This specification sha ll define th e e lectrical and mechanical characteristics a nd requirements for a c ontinuousduty, single-phase, solid-state uninterruptible power system (UPS). The UPS s hall provide h igh-quality mains
power for sensitive, e lectronic equipment loads. The UPS is not designed to support large inductive or half-wave
rectified loads, for example: motors, co mpressors, vacuum pumps, electric drills, laser printers a nd hair dryers.
1.2
STANDARDS
The UPS shall be designed in accordance with applicable s ections of the current revision of the following
documents. Where a conflict arises between these d oc uments a nd statements made herein, th e statements in this
specification shall govern.
Safety-IEC62040-1:2008 version
Emission (Low limits – Conducted and r adiated):
•
IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 1)
•
CISPR22 Class A (RFI)
•
IEC/EN/AS61000-3-12 (Harmonics)
Immunity (High commercial and light industry immunity levels for enclosure, power, signal and control
ports):
•
IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6) for IEC/EN/AS:
•
61000-4-2 Electrostatic discharge
•
61000-4-3 Radiated E-RFI fields
•
61000-4-4 Fast E transients
•
61000-4-5 Surges/Lightning
•
61000-4-6 Conducted RFI
Transportation and Shipping- ISTA Procedure 1E Certification
Additional Agency Compliance:
•
C-Tick (Liebert in Australia / New Zealand will pursu e c ertification)
•
WEEE and RoHS (6 by 6)
The 230 VAC UPS units will be TUV and GS liste d and will bear the CE compliance mark and Australia Ctick (C√) mark.
SLI-23197_Rev 1 1 Guide Specifications
Liebert GXT4-10000RT230
1.3
1.3.1
SYSTEM DESCRIPTION
Modes of Operation
The UPS shall be designed to op erate in the following modes:
A.Normal - During normal operation, mains power shall provide energy to the UPS. The filters, the power
factor correction circuit and the inverter shall process the mains to provide computer-grade power to
connected loads. The UPS shall maintain the batteries in a fully charged state.
B.Battery - The UPS shall enter Battery mode if there is an ex treme power surge, extreme power sag or mains
failure. The battery system shall supply power through the DC-to-DC converter to the inverter to generate
computer-grad e power for the connected load.
C.Recharge - When the UPS is supplied with qu a lified mains power, the UPS shall charge connected internal
and optional external battery cabinets (if connected).
D.Internal Bypass - Bypass mode shall provide an a lternate pa th for mains power to the connected load in the
unlikely event of a UPS malfunction, such a s overload, over
temperature or an internal circuit failure.
E.Maintenance Bypass - Maintenance Bypass mode shall provide an alternate path for mains power to the
connected load during UPS maintenanc e or UPS replacement.
F.Automatic Restart - Upon restoratio n of mains p ower and after a complete b attery discharge, the UPS shall
be able to automatically restart and resume supplying power to the critical loa d based on the settings in the
supplied configuration program.
SLI-23197_Rev 1 2 Guide Specifications
Liebert GXT4-10000RT230
10000
9000
1.3.2
Design Requirements
A. Voltage: Nominal mains/output voltage specifications of the UPS at rated load shall be:
Mains
The UPS shall operate from 230V, 50Hz without the use o f selector switch es or voltage taps. Mains wiring
must be 2-wire (L, N) plus earth ground.
Output
Output voltage is present at terminals L and N. The output voltage sh all be a utomatically set to match mains
voltage upon initial startup. The UPS shall be con figurable us ing the included configuration program to
provide the following alternate voltages:
200/208/220/230/240, all voltages ± 3% at 50Hz
(If the UPS is started on battery with no mains power present, the default output voltage s h all be 230V, 50Hz
from the factory. After the UPS has bee n started from mains, the o utput voltage/frequency shall match the last
known mains voltage/frequency that was applied.)
B. Output Load Capacity: Specified ou tput load capacity of the UPS shall be:
UPS Model #
GXT4-
C. Internal Battery: Valve-regulated, non-spill able, lead acid cells.
D. Battery Reserve Time: Minimum 3 minutes with an ambient temperature of 25°C (77°F).
VA
Watt
s
E. Battery Recharge: The UPS shall contain a three-stage battery charger designed to prolong battery life.
Recharge time for UPS internal batteries shall be 3 hours maximum to 90% capacity after a co mplete
discharge into full load.
SLI-23197_Rev 1 3 Guide Specifications
Liebert GXT4-10000RT230
L/L Transfer
176 ± 5.0VAC
L/L Comeback
188 ± 5.0VAC
L/L Transfer
159 ± 5.0VAC
L/L Comeback
171 ± 5.0VAC
L/L Transfer
139 ± 5.0VAC
L/L Comeback
151 ± 5.0VAC
L/L Transfer
100 ± 5.0VAC
High Line Transfer
280 ± 5.0VAC
High Line Comeback
268 ± 5.0VAC
UPS Model #
VA
Watt
GXT4-10000RT230
10000 9000
39 Amps
2
2.26 Nm
1.3.3
Performance Requirements
1.3.3.1 Mains to UPS
A. Voltage: The point at which the UPS transfers to battery operation shall be dependent on the amount of load
that the UPS is supporting. The following range defines where the UPS will transfer to b attery and where it
returns to op erating from mains:
Low Line Voltage Range
GXT4-
Low Line Voltage
10000RT230
100% to 91%
90% to 71%
70% to 31%
30% to 0%
High Line Voltage Range
High Line Voltage
230V Models
B. Frequency: The UPS shall auto-sense mains frequency of 50Hz or 60Hz when first powered up a nd shall use
this frequency as the default output frequency. Once started the mains frequency operating window shall be
40-70Hz without going to batteries. The UPS shall be capable of cold start with a default output frequency of
50Hz.
C. Input Power Factor: >0.99 lagging at rated load.
D. Input Current reflected distortion: 5% THD maximum at rated load.
E. Input Current Ratings:
Total Amps
F. Surge Protection: The UPS shall utilize metal oxide varistors (MOVs) rated a t 385VAC(rms) @ 320 Joules.
G. Electrical Specifications:
UPS Model #
GXT4 RT
10000RT230
Recommended
(Maximum)
External Over
current
Protection
1 pole 53A
Recommended
Wire
(Including
ground wire)
(75°C copper wire)
10mm2(6AWG)
Maximum Wire
Accepted by
Terminal Block
16mm
(4AWG)
Terminal
Tightening
Torque
(20 in-lb)
SLI-23197_Rev 1 4 Guide Specifications
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.