Emerson IFT9701 User Manual

Instruction Manual
Micro Motion
®
Model IFT9701 Transmitter with Optional Display
Instruction Manual
Micro Motion
TM
Micro Motion
®
Model IFT9701 Transmitter with Optional Display
Instruction Manual
For online technical support, refer to the EXPERT2™ tool at www.expert2.com. To speak to a customer service representative, call the support center nearest you:
• In U.S.A., phone 1-800-522-MASS (1-800-522-6277)
• In Canada and Latin America, phone (303) 530-8400
• In Asia, phone (65) 6770-8155
• In the U.K., phone 0800 - 966 180 (toll-free)
• Outside the U.K., phone +31 (0) 318 495 670
©2004, Micro Motion, Inc. All rights reserved. Micro Motion is a registered trademark of Micro Motion, Inc. The Micro Motion and Emerson logos are trademarks of Emerson Electric Co. All other trademarks are property of their respective owners.
Contents
Chapter 1 Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1 About this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3 European installations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.4 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.5 Flowmeter components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Chapter 2 Getting Started. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 Safety, reliability, accessibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1.1 Hazardous area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1.2 Orientation and mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1.3 Temperature, humidity, and vibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1.4 Visibility of tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Transmitters approved for ATEX Zone 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.3 Jumper settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3.1 Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3.2 Fault output levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3.3 Re-installing the circuit board compartment cover. . . . . . . . . . . . . . . . . . 10
Chapter 3 Remotely Mounting the Transmitter . . . . . . . . . . . . . . . . . . . . . . . 11
3.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.2 Choosing the proper location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.3 Mounting the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.3.1 Guidelines for flat-surface mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.3.2 Guidelines for pole mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.4 Connecting the transmitter to the sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.4.1 Cable types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.4.2 Guidelines for conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.4.3 Guidelines for cable gland . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.4.4 Wiring connections to sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Chapter 4 Power Supply and Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.2 Wiring guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.3 Connect power supply wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.4 Connect output wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.4.1 Milliamp output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
4.4.2 Milliamp output connected to Bell 202 multidrop network . . . . . . . . . . . . 23
4.4.3 Communication tools connected to milliamp output. . . . . . . . . . . . . . . . . 24
4.4.4 Pulse output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Model IFT9701 Transmitter Instruction Manual i
Contents continued
Chapter 5 Flowmeter Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.2 Customer service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.3 Startup procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.4 Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.4.1 Diagnostic LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.4.2 Optional display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.4.3 Startup mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.4.4 Operating mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.5 Flowmeter zeroing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.5.1 Zeroing procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.5.2 Diagnosing zero failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.6 Configuration, calibration, and characterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.7 Process measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Chapter 6 Configuration with a HART Communicator . . . . . . . . . . . . . . . . . . . 35
6.1 Configuration overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.2 Configuration parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.2.1 HART tag. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.2.2 Measurement units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.2.3 Flow cutoff . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
6.2.4 Damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
6.2.5 Flow direction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
6.2.6 Range values for milliamp output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
6.2.7 Pulse output scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
6.3 Calibration procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
6.3.1 Auto zero . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
6.3.2 Flow calibration procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6.4 Characterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Chapter 7 Configuration with ProLink II Software . . . . . . . . . . . . . . . . . . . . . 45
7.1 Configuration overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
7.2 Configuration parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
7.2.1 HART tag. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
7.2.2 Process variable measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
7.2.3 Output configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
7.3 Calibration procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
7.3.1 Auto zero . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
7.3.2 Flow calibration procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.4 Characterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Chapter 8 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
8.1 Customer service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
8.2 General guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
8.3 Transmitter diagnostic tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
8.3.1 Diagnostic LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
8.3.2 Optional LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
8.3.3 Fault outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
8.4 Power supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
8.5 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
8.6 Over range and sensor failure conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
ii Model IFT9701 Transmitter Instruction Manual
Contents continued
8.7 Slug flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
8.8 Transmitter failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
8.9 Digital diagnostic messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Appendix A IFT9701 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
A.1 Performance specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
A.2 Functional specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
A.2.1 Output signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
A.2.2 Local display (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
A.2.3 Low-flow cutoff . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
A.2.4 Slug-flow inhibit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
A.2.5 Damping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
A.2.6 Fault indication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
A.2.7 Output testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
A.2.8 Power supply options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
A.3 Environmental limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
A.3.1 Temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
A.3.2 Process fluid temperature limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
A.3.3 Humidity limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
A.3.4 Vibration limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
A.4 Density limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
A.5 Environmental effects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
A.6 Ambient temperature effect on milliamp output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
A.7 Shipping weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
A.8 Hazardous area classifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Appendix B HART Communicator Menu Trees . . . . . . . . . . . . . . . . . . . . . . . . . 71
Appendix C Installing the Optional Display . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Appendix D Return Policy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
D.1 General guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
D.2 New and unused equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
D.3 Used equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Model IFT9701 Transmitter Instruction Manual iii
iv Model IFT9701 Transmitter Instruction Manual

Chapter 1

Before You Begin

1.1 About this manual

This instruction manual explains how to install, start up, configure, and troubleshoot the Micro Motion IFT9701 transmitter for use with Micro Motion Coriolis flow sensors. For more information about the sensor, see the appropriate sensor instruction manual.

1.2 Safety

Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully before proceeding to the next step.
Getting Started Power Supply and Output WiringMounting the Remote TransmitterBefore You Begin
WARNING
Improper installation in a hazardous area can cause an explosion.
For information about hazardous applications, refer to Micro Motion ATEX, CSA, or UL installation instructions, shipped with the transmitter or available from the Micro Motion web site.
WARNING
Hazardous voltage can cause severe injury or death.
Make sure power is disconnected before installing transmitter.
CAUTION
Improper installation could cause measurement error or transmitter failure.
Follow all instructions to ensure transmitter will operate correctly.
Model IFT9701 Transmitter Instruction Manual 1
Before You Begin continued

1.3 European installations

This Micro Motion product complies with all applicable European directives when properly installed in accordance with the instructions in this manual. Refer to the EC declaration of conformity for directives that apply to this product.
The EC declaration of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available on the internet at www.micromotion.com/atex or through your local Micro Motion support center.

1.4 Definitions

The term “sensor” refers to a Micro Motion sensor only.
The term “flowmeter” refers to an IFT9701 transmitter and a sensor installed as a flowmetering system.

1.5 Flowmeter components

The IFT9701 transmitter can be integrally mounted to a Micro Motion F-Series sensor, or remotely mounted from an ELITE
The IFT9701 transmitter does not operate with Micro Motion T-Series, R-Series, or Model D600 or DT sensors.
If the transmitter is integrally mounted to the sensor, the flowmeter includes the components shown in Figure 1-1.
If the transmitter will be remotely mounted from the sensor, the transmitter includes the components shown in Figure 1-2.
The transmitter is available with an optional liquid crystal display (LCD), as shown in Figure 1-1 and Figure 1-2, except for ATEX Zone 1 areas.
®
, F-Series, Model D, or Model DL sensor.
Figure 1-1 Integrally mounted IFT9701 transmitter with F-Series sensor
Field wiring compartment
With optional LCD
Case ground
Sensor wiring compartment
4X M8 mounting bolt 4X lock washer 4X flat washer
To rotate transmitter: remove, then re-install to 12 ft-lb (16 N-m) torque
Model IFT9701 transmitter
Flowmeter
F-Series sensor
2 Model IFT9701 Transmitter Instruction Manual
Before You Begin continued
Figure 1-2 Remotely mounted IFT9701 transmitter
Field wiring
compartment
Model
IFT9701
transmitter
4X M8 mounting bolt
•4X lock washer
• 4X flat washer To rotate transmitter: remove, then re-install to 12 ft-lb (16 Nm)
torque
For minimum bend radius of cable,
see Figure 3-4, 3-5, or 3-6
If conduit is used, install drip
With optional LCD
Sensor wiring
compartment
Sensor cable
leg in conduit
Circuit board compartment
User access not normally required
Mounting bracket
Requires 4 user-supplied bolts
Cable gland
• To assemble, see instructions shipped with cable kit
• Connects to sensor junction box
Getting Started Power Supply and Output WiringMounting the Remote TransmitterBefore You Begin
Model IFT9701 Transmitter Instruction Manual 3
4 Model IFT9701 Transmitter Instruction Manual

Chapter 2

Getting Started

2.1 Safety, reliability, accessibility

Improper installation in a hazardous area could cause an explosion.
Install the transmitter in an environment that is compatible with the hazardous area specified on the approvals tag.
• For intrinsically safe sensor installations, use this document with Micro Motion ATEX, CSA, or UL installation instructions.
• For hazardous area installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
WARNING
Getting Started Power Supply and Output WiringMounting the Remote TransmitterBefore You Begin
2.1.1 Hazardous area
If you plan to mount the transmitter in a hazardous area, ensure that your equipment and installation meet the hazardous area requirements. For more information about hazardous area classifications, see Section A.8. See Figure 2-1 for the location of the approvals tag on your transmitter.
Model IFT9701 Transmitter Instruction Manual 5
Getting Started continued
Figure 2-1 Location of approvals tag
Hazardous area approvals tag
2.1.2 Orientation and mounting
Orient the transmitter so wiring compartments and conduit openings are easily accessible.
To rotate the transmitter on the sensor manifold or the mounting bracket, use the four supplied mounting bolt assemblies. Each bolt assembly includes one M8 bolt, one lock washer, and one flat washer. Remove the bolt assemblies, rotate the transmitter, then reinstall the bolt assemblies to 12 ft-lb (16 N-m) of torque.
If the transmitter will be integrally mounted to a Micro Motion F-Series sensor, see the sensor product data sheet for transmitter and sensor dimensions, and see the instruction manual that was shipped with the sensor for information about flowmeter mounting and location.
If the transmitter will be remotely mounted, use the supplied bolt assemblies to attach the transmitter to the mounting bracket. Attach the bracket to a rigid, stable surface or instrument pole that will not transfer excessive vibration into the transmitter. See Chapter 3 for more information about remote mounting.
2.1.3 Temperature, humidity, and vibration
Install the transmitter according to specified limits:
Ambient temperature
- without optional LCD: –22 to +131 °F (–30 to +55 °C)
- with optional LCD: 32 to 131 °F (0 to 55 °C)
Humidity: 5 to 95% non-condensing
Vibration: Meets IEC 68.2.6, 2 g
6 Model IFT9701 Transmitter Instruction Manual
Getting Started continued
2.1.4 Visibility of tags
For personal and system safety, all tags attached to the transmitter housing must remain visible. Clean or replace them as necessary.

2.2 Transmitters approved for ATEX Zone 1

Explosion hazard
The circuit board compartment is rated EEx d (flameproof), and should remain closed at all times after the flowmeter has been installed.
To avoid risk of explosion in an explosive atmosphere:
• Read label that points to compartment cover before accessing circuit board compartment. Figure 2-2 shows the location of the labels on the transmitter housing.
• Shut off power, and wait at least 2 minutes before removing EEx d (circuit board) compartment cover. Figure 2-2 also identifies the EEx e (field wiring), EEx i (sensor wiring), and EEx d (circuit board) compartments.
WARNING
Getting Started Power Supply and Output WiringMounting the Remote TransmitterBefore You Begin
If the transmitter carries an ATEX Zone 1 approval, wiring compartments are labeled as shown in Figure 2-2.
The sensor wiring compartment is rated EEx i (intrinsically safe), and may be opened at any time. See Label 1 in Figure 2-2.
The field wiring compartment is rated EEx e (increased safety), and should remain closed when power is on. See Label 2 in Figure 2-2.
The circuit board compartment is rated EEx d (flameproof), and should remain closed at all times after the transmitter has been installed. If the transmitter is approved by ATEX as flameproof, the compartment has a lockout device, shown in Figure 2-2. The lockout device must be loosened and rotated before the compartment cover can be unscrewed.
Model IFT9701 Transmitter Instruction Manual 7
Getting Started continued
Figure 2-2 Compartment tags and lockout device
Field wiring compartment
Rated EEx e
Circuit board compartment
Rated EEx d

2.3 Jumper settings

Unless otherwise specified on the order, jumpers are set so the transmitter generates downscale fault outputs and enables flowmeter configuration. If jumper settings need to be changed, the procedure should be performed before the transmitter is installed.
To access security and fault output jumpers, unscrew the circuit board compartment cover.
If the transmitter is approved by ATEX as flameproof, the compartment has a lockout device. See Figure 2-2. The lockout device must be loosened and rotated before the compartment cover can be unscrewed.
Label 1
Lockout device
Loosen and rotate before opening circuit board compartment
CAUTION
Improper handling of transmitter components can damage the transmitter.
Label 2
Sensor wiring compartment
Rated EEx i
• If a breaker bar is used for loosening the cover of the circuit board compartment:
- Apply steady pressure to avoid chipping the paint on
the transmitter housing. Chipped paint can result in corrosion of the housing. If paint becomes chipped, repaint the housing.
- Do not apply too much pressure. Excessive torque
can damage the pipeline, transmitter, or sensor.
• To prevent electrostatic discharge, wear an anti-static wrist strap while setting jumpers.
8 Model IFT9701 Transmitter Instruction Manual
Getting Started continued
2.3.1 Security
The security jumper enables the user to write-protect the flowmeter configuration, so it cannot be changed using a HART communication device:
With the security jumper OFF, the flowmeter configuration can be changed.
With the security jumper ON, the flowmeter configuration cannot be changed.
The default setting is OFF. To set the security jumper, see Figure 2-3.
2.3.2 Fault output levels
The transmitter can be configured to produce downscale or upscale fault outputs. In a fault condition:
Downscale: The milliamp output goes to 2 mA; the pulse output goes to 0 Hz.
Upscale: The milliamp output goes to 22 mA; the pulse output goes to 7200 Hz.
The diagnostic LED blinks ON four times per second, whether the setting is upscale or downscale.
The default setting is downscale. To set the fault output jumper, see Figure 2-3.
Figure 2-3 Jumper location and settings
Getting Started Power Supply and Output WiringMounting the Remote TransmitterBefore You Begin
Default settings
With standoff beneath jumpers
Security
OFF
Optional settings
With standoff beneath jumpers
Security
OFF
Security
ON
Security
ON
Downscale faults
Upscale faults
Upscale faults
Downscale faults
Model IFT9701 Transmitter Instruction Manual 9
Getting Started continued
2.3.3 Re-installing the circuit board compartment cover
To re-install the cover of the circuit board compartment:
1. Screw the cover back onto the housing.
2. Hand-tighten the cover until it seats on the O-ring.
3. If the circuit board compartment has a lockout device, as shown in Figure 2-2, rotate the clamp into place and push it into the slot. Use a 4-mm (5/32-inch) Allen wrench to tighten the lockout screw to 5 inch-pounds (0,56 N-m) of torque.
10 Model IFT9701 Transmitter Instruction Manual

Chapter 3

Remotely Mounting the Transmitter

Note: The instructions in this chapter apply only if the transmitter will be remotely mounted from the sensor. If the transmitter is integrally mounted to the sensor, proceed to Chapter 4.

3.1 Overview

To mount the transmitter remotely from the sensor, the following steps are required:
Choosing the proper location (see Section 3.2)
Mounting the sensor on a flat surface or instrument pole (see Section 3.3)
Connecting the transmitter to the sensor (see Section 3.4)

3.2 Choosing the proper location

Install the transmitter according to the conditions stated in Section 2.1.
Getting Started Power Supply and Output WiringMounting the Remote TransmitterBefore You Begin
For mounting dimensions, see Figure 3-1. Total length of cable from sensor to transmitter must not exceed 1000 feet (300 meters). For bend radii of cables, see Figure 3-4, Figure 3-5, or Figure 3-6, according to the type of cable to be
used.

3.3 Mounting the transmitter

A transmitter that is to be remotely mounted from the sensor is shipped with an L-shaped mounting bracket. Attach the bracket to a rigid, stable surface or instrument pole that will not transfer excessive vibration into the transmitter.
3.3.1 Guidelines for flat-surface mounting
Use four 5/16-inch (M8) nuts (not included), suitable for the environment.
Do not secure bolts to separate beams, girders, wall studs, etc., which can move independently.
To prevent unnecessary stress on the mounting bracket, use washers to shim the bracket if the mounting surface is not flat.
For more information, see Figure 3-2.
3.3.2 Guidelines for pole mounting
Use two 5/16-inch (M8) U-bolts for 2-inch pipe, and four 5/16-inch (M8) nuts (not included), suitable for the environment.
For more information, see Figure 3-3.
Model IFT9701 Transmitter Instruction Manual 11
Remotely Mounting the Transmitter continued
Figure 3-1 Installation dimensions for remote mounting
Dimensions in
3/4–14 NPT or M20 X 1.5
for power wiring
gland for sensor wiring
inches
(mm)
Character
height
3/4–14 NPT
4X
1/2
(13)
Ø 25/64
(10)
5 3/4 (146)
2 13/16
(71)
3/4–14 NPT or M20 X 1.5 for output wiring
Field wiring compartment
61/64
(24)
4 1/4
2 13/16
(108)
(71)
(44)
7 1/64
(178)
2X 5 57/64
9 43/64
(245)
1 3/4
(150)
(1)
4 1/4 (107)
4 53/64
(122)
6 17/64
(159)
19/32
(15)
(1)If transmitter is ordered without display,
dimension is 1 3/8 (35).
For minimum bend radii of cable, see Figure 3-4,
Figure 3-5, or Figure 3-6
12 Model IFT9701 Transmitter Instruction Manual
Remotely Mounting the Transmitter continued
Figure 3-2 Mounting the transmitter to a wall or other surface
Circuit board compartment
User access not normally required
Area approvals tag
Field wiring compartment
Sensor wiring compartment
4X M8 bolt 4X lock washer 4X flat washer
To rotate transmitter: remove, then re-install to 12 ft-lb (16 N-m) torque
4X 5/16 (M8) bolt
User-supplied
Figure 3-3 Mounting the transmitter to an instrument pole
Area approvals tag
Field wiring compartment
Sensor wiring compartment
4X 5/16 (M8) bolt
User-supplied
Getting Started Power Supply and Output WiringMounting the Remote TransmitterBefore You Begin
Circuit board compartment
User access not normally required
4X M8 bolt 4X lock washer 4X flat washer
To rotate transmitter: remove, then re-install to 12 ft-lb (16 N-m) torque
Model IFT9701 Transmitter Instruction Manual 13
2X 5/16-inch (M8) U-bolt for 2-inch pipe
User-supplied
Remotely Mounting the Transmitter continued
Jack

3.4 Connecting the transmitter to the sensor

Improper installation of cable, cable gland, or conduit could cause inaccurate measurements or flowmeter failure.
To ensure 360° termination shielding for flowmeter wiring, install the factory-supplied cable gland or user-supplied sealed metallic conduit to the conduit opening on the sensor junction box.
To connect the transmitter to the sensor:
Micro Motion 9-wire cable is required. See Section 3.4.1 for information on cable types offered by Micro Motion.
Depending on your cable type, you must either install the cable in conduit or use cable glands. See Section 3.4.2 for information on conduit installations. See Section 3.4.3 for information on cable gland installations.
For information on connecting the wires to the terminals, see Section 3.4.4.
CAUTION
Micro Motion’s 9-Wire Flowmeter Cable Preparation and Installation Guide, shipped with the cable, provides additional information on cable types, cable preparation, and installation requirements.
3.4.1 Cable types
Micro Motion supplies 9-wire jacketed, shielded, or armored cable.
Jacketed cable is CE-compliant when it is installed inside user-supplied sealed metallic conduit that provides 360° termination shielding for the enclosed cable. See Figure 3-4 for an illustration of jacketed cable.
Shielded and armored cable are CE-compliant when the cable is installed with the factory-supplied cable glands. See Figure 3-5 for an illustration of shielded cable, and Figure 3-6 for an illustration of armored cable.
Each cable type is available with a PVC or Teflon cable jacket materials, see Table 3-1.
See Table 3-2 for guidelines on cable selection. All cable types are acceptable for cable tray installation.
Figure 3-4 Jacketed cable
et
Drain wire (4)
Foil shield (4)
Filler (5)
®
FEP jacket. For temperature ranges of
Minimum bend radii
Static
Outside
Jacket material
PVC 0.415 (10) 3 1/8 (80) 6 1/4 (159) Te fl on
FEP
diameter
inches (mm) inches (mm) inches (mm)
®
0.340 (9) 2 5/8 (67) 5 1/8 (131)
(no load) condition
Under dynamic load
14 Model IFT9701 Transmitter Instruction Manual
Remotely Mounting the Transmitter continued
Figure 3-5 Shielded cable
Outer jacket
Figure 3-6 Armored cable
Outer jacket
Tin-plated copper braided shield
Foil shield (1)
Inner jacket
Drain wire (4)
Foil shield (4)
Filler (5)
Stainless steel braided shield
Foil shield (1)
Inner jacket
Drain wire (4)
Minimum bend radii
Static
Outside
Jacket material
PVC 0.525 (14) 4 1/4 (108) 8 1/2 (216) Te fl on
FEP
diameter
inches (mm) inches (mm) inches (mm)
®
0.425 (11) 3 1/4 (83) 6 3/8 (162)
(no load) condition
Under dynamic load
Minimum bend radii
Static
Outside Jacket material
PVC 0.525 (14) 4 1/4 (108) 8 1/2 (216) Te fl on
FEP
diameter
inches (mm) inches (mm) inches (mm)
®
0.425 (11) 3 1/4 (83) 6 3/8 (162)
(no load) condition
Under dynamic load
Getting Started Power Supply and Output WiringMounting the Remote TransmitterBefore You Begin
Foil shield (4)
Filler (5)
Table 3-1 Temperature ranges for jacket material
Jacket material Low operating temperature limit High operating temperature limit
PVC –40 °F (–40 °C) 221 °F (105 °C) Te fl on® FEP –76 °F (–60 °C) 302 °F (150 °C)
Table 3-2 Cable selection guidelines
Installation requirements Jacketed cable Shielded cable Armored cable
Conduit is used Conduit is not used Conduit is not used and
mechanical protection is required
Model IFT9701 Transmitter Instruction Manual 15
Remotely Mounting the Transmitter continued
3.4.2 Guidelines for conduit
If sealed metallic conduit is installed, it must provide 360° termination shielding for the enclosed flowmeter cable.
1. Install a drip leg in conduit to prevent liquids from entering the junction box.
2. Connect the sealed end of the conduit to the ¾-inch NPT female conduit opening on the sensor junction box.
3.4.3 Guidelines for cable gland
1. Prepare cable ends and assemble the supplied cable gland according to the instructions that are enclosed with the cable preparation kit.
2. Connect the ¾-inch NPT male cable gland to the ¾-inch NPT female conduit opening on the sensor junction box.
3.4.4 Wiring connections to sensor
1. At the sensor, insert the ends of the individual wires into the terminals inside the sensor junction box. Match the wire colors of the cable with the wire colors at the sensor wiring terminal as described in Figure 3-7 and Table 3-3. No bare wire should remain exposed.
2. If possible, position the junction box on the sensor so the conduit entrance points downward to prevent moisture from entering.
3. At the transmitter, if cable is not preinstalled, connect the cable to the transmitter terminals as indicated in Figure 3-8.
WARNING
Failure to seal sensor junction box or transmitter housing could cause a short circuit, which would result in measurement error or flowmeter failure.
• Seal all conduit openings.
• Install drip legs in cable or conduit.
• Fully tighten sensor junction box and transmitter housing covers. See Figure 3-8.
16 Model IFT9701 Transmitter Instruction Manual
Remotely Mounting the Transmitter continued
10 11 12
GND
10 11 12
GND
Figure 3-7 Cable connections to sensors
ELITE and F-Series
sensor terminals
Maximum cable length 1000 ft. (330 m)
Green
White
Violet
Yellow
Orange
Brown
Blue Gray Red
Clip drain wire back
Clip drain wire back
Clip drain wire back
Clip drain wire back
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Prepare cable in accordance with the
instructions that are shipped with the cable
Flowmeter
cable
Black (Drains from all wire sets)
Brown Red
Green White
Blue Gray
Orange Violet Ye l l ow
IFT9701
terminals
Brown
Black (Drains,
remote-mount only)
Red
Blue
Gray
Violet
Green
Yellow
Orange
White
D and DL
sensor terminals*
Brown Red Orange Ye l l ow Green Blue Violet Gray White
Brown
Clip drain wire back
Clip drain wire back
Clip drain wire back
Clip drain wire back
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Flowmeter
cable
Maximum cable length 1000 ft. (300 m)
Black (Drains from all wire sets)
Brown Red
Green White
Blue Gray
Orange Violet Yellow
Prepare cable in accordance with the
instructions that are shipped with the cable
*Model D600 and DT sensors cannot be used
with IFT9701 transmitters
Table 3-3 Sensor terminal designations
Terminal number Wire color Function
1 Brown Drive + 2 Red Drive – 3 Orange Temperature – 4 Yellow Temperature lead length compensator 5 Green Left pickoff + 6 Blue Right pickoff + 7 Violet Temperature + 8 Gray Right pickoff – 9 White Left pickoff –
IFT9701
terminals
Brown
Black (Drains,
remote-mount only)
Red
Getting Started Power Supply and Output WiringMounting the Remote TransmitterBefore You Begin
Blue
Gray
Violet
Green
Ye l l ow
Orange
White
Model IFT9701 Transmitter Instruction Manual 17
Remotely Mounting the Transmitter continued
Figure 3-8 Sensor wiring compartment and sensor wiring terminals
Sensor wiring terminals
Sensor wiring compartment
18 Model IFT9701 Transmitter Instruction Manual

Chapter 4

Power Supply and Output Wiring

4.1 Overview

To wire the transmitter power supply and outputs:
Review the wiring guidelines (see Section 4.2)
Connect the power supply wiring (see Section 4.3)
Connect the output wiring (see Section 4.4)

4.2 Wiring guidelines

Install cable and wiring so they meet local code requirements.
The transmitter has two separate ¾-inch NPT or M20 female conduit openings, which must remain sealed to keep the transmitter watertight. See Figure 4-1 and Figure 4-2.
The transmitter has a sensor wiring compartment for intrinsically safe sensor wiring, and a field wiring compartment for non-intrinsically safe power supply and output wiring. See Figure 4-1 and Figure 4-2.
- For power supply and output wiring, loosen the four captive screws that secure the cover
of the field wiring compartment.
- Access to the sensor wiring and circuit board compartments is not required for power
supply and output wiring.
Getting Started Power Supply and Output WiringMounting the Remote TransmitterBefore You Begin
Model IFT9701 Transmitter Instruction Manual 19
Loading...
+ 63 hidden pages