Emerson HSR Instruction Manual

Instruction Manual Form 5753
February 2014
Type HSR
Type HSR Pressure Reducing Regulator for Residential, Commercial or Industrial Applications
P1524 P1275
TYPE HSR ANGLE BODY TYPE HSR STRAIGHT
Figure 1. Type HSR Pressure Reducing Regulator
!
Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion
and/or  re causing property damage and
personal injury or death.
Fisher® regulators must be installed, operated and maintained in accordance with federal, state and local codes, rules and regulations and Emerson Process Management Regulator Technologies, Inc. instructions.
If the regulator vents gas or a leak develops in the system, service to the unit may be required.
Failure to correct trouble could result in a hazardous condition.
Call a gas service person to service the
unit. Only a quali ed person shall install
or service the regulator.
Introduction
Scope of the Manual
This manual provides instructions for the installation, adjustment, maintenance and parts ordering information for the Type HSR residential and/or industrial/commercial pressure regulator.
Description
The Type HSR direct-operated, spring-loaded regulators with internal relief provide economical pressure reducing control in a variety of residential, commercial and industrial applications. These regulators can be
used with natural, manufactured or lique ed petroleum
gases. In addition, the Type HSR regulator has internal relief across the diaphragm to help minimize overpressure. Any outlet pressure above the start-to­discharge point of the nonadjustable relief valve spring moves the diaphragm off the relief valve seat, allowing excess pressure to bleed out through the screened spring case vent.
www.fisherregulators.com
D103074X012
Type HSR
Specications
This section lists the specications of Type HSR. Factory specication such as type number, orice size, spring range and date
of manufacture are stamped on the nameplate fastened on the regulator at the factory.
Body Sizes (Inlet x Outlet) and End Connection Styles
3/4, 3/4 x 1 and 1 NPT All sizes available in Globe or Angle body.
Allowable Inlet Pressures
(1)
Emergency: 150 psig / 10.3 bar Maximum Operating Pressure: See Table 1
Allowable Outlet Pressures
(1)
Emergency (Casing): 25 psig / 1.7 bar Maximum Operating Pressure to Avoid Internal Parts Damage: 3 psi / 0.21 bar differential above outlet
pressure setting
Outlet Pressure Ranges
See Table 2
Spring Case Vent Connection
Standard: 1 NPT with removable screen Optional: 3/4 NPT with removable screen
Flow and Sizing Coefcients
See Table 4
Temperature Capabilities
-20 to 160°F / -29 to 71°C
1. The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.
Internal Relief Performance
Approximate Internal Relief Start-To-Discharge Point:
6 to 12 inches w.c. / 15 to 30 mbar above outlet pressure setting (Applies to 6 to 8 inches w.c. / 15 to 20 mbar and 8 to 10 inches w.c. / 20 to 25 mbar springs only.)
Relief Performance: See Figures 4 and 5
Lockup Performance During Normal Operation
ORIFICE SIZE LOCKUP ABOVE SETPOINT
Inch mm Inch w.c. mbar
1/8
3/16
1/4 3/8 1/2
Pressure Setting Adjustment
Adjusting Screw
Pressure Registration
Internal
Approximate Weight
4 pounds / 2 kg
Designed, Tested and Evaluated Consistent With:
ANSI B109.4 / CSA 6.18
Table 1. Maximum Operating Inlet Pressure
ORIFICE SIZE
Inch mm
1/8
3/16
1/4 3/8 1/2
3.2
4.8
6.4
9.5 13
WIDE-OPEN Cg
FOR RELIEF SIZING
12.5
28.2
50.0 105 185
MAXIMUM OPERATING INLET PRESSURE TO OBTAIN
GOOD REGULATING PERFORMANCE
3.2
4.8
6.4
9.5 13
psig
125 100
60 30 20
2.5
1 1 2
3
2 2 5 6 7
bar
8.6
6.9
4.1
2.1
1.4
Table 2. Outlet Pressure Ranges
OUTLET PRESSURE RANGE Inch w.c. mbar Inch mm Inch mm
4 to 6 10 to 15 T14398T0012 Orange Black 0.062 1.57 3.40 86.4
6 to 8 15 to 20 T14399T0012 Yellow Black 0.067 1.70 3.61 91.4
8 to 10 20 to 25 T14405T0012 Black Black 0.067 1.70 3.71 94.0
10 to 12.5 25 to 31 T14400T0012 Silver Black 0.072 1.83 4.10 104
12.5 to 20 31 to 50 T14401T0012 Gray Black 0.080 2.03 3.60 91.4
20 to 35 50 to 87 T14402T0012 Pink Black 0.093 2.36 3.52 88.9
1.25 to 2.2 psig 0.09 to 0.15 bar T14403T0012 Light Blue Red 0.105 2.67 3.66 94.0
SPRING
PART NUMBER
SPRING
COLOR
STANDARD CLOSING
CAP COLOR
SPRING WIRE DIAMETER SPRING FREE LENGTH
Table 3. Relief Performance
ORIFICE SIZE MAXIMUM ALLOWABLE INLET PRESSURE IF OUTLET PRESSURE IS HELD AT OR BELOW 2 psig / 140 mbar
Inch mm psig bar
1/8 3.2 125 8.6
3/16 4.8 65 4.5
1/4 6.4 30 2.1
3/8 9.5 10 0.69
1/2 13 7 0.48
1. The relief performance testing is in accordance with ANSI B109.4 and CGA 6.18, with the regulator set at 7-inch w.c. / 17 mbar, stem linkage disconnected and vented directly to atmosphere using the 3/4 or 1-inch / 19 or 25 mm vent.
2
Type HSR
UPPER SPRING CASE
STEM
VALVE DISK
ORIFICE
LEVER
PUSHER POST
RELIEF VALVE SPRING
CONTROL (MAIN)
SPRING
UPPER SPRING CASE
STEM
VALVE DISK
LEVER
ORIFICE
E0908
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
Principle of Operation
Figure 2. Type HSR Pressure Regulator Operational Schematic
Refer to Figure 2. When downstream demand decreases, the pressure under the diaphragm increases. This pressure overcomes the regulator setting (which is set by a spring). Through the action of the pusher post assembly, lever and
stem, the valve disk moves closer to the orice and reduces gas ow. If demand downstream increases, pressure under
the diaphragm decreases.
Spring force pushes the pusher post assembly downward and
the lever, stem and valve disk move away from the orice.
The Type HSR regulators include an internal relief valve for overpressure protection. If the downstream pressure exceeds the regulator setting by 7-inch w.c. to 1.25 psig / 17 to 86 mbar, depending on the main spring used, the relief valve opens and excess gas escapes through the vent in the
upper spring case.
Installation
CONTROL (MAIN)
SPRING
RELIEF VALVE SPRING
PUSHER POST
To avoid such injury or damage, provide pressure-relieving or pressure-limiting devices (as required by the appropriate code, regulation or standard) to prevent service conditions from exceeding those limits.
Additionally, physical damage to a regulator could cause personal injury and property damage due to escaping gas. To avoid such injury and damage, install the regulator in a safe location.
A regulator may vent some gas to the
atmosphere in hazardous or ammable gas
service, vented gas might accumulate and cause personal injury, death or property
damage due to re or explosion. Vent a
regulator in hazardous gas service to a remote, safe location away from air intakes or any hazardous location. The vent line must be
protected against condensation or clogging.
!
Personal injury, equipment damage or leakage due to escaping gas or bursting of pressure-containing parts might result if these regulators are overpressured or installed where service conditions could exceed the limits for which the regulators were designed or where conditions exceed any ratings of the adjacent piping or piping connections.
Before installing the regulator, check for damage which might have occurred in shipment. Also check for dirt or foreign matter which may have accumulated in the regulator body or in the pipeline. Apply pipe compound to the external threads
of the pipeline and install the regulator so that the ow is in
the direction of the arrow cast on the side of the body. The diaphragm actuator assembly can be rotated to any position relative to the body, in 90° increments. Remove the two cap
screws (key 17) that hold the body to the actuator in order to rotate the diaphragm actuator assembly.
3
Type HSR
TO APPLIANCE
VENT ASSEMBLY
VENT LINE
BASEMENT
B2497
Figure 3. Typical Vent Line Installation
Table 4. Flow and Sizing Coef cients
ORIFICE SIZE WIDE-OPEN FOR RELIEF SIZING
Inch mm C
1/8 3.2 12.5 0.36
3/16 4.8 28.2 0.81 0.82
1/4 6.4 50 1.43 0.82 3/8 9.5 105 3.00 0.79 1/2 13 185 5.29 0.79
g
C
V
C
1
35 0.78
X
T
IEC SIZING
COEFFICIENTS
F
D
0.82
F
0.89
L
Do not install the regulator in a location where there can be excessive water accumulation, such as directly beneath a downspout or in an undrained pit.
To obtain the maximum  ow capacities or other performance
characteristics, the length of pipe from the regulator outlet
to the meter—or for the  rst 18-inch / 457 mm, whichever is
closer—should have no bends and should be the same size as the regulator outlet. Replace the regulator if water gets into the spring case or the lower casing of the regulator.
HSR Series regulators have a spring case vent (1 or 3/4 NPT) which is screened to prevent insects or foreign material from entering.
CAUTION
You are advised to use new vent piping because defective threads on the relief vent piping may interfere with the venting assembly if the piping obstructs the movement of the vent stabilizer.
On indoor installations, the vent should be piped outside the building, see Figure 3. Remove the screen from the regulator vent connection and connect vent piping from that connection to the outdoors. Vent piping should be as large in diameter as practical, be as short as possible and have a minimum number of bends and elbows. Install a
weather and insect resistant vent assembly on the outside end of the pipe, such as a Type Y602. The same installation precautions apply to vent assemblies as the integral regulator vents described previously.
A program of regular inspection of the vent opening should be established to see that it has not become plugged by foreign material. On some installations, such as in areas of heavy snowfall, it may be necessary to install the regulator beneath a protective hood. If other protection is provided from the elements, the vent should be pointing or sloping down
suf ciently to allow any condensate to drain. Also check the
regulator periodically for external or internal corrosion.
Overpressure Protection
!
Some type of overpressure protection is needed if actual inlet pressure can exceed the outlet pressure rating. Overpressuring any portion of this equipment above the
limits given in the Speci cations section and
Tables 1 and 2 may cause damage to regulator parts, leaks in the regulator or personal injury due to bursting of pressure-containing parts or explosion of accumulated gas.
4
Type HSR
OUTLET PRESSURE, psig / bar
OUTLET PRESSURE, psig / bar
10 /
0.69
9 /
0.62
8 /
0.55
7 /
0.48
6 /
0.41
5 /
0.35
4 /
0.28
3 /
0.21
2 /
0.14
1 /
0.07
0
0
20 /
1.4
40 /
2.8
60 /
4.1
INLET PRESSURE, psig / bar
Figure 4. 7-inch w.c. / 17 mbar Setpoint Relief Curves (with lever disconnected, no vent piping and 3/4 or 1-inch / 19 or 25 mm vent)
80 /
5.5
1/2-INCH / 13 mm ORIFICE 3/8-INCH / 9.5 mm ORIFICE 1/4-INCH / 6.4 mm ORIFICE 3/16-INCH / 4.8 mm ORIFICE 1/8-INCH / 3.2 mm ORIFICE
100 /
6.9
120 /
8.3
140 /
9.7
10
0.69
9
0.62
8
0.55
7
0.48
6
0.41
5
0.35
4
0.28
3
0.21
2
0.14
1
0.07
0
0 20 /
1.4
40 /
2.8
60 /
4.1
80 /
5.5
1/2-INCH / 13 mm ORIFICE 3/8-INCH / 9.5 mm ORIFICE 1/4-INCH / 6.4 mm ORIFICE 3/16-INCH / 4.8 mm ORIFICE 1/8-INCH / 3.2 mm ORIFICE
100 /
6.9
120 /
8.3
140 /
9.7
INLET PRESSURE, psig / bar
Figure 5. 2 psig / 0.14 bar Setpoint Relief Curves (with lever disconnected, no vent piping and 3/4 or 1-inch / 19 or 25 mm vent)
5
Type HSR
Type HSR regulators provide internal relief that limits the total outlet pressure build-up over setpoint. This internal relief may be adequate for the application, if not, provide additional pressure relief or a pressure-limiting device downstream. Regulators should be inspected for damage after any overpressure condition.
Startup
!
To avoid personal injury or property damage due to explosion or damage to regulator or downstream components during startup, release downstream pressure to prevent an overpressure condition on the diaphragm of the regulator.
In order to avoid an overpressure condition and possible equipment damage, pressure gauges should always be used to monitor pressures during startup.
1. Check to see that all appliances are turned off.
2. Slowly open the upstream shutoff valve.
3. Slowly open the downstream shutoff valve.
4. Check all connections for leaks.
5. Make nal control spring adjustments according to the
adjustment procedures.
6. Light the appliance pilots.
Adjustment
To increase the outlet pressure setting of the regulator, the adjusting screw (key 26, Figure 6) must be turned clockwise. This requires removal of the closing cap (key 8). To reduce the outlet pressure setting, turn the adjusting screw counterclockwise. A pressure gauge should always be used to monitor downstream pressure while adjustments are being made. Do not adjust the spring to produce an outlet
pressure setting above the limit identied on the information
label. If the required pressure setting is not within the range of the spring being used, substitute with the correct spring, see Table 2. When changing the spring, also change the
range identied on the information label to indicate the
actual pressure range of the spring in use. After the spring adjustment has been completed, replace the closing cap.
Shutdown
!
To avoid personal injury or property damage due to explosion or damage to regulator or downstream components during shutdown, release downstream pressure to prevent an overpressure condition on the regulator diaphragm.
Installation arrangements may vary, but in any installation it is important that the valves be opened or closed slowly. These steps apply to the typical installation.
1. Slowly close the downstream shutoff valve.
2. Slowly close the upstream shutoff valve.
3. Open vent valves downstream of the regulator.
4. Open vent valves upstream of the regulator.
Maintenance
!
Avoid personal injury or damage to property from sudden release of pressure
or uncontrolled gas or other process uid.
Before starting to disassemble, isolate the regulator from all pressure and cautiously release trapped pressure from the regulator. Use gauges to monitor inlet, loading and outlet pressures while releasing these pressures.
These procedures are for gaining access to the diaphragm,
valve disk and orice. All pressure must be released from the
diaphragm actuator assembly before the following steps can be performed.
While using the following procedures, refer to Figure 6 for key number locations.
Diaphragm Replacement
1. Remove the closing cap (key 8) and adjusting screw (key 26).
2. Remove the spring case machine screws (key 9) out of the spring case (key 1) and remove the spring case and control spring (key 25).
3. Lift the diaphragm (key 11) slightly and slide it away from the lever (key 4), so that the pusher post (key 12) releases the lever.
6
Type HSR
4. Remove the relief spring retainer (key 14). Note the direction of the spring retainer assembly to aid in proper reassembly. Remove the relief valve spring (key 10).
5. Remove the diaphragm (key 11). Examine the diaphragm and replace if necessary.
6. Reassemble in the reverse order of the above procedures. Before attaching the spring retainer (key 14) to the pusher post (key 12) to secure the new diaphragm (key 11), place the loosely assembled diaphragm into position in the lower casing (key 2), being sure the pusher post is properly hooked on the lever (key 4). Rotate the diaphragm so that the diaphragm and lower casing holes align. Check the diaphragm for proper orientation. The open slot in the spring retainer is inserted from the notched side of the pusher post. Install the spring retainer and proceed with reassembly. Tighten the spring case machine screws
(key 9) to 15 to 30 inch-pounds / 1.7 to 3.9 N•m.
Valve Disk and Orice Replacement
1. Remove the cap screws (key 17) which hold the actuator assembly to the body.
2. The regulator can be removed from the body, exposing
the disk (key 23) and the orice (key 22).
3. Examine the disk (key 23). If it is nicked, cut or otherwise damaged, the disk should be removed from the valve stem (key 5) and replaced with a new part.
4. Examine the seating edge of the orice (key 22). If it is nicked or rough, it should be unscrewed from the body with a thin wall 7/8-inch / 22 mm socket wrench
and replaced with a new orice to provide proper shutoff. Treat the external threads of the new orice
with lubricant before reassembling, tightening to 25 to
35 foot-pounds / 34 to 48 N•m of torque.
5. Reassemble in the reverse order of the above procedures. Tighten the cap screws (key 17) to
6 to 10 foot-pounds / 8.1 to 14 N•m.
Regulator Reassembly
As indicated by the square callouts in Figure 6 it is recommended that a good quality pipe thread sealant be
applied to pressure connections and ttings and a good
quality lubricant be applied to O-rings. Also apply an anti­seize compound to the adjusting screw threads and other
areas as needed.
Parts Ordering
When ordering replacement parts, reference the key number of each needed part as found in the following parts
list. If construction changes are made in the eld, be sure that the information label is also changed to reect the most
recent construction.
Parts List
Key Description Part Number
1 Spring Case Assembly 3/4-inch / 19 mm Vent T40655T0GY2 1-inch / 25 mm Vent T40656T0GY2 2 Lower Casing, Aluminum T80565T0GY2 3 Screen, 18-8 Stainless steel T1121338982 4 Lever, Cast steel T21184T0012 5 Stem, Aluminum T14385T0012 6 Straight Pin, 18-8 Stainless steel T14397T0012 7 Machine Screw, Carbon-plated steel (2 required) 1E175828982 8 Closing Cap Black T21187T0012 Red T21187T0022 9 Machine Screw, Carbon steel (8 required) T13526T0012 10 Relief Valve Spring, 302 Stainless steel, Silver T14406T0012 11 Diaphragm T21163T0012 12 Pusher Post, Acetal T40653T0012 13 Lower Spring Seat, Zinc-plated steel T14396T0012 14 Relief Spring Retainer, 18-8 Stainless steel T13613T0012 15 Body, Cast iron Globe Body 3/4 NPT T21183T0GY2 3/4 x 1 NPT T21199T0GY2 1 NPT T21182T0GY2 Angle Body 3/4 NPT T21193T0GY2 3/4 x 1 NPT T21200T0GY2 1 NPT T21194T0GY2 16 O-ring, Nitrile (NBR) T14057T0042 17 Cap Screw, Zinc-plated steel (2 required) 1A352624052
22* Orice, Aluminum
1/8 inch / 3.2 mm 1A936709012 3/16 inch / 4.8 mm 00991209012 1/4 inch / 6.4 mm 0B042009012 3/8 inch / 9.5 mm 0B042209012 1/2 inch / 13 mm 1A928809012 23* Disk, Nitrile (NBR) T14386T0012 25 Spring, Zinc-plated steel 4 to 6 inches w.c. / 10 to 15 mbar, Orange T14398T0012 6 to 8 inches w.c. / 15 to 20 mbar, Yellow T14399T0012 8 to 10 inches w.c. / 20 to 25 mbar, Black T14405T0012 10 to 12.5 inches w.c. / 25 to 31 mbar, Silver T14400T0012
12.5 to 20 inches w.c. / 31 to 50 mbar, Gray T14401T0012 20 to 35 inches w.c. / 50 to 87 mbar, Pink T14402T0012
1.25 to 2.2 psig / 0.09 to 0.15 bar, Light Blue T14403T0022 26 Adjusting Screw, Delrin® T21186T0012 27 Information Label - - - - - - - - - - ­ 31 Closing Cap O-ring, Nitrile (NBR) (only CSA) GE13895T012
The type number, orice size, spring range and date of
manufacture are located on the spring case. Always provide this information in any correspondence with your local Sales
Ofce regarding replacement parts or technical assistance.
*Recommended spare part Delrin® is a mark owned by E.I. du Pont de Nemours and Co.
7
Type HSR
15
23
L1 L2
5
10
14 25
26
1 8
31
3
2
T80573
22
L1
APPLY LUBRICANT L1 = ANTI-SEIZE COMPOUND L2 = MULTI-PURPOSE POLYTETRAFLUOROETHYLENE (PTFE) LUBRICANT
NOTE: KEY 31 ONLY USED ON UNITS WITH CSA APPROVAL.
1. Lubricants must be selected such that they meet the temperature requirements.
16
L2
Figure 6. Type HSR Regulator Assembly
Industrial Regulators
Emerson Process Management Regulator Technologies, Inc.
USA - Headquarters McKinney, Texas 75070 USA Tel: +1 800 558 5853 Outside U.S. +1 972 548 3574
Asia-Pacic
Shanghai 201206, China Tel: +86 21 2892 9000
Europe Bologna 40013, Italy Tel: +39 051 419 0611
Middle East and Africa Dubai, United Arab Emirates Tel: +011 971 4811 8100
Natural Gas Technologies
Emerson Process Management Regulator Technologies, Inc.
USA - Headquarters McKinney, Texas 75070 USA Tel: +1 800 558 5853 Outside U.S. +1 972 548 3574
Asia-Pacic
Singapore 128461, Singapore Tel: +65 6770 8337
Europe Bologna 40013, Italy Tel: +39 051 419 0611 Chartres 28008, France Tel: +33 2 37 33 47 00
Middle East and Africa Dubai, United Arab Emirates Tel: +011 971 4811 8100
L2
12
6
47
13
11
TESCOM
Emerson Process Management Tescom Corporation
USA - Headquarters Elk River, Minnesota 55330-2445, USA Tels: +1 763 241 3238 +1 800 447 1250
Europe Selmsdorf 23923, Germany Tel: +49 38823 31 287
Asia-Pacic
Shanghai 201206, China Tel: +86 21 2892 9499
For further information visit www.fisherregulators.com
The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls International LLC, a business of Emerson Process Management.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or
guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specications of such
products at any time without notice.
Emerson Process Management Regulator Technologies, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson Process Management Regulator Technologies, Inc. product remains solely with the purchaser.
©Emerson Process Management Regulator Technologies, Inc., 2003, 2014; All Rights Reserved
Loading...