Section 1: Adding XTE3000 Actuators into Existing Network
January 2022
Section 1: Adding XTE3000 Actuators into
Existing Network
(Number of actuators increases)
1.1 Update Firmware in Slot 1 Coprocessor Module
• Obtain rmware le "M124N500.abm" and "Controlinc Network Master Firmware
Download Procedure" from Emerson website, link: www.Emerson.com/Controlinc.
• Use the procedure to download M124N500.abm rmware to
Slot 1 Coprocessor module.
1.2 Congure Controlinc Network Master to
Communicate with XTE3000 Actuators
1. Update number of actuators in the loop.
—Open up TECLINC and established communication, Figure 1.
Figure 1
Adding XTE3000 Actuators into Existing Network
1
Section 1: Adding XTE3000 Actuators into Existing Network
January 2022
—Change the "Slave Count" number to match with the number of devices on
the loop, Figure 2.
Figure 2
Change number of
devices on the network
Installation Instructions
VCIOM-17028 Rev. 0
Figure 3
—Click "Send" and wait for 5 seconds then "Read" to make sure it is written,
Figure 3.
Click "Send"
2
Adding XTE3000 Actuators into Existing Network
Installation Instructions
VCIOM-17028 Rev. 0
2. Edit Scanlist
Figure 4
Section 1: Adding XTE3000 Actuators into Existing Network
January 2022
—On TECLINC master Main Page, refer to Figure 1.
—Select "Address" to edit or to add more actuators to the network, Figure 4.
Add or edit Scanlist
by entering actuator
node address
—Click "Send" and wait for 5 seconds then "Read" to verify it is written.
Adding XTE3000 Actuators into Existing Network
3
Section 1: Adding XTE3000 Actuators into Existing Network
January 2022
3. Enter Device Type
In order for Controlinc to recognize XTE3000 actuators, set "Device Type" to 7.
—On TECLINC master Main Page, refer to Figure 1.
—Select "Device Type" then enter "7" for XTE3000 actuator, Figure 5.
Figure 5
Installation Instructions
VCIOM-17028 Rev. 0
Edit "Device Type" for
XTE actuator to "7"
—Click "Send" and wait for 5 seconds then "Read" to make sure it is written.
—Cycle Network Master power.
4
Adding XTE3000 Actuators into Existing Network
Installation Instructions
VCIOM-17028 Rev. 0
Section 2: Replacing Actuators with XTE3000 in Existing Network
January 2022
Section 2: Replacing Actuators with XTE3000
in Existing Network
(Number of actuators stays the same)
2.1 Update Firmware in Slot 1 Coprocessor Module
• Obtain rmware le "M124N500.abm" and "Controlinc Network Master Firmware
Download Procedure" from Emerson website, link: www.Emerson.com/Controlinc.
• Use the procedure to download M124N500.abm rmware to Slot 1
Coprocessor module.
2.2 Congure Controlinc Network Master to
Communicate with XTE3000 Actuators
1. No change to the number of actuators in the loop.
2. No change to the Scanlist.
3. Edit "Device Type".
In order for Controlinc to recognize XTE3000 actuators, change "Device Type" to 7.
—On Touch Panel go to Main Menu, Figure 1.
—Select "Device Type" then enter "7" for XTE3000 actuator, Figure 6.
Figure 6
Edit "Device Type" for
XTE actuator to "7"
—Click "Send" and wait for 5 seconds then "Read" to verify it is written.
—Cycle Network Master power.
Replacing Actuators with XTE3000 in Existing Network
5
World Area Conguration Centers (WACC) offer sales support, service,
inventory and commissioning to our global customers.
Choose the WACC or sales ofce nearest you:
NORTH & SOUTH AMERICA
19200 Northwest Freeway
Houston TX 77065
USA
T +1 281 477 4100
Av. Hollingsworth
325 Iporanga Sorocaba
SP 18087-105
Brazil
T +55 15 3413 8888
ASIA PACIFIC
No. 9 Gul Road
#01-02 Singapore 629361
T +65 6777 8211
No. 1 Lai Yuan Road
Wuqing Development Area
Tianjin 301700
P. R. China
T +86 22 8212 3300
For complete list of sales and manufacturing sites, please visit
www.emerson.com/actuationtechnologieslocations or contact us at
info.actuationtechnologies@emerson.com
MIDDLE EAST & AFRICA
P. O. Box 17033
Jebel Ali Free Zone
Dubai
T +971 4 811 8100
P. O. Box 10305
Jubail 31961
Saudi Arabia
T +966 3 340 8650
24 Angus Crescent
Longmeadow Business Estate East
P.O. Box 6908 Greenstone
1616 Modderfontein Extension 5
South Africa
T +27 11 451 3700
The Emerson logo is a trademark and service mark of Emerson Electric Co.
All other marks are property of their respective owners.
The contents of this publication are presented for information purposes
only, and while effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding
the products or services described herein or their use or applicability.
All sales are governed by our terms and conditions, which are available
on request. We reserve the right to modify or improve the designs or
specifications of our products at any time without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.