![](/html/da/da6c/da6c45c1fd89e8de82d4e4b5ca7da4c5f35fbb8c6f3ba50f7f5e8c1dba9cd46a/bg1.png)
Instruction Manual
Form 5187
March 2009
Type H800 Relief Valve
WARNING
!
Failure to follow these instructions or to
properly install and maintain this equipment
could result in an explosion, re and/or
chemical contamination causing property
damage and personal injury or death.
Fisher® relief valves must be installed, operated
and maintained in accordance with federal,
state, and local codes, rules and regulations,
and manufacturer’s instructions.
If a leak develops or if the outlet continually
vents gas, service to the unit may be required.
Failure to correct trouble could result in a
hazardous condition. Only a qualied person
must install or service the unit
Type H800
W3618
Figure 1. Type H800 Relief Valve
Installation, operation, and maintenance
procedures performed by unqualied personnel
may result in improper adjustment and unsafe
operation. Either condition may result in
equipment damage or personal injury. Use
qualied personnel when installing, operating,
and maintaining the Type H800 relief valve.
Introduction
Scope of the Manual
This manual provides installation, maintenance, and parts
ordering information for the Type H800 relief valve. Information
for other equipment used with this relief valve is contained in
separate manuals.
Product Description
(1)
The Type H800 relief valve
Direct-Operated relief valve. It is used primarily between a
pneumatic instrument and its supply pressure regulator to limit
the instrument supply pressure to 50 psig (3,4 bar) should
the supply pressure regulator fail open. The Type H800 relief
valve can also be mounted on other equipment, such as an air
compressor, where limited relief capacity is desired.
(See Figure 1) is a compact,
Specications
Specications for the Type H800 relief valve are given on
page 2. Additional specications for 67 Series regulators used
with Type H800 relief valves are shown in Table 1.
Installation
Upon receipt, inspect the relief valve to be sure it is free of
foreign material.
WARNING
!
Installing a Type H800 relief valve where its
capabilities can be exceeded or where proper
operation might be impaired may cause
personal injury, property damage, or leakage
due to bursting of pressure-containing parts or
explosion of accumulated gas. To avoid such
conditions, install a Type H800 relief valve where:
• Service conditions are within the unit
capabilities are specied in specications
section and Table 1, and
• The relief valve is protected from
exposure to physical damage and/or
corrosive substances.
1. Relief valve dened in ANSI Standard B95.1-1972. Not all codes or regulations permit these valves to be used as nal overpressure protection devices.
www.emersonprocess.com/regulators
D100405X012
![](/html/da/da6c/da6c45c1fd89e8de82d4e4b5ca7da4c5f35fbb8c6f3ba50f7f5e8c1dba9cd46a/bg2.png)
Type H800
Specications
Body Size and End Connection Style
NPS 1/4, NPT (internal)
Maximum Allowable Inlet (Relief) Pressure
(1)
250 psig (17,2 bar)
Relief Pressure Ranges
Non-adjustable, Start-to-discharge between
39 and 44 psig (2,7 and 3,0 bar)
Reseat Pressure
(1)
35 psig (2,4 bar) or higher
Wide-Open Flow Coefcients for Relief Valve Sizing
Maximum Temperature Capabilities
-20° to 150°F (-29° to 66°C)
IEC Sizing Coefcients
XT: 0.775
FD: 0.50
FL: 0.89
Vent Connection
1/2 NPT (internal)
Approximate Weight
5 ounces (140 grams)
(1)
Cg: 55
1. The pressure/temperature limits in this Instruction Manual or any applicable standard limitation should not be exceeded.
Table 1. Maximum Allowable Inlet Pressure to 67 Series Regulators (with Type H800 Relief Valve)
to Prevent Instrument Supply Pressure from Exceeding 50 psig (3,4 bar)
TYPE H800 INSTALLATIONS
FROM FIGURE 2
A
B
1. Limit vent piping to 30 equivalent feet (9,14 equivalent meters) of 1/2-inch (13 mm) piping. Lower vent piping may reduce the maximum allowable inlet pressure to supply
pressure regulator.
SUPPLY PRESSURE
REGULATOR TYPES
67, 67R, 67R, 67FR,
67CF, or 67CFR
67, 67R, 67CF, or 67CFR
67FR or 67F
REMOTE
VENT PIPING
(1)
Yes
No
Yes 100 (6,9)
No 250 (17,2)
Yes 100 (6,9)
No 200 (13,8)
MAXIMUM ALLOWABLE INLET PRESSURE TO
SUPPLY PRESSURE REGULATOR, PSIG (bar)
250 (17,2)
The relief valve may be shipped already mounted on other
equipment; if so, install that equipment by referring to its
Instruction Manual.
WARNING
!
This relief valve vents gas from the connection
marked “vent”. In hazardous or ammable
gas service, the vented gas may accumulate,
causing personal injury or equipment damage
due to re or explosion. Provide piping or
tubing to vent the gas to a safe, well-ventilated
location, and protect all vent openings from
condensation, freezing, or any substance that
could clog the vents.
The 1/2 NPT vent connection must face down in any installation.
Also, the screen (key 7) and disk restriction (key 6) must either
remain in the relief valve body (key 1) or be replaced by remote
vent piping or tubing that is as short and as straight as practical.
The piping or tubing should be 1/2-inch (13 mm) in diameter to
avoid the effects of backpressure build-up on relief performance.
Provide a screened vent for the open end of the remote vent
piping or tubing.
Figure 2 illustrates two typical methods of connecting a Type H800
relief valve to a 67 Series regulator. A yoke-mounted supply
pressure regulator and pneumatic instrument are shown in
Figure 2; however, the two methods of connecting a Type H800
relief valve to a 67 Series regulator also apply to pneumatic
instruments mounted on other equipment in other orientations.
Table 1 lists the conditions for the two typical methods of
installing a Type H800 relief valve. Whenever possible, use
installation A since a Type H800 relief valve with or without
remote vent piping will limit instrument supply pressure to 50 psig
(3,4 bar) when a 67 Series regulator fails open with 250 psig
(17,2 bar) inlet pressure.
For installation A, install the relief valve in the instrument
supply tubing between the supply pressure regulator and the
pneumatic instrument. Apply pipe compound to the male
threads of the pipe nipple and the tting for the instrument
supply pressure tubing.
For installation B, connect the relief valve with a pipe nipple to
the outlet pressure gauge connection of the 67 Series regulator.
Install a pipe plug or pressure gauge as shown in Figure 2. Apply
pipe compound to the male threads of the pipe nipple and pipe
plug or pressure gauge.
Maintenance
Relief valve parts are subject to normal wear and must be
inspected and replaced as necessary. The frequency of inspection
and parts replacement depends on the severity of service
conditions and the requirements of local, state, and federal rules
and regulations.
2