Emerson H800 Instruction Manual

Instruction Manual Form 5187
March 2009
Type H800 Relief Valve
!
Failure to follow these instructions or to properly install and maintain this equipment
could result in an explosion, re and/or
chemical contamination causing property damage and personal injury or death.
Fisher® relief valves must be installed, operated and maintained in accordance with federal, state, and local codes, rules and regulations, and manufacturer’s instructions.
If a leak develops or if the outlet continually vents gas, service to the unit may be required.
Failure to correct trouble could result in a
hazardous condition. Only a qualied person
must install or service the unit
Type H800
W3618
Figure 1. Type H800 Relief Valve
Installation, operation, and maintenance
procedures performed by unqualied personnel
may result in improper adjustment and unsafe operation. Either condition may result in equipment damage or personal injury. Use
qualied personnel when installing, operating,
and maintaining the Type H800 relief valve.
Introduction
Scope of the Manual
This manual provides installation, maintenance, and parts ordering information for the Type H800 relief valve. Information for other equipment used with this relief valve is contained in separate manuals.
Product Description
(1)
The Type H800 relief valve Direct-Operated relief valve. It is used primarily between a pneumatic instrument and its supply pressure regulator to limit the instrument supply pressure to 50 psig (3,4 bar) should the supply pressure regulator fail open. The Type H800 relief valve can also be mounted on other equipment, such as an air
compressor, where limited relief capacity is desired.
(See Figure 1) is a compact,
Specications
Specications for the Type H800 relief valve are given on page 2. Additional specications for 67 Series regulators used
with Type H800 relief valves are shown in Table 1.
Installation
Upon receipt, inspect the relief valve to be sure it is free of foreign material.
!
Installing a Type H800 relief valve where its capabilities can be exceeded or where proper operation might be impaired may cause personal injury, property damage, or leakage due to bursting of pressure-containing parts or explosion of accumulated gas. To avoid such
conditions, install a Type H800 relief valve where:
• Service conditions are within the unit capabilities are specied in specications
section and Table 1, and
• The relief valve is protected from
exposure to physical damage and/or corrosive substances.
1. Relief valve dened in ANSI Standard B95.1-1972. Not all codes or regulations permit these valves to be used as nal overpressure protection devices.
www.emersonprocess.com/regulators
D100405X012
Type H800
Specications
Body Size and End Connection Style
NPS 1/4, NPT (internal)
Maximum Allowable Inlet (Relief) Pressure
(1)
250 psig (17,2 bar)
Relief Pressure Ranges
Non-adjustable, Start-to-discharge between
39 and 44 psig (2,7 and 3,0 bar)
Reseat Pressure
(1)
35 psig (2,4 bar) or higher
Wide-Open Flow Coefcients for Relief Valve Sizing
Maximum Temperature Capabilities
-20° to 150°F (-29° to 66°C)
IEC Sizing Coefcients
XT: 0.775 FD: 0.50
FL: 0.89
Vent Connection
1/2 NPT (internal)
Approximate Weight
5 ounces (140 grams)
(1)
Cg: 55
1. The pressure/temperature limits in this Instruction Manual or any applicable standard limitation should not be exceeded.
Table 1. Maximum Allowable Inlet Pressure to 67 Series Regulators (with Type H800 Relief Valve)
to Prevent Instrument Supply Pressure from Exceeding 50 psig (3,4 bar)
TYPE H800 INSTALLATIONS
FROM FIGURE 2
A
B
1. Limit vent piping to 30 equivalent feet (9,14 equivalent meters) of 1/2-inch (13 mm) piping. Lower vent piping may reduce the maximum allowable inlet pressure to supply
pressure regulator.
SUPPLY PRESSURE REGULATOR TYPES
67, 67R, 67R, 67FR,
67CF, or 67CFR
67, 67R, 67CF, or 67CFR
67FR or 67F
REMOTE
VENT PIPING
(1)
Yes
No
Yes 100 (6,9)
No 250 (17,2)
Yes 100 (6,9)
No 200 (13,8)
MAXIMUM ALLOWABLE INLET PRESSURE TO
SUPPLY PRESSURE REGULATOR, PSIG (bar)
250 (17,2)
The relief valve may be shipped already mounted on other equipment; if so, install that equipment by referring to its
Instruction Manual.
!
This relief valve vents gas from the connection
marked “vent”. In hazardous or ammable
gas service, the vented gas may accumulate, causing personal injury or equipment damage
due to re or explosion. Provide piping or
tubing to vent the gas to a safe, well-ventilated location, and protect all vent openings from condensation, freezing, or any substance that
could clog the vents.
The 1/2 NPT vent connection must face down in any installation. Also, the screen (key 7) and disk restriction (key 6) must either
remain in the relief valve body (key 1) or be replaced by remote vent piping or tubing that is as short and as straight as practical.
The piping or tubing should be 1/2-inch (13 mm) in diameter to
avoid the effects of backpressure build-up on relief performance.
Provide a screened vent for the open end of the remote vent
piping or tubing.
Figure 2 illustrates two typical methods of connecting a Type H800
relief valve to a 67 Series regulator. A yoke-mounted supply
pressure regulator and pneumatic instrument are shown in
Figure 2; however, the two methods of connecting a Type H800
relief valve to a 67 Series regulator also apply to pneumatic
instruments mounted on other equipment in other orientations.
Table 1 lists the conditions for the two typical methods of installing a Type H800 relief valve. Whenever possible, use installation A since a Type H800 relief valve with or without remote vent piping will limit instrument supply pressure to 50 psig
(3,4 bar) when a 67 Series regulator fails open with 250 psig
(17,2 bar) inlet pressure.
For installation A, install the relief valve in the instrument supply tubing between the supply pressure regulator and the pneumatic instrument. Apply pipe compound to the male
threads of the pipe nipple and the tting for the instrument
supply pressure tubing.
For installation B, connect the relief valve with a pipe nipple to
the outlet pressure gauge connection of the 67 Series regulator.
Install a pipe plug or pressure gauge as shown in Figure 2. Apply pipe compound to the male threads of the pipe nipple and pipe
plug or pressure gauge.
Maintenance
Relief valve parts are subject to normal wear and must be
inspected and replaced as necessary. The frequency of inspection and parts replacement depends on the severity of service conditions and the requirements of local, state, and federal rules and regulations.
2
Loading...
+ 2 hidden pages