Do not throw away, destroy or lose this manual. Please read carefully and store in a safe place for future
reference. Content familiarity required for proper installation.
The instructions included in this manual must be followed to prevent product malfunction, property
damage, injury, or death to the user or other people. Incorrect operation due to ignoring any instructions
will cause harm or damage.
For more technical materials such as submittals, engineering databooks and catalogs,
visit www.liebert.com.
WARNING
Risk of improper unit installation and/or removal. Can cause water and/or refrigerant leakage,
electric shock, smoke, fire and explosion resulting in building and equipment damage, serious
injury or death. Do not install, remove, or re-install the unit by yourself (customer). Ask the dealer
or an authorized technician to install the unit. For replacement of an installed unit, always contact
an authorized Liebert service provider.
WARNING
Risk of explosive discharge of high pressure gas. Can cause serious injury. The unit is shipped
with refrigerant and the service valves closed. Do not open service valves on the unit until all noncondensibles have been removed from the piping system and authorization to do so has been
obtained from the commissioning agent.
Important Safety Instructions
WARNING
Risk of excessive refrigerant pressure. Can cause equipment damage, serious injury or death. Do
not run the compressor with the service valves closed.
WARNING
Arc flash and electric shock hazard. Can cause serious injury or death. Open all local and remote
electric power disconnect switches, verify with a voltmeter that power is off and wear personal
protective equipment per NFPA 70E before working within the electric control enclosure. All
electric work must be performed by a licensed electrician and conform to all applicable national,
state and local electrical codes Replace and securely fasten all control box and panel covers
immediately after working on the unit to protect the operator from the hazards above and prevent
the intrusion of dust, water and animals that may cause additional hazards to develop.
WARNING
Risk of contact with sharp edges, nails, splinters, and other packaging materials and improper
disposal of plastic bags. Can cause injury or death. Wear gloves and arm protection when
unpacking the unit and and Dispose the packing materials safely.
Cut the plastic packaging bag into small pieces or dispose of securely to eliminate the risk of
suffocation and death from improperly wearing the plastic bag as a head cover.
1Liebert
®
SRC™ User Manual
Important Safety Instructions
!
!
!
!
!
WARNING
Risk of improper installation. Can cause equipment and building damage, injury or death. Utilize a
structural engineer to evaluate the mounting surface and environmental risks and recommend the
safest fastening method.
WARNING
Risk of protective safety devices not operating properly. Can cause electrical short circuit, electric
shock, explosion, fire, injury or death. Do not change the settings of the protection devices and
only use replacement parts that are specified by Liebert.
WARNING
Risk of improper installation, operation and maintenance. Can cause building and equipment
damage, injury or death from electric shock, fire, explosion, or scalding. When using this product,
follow basic precautions, including but not limited to:
• Read and follow all instructions in this manual.
• Installation and or repairs must only be completed made by unauthorized Liebert trained and
qualified HVAC technicians.
• Installation MUST conform to the local building codes or, in the absence of local codes, the
National Electrical Code NFPA 70/ANSI C1-1003 or current edition and Canadian Electrical
Code Part1 CSA C.22. 1 as applicable and appropriate.
• The information contained in the manual is intended for use only by Liebert trained and a
qualified service technicians who are familiar with the appropriate safety procedures and
equipped with the proper tools and test instruments.
• Power cord replacement must only be be performed by authorized personnel using only Liebert
specified replacement parts.
• This product contains chemicals known to the State of California to cause cancer and birth
defects or other reproductive harm. Wash hands after handling.
WARNING
Risk of improper installation location. Can cause serious injury or death. Install the unit in a safe
location where nobody can step on or fall onto it. Utilize a structural engineer to verify that the
mounting surface and method is secure.
WARNING
Arc flash and electric shock hazard. Can cause serious injury or death. Open all local and remote
electric power disconnect switches, verify with a voltmeter that power is off and wear personal
protective equipment per NFPA 70E before working within the electric control enclosure. Verify
that the input power wiring is properly sized and grounded per applicable national, state and local
electric codes.
Properly size all and circuit breakers or fuses protecting the input power wiring.
Do not operate the disconnect switch with wet hands.
Liebert® SRC™ User Manual2
Important Safety Instructions
!
!
!
!
!
!
!
!
WARNING
Risk of electric shock. Can cause injury or death. Secure all hazardous voltage field wiring
connections with appropriate wire strain relief.
Improperly secured wires will create excessive stress on electrical power connection lugs.
Improper or loose connections may generate excessive heat and cause smoke and fire.
WARNING
Risk of damaged electrical components and short circuits. Can cause building and equipment
damage, smoke, fire, injury and death. Do not provide power to or operate the unit if it is flooded or
submerged.
WARNING
Risk of unit mounting base deterioration and collapse. Can cause building and equipment
damage, injury or death. Periodically verify the equipment mounts have not deteriorated.
WARNING
Risk of electric shock and contact with high speed moving parts. Can cause serious injury or
death. Do not operate the unit with the panel(s) or protective cover(s) removed; keep fingers and
clothing away from moving parts. Do not open the inlet grille of the unit during operation. Do not
insert hands or other objects through the inlet or outlet when the unit is plugged in. Do not touch
the electrostatic filter, if the unit includes one.
WARNING
Risk of electric shock. Can cause injury or death. Periodically, check power cord and plug for
damage. Damaged power cords must be replaced by the manufacturer, its service agent, or
similar Liebert-trained and qualified persons.
CAUTION
Risk of exposure to refrigerant gas. Can cause injury or illness. Always check for system
refrigerant leaks after the unit has been installed or serviced.
CAUTION
Risk of contact with sharp edges. Can cause injury. Wear protective gloves when handling
equipment.
CAUTION
Risk of exposure to excessive refrigerant concentration and oxygen depletion. Can cause illness
or injury. If the unit is installed in a small improperly or non-ventilated space, take measures to
prevent the refrigerant concentration from exceeding safety limits in the event of a refrigerant leak.
Consult the latest edition of ASHRAE (American Society of Heating, Refrigerating, and Air
Conditioning Engineers) Standard 15.
3Liebert
®
SRC™ User Manual
Important Safety Instructions
!
!
!
CAUTION
Risk of contact with extremely hot and cold surfaces. Can cause injury. Refrigerant piping is
extremely hot or cold during unit operation. Do not touch the refrigerant piping during or after
operation. Wear thermally insulated gloves and arm protection or allow the piping to cool or warm
to a safe handling temperature before working on the piping.
CAUTION
Risk of improper lifting and moving of a heavy unit. Can cause building and equipment damage
and injury. Be very careful when transporting the product.
• Do not attempt to carry the product without assistance. Some products use polypropylene
bands for packaging. Do not use polypropylene bands to lift the unit.
• Suspend the unit from the base at specified positions.
• Support the unit a minimum of four points to avoid slippage from rigging apparatus.
Verify that all lifting apparatus is rated for the weight of the unit. See XREF TABLE for indoor and
outdoor unit weights.
CAUTION
Risk of contact with sharp edges, and extremely hot or cold components. Can cause injury. Wear
OSHA approved head and eye protection, thermally insulated gloves and arm protection or allow
the unit to reach a safe for contact temperature and use caution when cleaning or servicing the
unit.
NOTICE
Risk of exposure to corrosive environments. Can cause equipment damage. Don’t install the unit
where it’s directly exposed to ocean winds.
Ocean winds may cause corrosion, particularly on the condenser and evaporator fins, which, in
turn could cause product malfunction or inefficient performance.
NOTICE
Risk of water damage and abnormal vibration. Can cause equipment damage
When installing the unit in a low-lying area, or a location that is not level, use a raised concrete pad
or concrete blocks to provide a solid, level foundation.
NOTICE
Risk of excessive condensation. Can cause building and equipment damage.
Properly insulate all cold surfaces to prevent “sweating.” Cold surfaces such as uninsulated piping
can generate condensate that may drip and cause a slippery floor condition and/or water damage
to walls.
NOTICE
Risk of exposure to excessive Electro-Magnetic Interference. Can cause equipment malfunction.
When installing the unit in a hospital, mechanical room, or similar electromagnetic field (EMF)
sensitive environment, provide sufficient protection against electrical noise.
Inverter equipment, power generators, high-frequency medical equipment, or radio communication
equipment may cause the unit to operate improperly. The unit may also affect such equipment by
creating electrical noise that disturbs medical treatment or image broadcasting.
Liebert® SRC™ User Manual4
Important Safety Instructions
NOTICE
Risk of using the wrong refrigerant. Can cause equipment damage
Do not make refrigerant substitutions. Use R410A only.
If a different refrigerant is used, or air mixes with original refrigerant, the unit will malfunction and
be damaged.
NOTICE
Risk of excessive vibration and water leakage. Can cause building and equipment damage
Keep the unit upright during installation to avoid compressor, piping and component damage.
NOTICE
Risk of improper refrigerant piping practices. Can cause refrigerant leaks resulting in building and
equipment damage
When connecting refrigerant tubing, remember to allow for pipe expansion. Improper piping may
cause refrigerant leaks and system malfunction.
NOTICE
Risk of an improper installation location. Can cause equipment damage
Install the unit in a safe location where nobody can step on or fall onto it. Do not install the unit on
a defective stand. Periodically check that the outdoor frame is not damaged
NOTICE
Risk of leaking water. Can cause building and equipment damage.
Install the drain hose as specified in this manual to ensure adequate drainage and periodically
check for damage, obstruction and leaks.
NOTICE
Risk of leaking refrigerant. Can cause equipment malfunction and damage.
Always check for system refrigerant leaks after the unit has been installed or serviced. Low
refrigerant levels may cause product failure.
NOTICE
Risk of cold compressor at startup. Can cause equipment damage.
Provide power to the compressor crankcase heaters at least six (6) hours before operation begins.
Starting operation with a cold compressor sump(s) may result in severe bearing damage to the
compressor(s). Keep the power switch on during the operational season.
NOTICE
Risk of blocked inlet and outlet air vents. Can cause equipment malfunction and damage. Do not
block the inlet or outlet. Unit may malfunction.
NOTE
Do not install the unit in a noise sensitive area.
5Liebert
®
SRC™ User Manual
Important Safety Instructions
NOTE
Take appropriate actions at the end of HVAC equipment life to recover,
recycle, reclaim or destroy R410A refrigerant according to applicable U.S.
Environmental Protection Agency (EPA) rules.
NOTE
Don’t store or use flammable gas / combustibles near the unit. There is risk of
product failure.
NOTE
Clean up the site after installation is finished, and check that no metal scraps,
screws, or bits of wiring have been left inside or surrounding the unit.
NOTE
Do not use this equipment in mission critical or special purpose applications
such as preserving foods, works of art, wine coolers or refrigeration. The
equipment is designed to provide cooling and heating for electronic and
telecommunications equipment.
Oil, steam, sulfuric smoke, etc., can significantly reduce the performance of
the unit, or damage its parts.
NOTE
• If the leaking battery fluid has been swallowed, wash off the inside of the
mouth thoroughly and consult a doctor.
• Do not drink the water drained from the unit.
• Do not use the product for special purposes, such as preserving foods,
works of art, and etc. It is an unit for consumer purposes, not a precision
refrigeration system. There is risk of damage or loss of property.
• Do not recharge or disassemble the batteries.
NOTE
Maintenance
• Never touch the metal parts of the unit when removing the air filter.
• Use a sturdy stool or ladder when cleaning, maintaining, or repairing the
unit at a height.
• Never use strong cleaning agents or solvents when cleaning the unit or
spray water.
• Use a smooth cloth.
Liebert® SRC™ User Manual6
Safety Symbols
The following symbols may appear within the documentation or on the product.
SymbolMeaning
High Temperature
Alerts the user where the enclosure temperature may exceed 158°F (70°C) while operating under highambient temperature and at maximally rated load.
Instructions
Signifies the presence of important operating and maintenance (servicing) instructions in the literature
accompanying the appliance.
Dangerous Voltage
Warns about the presence of uninsulated dangerous voltage within the product’s enclosure that may be
of sufficient magnitude to constitute a risk of electric shock to persons.
Power On
Indicates the principal On/Off switch is in the On position.
Safety Symbols
Power Off
Indicates the principal On/Off switch is in the Off position.
Protective Grounding Terminal
Indicates a terminal that must be connected to earth ground before any other connections to the
equipment may be made.
Unit Type
N = Indoor evaporator
C = Outdoor condensing unit
0
Placeholder
SRC
Figure 1-1 Product Nomenclature
Model Number and Nomenclature
9Liebert
®
SRC™ User Manual
Model Number and Nomenclature
Page intentionally left blank.
Liebert® SRC™ User Manual10
2.0Product Introduction
Suggestions for Energy Saving when Operating the Liebert SRC:
• Do not cool excessively indoors. This may be harmful for your health and may consume more
electricity.
• Block sunlight with blinds or curtains while you are operating the unit.
• Keep doors or windows closed tightly while you are operating the unit.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, within a short period of time.
• Open windows regularly for ventilation. The indoor air quality may deteriorate if the unit is used for long
durations.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air
flow or weaken the cooling / dehumidifying functions.
Figure 2-1 Indoor Unit Parts and Functions
Product Introduction
No. DescriptionNo. Description
1Air filter (under the panel)5Air deflector (vertical louver)
2Air intake6Air deflector (horizontal vane)
3Front cover7Air outlet
4On/Off button
Figure 2-2 Outdoor Unit Parts and Functions
No. Description
1Air intake vents
2Air outlet vents
11Liebert® SRC™ User Manual
Product Introduction
1
7
8
9
10
11
13
12
14
15
16
17
2
3
4
5
6
Connection Cable
(1EA, 32ft (10m))
Screw
(4 EA)
Installation & Operation
Manual
NOTE
The number and location of operation lamps may vary by unit model.
The features may vary by model.
Figure 2-3 Thermostat parts and functions
No. DescriptionNo. Description
1Operation indication10Air-flow button
2Set temperature button11Cooling temperature setpoint
3Fan speed button12Function setting button
4Set back button13Up, down, left and right buttons
5Operation-mode select button14On/Off button
Wireless thermostat receiver
6
(not included on some models)
7Sub function button16Set/Cancel button
8Ventilation button17Exit button
9Reservation button
15Heating temperature setpoint
NOTE
Some functions may not be available or displayed depending on unit type.
Figure 2-4 Accessories
No. DescriptionNo. Description
1Connection cable, 1 each, 32 ft (10 m) 3User Manual
2Screw, 4 each
Liebert® SRC™ User Manual12
NOTE
Some options and functions may not be displayed or the menu name may be
different depending on your system and model.
Figure 2-5 Icon descriptions and functions
Product Introduction
345
1
2
SectionIconDescription
Auto—change to cooling or heating mode automatically.
Operating in cooling mode.
1 Operating Mode
Operating in dehumidification mode.
Operating in heating mode.
Operating in fan-only mode.
6
7
8
9
10
2 Sub functions
Plasma purification filter is operating.
Energy-saving cooling mode, operating in limited temperature range.
Automatic drying is operating.
Electric heater is operating in heater mode.
Humidifier is operating.
Automatic fan function on indoor unit.
The fan doesn’t operate in the indoor unit when the compressor is off.
13Liebert® SRC™ User Manual
Product Introduction
SectionIconDescription
Current temperature.
3 Temperature
4 Fan SpeedFan-speed settings.
5 Air-flow/Louvers
6 Controller Modes
Cooling temperature setpoint.
Heating temperature setpoint.
Swing louvers up/down.
Swing louvers left/right.
Swing louvers for “swirl” (paired, opened cross swing).
Operate in schedule mode.
Temporarily operate in a mode.
Override schedule (occupied/unoccupied).
7 State Monitoring
8 Schedule
Operate in set-back mode.
Command received from central controller or outdoor unit.
Slave indoor unit to a heat-pump system.
Prevents changing to a mode that is incompatible with the current mode of
the outdoor unit.
Outdoor unit is operating.
Indoor unit is pre-heating.
Defrost is operating.
Function is not applied.
Simple schedule is in use.
Sleep schedule is in use.
Weekly schedule is in use.
Holiday schedule is in use.
Liebert® SRC™ User Manual14
SectionIconDescription
Day of Week:
• SUN = Sunday
• MON = Monday
• TUE = Tuesday
• WED = Wednesday
• THU = Thursday
• FRI = Friday
• SAT = Saturday
Number of the weekly-schedule event.
9 Schedule Set-up
Schedule time AM/PM.
Schedule time hour/minute.
min. = minute.
hr. = hour.
Product Introduction
Weekly schedule occupied/un-occupied state.
Copy/Paste schedule data.
15Liebert® SRC™ User Manual
Product Introduction
SectionIconDescription
10 Function Settings
Louver set-up.
1, 2, 3, 4, All = louver number.
STD = standard louver angle setting.
Angle of the louver.
Elevation grill set-up.
Grill up.
Grill closed.
Grill down.
Display lock set-up
Display is locked.
Display is not locked.
Set-up minimum-difference value between cooling and heating setpoints.
Set current time.
Set timer for schedule override.
Set-up default setback for cooling/heating temperature setpoints.
Clear the air-filter cleaning alarm.
Check the indoor-unit air filter and clean if necessary.
2.1Electrical Data
Table 2-1Unit electrical data
Compressor
ModelNom. Tons
SRC181-1/2114.6/14.610.250.401925
SRC241-3/4117.3/17.310.250.52335
SRC362-3/4117.3/17.310.250.52335
Qty.
Compressor (A)
Cool/Heat
Fan
Qty. ODU Fan (A) IDU Fan (A)MCA (A)MOP (A)
Liebert® SRC™ User Manual16
2.2R410A Refrigerant
!
R410A refrigerant has a higher operating pressure in comparison to R22 refrigerant and, therefore, all
piping-system materials installed must have a higher resisting pressure that the materials traditionally used
in R22 systems.
R410A refrigerant is an azeotrop of R32 and R125, mixed at 50:50, so the ozone depletion potential (ODP)
is zero. Many countries have approved-of and encouraged R410A for use as an alternate refrigerant.
WARNING
Risk of piping ruptures and refrigerant leaks. Can cause equipment damage, illness, serious injury
and death from suffocation. Do not use piping that is not approved for use in high-pressure
refrigerant systems. Refrigerant leaks in non-ventilated spaces could cause oxygen depletion
levels that are dangerous to humans. Follow accepted safety practices for refrigerant storage,
discharging and charging.
NOTE
• Piping wall thickness must comply with the applicable local, state, and
federal codes for the 551-psi design pressure of R410A.
• Because R410A is a combination of R32 and R125, the required additional
refrigerant must be charged in its liquid state. If the refrigerant is charged in
its gaseous state, its composition changes and the system will not work
properly.
Product Introduction
17Liebert® SRC™ User Manual
Product Introduction
Page intentionally left blank.
Liebert® SRC™ User Manual18
3.0Installation
!
3.1Selecting the Location for the Outdoor Unit
WARNING
Risk of improper installation. Can cause serious injury or death.
• To avoid the possibility of fire, do not install the unit in an area where combustible gas may
generate, flow, stagnate, or leak.
• Do not install the unit in a location where acidic solution and spray (sulfur) are often used.
• Do not use the unit in environments where oil, steam, or sulfuric gas are present.
NOTICE
Risk of unauthorized access to the unit. Can cause equipment malfunction or damage.
Install a fence to prevent vermin from crawling into the unit or unauthorized individuals from
accessing it.
Select a location for installing the outdoor unit that will meet the following conditions:
Installation
• Where the unit will not be subjected to direct thermal radiation from other heat sources.
• Where operating sound from the unit will not disturb inhabitants of surrounding buildings.
• Where the unit will not be exposed to direct, strong winds.
• Where there is enough strength to bear the weight of the unit.
• Include space for drainage to ensure condensate flows properly out of the unit when it is in
heating mode.
• Include enough space for air flow and for service access.
To ensure that the outdoor unit operates properly, certain measures are required in locations where there is
a possibility of heavy snowfall or severe wind chill or cold.
1. Prepare for severe winter wind chills and heavy snowfall, even in areas of the country where these are
unusual phenomena.
2. Position the outdoor unit so that its airflow fans are not buried by direct, heave snowfall. If snow piles
up and blocks the airflow, the system may malfunction.
3. Remove any snow that has accumulated 3-15/16 inches or more on the top of the outdoor unit.
4. Place the outdoor unit on a raised platform at least 19-11/16 inches higher than the average annual
snowfall for the area. In environments where there is a possibility of heavy snow, the frame height
must be more than 2 times the amount of average annual snowfall, and should not exceed the width of
the outdoor unit. If the frame width is wider than the outdoor unit, snow may accumulate.
5. Install a snow-protection hood.
6. To prevent snow and heavy rain from entering the outdoor unit, install the suction and discharge ducts
facing away from direct winds.
7. Additionally6, the following conditions should be taken into consideration when the unit operates in
defrost mode:
• If the outdoor unit is installed in a highly-humid environment (near an ocean, lake, etc.), ensure
that the site is well-ventilated and has a lot of natural light. (For example: Install on a rooftop.)
• Sidewalks or parking lots near the outdoor unit may accumulate moisture after unit operates in
defrost mode that can turn into ice.
19Liebert® SRC™ User Manual
Installation
Installation location of the outdoor unit can affect indoor-unit operation. The indoor unit may take longer to
provide heat, or heating performance will be reduced in winter in the outdoor unit is installed:
• In a narrow, shady location.
• Near a location that has a lot of ground moisture.
• In a highly-humid environment.
• In an area in which condensate does not drain properly.
3.1.1Ambient air conditions
NOTICE
Risk of exposure to improper environmental conditions. Can cause equipment damage.
• Avoid exposing the outdoor unit to steam, combustible gases, or other corrosive elements.
• Avoid exposing the unit to discharge from boiler stacks, chimneys, steam relief ports, other air-
conditioning units, kitchen vents, plumbing vents, or substances that may degrade performance
or cause damage to the unit.
• When installing multiple outdoor units, avoid placing the units where discharge of one outdoor
unit will blow into the inlet side of an adjacent unit.
3.1.2Oceanside Applications
Using a Windbreak to Shield the Unit from Sea Wind
NOTE
Ocean winds may cause corrosion, particularly on the condenser and
evaporator fins, which, in turn could cause product malfunction or inefficient
performance.
• Avoid installing the unit where it would be directly exposed to ocean winds.
• Install the outdoor unit on the side of the building opposite from direct ocean winds.
• Select a location with good drainage.
• Periodically clean dust or salt particles off of the heat exchanger with water.
• If the outdoor unit must be placed in a location where it would be subjected to direct ocean winds,
install a concrete windbreak strong enough to block any winds, see Figure 3-1 for windbreak location.
• The windbreak should be more than 150% of the outdoor unit’s height. There must be 2 to 3-1/2 inches
of clearance between the outdoor unit and the windbreak for purposes of flow.
Liebert® SRC™ User Manual20
Figure 3-1 Oceanside placement using a windbreak
1
2
No. Description
1Windbreak
2Sea wind
Installation
21Liebert® SRC™ User Manual
Installation
Using a Building to Shield the Unit from Sea Wind
If a windbreak is not possible, a building or larger structure must be used to shield the outdoor unit from
direct exposure to the sea wind. The unit should be placed on the side of the building directly opposite to
the direction of the wind as shown in Figure 3-2.
Figure 3-2 Oceanside placement using a building
2
1
1
2
No. Description
1Building
2Sea wind
Liebert® SRC™ User Manual22
3.2Mounting the Outdoor Unit
Securely attach the outdoor unit to a condenser pad, base rails, or another mounting platform that is
securely anchored to the ground or building structure. Attach the outdoor unit with a bolt and nut on a
concrete or rigid mount. See Figure 3-3. Follow applicable local codes for clearance, mounting, anchor
and vibrations attenuation requirements.
NOTE
All referenced materials are field-supplied. Images are not to scale.
Figure 3-3 Outdoor unit mounting methods
Installation
1
Top of Unit
2
No. DescriptionNo. Description
1Bolt placement and Anti-vibration pad 3Piping connection
2Foundation
3
3.2.1Mounting Platform
The underlying structure or foundation must be designed to support the weight of the unit. Avoid placing
the unit in a low-lying area where water may accumulate. When installing the outdoor unit on the wall or
roof top, anchor the mounting base securely to account for wind, earthquake or vibration.
3.2.2Tie-downs and Wind Restraints
The strength of the inverter system frame is adequate to be used with field-provided wind restraint tiedowns. The overall tie-down configuration must be approved by a local, professional engineer.
NOTE
Always refer to local code when designing a wind-restraint system.
23Liebert® SRC™ User Manual
Installation
!
12
28
24
12
24
Unit: Inch
3.2.3Snow and Ice Conditions
In climates that experience snow build-up, place the unit on a raised platform to ensure condenser air flow.
The raised support platform must be high enough to allow the unit to remain above possible snow drifts.
Mount the unit on a field-provided snow stand at a minimum height that is equal to the average annual
snowfall plus 20 inches. Design the mount base to prevent snow accumulation on the platform in front or
back of the unit case. If necessary, provide a field fabricated hood to keep snow and ice and/or drifting
snow from accumulating on the coil surfaces. Use inlet and discharge duct or hoods to prevent snow or
rain from accumulating on the fan inlet and outlet guards. Best practice prevents snow from accumulating
on top of the unit. Consider the tie-down requirements in case of high winds or where required by local
codes.
CAUTION
Risk of run-off water freezing on sidewalks and driveways. Can cause falls and injuries. When
selecting the location for the outdoor unit, be sure to choose an area where run-off from defrost will
not accumulate and freeze on sidewalks or driveways.
3.3Clearance requirements
Proper airflow through the outdoor unit coil is critical for correct unit operation. When installing, consider
service, inlet and outlet, and minimum allowable space requirements as illustrated in Figure 3-4.
3.3.1Outdoor Unit Clearance
Specific clearance requirements are for the wall-mount systems. Figure 3-4 shows the overall minimum
clearances that must be observed for safe operation and adequate airflow around the outdoor unit.
Figure 3-4 Outdoor-unit clearances
When placing the outdoor unit under an overhang, awning, sunroof or other “roof-like” structure, observe
the clearance requirements (as shown in Figure 3-5) for height in relation to the unit. This clearance
ensures that heat radiation from the condenser is not restricted around the unit. See Figures 3-6 and 3-7
for recommendations when other obstacles are present.
Adhere to all clearance requirements if installing the unit on a roof. Be sure to level the unit and ensure that
the unit is adequately anchored. Consult local codes for roof-top mounting requirements.
NOTE
Do not place the unit where animals and/or plants will be in the path of the
warm air, or where the warm air and/or noise will disturb neighbors.
Liebert® SRC™ User Manual24
Figure 3-5 Outdoor-unit sunroof/awning clearances
More than
12
More than
12
More than
28
Unit: Inch
More than
24
M
inimum
12
79
24
Minimum 28
Unit: Inch
Figure 3-6 Clearances when there are obstacles on both air-inlet and air-outlet sides
Installation
Minimum
12
Minimum
28
Unit: Inch
NOTE
In Figures 3-6 and 3-7, the obstacle on the outlet side is lower than the
outdoor unit.
Figure 3-7 Clearances when there are obstacles above and on both air-inlet and air-outlet sides
25Liebert® SRC™ User Manual
Installation
!
!
3.3.2Indoor Unit Clearance
Follow recommended practices when choosing an indoor location for the wall-mounted indoor unit.
• Keep unit away from any indoor steam or excessive heat.
• No obstacles should be placed around the unit.
• Condensation drain (leakage piping) should be routed away from the unit.
• Do not install near a doorway.
• Clearance gap between any wall or enclosure and the left or right side of the unit must be greater than
4 inches, Figure 3-8.
• From the top of the unit to the ceiling, there must be greater 8 inches of clearance, see Figure 3-8.
• Unit should be at least 6.5 feet from the floor for adequate clearance.
Figure 3-8 Indoor unit clearance requirements
More than 4 inches
At least 6.5 feet from the floor
Minimum clearance
from ceiling - 8”
More than
4 inches
3.4Installing the Indoor Unit
3.4.1Mounting the Installation Plate to the Wall (SRC18)
WARNING
Risk of electrical shock. Can cause injury or death.
• When choosing a location for the wall-mount plate, be sure to take into consideration routing of
wiring for power outlets within the wall. Avoid contact with hazardous voltage wiring.
• Use caution when drilling holes through the walls for the purposes of piping connections.
Refer to 3.4.3 - Drilling a Piping Hole in the Wall, as you following the plate-installation
procedure.
WARNING
Risk of improper mounting.Can cause building and equipment damage, serious injury or death.
Consult a structural engineer to determine the suitability of the wall for mounting and the
recommended fastening method. Unit must be anchored tightly to a wall having sufficient strength
to support the unit during operation to prevent the unit from falling or creating excessive,
unnecessary vibration during operation.
Follow this procedure and best practices when mounting the indoor unit’s plate to a wall.
Liebert® SRC™ User Manual26
1. Before installation of the plate, confirm the position of the screw types (A or B) between the chassis
A-Type
B-Type
and the installation plate, Figure 3-9.
Figure 3-9 Installation-plate screws for SRC18
Installation
2. Depending on indoor-unit model refer to Figure 3-10 and mount the plate as follows:
• Use the provided screws and mount the installation plate horizontally by aligning the centerline
using a leveling tool.
• Observe the left and right rear piping clearance when drilling into the wall.
Figure 3-10 Piping clearance for SRC18 plate
Unit Outline
18-3/3222-13/32
Ø2-19/32
Left rear
piping
2 -11/16
4-3/32
Place a level on raised tab
Installation Plate
Measuring Tape
Measuring Tape
Hanger
Ø2-19/32
Right rear
piping
2-3/16
8-3/32
Unit: Inch
27Liebert® SRC™ User Manual
Installation
!
Left rear pipingRight rear piping
1-11/16
4-11/32
4-11/16
Unit: Inch
1-11/16
30-
11/16
13-
3/16
3.4.2Mounting the Installation Plate to the Wall (SRC24, SRC36)
WARNING
Risk of electrical shock. Can cause injury or death.
• When choosing a location for the wall-mount plate, be sure to take into consideration routing of
wiring for power outlets within the wall. Avoid contact with hazardous voltage wiring.
• Use caution when drilling holes through the walls for the purposes of piping connections.
Refer to 3.4.3 - Drilling a Piping Hole in the Wall, as you following the plate-installation
procedure.
NOTE
Select the location carefully. Unit should be anchored to a strong wall to
prevent unnecessary vibration.
Follow this procedure and best practices when mounting the indoor unit’s plate to a wall.
1. Use the provided screws, mount the installation plate horizontally by aligning the centerline using a
leveling tool, Figure 3-11.
Figure 3-11 Installation-plate screws for SRC24 and SRC36
Chassis
Hook
Type "A" Screws
2. Observe the left and right rear piping clearance when drilling into the wall, Figure 3-12.
Figure 3-12 Piping clearance for SRC24 and SRC36 plate
Liebert® SRC™ User Manual28
3.4.3Drilling a Piping Hole in the Wall
Installation plate
Indoor uni t
3”
Spacer
1
2
Follow the left or right piping-clearance recommendations.
1. Using a 2-5/8 in. (0.65 mm) hole-core drill bits, drill a hole at either the right or left side of the wall
mounting, Figure 3-13.
• The slant of the hole should be 3/16 to 5/16 of an inch from level with an upward slant on the
indoor-unit side and downward on the outdoor-unit side.
2. Finish-off the newly-drilled hole as shown in Figure 3-13 with a bushing and sleeve covering.
• The sleeve and bushing prevents damage to the tubing/bundling of the piping.
Figure 3-13 Drilling a piping hole
Installation
WALL
Indoor
Core Drill
Bushing
Sleeve
3.4.4Mounting the Indoor Unit to the Plate
1. Hook the indoor unit onto the upper portion of the installation plate, Figure 3-14.
2. Engage the hooks at the top of the indoor unit with the upper edge of the installation plates.
• Make sure that the hooks are properly seated on the installation plate by moving the unit left and
right.
Figure 3-14 Hook the top of the unit to the plate
Outdoor
(3/16"~5/16")
29Liebert® SRC™ User Manual
Installation
Installation Plate
Drain Hose
Holder
L-bracket
Type 'C' Screws
Bo om of
Indoor Unit
Indoor Unit
Piping
Thr ough
Wall
3. Move the bottom of the unit toward the installation plate to anchor to wall, Figure 3-15.
• It helps to press the lower-left and -right sides of the unit against the installation plate until the
hooks engage in their slots.
• You will hear a clicking sound as the bottom attaches to the installation plate.
Figure 3-15 Move the bottom of the unit to the plate and attach to plate
4. Finish by inserting 2 type “C” screws into the bottom of the installation plate, Figure 3-16.
• As you insert the screws, pay attention to the position of the piping through any wall, as shown in
the figure.
Figure 3-16 Insert and tighten screws
Liebert® SRC™ User Manual30
3.4.5Prepare for Piping/Electrical Connection
1. To prepare the indoor unit for piping, disengage the bottom on the indoor unit from the installation plate
by reversing Step 3 of 3.4.4 - Mounting the Indoor Unit to the Plate.
• This separates the bottom of the indoor unit from the wall mount so you can route the drain hose
correctly. Figure 3-17 shows the rear view of the indoor unit.
2. Swing the drain-hose holder (L-bracket) out and anchor as show in Figure 3-15.
3. Refer to 5.0 - Piping, to continue with the piping connections to the indoor unit.
!
!
– or –
Refer to 6.0 - Electrical Connections, to continue with the conduit/electrical wiring to the indoor unit.
Figure 3-17 Rear view of indoor unit
Installaon Plat e
Drain Hose
Drain Hose Holder
3.5Pump Down Procedure
Installation
CAUTION
Risk of inhalation of refrigerant gas. Can cause illness and injury.
Never air purge with refrigerant as it can cause refrigerant leakage.
NOTE
Use a vacuum pump that can evacuate down to 500 microns.
1. If moisture remains in the piping after the system is evacuated for
2 hours, break the vacuum (down to 7.5 psi with nitrogen gas).
2. Evacuate the system again with the vacuum pump for at least 1 hour to
500 microns.
3. If the system does not reach 500 microns within 2 hours, repeat the
vacuum break and evacuation procedure until the gauge does not rise.
This procedure is performed when a unit must be relocated or the refrigerant circuit is serviced. “Pumping
down” is a term that means collecting all refrigerant into the outdoor unit without the loss of any refrigerant.
Use the following procedure to safely collect refrigerant back into the outdoor unit. Always adhere to and
be familiar with local codes regarding the handling of refrigerant.
The system must be placed in Cooling mode to proceed with the pump-down procedure. Refer to 8.3 - Enabling Cooling-only Mode, for the steps.
CAUTION
Risk of exposure or contact with refrigerant. Can cause injury and illness.
Refrigerant is toxic and too cold for safe human contact. Do not inhale or handle refrigerant
directly.
NOTE
Perform pump-down procedure only in cooling mode.
1. Connect a low-pressure gauge with manifold hose to the charge port on the gas-line service valve.
2. Open the gas-line service valve half-way.
31Liebert® SRC™ User Manual
Installation
3. Purge the air in the manifold hose using the refrigerant.
4. Close the liquid line service valve completely.
5. Turn on the cooling-unit’s power switch and start cooling-mode operation, 8.3 - Enabling Cooling-
6. Observe the pressure gauge reading.
only Mode.
• When the gauge reads 1 to 0.5 kg/cm
2
(14.2 to 7.1 psig), fully-close the gas-line valve and
immediately turn of the cooling unit.
Pump-down is complete, and all refrigerant should be collected into the outdoor unit.
Liebert® SRC™ User Manual32
4.0Installation Checklist
Major Component Rough-in
___ 1. Unit was connected properly per local code and the product installation procedures.
___ 2. All literature and bagged accessories have been removed from the fan discharge.
___ 3. Indoor unit was installed, properly supported, and located indoors in a non-corrosive environment.
___ 4. Unit’s gravity condensate drain line was connected and routed where it properly drains away or, if
installed in a mechanical room, was connected and properly routed to a drain terminal.
Piping and Insulation
___ 1. Copper
___ 2. Over 5/8 inches—Rigid ACR only
___ 3. 5/8 inches and under—can use soft ACR.
___ 4. 15% silver brazing material only.
___ 5. All refrigerant pipes and valves were insulated separately. Insulation butts up against the walls of
the indoor units. No gaps or cracks. Insulation was not compressed at clamps and hangers.
Installation Checklist
Brazing Practices
___ 1. Medical grade (there are 4 available) dry nitrogen for purging during brazing was used (constant
3 psi while brazing).
Installation
Refer to the details in the Installation section for more information on any procedure.
Refrigerant Piping
___ 1. All pipe materials were properly stored, capped, and clean. All burrs were removed after cutting
and pipe ends were reamed before brazing.
___ 2. During refrigerant pipe installation, for each segment of pipe, a record was made of the pipe length
(including expansion loops, offsets, double-back sections), and sizes, as well as the quantity and
type of elbows used.
___ 3. All long runs of straight pipe were provided with expansion loops.
___ 4. A torque wrench and backup wrench were used to tighten all flare connections.
___ 5. The back side of all flares were lubricated with a small drop of PVE refrigeration oil before
tightening flare fittings.
___ 6. Ensure all field-made flares are 45°. Used factory-suppled flare nuts only.
___ 7. Pipe segments were properly supported and all wall penetrations were sleeved.
___ 8. Pipe insulation was not compressed at any point.
___ 9. No oil traps, solenoid valves, sight glasses, filter driers, or any other unauthorized refrigerant
specialties were present.
___ 10. Best practice including a minimum of 20-inch straight pipe was installed between each elbow.
33Liebert® SRC™ User Manual
Installation Checklist
Power Wire and Communication Cables
___ 1. Power wiring was connected to a single-phase 208 – 230-V source.
___ 2. Ground wire was installed and properly terminated at the unit.
___ 3. The power supplied was clean with voltage fluctuations with specifications. (±10% of nameplate).
___ 4. Power wiring to the outdoor unit was installed per all local electrical code requirements.
___ 5. Power wiring to the indoor unit was installed per all local electrical code requirements.
___ 6. Factory-supplied cable was used between the indoor unit and the thermostat. No cables were
spliced and no wire caps are present.
___ 7. Communication type RS-485-BUS type.
___ 8. All communication cables were a minimum of 18-AWG, 4 conductor, shielded, and stranded, with
insulation material per local code. Cable segment shield were tied together.
___ 9. Used appropriate crimping tool to attach ring or spade terminals at all power wiring and control
cable terminations.
___ 10. All power and control wires were properly separated using the recommended distance provided in
the installation manual.
Liebert® SRC™ User Manual34
5.0Piping
!
!
5.1Piping Preparation
WARNING
• Do not allow the refrigerant to leak during brazing. If the refrigerant is combusted, it generates a
toxic gas that can cause physical injury or death.
• Do not braze in an enclosed location, and always test for gas leaks before/after brazing.
• After brazing, check for refrigerant gas leaks.
NOTE
1. Do not use kinked pipe cause by excessive bending in one specific area
on its length.
2. Braze the pips to the service-valve pipe stem of the outdoor unit.
5.1.1Creating a Flare Fitting
WARNING
Risk of refrigerant leaks. Can cause equipment malfunction, injury, sickness and death from
suffocation due to oxygen depletion in closed, non-ventilated areas.
When selecting flare fittings, always use a 45° fitting rated for use with high-pressure refrigerant
R410A. Verify that all fittings comply with local, state, or federal standards.
Piping
NOTE
One of the main causes of refrigerant leaks is defective flared connections.
Create flared connections using the procedure shown in Figure 5-1 and steps
that follow.
35Liebert® SRC™ User Manual
Piping
Figure 19: Creating a Flare Fitting
Copper
tube
90°
Slanted Uneven Rough
Pipe
Reamer
Point
down
Flare nut
Copper
tube
Bar
Copper pipe
Clamp handle
Red arrow
Cone
Yoke
Handle
Bar
"A"
Slanted
Inside is shiny with no scratches
Smooth
Even length
Damaged
surface
Cracked Uneven
thickness
Incorrect Flares
1.
2A.2B.
3.
4.
Figure 5-1 Creating a flared fitting
1. Cut the pipe to length.
• Measure the distance between the indoor unit and the outdoor unit.
• Cut the pipes a littler longer than the measured distance.
• Cut the cable 4.9 ft longer than the pipe length.
2. A. Remove the burrs.
• Completely remove all burrs from pipe ends.
• When removing burrs, point the end of the copper pipe down to avoid introducing foreign materials
B. Slide the flare nut onto the copper tube.
3. Flaring the pipe end.
• Use the proper size flaring tool to finish flared connections as shown in Figure 5-1.
into the pipe.
• Always create a 45° flare when working with R410A. Refer to the Warning preceding this
Liebert® SRC™ User Manual36
procedure.
4. Carefully inspect the flared pipe end.
90°
2
45°
2
A
R=0.4~0.8
• Compare the geometry with Figure 5-1 and the dimensions detailed in Figure 5-2 and Table 5-1.
Do not use polyolyester (POE) or any other type of mineral oil as a thread
lubricant. These lubricants are not compatible with PVE oil used in this system
and create oil sludge leading to equipment damage and system malfunction.
1. When connecting the flare nuts, coat the flare (inside and outside) with polyvinyl ether (PVE)
refrigeration oil only.
2. Initially, hand tighten the flare nuts using 3 or 4 turns.
3. Finishing tightening the flare nuts using both a torque wrench and a backup wrench as shown in
Figure 5-3.
Table 5-2Tightening torque for flare nuts
Pipe size (in. O.D.)Tightening torque (ft-lbs)Width of flare (A [in.])
1/4∅
3/8∅
1/2∅
5/8∅
Figure 5-3 Tightening the flare nuts
13.9 – 181/8
24.5 – 30.31/8
39.7 – 47.71/8
45.5 – 59.21/16
Union
37Liebert® SRC™ User Manual
Piping
Moisture
Leaks
5.1.3Loosening Flare Nuts
Always use 2 wrenches to loosen the flare nuts.
5.2Piping Materials and Handling
Pipes used for the refrigerant piping system must include the specified thickness, and the interior must be
clean.
While handling and storing, do not bend or damage the pipes, and take care not to contaminate the interior
with dust, moisture, etc. See Table 5-3 for care of piping.
Figure 5-4 Keep piping capped while storing
-
Table 5-3Three principles of refrigerant piping
DryCleanAirtight
PrinciplesNo moisture should be inside the
piping.
No dust should be inside the
piping.
No leaks should occur.
Problems
Caused
Solutions• Remove moisture from the piping.
• Significant hydrolysis of refrigerant
oil.
• Refrigerant oil degradation.
• Poor insulation of the compressor.
• System does not operate properly.
• EEVs, capillary tubes are clogged.
• Piping ends should remain capped
until connections are complete.
• Do not install piping on a rainy day.
• Connect piping properly at the
unit’s side.
• Remove caps only after the piping
is cut, the burrs are removed, and
after passing the piping through
the walls.
• Evacuate system to a minimum of
500 microns and ensure the
vacuum holds at that level for 24
hours.
Dust
• Refrigerant oil degradation.
• Poor insulation of the
compressor.
• System does not operate
properly.
• EEVs and capillary tubes
become clogged.
• Remove dust from the piping.
• Piping ends should remain
capped until connections are
complete.
• Connect piping properly at the
side of the unit.
• Remove caps only after the
piping is cut and burrs are
removed.
• Retain the cap on the piping
when passing it through walls,
etc.
• Refrigerant gas leaks/shortages.
• Refrigerant oil degradation.
• Poor insulation of the
compressor.
• System does not operate
properly.
• Test system for air-tightness.
• Perform brazing proc3edures
that comply with all applicable
standards.
• Perform flaring procedures that
comply with all applicable
standards.
• Perform flanging procedures that
comply with all applicable
standards.
• Ensure that refrigerant lines are
pressure-test to 550 psig.
Liebert® SRC™ User Manual38
5.2.1Brazing Practices
Pressure-reducing
Valve
Valve
Taping
Nitrogen
Pipe to
be brazed
Refrigerant
Piping
NOTE
It is imperative to keep the piping system free of contaminants and debris
such as copper burrs, slag, or carbon dust during installation. Contaminants
can result in mechanical failure of the system.
All joints are brazed in the field. Refrigeration-system components contain very small capillary tubes, small
orifices, electronic expansion valves, oil separators, and heat exchangers that can easily become blocked.
Proper system operation depends on the installer using best practices and utmost care while assembling
the piping system.
Figure 5-5 Refrigerant-pipe brazing
• While brazing, use a dry-nitrogen purge operating at a minimum pressure of 3 psig and maintain a
steady flow.
Piping
• Before assembly, use dry nitrogen to blow clean all pipe sections.
• Use a tubing cutter, do not use a saw to cut pipe. De-burr and clean all cuts before assembly.
• Store pipe stock in a dry place. Keep pipe capped and clean.
• Use adapters to assemble different sizes of pipe.
• Do not use flux, soft solder, or anti-oxidant agents.
• Use a 15% silver phosphorous copper-brazing alloy to avoid overheating and produce good flow.
• Protect isolation valves, electronic expansion valves, and other heat-sensitive control components
from excessive heat with a wet rag or a heat-barrier spray product.
39Liebert® SRC™ User Manual
Piping
5.2.2Refrigerant-piping System Insulation
NOTE
All refrigerant piping, field-provided isolation ball valves, service valves, and elbows shall be
completely insulated using closed-cell pipe insulation. The liquid and vapor lines must be insulated
separately.
To prevent heat loss/heat gain through the refrigerant5 piping, all refrigerant piping, including liquid
lines and vapor lines shall be insulated separately. Insulation shall be a minimum 1/2-in. thick, and
thickness may need to be increased based-on ambient conditions and local codes.
All insulation joints shall be glued with no air gaps. Insulation material shall fit snugly against the
refrigeration pip3e with no air space between it and the pipe. Insulation passing through pipe
hangers, inside conduit, and/or sleeves must not be compressed. Protects insulation inside
handers and supports with a second layer. All pipe insulation exposed to the sun and outdoor
elements shall be properly protected with PVC, aluminum vapor barrier, or alternatively placed in a
weather-resistant enclosure such as a pipe rack with a top cover and meet local codes.
The design engineer should perform calculations to determine if the factory-supplied insulation
jackets are sufficient to meet local codes and avoid sweating. Add additional insulation if
necessary. Mark all pipes at the pint where the insulation jacket ends. Remove the jacket. Install
field-provided insulation on the run-out and main-trunk pipes first. Peel the adhesive glue protector
slip from the insulation jacket and install the clam-shell jacket over the fitting.
For specific insulation procedures, see 5.4 - Piping Insulation.
5.2.3Selecting Field-supplied Copper Tubing
Copper is the only approved refrigerant-pipe material for use with the Liebert SRC, and Emerson
recommends seamless phosphorous deoxidized ACR type copper pipe, hard-drawn rigid type “K” or “L,” or
annealed-tempered, copper pipe.
• Drawn temper (rigid) ACR copper tubing is available in sizes 3/8 through 2-1/8 inches (ASTM B 280,
clean, dry, and capped).
• Annealed temper (soft) ACR copper tubing is available in sizes 1/4 through 2-1/8 inches (ASTM B 280,
clean, dry, and capped).
NOTE
Tube wall thickness should meet local code requirements and be approved for
an operating pressure of 551 psi. If local code does not specify wall thickness,
Emerson suggests using tube thickness per Table 5-4. When bending tubing,
try to keep the number of bends to a minimum, and use the largest radii
possible to reduce the equivalent length of installed pipe. Also, bending radii
greater than 10 pipe diameters can minimize pressure drop. Be sure that no
traps or sags are present when rolling-out soft copper-tubing coils.
Table 5-4ACR copper-tubing material
TypeSeamless phosphorous deoxidized
ClassUNS C12200 DHP
Straight LengthsH58 temper
CoilsO60 temper
Liebert® SRC™ User Manual40
Piping
Table 5-5Piping-tube thickness
OD (in.)1/43/81/25/83/47/81-1/81-3/81-5/8
MaterialRigid type “K” or “L” and a soft ACR acceptableRigid type “K” or “L” only
Min. Bend
Radius (in.)
Min. Wall
Thickness
(in.)
.563.93751.52.253.03.03.54.04.5
.03.03.035.040.042.045.050.050.050
Table 5-6ACR copper-tubing dimensions and physical characteristics
Drawn TemperAnnealed Temper
Nominal
Pipe Outside
Diameter
(in.)
1/40.250———0.0300.081.00020
3/80.3750.0300.126.000540.0320.134.00053
1/20.5000.0350.198.001010.0320.182.00103
5/80.6250.0400.285.001620.0350.251.00168
3/40.7500.0420.362.002420.0420.362.00242
7/80.8750.0450.455.003360.0450.455.00336
1-1/81.1250.0500.655.005730.0500.655.00573
1. All dimensions provided are in accordance with ASTM B280 – Standard.
2. Design pressure = 551 psig.
3. ACR tubing is available as hard-drawn or annealed (soft) and are suitable for use with R410A refrigerant.
4. The Copper Tube Handbook, 2010, Copper Development Association Inc., 260 Madison Avenue, New York, NY 10016.
Actual
Outside
Diameter
(in.)
Nominal
Wall
Thickness
(in.)Weight (lb/ft)
Cubic ft per
Linear ft
Nominal
Wall
Thickness
(in.)Weight (lb/ft)
1-4
NOTE
• Commercially-available piping often contains dust and other materials.
Always blow it clean with a dry, inert gas.
• Prevent dust, water or other contaminants from entering the piping during
installation. Contaminants can cause mechanical failure.
Cubic ft per
Linear ft
5.2.4No Pipe Size Substitutions
Use only the pipe size recommended by this manual. Using a different size is prohibited and may result in
a system malfunction or failure to work at all.
41Liebert® SRC™ User Manual
Piping
3X
Above an obstacle.
Below an obstacle.
5.2.5Obstacles
When an obstacle, such as an I-beam or concrete T, is in the path of the planned refrigerant-pipe run, it is
best practice to route the pipe over the obstacle. If adequate space is not available to route the insulated
pipe over the obstacle, then route the pipe under the obstacle. In either case, it is imperative that the length
of the horizontal section of pipe above or below the obstacle be a minimum of 3-times the longest vertical
rise (or fall) at either end of the segment, Figure 5-6.
Figure 5-6 Installing piping above and below an obstacle
5.2.6Copper Expansion and Contraction
Under normal operating conditions, the vapor pipe temperature of a Liebert SRC can vary as much as
280°F. With this large variance in pipe temperature, the designer must consider pipe expansion and
contraction to avoid pipe and fitting fatigue failures.
Refrigerant pipe along with the insulation jacket form a cohesive unit that expands and contracts together.
During system operation, thermal heat transfer occurs between the pipe and the surrounding insulation.
If the pipe is mounted in free-air space, no natural restriction to movement is present, if the mounting clips
are properly spaced and installed. When the refrigerant pipe is mounted underground in a utility duct,
stacked among other pipes, natural restriction to linear movement is present. In extreme cased, the
restrictive force of surface friction between insulation jackets could become so great that natural expansion
ceases and the pipe is “fixed” in place. In this situation, opposing force caused by change in refrigerant
fluid/vapor temperature can lead to stress failure of pipes/fittings.
The refrigerant-pipe support system must be engineered to allow free expansion to occur. When a
segment of pipe is mounted between two fixed points, provisions must be provided to allow pipe expansion
to naturally occur. The most common method is the inclusion of expansion loops or U-bends. Each
segment of pipe has a natural fixed point where no movement occurs. This fixed point is located at the
center point of the segment assuming that the entire pipe is insulated in a similar fashion. The natural fixed
point of the pipe segment is typically where the expansion loop or U-bend should be.
Linear pipe expansion can be calculated using the following formula:
LE = C x L x (T
– Ta) x 12
r
LE = Anticipated linear tubing expansion (in.)
-6
C = Constant (for copper = 9.2 x 10
in./in.°F)
L = Length of pipe (ft)
T
= Refrigerant-pipe temperature (°F)
r
= Ambient air temperature (°F)
T
a
12 = Inches-to-feet conversion (12 in./ft)
Liebert® SRC™ User Manual42
1. From Table 5-7 , find the row corresponding with the actual length of the straight pipe segment.
2. Estimate the minimum and maximum temperature of the pipe.
In the column showing the minimum pipe temperature, look up the anticipated expansion distance. Do
the same for the maximum pipe temperature.
3. Calculate the difference in the two expansion distance values.
The result is the anticipated change in pipe length.
Table 5-7Linear thermal expansion of copper tubing, in inches
Pipe
Length
1. Pipe length baseline temperature = 0°F. “Expansion of Carbon, Copper and Stainless Steel Pipe,” The Engineer’s Toolbox,
A system is installed and the design shows that there is a 100-foot straight segment of tubing between an
indoor unit and the outdoor unit. When heating, this pipe transports hot gas vapor to the indoor units at
120°F. When cooling, the same tube is a suction line that returns refrigerant vapor to the outdoor unit at
40°F. Look-up the copper-tubing expansion at each temperature and calculate the difference.
Vapor Line
Piping
Transporting hot vapor: 100-ft pipe at 120°F = 1.40 in.
Transporting suction vapor: 100-ft pipe at 40°F = 0.40 in.
Anticipated change in length: 1.40 in. – 0.40 in. = 1.00 in.
Liquid Line
The liquid temperature remains relatively the same temperature, only direction of flow reverses. Therefore,
no significant change in length of the liquid line is anticipated.
When creating an expansion joint, the joint height should be a minimum of two times the joint width.
Although different types of expansion arrangements are available, the data for correctly sizing an
expansion loop is provided in Tab le 5-8. Use soft copper with long-radius bends on longer runs or longradius elbows for shorter pipe segments. Using the anticipated linear expansion (LE) distance calculated,
look-up the expansion loop or U-bend minimum design dimensions. If you choose to use other types of
expansion joints, design per ASTM B-88 Standards.
43Liebert® SRC™ User Manual
Piping
Large Tubing U-bend (>3/4 in.)LoopSmall Tubing U-bend (<3/4 in.)
R
L
R
L
L
Figure 5-7 Coiled expansion loops and offsets
Table 5-8Radii of coiled expansion loops and developed lengths of expansion offsets
Anticipated Linear
Expansion (LE)
1/2
1
1-1/2
2
2-1/2
3
3-1/2
4
(in.)
1
R
2
L
1
R
2
L
1
R
2
L
1
R
2
L
1
R
2
L
1
R
2
L
1
R
2
L
1
R
2
L
1/43/81/23/4
6789
38445059
9101113
54637083
11121416
667786101
12141619
778999117
14161821
8699111131
15171923
94109122143
16192125
102117131155
17202226
109126140166
Nominal Tube Size (OD) in.
5.2.7Pipe Bends
When bending soft copper, use long-radius bends. Refer to Table 5-8 for minimum radius specifications.
5.2.8In-line Refrigeration Components
NOTE
Components such as oil traps, solenoid valves, filter-dryers, sight glasses, tee
fittings, and other after-market accessories are not permitted on the
refrigerant-piping system between the outdoor unit and the indoor unit.
Liebert SRC systems are provided with redundant systems that assure oil is properly returned to the
compressor. Sight glasses and solenoid valves may cause vapor to form in the liquid stream.
NOTE
Over time, dryers may deteriorate and introduce debris into the system. The
designer and installer should verify that the refrigerant-piping system is free of
Liebert® SRC™ User Manual44
traps, sagging pipes, sight glasses, filter dryers, etc.
5.2.9Field-provided Isolation Ball Valves
Emerson allows the installation of field-supplied ball valves with Schrader ports at each indoor unit. Fullport isolation ball valves with Schrader ports (positioned between valve and indoor unit) rated for use with
R410A refrigerant should be used on both the liquid and vapor lines.
If valves are not installed and a single indoor unit must be removed or repaired, the entire system must be
shut down and evacuated. Position valves with a minimum distance of 3 to 6 inches of pipe on either side
of the valve, and placed between 6 and 12 inches from the run-out pipe to the upstream main pipe. If ball
valves are installed closer that this to the indoor unit, a section of pipe becomes a dead zone where oil may
accumulate when the valves are closed.
5.2.10 Using Elbows
Filed-supplied elbows are allowed as long as they are designed for use with R410A refrigerant. The
designer, however, should be cautious with the quantity and size of fittings used, and must account for the
additional pressure losses in equivalent-pipe-length calculation.
The equivalent pipe length of each elbow must be added to each pipe segment, Ta ble 5- 9.
Table 5-9Equivalent piping length for piping components
ComponentSize (in.)
Elbow (ft)
1/43/81/25/83/4
0.50.60.70.81.2
Piping
5.2.11 Pipe Supports
NOTE
A properly-installed pipe system should be adequately supported to avoid
pipe sagging. Sagging pipes become oil traps that lead to equipment
malfunction.
Pipe supports should never touch the pipe wall. Insulate the pipe first because pipe supports must be
install outside (around) the primary pipe-insulation jacket, Figure 5-8. Use Clevis hangers with shield
between the hangers and insulation. Field-provided pipe supports should be designed to meet local codes.
If allowed by code, use fiber straps or split-ring hangers suspended from the ceiling on all-thread rods
(fiber straps or split-ring hangers may be used as long as they do not compress the pipe insulation). Place
a second layer of insulation of the pipe-insulation jacket to prevent chafing and compression of the primary
insulation withing the confines of the support-pipe clamp.
Figure 5-8 Pipe-hanger details
45Liebert® SRC™ User Manual
Piping
A
B
Pipe
Clamps
A + B 12”–19”
A properly-installed pipe system has sufficient supports to prevent pipes from sagging during the life of the
system. As necessary, place supports closer for segments where potential sagging could occur. Maximum
spacing of the pipe supports must meet local codes.
If local codes do not specify pipe-support spacing, support the pipes as follows:
• Maximum of 5 feet on center for straight segments of pipe up to 3/4-in. outside diameter.
• Maximum of 6 feet on center for pipe up to 1-in. outside diameter.
• Maximum of 8 feet on center for pipe up to 2-in. outside diameter.
Wherever the pipe changes direction, place pipe clamps within 12 inches on one side and within 12 to 19
inches of bend on the other side, as shown in Figure 5-9.
Figure 5-9 Typical pipe-support location for a change in pipe direction
Liebert® SRC™ User Manual46
5.2.12 Pipe Sleeves at Penetrations
Emerson requires that all pipe penetrations through walls, floors, and pipes buried underground be
properly-insulated and routed through an appropriate wall sleeve of sufficient size to prevent compression
of refrigerant-pipe insulation and free movement of the pipe withing the sleeve, Figure 5-10.
Figure 5-10 Pipe sleeve options
Piping
NOTE
The diameter of the penetrations must be determined by the pipe diameter
plus the thickness of the insulation.
47Liebert® SRC™ User Manual
Piping
Vapor Line
Liquid Line
Min. 18 Gauge
Cable
Power/Communication
Pipe Sleeve
Insulation Material
Insulation
Material
5.2.13 Underground Refrigerant Piping
Refrigerant pipe installed underground should be routed inside a vapor-tight protective sleeve to prevent
deterioration of the insulation and water infiltration. Refrigerant pipe installed inside underground casing
must be continuous without any joints. Underground refrigerant pipe must be located at a level below the
frost line.
Figure 5-11 shows the arrangement of refrigerant pipe and cable(s) in a conduit. Tabl e 5 -10 shows
conduit sizes for utility conduit.
Figure 5-11 Typical arrangement of pipe and cables in a utility conduit
Table 5-10 Utility-conduit sizes
Vapor Pipe
Liquid Pipe
3/8 (1-1/8)
1. OD pipe diameter in inches. Values in parentheses indicate OD of pipe with insulation
jacket.
2. Diameter of pipe with insulation. Thickness of pipe insulation is typical. Actual required
thickness may vary based on surrounding ambient conditions and should be calculated
and specified by the design engineer.
3. Insulation thickness (value in parenthesis) = 3/8 inch.
4. Insulation thickness (value in parenthesis) = 1 inch.
1
3
3/8 (1-1/8
2,3
)5/8 (2-1/8
44
1
2,4
)
Table 5-11 Heat-pump unit refrigerant-pipe connections (All brazed type)
ModelLiquid Conn., in. Vapor Conn., in.
SCR18, 24, 363/85/8
Liebert® SRC™ User Manual48
5.3Piping Connections
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
Max Length = A
Max Elevation = B
Unit = Feet
5.3.1Connection Limitations
Liebert SRC systems consist of one outdoor unit and one indoor unit. One of the most critical elements of
a system is the refrigerant piping. Ta bl e 5-12 lists pipe-length limits that must be followed in the design of
an SRC system. Refer to Figure 5-12 for maximum length and elevation of piping.
Table 5-12 Refrigerant-piping system limitations
Pipe Length
(ELF = Equivalent length of pipe in feet)
Elevation
(All elevation limitations are measured
in actual feet.)
Figure 5-12 System layout
Longest total equivalent piping length
Shortest total equivalent piping length9.89.89.8
Distance between fittings and indoor units or outdoor units >
If outdoor unit is above indoor unit.49.298.498.4
If outdoor unit is below indoor unit.49.298.498.4
Piping
SRC18 SRC24 SRC36
98.4164.0164.0
20 in. >20 in. >20 in.
Additional refrigerant needed (oz/ft)0.220.380.38
49Liebert® SRC™ User Manual
Piping
Vinyl tape (Wide)
a
Saddle
A
B
Pipe
Clamps
A + B 12”–19”
5.3.2Piping Connections Layout
Liebert SRCs are a 1-to-1 system. There is a direct piping connection between the outdoor unit and the
indoor unit. Figure 5-13 illustrates the basic pipe connections between the outdoor and indoor unit. Refer
back to this illustration as you proceed with pipe connection. Figure 5-13 shows the indoor unit installed at
a higher position than the outdoor unit. However, if you install the outdoor unit in a higher position than the
indoor units, the basic pipe connections still apply.
Refer to Table 5 -12 for specific length limitations on indoor- and outdoor-unit positioning.
Figure 5-13 Piping installation and connection overview
NOTE
• As you proceed with the piping connections, be sure to adhere to the pipesupport spacing as shown in Figure 5-14. Refer back to 5.2.11 - Pipe Supports, for more information about using elbows, clamps and pipesupport materials.
• Always follow state and local codes for piping and accurate supportspacing along the outdoor pipe line.
Figure 5-14 Pipe-support spacing for outdoors
Liebert® SRC™ User Manual50
5.3.2.1Pipe bundling
Vapor Line
Liquid Line
Min. 18 Gauge
Cable
Power/Communication
Pipe Sleeve
Insulation Material
Insulation
Material
Refer to Figure 5-15 for proper cable and pipe bundling. Note the placement of the piping along with the
necessary insulation material.
Figure 5-15 Proper pipe and cable bundling—cut-away
1. Be sure to wrap each pipe with proper insulation material.
2. Secure the piping by wrapping vinyl tape vinyl tape around the pipe.
• Use narrow-size tape for wrapping the actual pipe, Figure 5-16.
3. You can include the drain hose in the bundled piping and wrap all of them together using wider vinyl
tape, Figure 5-16.
Piping
• The end of the drain-hose outlet must be routed above the ground.
Figure 5-16 Bundling and taping piping and cables
Bundling Piping
Drain hos e
Pipe
Vinyl tape(narrow)
Wrap with
vinyl tape(wide)
51Liebert® SRC™ User Manual
Piping
5.3.2.2Bundling and Trap when Indoor Unit is above Outdoor Unit
1. Refer to Figure 5-17, and tape the piping, drain hose, and connection cable from down to up.
2. Secure the taped piping along the exterior wall using pipe clamps.
3. Create a trap above the electrical connections cover to prevent water from penetrating electrical
components and wiring.
Figure 5-17 Piping/Trap when indoor unit is above outdoor unit
Seal small openings
around pipings with a
gum type sealant.
Pipe Clamps
to Secure Pipe
Against Wal l
Trap is required to prevent water
from entering into electrical parts.
Connecting cable
Pipings
Taping
Drain hose
5.3.2.3Bundling and Trap when Indoor Unit is below Outdoor Unit
1. Refer to Figure 5-18, and tape and tape the piping, drain hose, and connection cable from down to up.
2. Secure the taped piping along the exterior wall using pipe clamps.
3. Create a trap above the electrical connections cover to prevent water from penetrating electrical
components and wiring.
Figure 5-18 Piping/Trap when indoor unit is below outdoor unit
Seal a small opening
around the pipings
with gum type sealant .
Trap
Liebert® SRC™ User Manual52
Pipe Clamps
to Secure Pipe
Against Wall
Trap
5.3.3Routing the Drain Hose for Indoor Unit
Downward slope
to outdoor
for proper drainage
Indoor
Unit
Piping
Drain hose is routed from the indoor unit, through the structure (wall) to the outdoors. The hose should
slope at an angle where it is higher at the indoor unit and lower at the outdoor area, letting gravity push
condensation down and out. Figure 5-19 shows the proper drainage slope. Figure 5-20 shows incorrect
methods of routing the drain hose, which cause leakage at the indoor unit.
Figure 5-19 Correct slope angle for drain hose
Figure 5-20 Incorrect methods of routing drain hose
Piping
Indoor Uni t
Indoor Uni t
Indoor Unit
Incorr ect Drainage Setup
Upward slope
to outdoor
can cause indoor
Water
leakage
Water
leakage
Water
leakage
Accumulated
drain water
Waving
Tip of drain hose
dipped in water
leaks.
Air
Ditch
Drain Hose
Less than
2 Inch gap from ground
53Liebert® SRC™ User Manual
Piping
B
A
C
5.3.4Installing a Drain Hose on the Outdoor Unit
Depending on the installation site, it may be necessary to install a drain plug (factory-supplied).
1. Depending on your unit model, refer to Figure 5-21 or 5-22 and to Tabl e 5-13 for the drain-connection
components.
2. Connect a field-suppled hose to the drain connections (A). If the hose is too long, position it carefully to
prevent kinks.
Table 5-13 Outdoor unit drain-connection components
Quantity, each
SRC24,
Label
A11Drain connection
B31Drain cap
C11Drain washer
NOTE
Do not use a drain hose with the outdoor unit in cold climates, otherwise the
drain water may freeze and impair heating performance.
Figure 5-21 Outdoor unit drain-connection components for SRC18
SRC36
ComponentSRC18
B
B
A
B
C
Figure 5-22 Outdoor unit drain-connection components for SRC24 and SRC36
Liebert® SRC™ User Manual54
5.3.5Connecting Piping on the SCR18 Outdoor Unit
1. Remove the tubing cover by loosening the fastening screws, Figure 5-23.
NOTE
Do not thread liquid or gas piping through bracket used to hold main power
cables.
Figure 5-23 Removing connection cover from SRC18 outdoor unit
Tubing Cover
Piping
Bracket for
Main Power Cables
2. Align the center of the refrigerant pipe and corresponding connection as shown in Figure 5-24.
Figure 5-24 Align center of piping connection
3. Refer to Figure 5-25 for correct liquid and gas pipe attachment to the outdoor unit.
4. Place a couple of drops of refrigerant oil on the opening rim of the flare before assembling, making
sure that you do not introduce any contaminants, and tighten the flare nut by hand.
55Liebert® SRC™ User Manual
Piping
Outdoor Unit
Gas Piping
(Larger diameter)
Liquid Piping
(Smaller diameter)
Torque Wrench
Bracket for
Main Power
Cables
5. Following the torque guidelines in Figure 5-14, finish tightening the flare nut with a torque wrench until
the wrench clicks referring to Tab le 5-25 for correct connection points.
NOTE
When tightening the flare nut with a torque wrench, make sure the direction
for tightening follows the arrow on the wrench.
Table 5-14 Tightening torque for flare nuts
Pipe size (in. O.D.)Tightening torque (ft-lbs)
1/4
3/8
1/2
5/8
3/471.6 – 87.5
Figure 5-25 Correct piping attachment for SRC18 outdoor unit
13.9 – 18
24.5 – 30.3
39.7 – 47.7
45.5 – 59.2
Liebert® SRC™ User Manual56
5.3.6Connecting Piping on the SCR24 and SCR36 Outdoor Unit
Tubing
Cover
Terminal
Block Cover
Terminal Block
1. Remove the tubing cover by loosening the fastening screws, Figure 5-26.
NOTE
When tightening the flare nut with a torque wrench, make sure the direction
for tightening follows the arrow on the wrench.
Figure 5-26 Removing connection cover from SRC24 and SRC36 outdoor unit
Piping
2. Align the center of the refrigerant pipe and corresponding connection as shown in Figure 5-27.
Figure 5-27 Align center of piping connection
3. Refer to Figure 5-28 for correct liquid and gas pipe attachment to the outdoor unit.
4. Place a couple of drops of refrigerant oil on the opening rim of the flare before assembling, making
sure that you do not introduce any contaminants, and tighten the flare nut by hand.
57Liebert® SRC™ User Manual
Piping
Torque wrench
Liquid side piping
(Smaller diameter)
Gas side piping
(Bigger diameter)
Outdoor unit
5. Following the torque guidelines in Tab le 5-15, finish tightening the flare nut with a torque wrench until
the wrench clicks referring to Figure 5-28 for correct connection points.
NOTE
When tightening the flare nut with a torque wrench, make sure the direction
for tightening follows the arrow on the wrench.
Table 5-15 Tightening torque for flare nuts
Pipe size (in. O.D.)Tightening torque (ft-lbs)
1/4
3/8
1/2
5/8
13.9 – 18
24.5 – 30.3
39.7 – 47.7
45.5 – 59.2
3/471.6 – 87.5
Figure 5-28 Correct piping attachment for SRC24 and SRC36 outdoor unit
Liebert® SRC™ User Manual58
5.3.7Connecting Piping on the Indoor Unit
Chassis cover
While following this procedure, refer to 5.3.2.1 - Pipe bundling for specific bundling instructions, and to
5.3.3 - Routing the Drain Hose for Indoor Unit for proper drainage slope during piping.
1. Pull the screw cap at the bottom of the indoor unit.
2. Unscrew the 3 screws at the bottom of the chassis cover, Figure 5-29, and remove the chassis cover,
taking care not to scratch the main horizontal vane.
Figure 5-29 Removing the chassis cover from indoor unit
Piping
59Liebert® SRC™ User Manual
Piping
Insulation material
3. From the rear of the indoor unit, pull the tubing holder away from the unit as shown in Figure 5-30.
4. Remove the pipe port cover.
5. Position the tubing by unfolding the tubing and bending the tubing slowly downward first, as shown in
Figure 5-30.
NOTE
Bending the tubing directly left or right, without bending downward first, may
cause damage.
Figure 5-30 Bending drain tubing at rear of indoor unit
Unfold
slowly
downward
Bend from
downward position
6. As shown in Figure 5-31, the fully encase the connection pipe and the indoor-unit pipe in insulation
material by binding them together using vinyl tape. Make sure there are not gaps when binding.
Figure 5-31 Piping connection with insulation material
Liebert® SRC™ User Manual60
7. Make sure the tube cutting line is placed upward, Figure 5-32.
Gas Pipe
Liquid Pipe
Cutting Line
Cutting Line
Correct Incorrect
Figure 5-32 Correct cutting line placement
8. Use narrow type vinyl tape, and make sure that the section placed in the rear pipe housing is wrapped
sufficiently.
9. Continue to wrap the indoor-unit pipe connection to the outdoor-unit as shown in Figure 5-33.
Figure 5-33 Wrapping connection pipe to indoor-unit pipe
Piping
Connection pipe
Vinyl tape (wide)
Connecting cabl e
Indoor unit pipe
Wrap with vinyl tape
Pipe
Vinyl tape(narrow )
61Liebert® SRC™ User Manual
Piping
Wrap with vinyl tape
Drain hose
Pipe
Vinyl tape(wide)
10. Using a wider vinyl tape, bundle the piping and the drain hose together, Figure 5-34.
• The tape should cover the piping and fit into the rear pipe housing on the back of the indoor unit as
shown in Figure 5-35.
Figure 5-34 Bundling pipe and drain hose at rear of indoor unit
Figure 5-35 Piping bundle placement in housing at rear of indoor unit
Drain hose
Tape
Connecting
cable
Drain hose
Connecting pipe
Liebert® SRC™ User Manual62
5.4Piping Insulation
Liquid Pipe
Communication Cables
Gas Pipe
Power Wiring
Insulation
A
B
C
D
E
E
D
D
B
A
C
To prevent heat loss/heat gain through the refrigerant piping, all refrigerant piping, including liquid lines and
vapor lines, must be insulated separately. Insulation must be a minimum 1/2-in. thick, and the thickness
may need to be increased based on ambient conditions and local codes. All refrigerant piping, including
field-supplied isolation ball valves, service valves, and elbows must be completely insulated using closedcell pipe insulation. All insulation joints must be glued with no air gaps. Insulation material must fit snugly
against the refrigerations pipe with now space between it and the pipe. Insulation passing through pipe
hangers, inside conduit, and/or sleeves must not be compressed. Protect insulation inside hangers and
supports with a second layer. All pipe insulation exposed to direct sunlight and deterioration-producing
elements must be properly protected with a PVC-aluminum vapor-barrier jacket, or placed in a weatherresistant enclosure such as a pipe rack with a top cover. The design engineer should perform calculations
to determine if the factory-supplied insulation jackets have sufficient thickness to meet local codes and to
void sweating at job-site conditions. Maximum refrigerant-pipe temperature is 227°F. Minimum refrigerantpipe temperature is –4°F. Add additional insulation if necessary.
NOTE
• Do not insulate gas and liquid pipes together as this can result in pipe
leakage and malfunction due to extreme temperature fluctuations.
• Be sure to fully insulate the piping connections.
Figure 5-36 Typical pipe-insulation, power wire, and communications-cable arrangement
Piping
63Liebert® SRC™ User Manual
Piping
Surface of
Indoor Unit Casing
Field-Provided
Pipe Insulation
Figure 5-37 Typical butt-joint insulation at indoor unit
1. Typical location (air-conditioned): When the piping passes through and indoor area where the indoor
unit operates.
• Apartment, classroom, office, mall, hospital, etc.
2. Special location (air-conditioned):
a. When the location is air-conditioned, but there is severe temperature/humidity difference due to
high ceilings.
• Church, auditorium, theater, lobby, etc.
b. When the location is air-conditioned, but internal temperature/humidity are high.
• Bathroom, swimming pool, locker room, etc.
3. Typical location (non air-conditioned): When the piping passes through an indoor area where the
indoor unit does not operate.
• Hallway, dormitory, school, etc.
4. Special location (non air-conditioned): If the following conditions are present:
a. When the piping passes through an indoor area where the indoor unit does not operate.
b. When the humidity is high and there is no air flow in the location where the piping is installed.
• The thickness of the above insulation material is based on heat conductivity of 0.61
Btu/in/h/ft
2
/°F.
65Liebert® SRC™ User Manual
Piping
5.5Air Purging
Air purging is performed after all piping is connected between the indoor and the outdoor unit. This step is
necessary to be sure that air refrigerant can flow through the system without the danger of leakage or
pressure issues. Air and moisture that is left in the ping can lead to undesirable results and can cause
damage to the working unit. it is important to go through a complete air-purging cycle to be sure that the
lines are cleared out. Note that you may have to repeat this process if any air or moisture is found to
remain in the piping. After air purging and evacuating the lines, be sure do a leak test for all piping and
tubing.
NOTE
Insufficient or incorrectly-performed air purging may lead to the following:
• Pressure in the system can rise.
• Operating current can rise.
• Cooling or heating efficiency falls.
• Moisture in the refrigerant circuit may freeze and block capillary tubing.
• Water can lead to corrosion of parts in the system.
1. Verify that each set of pipes (liquid and gas) are properly connected between the indoor and outdoor
unit.
2. Verify that all wiring for a test run is complete.
3. Remove the service-valve caps from the gas and liquid valves at the outdoor unit, Figure 5-39.
• Keep both liquid and gas service valves closed at this step.
Figure 5-39 Removing service-valve caps from outdoor unit for purging
Evacuation
Outdoor Unit
Gas sid e
3-way valve(Close)
3-way valve(Close)
2-way valve(Close)
2-way valve(Close)
Liquid side
Valve
Caps
Liebert® SRC™ User Manual66
4. Set-up the purging-hose connections, Figure 5-40.
!
Figure 5-40 Evacuation set up
Piping
Indoor Unit
Outdoor Unit
Piping Bundl e
Manifold Valve
Pressure
Gauge
Lo=Open
Lo Hi
Hi=Close
Charge Hose
Vacuum Pum p
5. Do a leak test per 5.5.1 - Piping Leak Test.
• A successful leak test must be completed before beginning evacuation.
6. Refer to 5.5.2 - Evacuation to complete the purge process.
5.5.1Piping Leak Test
Perform the leak test by pressurizing nitrogen gas to 550 psi on both the liquid and gas pipes. Test with the
piping service valves closed. if the pressure does not drop for 24 hours, the system passes the test. It the
pressure drops, there is a nitrogen leak in the system. Find the leak, repair it, and test again.
WARNING
Risk of using combustible gases. Can cause explosion and fire resulting in building and equipment
damage, serious injury or death.
Do not use combustible gases, including oxygen for leak detection. Use only inert gas (nitrogen)
when checking plumbing leaks, cleaning or repairing pipes, etc.
67Liebert® SRC™ User Manual
Piping
5.5.1.1Connecting the pressure gauge
NOTE
• To avoid nitrogen entering the refrigerant system in a liquid state, the top of
the cylinder must be higher than its bottom when you pressurize the
system.
• Be sure the cylinder is used in a vertical standing position.
1. Connect the manifold valve (which includes the pressure gages) and the dry-nitrogen gas cylinder to
the services valves using a charge hose, Figure 5-41.
2. Pressurize the system to maximum 550 psig with dry-nitrogen gas and close the cylinder valve when
the gauge reaches 550 psig.
Figure 5-41 Leak-test set-up diagram
Indoor Uni t
Piping Bundle
Pressure
Gauge
Charge Hos e
Manifold Valve
Lo Hi
Nitrogen Gas
Tank (Upright
Position)
Outdoor Uni t
5.5.1.2Soap-and-Water Leak Testing
1. Remove the caps from the 2-way and 3-way valves, Figure 5-39.
2. Open the 2-way valve by turning the valve stem counter-clockwise approximately 90 degrees, wait for
2 to 3 seconds, and close it.
3. While running nitrogen pressure, apply a soapy-water or liquid, neutral detergent on the indoor or
outdoor unit connections using a soft brush, and observe the connections for any leaks.
• Bubbles at connection points or joints indicate a leak.
4. Make a note of any leaks along the liquid and gas piping.
5. Disengage the nitrogen pressure by loosening the charge hose at the cylinder, Figure 5-41.
6. When pressure returns to normal, disconnect the charge hose from the cylinder.
7. Make repairs to all connections and piping where leaks were observed.
8. When repairs are complete, repeat the leak test using nitrogen pressure and check for further leaks.
9. Once the piping system is leak-free, proceed to 5.5.2 - Evacuation.
Liebert® SRC™ User Manual68
5.5.1.3Ambient Temperature for Leak Test
If the ambient temperature changed between the time when the pressure was applied and when the
pressure-drop was checked, adjust the results by factoring-in approximately 1.45 psi for each 2°F of
temperature difference.
Correction formula = (Ambient temperature when pressure was applied – Ambient temperature when
pressure drop was checked) x 0.01.
For example:
When pressure (550 psig) was applied, the ambient temperature was 80.6°F. When the pressure drop was
checked 24 hours later (540 psi), the ambient temperature was 68°F.
Therefore, 80.6 – 68 x 0.01 = 0.126. In this case, the pressure drop of 0.126 was due to temperature
difference, and there is no leak in the refrigerant-piping system.
5.5.2Evacuation
After successfully completing leak testing, use the same hook-up described in Figure 5-40, page 67, to
perform the evacuation procedure.
NOTE
• Be sure to use a manifold valve for air purging. If it is not available, use a
stop valve.
• Be sure that the knob of the 3-way valve is always kept closed.
Piping
1. Confirm that the “Lo” knob of the manifold valve is open, Figure 5-40, page 67.
2. Confirm that the “Hi” know of the manifold valve is closed.
3. Run the vacuum pump until the system is evacuated down to 300 microns, and continue to run the
pump an additional 15 minutes.
NOTE
The duration of running the vacuum pump will vary according to pipe length
and pump capacity. Refer to Table 5-17 for accurate time duration.
Table 5-17 Evacuation timing*
Tubing less than 33 ft.Tubing more than 33 ft.
10 minutes or more15 minutes or more
* Required time for evacuation when 30-gal/h vacuum pump is used.
4. When appropriate time has elapsed, turn-off the pump and leave the connections secured on the
service valves for 5 minutes.
5. If the system fails to hold 500 microns or less, check all connections for a tight fit and repeat the
evacuation steps.
6. When the correct vacuum is reached, close the “Lo” know of the manifold valve and stop the vacuum
pump.
69Liebert® SRC™ User Manual
Piping
5.5.3Removing Purge and Test Equipment
When evacuation is completed, turn-off all valves a t the outdoor unit and safely disengage the manifold
valve and vacuum pump using the following steps.
1. Using a wrench, turn the valve of the liquid stem counter-clockwise to fully open the valve, Figure 5-40, page 67.
2. Turn the valve of the gas temp counter-clockwise to fully open the valve.
3. Loosen the charge hose connected to the gas-side service port slightly to release the pressure, and
remove the hose.
4. Replace the flare nut and its cap on the gas service port, and fasten the flare nut securely using an
adjustable wrench.
• This step is very important to prevent leakage from the system.
5. Replace the valve caps at both gas- and liquid-side service valves and fasten them tightly.
Liebert® SRC™ User Manual70
6.0Electrical Connections
!
!
WARNING
Arc flash and electric shock hazard. Can cause serious injury or death. Open all local and remote
electric power disconnect switches, verify with a voltmeter that power is off and wear personal
protective equipment per NFPA 70E before working within the electric control enclosure.
WARNING
Risk of electric shock and overheated wiring. Can cause injury or death. All field-supplied power
wiring, overcurrent protection (circuit breakers/fuses) and earth grounding must be installed by a
trained and qualified HVAC technician in accordance with local, state, and National Electrical Code
regulations related to electrical equipment and wiring.
• Read and follow explicitly all instructions and safety alert messages in this manual.
• Do not connect ground wire to refrigerant, gas or water piping, to lightning rods, to telephone
ground wiring, or to the building plumbing system.
• Replace and securely fasten all control box and panel covers immediately after working on the
unit to protect the operator from the hazards above.
NOTICE
Risk of electrical phase reversal. Can cause equipment damage, unit malfunction and loss of
cooling operation.
Electrical Connections
If there is a possibility of reversed phase, phase loss, momentary blackout, or the power goes on
and off while the system is operating, install a field-supplied phase-loss protection circuit.
NOTE
Consider ambient conditions (temperature, direct sunlight, inclement weather,
etc.) when selecting, installing, and connecting the power wiring.
6.1Power-supply/Power-wiring Specifications
• Liebert SRC systems operate at 1∅, 208 – 230 V, 60 Hz.
• Power-supply wire type and size should be selected based on National Electrical Code and local
codes. Maximum allowable voltage fluctuation ±10% or nameplate rated value. Refer to Figure 6-1 for
wiring guidelines.
• Properly ground the indoor and outdoor unit per National Electrical Code and local codes.
• Use only copper wiring that is stranded and shielded with the wires separately insulated.
• Ground wire should be longer than the common power/communication wires.
• Refer to the appropriate circuit and terminal-block diagrams for your model unit.
• Always match color codes of each wire and follow wiring diagram.
71Liebert® SRC™ User Manual
Electrical Connections
Ring Terminal
Power Wiring
Figure 6-1 Indoor and Outdoor wiring and communications cable diagram
Line Voltage
(208/230V)
For 9/12K Indoor Units: AWG 14
For 18K Indoor Units: AWG 12
6/16” ± 2/16”
Power Wiring, Ground
to Outdoor Unit
GN/YL
13/16”
Power Wiring, Ground,
Communication Cable
From Outdoor Unit
To Indoor Unit
GN/YL = (Ground, Yellow)
Best practice dictates using ring or spade terminals to terminate power wiring at the power terminal block,
Figure 6-2.
Figure 6-2 Typical ring terminal
For 9/12/18K Indoor Units: AWG 18
GN/YL
6/16” ± 2/16”
13/16”
Liebert® SRC™ User Manual72
If ring terminals or space clips are not available then:
!
:Copper Wire
Terminate multiple power wires of
the same gauge to both sides.
Do not terminate two wires on
one side.
Do not terminate different gauge
wires to a terminal block.
WARNING
Risk of improper electrical connection termination. Can cause building and equipment damage,
excessive heat at the terminations, smoke, fire, electric shock, serious injury and death.
Do not terminate different gauge wires to the power terminal block. Slack in the wiring may
generate heat and fire.Do not ground the shield of the communications cable to the indoor unit
frame or other grounded entities of the building.
NOTE
• When terminating wires of the same thickness, follow the instructions in
Figure 6-3.
• Attach the wire securely without placing external force on the terminal
block.
• Use an appropriately-sized screwdriver to tighten the terminals.
• Do not over-tighten the connections. Over-tightening may damage the
terminals.
• Never apply line-voltage power to the communications-cable terminal
block. If contact is made, the PCBs may be damaged.
• Always include some allowance in the wiring length when terminating.
Provide some slack to facilitate removal of electrical panels when servicing.
Electrical Connections
Figure 6-3 Proper and Improper power-wiring connections
73Liebert® SRC™ User Manual
Electrical Connections
6.2Communication-cable Specifications
• Use a 4 conductor, shielded, stranded cable between the outdoor unit and the indoor unit.
• Minimum 18-gauge shielded CVVS or CPEVS cable.
• Insulation materials as required by local code.
• Rated for continuous exposure of temperatures up to 140°F.
• Maximum allowable cable length: 984 ft.
• Firmly attach the cable. Provide slack but secure in a way to prevent external forces from being
imparted on the terminal block.
• Terminate the cable shield to a grounded surface at the outdoor unit only.
NOTE
• Always verify that the communication cable is connected to a
communications terminal on the unit. Never apply line-voltage power to the
communication-cable connection. If contact is made, PCBs may be
damaged.
• The shield of the communication cable connecting the outdoor unit to the
indoor unit should be grounded only to the outdoor-unit frame.
• Tie the shield of each cable segment together using a wire nut at each
indoor unit. Maintain polarity through the communication network.
• Never use a common multiple-core communication cable. Each
communications bus must be provided a separate cable (that is, between
the outdoor unit and indoor unit).
6.3Communication Cables between the Unit and Controller
• Field-supplied, 18 gauge, stranded 4-conductor communication cable (shielded).
• All insulation material as recommended by local code.
• Starting at the outdoor unit, terminate the cable on terminals Internet A and Internet B. Route the cable
as needed between each device.
Liebert® SRC™ User Manual74
6.4Connecting Indoor Unit Electrical Wiring
!
The general guidelines for connecting electrical and communication cables to the indoor unit are the same
for each system. However, the actual connections on the terminal block will differ. Refer to the figures for
the model that you are wiring for correct contact on each terminal block. Depending on your indoor unit, the
location of the terminal block may vary slightly from the images shown in this section.
WARNING
Arc flash, electric shock and short circuit hazard. Open all local and remote electric power
disconnect switches, verify with a voltmeter that power is off and wear personal protective
equipment per NFPA 70E before working within the electric control enclosure or making any
electrical connections or disconnections. Verify that all field wiring is connected correctly before
closing the disconnect switches and starting the unit.
Failure to comply can cause building and equipment damage, smoke, fire, serious injury or death.
NOTE
• Follow all safety information outlined at the beginning and throughout
this manual.
• Some units may require you to remove the control cover from the terminalblock area. Most control covers are attached with a Phillips-head screw.
• Connect the electrical cable to the indoor unit by connecting the wires to
the terminals on the control board individually according to the outdoor-unit
connection. Be sure that the color of the wires at the outdoor unit and the
terminal numbers are the same as those for the indoor unit.
Electrical Connections
1. At the bottom panel of the indoor units, un-snap the latches that cover the Phillips screw heads,
Figure 6-4.
Figure 6-4 Latch over the screws on bottom panel of indoor unit
75Liebert® SRC™ User Manual
Electrical Connections
2. Using a Phillips-head screwdriver, remove the screws from the bottom panel of the indoor unit,
Figure 6-5 and set the bottom panel aside, Figure 6-6.
• The electrical/communication wiring is usually routed through the back/bottom of the indoor unit
through a knockout panel, Figure 6-7.
Figure 6-5 Remove screws from bottom panel
Figure 6-6 Remove bottom panel
Figure 6-7 Communication-wires knockout panel
Liebert® SRC™ User Manual76
3. Using a screwdriver, connect the wires as shown in Figure 6-8.
• Attach each wire securely to the terminal block.
• Pay attention to the location/connection of the green/yellow ground cable.
Figure 6-8 Indoor-unit terminal block with grounding cable (example only)
6.4.1Terminal-block Connection for SRC18
Electrical Connections
NOTE
• Pay special attention to the location of the grounding cable and the cable
restrainer around the other electrical/communication cables when
connecting.
• The terminal block is located behind the drain hose and bundled piping on
Figure 6-10 SRC24 and SRC36 indoor unit terminal-block connections
6.5Connecting Outdoor Unit Electrical Wiring
The general guidelines for the electrical and communication cables to the outdoor unit are the same for
each system. However, the actual connections on the terminal block will differ. Refer to each figure for the
model you are installing for the correct wiring of each terminal block.
WARNING
Arc flash and electric shock hazard. Can cause serious injury or death. Open all local and remote
electric power disconnect switches, verify with a voltmeter that power is off and wear personal
protective equipment per NFPA 70E before working within the electric control enclosure or making
any electrical connections or disconnections.
• Follow all safety information in this manual.
• Verify that a circuit breaker or some other emergency-power cutoff device is in place before any
power wiring is done to the system.
• Never touch any power lines or live cables before power is cut-off to the system.
• Familiarize yourself with the location of the circuit breaker.
transportation and installation.
• Loose wires can cause the wiring to burn-out quickly.
• Inspect wires for damage or cracks (manufacturing defects).
in 2.1 - Electrical Data.
1. Using a Phillips-head screwdriver, remove the conduit-panel cover from the outside of the unit.
2. Inspect all wiring inside the casing to make sure that they are secure and have not come loose during
3. Confirm that the Electrical power-supply capacity is sufficient to run the unit. Refer to the specifications
4. Confirm that you are using the correct wire gauge size to proceed.
Liebert® SRC™ User Manual78
5. Using a screwdriver, refer to Figure 6-11 or Figure 6-12, and connect the wires as follows:
• Securely attach each wire to the terminal block.
• Bundle cabling using a cable restrainer.
• Pay attention to the location/connection of the green/yellow grounding cable. In some models, the
connection is located on the side of the actual terminal block.
• Maintain a minimum of 0.2-in. of wire length from the terminal block to cable bundle.
Connection/Communication
Cable (Leading to Indoor Unit)
3
79Liebert® SRC™ User Manual
Electrical Connections
Outdoor Unit
Terminal Block
Ov er 0.2”
Conduit Panel
Conduit Panel Cover
Connection/Communication
Cable (Leading to Indoor Unit)
Power Cord
1(L1) 2(L2)1(L1) 2(L2)
3
Air
Conditioner
Main Power Source
Circuit Breaker
Use a circuit breaker
or time delay fuse
Figure 6-12 SRC24 and SRC36 outdoor-unit terminal-block connections
6. Use a recognized circuit breaker between the power source and the unit. A disconnecting device to
adequately disconnect all supply lines must be fitted.
Figure 6-13 shows an example of how a circuit breaker should be wired through the Liebert SRC system.
Figure 6-13 Circuit breaker wiring
Liebert® SRC™ User Manual80
6.6Thermostat Installation and Wiring
NOTICE
Risk of improper thermostat installation. Can cause unit malfunction.
• Installation work must be performed in accordance with the national wiring standards and local
code by authorized personnel only.
• If local electric and building code requires plenum(CMP) cable, use an enclosed, noncombustible conduit (metal raceway) or FT-6 rated or above cable.
• When using back cable-entry, AWG#22, 3 core shielded wire is recommended.
• When using top or right-side cable entry, AWG#24, 3 core shielded wire is recommended.
• Do not bury the thermostat in the wall. This can damage the temperature sensor.
• Do not install a cable 164 ft (50 m) or longer. This can cause communication errors.
NOTE
If the distance between the thermostat and the indoor unit is longer than 32 ft
(10 m), use an extension cable.
Because the room-temperature sensor is in the thermostat, it should be installed in a place away from
direct sunlight, high humidity, and direct supply of cold air to maintain proper temperature of the space.
Install the thermostat about 5 ft. (1.5 m) above the floor in an area with good air circulation at an average
temperature, Figure 6-14.
Do not install the thermostat where it can be affected by the following:
• Drafts or dead spots behind doors and in corners.
Electrical Connections
• Hot or cold air from ducts.
• Radiant heat from sun or appliances.
• Concealed pipes or chimneys.
• Uncontrolled areas such as on an outside wall.
The thermostat is equipped with an LCD display and should be installed at the recommended height for
proper view of the display.
Figure 6-14 Proper and Improper thermostat locations
Direct
Sun ray contact area
yes
no
NOI
TCNU
tF
a
eB
hU
e
yr
S
f
iP
d
ire
D
t
ruma
E
oHe
o
E
H
t
d
P
s
to
S
ur
O
fO
T
e
U
N
DA
A
4
F
retl3i
ETFJ
I
2
P
H
1
ME
DE
T
p
M
m
T
eT
E
3
S
O
m
2
L
o
E
o
R
N
1
O
N
2
Z
OITA
91
REP
7
O
1
em
G
i
5
N
T
1
I
tes
WS
m
3
a
1
r
O
g
T
or
U
1
P
A
910
ti
7
n
0
unio
5
ta
0
repO
30
r
1
e
0
f
m
f
i
eO
T
mi
TnOno.teS
5feet
(1.5meters)
no
NO
ITAERPO
GN
IWSO TUA
it
7
n
0
unoi
5
ta
r
0
e
p
O
30
r
1
e
0
m
ff
i
eO
T
miTn.OonteS
no
NOITCNU
tF
ae
B
h
U
e
y
S
r
f
iPdirm
eDt
u
r
aE
oH
e
E
o
H
td
P
st
o
S
r
u
OfT
O
e
N
UDA
A
4
F
retl
3
iETFJ
I
2
PH
1ME
DE
T
p
M
meT
3
SET
OL
om
2
E
Ro
N
1
O
2
Z
19
7
em
i
51
T
1
te sm
3
a
1
rgorP
11
90
81Liebert® SRC™ User Manual
Electrical Connections
2
2
1
3
3
1. Once the proper location for the thermostat is determined, determine the cable-entry location from one
of three options:
•Back
•Top
• Right
2. If you use top or right-side entry, remove the cable-guide groove from the back plate with long-nose
pliers, Figure 6-15.
Figure 6-15 Cable-entry hole/guide grooves
No. Description
1Back entry (through wall)
2Top entry
3Right-side entry
3. Place the back plate in the installation location and secure it with screw, Figure 6-16.
• Do not bend the back plate when tightening screws.
• If there is an electric box, fit the back plate to the box when installing.
• Do not leave a gap between the wall and back plate or the thermostat could move or shake.
Figure 6-16 Thermostat back plate installation
Liebert® SRC™ User Manual82
4. Making sure that the cable does not interfere, place the upper part of the thermostat on the back plate
Wall
Side
Wall
Side
Wall
Side
Wall
Side
<Connecting or der>
<Separating or der>
Please check if the connect ors ar e connect ed pr operly.
C/BO X Cable (Plug type)
Extension cable(housing type)
Indoor
Unit side
as shown in Figure 6-17, and press the lower part onto the back plate to connect it.
• Leave no gaps between the thermostat and the back plate.
• To remove the thermostat from the back plate, insert a screwdriver into one of the separating holes
on the bottom of the thermostat and twist. Repeat in the second hole, to release the thermostat
from the back plate.
Figure 6-17 Mounting thermostat onto back plate
Electrical Connections
5. Refer to Figure 6-18 to connect the indoor unit to the thermostat using the extension cable.
NOTICE
Risk of improper thermostat installation. Can cause unit malfunction.
If local electric and building code requires plenum(CMP) cable, use an enclosed, non-combustible
conduit (metal raceway) or FT-6 rated or above cable.
Figure 6-18 Extension cable from indoor unit to thermostat
No. Description
1AWG#24
2AWG#22
3AWG#22
6. To connect the extension cable directly to the thermostat
• Loosen the screw holding the cable in the thermostat terminal block.
• Use a cutting nipper to remove the housing from the extension cable and peel it as shown in
Figure 6-19.
83Liebert® SRC™ User Manual
Electrical Connections
YELLOW RED BLACK
Signal 12V GND
Thermostat PCB
Indoor unit
side
Figure 6-19 Thermostat cable prep
0.394 inch(10mm) ± 0.11 8 inch(3mm)
1.3 78 inch(35mm)
± 0.197 inch(5m m)
7. Connect the wires to the thermostat terminal block and the indoor-unit terminal block as shown in
Figure 6-20.
• Tighten securely and make sure wires are not touching each other.
Figure 6-20 Thermostat and Indoor unit terminal-block connections
Thermostat
terminal block
Indoor-unit
terminal blockFunction
YELLOWYLSignal
REDRD12 V
BLACKBKGND
Liebert® SRC™ User Manual84
Installation Set-up and System Start-up
7.0Installation Set-up and System Start-up
NOTICE
Risk of improper thermostat installation. Can cause unit malfunction.
The Installer setting mode sets up the detailed function of the thermostat.
If the installation is not set correctly, it can cause problems for the product, user injury, or property
damage. Installation set-up must be performed by a certified technician. Non-certified personnel
attempting to install or make changes shall be responsible for any adverse effects or operation.
7.1Accessing Installer Set-up Mode
1. On the thermostat, press for at least 3 seconds.
The function code displays.
NOTE
A press less than 3 seconds enters “user” settings mode.
2. Refer to the following procedures and Table 7-1 to make the correct settings for your installation.
NOTE
Some menu options and functions may not be displayed or the menu name
may be different depending on your system and model.
Table 7-1General unit functions—Installer set-up codes
Function
CodeDescriptionValue
01Test Run01 = Set
02Address Setting00 ~ FF = Address
Step:
01 = Very Low
02 = Low
03E.S.P Value
04Thermistor
05Ceiling Height
06Static Pressure
Some menu options and functions may not be displayed or the menu name may be different
depending on your system and model.
03 = Med
04 = High
05 = Very High
Value:
0 ~ 255
01 = Remo
02 = Indoor
03 = 2TH
01 = Low
02 = Med
03 = High
04 = Very High
01 = V-H
02 = F-H
03 = V-L
04 = F-L
85Liebert® SRC™ User Manual
Installation Set-up and System Start-up
Table 7-1General unit functions—Installer set-up codes (continued)
Function
CodeDescriptionValue
07Master setting
08Override setting
09Dry contact
12Celsius/Fahrenheit
18Emergency heater
20Plasma
21Electric heater
22Humidifier
23Elevation grill
24Ventilation kit
25Auxiliary heater
31
Some menu options and functions may not be displayed or the menu name may be different
depending on your system and model.
Settings temperature
range
00 = Slave
01 = Master
(only “Plus 1 series models)
00 = Group
01 = Single
00 = Slave
01 = Master
00 = Auto-off
01 = Auto-on
00 = Celsius
01 = Fahrenheit
Select mode:
00 = not used
01 = use
Low-ambient heating operation:
0 = not used
1 = compressor off 0°F (–18°C)/ on 5°F (–15°C)
2 = compressor off 5°F (–15°C)/ on 10°F (–12°C)
3 = compressor off 10°F (–12°C)/ on 15°F (–9°C)
Fan speed:
0 = fan off
1 = fan on
00 = not installed
01 = installed
00 = 60~86°F / 16~30°C
01 = 40~99°F / 4~37.5°C
7.2Running Test Mode
NOTE
Before running test mode, make sure of the following:
• Leak testing is complete and there are no leaks.
• Air purge/evacuation is complete and successful.
• All tubing, piping, and wiring are properly connected.
1. On the thermostat, press for at least 3 seconds.
The function code blinks in the lower-middle of the display.
NOTE
A press less than 3 seconds enters “user” settings mode.
Liebert® SRC™ User Manual86
2. Press .
The test run starts.
• During the test run, pressing any of the following buttons will exit the test: Oper Mode, Temp
up/down, Fan Speed, Wind Direction, or Start/Stop.
7.3Setting the Address of Central Control
Refer to Table 7 -1 for the specific function-setting values.
1. On the thermostat, press for at least 3 seconds.
The function code blinks in the lower-middle of the display.
NOTE
A press less than 3 seconds enters “user” settings mode.
2. Press repeatedly to select the function code.
3. Press , to select the Group No., then use to select the setting.
4. Press , to select the Indoor No., then use to select the setting.
Installation Set-up and System Start-up
5. Press .
The setting is saved.
6. Press to exit installer setting mode.
NOTE
If there is no button input for 25 seconds, set-up mode is automatically exited.
If you exit without pressing , your settings are not saved.
7.4Setting E.S.P.
This function determines the wind-strength for each wind level.
Refer to Table 7 -1 for the specific function-setting values.
NOTE
If E.S.P is set incorrectly, the unit may malfunction.
ESP may not work on products that do not have “weak” or power fan-speed
settings.
1. On the thermostat, press for at least 3 seconds.
The function code blinks in the lower-middle of the display.
NOTE
A press less than 3 seconds enters “user” settings mode.
2. Press repeatedly to select the function code.
3. Press to select the Step (wind level).
4. Press to select the Value (wind strength), then use to select the setting.
87Liebert® SRC™ User Manual
Installation Set-up and System Start-up
5. Press then to select the next Step.
6. Press to select the Value, then use to select the setting.
7. Repeat Steps 5 to 6 until the strength is set for each wind level.
8. Press .
The setting is saved.
• Press to exit installer setting mode.
NOTE
If there is no button input for 25 seconds, set-up mode is automatically exited.
If you exit without pressing , your settings are not saved.
7.5Setting the Thermistor
Refer to Table 7 -1 for the specific function-setting values.
1. On the thermostat, press for at least 3 seconds.
The function code blinks in the lower-middle of the display.
NOTE
A press less than 3 seconds enters “user” settings mode.
2. Press repeatedly to select the function code.
3. Press , to select Value, then use to select the setting. Refer to Tab le 7-2 for descriptions of
the thermistor settings.
Table 7-2Thermistor setting options
ValueFunction
01 ThermostatOperates based on temperature sensor in thermostat.
02 Indoor UnitOperates based on temperature sensor in indoor unit.
Operates based on higher temperature comparing the
Cooling
03 2TH
Heating
The 2TH functions differently depending on product model.
If the indoor temperature is below 10°F, the value for the temperature sensor of the thermostat is
displayed regardless of the thermistor setting.
reading from thermostat temp. sensor and indoor-unit
temp sensor.
Operates based on lower temperature comparing the
reading from thermostat temp. sensor and indoor-unit
temp sensor.
4. Press .
The setting is saved.
5. Press to exit installer setting mode.
NOTE
If there is no button input for 25 seconds, set-up mode is automatically exited.
If you exit without pressing , your settings are not saved.
Liebert® SRC™ User Manual88
7.6Setting the Ceiling Height
Refer to Table 7 -1 for the specific function-setting values.
1. On the thermostat, press for at least 3 seconds.
The function code blinks in the lower-middle of the display.
NOTE
A press less than 3 seconds enters “user” settings mode.
2. Press repeatedly to select the function code.
3. Press , to select the Value, then use to select the setting. Refer to Table 7 -3 for
descriptions of the ceiling-height settings.
Table 7-3Ceiling-height setting options
ValueFunction
01 LowDecrease indoor air-flow rate 1 step from standard level.
02 MediumSet indoor air-flow rate as standard level.
03 HighIncrease indoor air-flow rate 1 step from standard level.
04 Very highIncrease indoor air-flow rate 2 steps from standard level.
Installation Set-up and System Start-up
4. Press .
The setting is saved.
5. Press to exit installer setting mode.
NOTE
If there is no button input for 25 seconds, set-up mode is automatically exited.
If you exit without pressing , your settings are not saved.
7.7Setting Fahrenheit/Celsius
Refer to Table 7 -1 for the specific function-setting values.
1. On the thermostat, press for at least 3 seconds.
The function code blinks in the lower-middle of the display.
NOTE
A press less than 3 seconds enters “user” settings mode.
2. Press to select the function code.
3. Press , to select Value, then use to select the setting.
4. Press .
The setting is saved.
5. Press to exit installer setting mode.
NOTE
If there is no button input for 25 seconds, set-up mode is automatically exited.
If you exit without pressing , your settings are not saved.
89Liebert® SRC™ User Manual
Installation Set-up and System Start-up
7.8Setting Optional Functions
Used when options are added or removed.
Refer to Table 7 -1 for the specific function-setting values.
1. On the thermostat, press for at least 3 seconds.
The function code blinks in the lower-middle of the display.
NOTE
A press less than 3 seconds enters “user” settings mode.
2. Press repeatedly to select the function code.
3. Press , to select the condition, then use to select the setting.
4. Press .
The setting is saved.
5. Press to exit installer setting mode.
NOTE
If there is no button input for 25 seconds, set-up mode is automatically exited.
If you exit without pressing , your settings are not saved.
7.9Setting Temperature Range
Refer to Table 7 -1 for the specific function-setting values.
1. On the thermostat, press for at least 3 seconds.
The function code blinks in the lower-middle of the display.
NOTE
A press less than 3 seconds enters “user” settings mode.
2. Press repeatedly to select the function code.
3. Press , to select the Value, then use to select the setting.
4. Press .
The setting is saved.
5. Press to exit installer setting mode.
NOTE
If there is no button input for 25 seconds, set-up mode is automatically exited.
If you exit without pressing , your settings are not saved.
Liebert® SRC™ User Manual90
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.