1 Low)
Temperature sensor #1 (connected to SM-Temp 8 and set as Ambient) sensing temperature lower than low temperature threshold.
SMTemp8 Temp8 High 2 (SMTemp8 T8 Hi2)
Temperature sensor #8 (connected to SM-Temp 8 and set as Ambient) sensing temperature higher than high temperature threshold 2.
Check why temperature is high or low.
SMTemp8 Temp8 High 1 (SMTemp8 T8 Hi1)
Temperature sensor #8 (connected to SM-Temp 8 and set as Ambient) sensing temperature higher than high temperature threshold 1.
SMTemp8 Temp8 Low (SMTemp8 T8 Low)
Temperature sensor #8 (connected to SM-Temp 8 and set as Ambient) sensing temperature lower than low temperature threshold.
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
42 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
High Load Level1 (HighLoadLevel1)
Load current above high level 1.
Check to see why load current is high. High Load Level2
(HighLoadLevel2)
Load current above high level 2.
Load Current Alarm (Load Curr Alarm)
Load current alarm active.
Check to see why load current alarm is active.
Rectifier Group Alarms (Rect Group)
Multiple Rectifiers Failure (Multi-Rect Fail)
More than one rectifier has failed.
Check input voltage to rectifiers. Replace rectifiers.
Rectifier Lost (Rectifier Lost)
A rectifier cannot be detected by the Controller.
Reset the Rectifier Lost alarm. Replace defective rectifier.
ECO Active (ECO Active)
Rectifier Energy Optimization Mode is enabled.
Check to see why system was placed into this mode.
All Rectifiers Comm Fail (AllRectCommFail)
No response from all rectifiers.
Check the connectors and cables or the CAN loop. Replace the Controller.
ECO Cycle Alarm (ECO Cycle Alarm)
If Energy Optimization Mode is enabled and the Controller oscillates in and out of Energy Optimization more than 5 times, this alarm is generated.
Check for other alarms. Reset this alarm.
Rectifier Alarms (Rectifier)
AC Input Failure (AC Failure)
No AC input power to a rectifier.
Check why no AC input power available.
Rect Temperature High (Rect Temp High)
A rectifier has a high temperature condition.
Check why temperature is high.
Rectifier Fault (Rect Fault)
A rectifier has a fault condition.
Refer to Rectifier User Manual for troubleshooting information.
HVSD (HVSD)
A rectifier has an overvoltage condition.
Rectifier Protected (Rect Protected)
A rectifier is in protected mode.
Fan Failure (Fan Failure)
A rectifier’s fan has failed.
Replace fan.
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 2. Operation 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
Current Limit (Current Limit)
A rectifier is in current limit.
Rectifier overload. The load is higher than rectifier capacity. If the batteries are being recharged, the alarm will cease by itself when the battery voltage has increased to the charging level. If the system load is higher than the rectifier capacity, the batteries will discharge. If this is the reason, install additional rectifiers. If one or more of the rectifiers are defective, replace the faulty rectifiers.
Rectifier Communication Fail (Rect Comm Fail)
A rectifier has lost communications with the Controller.
Check communications cables. Reset the Communication Fail alarm. Replace the rectifier.
Derated (Derated)
A rectifier is in output power derating mode.
Refer to Rectifier User Manual for troubleshooting information.
Current Share Alarm (Curr Share Alm)
A rectifier has a current sharing alarm.
AC Under Voltage Protection (Low AC Protect)
A rectifier is in under voltage protection mode.
Battery Group Alarms (Battery Group)
Short Battery Test Running (ShortBatTestRun)
Battery is in short time test mode.
--
Equalize for Test (EQ for Test)
Battery is in equalize charge test mode.
--
Manual Test (Manual Test)
Battery is in manual battery discharge test mode.
--
Planned Test (Planned Test)
Battery is in planned battery test mode.
--
AC Fail Test (AC Fail Test)
AC power has been switched off to the rectifiers to perform a battery discharge test.
--
Manual Equalize (Manual EQ)
Battery is in manual equalize charging mode.
--
Automatic Equalize (Auto EQ)
Battery is in automatic equalize charging mode.
--
Cyclic Equalize (Cyclic EQ)
Battery is in cyclic equalize charging mode.
--
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
44 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
Master Equalize (Master EQ)
In slave mode, the slave unit starts equalize charging with the master unit.
--
Master Battery Test (Master Bat Test)
In slave mode, the slave unit starts the test with the master unit.
--
Discharge Current Imbalance (Dsch Curr Imb)
Battery distribution current imbalance alarm.
The currents from two groups of batteries are not equal. Check the batteries.
Abnormal Battery Current (Abnl Batt Curr)
The equalize charging current exceeds the alarm setting.
Check the alarm setting.
Temperature Compensation Active (TempComp Active)
Battery charge temperature compensation is active.
--
Battery Current Limit Active (Batt Curr Limit)
Battery is in current limit.
--
Bad Battery (Bad Battery)
Battery test fails.
Check the batteries.
Battery Discharge (Battery Disch)
Battery is discharging.
A battery test is active (the discharge test will stop automatically). There is a mains failure (check that it is not caused by open AC input circuit breaker). The system load is higher than rectifier capacity, causing the batteries to discharge (install additional rectifiers).
Battery Test Fail (BatteryTestFail)
Battery test fails.
Check the batteries.
Comp Temp High2 (Comp Temp High2)
Compensation temperature sensor sensing temperature higher than high temperature threshold 2.
Check why temperature is high or low.
Comp Temp High1 (Comp Temp High1)
Compensation temperature sensor sensing temperature higher than high temperature threshold 1.
Comp Temp Low (Comp Temp Low)
Compensation temperature sensor sensing temperature lower than low temperature threshold.
Compensation Sensor Fault (CompTempFail)
Temperature Compensation temperature sensor failure.
Replace temperature sensor.
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 2. Operation 45
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
System Temp1 High 2 (System T1 Hi2)
Temperature sensor #1 sensing temperature higher than high temperature threshold 2.
Note: This alarm is not used at this time.)
System Temp1 High 1 (System T1 Hi1)
Temperature sensor #1 sensing temperature higher than high temperature threshold 1.
System Temp1 Low (System T1 Low)
Temperature sensor #1 sensing temperature lower than low temperature threshold.
System Temp2 High 2 (System T2 Hi2)
Temperature sensor #2 sensing temperature higher than high temperature threshold 2.
Note: This alarm is not used at this time.)
System Temp2 High 1 (System T2 Hi1)
Temperature sensor #2 sensing temperature higher than high temperature threshold 1.
System Temp2 Low (System T2 Low)
Temperature sensor #2 sensing temperature lower than low temperature threshold.
System Temp3 High 2 (System T3 Hi2)
Temperature sensor #3 sensing temperature higher than high temperature threshold 2.
Note: This alarm is not used at this time.)
System Temp3 High 1 (System T3 Hi1)
Temperature sensor #3 sensing temperature higher than high temperature threshold 1.
System Temp3 Low (System T3 Low)
Temperature sensor #3 sensing temperature lower than low temperature threshold.
IB2 Temp1 High 2 (IB2 T1 Hi2)
Temperature sensor #1 (connected to IB2 board and set as Battery) sensing temperature higher than high temperature threshold 2.
Check why temperature is high or low.
IB2 Temp1 High 1 (IB2 T1 Hi1)
Temperature sensor #1 (connected to IB2 board and set as Battery) sensing temperature higher than high temperature threshold 1.
IB2 Temp1 Low (IB2 T1 Low)
Temperature sensor #1 (connected to IB2 board and set as Battery) sensing temperature lower than low temperature threshold.
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
46 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
IB2 Temp2 High 2 (IB2 T2 Hi2)
Temperature sensor #2 (connected to IB2 board and set as Battery) sensing temperature higher than high temperature threshold 2.
Check why temperature is high or low.
IB2 Temp2 High 1 (IB2 T2 Hi1)
Temperature sensor #2 (connected to IB2 board and set as Battery) sensing temperature higher than high temperature threshold 1.
IB2 Temp2 Low (IB2 T2 Low)
Temperature sensor #2 (connected to IB2 board and set as Battery) sensing temperature lower than low temperature threshold.
EIB Temp1 High 2 (EIB T1 Hi2)
Temperature sensor #1 (connected to EIB board and set as Battery) sensing temperature higher than high temperature threshold 2.
Check why temperature is high or low.
EIB Temp1 High 1 (EIB T1 Hi1)
Temperature sensor #1 (connected to EIB board and set as Battery) sensing temperature higher than high temperature threshold 1.
EIB Temp1 Low (EIB T1 Low)
Temperature sensor #1 (connected to EIB board and set as Battery) sensing temperature lower than low temperature threshold.
EIB Temp2 High 2 (EIB T2 Hi2)
Temperature sensor #2 (connected to EIB board and set as Battery) sensing temperature higher than high temperature threshold 2.
Check why temperature is high or low.
EIB Temp2 High 1 (EIB T2 Hi1)
Temperature sensor #2 (connected to EIB board and set as Battery) sensing temperature higher than high temperature threshold 1.
EIB Temp2 Low (EIB T2 Low)
Temperature sensor #2 (connected to EIB board and set as Battery) sensing temperature lower than low temperature threshold.
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 2. Operation 47
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
SMTemp1 Temp1 High 2 (SMTemp1 T1 Hi2)
Temperature sensor #1 (connected to SM-Temp 1 and set as Battery) sensing temperature higher than high temperature threshold 2.
Check why temperature is high or low.
SMTemp1 Temp1 High 1 (SMTemp1 T1 Hi1)
Temperature sensor #1 (connected to SM-Temp 1 and set as Battery) sensing temperature higher than high temperature threshold 1.
SMTemp1 Temp1 Low (SMTemp1 T1 Low)
Temperature sensor #1 (connected to SM-Temp 1 and set as Battery) sensing temperature lower than low temperature threshold.
SMTemp1 Temp8 High 2 (SMTemp1 T8 Hi2)
Temperature sensor #8 (connected to SM-Temp 1 and set as Battery) sensing temperature higher than high temperature threshold 2.
Check why temperature is high or low.
SMTemp1 Temp8 High 1 (SMTemp1 T8 Hi1)
Temperature sensor #8 (connected to SM-Temp 1 and set as Battery) sensing temperature higher than high temperature threshold 1.
SMTemp1 Temp8 Low (SMTemp1 T8 Low)
Temperature sensor #8 (connected to SM-Temp 1 and set as Battery) sensing temperature lower than low temperature threshold.
SMTemp8 Temp1 High 2 (SMTemp8 T1 Hi2)
Temperature sensor #1 (connected to SM-Temp 8 and set as Battery) sensing temperature higher than high temperature threshold 2.
Check why temperature is high or low.
SMTemp8 Temp1 High 1 (SMTemp8 T1 Hi1)
Temperature sensor #1 (connected to SM-Temp 8 and set as Battery) sensing temperature higher than high temperature threshold 1.
SMTemp8 Temp1 Low (SMTemp8 T1 Low)
Temperature sensor #1 (connected to SM-Temp 8 and set as Battery) sensing temperature lower than low temperature threshold.
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
48 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
SMTemp8 Temp8 High 2 (SMTemp8 T8 Hi2)
Temperature sensor #8 (connected to SM-Temp 8 and set as Battery) sensing temperature higher than high temperature threshold 2.
Check why temperature is high or low.
SMTemp8 Temp8 High 1 (SMTemp8 T8 Hi1)
Temperature sensor #8 (connected to SM-Temp 8 and set as Battery) sensing temperature higher than high temperature threshold 1.
SMTemp8 Temp8 Low (SMTemp8 T8 Low)
Temperature sensor #8 (connected to SM-Temp 8 and set as Battery) sensing temperature lower than low temperature threshold.
BTRM Temp High 2 (BTRM Temp High2)
Battery temperature (monitored by the sensor set as BTRM) is higher than the BTRM Temperature Alarm 2 threshold.
Check why temperature is high or low. BTRM Temp High 1
(BTRM Temp High1)
Battery temperature (monitored by the sensor set as BTRM) is higher than the BTRM Temperature Alarm 1 threshold.
BTRM Sensor Fault (BTRM TempFault)
BTRM temperature sensor failure.
Replace temperature sensor.
Li-Ion Battery Lost (LiBatt Lost)
A Li-Ion Battery cannot be detected by the Controller.
Check communications cables. Clear the Li-Ion Battery Lost alarm.
1 Li-Ion Battery Disconnect (1 LiBattDiscon)
One (1) Li-Ion Battery is disconnected.
Check why the Li-Ion Battery disconnected.
2+Li-Ion Battery Disconnect (2+LiBattDiscon)
Two (2) or more Li-Ion Batteries are disconnected.
Check why the Li-Ion Batteries disconnected.
1 Li-Ion Battery No Reply (1 LiBattNoReply)
One (1) Li-Ion Battery has lost communications with the Controller.
Check communications cables. Clear the Li-Ion Communication Fail alarm.
2+Li-Ion Battery No Reply (2+LiBattNoReply)
Two (2) or more Li-Ion Batteries have lost communications with the Controller.
Check communications cables. Clear the Li-Ion Communication Fail alarm.
Inventory Update In Process (InventUpdating)
Li-Ion Battery inventory being updated.
--
ABCL is active (ABCL Active)
Active Battery Charge Current Limit is active.
--
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 2. Operation 49
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
Battery Alarms (Battery)
Battery Current Limit Exceeded (Ov Batt Cur Lmt)
Battery current limit point is exceeded.
--
Battery Over Current (Batt Over Curr)
Battery is in over current.
--
Low Battery Capacity (Low Batt Cap)
Battery has low capacity.
Check the batteries.
SMDU Battery Alarms (SM-DU Module must be present in system) (SMDU Battery)
Exceed Current Limit (Exceed Curr Lmt)
Battery current limit point is exceeded.
--
Over Battery Current (Over Current)
Battery is in over current.
--
Low Capacity (Low Capacity)
Battery has low capacity.
Check the batteries.
EIB (Extended Interface Board) Battery Alarms (EIB Board must be present in system) (EIB Battery)
Battery Current Limit Exceeded (Ov Bat Curr Lmt)
Battery current limit point is exceeded.
--
Battery Over Current (Bat Over Curr)
Battery is in over current.
--
Battery Low Capacity (Low Batt Cap)
Battery has low capacity.
Check the batteries.
SM Battery Alarms (SM-BAT Module must be present in system) (SM Battery)
Exceed Batt Current Limit (Over Curr Limit)
Battery is in over current.
--
Over Battery Current (Over Batt Curr)
Battery current is high.
--
Battery Leakage (Battery Leakage)
Battery has leakage current.
Check the batteries.
Low Acid Level (Low Acid Level)
Battery has low acid level.
Check the batteries.
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
50 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
Battery Disconnected (Batt Disconnec)
Battery disconnection is active.
--
Battery High Temperature (Batt High Temp)
Battery has high temperature condition.
--
Battery Low Temperature (Batt Low Temp)
Battery has low temperature condition.
--
Cell Voltage Difference (Cell Volt Diff)
Battery cell voltage difference detected.
Check the batteries.
SM Unit Fail (SM Unit Fail)
Battery monitoring device has failed.
Replace device.
Battery Temperature Sensor Fault (T Sensor Fault)
Battery temperature sensor has failed.
Replace temperature sensor.
Low Capacity (Low Capacity)
Battery has low capacity.
Check the batteries.
Battery Communication Fail (Batt Comm Fail)
Battery monitoring device has lost communications with the Controller.
Check communications cables.
Battery Temp not Used (Bat Temp No Use)
No battery temperature sensor.
--
LargeDU Battery Alarms (Large Distribution Unit must be present in system) (LargeDU Batt)
Battery Current Limit Exceeded (Ov Batt Cur Lmt)
Battery current limit point is exceeded.
--
Battery Low Capacity (Batt Low Cap)
Battery has low capacity.
Check the batteries.
Battery Fuse Failure (Batt Fuse Fail)
Battery fuse is open.
--
Battery Over Voltage (Batt Over Volt)
Battery has over voltage condition.
--
Battery Under Voltage (Batt Under Volt)
Battery has under voltage condition.
--
Battery Over Current (Batt Over Curr)
Battery has over current condition.
--
Communication Fail (Comm Fail)
Battery monitoring device has lost communications with the Controller.
Check communications cables.
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 2. Operation 51
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
SMBRC Battery Alarms (SM-BRC Module must be present in system) (SMBRC Battery)
Cell Volt Low Alarm (Volt Low Alm)
Battery string low voltage alarm.
--
Cell Temp Low Alarm (Temp Low Alm)
Battery string low temperature alarm.
--
Cell Resist Low Alarm (Resist Low Alm)
Battery string low resistance alarm.
--
Cell Inter Low Alarm (Inter Low Alm)
Battery string inter-cell low resistance alarm.
--
Cell Ambient Low Alarm (Amb Low Alm)
Battery string ambient low alarm.
--
Overall Voltage High (Overall Volt Hi)
Battery string high voltage alarm.
--
Overall Voltage Low (Overall Volt Lo)
Battery string low voltage alarm.
--
String Current High (String Curr Hi)
Battery string high current alarm.
--
String Current Low (String Curr Lo)
Battery string low current alarm.
--
Ripple Current High (Ripple Curr Hi)
Battery string ripple current high.
--
Ripple Current Low (Ripple Curr Lo)
Battery string ripple current low.
--
Exceed Current Limit (Exceed Curr Lmt)
Battery string current limit exceeded.
--
Over Battery Current (Over Current)
Battery string over current alarm.
--
Low Capacity (Low Capacity)
Battery string low capacity alarm.
--
Cell High Voltage Alarm (Cell HiVolt Alm)
Battery cell high voltage alarm.
--
Cell High Cell Temperature Alarm (Cell HiTemp Alm)
Battery cell high temperature alarm.
--
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
52 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
Cell High Resistance Alarm (Cell HiRes Alm)
Battery cell high resistance alarm.
--
Cell High Intercell Resist Alarm (Inter HiRes Alm)
Battery inter-cell high resistance alarm.
--
Cell High Ambient Temp Alarm (Cell HiAmb Alm)
Battery cell high ambient temperature alarm.
--
Temperature 1 Not Used (Temp1 Not Used)
Temperature sensor #1 not used.
--
Temperature 24 Not Used (Temp24 Not Used)
Temperature sensor #24 not used.
Battery Temperature Fault (Batt Temp Fault)
Li-Ion battery internal temperature sensor has failed.
Replace the battery.
Battery Current Fault (Current Fault)
Li-Ion battery internal current monitoring circuit has failed.
Replace the battery.
Battery Hardware Failure (Hardware Fail)
Li-Ion battery hardware has failed.
Replace the battery.
Battery Over-Voltage (Over-volt)
Li-Ion battery has over voltage condition.
Check why battery voltage is high.
Battery Low-Voltage (Low-volt)
Li-Ion battery has low voltage condition.
Check why battery voltage is low.
Cell Volt Deviation (CellVoltDeviat)
Li-Ion battery cell voltage deviation detected.
Check why cell voltage has deviated.
Low Cell Voltage (Lo Cell Volt)
Li-Ion battery has low cell voltage condition.
Check why cell voltage is low.
High Cell Voltage (Hi Cell Volt)
Li-Ion battery has high cell voltage condition.
Check why cell voltage is high.
High Cell Temperature (Hi Cell Temp)
Li-Ion battery has high cell temperature condition.
Check why temperature is high.
High Switch DisTemp (HiSwitchDisTemp)
Li-Ion battery has high switch discharge temperature.
Check why temperature is high.
Charge Short Circuit (Char ShortCirc)
Li-Ion battery has charge short circuit condition.
Replace the battery.
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 2. Operation 53
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
DisChar Short Circuit (DisCharShortCir)
Li-Ion battery has discharge short circuit condition.
Replace the battery.
High Switch CharTemp (HiSwitchCharTem)
Li-Ion battery has high switch charge temperature.
Check why temperature is high.
Hardware Fail 20 (HardwareFail20)
Li-Ion battery has hardware failure.
Replace the battery.
Hardware Fail 21 (HardwareFail21)
Li-Ion battery has hardware failure.
Replace the battery.
High Charge Current (Hi Charge Curr)
Li-Ion battery has high charge current.
Check why charge current high.
High DisCharge Current (Hi Dischar Curr)
Li-Ion battery has high discharge current.
Check why discharge current high.
Communication Interrupt (Comm Interrupt)
Li-Ion battery communications have been interrupted.
Check why communications failure.
Battery Disconnected (Batt Disconnect)
Li-Ion battery is disconnected.
Check why battery disconnected.
Charge Enabled (Charge Enable)
Li-Ion battery charge is enabled.
--
Battery Discharging (Batt Discharge)
Li-Ion battery is discharging.
--
Battery Charging (Batt Charge)
Li-Ion battery is charging.
--
DisCharging (DisCharging)
Li-Ion battery is discharging.
--
Charging(5A) (Charging(5A))
Li-Ion battery is charging.
--
DisCharging(5A) (DisCharging(5A))
Li-Ion battery is discharging.
--
Battery Relay Status (BattRelayStatus)
State of alarm relay.
If in alarm state, check battery.
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
54 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
OB Battery Fuse Alarms (SM-DU Module must be present in system) (OB Batt Fuse)
Fuse 1 Alarm (Fuse 1 Alarm)
Fuse #1 is open.
Find out and eliminate the reason the fuse is open before replacing. Check for overload or short circuit. If the fuse was manually removed, check with the person that removed it before reinserting it.
Fuse 4 Alarm (Fuse 4 Alarm)
Fuse #4 is open.
SMDU Battery Fuse Unit Alarms (SM-DU Module must be present in system) (SMDU Bat Fuse)
Batt Fuse 1 Alarm (Batt Fuse 1 Alm)
Battery fuse #1 is open.
Find out and eliminate the reason the fuse is open before replacing. Check for overload or short circuit. If the fuse was manually removed, check with the person that removed it before reinserting it.
Batt Fuse 4 Alarm (Batt Fuse 4 Alm)
Battery fuse #4 is open.
DC Distribution Alarms (DC Distr)
Over Voltage 1 (Over Voltage 1)
DC output is above over voltage 1 threshold.
Check to see why voltage is high. Over Voltage 2
(Over Voltage 2)
DC output is above over voltage 2 threshold.
Under Voltage 1 (Under Voltage 1)
DC output is below under voltage 1 threshold.
Check to see why voltage is low. Under Voltage 2
(Under Voltage 2)
DC output is below under voltage 2 threshold.
Over Voltage 1 (24V) (24V Over Volt1)
DC output is above over voltage 1 threshold.
Check to see why voltage is high. Over Voltage 2 (24V)
(24V Over Volt2)
DC output is above over voltage 2 threshold.
Under Voltage 1 (24V) (24V Under Volt1)
DC output is below under voltage 1 threshold.
Check to see why voltage is low. Under Voltage 2 (24V)
(24V Under Volt2)
DC output is below under voltage 2 threshold.
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 2. Operation 55
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
DC Fuse Unit Alarms (DC Fuse Unit)
Fuse 1 Alarm (Fuse 1 Alarm)
DC output fuse #1 is open.
Find out and eliminate the reason the fuse is open before replacing. Check for overload or short circuit. If the fuse was manually removed, check with the person that removed it before reinserting it.
Fuse 10 Alarm (Fuse 10 Alarm)
DC output fuse #10 is open.
SMDU DC Fuse Alarms (SM-DU Module must be present in system) (SMDU DC Fuse)
Fuse 1 Alarm (DC Fuse 1 Alm)
DC output fuse #1 is open.
Find out and eliminate the reason the fuse is open before replacing. Check for overload or short circuit. If the fuse was manually removed, check with the person that removed it before reinserting it.
Fuse 16 Alarm (DC Fuse 16 Alm)
DC output fuse #16 is open.
SMDUP DC Fuse Alarms (SM-DU+ Module must be present in system) (SMDUP DC Fuse)
Fuse 1 Alarm (DC Fuse 1 Alm)
DC output fuse #1 is open.
Find out and eliminate the reason the fuse is open before replacing. Check for overload or short circuit. If the fuse was manually removed, check with the person that removed it before reinserting it.
Fuse 25 Alarm (DC Fuse 25 Alm)
DC output fuse #25 is open.
LVD Unit Alarms (Low voltage disconnect must be present in system) (LVD Unit)
LVD1 Disconnect (LVD1 Disconnect)
LVD1 contactor is in disconnect mode.
--
LVD2 Disconnect (LVD2 Disconnect)
LVD2 contactor is in disconnect mode.
--
LVD1 Failure (LVD1 Failure)
LVD1 contactor has failed.
Check the contactor functions. Replace the contactor.
LVD2 Failure (LVD2 Failure)
LVD2 contactor has failed.
SMDU LVD Alarms (SM-DU Module must be present in system) (SMDU LVD)
LVD 1 Disconnected (LVD 1 Disconn)
LVD1 contactor is in disconnect mode.
--
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
56 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
LVD 2 Disconnected (LVD 2 Disconn)
LVD2 contactor is in disconnect mode.
--
LVD 1 Contactor Failure (LVD 1 Failure)
LVD1 contactor has failed.
Check the contactor functions. Replace the contactor.
LVD 2 Contactor Failure (LVD 2 Failure)
LVD2 contactor has failed.
LargeDU LVD Alarms (Large Distribution Unit must be present in system) (LargeDU LVD)
LVD1 Disconnected (LVD1 Disconnect)
LVD1 contactor is in disconnect mode.
--
LVD2 Disconnected (LVD2 Disconnect)
LVD2 contactor is in disconnect mode.
--
Rectifier AC Alarms (Rectifier AC)
Line AB Over Voltage 1 (L-AB Over Volt1)
Voltage between Line A and Line B is higher than the High Line Voltage AB Alarm threshold.
Check why voltage is high. Line AB Over Voltage 2
(L-AB Over Volt2)
Voltage between Line A and Line B is higher than the Very High Line Voltage AB Alarm threshold.
Line AB Under Voltage 1 (L-AB UnderVolt1)
Voltage between Line A and Line B is lower than the Low Line Voltage AB Alarm threshold.
Check why voltage is low. Line AB Under Voltage 2
(L-AB UnderVolt2)
Voltage between Line A and Line B is lower than the Very Low Line Voltage AB Alarm threshold.
Line BC Over Voltage 1 (L-BC Over Volt1)
Voltage between Line B and Line C is higher than the High Line Voltage BC Alarm threshold.
Check why voltage is high. Line BC Over Voltage 2
(L-BC Over Volt2)
Voltage between Line B and Line C is higher than the Very High Line Voltage BC Alarm threshold.
Line BC Under Voltage 1 (L-BC UnderVolt1)
Voltage between Line B and Line C is lower than the Low Line Voltage BC Alarm threshold.
Check why voltage is low. Line BC Under Voltage 2
(L-BC UnderVolt2)
Voltage between Line B and Line C is lower than the Very Low Line Voltage BC Alarm threshold.
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 2. Operation 57
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
Line CA Over Voltage 1 (L-CA Over Volt1)
Voltage between Line C and Line A is higher than the High Line Voltage CA Alarm threshold.
Check why voltage is high. Line CA Over Voltage 2
(L-CA Over Volt2)
Voltage between Line C and Line A is higher than the Very High Line Voltage CA Alarm threshold.
Line CA Under Voltage 1 (L-CA UnderVolt1)
Voltage between Line C and Line A is lower than the Low Line Voltage CA Alarm threshold.
Check why voltage is low. Line CA Under Voltage 2
(L-CA UnderVolt2)
Voltage between Line C and Line A is lower than the Very Low Line Voltage CA Alarm threshold.
Phase A Over Voltage 1 (PH-A Over Volt1)
Phase A voltage is above over voltage 1 threshold.
Check why voltage is high. Phase A Over Voltage 2
(PH-A Over Volt2)
Phase A voltage is above over voltage 2 threshold.
Phase A Under Voltage 1 (PH-A UnderVolt1)
Phase A voltage is below under voltage 1 threshold.
Check why voltage is low. Phase A Under Voltage 2
(PH-A UnderVolt2)
Phase A voltage is below under voltage 2 threshold.
Phase B Over Voltage 1 (PH-B Over Volt1)
Phase B voltage is above over voltage 1 threshold.
Check why voltage is high. Phase B Over Voltage 2
(PH-B Over Volt2)
Phase B voltage is above over voltage 2 threshold.
Phase B Under Voltage 1 (PH-B UnderVolt1)
Phase B voltage is below under voltage 1 threshold.
Check why voltage is low. Phase B Under Voltage 2
(PH-B UnderVolt2)
Phase B voltage is below under voltage 2 threshold.
Phase C Over Voltage 1 (PH-C Over Volt1)
Phase C voltage is above over voltage 1 threshold.
Check why voltage is high. Phase C Over Voltage 2
(PH-C Over Volt2)
Phase C voltage is above over voltage 2 threshold.
Phase C Under Voltage 1 (PH-C UnderVolt1)
Phase C voltage is below under voltage 1 threshold.
Check why voltage is low. Phase C Under Voltage 2
(PH-C UnderVolt2)
Phase C voltage is below under voltage 2 threshold.
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
58 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
Mains Failure (Mains Failure)
Commercial AC power failure.
Check why no commercial AC power.
OB AC Unit (OB-AC Module must be present in system) (OBAC)
Phase A Over Voltage 1 (PH-A Over Volt1)
Phase A voltage is above over voltage 1 threshold.
Check why voltage is high. Phase A Over Voltage 2
(PH-A Over Volt2)
Phase A voltage is above over voltage 2 threshold.
Phase A Under Voltage 1 (PH-A UnderVolt1)
Phase A voltage is below under voltage 1 threshold.
Check why voltage is low. Phase A Under Voltage 2
(PH-A UnderVolt2)
Phase A voltage is below under voltage 2 threshold.
Phase B Over Voltage 1 (PH-B Over Volt1)
Phase B voltage is above over voltage 1 threshold.
Check why voltage is high. Phase B Over Voltage 2
(PH-B Over Volt2)
Phase B voltage is above over voltage 2 threshold.
Phase B Under Voltage 1 (PH-B UnderVolt1)
Phase B voltage is below under voltage 1 threshold.
Check why voltage is low. Phase B Under Voltage 2
(PH-B UnderVolt2)
Phase B voltage is below under voltage 2 threshold.
Phase C Over Voltage 1 (PH-C Over Volt1)
Phase C voltage is above over voltage 1 threshold.
Check why voltage is high. Phase C Over Voltage 2
(PH-C Over Volt2)
Phase C voltage is above over voltage 2 threshold.
Phase C Under Voltage 1 (PH-C UnderVolt1)
Phase C voltage is below under voltage 1 threshold.
Check why voltage is low. Phase C Under Voltage 2
(PH-C UnderVolt2)
Phase C voltage is below under voltage 2 threshold.
Mains Failure (Mains Failure)
Commercial AC power failure.
Check why no commercial AC power.
Severe Mains Failure (SevereMainsFail)
Commercial AC power voltage is too low.
Check why voltage is low.
Mains Failure (Single) (Mains Failure)
Commercial AC power failure.
Check why no commercial AC power.
Severe Mains Failure (Single) (SevereMainsFail)
Commercial AC power voltage is too low.
Check why voltage is low.
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 2. Operation 59
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
SMAC Alarms (SM-AC Module must be present in system) (SMAC)
Supervision Fail (Supervise Fail)
AC monitoring device has failed.
--
High Line Voltage AB (Hi LineVolt AB)
Voltage between Line A and Line B above high voltage threshold.
Check why voltage is high. Very High Line Voltage AB
(VHi LineVolt AB)
Voltage between Line A and Line B above very high voltage threshold.
Low Line Voltage AB (Lo LineVolt AB)
Voltage between Line A and Line B below low voltage threshold.
Check why voltage is low. Very Low Line Voltage AB
(VLo LineVolt AB)
Voltage between Line A and Line B below very low voltage threshold.
High Line Voltage BC (Hi LineVolt BC)
Voltage between Line B and Line C above high voltage threshold.
Check why voltage is high. Very High Line Voltage BC
(VHi LineVolt BC)
Voltage between Line B and Line C above very high voltage threshold.
Low Line Voltage BC (Lo LineVolt BC)
Voltage between Line B and Line C below low voltage threshold.
Check why voltage is low. Very Low Line Voltage BC
(VLo LineVolt BC)
Voltage between Line B and Line C below very low voltage threshold.
High Line Voltage CA (Hi LineVolt CA)
Voltage between Line C and Line A above high voltage threshold.
Check why voltage is high. Very High Line Voltage CA
(VHi LineVolt CA)
Voltage between Line C and Line A above very high voltage threshold.
Low Line Voltage CA (Lo LineVolt CA)
Voltage between Line C and Line A below low voltage threshold.
Check why voltage is low. Very Low Line Voltage CA
(VLo LineVolt CA)
Voltage between Line C and Line A below very low voltage threshold.
High Phase Voltage A (Hi PhaseVolt A)
Phase A voltage is above high voltage threshold.
Check why voltage is high. Very High Phase Voltage A
(VHi PhaseVolt A)
Phase A voltage is above very high voltage threshold.
Low Phase Voltage A (Lo PhaseVolt A)
Phase A voltage is below low voltage threshold.
Check why voltage is low. Very Low Phase Voltage A
(VLo PhaseVolt A)
Phase A voltage is below very low voltage threshold.
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
60 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
High Phase Voltage B (Hi PhaseVolt B)
Phase B voltage is above high voltage threshold.
Check why voltage is high. Very High Phase Voltage B
(VHi PhaseVolt B)
Phase B voltage is above very high voltage threshold.
Low Phase Voltage B (Lo PhaseVolt B)
Phase B voltage is below low voltage threshold.
Check why voltage is low. Very Low Phase Voltage B
(VLo PhaseVolt B)
Phase B voltage is below very low voltage threshold.
High Phase Voltage C (Hi PhaseVolt C)
Phase C voltage is above high voltage threshold.
Check why voltage is high. Very High Phase Voltage C
(VHi PhaseVolt C)
Phase C voltage is above very high voltage threshold.
Low Phase Voltage C (Lo PhaseVolt C)
Phase C voltage is below low voltage threshold.
Check why voltage is low. Very Low Phase Voltage C
(VLo PhaseVolt C)
Phase C voltage is below very low voltage threshold.
Mains Failure (Mains Failure)
Commercial AC power failure.
Check why no commercial AC power.
Severe Mains Failure (SevereMainsFail)
Commercial AC power voltage is too low.
Check why voltage is low.
High Frequency (High Frequency)
Commercial AC power has high frequency.
--
Low Frequency (Low Frequency)
Commercial AC power has low frequency.
--
High Temperature (High Temp)
AC input temperature sensor sensing high temperature condition.
--
Low Temperature (Low Temperature)
AC input temperature sensor sensing low temperature condition.
--
Phase A High Current (PH-A Hi Current)
High phase A current.
--
Phase B High Current (PH-B Hi Current)
High phase B current.
--
Phase C High Current (PH-C Hi Current)
High phase C current.
--
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 2. Operation 61
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
IB (Interface Board) Alarms (IB board must be present in system) (IB)
Communication Fail (Comm Fail)
IB board has lost communications with the Controller.
Check communications cables.
Digital Input 1 Alarm (DI1 Alarm)
Digital input #1 in alarm state.
--
Digital Input 8 Alarm (DI8 Alarm)
Digital input #8 in alarm state.
--
Testing Relay1 (Testing Relay1)
Testing Relay 1 (on IB2 Board).
--
Testing Relay8 (Testing Relay8)
Testing Relay 8 (on IB2 Board).
EIB (Extended Interface Board) Alarms (EIB2 board must be present in system) (EIB)
EIB Communication Fail (EIB Comm Fail)
EIB board has lost communications with the Controller.
Check communications cables.
Bad Battery Block (Bad Batt Block)
Battery block fails.
Check batteries.
Testing Relay9 (Testing Relay9)
Testing Relay 9 (on EIB Board).
--
Testing Relay13 (Testing Relay13)
Testing Relay 13 (on EIB Board).
SMDU 1 [2, 3, 4, 5, 6, 7, 8] Alarms (SM-DU Module must be present in system) (SMDU 1 [2, 3, 4, 5, 6, 7, 8])
Under Voltage (Under Voltage)
Distribution voltage is below under voltage threshold.
Check to see why system voltage is low.
Over Voltage (Over Voltage)
Distribution voltage is above over voltage threshold.
Check to see why system voltage is low.
Communication Fail (Comm Fail)
The SM-DU 1 has lost communications with the Controller.
Check communications cables.
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
62 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
Current1 High Current (Curr 1 Hi)
Current 1 has high current.
Check why current is high.
Current1 Very High Current (Curr 1 Very Hi)
Current 1 has very high current.
Current5 High Current (Curr 5 Hi)
Current 5 has high current.
Current5 Very High Current (Curr 5 Very Hi)
Current 5 has very high current.
Shunt1 Coefficient Conflict (Shunt1 Conflict)
Shunt 1 coefficient conflicting.
Verify shunt size.
Shunt5 Coefficient Conflict (Shunt5 Conflict)
Shunt 4 coefficient conflicting.
Converter Group Alarms (Converter Grp)
Multiple Converters Failure (Multi-Conv Fail)
More than one converter has failed.
Check input voltage to converters. Replace converters.
Converter Lost (Converter Lost)
A converter cannot be detected by the Controller.
Reset the Converter Lost alarm. Replace defective converter.
All Converters Comm Fail (AllConvCommFail)
No response from all converters.
Check the connectors and cables or the CAN loop. Replace the Controller.
Over Current (Over Current)
Over current condition exists.
Check why.
Converter Alarms (Converter)
Communication Fail (Comm Fail)
A converter has lost communications with the Controller.
Check communications cables. Reset the Communication Fail alarm. Replace the converter.
Over Temperature (Over Temp)
A converter has an over temperature condition.
Check why temperature is high.
HVSD Alarm (HVSD Alarm)
A converter has an overvoltage condition.
Refer to Converter User Manual for troubleshooting information.
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 2. Operation 63
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
Fan Failure (Fan Failure)
A converter’s fan has failed.
Replace fan.
Power Limit (Power Limit)
A converter is in temperature power limit.
Converter overload. The load is higher than converter capacity.
Input Low Voltage (Input Low Volt)
Input voltage to a converter is low.
--
Converter Failure (Converter Fail)
A converter has a fault condition.
Refer to Converter User Manual for troubleshooting information.
EEPROM Fail (EEPROM Fail)
A converter’s EEPROM has failed.
Thermal Shutdown (Thermal SD)
A converter is in thermal shutdown.
Mod ID Overlap (Mod ID Overlap)
Converter module ID’s overlap.
--
Under Voltage (Under Voltage)
A converter has an under voltage condition.
--
Over Voltage (Over Voltage)
A converter has an over voltage condition.
--
SMIO 1 Generic Unit 1 Alarms (SM-IO Module must be present in system) (SMIO 1)
SMIO Failure (SMIO Fail)
SMIO has failed.
--
SMIO Generic Unit 3 [4, 5, 6, 7, 8] Alarms (SM-IO Module must be present in system) (SMIO Unit 3 [4, 5, 6, 7, 8])
High Analog Input 1 Alarm (Hi AI 1 Alarm)
Input #1 above high alarm threshold.
--
Low Analog Input 1 Alarm (Low AI 1 Alarm)
Input #1 below low alarm threshold.
--
High Analog Input 5 Alarm (Hi AI 5 Alarm)
Input #5 above high alarm threshold.
--
Low Analog Input 5 Alarm (Low AI 5 Alarm)
Input #5 below low alarm threshold.
--
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
64 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
High Frequency Input Alarm (Hi Freq In Alm)
Input frequency above high frequency alarm threshold.
--
Low Frequency Input Alarm (Low Freq In Alm)
Input frequency below low frequency alarm threshold.
--
SMIO Failure (SMIO Fail)
SM-IO board failure.
Replace the board.
Testing Relay 1 (Testing Relay 1)
Testing Relay 1.
--
Testing Relay 2 (Testing Relay 2)
Testing Relay 2.
Testing Relay 3 (Testing Relay 3)
Testing Relay 3.
LargeDU AC Distribution Group Alarms (Large Distribution Unit must be present in system) (LargeDUACDist)
Mains Failure (Mains Failure)
Commercial AC power failure.
--
LargeDU AC Distribution Alarms (Large Distribution Unit must be present in system) (AC Distributi)
Mains 1 Failure (Mains 1 Fail)
AC input 1 power failure.
--
Mains 2 Failure (Mains 2 Fail)
AC input 2 power failure.
--
Mains 3 Failure (Mains 3 Fail)
AC input 3 power failure.
--
Mains 1 Uab/Ua Failure (M1 Uab/Ua Fail)
No AC input voltage between Line A and Line B of input 1.
--
Mains 1 Ubc/Ub Failure (M1 Ubc/Ub Fail)
No AC input voltage between Line B and Line C of input 1.
--
Mains 1 Uca/Uc Failure (M1 Uca/Uc Fail)
No AC input voltage between Line C and Line A of input 1.
--
Mains 2 Uab/Ua Failure (M2 Uab/Ua Fail)
No AC input voltage between Line A and Line B of input 2.
--
Mains 2 Ubc/Ub Failure (M2 Ubc/Ub Fail)
No AC input voltage between Line B and Line C of input 2.
--
Mains 2 Uca/Uc Failure (M2 Uca/Uc Fail)
No AC input voltage between Line C and Line A of input 2.
--
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 2. Operation 65
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
Mains 3 Uab/Ua Failure (M3 Uab/Ua Fail)
No AC input voltage between Line A and Line B of input 3.
--
Mains 3 Ubc/Ub Failure (M3 Ubc/Ub Fail)
No AC input voltage between Line B and Line C of input 3.
--
Mains 3 Uca/Uc Failure (M3 Uca/Uc Fail)
No AC input voltage between Line C and Line A of input 3.
--
Over Frequency (Over Frequency)
Input frequency above over frequency alarm threshold.
--
Under Frequency (Under Frequency)
Input frequency below under frequency alarm threshold.
--
Mains 1 Uab/Ua Over Voltage (M1 Uab/Ua OverV)
AC input 1 voltage between Line A and Line B above over voltage threshold.
--
Mains 1 Ubc/Ub Over Voltage (M1 Ubc/Ub OverV)
AC input 1 voltage between Line B and Line C above over voltage threshold.
--
Mains 1 Uca/Uc Over Voltage (M1 Uca/Uc OverV)
AC input 1 voltage between Line C and Line A above over voltage threshold.
--
Mains 2 Uab/Ua Over Voltage (M2 Uab/Ua OverV)
AC input 2 voltage between Line A and Line B above over voltage threshold.
--
Mains 2 Ubc/Ub Over Voltage (M2 Ubc/Ub OverV)
AC input 2 voltage between Line B and Line C above over voltage threshold.
--
Mains 2 Uca/Uc Over Voltage (M2 Uca/Uc OverV)
AC input 2 voltage between Line C and Line A above over voltage threshold.
--
Mains 3 Uab/Ua Over Voltage (M3 Uab/Ua OverV)
AC input 3 voltage between Line A and Line B above over voltage threshold.
--
Mains 3 Ubc/Ub Over Voltage (M3 Ubc/Ub OverV)
AC input 3 voltage between Line B and Line C above over voltage threshold.
--
Mains 3 Uca/Uc Over Voltage (M3 Uca/Uc OverV)
AC input 3 voltage between Line C and Line A above over voltage threshold.
--
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
66 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
Mains 1Uab/Ua Under Voltage (M1Uab/Ua UnderV)
AC input 1 voltage between Line A and Line B below under voltage threshold.
--
Mains 1Ubc/Ub Under Voltage (M1Ubc/Ub UnderV)
AC input 1 voltage between Line B and Line C below under voltage threshold.
--
Mains 1Uca/Uc Under Voltage (M1Uca/Uc UnderV)
AC input 1 voltage between Line C and Line A below under voltage threshold.
--
Mains 2Uab/Ua Under Voltage (M2Uab/Ua UnderV)
AC input 2 voltage between Line A and Line B below under voltage threshold.
--
Mains 2Ubc/Ub Under Voltage (M2Ubc/Ub UnderV)
AC input 2 voltage between Line B and Line C below under voltage threshold.
--
Mains 2Uca/Uc Under Voltage (M2Uca/Uc UnderV)
AC input 2 voltage between Line C and Line A below under voltage threshold.
--
Mains 3Uab/Ua Under Voltage (M3Uab/Ua UnderV)
AC input 3 voltage between Line A and Line B below under voltage threshold.
--
Mains 3Ubc/Ub Under Voltage (M3Ubc/Ub UnderV)
AC input 3 voltage between Line B and Line C below under voltage threshold.
--
Mains 3Uca/Uc Under Voltage (M3Uca/Uc UnderV)
AC input 3 voltage between Line C and Line A below under voltage threshold.
--
AC Input MCCB Trip (Input MCCB Trip)
Main input circuit breaker open.
--
AC Output MCCB Trip (OutputMCCB Trip)
Main output circuit breaker open.
--
SPD Trip (SPD Trip)
Surge protection device tripped.
--
Communication Fail (Comm Fail)
AC distribution monitoring device has lost communications with the Controller.
Check communications cables.
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 2. Operation 67
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
LargeDU DC Distribution Alarms (Large Distribution Unit must be present in system) (DC Distributi)
DC Over Voltage (DC Over Volt)
DC output voltage above over voltage threshold.
--
DC Under Voltage (DC Under Volt)
DC output voltage below under voltage threshold.
--
DC Output 1 Disconnected (Output1 Discon)
Output #1 distribution device open.
--
...
...
DC Output 64 Disconnected (Output64 Discon)
Output #64 distribution device open.
--
Communication Fail (Comm Fail)
DC distribution monitoring device has lost communications with the Controller.
Check communications cables.
Temperature 1 Over Temperature (T1 Over Temp)
Temperature sensor #1 sensing temperature higher than over temperature threshold.
--
Temperature 2 Over Temperature (T2 Over Temp)
Temperature sensor #2 sensing temperature higher than over temperature threshold.
--
Temperature 3 Over Temperature (T3 Over Temp)
Temperature sensor #3 sensing temperature higher than over temperature threshold.
--
Temperature 1 Under Temperature (T1 Under Temp)
Temperature sensor #1 sensing temperature lower than under temperature threshold.
--
Temperature 2 Under Temperature (T2 Under Temp)
Temperature sensor #2 sensing temperature lower than under temperature threshold.
--
Temperature 3 Under Temperature (T3 Under Temp)
Temperature sensor #3 sensing temperature lower than under temperature threshold.
--
Temperature 1 Sensor Failure (T1 Sensor Fail)
Temperature sensor #1 failure.
--
Temperature 2 Sensor Failure (T2 Sensor Fail)
Temperature sensor #2 failure.
--
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
68 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
Temperature 3 Sensor Failure (T3 Sensor Fail)
Temperature sensor #3 failure.
--
Diesel Generator Group Alarms (Dsl Gen Group)
Diesel Generator Test Running (Test Running)
Diesel test in progress.
--
Diesel Generator Test Failure (Test Failure)
Diesel test failed.
--
Diesel Generator Alarms (Dsl Generator)
Low DC Voltage (Low DC Voltage)
Generator has low DC voltage.
--
Diesel Generator Supervision Fai (SupervisionFail)
Generator monitoring device has failed.
--
Diesel Generator Failure (Diesel Fail)
Generator has failed.
--
Diesel Generator Connected (Diesel Connect)
Generator is connected to the system.
--
Low Fuel Level (Low Fuel Level)
Generator has low fuel level.
--
High Water Temperature (High Water Temp)
Generator has high water temperature.
--
Low Oil Pressure (Low Oil Press)
Generator has low oil pressure.
--
Rectifier Group 2 [3, 4] Alarms (Rect Group 2 [3, 4])
All Rectifiers Comm Fail (AllRectCommFail)
No response from all rectifiers.
Check the connectors and cables or the CAN loop. Replace the Controller.
Rectifier Lost (Rectifier Lost)
A rectifier cannot be detected by the Controller.
Reset the Rectifier Lost alarm. Replace defective rectifier.
Comm Failure (Comm Failure)
A rectifier has lost communications with the Controller.
Reset the Comm Fail alarm. Replace defective rectifier.
Mains Failure (Mains Failure)
Rectifier commercial AC input power failure.
--
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 2. Operation 69
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
Group 2 [3, 4] Rectifier Alarms (Group 2 [3, 4] Rect)
AC Input Failure (AC Failure)
No AC input power to a rectifier.
Check why no AC input power available.
Rect Temperature High (Rect Temp High)
A rectifier has a high temperature condition.
Check why temperature is high.
Rectifier Fault (Rect Fault)
A rectifier has a fault condition.
Refer to Rectifier User Manual for troubleshooting information.
Over Voltage (Over Voltage)
A rectifier has an over voltage condition.
Rectifier Protected (Rect Protected)
A rectifier is in protected mode.
Fan Failure (Fan Failure)
A rectifier’s fan has failed.
Replace fan.
Current Limit (Current Limit)
A rectifier is in current limit.
Rectifier overload. The load is higher than rectifier capacity. If the batteries are being recharged, the alarm will cease by itself when the battery voltage has increased to the charging level. If the system load is higher than the rectifier capacity, the batteries will discharge. If this is the reason, install additional rectifiers. If one or more of the rectifiers are defective, replace the faulty rectifiers.
Rectifier Communication Fail (Rect Comm Fail)
A rectifier has lost communications with the Controller.
Check communications cables. Reset the Communication Fail alarm. Replace the rectifier.
Derated (Derated)
A rectifier is in output power derating mode.
Refer to Rectifier User Manual for troubleshooting information.
Current Share Alarm (CurrShare Alarm)
A rectifier has a current sharing alarm.
Low AC Voltage Protection (Low AC Protect)
A rectifier is in under voltage protection mode.
SMDUP Alarms (SM-DU+ Module must be present in system) (SMDUP)
Communication Fail (Comm Fail)
Communications failure.
Check communications cables.
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
70 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
Current1 High Current (Curr 1 Hi)
Current 1 high.
--
Current1 Very High Current (Curr 1 Very Hi)
Current 1 very high.
--
--
--
Current25 High Current (Curr 25 Hi)
Current 25 high.
--
Current25 Very High Current (Curr 25 Very Hi)
Current 25 very high.
--
SMBRC Unit Alarms (SM-BRC Module must be present in system) (SMBRC Unit)
Communication Fail (Comm Fail)
Communications failure.
Check communications cables.
Ambient High Temperature (Amb Temp High)
Ambient high temperature alarm.
--
Ambient Low Temperature (Amb Temp Low)
Ambient low temperature alarm.
--
Ambt Temp Not Used (Amb Temp No Use)
No ambient temperature sensor.
--
Fuel Tank Group Alarms (Fuel Tank Grp)
Fuel Group Communication Failure (Fuel Comm Fail)
Fuel tank group communication failure.
Check communications cables.
Fuel Tank Alarms (Fuel Tank)
High Fuel Level Alarm (Hi Level Alarm)
Fuel tank high level alarm.
--
Low Fuel Level Alarm (Low Level Alarm)
Fuel tank low level alarm.
--
Fuel Theft Alarm (Fuel Theft Alm)
Fuel tank theft alarm.
--
Tank Height Error (Tank Height Err)
Fuel tank height error.
--
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 2. Operation 71
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
Fuel Tank Config Error (Fuel Config Err)
Fuel tank configuration error.
--
SM Temp Group (SM-Temp Module must be present in system) (SM Temp Group)
SM Temp Lost (SMTemp Lost)
SM-Temp cannot be detected by the Controller.
Reset the SMTemp Lost alarm. Replace defective SM-Temp.
SM Temp 1-8 (SM-Temp Module must be present in system) (SMTemp 1-8)
Communication Interrupt (Comm Interrupt)
SM-Temp has lost communications with the Controller.
Check communications cables.
Temperature Probe 1 Shorted (Probe1 Short)
Probe shorted.
Replace temperature probe.
Temperature Probe 8 Shorted (Probe8 Short)
Probe shorted.
Temperature Probe 1 Open (Probe1 Open)
Probe open.
Replace temperature probe.
Temperature Probe 8 Open (Probe8 Open)
Probe open.
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
Available Alarms
72 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Table 4
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)

2.7 Power Split Feature

In Power Split applications, the output of the power system controlled by the ACU+ can be connected in parallel with an existing power system. Each system is controlled independently via its own Controller. The ACU+ power system is referred to as the "slave" system and the existing power system as the "master" system. The Power Split feature controls the ACU+ power system’s output voltage and rectifiers' current limit so that the "slave" power system shares the load with the "master" system.
Optional Functions: The ACU+ Controller can mimic the equalize and battery test functions of the “master”
system’s Controller. In addition, the ACU+ Controller can mimic the low voltage load disconnect and/or low voltage battery disconnect functions of the “master” system. This is accomplished by supplying digital signals from the “master” system’s Controller to the ACU+. This allows these functions to remain active in the “master” system.

2.7.1 Overview

See 1.3.7 Power Split Feature.

2.7.2 How Power Split Works

There are four User adjustable parameters for Power Split. They are:
Slave Curr Lmt: Current limit point for power system designated as the slave system in a "Power
Split" configuration.
Delta Volt: The offset voltage that the power system designated as the slave system in a "Power
Split" configuration is set to. It is suggested to leave this value at the default (0.5 volts).
Proportion Coeff: The proportional coefficient that the power system designated as the slave system
in a "Power Split" configuration is set to. It is suggested to leave this value at the default (30%).
Integral Time: The integral time that the power system designated as the slave system in a "Power
Split" configuration is set to. It is suggested to leave this value at the default (60 seconds). The ACU+ Controller uses these parameters to control the load sharing operation between the two power
systems. Depending on the systems’ configurations, their rectifier capacities, their distribution load capacities, and
the Power Split configuration; four operating modes can occur.
Low Load Operation
When the total load current demand is lower than the SLAVE CURRENT LIMIT value, the ACU+ power system voltage will be increased by the programmed DELTA VOLTAGE setting forcing the ACU+ power system to carry the load. Make sure that the output voltage does not exceed the battery float range recommended by the manufacturer. In this operating mode, no current will be delivered by the existing power system.
Normal Load Operation
When the total load current demand reaches the SLAVE CURRENT LIMIT value, the ACU+ power system operates in output current limit and its output voltage will be decreased (up to the DELTA VOLTAGE setting) in order to regulate the current, allowing the existing power system to deliver the remaining current. Both the ACU+ power system and the existing power system are now providing current to the load.
High Load Operation
If current demand increases and the existing power system reaches its current limit setting, float voltage will again begin to decrease. When the voltage falls below the float setting minus the DELTA VOLTAGE setting, the ACU+ system will come out of current limit and now deliver the additional current necessary to satisfy the load. This operation may occur when the batteries are being recharged, such as after a commercial AC failure.
Chapter 2. Operation 73
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
Over Load Operation
If the load current is greater than the combined current capacities of the ACU+ system and the existing power system, both power systems will go into current limit. Both systems and the batteries will feed the load. The output voltage will depend on the conditions of the batteries. This operation occurs if the total capacity of the rectifiers is too low in relation to the need for increased current.

2.7.3 Operating Modes

Figure 5 illustrates the four modes of operation described above. The Normal Load Operation is considered to be the normal mode. In this mode both the ACU+ system
and the existing parallel power system are both delivering load current. This is main purpose of using Power Split, to avoid putting the burden of delivering the entire load onto one of the two power systems.

2.7.4 Requirements and Conditions

The two DC power systems must be connected in parallel as described in “2.7.5. Paralleling the Existing and ACU+ Power Systems”.
Before paralleling the two systems, the following conditions must be met for proper Power Split function.
Note: The control features of the combined system are limited to those of the original power system. Note: The same type of batteries with an equal amount of cells and the same charging voltages must be
used for both systems.
The float voltage, equalize voltage, and battery test voltage of the ACU+ power system must be set to
the same levels as that of the existing power system.
The remote sense, if available and connected, of both the ACU+ power system and existing power
system must be connected to the same point.
If batteries are used, they must be of the same type. All the functions specific to the existing power system and ACU+ power system and which depend on
the voltage or which act on the voltage must be disabled from the existing power system and ACU+
power system. This includes the following
any equalization function, any temperature compensation function, any charge control function, any battery discharge test function, and any invalid current alarm.
In lieu of this, if battery charging and battery test functions are implemented in the existing power
system, they can remain if signals for starting are connected from the control system of the existing
system to the ACU+ system.
74 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)

2.7.5 Paralleling the Existing and ACU+ Power Systems

Admonishments
General Safety
Danger: YOU MUST FOLLOW APPROVED SAFETY PROCEDURES.
Performing the following procedures may expose you to hazards. These procedures should be performed by qualified technicians familiar with the hazards associated with this type of equipment. These hazards may include shock, energy, and/or burns. To avoid these hazards:
a) The tasks should be performed in the order indicated. b) Remove watches, rings, and other jewelry. c) Prior to contacting any uninsulated surface or termination, use a voltmeter to
verify that no voltage or the expected voltage is present. d) Wear eye protection, and use recommended tools. e) Use double insulated tools appropriately rated for the work to be performed.
AC Input Voltages
Danger: This system operates from AC voltage capable of producing fatal electrical shock.
DC Input/Output Voltages
Danger: Connecting the ACU+ power system to an existing power system for “Power Split”
mode involves working on live equipment carrying live loads. This system produces DC power and may require battery to be connected to it. Although the DC voltage is not hazardously high, the rectifiers and/or battery can deliver large amounts of current. Exercise extreme caution not to inadvertently contact or have any tool inadvertently contact a battery terminal or exposed wire connected to a battery terminal. NEVER allow a metal object, such as a tool, to contact more than one termination at a time, or to simultaneously contact a termination and a grounded object. Even a momentary short circuit can cause explosion and injury. Remove watches, rings, or other jewelry before connecting leads. Cover any live busbars with a canvas sheet to prevent short circuits caused by falling tools or parts.
Preparing the Existing and ACU+ Power Systems
Install and turn-up the ACU+ power system as describe in the installation instructions furnished with
the power system.
Set the float voltage on both the existing and ACU+ power systems to the same level. Temperature
compensation functionality, if used, should be disabled on both power systems.
Paralleling the Systems
Connect the Battery and Battery Return busbars of the ACU+ Power System to the main charge
busbars (rectifier side of the shunt) on the parallel power system. Size the cable for the largest current between systems.
Note 1: The connections between the two power systems should be done with power cables
appropriately sized to be capable of carrying the maximum current that can circulate between the two power systems.
Chapter 2. Operation 75
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
Note 2: If the parallel power system incorporates a main plant shunt, the connections of the cables
from the ACU+ power system to the parallel power system shall be made on the main charge busbars (rectifier side of the shunt).
Note 3: To compensate for voltage drop, it is recommended to connect the ACU+ power system’s
remote sense leads (if available) to the same point of sensing as the parallel power system.
Note 4: There shall be only one battery return reference (BRR) cable for the two power systems. If
the cable is appropriately sized on the parallel power system, keep it as the BRR for both power systems. If the cable is not appropriately sized on the parallel power system, install a new BRR cable and connect it preferably to the ACU+ power system since the parallel power system may eventually be phased out.
Note 5: If battery disconnect units (BDUs) are used on the new or parallel power system, these shall
be wired in such a way as to be all triggered simultaneously in order to prevent any overloading of these.
Note 6: For the size and number of bridge cables between the two power systems, take into
consideration the voltage drop, the available connecting points in each system, as well as the fact that these cables are unfused and shall therefore be run on a dedicated cable rack. “C” or “H” taps may be used to make full use of available connecting points.
Note 7: The legacy system retains the function of its controller and the percent of load on each plant
is controlled by the ACU+. Alarms may be sent individually from each plant, or combined using an ACU+ Interface Board and the programmable relays resident in the controller.
Note 8: Add a label on both power systems to indicate that these are operating in the Power Split
Mode with each other.
Optional Function Connections: The following signals from the existing system must be connected
to digital inputs of the ACU+ system interface board for these functions to be active: Equalize Charge in Progress, Battery Test in Progress, Load LVD Active, and Battery LVD Active. Otherwise disable these functions.
76 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)

2.7.6 Programming the ACU+ Power Split Feature

After an ACU+ power system has been connected to an existing power system and both systems set for the same float voltage, you will have to configure the Power Split parameters in the ACU+.
Procedure
1) Set the Power Split mode to slave. Navigate to Main Menu / Settings / Power System / General / Contactor Mode. Set this parameter to “Slave Control”.
2) Reboot the ACU+ by pressing ESC and ENT at the same time.
3) Navigate to Main Menu / Settings / Power System / Power Split.
4) Navigate to and set the “Slave Current Limit” to a value that will force the ACU+ system’s rectifiers to operate in current limiting mode.
Note: The Slave Current Limit must be set lower than the total distribution current from the two
plants. The default value is 60% of the ACU+ power system’s rectifier capacity.
5) Navigate to and set the “Delta Voltage”. This voltage is by default set to 0.5V but can be readjusted.
If the distribution current is lower than 50% of the total capacity of the ACU+ power system, the
“Delta Voltage” can be adjusted to a lower level than 0.5V to get a system voltage that is closer to the desired float charging voltage.
If the voltage drop between the existing system and the ACU+ system is expected to be >0.5V,
the “Delta Voltage” can be adjusted to a higher level than 0.5 V to get a correct split function.
Temperature controlled battery charging cannot be set in the ACU+ power system in power
split mode. If this function is implemented in the existing power system, a limited function within a temperature range of approximately ±15°C will be achieved if the Delta Voltage is set to a higher level, maximum 2.00V.
If the “Delta Voltage” 0.5V is considered to be too high, the split function can be tested at
various modes of operation to find a lower setting.
Optional Function Setup
Equalize Charge Setup
If the equalize charge function is to be used, equalize charge must be implemented in the existing power system and an equalizing signal from its control unit must be connected to the ACU+.
1) Navigate to Main Menu / Settings / Battery / Charge / EQ Voltage. Set the “EQ Voltage” to the
same value as the equalize voltage of the existing power system.
2) Using the Web Interface (Maintenance / Edit PowerSplit), select the ACU+ digital input
connected to the existing systems equalize control circuit.
Note: Equalize charging is controlled by the existing power system via an incoming digital signal.
The system will remain at the set equalize charge voltage level as long as this signal is active.
Battery Test Setup
If the battery test function is to be used, battery test must be implemented in the existing power system and a test signal from its control unit must be connected to the ACU+.
1) Navigate to Main Menu / Settings / Battery / Test.
2) Navigate to and set the “Test End Volt” to the same value as the end voltage of the existing
power system.
Chapter 2. Operation 77
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
3) Navigate to and set the “Test Volt Lmt” to the same value as the test voltage of the existing
power system.
4) Using the Web Interface (Maintenance / Edit PowerSplit), select the ACU+ digital input
connected to the existing systems battery test control circuit.
Note: Other settings in this menu regarding “Battery Test” are inactive. Note: Battery test is controlled by the existing power system via an incoming digital signal. The
system will remain at battery test as long as this signal is active.
Low Voltage Disconnect Setup
If low voltage disconnect functions are to be used, they must be implemented in the existing power system and signals from its control unit must be connected to the ACU+.
1) Using the Web Interface (Maintenance / Edit PowerSplit), select the ACU+ digital inputs
connected to the low voltage disconnect control circuits.
Temperature Compensated Battery Charge
There is no possibility to activate the “Temperature Compensated Battery Charge” function when the ACU+ power system is configured for “Power Split” mode.
However, the possibility to change the “Delta Voltage” enables the ACU+ power system to follow
the existing power system that has the functionality to a certain limit.
Example: The “Delta Voltage” in the ACU+ power system is set to 1.0V. The existing power system
is set to compensate 3.0 mV/cell/°C. This means that the ACU+ power system can follow the temperature compensation of the existing ;power system in the range of ±14°C from the set normal battery temperature (3.0 mV x 24 cells x 14°C = 1.008 V).
78 Chapter 2. Operation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)

2.7.7 Verifying the Operation of the Power Split Feature

After programming the “Power Split feature, verify its operation as follows.
a) In a Power Split application where the ACU+ power system is taking all of the load and the rectifiers
in the existing power system are all in the standby mode, use an external dry load bank of sufficient capacity to increase the load on the ACU+ power system over the “SLAVE CURRENT LIMIT” value.
1) Verify that the ACU+ power system limits the total output of its rectifiers to the current
equivalent to this programmed percentage.
2) Verify that the ACU+ power system lowers its output voltage by the value of the programmed
DELTA VOLTAGE”.
3) Verify that the rectifiers in the existing power system take the additional load as the load
increases pass the “SLAVE CURRENT LIMIT value.
4) Further increase the load in order to exceed the total capacity of the rectifiers in the existing
power system (or shut down some of the rectifiers in the existing power system if the capacity of the external dry load bank is not sufficient). Verify that the ACU+ power system starts taking the additional load as soon as the total capacity of the rectifiers in the existing power system is exceeded.
b) In a Power Split application where the ACU+ power system is taking only part of the load (operating
continuously at the current level equivalent to the programmed “SLAVE CURRENT LIMIT percentage) and the rectifiers in the existing power system are taking the rest of the load, use an external dry load bank of sufficient capacity to increase the load in order to exceed the total capacity of the rectifiers in the existing power system (or shut down some of the rectifiers in the existing power system if the capacity of the external dry load bank is not sufficient).
1) Verify that the ACU+ power system starts taking the additional load as soon as the total
capacity of the rectifiers in the existing power system is exceeded.
Chapter 2. Operation 79
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)

CHAPTER 3. LOCAL DISPLAY MENUS

3.1 Overview

This section provides descriptions of the Local Display Menus. Refer also to “2.2 Passwords and Access Levels and 3.3 Description of Local Display (and Web Interface) Menus Line Items. For WEB interface, refer to “Chapter 4. WEB Interface Menus.

3.2 Menus

Figure 8 provides flow diagrams of the menus accessed via the ACU+ Controller local display and keypad.
Note: These instructions describe the complete functionality of the ACU+. Some functionality is
dependent on hardware connected to the ACU+. Some menu items shown may not be present in the ACU+ used in your system.
80 Chapter 3. Local Display Menus
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)

3.2.1 Adjustment Range Restrictions

Float Voltage Setting
Cannot be adjusted higher than EQ Voltage setting. Cannot be adjusted lower than 1V (24V systems) or 2V (48V systems) above Under Voltage 1 Alarm”
setting or higher than 1V (24V systems) or 2V (48V systems) below Over Voltage 1 Alarm” setting.
EQ Voltage Setting
Cannot be adjusted lower than Float Voltage setting.
HVDS Limit
Cannot be adjusted lower than 0.5V above the EQ Voltage setting.
Under Voltage 1 Alarm Setting
Cannot be adjusted lower than Under Voltage 2 Alarm” setting. Cannot be adjusted higher than Over Voltage 1 Alarm” setting.
Under Voltage 2 Alarm Setting
Cannot be adjusted higher than Under Voltage 1 Alarm” setting.
Over Voltage 1 Alarm Setting
Cannot be adjusted higher than Over Voltage 2 Alarm” setting. Cannot be adjusted lower than Under Voltage 1 Alarm” setting.
Over Voltage 2 Alarm Setting
Cannot be adjusted lower than Over Voltage 1 Alarm” setting.
LVD1 and LVD2 Disconnect Setting
Cannot be adjusted higher than LVD Reconnect Voltage setting.
LVD1 and LVD2 Reconnect Setting
Cannot be adjusted lower than LVD Disconnect Voltage setting.
Chapter 3. Local Display Menus 81
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions
Main Menu
S ta tu s Settings ECO Mode Manual
09:20:20
Float Charge
##.#V ###A
Auto No Alm
Number of Rec 4
E N T
E S C
E N T
Main Menu
S ta tu s Settings
Select User
Admin
Enter Password
*
Select User
Admin
Enter Password
*
Select User
Admin
Enter Password
*
Select User
Admin
Enter Password
*
E N T
E S C
E N T
A
B
Main Screen Main Menu
E S C
Quick Setting
E N T
E S C
ECO Mode Manual
Quick Setting
Main Menu
S ta tu s Settings ECO Mode Manual Quick Setting
E N T
E S C
Main Menu
S ta tu s
Settings ECO Mode Manual
Quick Setting
E N T
E S C
Main Menu
S ta t us Settings ECO Mode Manual
Quick Setting
E N T
E N T
E N T
E N T
E S CE S C
E S C
E N T
C
E N T
D
E N T
E
*
*
*
*
* Note: Use or to move the cursor
to the Select User field. Press ENT to select a different User if required.
To select a User, press ENT to highlight the Select User field, and use or to select a User. Press ENT to select the User displayed in the Select User field. Note that only Users programmed into the ACU+ are shown. Users are programmed via the Web Interface.
Use or to move the cursor to the Enter Password field. Press ENT to enter a password.
To enter password, press ENT to highlight bit, and use or to choose character. Press ENT to accept and move to the next character. Press ENT again to accept password.
Press or to move cursor in MAIN MENU screen.
Press ENT to enter selected sub-menu.
Press or to move to next or previous screen.
E S C
E S C
E S C
E S C
INFO SCREENS (Returns to MAIN SCREEN after a preset time period.)
Date and time are alternately displayed.
In the MAIN SCREEN: Press ENT and , or ENT and at the same time to change the contrast of the LCD. Press , , and ESC at the same time to log out. Press ENT and ESC at the same time to reset the ACU+ Controller.
Local and Remote Access Passwords (set via the Web Interface) Maximum 13 Characters (0-9, a-z, A-Z, _ )
Access Level Default Password Authority
Once a password is entered, it remains in effect for a preset time period to allow navigating between menus without re-entering the password.
AUser has access to his/her level menus, plus all menus of the lesser access levels.
Level A (Browser) none set Browse System Information. Level B (Operator) none set Change System Control Settings. Level C (Engineer) noneset Modify System Parameters.
Download Configuration File.
Level D (Administrator) 1 Update OS Application.
Modify,Add, Delete User Information.
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
Figure 8 (cont’d on next page)
Local Menu Flow Diagrams
82 Chapter 3. Local Display Menus
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Status
Active Alarms
Power System
Rectifier
Battery
DC
AC
EIB
SMDU
Converter
SMDUP
SMTemp
Alarm History
Sys Inventory
E S C
A
E N T
Active Alarms Minor: 0 Major: 0 Critical: 2
System Voltage
54.0 V
System L oad
0.0 A
Mtnc Ru n Time
1.3 h
Alarm S tatus
No Alm
Power Split
Master
IB2 T2
21 deg. C ... SMTemp1T1
21 deg. C
DC Voltage
53.8 V
DC Current
8.5 A
Temperature
30 deg. C
DC S ta tus
On
AC On/Off
On
Rated Current
35 A
Walk-In
Disabled
Rectifier ID
1
Rect Phase
A
Rectifier SN
010700213
Running Time
200 h
AC Voltage
224 V
Rectifier
Rect Group Rect #1 Rect #2
1 Rect AC Mains Failure 081104 8:00:12 Critical
2 Power System CAN Comm Fail 081104 8:05:02 Critical
DC Voltage
54.0 V
Load C urrent
0.0 A
SYS Inve ntory
ACU+ Rect #1 Rect #2 EIB 1 IB 1 SMDUP 1 Conv #1 Conv #2 SMTemp 1
ENT
ENT
ENT
ENT
ENT
ENT
ESC
ESC
ESC
ESC
ESC
ESC
ESC
ESC
ESC
ENT
ENT
ENT
ESC
ESC
ENT
ENT
ESC
ENT
ESC
ENT
ENT
Press or to cycle through list of alarms. Press ESC to return to STATUS menu.
Press or to cycle through list of alarms.
ENT
ESC
1 IB2 DI3 Alarm 100629 12:18:35 100629 12:19:52
Device Name
ACU+
Part Number
M820D
Product Ver
001
SW Version
2.25
Serial Number
21024402512
ENT
ESC
ENT
ESC
Power System
DC
Alarm History
Minor: 0 Major: 0 Critical: 1
Press or to move cursor in STATUSscreen.
Press ENT to enter selected sub-menu.
ToView Parameters: Press or to move up and down list of parameters.
ToSelect a Sub-Menu: Press or to move cursor in menu screen (selects menu item).
Press ENT to enter selected sub-menu.
Note: For a complete list of alarms that can be displayed in the STATUS Active Alarm menus, see the table titled Available Alarmsin the Operation Chapter.
A3
ESC
A2
A5
A6
Average Voltage
52.0 V
Total Current
0.2 A
Number of Rects
2
Num Rects Comm
2
Sys Cap Used
0.9 %
Max Cap Used
3.4 %
Min Cap Used
0.0 %
Rated Voltage
52.0 V
AC Phases
Single Phase
Max Curr Limit
462.2 A
Total Rated Cur
382.0 A
Rect Group
Battery
AC
EIB
ESC
A4
SMDU
Converter
Similar information is displayed for each device in the system.
SMDUP
A7
SMTemp
Rect #1
A1
ENT
ESC
Temp.
Probes
set as
ambient
show up
here.
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 3. Local Display Menus 83
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 8 (cont’d from previous page, cont’d on next page)
Local Menu Flow Diagrams
UM1M820BNA User Instructions
ESC
A5
ENT
Output Voltage
48.2 V
Output Current
0.0 A
Temperature
25.0 deg. C
On/Off Status
On
Rated Current
xxx.x A
Converter ID
1
Converter SN
xxxxxx
Running Time
200 h
Conv #1
SMDUP 1
ESC
A6
ENT
SMDUP
SMDUP 1
Current 1
0.0 A ... Current 2 5
0.0 A Shunt S ettable
By Software
ESC
A3
ENT
ESC
A2
ENT
EIB
EIB 1
Block In-Use
8
Voltage 1
0.0 V
Voltage 2
0.0 V
Voltage 3
0.0 V
Voltage 4
0.0 V
Voltage 5
0.0 V
Voltage 6
0.0 V
Voltage 7
0.0 V
Voltage 8
0.0 V
EIB 1
Battery Voltage
53.8 V
TotalB att Curr
0.0 A
Comp Temp
21 deg. C
Short BOD Time
2 mi n
ShortBODCounter
8
Long BOD Time
1 mi n
LongBODCounter
7
Full BOD Time
0 mi n
FullBODCounter
1
Remaining Time
360.0 h r
LiBatt AvgTemp
20 deg. C
Num Installed
8
NumDisconnected
0
Num No Reply
0
InventUpdating
No
IB2 T1
21 deg. C
...
Batt Group
Battery Voltage
0.0 V
Battery Current
0.0 A
Batt Rating(Ah)
300 Ah
Batt Cap (%)
100.0 %
Battery
Batt G roup Battery 1 Battery 2 LiBattery1
ESC
A1
ENT
AC
Rect AC
Phase A Voltage
253 V
Phase B Voltage
253 V
Phase C Voltage
254 V
Battery 1
Batt Voltage
52.3 V
Batt Current
0.0 A
State of Charge
98.8%
Batt Term Volt
52.3 V
Cell Temp
21.0 de g. C
Switch Temp
21.0 de g. C
Batt LED Status
Full Green
LiBattery1
Rect AC
ESC
ENT
ENT
ESC
ENT
ESC
ESC
ENT
Converter
Conv Group Conv #1 Conv #2
ENT
ESC
ENT
ESC
SMTemp
ESC
A7
ENT
SMTemp
SMTemp1
SMTemp1 Temp1
21 deg. C ... SMTemp1 Temp8
21 deg. C ... SMTemp8 Temp1
21 deg. C ... SMTemp8 Temp8
21 deg. C TempT1 S tatus
Normal ... TempT8 S tatus
Normal
ENT
ESC
Average Voltage
52.0 V
Total Current
0.2 A
Number of Convs
2
Num Convs Comm
2
Rated Voltage
52.0 V
Total Rated Cur
xxx.x A
Max Curr Limit
31.3 A
Conv Group
ENT
ESC
ESC
A4
ENT
Bus Bar Voltage
54.0 V
Load 1 Current
0.0 A
SMDU 1
SMDU
SMDU Group SMDU 1
ENT
ESC
Num of SMDUs
1
SMDU Group
ENT
ESC
Temp.P robes set as battery show up here.
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
84 Chapter 3. Local Display Menus
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 8 (cont’d from previous page, cont’d on next page)
Local Menu Flow Diagrams
User Instructions UM1M820BNA
Settings
Alarm Setting
Power System
Rectifier
Battery
BattFuseUnit
DC
LVD
AC
EIB
SMDU
Converter
SMTemp
Communication
Controller
ESC
B1
B
B3
B2
ENT
ENT
ENT
ENT
ENT
ENT
ESC
ESC
ESC
B5
B4
ESC
ESC
ESC
ESC
ESC
ESC
ESC
ENT
ENT
ENT
ENT
ENT
ENT
Language
English
Date
2010-06-30
Time
13:04:10
Keypad Voice
On (on / off)
Reload Config
Yes
Download Config
Yes
Auto Config
Yes
DHCP
Disabled (enabled / disabled)
IP Address
126.50.143.70
Subnet Mask
255.255.255.0
Default Gateway
0.0.0.0
Rectifier
All Rect Set Rect #1 Rect #2
Rectifier ID
2 (1-999)
Rect Phase
B (A/ B / C)
HVSD
Enabled (enabled / disabled)
HVSD Limit
59.0 V (56.0-59.5) (28.0-29.7)
Restart on HVSD
Enabled (enabled / disabled)
HVSD Re start T
300 s (0-300)
Start Interval
0 s (0-10)
Walk-In
Enabled (enabled / disabled)
Walk-In Time
8 s (8-128)
Turn On ACOverV
No (no / yes)
ECO Mode
Disabled (enabled / disabled)
Best Oper Point
80 % (30-90)
Fluct Range
10 % (1-50)
Energy Save Pt
45 % (10-90)
Cycle Period
168 h (1-8760)
Rects ON Time
120 min (0-255)
Turn Off Delay
5 min (1-60)
Input Curr Lmt
30 A (1-50)
MixHE Power
Non-Derate (non-derate / derate)
DG Pwr Lmt
Enabled (disabled / enabled)
Diesel DI Input
None (none / Digital Input 1 / ... / Digital I nput8)
DG Pwr Lmt Pt
40.0 % (40-100)
Current Limit
Enabled (enabled / disabled)
Current Limit Pt
400 A (dependent on # of rectifiers)
ESC
ENT
ESC
ENT
AC
Rect AC
Nominal PH-Volt
220 V (50-450)
Mains Fai l Alm1
20 % (0.0-100.0)
Mains Fai l Alm2
20 % (0.0-100.0)
ENT
ESC
All Rect Set
Alarm Setting
Power System
Battery
LVD
EIB
Rect #1
Communication
Controller
Rect AC
ENT
ENT
ESC
B6
ESC
SMDU
B7
ESC
SMTemp
ESC
ENT
Shunt Current
150.0 A (50.0-50000.0)
Shunt Voltage
25.0 mV (1.0-150.0)
LoadShuntExist
No (No / Yes)
DC
Num of Bat Fuse
0
BattFuseUnit
Converter
All Conv Set Conv #1 Conv #2
Output Voltage
52.0 V (48.0-55.5)
Under Voltage
47.0 V (42.0-55.0)
Over Voltage
56.0 V (49.0-59.0)
Over Current
500 A (1-500)
HVSD
Enabled (enabled / disabled)
HVSD Limit
59.0 V (48.0-60.0)
Current Limit
Enabled (enabled / disabled)
Current Limit Pt
94 A (dependent on # of converters)
ESC
ENT
ENT
All Conv Set
Set Conv ID
1 (1-999)
ESC
Conv #1
ToSelect a Sub-Menu: Press or to move cursor in menu screen (selects menu item).
Press ENT to enter selected sub-menu.
ToChange a Parameter: Press or to move up and down list of parameters.
Press ENT to highlight selected parameter.
Press or to change highlighted value.
Press ENT to make the change. Press ESC to cancel the change.
The parameter values shown in ( ) are the adjustment range or acceptable values. Factory default settings are listed in the ACU+ Configuration Drawing (C-dwg) furnished with your system.
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 3. Local Display Menus 85
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 8 (cont’d from previous page, cont’d on next page)
Local Menu Flow Diagrams
UM1M820BNA User Instructions
Alarm Setting
Alm Severity
Alarm Relay
Alarm Param
Alm Severity or Alarm Relay
Power System Rect Group Rectifier Battery Group Battery SMDU Battery EIB Battery SM Battery LargeDU Batt SMBRC Battery OB Batt Fuse SMDU Bat Fuse DC Distr DC Fuse Unit SMDU DC Fuse SMDUP DC Fuse LVD Unit SMDU LVD LargeDU LVD Rectifier AC SMAC IB EIB SMDU 1 SMDU 2 SMDU 3 SMDU 4 SMDU 5 SMDU 6 SMDU 7 SMDU 8 Converter Grp Converter SMIO 1 SMIO Unit 3 SMIO Unit 4 SMIO Unit 5 SMIO Unit 6 SMIO Unit 7 SMIO Unit 8 LargeDUACDist AC Distributi DC Distributi Dsl Gen Group Dsl Generator Rect Group 2 Group 2 Rect Rect Group 3 Group 3 Rect Rect Group 4 Group 4 Rect SMDUP SMBRC Unit Fuel Tank Grp Fuel Tank SMTemp Group SMTemp 1 SMTemp 2 SMTemp 3 SMTemp 4 SMTemp 5 SMTemp 6 SMTemp 7 SMTemp 8
AC Failure
Major (none / minor / major / critical)
Rect TempHigh
Major (none / minor / major / critical)
Rect Fault
Major (none / minor / major / critical)
HVSD
Major (none / minor / major / critical)
(see Available Alarms Table for complete list of available alarms)
Alarm Voice
On (on / off / 3 min / 10 min / 1 hour / 4 hour)
Block Alarm
Normal (normal / blocked)
Clr Alm Hist
Yes
AC Failure
Relay # (none / relay 1 / ... / relay 13)
Rect Temp High
Relay # (none / relay 1 / ... / relay 13)
Rect Fault
Relay # (none / relay 1 / ... / relay 13)
HVSD
Relay # (none / relay 1 / ... / relay 13)
(see Available Alarms Table for complete list of available alarms)
ENT
ENT
ESC
ESC
ESC
ESC
ESC
ENT
ENT
ENT
ESC
B1
ENT
Rectifier
Rectifier
Alarm Param
ToChange a Parameter: Press or to move up and down list of parameters.
Press ENT to highlight selected parameter.
Press or to change highlighted value.
Press ENT to make the change. Press ESC to cancel the change.
The parameter values shown in ( ) are the adjustment range or acceptable values. Factory default settings are listed in the ACU+ Configuration Drawing (C-dwg) furnished with your system.
Note: After setting the Alarm Severity Level, press ENT and together to jump to the related Alarm Relay setting menu for this alarm. Press ENT and together again to return to the previous Alarm Severity Level screen.
ToSelect a Sub-Menu: Press or to move cursor in menu screen (selects menu item).
Press ENT to enter selected sub-menu.
Note: The Alarm Severity and Alarm Relay screens are the same so only one is shown here. Also, the alarms for the Device Groups is lengthy so only part of the alarms for the Rectifier Device Group is shown. See the table titled AvailableAlarmsin the Operation Chapter for a complete listing of the Device Groups alarms.
Alarm Severity Screen
Alarm Relay Screen
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
Figure 8 (cont’d from previous page, cont’d on next page)
Local Menu Flow Diagrams
86 Chapter 3. Local Display Menus
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA
Power S ystem
General
Power Split
Slave Curr Lmt
60 % (10-90)
Delta Volt
0.5 V (0.1-2.0)
Proportion Coeff
30.0 (0-100)
Integral Time
60 s (10-2000)
ENT
ENT
ESC
ESC
ESC
B2
ENT
Power Split
To Change a Parameter: Press or to move up and down list of parameters.
Press ENT to highlight selected parameter.
Press or to change highlighted value.
Press ENT to make the change. Press ESC to cancel the change.
The parameter values shown in ( ) are the adjustment range or acceptable values. Factory default settings are listed in the ACU+ Configuration Drawing (C-dwg) furnished with your system.
To Select a Sub-Menu: Press or to move cursor in menu screen (selects menu item).
Press ENT to enter selected sub-menu.
Auto/Man State
Auto (auto / manual)
Manual Mode Lmt
1 h (0-24)
Mtnc Cycle Time
360 days (10-7200)
EStop/EShutdown
Disabled (disabled / EStop / EShutdown)
Load Curr Alarm
3000 A (0-4000)
Alarm Blocked
Normal (n ormal / blocked)
Rect Expansion
Inactive ( i nactive / primary / secondary)
Address (Slave)
201 (201 / 202 / 203)
Over Voltage 1
57.0 V (40-60) (20-30)
Over Voltage 2
58.0 V (40-60) (20-30)
Under Voltage 1
48.0 V (40-60) (20-30)
Under Voltage 2
44.0 V (40-60) (20-30)
Fail Safe
enable (disabl e / enable)
Hybrid Mode
disable (disable / fixed daily / capacity)
DG Run Overtemp
enable (disabl e / enable)
DG Run Time
60 min (30-120)
DG Used
DG1 (DG1 / DG2 / Both)
DI for Grid
DI3 (DI1 / ... / DI8)
DOD
40.0 % (2 0-80)
Dsch Duration
12 hours (1-22)
Start Dsch Time
19 clock (0-24)
High Load Set
40.0 % (2 0-80)
Equal StartTime
8 clock (0 -24)
DG Alarm Delay
60 sec. (30-180)
Fail Safe
Normally Open (normally open / normally close)
Contactor Mode
Master Ctrlr (Master Ctrlr / Slave Ctrlr)
Relay Test
Disabled (disabled / automatic / in dividual)
Relay Test Time
45 sec. (0-120)
HighLoadLevel1
70% (0-100)
HighLoadLevel2
85% (0-100)
DI1 Alarm State
High (Low / High) ... DI8 Alarm State
High (Low / High) Amb Temp Sensor
IB2 T2 (None / SMTemp8 T8 / ... / SMTemp8 T1 / ... /
SMTemp1 T8 / ... / SMTemp1T1 / EIB T2 / EIB T1 / IB2 T2 / IB2 T1 / System T3 / System T2 / System T1 / Average / Maximum)
Amb Temp High2
100.0 deg. C (-40 to +100)
Amb Temp High1
90.0 deg. C (-40 t o +100)
Amb Temp Low
-10.0 deg. C (-40 to +100)
System Temp1
None (None / Battery / Ambient) System Temp2
None (None / Battery / Ambient) System Temp3
None (None / Battery / Ambient) IB2 Temp1
Battery (None / Battery / Ambient) IB2 Temp2
Ambient (None / Battery / Ambient) EIB Temp1
None (None / Battery / Ambient) EIB Temp2
None (None / Battery / Ambient)
Special
Configurations
Only
General
The temperature monitored by the
Temp.P robe selected
here is displayed on
the Homepage of
the Web Interface.
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 3. Local Display Menus 87
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 8 (cont’d from previous page, cont’d on next page)
Local Menu Flow Diagrams
UM1M820BNA User Instructions
Battery
Basic
Charge
Test
TempC omp
Capacity
Battery 1
Num Batt Shunts
1 (0-2)
Calc Batt Curr
No (no / yes)
Low Capacity Pt
75 % (25-100)
Current Limited
No (no / yes)
BTRM TempSensor
IB2 T2 (None / SMTemp8 T8 / ... / SMTemp8 T1 / ... /
SMTemp1T8 / ... / SMTemp1T1 / EIB T2 / EIB T1 / IB2 T2 / IB2 T1 / System T3 / System T2 / System T1 / Average SMBRC / Average / Maximum)
BTRM Temp High2
100.0 deg. C (0-100)
BTRM Temp High1
90.0 deg. C (0-100)
BTRM Action
Disabled (disabled / lower voltage)
BTRM Voltage
51.0 V (45-55) (22.5-27.5)
ABCL Point
20A (1-60)
Float Voltage
54.0 V (42.0-58.0) (21.0-29.0)
EQ Voltage
56.5 V (42.0-58.0) (21.0-29.0)
Batt Curr Limit
0.10 C10 (0.10-0.25)
Over Curr Lmt
0.30 C10 (0.30-1.00)
Auto EQ
No (no / yes)
EQ Start Curr
0.060 C10 (0.040-0.080)
EQ Start Cap
80.0 % (0-99)
EQ Stop Curr
0.010 C10 (0.002-0.020)
EQ Stop Delay
180 min (0-1440)
Maximum EQ Time
1080 min (60-2880)
Cyc EQ
No (no/yes)
Cyc EQ Interval
100 days (2-365)
Cyc EQ Duration
720 min (30-2880)
Test Volt Lmt
45.0 V (43.0-53.5) (21.5-27.0)
Test End Volt
45.2 V (43.2-53.5) (21.5-27.0)
End Test Time
100 min (10-1440)
EndTestCapacity
70 % (0-100)
RecordThreshold
0.100 V (0.100-1.000)
AC Fail Test
Disabled (disabled / enabled)
Planned Tests
0 (0-12)
Test 1 (M-D Hr)
10-21 10
Const Curr Test
Disabled (disabled / enabled)
ConstCurrT Curr
9999.0 A (1-9999)
Short Test
Disabled (disabled / enabled)
ShortTest Cycle
30 days (1-365)
Short Test Time
5 min (1-60)
Max Diff Curr
0.05 C10 (0.00-1.00)
BattTestLowCap
99 % (70-100)
Temp CompCenter
25.0 deg. C (0.0-40.0)
Temp Comp Coeff
72.0 mV/deg. C (0.0-500.0)
TempCompSensor
None (None / SMTemp8 T8 / ... / SMTemp8 T1 / ... /
SMTemp1T8 / ... / SMTemp1 T1 / EIB T2 / EIB T1 / IB2 T2 / IB2 T1 / System T3 / System T2 / System T1 / Average SMBRC / Average / Maximum)
Comp Temp High2
60 deg. C (0-100)
Comp Temp High1
50 deg. C (0-100)
Comp Temp Low
-10.0 deg. C (-40 to +100)
Temp Comp Max V
29.0 (42.0-58.0) (2 1.0-29.0)
Temp Comp Clamp
Enabled (disabled / enabled)
Temp Comp Min V
26.0 (42.0-58.0) (2 1.0-29.0)
Charging Eff
96 % (1 0-100)
Time 0.1C10
10.00 h (0.00-10.00)
Time 0.2C10
4.90 h (0 .00-10.00)
Time 0.3C10
3.00 h (0 .00-10.00)
Time 0.4C10
2.00 h (0 .00-10.00)
Time 0.5C10
1.40 h (0 .00-10.00)
Time 0.6C10
1.20 h (0 .00-10.00)
Time 0.7C10
1.10 h (0 .00-10.00)
Time 0.8C10
0.90 h (0 .00-10.00)
Time 0.9C10
0.70 h (0 .00-10.00)
Time 1.0C10
0.50 h (0 .00-10.00)
Rated Capacity
600.0 Ah (50.0-50000.0)
Shunt Current
800.0 A (50.0-50000.0)
Shunt Voltage
25.0 mv (1.0-150.0)
ENT
ENT
ENT
ENT
ENT
ESC
ESC
ESC
ESC
ESC
ESC
ENT
ESC
B3
ENT
Basic
Charge
Test
TempCo mp
Capacity
Battery 1
To Change a Parameter: Press or to move up and down list of parameters.
Press ENT to highlight selected parameter.
Press or to change highlighted value.
Press ENT to make the change. Press ESC to cancel the change.
The parameter values shown in ( ) are the adjustment range or acceptable values. Factory default settings are listed in the ACU+ Configuration Drawing (C-dwg) furnished with your system.
To Select a Sub-Menu: Press or to move cursor in menu screen (selects menu item).
Press ENT to enter selected sub-menu.
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
88 Chapter 3. Local Display Menus
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 8 (cont’d from previous page, cont’d on next page)
Local Menu Flow Diagrams
User Instructions UM1M820BNA
ESC
B5
ENT
EIB
EIB 1
Shunt 1 Current
500.0 A (50.0-50000.0)
Shunt 1 Voltage
75.0 mV (1.0-150.0)
Shunt 2 Current
500.0 A (50.0-50000.0)
Shunt 2 Voltage
75.0 mV (1.0-150.0)
Shunt 3 Current
500.0 A (50.0-50000.0)
Shunt 3 Voltage
75.0 mV (1.0-150.0)
Num Batt Shunts
0 (0-3)
Num Load Shunts
0 (0-3)
Voltage Type
48 (Block 4) (disable / 24 (block 2) /
midpoint / 48 (block 4))
Blk V Diff(12V)
1 (0 - 2)
Blk V Diff(Mid)
1 (0 - 2)
Block In-Use
0 (0-8)
EIB 1
ESC
B7
ENT
SMTemp
SMTemp 1
T1 Assign Equip
Ambient (None / Battery / Ambient) ... T8 Assign Equip
None (None / Battery / Ambient)
SMTemp 1
ESC
B6
ENT
SMDU
SMDU 1
Shunt 1 Voltage
75 mV (25-75)
Shunt 1 Current
500 A (100-2000)
Shunt 2 Voltage
75 mV (25-75)
Shunt 2 Current
500 A (100-2000)
Shunt 3 Voltage
75 mV (25-75)
Shunt 3 Current
500 A (100-2000)
Shunt 4 Voltage
75 mV (25-75)
Shunt 4 Current
500 A (100-2000)
Shunt 5 Voltage
75 mV (25-75)
Shunt 5 Current
500 A (100-2000)
SMDU 1
ESC
B4
ENT
ENT
LVD
LVD Group
LVD Unit
SMDU 1 LVD
HTD Recon Point
38.0 deg. C (20-80)
HTD Point
40.0 deg. C (20-80)
LVD Group
ESC
LVD1
Enable (enable / disable)
LVD1 Mode
Voltage (voltage / time)
LVD1 Volt
42.0 V (40-60) (20-30)
LVD1 Recon Volt
49.0 V (40-60) (20-30)
LVD1 ReconDelay
1 min (1-30)
LVD1 Time
300 min (30-1000)
LVD1 Dependency
None (none / LVD1 / LVD2)
LVD2
Enable (enable / disable)
LVD2 Mode
Voltage (voltage / time)
LVD2 Volt
42.0 V (40-60) (20-30)
LVD2 Recon Volt
49.0 V (40-60) (20-30)
LVD2 ReconDelay
1 min (1-30)
LVD2 Time
600 min (30-1000)
LVD2 Dependency
None (none / LVD1 / LVD2)
HTD1
Disable (enable / disable)
HTD2
Disable (enabled / disable)
LVD Type
Bistable (bistable / mono-stable / mono w/sample)
LVD Unit
LVD 1
Enable (enable / disable)
LVD 1 Mode
Voltage (voltage / time)
LVD 1 Voltage
42.0 V (40-60) (20-30)
LVD1 Recon Volt
49.0 V (40-60) (20-30)
LVD1 ReconDelay
1 min (1-30)
LVD 1 Time
300 min (30-1000)
LVD1 Dependency
None (none / LVD1 / LVD2)
LVD 2
Enable (enable / disable)
LVD 2 Mode
Voltage (voltage / time)
LVD 2 Voltage
42.0 V (40-60) (20-30)
LVD2 Recon Volt
49.0 V (40-60) (20-30)
LVD2 ReconDelay
1 min (1-30)
LVD 2 Time
600 min (30-1000)
LVD2 Dependency
None (none / LVD1 / LVD2)
HTD 1
Disable (enable / disable)
HTD 2
Disable (enabled / disable)
SMDU 1 LVD
ENT
ESC
ENT
ESC
Displayed when Voltage Type
set for other then disableand
Block In-Useset for other then 0.
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Chapter 3. Local Display Menus 89
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 8 (cont’d from previous page, cont’d on next page)
Local Menu Flow Diagrams
UM1M820BNA User Instructions
Manual
Man/Auto Set
Power System
Rectifier
Batt Group
LVD
EIB
Converter
SMTemp
Note
Items marked with an asterisk (*) can be changed while in Auto Mode. Before any other settings in the Manual submenus can be changed, you must first place the controller into Manual Mode. Use the MAN/AUTO SET menu to change the Controller from Auto Mode to Manual Mode.
When you return to Auto Mode, any settings changed in Manual Mode are returned to their previous setting (setting before being placed in Manual Mode).
D
ENT
ENT
ENT
ENT
ENT
ENT
ESC
ESC
ESC
ESC
ESC
ESC
Auto/Man State
Auto (auto / manual)
Relay Output 1
Active (active / not active) ... Relay Output 8
Active (active/ not active) Clr MtncRunTime
Yes
ENT
ECO Mode
Enabled (disabled / enabled)
Best Ope r Point
80 % (30-90)
Energy Save Pt
45 % (10-90)
Fluct Ran ge
10 % (1-50)
Cycle P eriod
168 hour (1-8760)
Rects ON Time
120 min (0-255)
Turn Off Delay
5 min (1-60)
C
ENT
ESC
ECO Mode
Man/Auto Set
Power System
ToChange a Parameter: Press or to move up and down list of parameters.
Press ENT to highlight selected parameter.
Press or to change highlighted value.
Press ENT to make the change. Press ESC to cancel the change.
The parameter values shown in ( ) are the adjustment range or acceptable values. Factory default settings are listed in the ACU+ Configuration Drawing (C-dwg) furnished with your system.
ToSelect a Sub-Menu: Press or to move cursor in menu screen (selects menu item).
Press ENT to enter selected sub-menu.
ESC
ESC
LVD
LVD Group LVD Unit
ENT
LVD1 Control
Connected (disconnected)
LVD2 Control
Connected (disconnected)
LVD Unit
SMTemp
SMTemp Group SMTemp 1 SMTemp 2
ENT
ESC
ESC
Converter Trim
42.0V (42.0-58.0)
DC O n/Off Ctrl
Switch On All (Switch Off All / Switch On All)
Conv LED Ctrl
Stop Flashing (All Flashing / Stop Flashing)
Fan Speed Ctrl
Auto Speed (Full Speed / Auto Speed)
Confirm I D
Yes
Clear Conv Lost
Clear
Clear Comm Fail
Yes
ClrAllCommFail
Yes
All Conv Ctrl
DC O n/Off Ctrl
On (On / Off)
Over Volt Reset
On (On / Off)
LED Control
Cancel (Flash / Cancel)
Conv #1
Converter
All Conv Ctrl Conv #1 Conv #2
ENT
*
*
Rectifier
All Rect Ctrl Rect #1 Rect #2
EQ/FLT Control
Float Charge (equalize charge)
BattTestControl
Stop (start)
Reset B att Cap
Yes
Clr B ad Bat Alm
Yes
Clr L iBatt Lost
Clear
ClrLiBatComFail
Clear
Clr AbnlCur Alm
Yes
Clr C u r Imb Alm
Yes
ClrBatTestFail
Yes
ENT
ESC
ESC
Rectifier Trim
53.9 V (42.0-58.0) (21.0-29.0)
DC On/Off Ctrl
Switch On All (switch off all)
AC On/Off Ctrl
Switch On All (switch off all)
Rect LED Ctrl
Stop Flashing (all flashing)
Fan Speed Ctrl
Auto Speed (full speed)
Confirm ID/PH
Yes
Clear Rect Lost
Clear
Reset Cycle Alm
Clear
Clear Comm Fail
Yes
ENT
Batt G roup
All Rect Ctrl
DC On/Off Ctrl
On (on / off)
AC O n/Off Ctrl
On (on / off)
LED Control
LED Control (LED control / cancel)
Rectifier Reset
Reset
Rect #1
*
*
*
*
*
*
*
*
*
*
*
*
*
*
EIB 1
Relay Output 9
Active (active/ not active)
Relay Output 10
Active (active/ not active)
Relay Output 11
Active (active/ not active)
Relay Output 12
Active (active/ not active)
Relay Output 13
Active (active/ not active)
ESC
EIB
EIB 1
ENT
ESC
ENT
ENT
ESC
*
*
*
*
ENT
ESC
ESC
Clr SMTemp Lost
Clear *
SMTemp Group
Clr Probe Alm
Clear *
SMTemp 1
ENT
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
90 Chapter 3. Local Display Menus
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 8 (cont’d from previous page, cont’d on next page)
Local Menu Flow Diagrams
User Instructions UM1M820BNA
Quick Setting
Auto/Manual
ECO Mode S et
FLT/EQ Volt
FLT/EQ Set
Temp Comp
RectExpansion
E
ENT
ENT
ENT
ENT
ENT
ENT
ENT
ESC
ESC
ESC
ESC
ESC
ESC
ESC
Auto/Man State
Auto (auto / manual)
Float Voltage
54.0 V (42.0-50.0) (21.0-29.0)
EQ Voltage
56.5 V (42.0-58.0) (21.0-29.0)
Rect Expansion
inactive (inactive / primary / secondary)
Address (Slave)
201 (201 / 202 / 203)
Auto/Manual
ECO Mode Set
FLT/EQ Volt
FLT/EQ Set
Temp Comp
Rect E xpansion
To Change a Parameter: Press or to move up and down list of parameters.
Press ENT to highlight selected parameter.
Press or to change highlighted value.
Press ENT to make the change. Press ESC to cancel the change.
The parameter values shown in ( ) are the adjustment range or acceptable values. Factory default settings are listed in the ACU+ Configuration Drawing (C-dwg) furnished with your system.
To Select a Sub-Menu: Press or to move cursor in menu screen (selects menu item).
Press ENT to enter selected sub-menu.
ECO Mode
Enabled (disabled / enabled)
Energy Save Pt
45 % (10-90)
Best Oper Point
80 % (30-90)
Fluct Range
10 % (1-50)
Cycle Period
168 hour (1-8760)
Rects ON Time
120 min (0-255)
Turn Off Delay
5 min (1-60)
Auto E Q
No (no / yes)
EQ S tart Curr
0.060 C10 (0.040-0.080)
EQ S tart Cap
80.0 % (0-99)
EQ S top Curr
0.010 C10 (0.002-0.020)
EQ S top Delay
180 min (0-1440)
Maximum EQ Time
1080 min (60-2880)
Cyc EQ
No (no / yes)
Cyc EQ Interval
100 days (2-365)
Cyc EQ Duration
720 min (30-2880)
TempCompCenter
25.0 deg. C (0.0-40.0)
TempComp Coeff
72.0 mV/deg. C (0.0-500.0)
TempComp Sensor
None (None / S MTemp8T8 / ... / SMTemp8 T1 / ... /
SMTemp1T8 / ... / SMTemp1T1 / EIB T2 / EIB T1 / IB2 T2 / IB2 T1 / System T3 / System T2 / System T1 / Average SMBRC / Average / Maximum)
Comp Temp High2
60 deg. C (0-100)
Comp Temp High1
50 deg. C (0-100)
Comp Temp Low
-10.0 deg. C (-40 to + 100)
TempComp Clamp
Enabled (disabled / enabled)
TempComp Max V
29.0 (42.0-58.0) (21.0-29.0)
TempComp Min V
26.0 (42.0-58.0) (21.0-29.0)
The temperature monitored by the
Temp. Probe selected
here as the TempComp
Sensor is also displayed
on the H omepage of
the Web Interface as
battery temperature.
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Figure 8 (cont’d from previous page)
Local Menu Flow Diagrams
Chapter 3. Local Display Menus 91
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)

3.3 Description of Local Display (and Web Interface) Menus Line Items

The following are descriptions of the editable parameters presented in the local display menus. Parameter descriptions can also be used for the WEB Interface menus. Note that the names in the WEB Interface menus may be longer since the WEB Interface allows more characters to be displayed then the local (LCD) display.

3.3.1 Settings Menu

Alarm Setting
Alarm Severity Menu Menu Navigation: Main Menu / Settings / Alarm Setting / Alm Severity
Note: For WEB Interface, menu item is found under Configuration / Signal Information Modification / select “Alarm Signal” in “Signal Type” drop-down box.
"Alarm Severity" Parameter Settings:
Use the menus to assign an Alarm Severity Level (none, minor, major, critical) to each
possible alarm.
Alarm Relay Menu Menu Navigation: Main Menu / Settings / Alarm Setting / Alarm Relay
Note: For WEB Interface, menu item is found under Configuration / Alarm Relays.
"Alarm Relay" Parameter Settings:
Use the menus to assign an alarm relay (for connection of external alarm circuits) to each
possible alarm.
Alarm Param Menu Menu Navigation: Main Menu / Settings / Alarm Setting / Alarm Param
Note: For WEB Interface; “Block Alarm” menu item is found under Device Information / Power System / Settings Tab, “Clr Alarm Hist” menu item is found under Maintenance / Clear Data, and “Alarm Voice” menu item is not available.
"Alarm Param" Parameter Settings:
Alarm Voice: Programs the audible alarm feature.
Off: Disables the audible alarm. On: When a new alarm occurs, the audible alarm sounds.
Press any key to silence the audible alarm.
3 minutes / 10 minutes / 1 hour / 4 hours: When a new alarm occurs, the audible
alarm sounds. The audible alarm automatically silences after the selected time period.
Block Alarm
Normal: Alarms are processed normally. Blocked: Forces the alarm relays in the "off" state and blocks alarms from changing
the relay state.
Clr Alm Hist: The only selection for "Clr Alm Hist" is Yes. Once Yes is selected and
confirmed, the alarm history log is cleared.
92 Chapter 3. Local Display Menus
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions UM1M820BNA Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013 Spec No. 1M820DNA (Model M820D)
Power System
General Menu Menu Navigation: Main Menu / Settings / Power System / General
Note: For WEB Interface; menu items are found under Device Information / Power System / Settings Tab.
"General" Parameter Settings:
Auto/Man State
Auto: The Controller automatically controls the power system. Manual: A User can manually change power system control settings. When you return
to Auto Mode, any settings changed in Manual Mode are returned to their previous setting (setting before being placed in Manual Mode).
Manual Mode Lmt: Time delay before returning to automatic control after being set for
manual control. A "0" setting disables the "Manual Mode Lmt" feature and the Controller MUST be manually set to Auto control after being set to Manual control.
Mtnc Cycle Time: The maintenance cycle time is the number of days before a
Maintenance Alarm is issued. To reset the maintenance timer and clear the Maintenance Alarm, clear the Maintenance Run Time (Main Menu / Manual / Power System / Clr MtncRunTime).
EStop / EShutdown
Disabled: Disables the Emergency Stop and Emergency Shutdown functions. EStop: Enables the Emergency Stop function.
EShutdown: Enables the Emergency Shutdown function. Load Curr Alarm: Sets the load current alarm point. Alarm Blocked
Normal: Alarms are processed normally.
Blocked: Forces the alarm relays in the "off" state and blocks alarms from changing
the relay state.
Rect Expansion
Inactive: Select this option if this is the only ACU+ Controller in the power system.
Primary: Select this option if the power system consists of multiple bays with multiple
ACU+ Controllers, and this ACU+ Controller is to be the Primary Controller. Note that only one (1) ACU+ Controller can be set as the Primary Controller.
Secondary: Select this option if the power system consists of multiple bays with
multiple ACU+ Controllers, and this ACU+ Controller is to be a Secondary Controller.
_____________________ Up to four (4) ACU+ Controllers can be connected together when a power system requires
a greater number of rectifiers than can be controlled by a single ACU+ Controller. One (1) Controller is designated as the primary Controller, the others as secondary Controllers. The rectifiers controlled by the secondary Controllers are designated as RectifierGroup 2 though 4 in the menus.
Primary/Secondary Procedure:
Note: Changing the Rectifier Expansion setting may take more than 3 minutes for the
ACU+ to configure the feature.
1) Connect the ACU+ Controllers in the multiple bays via the RS485 interface.
Chapter 3. Local Display Menus 93
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM1M820BNA User Instructions Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B) Spec No. 1M820DNA (Model M820D)
2) Set one of the ACU+ Controllers as the Primary Controller via the Rect Expansion menu item in the Power System "General" Parameters menu.
3) Set all other ACU+ Controllers as Secondary Controllers via the Rect Expansion menu item in the Power System "General" Parameters menu.
4) Set the Address of the ACU+ Controllers set as Secondary Controllers to 201, 202, or 203 via the Address (Slave) menu item in the Power System "General" Parameters menu. Note that each Secondary Controller must be set to a different address.
_____________________
Address (Slave): Sets the address of an ACU+ Controller set as a Secondary Controller. Over Voltage 1: Sets the Over Voltage 1 alarm point. Over Voltage 2: Sets the Over Voltage 2 alarm point. Under Voltage 1: Sets the Under Voltage 1 alarm point. Under Voltage 2: Sets the Under Voltage 2 alarm point. Fail Safe: When enabled, sets the relay designated as the "critical summary" alarm relay
to operate in the "fail safe" mode. In this mode, the relay is energized during normal operation and de-energized for an alarm condition.
Hybrid Mode: Refer to 1.3.11 Hybrid Control Function” for more information on the Hybrid
Mode.
Disable / Fixed Daily / Capacity: Sets the Hybrid Mode or disables the function. DG Run Overtemp: Enables or disables diesel generator operation in an over
temperature condition. DG Run Time: Sets the diesel generator run time. DG Used: Sets the diesel generator(s) to be utilized. DI for Grid: Sets the digital input monitoring the grid. DOD: Sets the Depth of Discharge. Dsch Duration: Sets the discharge duration. Start Dsch Time: Sets the start time for discharge. High Load Set: Sets the high load point. Equal StartTime: Sets the start time for equalizing. DG Alarm Delay: Sets the diesel generator alarm delay. Fail Safe: Tells the Controller the fail safe mode of the relay contacts connected to
start the generator(s) (either normally open or normally close).
Contactor Mode: Enables or disables the Power Split feature (master control indicates
the ACU+ system operates normally and slave control” indicates the ACU+ system is a slave system of the existing legacy system).
See also 2.7 Power Split Feature.
Relay Test: Sets the Relay Test feature to Automatic, Individual, or disables the feature. Relay Test Time: Sets the Relay Test Time for the Automatic Relay Test feature. HighLoadLevel1: Sets the High Load Level 1 alarm. HighLoadLevel2: Sets the High Load Level 2 alarm. DI1 through D18 Alarm State: Sets the alarm state for the digital input (high or low). Amb Temp Sensor: Sets the temperature sensor which displays the ambient temperature
on the Web Interface’s Homepage. Note that this temperature sensor MUST be set as an
94 Chapter 3. Local Display Menus
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Loading...