For online technical support, refer to the EXPERT2™ tool at
www.expert2.com. To speak to a customer service
representative, call the support center nearest you:
• In U.S.A., phone 1-800-522-MASS (1-800-522-6277)
• In Canada and Latin America, phone (303) 530-8400
This instruction manual explains how to install, start up, configure, and troubleshoot the Micro
Motion IFT9701 transmitter for use with Micro Motion Coriolis flow sensors. For more information
about the sensor, see the appropriate sensor instruction manual.
1.2Safety
Safety messages are provided throughout this manual to protect personnel and equipment. Read each
safety message carefully before proceeding to the next step.
Getting StartedPower Supply and Output WiringMounting the Remote TransmitterBefore You Begin
WARNING
Improper installation in a hazardous area can cause
an explosion.
For information about hazardous applications, refer to
Micro Motion ATEX, CSA, or UL installation instructions,
shipped with the transmitter or available from the Micro
Motion web site.
WARNING
Hazardous voltage can cause severe injury or death.
Make sure power is disconnected before installing
transmitter.
CAUTION
Improper installation could cause measurement error
or transmitter failure.
Follow all instructions to ensure transmitter will operate
correctly.
Model IFT9701 Transmitter Instruction Manual1
Before You Begin continued
1.3European installations
This Micro Motion product complies with all applicable European directives when properly installed
in accordance with the instructions in this manual. Refer to the EC declaration of conformity for
directives that apply to this product.
The EC declaration of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available on the internet at www.micromotion.com/atex or
through your local Micro Motion support center.
1.4Definitions
•The term “sensor” refers to a Micro Motion sensor only.
•The term “flowmeter” refers to an IFT9701 transmitter and a sensor installed as a
flowmetering system.
1.5Flowmeter components
The IFT9701 transmitter can be integrally mounted to a Micro Motion F-Series sensor, or remotely
mounted from an ELITE
The IFT9701 transmitter does not operate with Micro Motion T-Series, R-Series, or Model D600 or
DT sensors.
•If the transmitter is integrally mounted to the sensor, the flowmeter includes the components
shown in Figure 1-1.
•If the transmitter will be remotely mounted from the sensor, the transmitter includes the
components shown in Figure 1-2.
The transmitter is available with an optional liquid crystal display (LCD), as shown in Figure 1-1 and
Figure 1-2, except for ATEX Zone 1 areas.
®
, F-Series, Model D, or Model DL sensor.
Figure 1-1Integrally mounted IFT9701 transmitter with F-Series sensor
Field wiring compartment
With optional LCD
Case ground
Sensor wiring compartment
4X M8 mounting bolt
4X lock washer
4X flat washer
To rotate transmitter:
remove, then re-install to
12 ft-lb (16 N-m) torque
Model
IFT9701
transmitter
Flowmeter
F-Series sensor
2Model IFT9701 Transmitter Instruction Manual
Before You Begin continued
Figure 1-2Remotely mounted IFT9701 transmitter
Field wiring
compartment
Model
IFT9701
transmitter
4X M8 mounting bolt
•4X lock washer
• 4X flat washer
To rotate transmitter: remove,
then re-install to 12 ft-lb (16 Nm)
torque
For minimum bend radius of cable,
see Figure 3-4, 3-5, or 3-6
If conduit is used, install drip
With optional LCD
Sensor wiring
compartment
Sensor cable
leg in conduit
Circuit board compartment
User access not
normally required
Mounting bracket
Requires 4 user-supplied bolts
Cable gland
• To assemble, see instructions
shipped with cable kit
• Connects to sensor junction box
Getting StartedPower Supply and Output WiringMounting the Remote TransmitterBefore You Begin
Model IFT9701 Transmitter Instruction Manual3
4Model IFT9701 Transmitter Instruction Manual
Chapter 2
Getting Started
2.1Safety, reliability, accessibility
Improper installation in a hazardous area could cause
an explosion.
Install the transmitter in an environment that is compatible
with the hazardous area specified on the approvals tag.
• For intrinsically safe sensor installations, use this
document with Micro Motion ATEX, CSA, or UL
installation instructions.
• For hazardous area installations in Europe, refer to
standard EN 60079-14 if national standards do not
apply.
WARNING
Getting StartedPower Supply and Output WiringMounting the Remote TransmitterBefore You Begin
2.1.1Hazardous area
If you plan to mount the transmitter in a hazardous area, ensure that your equipment and installation
meet the hazardous area requirements. For more information about hazardous area classifications, see
Section A.8. See Figure 2-1 for the location of the approvals tag on your transmitter.
Model IFT9701 Transmitter Instruction Manual5
Getting Started continued
Figure 2-1Location of approvals tag
Hazardous area
approvals tag
2.1.2Orientation and mounting
Orient the transmitter so wiring compartments and conduit openings are easily accessible.
•To rotate the transmitter on the sensor manifold or the mounting bracket, use the four supplied
mounting bolt assemblies. Each bolt assembly includes one M8 bolt, one lock washer, and one
flat washer. Remove the bolt assemblies, rotate the transmitter, then reinstall the bolt
assemblies to 12 ft-lb (16 N-m) of torque.
•If the transmitter will be integrally mounted to a Micro Motion F-Series sensor, see the sensor
product data sheet for transmitter and sensor dimensions, and see the instruction manual that
was shipped with the sensor for information about flowmeter mounting and location.
•If the transmitter will be remotely mounted, use the supplied bolt assemblies to attach the
transmitter to the mounting bracket. Attach the bracket to a rigid, stable surface or instrument
pole that will not transfer excessive vibration into the transmitter. See Chapter 3 for more
information about remote mounting.
2.1.3Temperature, humidity, and vibration
Install the transmitter according to specified limits:
•Ambient temperature
-without optional LCD: –22 to +131 °F (–30 to +55 °C)
-with optional LCD: 32 to 131 °F (0 to 55 °C)
•Humidity: 5 to 95% non-condensing
•Vibration: Meets IEC 68.2.6, 2 g
6Model IFT9701 Transmitter Instruction Manual
Getting Started continued
2.1.4Visibility of tags
For personal and system safety, all tags attached to the transmitter housing must remain visible. Clean
or replace them as necessary.
2.2Transmitters approved for ATEX Zone 1
Explosion hazard
The circuit board compartment is rated EEx d
(flameproof), and should remain closed at all times after
the flowmeter has been installed.
To avoid risk of explosion in an explosive atmosphere:
• Read label that points to compartment cover before
accessing circuit board compartment. Figure 2-2
shows the location of the labels on the transmitter
housing.
• Shut off power, and wait at least 2 minutes before
removing EEx d (circuit board) compartment cover.
Figure 2-2 also identifies the EEx e (field wiring), EEx i
(sensor wiring), and EEx d (circuit board)
compartments.
WARNING
Getting StartedPower Supply and Output WiringMounting the Remote TransmitterBefore You Begin
If the transmitter carries an ATEX Zone 1 approval, wiring compartments are labeled as shown in
Figure 2-2.
•The sensor wiring compartment is rated EEx i (intrinsically safe), and may be opened at any
time. See Label 1 in Figure 2-2.
•The field wiring compartment is rated EEx e (increased safety), and should remain closed
when power is on. See Label 2 in Figure 2-2.
•The circuit board compartment is rated EEx d (flameproof), and should remain closed at all
times after the transmitter has been installed. If the transmitter is approved by ATEX as
flameproof, the compartment has a lockout device, shown in Figure 2-2. The lockout device
must be loosened and rotated before the compartment cover can be unscrewed.
Model IFT9701 Transmitter Instruction Manual7
Getting Started continued
Figure 2-2Compartment tags and lockout device
Field wiring
compartment
Rated EEx e
Circuit board
compartment
Rated EEx d
2.3Jumper settings
Unless otherwise specified on the order, jumpers are set so the transmitter generates downscale fault
outputs and enables flowmeter configuration. If jumper settings need to be changed, the procedure
should be performed before the transmitter is installed.
•To access security and fault output jumpers, unscrew the circuit board compartment cover.
•If the transmitter is approved by ATEX as flameproof, the compartment has a lockout device.
See Figure 2-2. The lockout device must be loosened and rotated before the compartment
cover can be unscrewed.
Label 1
Lockout device
Loosen and rotate
before opening
circuit board
compartment
CAUTION
Improper handling of transmitter components can
damage the transmitter.
Label 2
Sensor wiring
compartment
Rated EEx i
• If a breaker bar is used for loosening the cover of the
circuit board compartment:
- Apply steady pressure to avoid chipping the paint on
the transmitter housing. Chipped paint can result in
corrosion of the housing. If paint becomes chipped,
repaint the housing.
- Do not apply too much pressure. Excessive torque
can damage the pipeline, transmitter, or sensor.
• To prevent electrostatic discharge, wear an anti-static
wrist strap while setting jumpers.
8Model IFT9701 Transmitter Instruction Manual
Getting Started continued
2.3.1Security
The security jumper enables the user to write-protect the flowmeter configuration, so it cannot be
changed using a HART communication device:
•With the security jumper OFF, the flowmeter configuration can be changed.
•With the security jumper ON, the flowmeter configuration cannot be changed.
The default setting is OFF. To set the security jumper, see Figure 2-3.
2.3.2Fault output levels
The transmitter can be configured to produce downscale or upscale fault outputs. In a fault condition:
•Downscale: The milliamp output goes to 2 mA; the pulse output goes to 0 Hz.
•Upscale: The milliamp output goes to 22 mA; the pulse output goes to 7200 Hz.
•The diagnostic LED blinks ON four times per second, whether the setting is upscale or
downscale.
The default setting is downscale. To set the fault output jumper, see Figure 2-3.
Figure 2-3Jumper location and settings
Getting StartedPower Supply and Output WiringMounting the Remote TransmitterBefore You Begin
Default settings
With standoff beneath jumpers
Security
OFF
Optional settings
With standoff beneath jumpers
Security
OFF
Security
ON
Security
ON
Downscale
faults
Upscale
faults
Upscale
faults
Downscale
faults
Model IFT9701 Transmitter Instruction Manual9
Getting Started continued
2.3.3Re-installing the circuit board compartment cover
To re-install the cover of the circuit board compartment:
1. Screw the cover back onto the housing.
2. Hand-tighten the cover until it seats on the O-ring.
3. If the circuit board compartment has a lockout device, as shown in Figure 2-2, rotate the clamp
into place and push it into the slot. Use a 4-mm (5/32-inch) Allen wrench to tighten the lockout
screw to 5 inch-pounds (0,56 N-m) of torque.
10Model IFT9701 Transmitter Instruction Manual
Chapter 3
Remotely Mounting the Transmitter
Note: The instructions in this chapter apply only if the transmitter will be remotely mounted from the
sensor. If the transmitter is integrally mounted to the sensor, proceed to Chapter 4.
3.1Overview
To mount the transmitter remotely from the sensor, the following steps are required:
•Choosing the proper location (see Section 3.2)
•Mounting the sensor on a flat surface or instrument pole (see Section 3.3)
•Connecting the transmitter to the sensor (see Section 3.4)
3.2Choosing the proper location
Install the transmitter according to the conditions stated in Section 2.1.
Getting StartedPower Supply and Output WiringMounting the Remote TransmitterBefore You Begin
For mounting dimensions, see Figure 3-1.
Total length of cable from sensor to transmitter must not exceed 1000 feet (300 meters).
For bend radii of cables, see Figure 3-4, Figure 3-5, or Figure 3-6, according to the type of cable to be
used.
3.3Mounting the transmitter
A transmitter that is to be remotely mounted from the sensor is shipped with an L-shaped mounting
bracket. Attach the bracket to a rigid, stable surface or instrument pole that will not transfer excessive
vibration into the transmitter.
3.3.1Guidelines for flat-surface mounting
•Use four 5/16-inch (M8) nuts (not included), suitable for the environment.
•Do not secure bolts to separate beams, girders, wall studs, etc., which can move independently.
•To prevent unnecessary stress on the mounting bracket, use washers to shim the bracket if the
mounting surface is not flat.
•For more information, see Figure 3-2.
3.3.2Guidelines for pole mounting
•Use two 5/16-inch (M8) U-bolts for 2-inch pipe, and four 5/16-inch (M8) nuts (not included),
suitable for the environment.
•For more information, see Figure 3-3.
Model IFT9701 Transmitter Instruction Manual11
Remotely Mounting the Transmitter continued
Figure 3-1Installation dimensions for remote mounting
Dimensions in
3/4″–14 NPT
or M20 X 1.5
for power wiring
gland for sensor wiring
inches
(mm)
Character
height
3/4″–14 NPT
4X
1/2
(13)
Ø 25/64
(10)
5 3/4
(146)
2 13/16
(71)
3/4″–14 NPT
or M20 X 1.5
for output wiring
Field wiring
compartment
61/64
(24)
4 1/4
2 13/16
(108)
(71)
(44)
7 1/64
(178)
2X 5 57/64
9 43/64
(245)
1 3/4
(150)
(1)
4 1/4
(107)
4 53/64
(122)
6 17/64
(159)
19/32
(15)
(1)If transmitter is ordered without display,
dimension is 1 3/8 (35).
For minimum bend radii
of cable, see Figure 3-4,
Figure 3-5, or Figure 3-6
12Model IFT9701 Transmitter Instruction Manual
Remotely Mounting the Transmitter continued
Figure 3-2Mounting the transmitter to a wall or other surface
Circuit board compartment
User access not normally required
Area approvals tag
Field wiring compartment
Sensor wiring compartment
4X M8 bolt
4X lock washer
4X flat washer
To rotate transmitter: remove, then
re-install to 12 ft-lb (16 N-m) torque
4X 5/16 (M8) bolt
User-supplied
Figure 3-3Mounting the transmitter to an instrument pole
Area approvals tag
Field wiring compartment
Sensor wiring compartment
4X 5/16 (M8) bolt
User-supplied
Getting StartedPower Supply and Output WiringMounting the Remote TransmitterBefore You Begin
Circuit board compartment
User access not normally
required
4X M8 bolt
4X lock washer
4X flat washer
To rotate transmitter: remove, then
re-install to 12 ft-lb (16 N-m) torque
Model IFT9701 Transmitter Instruction Manual13
2X 5/16-inch (M8)
U-bolt for 2-inch pipe
User-supplied
Remotely Mounting the Transmittercontinued
Jack
3.4Connecting the transmitter to the sensor
Improper installation of cable, cable gland, or conduit
could cause inaccurate measurements or flowmeter
failure.
To ensure 360° termination shielding for flowmeter wiring,
install the factory-supplied cable gland or user-supplied
sealed metallic conduit to the conduit opening on the
sensor junction box.
To connect the transmitter to the sensor:
•Micro Motion 9-wire cable is required. See Section 3.4.1 for information on cable types
offered by Micro Motion.
•Depending on your cable type, you must either install the cable in conduit or use cable glands.
See Section 3.4.2 for information on conduit installations. See Section 3.4.3 for information
on cable gland installations.
•For information on connecting the wires to the terminals, see Section 3.4.4.
CAUTION
Micro Motion’s 9-Wire Flowmeter Cable Preparation and Installation Guide, shipped with the cable,
provides additional information on cable types, cable preparation, and installation requirements.
3.4.1Cable types
Micro Motion supplies 9-wire jacketed, shielded, or armored cable.
•Jacketed cable is CE-compliant when it is installed inside user-supplied sealed metallic
conduit that provides 360° termination shielding for the enclosed cable. See Figure 3-4 for an
illustration of jacketed cable.
•Shielded and armored cable are CE-compliant when the cable is installed with the
factory-supplied cable glands. See Figure 3-5 for an illustration of shielded cable, and
Figure 3-6 for an illustration of armored cable.
•Each cable type is available with a PVC or Teflon
cable jacket materials, see Table 3-1.
See Table 3-2 for guidelines on cable selection. All cable types are acceptable for cable tray
installation.
Figure 3-4Jacketed cable
et
Drain wire (4)
Foil shield (4)
Filler (5)
®
FEP jacket. For temperature ranges of
Minimum bend radii
Static
Outside
Jacket
material
PVC0.415 (10)3 1/8 (80)6 1/4 (159)
Te fl on
FEP
diameter
inches (mm)inches (mm)inches (mm)
®
0.340 (9)2 5/8 (67)5 1/8 (131)
(no load)
condition
Under
dynamic
load
14Model IFT9701 Transmitter Instruction Manual
Remotely Mounting the Transmitter continued
Figure 3-5Shielded cable
Outer jacket
Figure 3-6Armored cable
Outer jacket
Tin-plated copper
braided shield
Foil shield (1)
Inner jacket
Drain wire (4)
Foil shield (4)
Filler (5)
Stainless steel
braided shield
Foil shield (1)
Inner jacket
Drain wire (4)
Minimum bend radii
Static
Outside
Jacket
material
PVC0.525 (14)4 1/4 (108)8 1/2 (216)
Te fl on
FEP
diameter
inches (mm)inches (mm)inches (mm)
®
0.425 (11)3 1/4 (83)6 3/8 (162)
(no load)
condition
Under
dynamic
load
Minimum bend radii
Static
Outside
Jacket
material
PVC0.525 (14)4 1/4 (108)8 1/2 (216)
Te fl on
FEP
diameter
inches (mm)inches (mm)inches (mm)
®
0.425 (11)3 1/4 (83)6 3/8 (162)
(no load)
condition
Under
dynamic
load
Getting StartedPower Supply and Output WiringMounting the Remote TransmitterBefore You Begin
Foil shield (4)
Filler (5)
Table 3-1Temperature ranges for jacket material
Jacket materialLow operating temperature limitHigh operating temperature limit
Conduit is used
Conduit is not used
Conduit is not used and
mechanical protection is required
Model IFT9701 Transmitter Instruction Manual15
Remotely Mounting the Transmitter continued
3.4.2Guidelines for conduit
If sealed metallic conduit is installed, it must provide 360° termination shielding for the enclosed
flowmeter cable.
1. Install a drip leg in conduit to prevent liquids from entering the junction box.
2. Connect the sealed end of the conduit to the ¾-inch NPT female conduit opening on the sensor
junction box.
3.4.3Guidelines for cable gland
1. Prepare cable ends and assemble the supplied cable gland according to the instructions that are
enclosed with the cable preparation kit.
2. Connect the ¾-inch NPT male cable gland to the ¾-inch NPT female conduit opening on the
sensor junction box.
3.4.4Wiring connections to sensor
1. At the sensor, insert the ends of the individual wires into the terminals inside the sensor
junction box. Match the wire colors of the cable with the wire colors at the sensor wiring
terminal as described in Figure 3-7 and Table 3-3. No bare wire should remain exposed.
2. If possible, position the junction box on the sensor so the conduit entrance points downward to
prevent moisture from entering.
3. At the transmitter, if cable is not preinstalled, connect the cable to the transmitter terminals as
indicated in Figure 3-8.
WARNING
Failure to seal sensor junction box or transmitter
housing could cause a short circuit, which would
result in measurement error or flowmeter failure.
• Seal all conduit openings.
• Install drip legs in cable or conduit.
• Fully tighten sensor junction box and transmitter housing
covers. See Figure 3-8.
16Model IFT9701 Transmitter Instruction Manual
Remotely Mounting the Transmittercontinued
10
11
12
GND
10
11
12
GND
Figure 3-7Cable connections to sensors
ELITE and F-Series
sensor terminals
Maximum cable length 1000 ft. (330 m)
Green
White
Violet
Yellow
Orange
Brown
Blue
Gray
Red
Clip drain wire back
Clip drain wire back
Clip drain wire back
Clip drain wire back
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Prepare cable in accordance with the
instructions that are shipped with the cable
Flowmeter
cable
Black
(Drains from all
wire sets)
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Ye l l ow
IFT9701
terminals
Brown
Black (Drains,
remote-mount only)
Red
Blue
Gray
Violet
Green
Yellow
Orange
White
D and DL
sensor terminals*
Brown
Red
Orange
Ye l l ow
Green
Blue
Violet
Gray
White
Getting StartedPower Supply and Output WiringMounting the Remote TransmitterBefore You Begin
Blue
Gray
Violet
Green
Ye l l ow
Orange
White
Model IFT9701 Transmitter Instruction Manual17
Remotely Mounting the Transmitter continued
Figure 3-8Sensor wiring compartment and sensor wiring terminals
Sensor wiring
terminals
Sensor wiring
compartment
18Model IFT9701 Transmitter Instruction Manual
Chapter 4
Power Supply and Output Wiring
4.1Overview
To wire the transmitter power supply and outputs:
•Review the wiring guidelines (see Section 4.2)
•Connect the power supply wiring (see Section 4.3)
•Connect the output wiring (see Section 4.4)
4.2Wiring guidelines
•Install cable and wiring so they meet local code requirements.
•The transmitter has two separate ¾-inch NPT or M20 female conduit openings, which must
remain sealed to keep the transmitter watertight. See Figure 4-1 and Figure 4-2.
•The transmitter has a sensor wiring compartment for intrinsically safe sensor wiring, and a
field wiring compartment for non-intrinsically safe power supply and output wiring. See
Figure 4-1 and Figure 4-2.
-For power supply and output wiring, loosen the four captive screws that secure the cover
of the field wiring compartment.
-Access to the sensor wiring and circuit board compartments is not required for power
supply and output wiring.
Getting StartedPower Supply and Output WiringMounting the Remote TransmitterBefore You Begin
Model IFT9701 Transmitter Instruction Manual19
Loading...
+ 63 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.