Emerson Liebert SL-31080 User Manual

Page 1
SL-31080 Product Specification/Installation Sheet page 1 6/03 (Rev. 0)
TEMPERATURE /HUMIDITY TRANSMITTER - WALL (4-20 MA)
Description
The THW420 combination temperature/humidity transmitter is designed to meet applications that require local indication of both temperature and humidity in a single, aesthetically pleasing enclosure.
This device incorporates a 10K ohm () platinum RTD. The transmitter requires 24 VDC. The sensor provides an accurate and predictable four-wire, 4-20 mA output signal for temperature and a second 4-20 mA output signal for humidity.
Dimensions
Specifications
Termination
The THW420 transmitter must be powered from a 24 VDC supply. The combination temperature/ humidity sensor is terminated as follows:
•The humidity transmitter requires a three-wire termination for the 4-20mA output using 24 VDC.
•The temperature sensor also requires a three- wire termination. In most cases, it obtains power from the analog input to which it is connected and no external power is required.
Though interference from external sources is not a major problem with current transmitters, Liebert recommends separating the wiring from line voltage wiring and from wiring used to supply highly induc­tive loads such as motors, generators and coils. Lie­bert also recommends making power connections with twisted pair wire of at least 22 AWG and crimp­type connectors.
Ordering Information
Output 4 to 20 mA Sensor 10K platinum RTD Supply Voltage 24 VDC Tolerance of Resistance
(Accuracy)
±1.5°F (±0.83°C)
±2% RH (from 15 to 95% RH) Response Time 20 seconds for a 63% step Environmental Operating
Range (Transmitter)
45°F to 96°F; 0 to 100% RH
(7°C to 35°C); 0 to 100% RH
4.5"
(1143mm)
2.25"
(572mm)
2.75"
(699mm)
0.95"
(241mm)
0.75"
(191mm)
FRONT
VIEW
SIDE
VIEW
TOP VIEW
Wall
!
CAUTION
Liebert recommends wiring the sensor WITHOUT power applied because accidental arcing may damage the product and will void the warranty.
X
U3
Terminations
+24VDC should be used at all times
SW2 OUTPUT SELECT
ON
0-5V
0-5V
0-5V
CALRUN
RESIST.
4-20ma
4-20ma
SW2
C9
Gnd
V+
Ch1
Ch2
J2
J3
DISPLAY CYCLE
IN SECONDS
10
3 T
POT1
20 H
Ch3
CAL
Te mp
Te mp
R19
T&B
SWITCH
Short
Norm
Open
SW1
RTH1 RTH2
J1
%RH
Ch3
Ch2
Ch1
Building Automation
Products, Inc.
Copyright 2000
REV. 101600
XCOMBO T&B
4-20 mA Input #1
Ground
4-20 mA Input #2
+
-
+
-
Controller
To GND (common) of controller*
From +24VDC of controller or power supply
To controller’s analog input (humidity signal, 4-20mA)
To controller’s analog input (temperature signal, 4-20mA)
* NOTE:
The GND (common) terminal is common between the Power and Sensor
Quantity Part # Description
THW420 Combination Temperature/Humidity Transmitter Wall 4-20 mA @ 45°F to 96°F and 0 to 100% RH
Page 2
SL-31080 Product Specification/Installation Sheet page 2 6/03 (Rev. 0)
Mounting
Enclosure Mounting Instructions
Mounting hardware is provided for both junction box and drywall installation.
1. Pull the wires through the opening in the base plate.
2. For junction box installation: Secure the base to the box using the #6-32 x 1/2" mounting screws provided.
For drywall installation: Drill two 3/16" holes 3-1/4" apart on center. Insert the drywall anchors and secure the base using the #6 x 1" sheet metal screws provided.
3. Terminate the unit according to the guidelines in Termination on page 1.
4. Attach the cover by latching it to the top of the base, rotating the cover down and snapping it into place.
5. Secure the cover by backing out the lock-down screws using a 1/16" allen wrench until they are flush with the bottom of the cover.
Troubleshooting Guide
The following table lists common problems and possible solutions. For more information, consult your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Junction box 2" x 4"
Mounting screws
Cover
Delta base
Wall
Locking screws
NOTE
In a wall-mount application, the wall temperature and the temperature of the air within the wall cavity can cause erroneous readings. The mixing of room air and air from within the wall cavity can lead to condensation and premature failure of the sensor.
To prevent these conditions, seal the conduit leading to the junction box and seal the hole in the drywall by using an adhesive backed, foam insulating pad.
Problems Possible Solutions
Unit will not operate
• Check +24 VDC power supply at controller.
• Disconnect the sensor and check power wires for +24 VDC.
Humidity reading is maximum 20 mA or 100%
• Make sure the sensor is installed properly, and is not shorted.
Quick Check: Remove the sensor. If the reading does not change, contact technical support.
Humidity reading is minimum 4 mA or 0%
• Verify that the humidity sensor installed.
Quick Check: Short the sensor terminal block with a wire. Does the reading change? If so, the sensor may be faulty; if not, contact technical support.
Humidity reading in software appears to be off more than specified accuracy
• Check all software parameters.
• If available, check the sensor against a calibrated control such as a hygrometer.
• Determine if the sensor is exposed to an external source more than room.
Temperature sensor in front­end software is reading high
• Make sure wiring is correct.
• Disconnect wires and measure with a multimeter.
Temperature sensor in front­end software is reading low
• Make sure wiring is correct.
• Disconnect wires and measure with a multimeter.
Page 3
SL-31080 Product Specification/Installation Sheet page 3 6/03 (Rev. 0)
Troubleshooting - Humidity Signal Verification
4 to 20 mA Signal
You will measure the humidity output by placing an ammeter in series with the controller input. The control­ler input is connected to the terminal marked “Ch1 or Ch2” on the humidity board.
1. Verify the unit is terminated properly using Figure 2 shown below, and set your meter to the “Volts” setting.
2. Verify you have 24 VDC supplied to the unit by measuring between the “V+” and “GND” terminals at the sensor, as shown below in Figure 1.
3. Set your meter to “Amps” and measure the output between “Ch1 or Ch2” and the controller input as shown below in Figure 1.
4. Use the following formula to determine what humidity the sensor is reading:
(mA - 4) / 0.16 = %RH where mA is the current reading from the ammeter (in mA)
Example: If the current reading is 16 mA, then:
%RH = (16 - 4) / 0.16
= 12 / 0.16 = 75%
Figure 1 Supply Voltage and 4-20mA Verification Figure 2 4 to 20 mA Output Connection
Analog Input
ROOM SENSOR
CONTROLLER
GND(-)
V+
Ch1 or
Ch2
GND(-)
V+
Analog Input
GND(-)
V+
Ch1 or
Ch2
GND(-)
V+
ROOM SENSOR
CONTROLLER
V
-
A
+
+
-
POWER SUPPLY POWER SUPPLY
Loading...