Emerson GXT-RT series, GXT1000-RT, GXT2000-RT, GXT3000-RT, GXT1000L-RT User Manual

...
GXT RT Series 1-3 kVA UPS
User Manual
Version: V1.11 Revision date: Sept 21, 2005
Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.
While every precaution has been taken to ensure accuracy and completeness in this manual, Emerson Network Power assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
Emerson Network Power pursues a policy of continuous product development and reserves the right to change the equipment design without notice.
Copyright © 2005 by Emerson Network Power All rights reserved. The contents in this document are subject to change without notice
Liebert GXTRT Series Installation and User Manual 1-3 kVA UPS
Page 2 9/2005 Emerson Network Power
Contents
Safety Instructions............................................................................ 3-4
Description of Commonly used Notations.............................................5
1 Product Description ........................................................................6
1.1 Features...................................................................................6
1.2 System Components ...............................................................6
1.2.1 Power Module...................................................................6
1.2.2 Battery Module..................................................................8
1.3 System Type And Configuration ..............................................9
1.4 Operating Principle ................................................................10
1.5 Communication......................................................................11
2 Installation.....................................................................................12
2.1 Unpacking Inspection ............................................................12
2.2 Installation Notes ...................................................................12
2.3 Tower Installation ...................................................................13
2.3.1 Installing Single Power Module.......................................13
2.3.2 Installing Power Module Plus Battery Module.................13
2.4 Rack Installation ....................................................................14
2.4.1 Installing Single Power Module.......................................14
2.4.2 Installing Power Module Plus Battery Module.................15
2.5 Cable Connection ..................................................................15
2.5.1 Connecting Battery Cable ...............................................15
2.5.2 Connecting Input And Output Cables..............................16
2.5.3 Connecting Communication Cable .................................16
3 Operation......................................................................................18
3.1 Operator Control And Display Panel ......................................18
3.2 Operation Mode .....................................................................20
3.3 Operating Instructions............................................................20
3.3.1 Turning On And Completely Powering Down The UPS ..20
3.3.2 Conducting Battery Test..................................................21
4 Maintenance .................................................................................22
4.1 Battery Maintenance..............................................................22
4.2 Replacing Output Fuse ..........................................................22
4.3 Checking UPS Functions.......................................................22
4.4 Troubleshooting .....................................................................23
5 Specifications................................................................................25
5.1 Mechanical.............................................................................25
5.2 Electrical ................................................................................25
5.3 EMS .......................................................................................26
5.4 EMI ........................................................................................27
5.5 Environmental........................................................................27
5.6 Safety.....................................................................................27
Table of Contents
Liebert GXTRT Series Installation and User Manual 1-3 kVA UPS
Page 3 9/2005 Emerson Network Power
Safety Instructions
Safety Instructions
Caution - risk of electric shock. Even after the unit is disconnected from the mains power supply (building wiring socket outlet), components inside the UPS system are still connected to the battery and are still electrically live and dangerous.
Before carrying out any kind of servicing and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capacity capacitors such as BUS-capacitors
As dangerous voltages are present within the UPS, only an Emerson technician or an Emerson-authorized technician is permitted to open it. Failure to observe this could result in electric shock risk and invalidation of any implied warranty.
When the UPS is purchased to deliver power to the equipment listed below, please discuss with the Emerson or Emerson Authorized Representative in advance about the applicability, settings, management and maintenance of the UPS.
The Liebert GXT-RT has been designed for Commercial/Industrial use only, and is not recommended for use in life support applications
Never dispose of the battery in a fire, as it may explode when exposed to flame.
Do not apply pure inductive load to the UPS.
The UPS has its own energy source (i.e., a battery), therefore the output terminal of the
UPS may carry live voltage even when the UPS is not connected to the AC mains.
Before moving or re-wiring the UPS, please disconnect the mains source and make sure the UPS is completely shut down. Otherwise the output terminal may carry live voltage, presenting risk of electric shock.
To ensure safety and normal operation, the UPS must be solidly and adequately grounded before use.
The operating environment and storage method are two main factors affecting the lifetime and reliability of the UPS. Hence, it is advisable not to use the UPS for longer periods in the following environments:
Places where the temperature and relative humidity are outside the specifications (specified temperature: 0°C~40°C, specified relative humidity: 5%~95%);
Places where vibrations or shocks exist;
Places which are dusty, strewn with corrosive substances or salts or where
flammable gases are present.
Verify that the cabling and battery cable polarity are correct before switching on the UPS.
The external battery must be fitted with an appropriate overcurrent protection device.
The UPS installation must be firm and solid. The AC input socket that feeds the UPS
should be located near the UPS, and easy to access.
Liebert GXTRT Series Installation and User Manual 1-3 kVA UPS
Page 4 9/2005 Emerson Network Power
Safety Instructions
In case of fire, use dry chemical fire extinguisher to put out the fire. Using foam fire extinguisher may cause electric shock.
High ambient temperature shortens the battery’s lifetime, so the battery should be
monitored & maintained periodically and if required should be replaced. This is to
ensure normal UPS operation and adequate autonomy time. Only an
Emerson-authorized technician is permitted to replace the battery. In replacement of
battery or battery module, please use the same model and number of battery or battery
module.
It is recommended to place battery at a place with controlled ambient temperature. The rated battery performance is available at 25 degree Celsius.
Do not open or damage the battery, as the battery electrolyte is harmful to the eyes and the skin. If electrolyte comes into contact with the skin, wash the affected area with plenty of clean water and seek emergency medical assistance immediately
Liebert GXTRT Series Installation and User Manual 1-3 kVA UPS
Page 5 9/2005 Emerson Network Power
Commonly Used Notations
Description of commonly used notations
Some or all of the following Notations may be used in this manual and may appear in your application process. Therefore, all users should be familiar with them and understand their explanations.
Liebert GXTRT Series Installation and User Manual 1-3 kVA UPS
Page 6 9/2005 Emerson Network Power
Product Introduction
Product Introduction
The GXT-RT series 1~3kVA UPS is an online UPS with a sine wave output, and is developed by
Emerson Network Power.
The GXT-RT provides highly efficient and reliable AC Power for your sensitive equipment. The GXT-RT adopts a modular design. Rack installation and tower installation can be used depending
on the user’s requirements. It is an ideal product for applications that require small footprint, like communication stations and data machine rooms.
1.1 Features
Product features include:
z 2U thick.
z Exceptional electrical performance, with an on-line efficiency up to 88%.
z High system reliability, self-protection and fault diagnosis are achieved using the advanced DSP-based
full digital control technology.
z The system adopts a high-frequency, double conversion topology structure to achieve a high input
power factor up to 0.99, greatly reducing its contamination to the power grids.
z With a wide range of input voltages, and an output immune to the mains interference, the product is
suitable even for areas with unstable mains power supply. It is an environmentally efficient energy source.
z With a wide range of input frequencies, the product can be well connected to the generator output.
z Long Back up model has built-in large charger to satisfy users’ demand for extended battery back-up
time.
1.2 System Components
Power module and battery module are the basic components of GXT RT series UPS. The former performs power conversion, provides AC output for load and charges the battery, while the latter provides DC power for the UPS.
1.2.1 Power Module
Types and models
There are two types of power module: standard type and extended back-up time type, each available in the following ratings: 1kVA, 2kVA and 3kVA.
The power module types and models appear from Table 1-1. Users can confirm the module model by checking the nameplate on the enclosure.
Liebert GXTRT Series Installation and User Manual 1-3 kVA UPS
Page 7 9/2005 Emerson Network Power
Product Introduction
Product Introduction
Table 1-1 Power modul e types and models
Type Module name Model Remark
1kVA standard power module GXT1000-RT
With a 1A internal charger and a 3*12V/7.2Ah internal battery
2kVA standard power module GXT2000-RT With a 1A internal charger
Standard
3kVA standard power module GXT3000-RT With a 1A internal charger
1kVA extended back-up time power module
GXT1000L-RT With a 7A internal charger
2kVA extended back-up time power module
GXT2000L-RT With an 8A internal charger
Extended back-up time
3kVA extended back-up time power module
GXT3000L-RT With an 8A internal charger
Front panel appearance
All models of power modules have the same front panel, which provides ON/Alarm silence button, OFF button and LED indication, as shown in Figure 1-1.
Figure 1-1 Front panel of power module
Rear panel appearance
The power module’s rear panel differs with the model, as shown in figures from 1-2 to 1-6. The rear panel provides AC input socket, AC input overcurrent protection switch, output socket, output fuse and output terminal block (3kVA power modules only), external battery socket (except for 1kVA standard power module), DB9 communication port and SNMP card slot.
Figure 1-2 Rear panel of 1kVA standard power module
Figure 1-3 Rear panel of 1kVA extended back-up time power module
Liebert GXTRT Series Installation and User Manual 1-3 kVA UPS
Page 8 9/2005 Emerson Network Power
Product Introduction
Figure 1-4 Rear panel of 2kVA standard power module
Figure 1-5 Rear panel of 2kVA extended back-up time power module
Figure 1-6 Rear panel of 3kVA power modules
1.2.2 Battery Module
Model
The battery packs are available in two modules:
GXT2000-BAT and GXT3000-BAT, as shown in
Table 1-2. Users can confirm the module model by checking the nameplate on the enclosure.
Table 1-2 Battery module models
Module name Model Remark
72V/7.2Ah battery module GXT2000-BAT 72V, with a 6*12V/7.2Ah internal battery
72V/9.0Ah battery module GXT3000-BAT 72V, with a 6*12V/9Ah internal battery
Front panel and rear panel appearances
The
GXT2000-BAT and GXT3000-BAT battery modules have the same front panel and rear
panel, as respectively shown in Figure 1-7 and Figure 1-8.
Figure 1-7 Front panel of battery module
Liebert GXTRT Series Installation and User Manual 1-3 kVA UPS
Page 9 9/2005 Emerson Network Power
Product Introduction
Figure 1-8 Rear panel of battery module
1.3 System Type And Configuration
The above mentioned power modules and battery modules can comprise two types of UPS system: standard type and extended back-up time type, each available in the following ratings: 1kVA, 2kVA and 3kVA UPS.
The UPS types and configurations appear from Table 1-3.
Table 1-3 UPS types and configurations
Configuration
UPS type
Module Model Qty. Remark
1kVA standard UPS
Power module
GXT1000-RT 1
The UPS has only one power module
Power module
GXT2000-RT 1
2kVA standard UPS
Battery module
GXT2000-BAT 1
Power module
GXT3000-RT 1
Standard
3kVA standard UPS
Battery module
GXT3000-BAT 1
The UPS consists of a power module and a battery module
1kVA extended back-up time UPS
Power module
GXT1000L-RT 1
2kVA extended back-up time UPS
Power module
GXT2000L-RT 1
Extended backup time
3kVA extended back-up time UPS
Power module
GXT3000L-RT 1
External battery is needed and should be provided by users. Emerson battery and battery cabinet are recommended