Description: -48VDC power system @ up to 555 Amperes, 25000 Watts max.
The Model LXP48F1 is a complete Power System containing power conversion,
intelligent monitoring and control, and distribution. An LXP Power System typically
consists of...
SAG582135000
System Application Guide
Spec. No. 582135000 (Model LXP48F1)
Issue AE, January 31, 2007
Home
• Distribution Cabinets
The system always includes a minimum of one Distribution Cabinet, which
provides DC distribution through fuses and/or circuit breakers.
A variety of distribution options are available that provide combinations of load
distribution, and Low Voltage Load or Battery Disconnect. Each Distribution
Cabinet accepts Bullet Nose-type circuit breakers and TPS/TLS-type fuse
holders.
• Power Shelf
The system can include from one to three front access Power Shelves. The
Main Power Shelf houses the MCA and up to five (5) PCUs. Expansion Power
Shelves each house up to six (6) PCUs.
• MCA
Located in the Main Power Shelf, the Meter-Control-Alarm assembly (MCA)
controls the operation of all PCUs (17 max.) and provides system metering,
control, and alarm functions. The MCA features a Web Interface for
comprehensive remote monitoring and control capability.
• PCUs
Housed in the Power Shelves, the Power Conversion Units (PCUs) provide load
power, battery float current, and battery recharge current during normal operating
conditions.
Page 1 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Distribution Cabinet: Varies. See individual List Number.
Agency Approval: UL 1801 Listed (“c UL”)
Framework Type: Cabinets Designed for Relay Rack Mounting
Mounting Width: 23”
Mounting Depth: 12”
Front Projection: 5”
Access: Front and sides for installation; front for operation and maintenance
Control: Microprocessor
Color: Textured Cool Gray (M500-146)
Accessories: Circuit Breakers
, Fuses, GMT-Type Fuse Distribution Assembly,
Lugs, Relay Racks, Load Shed Card
Environment: +65°C (+149°F)
Page 2 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582135000
Spec. No. 582135000 (Model LXP48F1) Issue AE, January 31, 2007
582135000
Distribution Cabinet
List BD, BL, BS, GA,
LB, LD, LS, LX
Power Shelf(s)
List 1
Home
SEE ALSO
System Overview
Table of Contents
List Structure Table
Distribution Devices
Lugs
Relay Rack Options
Replacement Cables
List of Parts
Specifications
Dimensional Drawings
Related Documentation
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
List 61: 1U Wireway
List 62: 2 U Wireway
List 93: Battery Tray
Load Shed Card
Page 3 of 43
OTHER OPTIONS
and ACCESSORIES
SAG582135000 System Application Guide
Issue AE, January 31, 2007 Spec. No. 582135000 (Model LXP48F1)
TABLE OF CONTENTS
System
Overview
SYSTEM OVERVIEW................................................................................................................................................ 1
TABLE OF CONTENTS............................................................................................................................................ 4
LIST INFORMATION................................................................................................................................................. 6
Main List Numbers............................................................................................................................................... 6
Distribution List Numbers................................................................................................................................... 6
List Descriptions.................................................................................................................................................. 7
List 1: Model LXP9000SHF Integrated Power System ..................................................................................... 7
List 61: 1U Wireway .......................................................................................................................................... 7
List 62: 2U Wireway .......................................................................................................................................... 7
List 93: Battery Tray, Pre-cabled.......................................................................................................................8
List BD: Distribution Cabinet
List BL: Distribution Cabinet
List BS: Distribution Cabinet
List GA: Distribution Cabinet
List LB: Distribution Cabinet
List LD: Distribution Cabinet
List LS: Distribution Cabinet
List LX: Distribution Cabinet
Picture
(18) Fuse/Circuit Breaker Positions with
Low Voltage Battery Disconnect and Battery Shunt .......................................................................... 10
(18) Fuse/Circuit Breaker System Positions with
Low Voltage Battery Disconnect, Battery Shunt and Load Shunt...................................................... 11
Battery Shunt and Load Shunt........................................................................................................... 17
List
Information
Accessory
Information
List of
Parts
Specifications
Physical Size
Information
Related
Documentation
ACCESSORY INFORMATION ............................................................................................................................... 18
Distribution Devices .......................................................................................................................................... 18
Bullet Nose Type Circuit Breakers ................................................................................................................... 18
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582135000
Spec. No. 582135000 (Model LXP48F1) Issue AE, January 31, 2007
RJ-45 MCA Control Bus Cable......................................................................................................................... 31
MCA Control Bus Interconnect Cable .............................................................................................................. 31
MCA Control Bus Termination Plug ................................................................................................................. 31
RJ-45 MCA Control Bus Termination Plug....................................................................................................... 31
Battery Temperature Probe............................................................................................................................... 32
LIST OF PARTS...................................................................................................................................................... 33
Distribution Cabinet Dimensions—List GA..................................................................................................... 37
Distribution Cabinet Electrical Connection Locations and Dimensions— List GA.................................... 38
Wireway Dimensions—List 61 and 62 ............................................................................................................. 39
Dimensions of System Configured with List 93 Battery Trays..................................................................... 40
Overall Dimensions – Part No. 528927 Load Shed Card............................................................................... 41
RELATED DOCUMENTATION............................................................................................................................... 42
BATTERY MANUFACTURER INFORMATION ..................................................................................................... 42
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
(If viewed electronically, more detailed information is available for each option by clicking on t he desired number
in the column entitled List No. in the table below.)
Main List Numbers
Mounting
List
No.
Part Number
DDeessccrriippttiioonn
158213500001 Model LXP9000SHF Integrated Power System
6158213500061 Wireway, 19” x 1-3/4” 1 --
6258213500062 Wireway, 19” x 3-1/2” 2 --
9358213500093 Battery Tray, Pre-cabled As Requested--
Notes:
1) Order all List 1 components (Power Shelves, PCUs and MCA per System Application Guide
SAG589200100.
Positions
(1U =
1-3/4”)
2 per shelf,
6 max.
Notes
1, 2
2) Separately order relay racks as required. See Relay Rack Options
Distribution List Numbers
List
No.
BD 582135000BD
BL 582135000BL
BS 582135000BS
GA 582135000GA
LB 582135000LB
LD 582135000LD
LS 582135000LS
LX 582135000LX
Part Number
DDeessccrriippttiioonn
Distribution Cabinet: (18) Bullet Nose
Positions
Distribution Cabinet: (18) Bullet Nose
Positions
Distribution Cabinet: (18) Bullet Nose
Positions
Distribution Cabinet: (20) GMT Fuse
Positions, Split Bus
Distribution Cabinet: (18) Bullet Nose
Positions
Distribution Cabinet: (18) Bullet Nose
Positions
Distribution Cabinet: (18) Bullet Nose
Positions
Distribution Cabinet: (18) Bullet Nose
Positions
for available relay racks.
Mounting
Positions
(1U =
1-3/4”)
Single
or Dual
Voltage
Low
Voltage
Discon-
nect
Shunts
3 Single Battery Battery
3 Single Battery
Battery
& Load
3 Single None Battery
1 Single None None
3 Single Load
Battery
& Load
3 Single Load Load
3 Single None Load
3 Single None
Battery
& Load
Page 6 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582135000
Spec. No. 582135000 (Model LXP48F1) Issue AE, January 31, 2007
Home
List Descriptions
List 1: Model LXP9000SHF
Integrated Power System
Features
List of Parts
♦ Complete LXP Integrated Power System platform, provides Main Power Shelf, MCA, up to two Expansion
Power Shelves, and up to 17 PCUs.
♦ For more information, refer to System Application Guide SAG589200100.
Restrictions
♦ List 20 of 589200100 (Bulk Termination Panel) cannot be used when system is ordered with any of the
available distribution options (List BD, BL, BS, GA, LB, LD, LS, LX).
Ordering Notes
1) Order Power Shelves, PCUs and MCA, per SAG589200100.
2) If required, order relay rack per Table 6
3) Order Distribution Cabinets, as required, per Distribut ion List Numbers
4) Order load distribution fuses and/or circuit breakers, as required, per Tables 1
5) Order load distribution lugs, as required, per Table 4
6) Order battery lugs, as required, per Table 5
.
table.
, 2 and 3.
.
.
List 61: 1U Wireway
Features
List of Parts
♦ Designed to mount immediately above any 3U-high LXP Distribution Cabinet—provides protection for load,
battery, alarm and control cabling routed from top of Distribution Cabinet to rear of system.
♦ See Wireway Dimensions—List 61 and 62
under Physical Size Information.
List 62: 2U Wireway
Features
List of Parts
♦ Designed to mount immediately above any 3U-high LXP Distribution Cabinet—provides protection for load,
battery, alarm and control cabling routed from top of Distribution Cabinet to rear of system.
♦ See Wireway Dimensions—List 61 and 62
under Physical Size Information.
Page 7 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
♦ Provides one battery tray that mounts four (4) 12V front terminal VLRA batteries. Batteries are configured as
one (1) 48V string. Battery cabling is factory-connected to Power System main bus.
♦ Accepts various Valve Regulated Lead Acid (VLRA) batteries. See Ordering Notes below.
♦ Tray dimensions are 21.3” wide X 22.4” deep. See Dimensions of System Configured with List 93 Battery
Trays under Physical Size Information for a typical battery tray arrangement.
♦ Trays can be ordered with or without Battery Disconnect circuit breakers. When circuit breakers are ordered,
one is provided in the –48V lead of each battery string (1 circuit breakers per tray).
Home
Ordering Notes
1) Order multiples of List 93 for more than one (1) battery tray. See Restrictions below.
2) Order batteries separately. The following table lists batteries recommended for use with List 93.
Manufacturer*
Model Emerson
Network
Power
Part No.
Rated
8-Hr.
Capacity
(Ah)
Dimension
W x L x H
(Inches)
Required
Tray
Spacing
Weight
(lbs)
GNB Marathon M12V125FT -- 125 4.90 x 22.00 x 11.15 7U 105
GNB Marathon M12V155FT 112795 155 4.90 x 22.00 x 11.15 7U 119
Northstar NSB110FT -- 110 4.92 x 22.05 x 8.94 7U 91.3
Northstar NSB170FT -- 167 4.92 x 22.05 x 12.60 8U 131
Deka Unigy I 12AVR-150ET 122018 150 4.90 x 22.00 x 11.75 7U 115
C&D FA 12-150F FA12150 150 4.92 x 21.97 x 12.70 8U 131
Douglas DGS12-150F 125453 150 4.90 x 22.00 x 12.70 8U 137
Douglas DGS12-170F -- 170.8 4.92 x 22.05 x 12.60 8U 129.6
* See Battery Manufacturer Information.
3) Specify the batteries you intend to use with each List 93 ordered. Lugs for battery connections vary
according to the batteries to be installed. Battery cables will be lugged as shown in the following table.
The table is provided for reference only.
C&D FA 12-150F 528235 528235 528234
Douglas DGS12-150F 528237 528237 528236
Douglas DGS12-170F 528235 528235 528234
Page 8 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582135000
Spec. No. 582135000 (Model LXP48F1) Issue AE, January 31, 2007
4) Specify rack spacing of 7U (12.25”) or 8U (14”) between trays and above top tray as required for
battery clearance. See table above.
5) Specify with or without Battery Disconnect circuit breakers. Note: All List 93 trays in a bay will be furnished with or without Battery Disconnect circuit breakers as specified for the first tray ordered.
6) If ordering List 93 with circuit breakers, order one (1) circuit breaker per List 93 from the following table.
Provides an alarm during an electrical or manual trip condition.
2
Provides an alarm during an electrical trip condition only.
7) If ordering List 93 with circuit breakers, specify breaker mounting on left side or right side of tray.
Home
Restrictions
Maximum number of List 93’s per bay is five (5).
A single List 93 must mount at bottom of bay. Multiple List 93’s must mount starting at bottom of bay and
working upward.
Page 9 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
♦ (18) Mounting Positions for Load Distribution Fuses or Circuit Breakers, or accepts Alarm-Type Fuse
Distribution Assembly (Kit P/N 524679).
♦ Accepts TPS/TLS-Type Fuses (3 to 100A) or Bullet Nose Type Circuit Breakers (1 to 100A)
Caution:
A circuit breaker or fuse with a rating greater than 75 amperes SHALL HAVE an empty
mounting position between it and any other overcurrent protective device.
Caution
: The maximum size circuit breaker or fuse used in ambient temperatures above +50°C
ambient shall be 40 amperes.
♦ Includes (1) Low Voltage Battery Disconnect Contactor (LVBD)
♦ Includes (1) Battery Shunt
♦ See Distribution Cabinet Electrical Connection Locations and Dimensions
Restrictions
.
The maximum number of Distribution Cabinets in a system is three (3). Each Distribution Cabinet must be
mounted immediately above a Power Shelf with zero (0) inches of rack space between units to accommodate
the furnished busbar links. Adequate vertical mounting space must be provided above each Distribution
Cabinet to accommodate distribution and battery cabling.
Unless otherwise specified fuses and/or circuit breakers are mounted from right to left, starting with the
highest capacity and working to the lowest capacity.
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.
Ordering Notes
1) Order circuit breakers, as required, per Table 1
2) Order fuses, as required, per Tables 2
.
.
3) Order one (1) Part No. 117201 fuseholder per fuse ordered in 2) above.
4) Order one (1) Part No. 524690 mounting kit per circuit breaker or fuseholder ordered in 1) or 3) above.
Kit includes bullet socket busbar and hardware for mounting load and return lugs for one distribution
position.
5) Order one (1) Load lug (one-hole, 1/4” bolt clearance hole) and one (1) Load Return lug (two-hole, 1/4”
bolt clearance holes on 5/8” centers) as required for each distribution position per Table 4
.
Page 10 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582135000
Spec. No. 582135000 (Model LXP48F1) Issue AE, January 31, 2007
Home
List BL: Distribution Cabinet
(18) Fuse/Circuit Breaker System Positions with
Low Voltage Battery Disconnect, Battery Shunt and Load Shunt
List of Parts
Features
♦ Single Voltage Distribution (-48V)
♦ Maximum Capacity: Input: 500A max.
♦ (18) Mounting Positions for Load Distribution Fuses or Circuit Breakers, or accepts Alarm-Type Fuse
Distribution Assembly (Kit P/N 524679).
♦ Accepts TPS/TLS-Type Fuses (3 to 100A) or Bullet Nose Type Circuit Breakers (1 to 100A)
Caution:
A circuit breaker or fuse with a rating greater than 75 amperes SHALL HAVE an empty
mounting position between it and any other overcurrent protective device.
Caution
: The maximum size circuit breaker or fuse used in ambient temperatures above +50°C
ambient shall be 40 amperes.
♦ Includes (1) Low Voltage Battery Disconnect Contactor
♦ Includes and (1) Load Shunt (total distribution load) and (1) Battery Shunt
♦ Busbars are provided for power connections between Distribution Cabinet and Power Shelf.
♦ See Distribution Cabinet Electrical Connection Locations and Dimensions
Restrictions
.
The maximum number of Distribution Cabinets in a system is three (3). Each Distribution Cabinet must be
mounted immediately above a Power Shelf with zero (0) inches of rack space between units to accommodate
the furnished busbar links. Adequate vertical mounting space must be provided above each Distribution
Cabinet to accommodate distribution and battery cabling.
Fuses and/or circuit breakers are to be mounted from right to left, starting with the highest capacity and
working to the lowest capacity.
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.
Ordering Notes
1) Order circuit breakers, as required, per Table 1
2) Order fuses, as required, per Tables 2
.
.
3) Order one (1) Part No. 117201 fuseholder per fuse ordered in 2) above.
4) Order one (1) Part No. 524690 mounting kit per circuit breaker or fuseholder ordered in 1) or 3) above.
Kit includes bullet socket busbar and hardware for mounting load and return lugs for one distribution
position.
5) Order one (1) Load lug (one-hole, 1/4” bolt clearance hole) and one (1) Load Return lug (two-hole, 1/4”
bolt clearance holes on 5/8” centers) as required for each distribution position per Table 4
.
Page 11 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
♦ (18) Mounting Positions for Load Distribution Fuses or Circuit Breakers, or accepts Alarm-Type Fuse
Distribution Assembly (Kit P/N 524679).
♦ Accepts TPS/TLS-Type Fuses (3 to 100A) or Bullet Nose Type Circuit Breakers (1 to 100A)
Caution:
A circuit breaker or fuse with a rating greater than 75 amperes SHALL HAVE an empty
mounting position between it and any other overcurrent protective device.
Caution
: The maximum size circuit breaker or fuse used in ambient temperatures above +50°C
ambient shall be 40 amperes.
♦ Includes (1) Battery Shunt
♦ See Distribution Cabinet Electrical Connection Locations and Dimensions
Restrictions
.
The maximum number of Distribution Cabinets in a system is three (3). Each Distribution Cabinet must be
mounted immediately above a Power Shelf with zero (0) inches of rack space between units to accommodate
the furnished busbar links. Adequate vertical mounting space must be provided above each Distribution
Cabinet to accommodate distribution and battery cabling. Fuses and/or circuit breakers are to be mounted
from right to left, starting with the highest capacity and working to the lowest capacity.
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.
Ordering Notes
1) Order circuit breakers, as required, per Table 1
2) Order fuses, as required, per Tables 2
.
.
3) Order one (1) Part No. 117201 fuseholder per fuse ordered in 2) above.
4) Order one (1) Part No. 524690 mounting kit per circuit breaker or fuseholder ordered in 1) or 3) above.
Kit includes bullet socket busbar and hardware for mounting load and return lugs for one distribution
position.
5) Order one (1) Load lug (one-hole, 1/4” bolt clearance hole) and one (1) Load Return lug (two-hole, 1/4”
bolt clearance holes on 5/8” centers) as required for each distribution position per Table 4
.
Page 12 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582135000
Spec. No. 582135000 (Model LXP48F1) Issue AE, January 31, 2007
Home
List GA: Distribution Cabinet
(20) GMT Fuse System Positions with
List of Parts
Split Bus
Features
♦ Single Voltage Distribution (-48V)
♦ Maximum Capacity: Input: 163A @ +40°C; 155A @ 50°C; 110A @ +65°C.
Total Distribution: 30A per bus, 60A total @ +65°C
Battery Recharge Current: 163A @ +40°C; 155A @ 50°C; 110A @ +65°C.
Battery Terminals as Remote Feed: 103A @ +40°C; 95A @ 50°C; 50A @ +65°C.
♦ (20) Mounting Positions for Alarm-Type Load Distribution Fuses, (10) per bus.
♦ Accepts GMT-Type Fuses (1/4A to 15A).
♦ Includes (20) dummy fuses equipped with safety fuse covers.
♦ Provides local and external fuse alarm.
♦ See Distribution Cabinet Electrical Connection Locations and Dimensions
Restrictions
.
Maximum distribution fuse size: 15A
Maximum size wire each fuse position accepts is 14 AWG.
Input is cable-fed only.
Maximum size wire input terminals accept is (1) 2 AWG per polarity.
No load or battery shunts are provided.
Ordering Notes
1) Order fuses, as required, per Tables 3
.
Page 13 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.