Emerson ib-106-340cdr, Oxymitter DR User Manual

Instruction Manual
IB-106-340CDR Original Issue January, 2002
Oxymitter DR
Hazardous Area In-Situ Oxygen Probe
Certified to: CENELEC EEXd IIB + H2 T3
CSA Class I, Division 1, Groups B, C, D
http://www.processanalytic.com

ESSENTIAL INSTRUCTIONS

READ THIS PAGE BEFORE PROCEEDING!
Rosemount Analytical designs, manufactures and tests its products to meet many national and international standards. Because these instruments are sophisticated technical products, you MUST properly install, use, and maintain them to ensure they continue to operate within their normal specifications. The following instructions MUST be adhered to and integrated into your safety program when installing, using, and maintaining Rosemount Analytical products. Failure to follow the proper instructions may cause any one of the following situations to occur: Loss of life; personal injury; property damage; damage to this instrument; and warranty invalidation.
Read all instructions prior to installing, operating, and servicing the product.
If you do not understand any of the instructions, contact your Rosemount Analytical repre-
sentative for clarification.
Follow all warnings, cautions, and instructions marked on and supplied with the product.
Inform and educate your personnel in the proper installation, operation, and mainte-
nance of the product.
Install your equipment as specified in the Installation Instructions of the appropriate In- struction Manual and per applicable local and national codes. Connect all products to the
proper electrical and pressure sources.
To ensure proper performance, use qualified personnel to install, operate, update, program, and maintain the product.
When replacement parts are required, ensure that qualified people use replacement parts specified by Rosemount. Unauthorized parts and procedures can affect the product’s per­formance, place the safe operation of your process at risk, and VOID YOUR WARRANTY. Look-alike substitutions may result in fire, electrical hazards, or improper operation.
Ensure that all equipment doors are closed and protective covers are in place, except when maintenance is being performed by qualified persons, to prevent electrical shock and personal injury.
The information contained in this document is subject to change without notice.
Rosemount Analytical Inc. Process Analytic Division
1201 N. Main St. Orrville, OH 44667-0901 T (330) 682-9010 F (330) 684-4434 e-mail: gas.csc@EmersonProcess.com
http://www.processanalytic.com
Hazardous Area Oxymitter DR

TABLE OF CONTENTS

PREFACE............................................................................................................................1
Definitions ............................................................................................................................1
Safety Instructions ..............................................................................................................2
1-0 DESCRIPTION AND SPECIFICATIONS........................................................................ 1-1
1-1 Component Checklist of Typical System (Package Contents) .................................. 1-1
1-2 System Overview............................................................................................................ 1-1
1-3 Probe Options................................................................................................................. 1-4
1-4 Specifications................................................................................................................... 1-6
2-0 INSTALLATION .............................................................................................................. 2-1
2-1 Mechanical Installation ................................................................................................... 2-1
2-2 Electrical Installation....................................................................................................... 2-7
2-3 Pneumatic Installation .................................................................................................... 2-8
2-4 System Setup .................................................................................................................. 2-9
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
3-0 STARTUP AND OPERATION ........................................................................................ 3-1
3-1 General ............................................................................................................................ 3-1
4-0 MAINTENANCE AND SERVICE .................................................................................. 4-1
4-1 Overview.......................................................................................................................... 4-1
4-2 Calibration........................................................................................................................ 4-1
4-3 Hazardous Area Oxymitter DR Replacement................................................................ 4-1
4-4 Terminal Block Replacement........................................................................................... 4-3
4-5 Entire Probe Replacement ............................................................................................ 4-4
4-6 Heater Strut Replacement ............................................................................................. 4-4
4-7 Cell Replacement ........................................................................................................... 4-5
4-8 Ceramic Diffusion Element Replacement..................................................................... 4-7
4-9 Termination Housing Wiring ............................................................................................ 4-9
5-0 TROUBLESHOOTING .................................................................................................... 5-1
5-1 Overview.......................................................................................................................... 5-1
5-2 Probe Troubleshooting ................................................................................................... 5-1
6-0 RETURN OF MATERIAL ................................................................................................ 6-1
6-1 Equipment Return........................................................................................................... 6-1
7-0 REPLACEMENT PARTS ................................................................................................ 7-1
8-0 OPTIONAL ACCESSORIES .......................................................................................... 8-1
9-0 APPENDICES ................................................................................................................. 9-1
10-0 INDEX............................................................................................................................ 10-1
Rosemount Analytical Inc. A Division of Emerson Process Management i
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Figure 1-1. Typical System Package ....................................................................................... 1-2
Figure 1-2. Typical System Installation .................................................................................... 1-3
Figure 1-3. Flame Arrestor Diffusion Assembly......................................................................... 1-4
Figure 1-4. Flame Arrestor Snubber Diffusion Assembly......................................................... 1-4
Figure 1-5. Abrasive Shield Assembly ..................................................................................... 1-5
Figure 2-1. Hazardous Area Oxymitter DR Installation ............................................................ 2-2
Figure 2-2. Hazardous Area Oxymitter DR with Abrasive Shield............................................. 2-3
Figure 2-3. Hazardous Area Oxymitter DR Adapter Plate Dimensions .................................. 2-4
Figure 2-4. Hazardous Area Oxymitter DR Adapter Plate Installation .................................... 2-5
Figure 2-5. Orienting the Optional Vee Deflector..................................................................... 2-6
Figure 2-6. Installation with Drip Loop and Insulation Removal ............................................... 2-6
Figure 2-7. Terminal Block ....................................................................................................... 2-8
Figure 2-8. Air Set, Plant Air Connection ................................................................................. 2-9
Figure 2-9. Temperature Controller Card Calibration Points ................................................. 2-10
Figure 2-10. Main PCB (Model 218A) EPROM Replacement ................................................. 2-11
Figure 2-11. Main PCB (Model TC200) EPROM Replacement ............................................... 2-13
Figure 2-12. Main PCB (Model 132) EPROM Replacement .................................................... 2-14
Figure 2-13. IFT 3000 Power Supply Board Jumper Configuration ......................................... 2-15
Figure 2-14. Heater Power Supply (HPS 3000) Jumper Configuration ................................... 2-15
Figure 2-15. DR Probe Wired to the ZA8C or A V8C Converter.............................................. 2-16
Figure 4-1. Hazardous Area Oxymitter DR Exploded View ..................................................... 4-2
Figure 4-2. Terminal Block ....................................................................................................... 4-3
Figure 4-3. Heater Strut Assembly ........................................................................................... 4-5
Figure 4-4. Cell Replacement Kit ............................................................................................. 4-6
Figure 4-5. Ceramic Diffusion Element Replacement.............................................................. 4-8
Figure 4-6. Termination Housing Connections......................................................................... 4-9
Figure 7-1. Cell Replacement Kit ............................................................................................. 7-2
Figure 7-2. Probe Disassembly Kit........................................................................................... 7-2
Hazardous Area Oxymitter DR
LIST OF ILLUSTRATIONS
LIST OF TABLES
Table 1-1. Product Matrix ........................................................................................................ 1-7
Table 1-3. Calibration Components ........................................................................................ 1-8
Table 5-1. Fault Finding .......................................................................................................... 5-1
Table 7-1. Replacement Parts for Probe ................................................................................ 7-1
ii Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
PREFACE
The purpose of this manual is to provide information concerning the components, func­tions, installation and maintenance of the Hazardous Area Oxymitter DR.
Some sections may describe equipment not used in your configuration. The user should become thoroughly familiar with the operation of this module before operating it. Read this instruction manual completely.
DEFINITIONS
The following definitions apply to WARNINGS, CAUTIONS, and NOTES found throughout this publication.
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
Highlights an operation or maintenance procedure, practice, condition, state­ment, etc. If not strictly observed, could result in injury, death, or long-term health hazards of personnel.
Highlights an essential operating procedure, condition, or statement.
: EARTH (GROUND) TERMINAL
: PROTECTIVE CONDUCTOR TERMINAL
: RISK OF ELECTRICAL SHOCK
: WARNING: REFER TO INSTRUCTION BULLETIN
NOTE TO USERS
Highlights an operation or maintenance procedure, practice, condition, state­ment, etc. If not strictly observed, could result in damage to or destruction of equipment, or loss of effectiveness.
NOTE
The number in the lower right corner of each illustration in this publication is a manual illus­tration number. It is not a part number, and is not related to the illustration in any technical manner.
Rosemount Analytical Inc. A Division of Emerson Process Management P-1
Instruction Manual
IB-106-340CDR Original Issue January, 2002
FOR THE WIRING AND INSTALLATION
The following safety instructions apply specifically to all EU member states. They should be strictly adhered to in order to assure compliance with the Low Voltage Directive. Non­EU states should also comply with the following unless superseded by local or National Standards.
1. Adequate earth connections should be made to all earthing points, internal and external,
where provided.
2. After installation or troubleshooting, all safety covers and safety grounds must be replaced.
The integrity of all earth terminals must be maintained at all times.
3. Mains supply cords should comply with the requirements of IEC227 or IEC245.
Hazardous Area Oxymitter DR
IMPORTANT

SAFETY INSTRUCTIONS

OF THIS APPARATUS
4. All wiring shall be suitable for use in an ambient temperature of greater than 75°C.
5. All cable glands used should be of such internal dimensions as to provide adequate cable
anchorage.
6. To ensure safe operation of this equipment, connection to the mains supply should only be
made through a circuit breaker which will disconnect all circuits carrying conductors during a fault situation. The circuit breaker may also include a mechanically operated isolating switch. If not, then another means of disconnecting the equipment from the supply must be provided and clearly marked as such. Circuit breakers or switches must comply with a recognized standard such as IEC947. All wiring must conform with any local standards.
7. Where equipment or covers are marked with the symbol to the right, hazard-
ous voltages are likely to be present beneath. These covers should only be removed when power is removed from the equipment — and then only by trained service personnel.
8. Where equipment or covers are marked with the symbol to the right, there is a
danger from hot surfaces beneath. These covers should only be removed by trained service personnel when power is removed from the equipment. Cer­tain surfaces may remain hot to the touch.
9. Where equipment or covers are marked with the symbol to the right, refer to
the Operator Manual for instructions.
10. All graphical symbols used in this product are from one or more of the follow-
ing standards: EN61010-1, IEC417, and ISO3864.
P-2 Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
CERAMIC FIBER PRODUCTS
MATERIAL SAFETY DATA SHEET
JULY 1, 1996
SECTION I. IDENTIFICATION
PRODUCT NAME
Ceramic Fiber Heaters, Molded Insulation Modules and Ceramic Fiber Radiant Heater Panels.
CHEMICAL FAMILY
Vitreous Aluminosilicate Fibers with Silicon Dioxide.
CHEMICAL NAME
N.A.
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
CHEMICAL FORMULA
N.A.
MANUFACTURER’S NAME AND ADDRESS
Watlow Columbia 573-474-9402 2101 Pennsylvania Drive 573-814-1300, ext. 5170 Columbia, MO 65202
HEALTH HAZARD SUMMARY
WARNING
Possible cancer hazard based on tests with laboratory animals.
May be irritating to skin, eyes and respiratory tract.
May be harmful if inhaled.
Cristobalite (crystalline silica) formed at high temperatures (above 1800ºF) can cause severe respiratory
disease.
Rosemount Analytical Inc. A Division of Emerson Process Management P-3
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Hazardous Area Oxymitter DR
SECTION II. PHYSICAL DATA
APPEARANCE AND ODOR
Cream to white colored fiber shapes. With or without optional white to gray granular surface coating and/or optional black surface coating.
SPECIFIC WEIGHT: 12-25 LB./CUBIC FOOT BOILING POINT: N.A.
VOLATILES (% BY WT.): N.A. WATER SOLUBILITY: N.A.
SECTION III. HAZARDOUS INGREDIENTS
MATERIAL, QUANTITY, AND THRESHOLD/EXPOSURE LIMIT VALUES
Aluminosilicate (vitreous) 99+ % 1 fiber/cc TWA CAS. No. 142844-00-06 10 fibers/cc CL Zirconium Silicate 0-10% 5 mg/cubic meter (TLV) Black Surface Coating** 0 - 1% 5 mg/cubic meter (TLV) Armorphous Silica/Silicon Dioxide 0-10% 20 mppcf (6 mg/cubic meter)
PEL (OSHA 1978) 3 gm cubic meter (Respirable dust): 10 mg/cubic meter, Intended TLV (ACGIH 1984-85)
**Composition is a trade secret.
SECTION IV. FIRE AND EXPLOSION DATA
FLASH POINT: NONE FLAMMABILITY LIMITS: N.A.
EXTINGUISHING MEDIA
Use extinguishing agent suitable for type of surrounding fire.
UNUSUAL FIRE AND EXPLOSION HAZARDS / SPECIAL FIRE FIGHTING PROCEDURES
N.A.
P-4 Rosemount Analytical Inc. A Division of Emerson Process Management
Instruction Manual
IB-106-340CDR Original Issue
Hazardous Area Oxymitter DR
January, 2002
SECTION V. HEALTH HAZARD DATA
THRESHOLD LIMIT VALUE
(See Section III)
EFFECTS OF OVER EXPOSURE
EYE
Avoid contact with eyes. Slightly to moderately irritating. Abrasive action may cause damage to outer surface of eye.
INHALATION
May cause respiratory tract irritation. Repeated or prolonged breathing of particles of respirable size may cause inflam­mation of the lung leading to chest pain, difficult breathing, coughing and possible fibrotic change in the lung (Pneumo­coniosis). Pre-existing medical conditions may be aggravated by exposure: specifically, bronchial hyper-reactivity and chronic bronchial or lung disease.
INGESTION
May cause gastrointestinal disturbances. Symptoms may include irritation and nausea, vomiting and diarrhea.
SKIN
Slightly to moderate irritating. May cause irritation and inflammation due to mechanical reaction to sharp, broken ends of fibers.
EXPOSURE TO USED CERAMIC FIBER PRODUCT
Product which has been in service at elevated temperatures (greater than 1800ºF/982ºC) may undergo partial conversion to cristobalite, a form of crystalline silica which can cause severe respiratory disease (Pneumoconiosis). The amount of cristobalite present will depend on the temperature and length of time in service. (See Section IX for permissible expo­sure levels).
SPECIAL TOXIC EFFECTS
The existing toxicology and epidemiology data bases for RCF’s are still preliminary. Information will be updated as studies are completed and reviewed. The following is a review of the results to date:
EPIDEMIOLOGY
At this time there are no known published reports demonstrating negative health outcomes of workers exposed to re­fractory ceramic fiber (RCF). Epidemiologic investigations of RCF production workers are ongoing.
1) There is no evidence of any fibrotic lung disease (interstitial fibrosis) whatsoever on x-ray.
2) There is no evidence of any lung disease among those employees exposed to RCF that had never smoked.
3) A statistical “trend” was observed in the exposed population between the duration of exposure to RCF and a de-
crease in some measures of pulmonary function. These observations are clinically insignificant. In other words, if these observations were made on an individual employee, the results would be interpreted as being within the nor­mal range.
Rosemount Analytical Inc. A Division of Emerson Process Management P-5
Instruction Manual
IB-106-340CDR Original Issue January, 2002
4) Pleural plaques (thickening along the chest wall) have been observed in a small number of employees who had a
long duration of employment. There are several occupational and non-occupational causes for pleural plaque. It should be noted that plaques are not “pre-cancer” nor are they associated with any measurable effect on lung function.
TOXICOLOGY
A number of studies on the health effects of inhalation exposure of rats and hamsters are available. Rats were exposed to RCF in a series of life-time nose-only inhalation studies. The animals were exposed to 30, 16, 9, and 3 mg/m corresponds with approximately 200, 150, 75, and 25 fibers/cc.
Animals exposed to 30 and 16 mg/m posed to 9 mg/m the response typically observed any time a material is inhaled into the deep lung. While a statistically significant in­crease in lung tumors was observed following exposure to the highest dose, there was no excess lung cancers at the other doses. Two rats exposed to 30 mg/m
The International Agency for Research on Cancer (IARC) reviewed the carcinogenicity data on man-made vitreous fi­bers (including ceramic fiber, glasswool, rockwool, and slagwool) in 1987. IARC classified ceramic fiber, fibrous glasswool and mineral wool (rockwool and slagwool) as possible human carcinogens (Group 2B).
3
had developed a mild parenchymal fibrosis; animals exposed to the lowest dose were found to have
3
were observed to have developed a pleural and parenchymal fibroses; animals ex-
3
and one rat exposed to 9 mg/m3 developed masotheliomas.
Hazardous Area Oxymitter DR
EMERGENCY FIRST AID PROCEDURES
3
, which
EYE CONTACT
Flush eyes immediately with large amounts of water for approximately 15 minutes. Eye lids should be held away from the eyeball to insure thorough rinsing. Do not rub eyes. Get medical attention if irritation persists.
INHALATION
Remove person from source of exposure and move to fresh air. Some people may be sensitive to fiber induced irritation of the respiratory tract. If symptoms such as shortness of breath, coughing, wheezing or chest pain develop, seek medi­cal attention. If person experiences continued breathing difficulties, administer oxygen until medical assistance can be rendered.
INGESTION
Do not induce vomiting. Get medical attention if irritation persists.
SKIN CONTACT
Do not rub or scratch exposed skin. Wash area of contact thoroughly with soap and water. Using a skin cream or lotion after washing may be helpful. Get medical attention if irritation persists.
SECTION VI. REACTIVITY DATA
STABILITY/CONDITIONS TO AVOID
Stable under normal conditions of use.
HAZARDOUS POLYMERIZATION/CONDITIONS TO AVOID
N.A.
P-6 Rosemount Analytical Inc. A Division of Emerson Process Management
Instruction Manual
IB-106-340CDR Original Issue
Hazardous Area Oxymitter DR
January, 2002
INCOMPATIBILITY/MATERIALS TO AVOID
Incompatible with hydrofluoric acid and concentrated alkali.
HAZARDOUS DECOMPOSITION PRODUCTS
N.A.
SECTION VII. SPILL OR LEAK PROCEDURES
STEPS TO BE TAKEN IF MATERIAL IS RELEASED OR SPILLED
Where possible, use vacuum suction with HEPA filters to clean up spilled material. Use dust suppressant where sweep­ing if necessary. Avoid clean up procedure which may result in water pollution. (Observe Special Protection Informa­tion Section VIII.)
WASTE DISPOSAL METHODS
The transportation, treatment, and disposal of this waste material must be conducted in compliance with all applicable Federal, State, and Local regulations.
SECTION VIII. SPECIAL PROTECTION INFORMATION
RESPIRATORY PROTECTION
Use NIOSH or MSHA approved equipment when airborne exposure limits may be exceeded. NIOSH/MSHA approved breathing equipment may be required for non-routine and emergency use. (See Section IX for suitable equipment).
Pending the results of long term health effects studies, engineering control of airborne fibers to the lowest levels attain­able is advised.
VENTILATION
Ventilation should be used whenever possible to control or reduce airborne concentrations of fiber and dust. Carbon monoxide, carbon dioxide, oxides of nitrogen, reactive hydrocarbons and a small amount of formaldehyde may accom­pany binder burn-off during first heat. Use adequate ventilation or other precautions to eliminate vapors resulting from binder burn-off. Exposure to burn-off fumes may cause respiratory tract irritation, bronchial hyper-reactivity and asth­matic response.
SKIN PROTECTION
Wear gloves, hats and full body clothing to prevent skin contact. Use separate lockers for work clothes to prevent fiber transfer to street clothes. Wash work clothes separately from other clothing and rinse washing machine thoroughly after use.
EYE PROTECTION
Wear safety glasses or chemical worker’s goggles to prevent eye contact. Do not wear contact lenses when working with this substance. Have eye baths readily available where eye contact can occur.
Rosemount Analytical Inc. A Division of Emerson Process Management P-7
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Hazardous Area Oxymitter DR
SECTION IX. SPECIAL PRECAUTIONS
PRECAUTIONS TO BE TAKEN IN HANDLING AND STORING
General cleanliness should be followed. The Toxicology data indicate that ceramic fiber should be handled with caution. The handling practices described in this
MSDS must be strictly followed. In particular, when handling refractory ceramic fiber in any application, special cau­tion should be taken to avoid unnecessary cutting and tearing of the material to minimize generation of airborne dust.
It is recommended that full body clothing be worn to reduce the potential for skin irritation. Washable or disposable clothing may be used. Do not take unwashed work clothing home. Work clothes should be washed separately from other clothing. Rinse washing machine thoroughly after use. If clothing is to be laundered by someone else, inform launderer of proper procedure. Work clothes and street clothes should be kept separate to prevent contamination.
Product which has been in service at elevated temperatures (greater than 1800ºF/982ºC) may undergo partial conversion to cristobalite, a form of crystalline silica. This reaction occurs at the furnace lining hot face. As a consequence, this material becomes more friable; special caution must be taken to minimize generation of airborne dust. The amount of cristobalite present will depend on the temperature and length in service.
IARC has recently reviewed the animal, human, and other relevant experimental data on silica in order to critically evaluate and classify the cancer causing potential. Based on its review, IARC classified crystalline silica as a group 2A carcinogen (probable human carcinogen).
The OSHA permissible exposure limit (PEL for cristobalite is 0.05 mg/m value (TLV) for cristobalite is 0.05 mg/m ment when airborne exposure limits may be exceeded. The minimum respiratory protection recommended for given air­borne fiber or cristobalite concentrations are:
3
(respirable dust) (ACGIH 1991-92). Use NIOSH or MSHA approved equip-
3
(respirable dust). The ACGIH threshold limit
CONCENTRATION
0-1 fiber/cc or 0-0.05 mg/m3 cristobalite Optional disposable dust respirator (e.g. 3M 9970 (the OSHA PEL) or equivalent).
Up to 5 fibers/cc or up to 10 times the Half face, air-purifying respirator equipped with high OSHA PEL for cristobalite efficiency particulate air (HEPA) filter cartridges
(e.g. 3M 6000 series with 2040 filter or equivalent).
Up to 25 fibers/cc or 50 times the OSHA Full face, air-purifying respirator with high efficiency PEL for cristobalite (2.5 mg/m
Greater than 25 fibers/cc or 50 times the Full face, positive pressure supplied air respirator OSHA PEL for cristobalite (2.5 mg/m
If airborne fiber or cristobalite concentrations are not known, as minimum protection, use NIOSH/MSHA approved half face, air-purifying respirator with HEPA filter cartridges.
3
) particulate air (HEPA) filter cartridges (e.g. 3M 7800S
with 7255 filters or equivalent) or powered air -purifying respirator (PARR) equipped with HEPA filter cartridges (e.g. 3M W3265S with W3267 filters or equivalent).
3
) (e.g. 3M 7800S with W9435 hose & W3196 low
pressure regulator kit connected to clean air supply or equivalent).
P-8 Rosemount Analytical Inc. A Division of Emerson Process Management
Instruction Manual
IB-106-340CDR Original Issue
Hazardous Area Oxymitter DR
Insulation surface should be lightly sprayed with water before removal to suppress airborne dust. As water evaporates during removal, additional water should be sprayed on surfaces as needed. Only enough water should be sprayed to suppress dust so that water does not run onto the floor of the work area. To aid the wetting process, a surfactant can be used.
After RCF removal is completed, dust-suppressing cleaning methods, such as wet sweeping or vacuuming, should be used to clean the work area. If dry vacuuming is used, the vacuum must be equipped with HEPA filter. Air blowing or dry sweeping should not be used. Dust-suppressing components can be used to clean up light dust.
Product packaging may contain product residue. Do not reuse except to reship or return Ceramic Fiber products to the factory.
January, 2002
Rosemount Analytical Inc. A Division of Emerson Process Management P-9
Instruction Manual
IB-106-340CDR Original Issue January, 2002
For assistance with technical problems, please call the Customer Support Center (CSC). The CSC is staffed 24 hours a day, 7 days a week.
In addition to the CSC, you may also contact Field Watch. Field Watch coordinates Rosemount’s field service throughout the U.S. and abroad.
Rosemount may also be reached via the Internet through e-mail and the World Wide Web:
Hazardous Area Oxymitter DR
Technical Support Hotline:
Phone: 1-800-433-6076
Phone: 1-800-654-RSMT (1-800-654-7768)
e-mail: GAS.CSC@frco.com
World Wide Web: www.processanalytic.com
P-10 Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
1

DESCRIPTION AND SPECIFICATIONS

Instruction Manual
IB-106-340CDR Original Issue
January, 2002
SECTION 1
1-1 COMPONENT CHECKLIST OF TYPICAL
SYSTEM (PACKAGE CONTENTS)
A typical Rosemount Hazardous Area Oxymitter DR In-Situ Oxygen Probe should contain the items shown in Figure 1-1. Record the part num­ber, serial number, and order number for each component of your system in the table located on the back cover of this manual.
The Oxymitter DR is offered in both hazardous and general purpose con­figurations. The hazardous area ver­sion has the “EX” and CSA symbols on the apparatus approval label. The general purpose version does not have an approval label. If you received the general purpose version, ensure you do not install it in a potentially ex­plosive atmosphere.
Also, use the product matrix in Table 1-1 at the end of this section to compare your order num­ber against your unit. The first part of the matrix defines the model. The last part defines the various options and features of the Hazardous Area Oxymitter DR. Ensure the features and options specified by your order number are on or included with the unit.
b. System Description
The Hazardous Area Oxymitter DR is de­signed to measure the net concentration of oxygen in an industrial combustion process; i.e., the oxygen remaining after all fuels have been oxidized. The probe is permanently po­sitioned within an exhaust duct or stack and performs its task without the use of a sam­pling system.
The equipment measures oxygen percent­age by reading the voltage developed across a heated electrochemical cell, which consists of a small yttria-stabilized, zirconia disc. Both sides of the disc are coated with porous metal electrodes. When operated at the proper temperature, the millivolt output volt­age of the cell is given by the following Nernst equation:
EMF = KT log
Where:
1. P
is the partial pressure of the
2
oxygen in the measured gas on one side of the cell.
2. P
is the partial pressure of the
1
oxygen in the reference air on the opposite side of the cell.
3. T is the absolute temperature.
10(P1/P2
) + C

1-2 SYSTEM OVERVIEW

a. Scope
This Instruction Bulletin is designed to supply details needed to install, start up, operate, and maintain the Hazardous Area Oxymitter DR. The Hazardous Area Direct Replace­ment Oxymitter can be interfaced to a num­ber of different earlier model electronics packages. These electronic packages are not covered in this manual. For specification information concerning calibration and op­eration of the system, refer to the Instruction Bulletin applicable to your electronics.
Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 1-1
4. C is the cell constant.
5. K is an arithmetic constant.
When the cell is at operating temperature and there are unequal oxygen concentra­tions across the cell, oxygen ions will travel from the high oxygen partial pressure side to the low oxygen partial pressure side of the cell. The resulting logarithmic output voltage is approximately 50 mV per decade. The output is proportional to the inverse logarithm of the oxygen concentration. Therefore, the output signal increases as the oxygen con­centration of the sample gas decreases. This characteristic enables the Hazardous Area Oxymitter DR to provide exceptional sensi­tivity at low oxygen concentrations.
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Hazardous Area Oxymitter DR
The Hazardous Area Oxymitter DR meas­ures net oxygen concentration in the pres­ence of all the products of combustion, including water vapor. Therefore, it may be considered an analysis on a “wet” basis. In comparison with older methods, such as the portable apparatus, which provides an analysis on a “dry” gas basis, the “wet” analysis will, in general, indicate a lower per­centage of oxygen. The difference will be proportional to the water content of the sam­pled gas stream.
c. System Configuration
Hazardous Area Oxymitter DR units are available in three length options, giving the user the flexibility to use an in situ penetra­tion appropriate to the size of the stack or duct. The options on length are 457 mm (18 in.), 0.91 m (3 ft), 1.83 m (6 ft).
Abrasive shields are offered for applications where abrasive particulates are present. Acid resistant cells are available for SO
2
and HCl environments. Bypass and probe mounting jacket options are available for process temperatures above 1300°F (705°C).
d. System Features
1. The cell output voltage and sensitivity increase as the oxygen concentration decreases.
2. Field replaceable cell, heater, thermo­couple, and diffusion element.
3. The Hazardous Area Oxymitter DR is constructed of rugged 316L stainless steel for all wetted parts.
1
4
2
3
1. Instruction Bulletin
2. Adapter Plate with Mounting Hardware and Gasket
3. Hazardous Area Oxymitter DR
4. Reference Air Set
36220001
Figure 1-1. Typical System Package
1-2 Description and Specifications Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
1
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
e. Handling the Hazardous Area
Oxymitter DR
The Hazardous Area Oxymitter DR is designed for industrial applications. Treat each component of the system with care to avoid physical damage. Some probe components are made from ceramics, which are susceptible to shock when mishandled.
f. System Considerations
Prior to installing your Hazardous Area Oxymitter DR, make sure you have all the components necessary to make the system installation. Ensure all the components are properly integrated to make the system functional.
NOTE
Retain the packaging in which the Hazardous Area Oxymitter DR arrived from the factory in case any compo­nents are to be shipped to another
site. This packaging has been de­signed to protect the product.
After verifying that you have all the compo­nents, select mounting locations and deter­mine how each component will be placed in terms of available line voltage, ambient temperatures, environmental considera­tions, convenience, and serviceability. A typical system installation is illustrated in Figure 1-2.
Instrument air for reference is optional for most applications. Ambient air will passively diffuse into the inside of the probe in suffi­cient quantity for an accurate measurement. Instrument air is required for applications where the ambient air at the probe location may not contain the typical 20.95% O example would be an installation into a positive pressure flue gas duct which has many leaks into the surrounding air.
If the calibration gas bottles will be perma­nently connected, a blocking valve or check valve is required next to the calibration fit­tings on the termination housing.
. An
2
4-20 mA
SIGNAL
AC POWER
OXYMITTER DR
EXISTING SIGNAL
CONDITIONING
ELECTRONICS
Figure 1-2. Typical System Installation
GASES
STACK
HEATER
POWER
OXYGEN
SIGNAL
THERMOCOUPLE
SIGNAL
DUCT
FLOWMETER
CALIBRATION GAS
ADAPTER PLATE
PRESSURE
REGULATOR
INSTRUMENT
AIR SUPPLY
(REFERENCE AIR)
36210004
Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 1-3
Instruction Manual
IB-106-340CDR Original Issue January, 2002
This check valve or blocking valve is to prevent breathing of the calibration gas line and subsequent flue gas condensation and corrosion.
g. Upgrading the Hazardous Area
Oxymitter DR
The Hazardous Area Oxymitter DR can be easily upgraded to a full Oxymitter 4000 or 5000. This provides an economi­cal upgrade path for users looking to pre­serve their probe investment upon the eventual failure of the signal conditioning electronics. Upgrading the Hazardous Area Oxymitter DR to a full Oxymitter 4000 or 5000 requires only the addition of a small electronics package to the exist­ing termination housing of the Hazardous Area Oxymitter DR probe. The converted unit will be a full Oxymitter 4000 or 5000 Oxygen Transmitter with the capability of providing a 4-20 mA oxygen signal with­out the need for an external signal condi­tioning electronics package. HART or Fieldbus communications are provided with the Oxymitter electronics. See Ap­pendix A for upgrade information.

1-3 PROBE OPTIONS

a. Abrasive Shield Assembly
Hazardous Area Oxymitter DR
36220005
Figure 1-3. Flame Arrestor Diffusion Assembly
tures from igniting unburned fuel in the stack. The ceramic diffusion assembly is also available with a dust seal for use with the abrasive shield assembly.
c. Flame Arrestor Snubber Diffusion
Assembly
The snubber diffusion assembly, Figure 1­4, is satisfactory for most applications. This element is also available with a dust seal for use with an abrasive shield.
The abrasive shield assembly, Figure 1-5, is a stainless-steel tube that surrounds the probe assembly. The shield protects against particle abrasion and condensa­tions, provides a guide for ease of insertion, and acts as a position support, especially for longer probes. The abrasive shield assembly uses a modified diffusor and vee deflector assembly, fitted with dual dust seal packing.
b. Flame Arrestor Ceramic Diffusion
Assembly
The flame arrestor ceramic diffusion as­sembly, Figure 1-3, includes a set of baf­fles between the cell and the stack gases. This keeps 816°C (1500°F) cell tempera-
1-4 Description and Specifications Rosemount Analytical Inc. A Division of Emerson Process Management
Figure 1-4. Flame Arrestor Snubber Diffusion
Assembly
36220006
Hazardous Area Oxymitter DR
1
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
2
.187 .187
1
B
A
o
15
3.584
3.554
A
.45 MIN
VIEW A
o
90
ON INSIDE BREAK FOR SMOOTH ROUNDED EDGE ON BOTH ENDS OF CHAMFER
125
.187
6.00
SKIN CUT FACE FOR 90
o
B
VIEW B
o
22.5
0.75 THRU 4 PLS,
EQ SP ON 4.75 B.C.
NOTES:
16860033
1 WELD ON BOTH SIDES WITH EXPANDING
CHILL BLOCK.
2 BEFORE WELDING, BUTT ITEM 2 OR 4 WITH
ITEM 1 AS SHOWN.
.745
DIA ON A 7.50 DIA B.C. (REF)
.755
Figure 1-5. Abrasive Shield Assembly
NOTE
In highly abrasive applications, rotate the shield 90 degrees at normal
service intervals to present a new wear surface to the abrasive flow stream.
Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 1-5
Instruction Manual
IB-106-340CDR Original Issue January, 2002
1-4 SPECIFICATIONS
Hazardous Area Certifications ............................ CENELEC EEXd IIB + H2 T3
Probe Lengths .................................................... 18 in. (457 mm)
Temperature Limits in Process
Measurement Area .................................. 0° to 704°C (32° to 1300°F)
Hazardous Area Oxymitter DR
CSA Class I, Division 1, Groups B, C, D
3 ft (0.91 m) 6 ft (1.83 m)
up to 1300°C (2400°F) with optional accessories
Resolution Sensitivity ......................................... 0.01% O
Sensing Cell Repeatability ................................. ±0.75% of O
transmitted signal
2
reading, or 0.05% O
2
2
System Response to Calibration Gas ................ Initial response in less than 3 seconds T90 in less than
8 seconds
Resolution Sensitivity ......................................... 0.01% of O
value
2
Mounting and Mounting Position ........................ Vertical or horizontal
Materials:
Probe ....................................................... Wetted or welded parts - 316L stainless steel
Non-wetted parts - 304 stainless steel, low-copper aluminum
Termination Housing ............................... Low-copper aluminum
Calibration Gas Mixtures Recommended .......... 0.4% O
8% O2, Balance N
, Balance N
2
2
2
Calibration Gas Flow .......................................... 2.5 l/m (5 scfh)
Optional Reference Air ....................................... 1 l/m (2 scfh), clean, dry, instrument-quality air
(20.95% O
), regulated to 34 kPa (5 psi), Optional
2
Heater Voltage ................................................... 115 ±10% VAC, 50/60 Hz., 200VA
Thermocouple .................................................... Type K
Power Requirements:
Nominal ................................................... 175 W
Maximum ................................................. 500 W
Ambient Operating Temperature
(Junction Box) .......................................... 93°C (200°F) [71°C (160°F) max
for YEW replacement]
Fisher-Rosemount has satisfied all obligations coming from the European legislation to harmonize the product requirements in Europe.
1-6 Description and Specifications Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
1
Table 1-1. Product Matrix
OXT4ACDR Explosion Proof Oxymitter DR In Situ Oxygen Transmitter
Explosion Proof Exchange Probe - Instruction Book
Code Sensing Probe Type
1 Ceramic Diffusion Element Probe (ANSI 3 in. 150 lbs) 2 Snubber Diffusion Element Probe (ANSI 3 in. 150 lbs) 3 Ceramic Diffusion Element Probe (DIN 2572) - 1/4 in. Tube Fittings 4 Snubber Diffusion Element Probe (DIN 2572) - 1/4 in. Tube Fittings 5 Ceramic Diffusion Element Probe (JIS) 6 Snubber Diffusion Element Probe (JIS)
Code Probe Assembly
0 18 in. (457 mm) Probe 1 18 in. (457 mm) Probe with 3 ft (0.91 m) Bypass 2 18 in. (457 mm) Probe with Abrasive Shield 3 3 ft (0.91 m) Probe 4 3 ft (0.91 m) Probe with Abrasive Shield 5 6 ft (1.83 m) Probe 6 6 ft (1.83 m) Probe with Abrasive Shield
(1)
(1)
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
(1)
Code Mounting Hardware - Stack Side
0 No Mounting Hardware (“0” must be chosen under “Mounting Hardware - Probe Side” below) 1 New Installation - Square weld plate with studs 2 Mounting to Model 218 Mounting Plate (with Model 218 Shield Removed) 3 Competitor’s Mount
(2)
Code Mounting Hardware - Probe Side
0 No Mounting Hardware 1 Probe Only (ANSI) (N. American Std.) 2 New Bypass or Abrasive Shield (ANSI) 4 Probe Only (DIN) (European Std.) 5 New Bypass or Abrasive Shield (DIN) 7 Probe Only (JIS) (Japanese Std.) 8 New Bypass or Abrasive Shield (JIS)
Code Filtered Customer Termination - NEMA 4X, IP66
11 Standard Filtered Termination 12 Transient Protected Filtered Termination
OXT4ADR 3 2 1 1 11 Example
HIGH SULFUR SERVICE
For high sulfur applications, please add an additional line item to your purchase order requesting high sulfur cell part number 4847B63G02 in lieu of the standard ZrO
cell.
2
Cell replacement kits for high sulfur service are also available.
NOTES:
(1)
Recommended usages: High velocity particulates in flue stream, installation within 11.5 ft (3.5 m) of soot blowers or heavy salt cake buildup. Applications: Pulverized coal, recovery boilers, lime kiln.
(2)
Where possible, specify SPS number; otherwise, provide details of the existing mounting plate as follows:
Plate with studs Bolt circle diameter, number, and arrangement of studs, stud thread, stud height above mounting plate.
Plate without studs Bolt circle diameter, number, and arrangement of holes, thread, depth of stud mounting plate with accessories.
Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 1-7
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Part
Number Description
1A99119G01 Two disposable calibration gas bottles — 0.4%
1A99119G02 Two flow regulators for calibration gas bottles
1A99119G03 Bottle rack
*Calibration gas bottles cannot be shipped via airfreight.
Hazardous Area Oxymitter DR
Table 1-2. Calibration Components
and 8% O
, balance nitrogen — 550 liters each*
2
1-8 Description and Specifications Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
2

INSTALLATION

The Hazardous Area Oxymitter DR and probe abrasive shield are heavy. Use proper lifting and carrying procedures to avoid personal injury.
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
SECTION 2
4. The sensing point should be selected so the process gas temperature falls within a range of 0° to 704°C (32° to 1300°F). Figure 2-1 through Figure 2-4 provide mechanical installation refer­ences. The ambient temperature of the termination housing must not exceed 65°C (149°F).
Before installing this equipment, read the “Safety instructions for the wiring and installation of this apparatus” at the front of this Instruction Bulletin. Failure to follow safety instructions could result in serious injury or death.
2-1 MECHANICAL INSTALLATION
If the probe will be installed into an existing lo­cation, proceed to paragraph 2-1b.
a. Selecting Location
1. The location of the Hazardous Area Oxymitter DR in the stack or flue is most important for maximum accuracy in the oxygen analyzing process. The Hazardous Area Oxymitter DR must be positioned so the gas it measures is representative of the process. Best re­sults are normally obtained if the Haz­ardous Area Oxymitter DR is positioned near the center of the duct (40-60% insertion).
5. Ducts and stacks that operate under negative pressure will draw air in through any holes or torn seals, sub­stantially affecting the oxygen reading. Therefore, either make the necessary repairs or install the Hazardous Area Oxymitter DR upstream of any leak­age.
6. Ensure the area is clear of internal and external obstructions that will interfere with installation and maintenance. Al­low adequate clearance for removal of the Hazardous Area Oxymitter DR (Figure 2-1).
b. Installation
1. Ensure all components are available to install the Hazardous Area Oxymitter DR. If equipped with the optional ce­ramic diffusion element, ensure it is not damaged.
2. The Hazardous Area Oxymitter DR may be installed intact as it is received.
2. Longer ducts may require several Haz­ardous Area Oxymitter DR units since the O
can vary due to stratification.
2
3. A point too near the wall of the duct, or the inside radius of a bend, may not provide a representative sample be­cause of the very low flow conditions.
Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-1
An abrasive shield is recommended for high velocity particulate in the flue stream (such as those in coal-fired boilers, kilns, and recovery boilers).
3. Weld or bolt adapter plate (Figure 2-4) onto the duct.
NOTE
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Hazardous Area Oxymitter DR
EARTH
EXTERNAL
LABEL
APPROVED
CERTIFICATION
AMBIENT WEATHER CONDITIONS
INSULATE IF EXPOSED TO
803
DIM "B"
EARTH
REF.
GAS
E
V
I
-
L
A
E
R
T
E
I
H
P
U
S
C
O
M
T
A
E
V
I
S
O
O
M
T
A
E
V
I
S
O
R
-
I
C
G
N
I
N
R
A
L
S
G
N
I
N
R
A
L
N
E
H
W
W
-
T
P
H
X
E
G
I
T
N
I
P
-
E
E
K
500VA
5 Amps
R
TM
HART
SMART FAMILY
800-433-6076 Orrville,OH 44667-0901
Rosemount Analytical Inc.
R
TM
4-20 mA
85-264VAC 48-62 Hz
OXYMITTER 4000
SERIAL NO.
VOLTS: WATTS:
TAG NO.
OUTPUT: LINE FUSE:
E
V
I
-
L
A
E
R
T
E
I
H
P
U
C
R
-
I
C
N
E
H
W
W
-
T
P
H
X
E
G
I
T
N
I
P
-
E
E
K
EXTERNAL
EARTH
INTERNAL
3/4 NPT
ELEC CONN
REF AIR
CAL GAS
ANSI ( ) TUBE6.35 1/4
DIN 6.35 (1/4) TUBE
460
DIM "A"
PROBE
TABLE 2 INSTALLATION/REMOVAL
6 mm TUBEJIS
305
(12)
2174
(31.6)
(18.1)
18 IN.
1448
917
3 FT
(85.6)
(57.0)
1831
(36.1)
(72.1)
6 FT
PATTERNS; AND ARE NOT PRESSURE RATED.
THESE FLAT FACED FLANGES ARE
MANUFACTURED TO ANSI, DIN, & JIS BOLT
ALL DIMENSIONS ARE IN MILLIMETERS
WITH INCHES IN PARENTHESES UNLESS
OTHERWISE NOTED.
167
(6.58)
39
73
(1.55)
(2.89)
COVER REMOVAL & ACCESS
305
(12)
NOTES:
0.062 IN. THK GASKET
PROCESS FLOW MUST BE IN
THIS DIRECTION WITH RESPECT
TO DEFLECTOR 3534B48G01
CAL.
GAS
DIM "B"
343 (13.5)
REMOVAL ENVELOPE
BOTTOM VIEW
VENT
REF. AIR
66
(2.6)
WITH
DIM "A"
SNUBBER
76
(3.0)
DIFFUSER
210
DIN
(8.25)
18 (.71)
170
(6.69)
95 (3.8)
(GASKET INCLUDED)
ADD TO DIM “A
FOR PROBE WITH
CERAMIC DIFFUSER
TABLE 1 MOUNTING FLANGE
ANSI
190
FLANGE
(7.5)
152.4
(6.00)
19 (.75)
HOLE DIA
DIA
(4) HOLES
EQ SP
ON BC
35910002
Figure 2-1. Hazardous Area Oxymitter DR Installation
2-2 Installation Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
2
E
R
E
H
P
S
O
M
-
T
G
A
N
I
N
E
R
V
A
I
W
S
O
-
L
P
X
E
343
(13.50)
"B"
VAL ENVELOPE
DIM
O
REM
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
E
V
I
-
L
A
T
I
U
C
R
I
C
N
E
H
W
T
H
G
I
T
N
I
P
-
E
E
K
3/4 NPT ELECTRICAL CONNECTION
1/4 IN. TUBE
1/4 IN. TUBE
6 mm TUBE
CAL.
GAS
CAL GAS*
*ADD CHECK VALVE IN CAL GAS LINE
ANSI
DIN
JIS
REF AIR
THESE FLAT FACED FLANGES ARE MANUFACTURED TO ANSI, DIN, & JIS BOLT
NOTES:
24
190
(0.94)
(9.25)
(9.25)
(9.00)
DIA
(7.48)
19
190
(0.75)
(7.48)
19
190
(0.75)
(7.50)
EQ SP
ON BC
HOLE
DIA
(8) HOLES
178
235
DIN
-3D39003
JIS
235
229
TABLE 4 ABRASIVE SHIELD
ANSI
FLANGE
FLANGE
(7.00)
INAL
NOM
91 (3.6) DIA
"A"
DIM
Y BL
99
PATTERNS AND NOT PRESSURE RATED.
ALL DIMENSIONS ARE IN MILLIMETERS WITH INCHES IN PARENTHESES.
(3.9)
ASSEM
5
SNUBBER/DUST SEAL
(0.2)
SEAL ASSY
DIFFUSER/DUST
DEFLECTOR ASSY
VAL O
TABLE 3 INSTALLATION/REM
"B"
DIM
DIM "A"
PROBE
912
387
1367
2287
(53.8)
(90.0)
(35.9)
843
1762
(69.4)
(33.2)
(15.3)
18 IN
3 FT
6 FT
35910003
Figure 2-2. Hazardous Area Oxymitter DR with Abrasive Shield
Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-3
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Hazardous Area Oxymitter DR
OXYMITTER 4000 WITH ABRASIVE SHIELD
TABLE VI. MOUNTING PLATE DIMENSIONS FOR HAZARDOUS AREA
JIS
DIN
ANSI
(in.)
"A"
MM
DIMENSIONS
235
235
229
(9.25)
(9.25)
(9.00)
125
100
121
"B"
(4.92)
(3.94)
(4.75)
DIA
M16x2
M20 x 2.5
0.625-11
"C"
THREAD
200
190
191
"D"
(7.89)
(7.48)
(7.50)
DIA B.C.
TO PROVIDE ADDITIONAL
CROSSHATCHED AREA IN
4 CORNERS MAY BE USED
o
22.5
WALL SURFACE.
OF PLATE TO OUTSIDE
HOLES FOR FIELD BOLTING
8 THREADED HOLES
EQUALLY SPACED ON
A
D DIA B.C.
ABRASIVE SHIELD
FLANGE O.D.
A
C
MOUNTING PLATE FOR
WITH ABRASIVE SHIELD
B
HAZARDOUS AREA OXYMITTER DR
MOUNTING PLATE OUTLINE
HAZARDOUS AREA OXYMITTER DR
TABLE V. MOUNTING PLATE DIMENSIONS FOR
DIN
ANSI
MM
(in.)
DIMENSIONS
216
197
"A"
(8.50)
(7.75)
M16x2
0.625-11
"B"
STUD SIZE
170.0
(6.69)
152.4
(6.00)
“C"
DIA B.C.
A
WITH INCHES IN PARENTHESES.
NOTE: DIMENSIONS ARE IN MILLIMETERS
82.6
C
(3.25) DIA
Figure 2-3. Hazardous Area Oxymitter DR Adapter Plate Dimensions
4 STUDS,
LOCKWASHERS AND
NUTS EQUALLY
SPACED ON
C DIA B.C.
B
MOUNTING PLATE FOR
HAZARDOUS AREA OXYMITTER DR
36220002
2-4 Installation Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
2
INSTALLATION FOR METAL
WALL STACK OR DUCT
CONSTRUCTION
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
INSTALLATION FOR MASONRY
WALL STACK CONSTRUCTION
MTG HOLES SHOWN ROTATED
o
45 OUT OF TRUE POSITION
WELD OR BOLT MOUNTING PLATE TO METAL WALL OF STACK OR DUCT. JOINT MUST BE AIRTIGHT.
13 (0.50)
95 (3.75)
MIN DIA HOLE IN WALL
STACK OR DUCT METAL WALL
WITH ABRASIVE SHIELD
BOLT MOUNTING
PLATE TO OUTSIDE
WALL SURFACE
FIELD WELD
MOUNTING PLATE
MTG HOLES
SHOWN ROTATED
o
45 OUT OF
TRUE POSITION
JOINT MUST
BE AIRTIGHT
OUTSIDE WALL
SURFACE
NOTE: ALL MASONRY STACK WORK AND JOINTS EXCEPT
ADAPTOR PLATE NOT FURNISHED BY ROSEMOUNT.
PIPE TO
13 (0.50)
114 (4.50) O.D. REF
PIPE 4.00 IN. SCHED 40 PIPE SLEEVE (NOT BY ROSEMOUNT) LENGTH BY CUSTOMER
MASONRY STACK WALL
WITHOUT ABRASIVE SHIELD
82.5 (3.25)
WELD OR BOLT MOUNTING PLATE TO METAL WALL OF STACK OR DUCT. JOINT MUST BE AIRTIGHT.
MIN DIA HOLE IN WALL
STACK OR DUCT METAL WALL
NOTE: DIMENSIONS IN MILLIMETERS WITH
BOLT MOUNTING
PLATE TO OUTSIDE
WALL SURFACE
JOINT MUST
BE AIRTIGHT
OUTSIDE WALL
SURFACE
INCHES IN PARENTHESES.
FIELD WELD PIPE TO MOUNTING PLATE
102 (4.0) O.D. REF
PIPE 3.5 IN. SCHED 40 PIPE SLEEVE (NOT BY ROSEMOUNT) LENGTH BY CUSTOMER
MASONRY STACK WALL
36220007
Figure 2-4. Hazardous Area Oxymitter DR Adapter Plate Installation
Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-5
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Hazardous Area Oxymitter DR
4. If using the optional ceramic diffusion element, the vee deflector must be cor­rectly oriented. Before inserting the Hazardous Area Oxymitter DR, check the direction of gas flow in the duct. Ori­ent the vee deflector so the apex points upstream toward the flow (Figure 2-5). This may be done by loosening the setscrews and rotating the vee deflector to the desired position. Retighten the setscrews.
5. In vertical installations, ensure the sys­tem cable drops vertically from the Haz­ardous Area Oxymitter DR and the conduit is routed below the level of the termination housing. This drip loop minimizes the possibility that moisture will damage the electrical connections (Figure 2-6).
GAS FLOW DIRECTION
VEE
DEFLECTOR
APEX
DIFFUSION
FILTER
ELEMENT
SETSCREW
DEFLECTOR
VEE
22220020
Figure 2-5. Orienting the Optional Vee Deflector
LINE
VOLTAG E
OXYGEN, THERMOCOUPLE SIGNAL
REPLACE INSULATION
AFTER INSTALLING HAZARDOUS AREA
OXYMITTER DR
INSULATION
ADAPTER
Figure 2-6. Installation with Drip Loop and Insulation Removal
PLATE
E
V
I
-
L
A
E
R
T
E
I
H
P
S
O
-
M
T
G
A
N
I
N
E
R
V
A
I
W
S
O
L
P
U
C
R
I
C
N
E
H
-
X
E
W
T
H
G
I
T
N
I
P
-
E
E
K
DRIP LOOP
CAL.
GAS
STACK OR DUCT METAL WALL
36210007
2-6 Installation Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
2
6. If the system has an abrasive shield, check the dust seal gaskets. The joints in the two gaskets must be staggered 180°. Also, make sure the gaskets are in the hub grooves as the Hazardous Area Oxymitter DR slides into the 15° chamfer in the abrasive shield.
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
Disconnect and lock out power before connecting the unit to the power supply.
NOTE
If process temperatures will exceed 200°C (392°F), use anti-seize com­pound on stud threads to ease future removal of Oxymitter DR.
7. Insert probe through the opening in the mounting flange and bolt the unit to the flange.
NOTE
To maintain CE compliance, ensure a good connection exists between the mounting plate studs or earthing screws on termination housing and earth.
8. Ensure the Hazardous Area Oxymitter DR is properly earthed by way of both internal and external points.
9. If insulation is being removed to access the duct work for Hazardous Area Oxymitter DR mounting, make sure the insulation is replaced afterward (Figure 2-6).
Install all protective equipment covers and safety ground leads after installa­tion. Failure to install covers and ground leads could result in serious injury or death.
To meet the Safety Requirements of IEC 1010 (EC requirement), and ensure safe operation of this equipment, con­nection to the main electrical power supply must be made through a circuit breaker (min 10 A) which will discon­nect all current-carrying conductors during a fault situation. This circuit breaker should also include a me­chanically operated isolating switch. If not, then another external means of disconnecting the supply from the equipment should be located close by. Circuit breakers or switches must comply with a recognized standard such as IEC 947.
10. Ensure the installation does not obscure the messages on either housing cover.

2-2 ELECTRICAL INSTALLATION

All wiring must conform to local and national codes.
Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-7
The Hazardous Area Oxymitter DR and probe abrasive shield are heavy. Use proper lifting and carrying procedures to avoid personal injury.
a. Remove screw (11, Figure 4-1), captive
washer (13), and cover lock (12). Remove left housing cover (10).
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Hazardous Area Oxymitter DR
HEATER
POWER
THERMOCOUPLE
TYPE K
SIGNAL
OXYGEN
SIGNAL
LEFT SIDE OF
OXYMITTER DR
b. Connect Heater Power
Connect the heater power lines to the two terminals indicated in (Figure 2-7).
c. Connect O
and Heater Thermocouple
2
Signals
TERMINAL
BLOCK
+
-
+
-
Figure 2-7. Terminal Block
Instrument Air (Reference Air): 68.95 kPag (10 psig) minimum, 1551.38 kPag (225 psig) maxi­mum at 56.6 L/hr (2 scfh) maximum; less than 40 parts-per-million total hydrocarbons. Regu­lator outlet pressure should be set at 35 kPa (5 psi).
HEATER POWER
PORT
GROUND LUGS
SIGNAL
PORT
36210002
1. Oxygen Signal. Connect the oxygen signal lines from the signal conditioning electronics to the terminals shown in Figure 2-7.
2. Heater Thermocouple Signal. Connect the type K thermocouple signal lines from the signal conditioning electronics to the terminals indicated in Figure 2-7.
d. Install left housing cover (10, Figure 4-1)
and secure with cover lock (12), captive washer (13), and screw (11).

2-3 PNEUMATIC INSTALLATION

If instrument air will be used as reference air (see System Considerations, paragraph 1-2f), connect the reference air set to the Hazardous Area Oxymitter DR. The reference air set should be installed in accordance with Figure 2-8.
NOTE
!
Upon completing installation, make sure that the Hazardous Area Oxymit­ter DR is turned on and operating prior to firing up the combustion process. Damage can result from having a cold Hazardous Area Oxymitter DR ex­posed to the process gases.
During outages, and if possible, leave all Hazardous Area Oxymitter DR units running to prevent condensation and premature aging from thermal cycling.
If the ducts will be washed down dur­ing outage, MAKE SURE to power down the Hazardous Area Oxymitter DR units and remove them from the wash area.
2-8 Installation Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
2
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
4.81 (122.17)
FLOW SET
POINT KNOB
0.125-27 NPT FEMALE
OUTLET CONNECTION
1
0.250 OR 6 MM O.D.
TUBE COMPRESSION
FITTING
Rosemount Analytical Inc. Orrville,OH 44667-0901
800-433-6076
TM
OXYMITTER DR SERIAL NO. TAG NO.
0.250 OR 6 MM O.D. TUBING (SUPPLIED BY CUSTOMER)
2
OUTLET
1.19 (30.22)
DRAIN VALVE
10.0
(254)
REF
TO ELECTRONICS
3
REF AIR SET
263C152G01
3.12 (79.25) MAX
2.250 (57.15)
0.25-18 NPT FEMALE INLET CONNECTION
2.0
(50.80)
1.50
(38.10)
1 FLOWMETER 0.2-2.0 SCFH 771B635H02
2 2" PRESSURE GAGE 0-15 PSIG 275431-006
3 COMBINATION FILTER-REG. 0-30 PSIG 4505C21G01
NOTE: DIMENSIONS ARE IN INCHES WITH
2 MOUNTING HOLES
3.19 (81.03) LG
THROUGH BODY FOR
0.312 (7.92) DIA BOLTS
INSTRUMENT AIR SUPPLY 10-225 PSIG MAX PRESSURE
MILLIMETERS IN PARENTHESES.
8.50
(215.90)
MAX
SCHEMATIC HOOKUP FOR REFERENCE AIR SUPPLY ON OXYMITTER DR PROBE HEAD.
Install all protective equipment covers and safety ground leads before equipment startup. Failure to install covers and ground leads could result in serious injury or death.
2-4 SYSTEM SETUP
a. Overview
This section covers the setup procedures for the Oxymitter DR In-Situ Oxygen Probe. The DR probe can be used with several electronics packages including: Models 218, 218A, 225, 132 (analog and digital), TC200, and ZA8C.
For Westinghouse Models 218, 225, and 132 (analog), refer to paragraph 2-4b. Addi-
36210008
Figure 2-8. Air Set, Plant Air Connection
tional information can be found in IB-106-
101.
For Westinghouse Model 218A, refer to paragraph 2-4c. Additional information can be found in IB-106-101A.
For Westinghouse Model TC200, refer to paragraph 2-4d. Additional information can be found in IB-107-020.
For Westinghouse Model 132 (digital), refer to paragraph 2-4e. Additional information can be found in IB-106-106A.
For Rosemount World Class 3000, refer to paragraph 2-4f. Additional information can be found in IB-106-300NFX.
For Yokogawa Model ZA8C, refer to para­graph 2-4g.
Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-9
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Hazardous Area Oxymitter DR
b. WESTINGHOUSE MODELS 218, 225,
AND 132 (ANALOG) ELECTRONICS SETUP
Before beginning operation, it is important that the probe heater setpoint of the existing electronics be changed to support the Haz­ardous Area Oxymitter DR In-Situ Oxygen Probe. The setpoint adjustment procedure required for Models 218, 225, and 132 analog electronics is as follows:
1. Open electronics enclosure.
2. On temperature controller card, Figure 2-9, connect jumper wire from TP3 to either Pin 2 or Pin 7.
3. Set voltmeter to read DC millivolts (MV).
4. Attach voltmeter with positive (+) lead on TP1 and negative (-) on either Pin 2 or 7.
TP3
5. Adjust potentiometer M110-1 to read -
322.3 millivolts nominal.
6. Remove voltmeter leads.
7. Remove jumper wire.
TP1
M110-1
NOTE
The voltage given above is for an am­bient (machinery space) temperature of 25°C (77°F). For each degree of am­bient temperature above or below 25°C (77°F), add or subtract 0.242 mV from the nominal. Example: at 31°C (87°F), the nominal voltage of -322.3 Mv should be increased (made less nega­tive) by 10 x 0.242 or 2.42 mV, making the adjusted nominal -319.9 Mv.
PIN 2 (PSC)
23 567 1012
PIN 7 (PSC)
P0019
Figure 2-9. Temperature Controller Card
Calibration Points
2-10 Installation Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
2
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
c. WESTINGHOUSE MODEL 218A ELEC-
TRONICS SETUP
Before beginning operation, it is important that the probe heater setpoint of the existing electronics be changed to support the Haz­ardous Area Oxymitter DR probe. To con­vert the Model 218A Digital Electronics Package for use with the DR probe, an EPROM change is necessary. Remove Main PCB and check back of board to iden­tify unit as G02 or G04. The replacement EPROM needed is as identified below:
G02 G04
United States 1M03192G01 1M02982G01
United Kingdom 1M03192G02 1M02982G02
Germany 1M03192G03 1M02982G03
France 1M03192G04 1M02982G04
Italy 1M03192G05 1M02982G05
NOTE
The replacement EPROM when using a multiprobe averager unit is 1M02982G10.
To replace the EPROM, proceed as follows:
1. Shut off and lock out power to the electronics package.
2. Open electronics enclosure.
3. On the Main PCB, Figure 2-10, locate and remove old EPROM.
4. Replace with new EPROM.
5. Close electronics enclosure and power up system.
EPROM
MAIN PCB
Figure 2-10. Main PCB (Model 218A) EPROM Replacement
Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-11
P0020
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Hazardous Area Oxymitter DR
d. WESTINGHOUSE MODEL TC200 VERI-
TRIM ELECTRONICS SETUP
Before beginning operation, it is important that the probe heater setpoint of the existing electronics be changed to support the Haz­ardous Area Oxymitter DR In-Situ Oxygen Probe. To convert the Model TC200 Elec­tronics Package for use with the DR probe, an EPROM change is necessary. The re­placement EPROM needed is part number 1M03154G02.
1. EPROM replacement. To replace the EPROM, proceed as follows:
(a) Shut off and lock out power to the
electronics package.
(b) Open electronics enclosure.
(c) On the main PCB, Figure 2-11, lo-
cate and remove old EPROMs U11 and U12.
(d) Replace with new EPROMs (part
number 1M03154G02) being careful to install U11 and U12 in their proper locations.
2. Heater Setpoint Adjustment. The ad­justment procedure required for the Model TC200 Electronics Package is as follows:
(a) Open keylocked enclosure to ac-
cess membrane keyboard.
(b) Put controller in PAR (parameter)
mode by depressing "LOCK" "▲" "%O2" "INC" "ACK" in sequence.
(c) Depress "ACK" pushbutton to clear
display.
(d) Press "NUM" pushbutton.
(e) Using "INC", "DEC" buttons, dis-
play parameter 125.
(f) Press "VAL" button.
(g) Using "INC", "DEC" buttons,
change parameter 125 value to
15.4.
(h) Press "ENT" to save new value.
(e) Close electronics enclosure and
power up system.
2-12 Installation Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
2
DIS A/M
EPROMS
U11 AND U12
U12
U11
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
Figure 2-11. Main PCB (Model TC200) EPROM Replacement
P0021
Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-13
Instruction Manual
IB-106-340CDR Original Issue January, 2002
e. WESTINGHOUSE MODEL 132 DIGITAL
ELECTRONICS SETUP
Hazardous Area Oxymitter DR
To replace the EPROM, proceed as follows:
Before beginning operation, it is important that the probe heater setpoint of the existing electronics be changed to support the Haz­ardous Area Oxymitter DR In-Situ Oxygen Probe. To convert the Model 132 Digital Electronics Package for use with the DR probe, an EPROM change is necessary. The replacement EPROM needed is as identified below:
United States IM03222G01
R38
TP1
EPROM
R8
U2
C48
U1
C37
LM8
03
P61
U7
C44
R27
XT1
C26
C27
C38
R38
C29
C28
04
R12
U6
U4
C30
C29
R26
P25
P36
CR25
C13
D12
O18
1
C46
P28
LED1
U9
R41
RP1
TP2
C24
D14
C23
D13
C14
D1
C16
D2
MAIN PCB
J1
08
R63
R62
R54
R53
U13
R48
C22
C21
C12
C13
C10
C34
M55
CR18
CR17
R48
C39
20
C31
U10
C43
C42
R42
CR15
CR16
CR24
R36
CR13
CR14
CR12
CR11
R37
R86
CR18
R68
U3
09
C41
R64
BR1
1. Shut off and lock out power to the electronics package.
2. Open electronics enclosure.
3. On the Main PCB, Figure 2-12, locate and remove old EPROM.
4. Replace with new EPROM.
5. Close electronics enclosure and power up system.
TX2
C38
R56
CR19
C30
R44
R49
R47
U14
R43
R38
R61
P22
P29
C86
C10
U12
C16
U2
C32
TR1
TX1
C36
C11
R46
R48
P62
C7
C9
U11
C8
R6
C48
C4
C3 C8
C47
C1
C2
C3
R9
2001A
F2
2001A
CK1
F1
C7
I
R58
R57
R59
P68
U19
U17
R18
R16
R17
R19
U16
R11
R18
CR3
CR4
U18
R4
R5
CR1
CR2
CR21
CR22
08
A
28
28
R16
28
C46
CR7
CR6
CR8
CR5
28
28
LK2
28
R7
R6
R14
R23
R28
LK1
CR20
CR23
5A
F3
5A
F4
28
28
C17
R2
R1
R21
R13
R24
FIL1
R1
CR9
R81
ALARM
MTR-T/C CELL SKG STK-T/C ML-O/P
T83
C11
T82
OFF
N
L
HEATER
E
E
N
MAIN INPUT
L
T81
SW1
MOV1
MOV2
ON
P0022
Figure 2-12. Main PCB (Model 132) EPROM Replacement
2-14 Installation Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
2
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
f. WORLD CLASS 3000 INTELLIGENT
FIELD TRANSMITTER SETUP
The DR probe operates with a 115 VAC heater. Ensure that the voltage selection jumpers in the IFT or HPS, if used, are set
CONFIGURATION
LINE VOLTAGE
SELECTION
100 V.A.C.
120 V.A.C.
220 V.A.C.
240 V.A.C.
JUMPER
(INSTALL)
JM3, JM7, JM2
JM8, JM7, JM1
JM6, JM5, JM2
JM6, JM5, JM1
Figure 2-13. IFT 3000 Power Supply Board Jumper Configuration
JUMPER
WORLD CLASS PROBE (44V)
REPLACEMENT" PROBE (115V)
REPLACEMENT PROBE (115V)
ALWAYS DISCONNECT LINE VOLTAGE FROM INTELLIGENT FIELD TRANSMITTER BEFORE CHANGING JUMPERS.
PROBE HEATER
VOLTAGE SELECTION
218 PROBE (115V)
WORLD CLASS "DIRECT
OR OXYMITTER DIRECT
properly. Refer to Figure 2-13 for IFT jumper selection, and Figure 2-14 for HPS jumper selection. For additional setup and configuration information, refer to IB-106­300NFX.
JUMPER
(INSTALL)
JM10
JM9
JM9
36210015
If incorrect heater voltage is selected, damage to the Oxymitter DR may occur. Refer to IB-106-300NFX for additional configuration information. Always update the relevant labeling to reflect the set voltage.
ALWAYS DISCONNECT LINE VOLTAGE FROM HEATER POWER SUPPLY AND ANALOG ELECTRONICS (IF USED) BEFORE CHANGING JUMPERS.
HEATER
POWER
REMOTE
ON
ELECTRONICS
SELECTION
*ANALOG (EXISTING)
DIGITAL
(NEXT GENERATION)
JUMPER
REMOVE JM2
*INSTALL JM2
JUMPER
INSTALL JM3, JM6
REMOVE JM3, JM6
36210014
LINE VOLTAGE
SELECTION
1
100/120 V.A.C.
220/240 V.A.C.
PROBE HEATER
VOLTAGE SELECTION
WORLD CLASS PROBE
DIRECT REPLACEMENT
(44V)
218 PROBE (115V)
WORLD CLASS OR
DR OXYMITTER
NOTES:
1
JUMPER
CONFIGURATIONS
JUMPER
(INSTALL)
JM4, JM1
JM5
JUMPER
(INSTALL)
JM7
JM8
JM8
100 V.A.C. OPERATION REQUIRES TRANSFORMER PART NUMBER 1M02961G02.
Figure 2-14. Heater Power Supply (HPS 3000) Jumper Configuration
Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-15
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Hazardous Area Oxymitter DR
g. THE YOKOGAWA ZA8C AND AV8C
CONVERTER ELECTRONICS SETUP
The Hazardous Area Oxymitter DR probe can be wired to work with the Yokogawa®
ZA8C
OR
AV8C
TERMINAL
} } }
3+
4–
5+
6–
7+
8–
16
17
THERMOCOUPLE
32
ZA8C OR AV8C
GND SHIELD
CELL
COLD
JUNCTION
PROBE
HEATER
ZA8C and AV8C Converters. Connect the cabling from the ZA8C or AV8C terminal to the probe terminal in the junction box as shown in Figure 2-15.
COLD
JUNCTION
DEVICE
+
+
+
-
-
ZA8C
OR
AV8C
CONVERTER
HEATER AND SIGNAL CABLE
OXYMITTER DR PROBE
WITH ADAPTER FLANGE
NOTES: 1. HEATER TEMPERATURE SET TO 1380 F (750 C)
2.
THE GREATER MASS OF THE OXYMITTER DIRECT REPLACEMENT PROBE REQUIRES LONGER TIME TO HEAT UP. UPON STARTUP, THE YOKOGAWA ELECTRONICS MAY
INDICATE AN ERROR BECAUSE THE PROBE HAS NOT REACHED TEMPERATURE SETPOINT IN THE NORMAL TIME. REMOVE POWER FROM THE YOKOGAWA ELECTRONICS OR PROBE MODULE TO CLEAR THE ERROR, AND RESTORE POWER. THIS PROCEDURE MAY HAVE TO BE REPEATED A COUPLE OF TIMES BEFORE PROBE OPERATING TEMPERATURE IS REACHED.
oo
Figure 2-15. DR Probe Wired to the ZA8C or A V8C Converter
SHIELD
STACK WALL
EXISTING
MOUNTING
36210009
2-16 Installation Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
3

STARTUP AND OPERATION

Install all protective equipment covers and safety ground leads before equipment startup. Failure to install covers and ground leads could result in serious injury or death.
3-1 GENERAL
For startup and operation instructions, refer to the Instruction Bulletin provided with your elec­tronics package.
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
SECTION 3
Rosemount Analytical Inc. A Division of Emerson Process Management Startup and Operation 3-1
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Hazardous Area Oxymitter DR
3-2 Startup and Operation Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
4

MAINTENANCE AND SERVICE

Instruction Manual
IB-106-340CDR Original Issue
January, 2002
SECTION 4
When working on this equipment on the laboratory bench, be aware that the probe, probe tube, and flame arre­stor hub can be hot [up to 370°C (698°F)] in the region of the probe heater.
Install all protective equipment covers and safety ground leads after equip­ment repair or service. Failure to in­stall covers and ground leads could result in serious injury or death.
4-1 OVERVIEW
This section identifies the calibration methods available and provides the procedures to main­tain and service the Hazardous Area Oxymitter DR.
4-2 CALIBRATION
The Hazardous Area Oxymitter DR should be calibrated when commissioned. Under normal circumstances the probe will not require fre­quent calibration. When calibration is required, follow the procedure described in the Instruction Bulletin applicable to your electronics package.
It is recommended that the Hazardous Area Oxymitter DR be removed from the stack for all service activities. Wear heat resistant gloves and cloth­ing to remove probe from stack. Nor­mal operating temperature of diffusor and vee deflector are approximately 316 to 472°C (600 to 800°F). The unit should be allowed to cool and be taken to a clean work area. Failure to comply may cause severe burns.
Disconnect and lock out power before working on any electrical components. There is voltage up to 115 VAC.
4-3 HAZARDOUS AREA OXYMITTER DR
REPLACEMENT
a. Remove.
1. Turn off power to the system.
2. Shut off the calibration gases at the cylinders and the instrument air.
3. Disconnect the calibration gas and in­strument air lines from the Hazardous Area Oxymitter DR.
4. While facing the Hazardous Area Oxymitter DR and looking at the Rosemount label, remove screw (11, Figure 4-1), captive washer (13) and cover lock (12) securing left housing cover (10). Remove the cover to ex­pose the terminal block (Figure 4-2).
5. Loosen the screw on the heater termi­nal cover and slide the cover back to access the heater terminals. Loosen the heater terminal screws and remove the leads. Loosen the ground lug screws and remove the leads. Slide the heater power leads out of the heater power port.
6. Loosen the oxygen and heater thermo­couple signal terminal screws. Remove the leads from the terminals and slide the wires out of the signal port.
7. Remove insulation to access the mounting bolts. Unbolt the Hazardous Area Oxymitter DR from the stack and take it to a clean work area.
Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 4-1
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Hazardous Area Oxymitter DR
Note: Not all parts shown.
28
31
5
6
4
2
13
12
11
3
14
15
1
27
22
23
24
25
22
23
24
25
7
Integral Electrical
Barrier/Feedthrough
16
22
23
17
24
9
8
10
11
1. Right Housing Cover
2. Connecting Cable - Heater
3. Connecting Cable - Signal
4. Termination Housing
5. Screw
12
6. Lock Washer
13
7. Cable Clamp
8. Terminal Block
9. Captive Screw
10. Left Housing Cover
11. Screw
12. Cover Lock
13. Captive Washer
14. Washer
15. Screw
16. Probe Tube Assembly
17. Gasket
18. Corrugated Seal
19. Cell and Flange Assembly
20. Retainer Screw
21. Flame Arrester with Snubber Diffuser
22. Tube Nut (Inside Finned Housing)
23. Capillary Breather Tube
24. Gas Port
25. Cap
26. Tube Nut
27. O-ring
28. Strut Pressure Clamp
29. Heater Strut Assembly
30. Tube Clamp
31. Silicon Tube
18
19
20
21
29
30
26
36220004
Figure 4-1. Hazardous Area Oxymitter DR Exploded View
4-2 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
4
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
HEATER
POWER
+
THERMOCOUPLE
TYPE K
SIGNAL
OXYGEN
SIGNAL
LEFT SIDE OF
OXYMITTER DR
-
+
-
Figure 4-2. Terminal Block
8. Allow the unit to cool to a comfortable working temperature.
TERMINAL
BLOCK
HEATER POWER
PORT
GROUND LUGS
SIGNAL
PORT
36210002
6. Turn on the calibration gases at the cylinders and turn on instrument air.
b. Install.
1. Bolt the Hazardous Area Oxymitter DR to the stack and install insulation.
2. Insert the oxygen and heater thermo­couple signal leads in the signal port and connect to the oxygen and heater thermocouple screw terminals (Figure 4-2).
3. Insert the heater power leads in the heater power port and connect to the heater screw terminals. Slide the heater terminal cover over the terminal connection and tighten the cover screw.
4. Install left housing cover (10, Figure 4-1) and ensure it is tight. Se­cure the cover using cover lock (11), captive washer (13), and screw (12).
5. Connect the calibration gas and in­strument air lines to the Hazardous Area Oxymitter DR.
7. Restore power to the system.
Opening the termination housing will cause the loss of ALL hazardous per­mits. Opening the termination housing in hazardous areas may cause an ex­plosion resulting in loss of property, severe personal injury, or death. It may be required to get a hot work permit from your company safety offi­cer before opening the electronic housing.

4-4 TERMINAL BLOCK REPLACEMENT

Refer to Figure 4-2 and perform the following procedure to replace the terminal block.
a. Loosen the mounting screws on the termi-
nal block and carefully lift the block out of the housing.
Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 4-3
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Hazardous Area Oxymitter DR
b. Carefully align the new terminal block on
the pins so that it sits flat in the housing. The round end of the terminal block should be on the opposite side of the housing con­duit ports and should not be able to rotate.
c. Tighten the three mounting screws and en-
sure the terminal block is secure in the housing.
Opening the termination housing will cause the loss of ALL hazardous per­mits. Opening the termination housing in hazardous areas may cause an ex­plosion resulting in loss of property, severe personal injury, or death. It may be required to get a hot work permit from your company safety offi­cer before opening the electronic housing.

4-5 ENTIRE PROBE REPLACEMENT

Do not attempt to replace the probe until all other possibilities for poor performance have been considered. If probe replacement is needed, see Table 7-1 for part numbers.
a. Follow the instructions in paragraph 4-3a to
remove the Hazardous Area Oxymitter DR from the stack or duct.
b. Remove four screws (15, Figure 4-1) and
washers (14). Separate the electrical con­nectors between the heater strut assembly and the electrical barriers on the termination housing. The probe and termination housing can now be separated.
c. When installing the new probe, make sure
that o-ring (27) is in good condition. Con­nect the two electrical connectors between the heater strut and the electrical barrier on the termination housing. Make sure the conduit port of the termination housing is on the same side as the CAL and REF gas ports.
e. Replace the housing cover (20) and ensure
it is tight.
f. Follow the instructions in paragraph 4-3b to
install the Hazardous Area Oxymitter DR into the stack or duct.

4-6 HEATER STRUT REPLACEMENT

This paragraph covers heater strut replacement. Do not attempt to replace the heater strut until all other possibilities for poor performance have been considered. If heater strut replacement is needed, order a replacement heater strut (Table 7-1).
Use heat resistant gloves and clothing when removing probe. Do not attempt to work on the probe until it has cooled to room temperature. The probe can be as hot as 800°F (427°C). This can cause severe burns.
a. Follow the instructions in paragraph 4-3a to
remove the Hazardous Area Oxymitter DR from the stack or duct.
b. Remove four screws (15, Figure 4-1) and
washers (14). Separate the electrical con­nectors between the heater strut assembly and the electrical barriers on the termination housing. The probe and termination housing can now be separated.
c. Once the probe and termination housing are
separated, spring tension releases and the heater strut moves up. Carefully remove the CAL and REF gas silicon tubes by pulling them off the CAL and REF gas ports. Pull the silicon tubes off the CAL and REF gas lines.
d. Remove pressure clamp (28).
e. Remove tube nuts (26), and capillary
breather tubes (23) from the CAL, REF, and VENT ports.
d. Install the four washers (14) and screws
(15) and tighten.
4-4 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
4
V-DE FL EC TOR
CERAMIC
DIFFUSER
ASSEMBLY
CELL FLANGE
CERAMIC SUPPORT ROD
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
WIRE LOOP
HEATER
Figure 4-3. Heater Strut Assembly
f. Grasp the wire loop and carefully slide the
strut out of the probe tube (Figure 4-3).
g. When replacing the strut, align the slot on
the heater plate with the calibration gas line in the probe tube. Slide the strut into the probe tube. It will turn to align the hole on the back plate of the strut with the calibra­tion gas line. When the hole and the cali­bration gas line are aligned correctly, the strut will slide in the rest of the way.
h. Push down on the back plate of the strut to
make sure you have spring tension and then install the pressure clamp (28) on the back plate.
i. Install capillary breather tubes (23) and tube
nuts (26) on the CAL, REF, and VENT ports.
j. Replace the CAL and REF gas silicon
tubes.
k. Install the termination housing per the in-
27540007
structions in paragraph 4-5 steps c through e.
l. Follow the instructions in paragraph 4-3b to
install the Hazardous Area Oxymitter DR into the stack or duct.

4-7 CELL REPLACEMENT

This paragraph covers oxygen sensing cell re­placement. Do not attempt to replace the cell until all other possibilities for poor performance have been considered. If cell replacement is needed, order the cell replacement kit (Table 7-1).
The cell replacement kit (Figure 4-4) contains a cell and flange assembly, corrugated seal, setscrews, socket head cap screws, and anti­seize compound. The items are carefully pack­aged to preserve precise surface finishes. Do not remove items from the packaging until they are ready to be used. Spanner wrenches and hex wrenches needed for this procedure are part of an available special tools kit (Table 7-1).
Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 4-5
Instruction Manual
IB-106-340CDR Original Issue January, 2002
PROBE TUBE
(NOT INCLUDED
IN KIT)
CORRUGATED
CALIBRATION GAS
PASSAGE
SEAL
CELL AND
FLANGE
ASSEMBLY
SOCKET HEAD
CAP SCREWS
Hazardous Area Oxymitter DR
The flame arrestor and flame arrestor hub are among the critical compo­nents of this type of protection.
b. If the probe uses the standard diffusion
element, use a spanner wrench to remove the diffusion element.
NOTE
To determine if the diffusion element needs to be replaced, refer to para­graph 4-1.
22220028
Figure 4-4. Cell Replacement Kit
Use heat-resistant gloves and clothing when removing the probe. Do not at­tempt to work on these components until they have cooled to room tem­perature. Probe components can be as hot as 427°C (800°F). This can cause severe burns.
Disconnect and lock out power before working on any electrical components. There is voltage of up to 115 VAC.
Do not remove the cell unless certain it needs to be replaced. Removal may damage the cell and platinum pad. Go through the complete troubleshooting procedure to make sure the cell needs to be replaced before removing it.
a. Follow the instructions in paragraph 4-3a to
remove the Hazardous Area Oxymitter DR from the stack or duct.
c. If equipped with the optional ceramic diffu-
sion assembly, remove and discard the setscrews and remove the vee deflector (Figure 4-5). Use spanner wrenches from the probe disassembly kit (Table 7-1), to turn the hub free from the retainer. Inspect the diffusion element. If damaged, replace the element.
d. Loosen the four socket head cap screws
from the cell and flange assembly and re­move the assembly and the corrugated seal. The cell flange has a notch that may be used to gently pry the flange away from the probe. Note that the contact pad inside of the probe will sometimes fuse to the oxy­gen sensing cell. If the cell is fused to the contact pad, push the cell assembly back into the probe (against spring pressure) and quickly twist the cell assembly. The cell and contact pad should separate. If the contact pad stays fused to the cell, a new contact/thermocouple assembly must be in­stalled. Disconnect the cell and the thermo­couple wires at the probe electronics and withdraw the cell with the wires still attached.
e. Remove four screws (15, Figure 4-1) and
washers (14).
f. Separate the electrical connectors between
the heater strut and the termination hous­ing.
4-6 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
4
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
g. If the contact assembly is damaged, replace
the strut or the contact pad. Instructions for replacing the contact pad are in the cell re­placement kit.
h. Remove and discard the corrugated seal.
Clean the mating faces of the probe tube and retainer. Remove burrs and raised surfaces with a block of wood and crocus cloth. Clean the threads on the retainer and hub.
i. Rub a small amount of anti-seize compound
on both sides of the new corrugated seal.
j. Assemble the cell and flange assembly, cor-
rugated seal, and probe tube. Make sure the calibration tube lines up with the cali­bration gas passage in each component. Apply a small amount of anti-seize com­pound to the screw threads and use the screws to secure assembly. Torque to 4 N·m (35 in-lbs).
k. Install the termination housing per the
instructions in paragraph 4-5 steps c through e.
l. Apply anti-seize compound to the threads of
the cell assembly, hub, and setscrews. Re­install the hub on the cell assembly. Using pin spanner wrenches, torque to 14 N·m (10 ft-lbs). If applicable, reinstall the vee de­flector, orienting apex toward gas flow. Se­cure with the setscrews and anti-seize compound. Torque to 2.8 N·m (25 in-lbs).
Set reference air flow at 56.6 l/hr (2 scfh). After the Hazardous Area Oxymitter DR sta­bilizes, calibrate the unit. If new components have been installed, repeat calibration after 24 hours of operation.
4-8 CERAMIC DIFFUSION ELEMENT
REPLACEMENT
NOTE
This refers to the ceramic diffusion element only.
a. General
The diffusion element protects the cell from particles in process gases. Normally, it does not need to be replaced because the vee deflector protects it from particulate erosion. In severe environments, the filter may be broken or subject to excessive erosion. Ex­amine the ceramic diffusion element when­ever removing the probe for any purpose. Replace if damaged.
Damage to the ceramic diffusion element may become apparent during calibration. Compare probe response with previous re­sponse. A broken diffusion element will cause a slower response to calibration gas.
Hex wrenches needed to remove setscrews and socket head screws in the following procedure are available as part of a Probe Disassembly Kit, Table 7-1.
m. On systems equipped with an abrasive
shield, install the dust seal gaskets, with joints 180° apart.
n. Reinstall the probe and gasket on the stack
flange.
o. Follow the instructions in paragraph 4-3b to
install the Hazardous Area Oxymitter DR into the stack or duct. If there is an abrasive shield in the stack, make sure the dust seal gaskets are in place as they enter the 15° reducing cone.
p. Turn on power and monitor thermocouple
output. It should stabilize at 29.3+0.2 mV.
Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 4-7
b. Replacement Procedure
1. Follow the instructions in paragraph 4-3a to remove the Hazardous Area Oxymitter DR from the stack or duct.
2. Loosen setscrews, Figure 4-5, using hex wrench from Probe Disassembly Kit, Table 7-1, and remove vee deflec­tor. Inspect setscrews. If damaged, re­place with stainless setscrews coated with anti-seize compound.
Instruction Manual
IB-106-340CDR Original Issue January, 2002
M5-0.8 x 5 mm
LOCKING SET SCREW
(USE 2.5 mm HEX KEY)
THREADED
PROBE FLANGE
FLAME
ARRESTER
HUB
CEMENT
PORT
Figure 4-5. Ceramic Diffusion Element
Replacement
3. On systems equipped with abrasive shield, remove dual dust seal gaskets.
4. Use spanner wrenches from Probe Disassembly Kit, Table 7-1, to turn hub free from retainer.
5. Put hub in vise. Break out old ceramic diffusion element with chisel along ce­ment line. Use a 9.5 mm (3/8 in.) pin punch and clean fillet from the cement port.
CEMENT
FILLET
SPANNER
WRENCH
CERAMIC
DIFFUSION
ELEMENT
M6-1 x 6 mm SETSCREW (USE 3 mm HEX KEY)
VEE
DEFLECTOR
27540008
Hazardous Area Oxymitter DR
Do not get cement on ceramic diffu­sion element except where it touches the hub. Any cement on ceramic diffu­sion element blocks airflow through element. Wiping wet cement off of ce­ramic only forces cement into pores. Also, do not get any cement onto the flame arrestor element.
9. Thoroughly mix cement and insert tip of squeeze bottle into cement port. Tilt bottle and squeeze while simultane­ously turning ceramic diffusion element into seat. Do not get any cement on upper part of ceramic diffusion ele­ment. Ensure complete penetration of cement around 3 grooves in hub. Ce­ment should extrude from opposite hole. Wipe excess material back into holes and wipe top fillet of cement to form a uniform fillet. (A cotton swab is useful for this.) Clean any excess ce­ment from hub with water.
10. Allow filter to dry at room temperature overnight or 1 to 2 hours at 93°C (200°F).
11. Wipe a heavy layer of anti-seize com­pound onto the threads and mating surfaces of the flame arrestor, diffusion hub, and probe tube.
6. Break out remaining ceramic diffusion element by tapping lightly around hub with hammer. Clean grooves with pointed tool if necessary.
7. Replace ceramic diffusion element us­ing the ceramic diffusion element re­placement kit in Table 7-1. This consists of a diffusion element, ce­ment, setscrews, anti-seize compound, and instructions.
8. Test fit replacement ceramic diffusion element to be sure seat is clean.
4-8 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management
12. Assemble flame arrestor and diffusion hub with two pin spanner wrenches. Torque to 14 N·m (10 ft-lbs). Secure with hub retaining setscrew.
13. On systems equipped with abrasive shield, install dust seal gaskets with joints 180° apart.
14. Reinstall vee deflector, orienting apex toward gas flow. Apply anti-seize com­pound to setscrews and tighten with hex wrench.
15. Reinstall probe on stack flange.
Hazardous Area Oxymitter DR
4
Instruction Manual
IB-106-340CDR Original Issue
January, 2002

4-9 TERMINATION HOUSING WIRING

Under normal circumstances, the right termina­tion housing should not need to be removed. This side of the housing contains only two jumper wires that connect the connectors from the integral electrical barrier to pins in the housing wall. If these jumpers should become disconnected or need to be replaced, use the diagram in Figure 4-6 to connect the jumpers.
HEATER (BLACK)
HEATER (BLACK)
OXYGEN CELL +
(ORANGE)
THERMOCOUPLE -
(YELLOW)
THERMOCOUPLE +
(RED)
OXYGEN CELL -
(GREEN)
36210011
Figure 4-6. Termination Housing Connections
Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 4-9
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Hazardous Area Oxymitter DR
4-10 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
5

TROUBLESHOOTING

Instruction Manual
IB-106-340CDR Original Issue
January, 2002
SECTION 5

5-2 PROBE TROUBLESHOOTING

Install all protective equipment covers and safety ground leads after trouble­shooting. Failure to install covers and ground leads could result in serious injury or death.
5-1 OVERVIEW
Troubleshooting for the oxygen analyzer system is broken down to the main component level. In addition to the information in this section, instruc­tion bulletins for individual models also discuss troubleshooting.
For Models 218, 225, and 132 (analog), refer to IB-106-101.
For Model 218A, refer to IB-106-101A.
For Model TC200, refer to IB-107-020.
For Model 132 (digital), refer to IB-106-106A.
For Yokogawa (YEW) ZA8C Converter, refer to original converter documentation.
a. Probe Faults
Listed below are the five symptoms of probe failure.
1. The system does not respond to changes in the oxygen concentration.
2. The system responds to oxygen changes but does not give the correct indication.
3. The system does not give an accept­able indication of the value of the oxy­gen test gas being applied during cali­bration.
4. The probe takes a long time to return to flue gas value after the calibration gas is turned off.
5. The probe heater temperature is un­stable.
b. Symptoms
Table 5-1 provides a guide to fault finding for the above symptoms.
Table 5-1. Fault Finding
SYMPTOM CHECK FAULT REMEDY
1. No response to oxy­gen concentration change when:
Heater is cold and TC mV output is less than setpoint
Rosemount Analytical Inc. A Division of Emerson Process Management Troubleshooting 5-1
Thermocouple continuity Thermocouple failure Replace thermocouple
or return probe to Rosemount.
Cold heater resistance should be 67 ohm to 77 ohm
Triac O/P to heater Failure of electronics Check electronics pack-
Heater failure Replace heater or return
probe to Rosemount.
age.
Instruction Manual
IB-106-340CDR Original Issue January, 2002
SYMPTOM CHECK FAULT REMEDY
Hazardous Area Oxymitter DR
Table 5-1. Fault Finding (Continued)
Heater is hot and T/C mV output is at setpoint ±0.2 mV
2. System responds to oxygen concentra­tion changes but has incorrect indication
Good response, with incorrect indication
Recorder chart Recorder failure See Recorder Instruction
Manual.
Cell mV input to elec­tronics and cell mV at probe head
Recorder or remote indicator
System calibration Calibration error Recalibrate system. Re-
No cell mV at probe when test gas applied
Probe cell mV OK but no input to electronics
Cell mV satisfactory both at junction box and input to electronics - failure of electronics
Calibration error Recalibrate recorder or
Replace cell or return probe to Rosemount.
Check out cable con­nection.
Check electronics pack­age.
indicator. Reference Re­corder Instruction Man­ual.
place cell if necessary.
3. Probe does not give accurate indicationof applied test gas
4. Probe takes a long time to return to flue gas value after calibration gas is turned off
5. Probe heater temperature unstable
Probe mounting and condition of duct
Cell mV input to elec­tronics
Test gas input port Blocked port Clean port. If the flue
Ceramic diffusion ele­ment broken
Plugged diffusion ele­ment
Proper voltage heater is installed
Air ingress into duct Stop air leaks or resite
probe.
Failure of electronics Check electronics pack-
age.
gas is condensing in the test gas line, insulate the back of the probe. Make sure that the test gas line is capped between calibrations, or a check valve is installed.
Diffusion element cracked, broken, or missing
Plugged diffusion ele­ment
Wrong heater Change heater to proper
Replace diffusion ele­ment.
Change diffusion ele­ment or snubber diffu­sion element.
voltage.
5-2 Troubleshooting Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
6

RETURN OF MATERIAL

Instruction Manual
IB-106-340CDR Original Issue
January, 2002
SECTION 6

6-1 EQUIPMENT RETURN

If factory repair of defective equipment is re­quired, proceed as follows:
a. Secure a return authorization number from
a Rosemount Analytical Sales Office or rep­resentative before returning the equipment. Equipment must be returned with complete identification in accordance with Rosemount instructions or it will not be accepted.
In no event will Rosemount be responsible for equipment returned without proper authorization and identification.
b. Carefully pack defective unit in a sturdy box
with sufficient shock absorbing material to ensure that no additional damage will occur during shipping.
c. In a cover letter, describe completely:
1. The symptoms from which it was de­termined that the equipment is faulty.
2. The environment in which the equip­ment has been operating (housing, weather, vibration, dust, etc.).
3. Site from which equipment was removed.
5. Complete shipping instructions for re­turn of equipment.
6. Reference the return authorization number.
d. Enclose a cover letter and purchase order
and ship the defective equipment according to instructions provided in Rosemount Re­turn Authorization, prepaid, to:
Rosemount Analytical Inc. RMR Department 1201 N. Main Street Orrville, Ohio 44667
If warranty service is requested, the defec­tive unit will be carefully inspected and tested at the factory. If failure was due to conditions listed in the standard Rosemount warranty, the defective unit will be repaired or replaced at Rosemount's option, and an operating unit will be returned to the cus­tomer in accordance with shipping instruc­tions furnished in the cover letter.
For equipment no longer under warranty, the equipment will be repaired at the factory and returned as directed by the purchase order and shipping instructions.
4. Whether warranty or nonwarranty service is requested.
Rosemount Analytical Inc. A Division of Emerson Process Management Return of Material 6-1
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Hazardous Area Oxymitter DR
6-2 Return of Material Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
7
SECTION 7

REPLACEMENT PARTS

Table 7-1. Replacement Parts for Probe
Figure and Index No. Part Number Description
3D39496G06 3D39496G07 3D39496G08 3534B56G04 3534B56G05
3534B56G06 7-1 3535B44G01 7-1 3535B44G02 7-1 3535B44G03 7-1 3535B44G04 Cell Replacement Kit (No Inconel and Platinum Pad Assembly) 7-2 1L03825G01 Probe Disassembly Kit
1U05677G04 F/A Diffuser Hub Assembly (Snubber Diffusor)
1U05677G06 F/A Diffuser Hub Assembly (For use with Abrasive Shield)
6292A74G02 Ceramic Diffusion Element Replacement Kit
1N04966H02 Abrasive Shield Assembly (3 ft)
1N04966H03 Abrasive Shield Assembly (6 ft)
1M03241H01 90° Elbow for Bypass
4507C26G07 Bypass Gas Pickup Tube (3 ft)
4507C26G08 Bypass Gas Pickup Tube (6 ft)
4507C26G09 Bypass Gas Pickup Tube (9 ft)
263C152G01 Reference Gas Set
771B635H01 Calibration Gas Rotometer
1L03650H01 F/A Diffusion Hub Setscrew
1
V-Strut assembly includes contact and thermocouple assembly.
2
Contact and thermocouple assembly includes platinum pad and inconel wire
3
Cell replacement kit includes platinum pad and inconel wire.
1
V-Strut Assembly (18 in.)
1
V-Strut Assembly (3 ft)
1
V-Strut Assembly (6 ft.)
2
Contact and Thermocouple Assembly (18 in.)
2
Contact and Thermocouple Assembly (3 ft)
2
Contact and Thermocouple Assembly (6 ft)
3
Cell Replacement Kit (18 in.)
3
Cell Replacement Kit (3 ft)
3
Cell Replacement Kit (6 ft)
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
NOTE
The replacement parts listed above must be obtained only from the manu­facturer or his agent.
Rosemount Analytical Inc. A Division of Emerson Process Management Replacement Parts 7-1
Instruction Manual
IB-106-340CDR Original Issue January, 2002
GASKET
PROBE TUBE
(NOT INCLUDED
IN KIT)
CALIBRATION GAS
PASSAGE
ANSI
CORRUGATED
SEAL
Hazardous Area Oxymitter DR
CELL AND
FLANGE
ASSEMBLY
SOCKET HEAD
CAP SCREWS
WIRE AND PAD ASSEMBLY
TEFLON TUBING
ANTI-SEIZE COMPOUND
22 GA. WIRE
CLOSED END CONNECTOR
SET SCREWS
Figure 7-1. Cell Replacement Kit
HEX KEYS
SPANNER WRENCH
ANTI-SEIZE COMPOUND
PHILIPS SCREWDRIVER
WRENCH
35830009
TUBE INSERTION TUBE
35830010
Figure 7-2. Probe Disassembly Kit
7-2 Replacement Parts Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
8
SECTION 8

OPTIONAL ACCESSORIES

BY-PASS PACKAGES
The specially designed Rosemount Analytical By-Pass Package for oxygen analyzers has proven to withstand the high tempera­tures in process heaters while providing the same advantages offered by the in situ sensor. Inconel or Kanthal steel tubes pro­vide effective resistance to corrosion, and the package uses no moving parts, air pumps, or other components common to other sampling systems.
For more information, call Rosemount Analytical at 1-800-433-6076.
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
E
V
I
-
L
A
E
R
T
E
I
H
P
U
S
C
O
R
M
-
I
T
C
G
A
N
I
N
N
E
R
E
V
A
I
H
W
S
W
O
-
L
T
P
H
X
E
G
I
T
N
I
P
E
E
CAL.
GAS
26170024
O2 CALIBRATION GAS SEQUENCER
Rosemount Analytical’s O
Calibration Gas and Service Kits
2
have been carefully designed to provide a more convenient and fully portable means of testing, calibrating, and servicing Rosemount Analytical’s oxygen analyzers. These lightweight, disposable gas cylinders eliminate the need to rent gas bottles.
For more information, call Rosemount Analytical at 1-800-433-6076.
26170021
Rosemount Analytical Inc. A Division of Emerson Process Management Optional Accessories 8-1
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Hazardous Area Oxymitter DR
8-2 Optional Accessories Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
9
SECTION 9

APPENDICES

APPENDIX A. UPDATING DR OXYMITTER TO FULL OXYMITTER
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
Rosemount Analytical Inc. A Division of Emerson Process Management Appendices 9-1
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Hazardous Area Oxymitter DR
9-2 Appendices Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
A
UPGRADING HAZARDOUS AREA OXYMITTER DR TO
FULL HAZARDOUS AREA OXYMITTER
A-1 UPGRADE PROCEDURE
Perform the following procedure to upgrade the Hazardous Area Oxymitter DR to a full Hazard­ous Area Oxymitter.
a. Remove power from the Oxymitter DR.
b. Remove the left and right covers from the
Oxymitter termination housing.
Instruction Manual
Appendix A
January, 2002
APPENDIX A
c. Remove and discard the two cable assem-
blies (1 and 2, Figure A-1) from the right side of the termination housing.
d. Place the new Oxymitter electronic assem-
bly (3) near the right side of the termination housing.
e. Plug the white connector with the two black
wires into the white socket on the bottom power supply card.
f. Insert the electronics assembly into the ter-
mination housing. Ensure the black 4-wire connector remains outside the housing and in the slot provided in the top card of the electronics assembly. The electronics as­sembly should seat on the bulkhead pins easily. Do not force the assembly into place.
g. Plug the black 4-wire connector into the
black socket on the microprocessor card.
h. Tighten three screws (4) securing the elec-
tronics assembly into the termination hous­ing.
2
1
D
DIA
I
A
C
CALIBRA
A
L
G
GNOSTIC
N
O
S
A
ALARMS
T
L
I
C
A
R
M
S
I
B
R
A
T
TION RECOMMENDED
I
O
N
T
TEST
E
P
POINTS
S
O
T
I
N
T
S
I
INC
N
C
I
INC
H
HIGH
N
IG
H G
GAS
A
LO
S
G
GAS
D
DEC
E
C
D
DEC
H
HEA
E
A
T
TER
E
R
T
T/C
H
HEA
/
E
C
A
T
TER
C
CALIBRA
0
02 CELL
E
A
2
R
L
C
I
B
E
R
L
R
L
A
E
T
TION
C
I
O
O
N
M
M
E
N
D
0
02 CELL mV +
E
2
D
C
E
0
02 CELL mv
L
2
L
C
m
E
HEA
H
V
L
E
+
L
A
T
TER
m
E
H
HEA
v
R
E
-
A
T
T/C +
T
TER
/
C
E
R
+
C
T
T/C -
/
C
-
W A
S
C
CAL
A
L
E
C
T
TEST GAS +
E
S
T
PRPR
G
A
O
OCESS -
S
C
+
E
S
%
% 02
S
-
0
2
4
1. Signal connecting cable
2. Heater connecting cable
3. Electronic assembly
4. Screw
Figure A-1. Component Replacement
3
36210017
Rosemount Analytical Inc. A Division of Emerson Process Management Appendices A-1
Instruction Manual
Appendix A January, 2002
Hazardous Area Oxymitter DR
i. In the left side of the termination housing,
place the new termination designation la­bels over the labels on the existing terminal block. After placing the new labels, the ter­minal block should appear as shown in Figure A-2.
j. The existing wiring from the Oxymitter to the
electronics may be reused. However, the wires will be carrying new signals as noted by the new labels. The 4-20 mA wires must be removed from the old electronics and re­terminated to the wires carrying the 4-20 mA O
signal to the control room.
2
k. The wires carrying the heater power must
be converted to carry AC power (90-250
AC TERMINAL
COVER
LINE VOLTAGE
(90 TO 250 VAC)
AC L1
AC N
VAC, 50/60 Hz) for the Oxymitter. The re­terminations may be inside the old elec­tronics housing, which will function as a simple junction box. Alternatively, the old electronics may be removed and replaced with a smaller junction box.
l. Place the round error blink code and cali-
bration instructions label on the inside of the right housing cover.
m. Install both housing covers.
n. Refer to the instruction bulletin provided
with your upgrade kit, IB-106-340C, for startup and diagnostic information.
TERMINAL
BLOCK
AC LINE
VOLTAGE PORT
CALIBRATION HANDSHAKE
LOGIC I/O OR
4-20 mA SIGNAL
LEFT SIDE OF
OXYMITTER 4000
Figure A-2. Terminal Block and Wiring
4-20
+
-
+
-
GROUND LUGS
SIGNAL
PORT
36210016
A-2 Appendices Rosemount Analytical Inc. A Division of Emerson Process Management
Hazardous Area Oxymitter DR
10

INDEX

This index is an alphabetized listing of parts, terms, and procedures having to do with the Oxy­mitter DR In-Situ Oxygen Probe. Every item listed in this index refers to a location in the manual by one or more page numbers.
Instruction Manual
IB-106-340CDR Original Issue
January, 2002
SECTION 10
A
Abrasive Shield, 2-1, 2-3, 2-7 Absolute Temperature, 1-1 Adapter Plate, 1-2, 1-3, 2-1, 2-4, 2-5 Arithmetic Constant, 1-1
B
By-Pass Packages, 8-1
C
Calibration, 4-1 Calibration Gas, 1-3, 1-6, 2-2, 2-3, 4-1, 8-1 Calibration Gas Bottles, 1-8 Cell, 1-2, 4-5 Cell Constant, 1-1 Cell Replacement Kit, 7-2 Check Valve, 1-4
D
Diffusion Element, 1-2, 4-6, 4-8 Drip Loop, 2-6
E
Equipment Return, 6-1
H
Heater, 5-1 Heater Strut, 4-4 Heater Thermocouple, 1-2
I
Installation, Electrical, 2-7 Installation, Mechanical, 2-1 Installation, Pneumatic, 2-8 Instrument Air, 1-3, 2-8, 4-1 Insulation, 2-7, 4-1
M
Mounting, 1-6
N
Nernst Equation, 1-1
P
Packaging, 1-1 Partial Pressure, 1-1 Power Requirements, 1-6 Probe, 4-4, 7-1 Probe Disassembly Kit, 7-2 Probe Lengths, 1-2, 1-6 Process Temperature, 1-6 Product Matrix, 1-7
R
Reference Air, 1-3, 1-6, 2-2, 2-3 Reference Air Set, 1-2 Replacement Parts, Probe, 7-1
S
Specifications, 1-6
T
Terminal Block, 2-8, 4-1, 4-3 Thermocouple, Heater, 1-2 Troubleshooting, 5-1
V
Vee Deflector, 2-6
Z
Zirconia Disc, 1-1
Rosemount Analytical Inc. A Division of Emerson Process Management Index 10-1
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Hazardous Area Oxymitter DR
10-2 Index Rosemount Analytical Inc. A Division of Emerson Process Management

WARRANTY

Rosemount warrants that the equipment manufactured and sold by it will, upon shipment, be free of defects in workmanship or material. Should any failure to conform to this warranty become ap­parent during a period of one year after the date of shipment, Rosemount shall, upon prompt written notice from the purchaser, correct such nonconformity by repair or replacement, F.O.B. factory of the defective part or parts. Correction in the manner provided above shall constitute a fulfillment of all liabilities of Rosemount with respect to the quality of the equipment.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WAR­RANTIES OF QUALITY WHETHER WRITTEN, ORAL, OR IMPLIED (INCLUDING ANY WARRANTY OF MERCHANTABILITY OF FITNESS FOR PURPOSE).
The remedy(ies) provided above shall be purchaser's sole remedy(ies) for any failure of Rosemount to comply with the warranty provisions, whether claims by the purchaser are based in contract or in tort (including negligence).
Rosemount does not warrant equipment against normal deterioration due to environment. Factors such as corrosive gases and solid particulates can be detrimental and can create the need for re­pair or replacement as part of normal wear and tear during the warranty period.
Equipment supplied by Rosemount Analytical Inc. but not manufactured by it will be subject to the same warranty as is extended to Rosemount by the original manufacturer.
At the time of installation it is important that the required services are supplied to the system and that the electronic controller is set up at least to the point where it is controlling the sensor heater. This will ensure, that should there be a delay between installation and full commissioning that the sensor being supplied with ac power and reference air will not be subjected to component deterioration.
3622/1-02
Instruction Manual
IB-106-340CDR Original Issue January, 2002
Hazardous Area Oxymitter DR
Hazardous Area Oxymitter DR
Rosemount Analytical Inc. Process Analytic Division
1201 N. Main St. Orrville, OH 44667-0901 T (330) 682-9010 F (330) 684-4434 E gas.csc@emersonprocess.com
Part no.
Serial no.
Order no.
Fisher-Rosemount GmbH & Co.
Industriestrasse 1 63594 Hasselroth Germany T 49-6055-884 0 F 49-6055-884209
ASIA - PACIFIC Fisher-Rosemount Singapore Private Ltd.
1 Pandan Crescent Singapore 128461 Republic of Singapore T 65-777-8211 F 65-777-0947
http://www.processanalytic.com
© Rosemount Analytical Inc. 2002
EUROPE, MIDDLE EAST, AFRICA Fisher-Rosemount Ltd.
Heath Place Bognor Regis West Sussex PO22 9SH England T 44-1243-863121 F 44-1243-845354
LATIN AMERICA Fisher - Rosemount
Av. das Americas 3333 sala 1004 Rio de Janeiro, RJ Brazil 22631-003 T 55-21-2431-1882
Loading...