This instruction manual provides installation,
operation, maintenance, and parts ordering
information for the Type i2P-100 transducer (see
figure 1). Refer to separate manuals for instructions
covering equipment used with the transducer.
No person may install, operate or maintain a Type
i2P-100 electro-pneumatic transducer without
first D being fully trained and qualified in valve,
actuator and accessory installation, operation and
maintenance, and D carefully reading and
understanding the contents of this manual. If you
have any questions about these instructions, contact
your Fisher sales office.
INTEGRAL
PNEUMATIC
RELAY
W8710
Figure 1. Type i2P-100 Electro-Pneumatic Transducer
Description
The transducer, shown in figure 3, receives a 4 to 20
milliampere dc input signal and transmits a
proportional user field-configurable pneumatic output
pressure to a final control element. The pneumatic
output ranges are typically 0.2 to 1.0 bar (3 to 15
psig) and 0.4 to 2.0 bar (6 to 30 psig). A typical
application is in electronic control loops where the
final control element is a control valve assembly that
is pneumatically operated. The input signal and
output pressure range of the transducer is indicated
on the nameplate, attached to the housing.
CAUTION
Dropping or rough handling of the
transducer can cause damage to the
converter module resulting in a shifted
output or a minimum output.
REPLACEABLE
FILTER WITH
REMOVABLE
ORIFICE
VENT
www.Fisher.com
D103198X012
i2P-100 Transducer
Instruction Manual
Form 5777
September 2004
Table 1. Specifications
Input Signal
(1)
Available as standard with 4- 20 mA.
User configurable by dip switch for split ranging,
see table below.
Output Signal
(1)
Available as standard 0.2 to 1.0 bar (3 to 15 psig)
or 0.4 to 2.0 bar (6 to 30 psig). User configurable
by dip switch selection and zero and span
potentiometer adjustment, see table below.
INPUT SIGNAL
4 to 20 mA dc
4 to 12 mA dc0.2 to 1.03 to 15
12 to 20 mA dc0.2 to 1.03 to 15
OUTPUT PRESSURE
BAR
0.2 to 1.03 to 15
0.4 to 2.06 to 30
PSIG
Equivalent Circuit
The Type i2P- 100 equivalent circuit is a series
circuit consisting of a constant voltage drop
(battery) of approximately 4 V dc and a total
resistance of 40 ohms. Input is shunted by two
6.8 V zener diodes (see figure 9).
Supply Pressure
(1,5)
Recommended: 0.3 bar (5 psi) higher than upper
range limit of output signal
Maximum: 3.4 bar (50 psig)
Maximum Output Air Capacity
(2)
8.0 m3/hr (5.0 scfm) at 1.4 bar (20 psig) supply
pressure
Performance
(3)
Reference Accuracy: ±1.0% of full scale output
span; includes combined effects of hysteresis,
linearity, and deadband
Independent Linearity
output span
Hysteresis
(1)
: 0.4% of full scale output span
Frequency Response
(1)
: ±0.75% of full scale
(1)
: Gain is attenuated 3 dB
at 6 Hz with transducer output signal piped to a
typical instrument input
Temperature Effect: ±0.14% per degrees
Celsius (±0.75% per degrees Fahrenheit) of span
Supply Pressure Effect: 0.2% of full scale output
span per bar supply pressure change (0.2% of
full scale output span per psi supply pressure
change)
Vibration Effect: Less than 1% of full scale
output span when tested to SAMA PMC 31.1,
Condition 3
Electromagnetic Interference (EMI)
(1)
: Tested
per IEC 61326-1 (Edition 1.1).Conforms to the
European EMC Directive. Meets emission levels
for Class A equipment (industrial locations) and
Class B equipment (domestic locations). Meets
immunity requirements for industrial locations
(Table A.1 in the IEC specification document).
Immunity performance shown in table 2.
Operating Ambient Temperature Limits
(5)
-40 to 85_C ( -40 to +180_F)
Medium: Air or Natural Gas
Average Steady State Flow Rate
OUTPUT RANGE
0.2 to 1.0 bar (3-15 psig)0.4 to 2.0 bar (6-30 psig)
SUPPLY PRESSURE
1.5 bar (20 psig)2.4 bar (35 psig)
OUTPUTFLOW RATEOUTPUTFLOW RATE
BarPsig
0.230.083.00.460.093.6
0.690.124.51.2180.197.0
1.0150.176.32.1300.2710.2
2
Normal
3
m
/h
ScfhBarPsig
(4)
(1)(2)
Normal
3
m
/h
Scfh
(continued)
Electrical Classification
Hazardous Area
(6)
:
Explosion proof, Dust-Ignition proof, DIV 2,
Intrinsically Safe
Electrical Housing: NEMA 3R, CSA enclosure
Type 3R, IP66 per IEC60529
housing cap (see figure 10).
Switch: Allows input signal split range and
user-configurable 0.2 to 2 bar (3 to 30 psig)
Connections
Supply and Output Pressure: 0.25 inch NPT
female connection
Vent: 0.25 inch NPT female
output.
Mounting Position
J Actuator J pipestand or J surface
Electrical: J Standard 0.5 inch NPT
Wire Size: 18 to 22 AWG
Adjustments
(7)
Zero and Span: Trim potentiometers (20 turn) for
zero and span adjustments are located under the
1. These terms are defined in ISA Standard S51.1.
2. Normal m3/hr—Normal cubic meters per hour (0_C and 1.01325 bar, absolute). Scfh—Standard cubic feet per hour (60_F and 14.7 psia).
3. Performance values are obtained using a transducer with a 4 to 20 mA dc input signal and a 0.2 to 1.0 bar (3 to 15 psig) output signal at an ambient temperature of 24_ C (75_F).
4. This product is approved for use with Natural Gas. Natural gas to contain no more than 20 ppm of hydrogen sulphide.
5. The pressure and temperature limits in this manual and any applicable standard or code limitation should not be exceeded.
6. Approvals are pending
7. For other ranges, zero and span adjustments are needed.
Table 2. Immunity Performance
PortPhenomenonBasic StandardPerformance Criteria
Electrostatic discharge (ESD)IEC 61000-4-2A
Enclosure
I/O signal/control
Specification limit = ±1% of span
Radiated EM fieldIEC 61000-4-3A
Rated power frequency magnetic fieldIEC 61000-4-8A
Burst (fast transients)IEC 61000-4-4A
SurgeIEC 61000-4-5A
Conducted RFIEC 61000-4-6A
Approximate Weight (Transducer Only)
2.5 kg (5.5 lbs)
Actuator Stroking Time
See figure 2
100
90
80
OUTPUT
(% OF TYPE i2P-100 OUTPUT SPAN)
70
60
50
40
30
20
10
0
0 102030405060708090100
A6815 / IL
LOADING
EXHAUSTING
TIME (%)
Figure 2. Output-Time Relationships for Type i2P-100
Transducer
Specifications
Specifications for the Type i2P-100 transducer are
listed in table 1.
WARNING
This product is intended for a specific
current range, temperature range and
other application specifications.
Applying different current, temperature
and other service conditions could
result in malfunction of the product,
property damage or personal injury.
3
i2P-100 Transducer
CONDUIT
CONNECTION
FIELD
TERMINATION AND
ELECTRONICS
MODULE CAP
CONVERTER
MODULE CAP
FIELD
TERMINATION AND
ELECTRONICS
MODULE CAP
W8693
Instruction Manual
Form 5777
September 2004
CONDUIT
CONNECTION
CONVERTER
MODULE CAP
W8723
Figure 3. Type i2P-100 Electro-Pneumatic Transducer
Mounted on a Size 30 667 Sliding-Stem Actuator
Educational Services
For information on available courses for the Type
i2P-100 Electro-Pneumatic Transducer, as well as a
variety of other products, contact:
Emerson Process Management
Educational Services, Registration
P.O. Box 190; 301 S. 1st Ave.
Marshalltown, IA 50158- 2823
Phone: 800- 338- 8158 or
Phone: 641- 754- 3771
FAX: 641- 754- 3431
e-mail: education@emersonprocess.com
Note
Fisher does not assume responsibility
for the selection, use and maintenance
of any product. Responsibility for the
selection, use and maintenance of any
Fisher product remains with the
purchaser and end-user.
Figure 4. Type i2P-100 Electro-Pneumatic Transducer
Mounted on a Size 33 1052 Rotary Actuator, 3610J Positioner
and V300B Rotary Valve.
Installation
The i2P-100 transducer has been designed and
approved for use with either air or natural gas as the
supply medium. In normal operation the unit will vent
the supply medium into the surrounding atmosphere
unless it is remotely vented. When using natural gas
as the supply medium in a non-hazardous location,
remote venting of the unit is required. Failure to do
so could result in personal injury, property damage,
and area re-classification. For hazardous locations
remote venting of the unit may be required,
depending upon the area classification, and as
specified by the requirements of local, regional, and
federal codes, rules and regulations. Failure to do so
when necessary could result in personal injury,
property damage, and area re-classification.
WARNING
To avoid personal injury or property
damage from the sudden release of
pressure:
D Always wear protective clothing
and eyewear when performing any
installation operations.
D If installing into an existing
application, also refer to the WARNING
at the beginning of the Maintenance
section of this instruction manual.
D Check with your process or safety
engineer for any additional measures
that must be taken to protect against
process media.
4
Instruction Manual
Form 5777
September 2004
i2P-100 Transducer
74.2
81.6
(2.92)
(3.21)
67.8
(2.67)
GE0643
(sheet 1 of 4)
33.3
(1.31)
58.7
(2.31)
55.7
(2.19)
36.3
(1.43)
34.7
(1.37)
98.7
0.25 18 NPT
SUPPLY
CONNECTION
CONNECTION
(3.89)
0.25 18 NPT VENT
OR PIPE-A-WAY
CONNECTION
67 (2.62) CAP
REMOVAL
CLEARANCE
0.5 14 NPT
CONDUIT
103.9
(4.09)
0.25 18 NPT
OUTPUT
CONNECTION
75.2
(2.96)
22.3
(0.88)
22.9
(0.90)
33.3
(1.31)
33.3
(1.31)
0.25 18 NPT
OUTPUT
CONNECTION
75.7
(2.98)
103.9
(4.09)
67 (2.62) CAP
REMOVAL
CLEARANCE
mm
(INCH)
Figure 5. Dimensions and Connections
WARNING
This unit vents the supply medium into
the surrounding atmosphere. When
installing this unit in a non-hazardous
location with natural gas as the supply
medium, you must remotely vent this
unit to a safe location. Failure to do so
could result in personal injury or
property damage from fire or
explosion, and area re-classification.
When installing this unit in a
hazardous location remote venting of
the unit may be required, depending
upon the area classification, and as
specified by the requirements of local,
regional, and federal codes, rules and
regulations. Failure to do so when
necessary could result in personal
injury or property damage from fire or
explosion, and area re-classification.
Vent line piping should comply with
local and regional codes and should
be as short as possible with adequate
inside diameter and few bends to
reduce case pressure buildup.
Mounting
When a transducer is ordered as part of a control
valve assembly, the factory mounts the transducer
on the actuator and connects the necessary tubing,
then adjusts the transducer as specified on the
order. See figure 3 and 4 for typical mounting
configurations.
Transducers also can be ordered separately for
mounting on a control valve assembly already in
service, or for mounting on a 2-inch diameter
pipestand, or a flat surface. The transducer may be
ordered either with or without mounting parts.
Mounting parts include a mounting plate and bolts
and, if ordered for pipestand mounting, a pipe clamp.
Tubing is not included if the transducer is not factory
mounted. Use 0.375 inch diameter tubing for all
input and output connections. The length of tubing
5
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.