Emerson GXT2-6000RTL630 User Manual

Page 1
DISCONTINUED
PRODUCT
AC Power For Business-Critical Continuity™
Liebert GXT2-6000RTL630
User Manual - 208 / 240 VAC
Page 2
DISCONTINUED
Page 3
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.0 SYSTEM DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.1 Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters. . . . . . . . . . . . . . . . . . . . 5
2.2 Rectifier/Power Factor Correction (PFC) Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4 Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.5 DC-to-DC Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.6 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.7 Dynamic Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.0 MAJOR COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
3.1 Main Frame and Electronics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2 Internal Battery Packs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.3 Removable Power Distribution Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.0 WHATS INCLUDED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
5.0 INSTALLATION AND CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.1 Install the Main Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.1.1 Tower UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.1.2 Rack-Mount UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.1.3 Installing the Adjustable Rack-Mount Kit—Sold Separately . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.2 Install the Internal Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3 Connect the Internal Batteries Using the External Connector . . . . . . . . . . . . . . . . . . . . . . . 15
5.3.1 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.4 Connect Input/Output Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.4.1 Attach Power Distribution Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.4.2 Distribution Box Electrical Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.5 External Battery Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.0 INITIAL START-UP AND ELECTRICAL CHECKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
7.0 CONFIGURATION PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
7.1 GXT2-6000RTL630 Configuration Program Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
7.1.1 What You Will Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
8.0 CONTROLS AND INDICATORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
8.1 ON/Alarm Silence/Manual Battery Test Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
8.2 Standby/Manual Bypass Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
8.3 Load Level Indicators (4 Green, 1 Amber) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.4 Battery Level Indicators (5 Green) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.5 Fault Indicator LED (Red) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
i
DISCONTINUED
Page 4
8.6 Bypass Indicator LED (Amber) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.7 UPS ON Indicator LED (Green) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.8 Battery Indicator LED (Amber). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.9 AC Input Indicator LED (Green). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
9.0 OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
9.1 Normal Mode Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
9.2 Battery Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
9.3 Bypass Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
9.4 Battery Recharge Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
10.0 COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
10.1 Communications Interface Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
10.2 Pin 4 - Remote Shutdown on Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
10.3 UPS Intelligent Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
10.4 Remote Emergency Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
11.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
11.1 Internal Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
11.1.1 Internal Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
11.2 AC Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
11.2.1 Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
11.2.2 Reconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
12.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
12.0.1 Auto-Learning Battery Run Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
13.0 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
FIGURES
Figure 1 GXT2-6000RTL630, front view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 2 GXT2-6000RTL630, rear view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 3 Internal battery pack with connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 4 Optional power distribution—PD-L630 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 5 Tower-use support bases, spacers for external battery cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 6 PD-L630 power distribution box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 7 PD-L630 power distribution box electrical connections diagram . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 8 Power distribution box, PD-L630 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
TABLES
Table 1 DB-9 pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Table 2 Indicator meanings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Table 3 Troubleshooting guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Table 4 Alarm conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Table 5 Battery run times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Table 6 UPS specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Table 7 Internal battery specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Table 8 Output distribution specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Table 9 External battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
ii
DISCONTINUED
Page 5
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
WARNING
!
Opening or removing the cover may expose you to lethal voltages within this unit even when it is apparently not operating and the input wiring is disconnected from the electrical source.
Observe all cautions and warnings in this manual. Failure to do so may result in serious injury or death. Refer all UPS and battery service to qualified service personnel. Do not attempt to service this product yourself. Never work alone.
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions. Read all safety, installation and operating instructions before operating the Uninterruptible Power Supply (UPS). Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions. Individuals without previous training can install and operate this equipment.
It is not intended for use with life support and other designated critical devices. Maximum load must not exceed that shown on the UPS rating label. The UPS is designed for data processing equipment. If uncertain, consult your local dealer or Liebert representative.
This UPS is designed for use on a properly grounded (earthed), 208, 220, 230 or 240 VAC, 50Hz or 60Hz supply. The factory default setting is 208VAC, 60Hz. Installation instructions and warning notices are located in this manual.
This UPS is for use only with a three-wire input: L1, L2, G.
Electromagnetic Compatibility
The GXT2-6000RTL630 Series complies with the limits for a CLASS A DIGITAL DEVICE, PURSU­ANT TO Part 15 of FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference and (2) this device must accept any interference received, includ­ing interference that may cause undesired operation. Operating this device in a residential area is likely to cause harmful interference that users must correct at their own expense.
Operate the UPS in an indoor environment only in an ambient temperature range of 32°F to 104°F (0°C to 40°C). Install it in a clean environment, free from conductive contaminants, moisture, flam­mable liquids, gases and corrosive substances.
This UPS contains no user serviceable parts except the internal battery pack. The Off/Bypass push button does not electrically isolate internal parts. Under no circumstances attempt to gain access internally other than to replace the batteries due to risk of electric shock or burn. Do not continue to use the UPS if the front panel indications are not in accordance with these operating instructions or if the UPS performance alters in use. Refer all faults to your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from the batteries. PROPER DIS­POSAL OF BATTERIES IS REQUIRED. REFER TO YOUR LOCAL LAWS AND REGULATIONS FOR BATTERY DISPOSAL REQUIREMENTS.
Never block or insert any object into the ventilation holes or other openings of the UPS.
DO NOT CONNECT equipment that could overload the UPS or demand half-wave rectification from the UPS, for example: electric drills, vacuum cleaners, laser printers, hair dryers or any other appli­ance using half-wave rectification.
Storing magnetic media on top of the UPS may result in data loss or corruption.
Turn the UPS off and isolate the UPS before cleaning; use only a soft cloth, never liquid or aerosol cleaners. Keep the front and rear vents free of dust accumulation that could restrict airflow.
1
DISCONTINUED
Page 6
When replacing batteries, replace with the same Liebert authorized replacement battery kits.
CAUTION
!
Do not dispose of battery or batteries in a fire. The battery may explode.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to skin and eyes. It is toxic.
CAUTION
!
A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
2
DISCONTINUED
Page 7
GLOSSARY OF SYMBOLS
Risk of electrical shock
!
R
i
-
PbH2SO4
Indicates caution followed by important instructions
AC input
AC output
Requests the user to consult the manual
+
Indicates the unit contains a valve-regulated lead acid battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
ON/Alarm Silence/Battery Test
OFF/Bypass
Indicates the position of a fuse
3
DISCONTINUED
Page 8
1.0 INTRODUCTION
Congratulations on your choice of the Liebert GXT2-6000RTL630 Uninterruptible Power Supply (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment.
Upon generation, AC power is clean and stable. However, during transmission and distribution it may be subject to voltage sags, spikes or complete power failure that may interrupt computer opera­tions, cause data loss or even damage equipment. The GXT2-6000RTL630 protects equipment from these disturbances.
The GXT2-6000RTL630 comes in a nominal power rating of 6000 VA. Complete model specifications appear at the end of this manual.
The GXT2-6000RTL630 is a compact, on-line UPS. An on-line UPS continuously conditions and regu­lates its output voltage, whether utility power is present or not. It supplies connected equipment with clean sinewave power. Sensitive electronic equipment operates best from sinewave power.
For ease of use, the GXT2-6000RTL630 features a light-emitting diode (LED) display to indicate both load percentage and battery capacity. It also provides self-diagnostic tests, a combination ON/Alarm Silence/Manual Battery Test button, a Standby button, user configurable program, and two levels of alarms when the unit is operating on battery.
The GXT2-6000RTL630 has an interface port for communication between the UPS and a network server or other computer systems. This port provides detailed operating information including volt­ages, currents, and alarm status to the host system when used in conjunction with Liebert Multi­Link™ software. MultiLink software can also remotely control UPS operation.
Introduction
4
DISCONTINUED
Page 9
2.0 SYSTEM DESCRIPTION
Input Output
System Description
Dynamic
Bypass
L1
L2
G G
TVSS & EMI/RFI
Filters
Rectifier
DC-to-DC
Converter
Battery
Charger
/PFC
Inverter
Battery
2.1 Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters
These UPS components provide surge protection and filter both electromagnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the util­ity line and keep the sensitive equipment protected.
L1
L2
2.2 Rectifier/Power Factor Correction (PFC) Circuit
In normal operation, the rectifier/power factor correction (PFC) circuit converts utility AC power to regulated DC power for use by the inverter while ensuring that the waveshape of the input current used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives:
• The utility power is used as efficiently as possible by the UPS.
• The amount of distortion reflected on the utility is reduced.
This results in cleaner power being available to other devices in the building not being protected by the GXT2-6000RTL630.
2.3 Inverter
In normal operation, the inverter utilizes the DC output of the power factor correction circuit and inverts it into precise, regulated sinewave AC power. Upon a utility power failure, the inverter receives its required energy from the battery through the DC to DC converter. In both modes of oper­ation, the UPS inverter is on-line and continuously generating clean, precise, regulated AC output power.
2.4 Battery Charger
The battery charger utilizes energy from the utility power and precisely regulates it to continuously float charge the batteries. The batteries are being charged whenever the GXT2-6000RTL630 is con­nected to utility power.
5
DISCONTINUED
Page 10
2.5 DC-to-DC Converter
The DC to DC converter utilizes energy from the battery system and raises the DC voltage to the opti­mum operating voltage for the inverter. This allows the inverter to operate continuously at its opti­mum efficiency and voltage, thus increasing reliability.
2.6 Battery
The GXT2-6000RTL630 utilizes valve-regulated, nonspillable, lead acid batteries. To maintain bat­tery design life, operate the UPS in an ambient temperature of 68°F to 77°F (20°C to 25°C). Optional external battery cabinets are available to extend battery run times.
2.7 Dynamic Bypass
The GXT2-6000RTL630 provides an alternate path for utility power to the connected load in the unlikely event of a UPS malfunction. Should the UPS have an overload, overtemperature, or UPS failure condition, the UPS automatically transfers the connected load to bypass. Bypass operation is indicated by an audible alarm and illuminated amber Bypass LED (other LEDs may be illuminated to indicate the diagnosed problem). To manually transfer the connected load from the inverter to bypass, press the Standby button once.
NOTE
The bypass power path does NOT protect the connected equipment from disturbances in the utility supply.
System Description
6
DISCONTINUED
Page 11
3.0 MAJOR COMPONENTS
The GXT2-6000RTL630 is composed of three major assemblies to provide easier handling, installa­tion, and versatility.
3.1 Main Frame and Electronics
This 5U cabinet is shipped without internal batteries to lighten the UPS for easier installation. The internal batteries may be installed after the cabinet has been placed in its final floor or rack position. The Power Distribution box is shipped separately for easier handling of the UPS while being placed in its final position.
Figure 1 GXT2-6000RTL630, front view
Top Tri m (2 pieces; tower use only)
Major Components
Lower Bezel & Battery Access Door
Status Indicators & Controls
Upper Bezel
!
UPStation GXT
7
DISCONTINUED
Page 12
Figure 2 GXT2-6000RTL630, rear view
Battery Disconnect
External Battery Connector
OUTPUT BREAKER
30A/250V~T
UPS Output Circuit Breaker
DB-9 Communication Port
BREAKER 30A
OFF
OUTPUT ONLY CB DOES NOT
CONNECT BYPASS POWER TO
MANUAL BYPASS SWITCH.
ON
EXT. BATTERY
240V 25A
AND EXTENDED
STORAGE
ATTACH JUMPER
HERE FOR SHIPPING
SEE MANUAL
FOR CONNECTIONS
Major Components
INTERNAL BATTERY
CONNECTOR INSTALL
BEFORE OPERATING
+
-
ON
OFF
OFF
OFF
BREAKER
20A 240V~/T
COMMUNICATION PORT
REPO
ON
OUTPUT
ON
RELAY CARD USB/WEB CARD
Fans
REPO Connector
Relay Card Slot
Removable Power Distribution Box
Maintenance Bypass Switch
INPPUT
BREAKER
20A 240V~/T
OUTPUT
AVAILABLE
UPS
UPS
MAITANENCE BYPASS
AVAILABLE
UTILITY
Serial Card Slot (SNMP, OCWEB, USB)
3.2 Internal Battery Packs
The UPS has two internal battery packs behind a battery access door on the front of the unit. Each pack is fitted with a connector to link to the UPS. The batteries are shipped in packaging separate from the UPS. These must be installed before the UPS may be put into service. For installation instructions, see 5.2 - Install the Internal Batteries.
8
DISCONTINUED
Page 13
Figure 3 Internal battery pack with connector
3.3 Removable Power Distribution Box
The UPS incorporates a power distribution box that must be installed before the unit is placed into service. The power distribution box provides the benefits of plug and receptacle convenience with a manual bypass switch. For installation instructions, see 5.4 - Connect Input/Output Power.
Optional versions may be available to replace the standard box for custom installations.
Major Components
Figure 4 Optional power distribution—PD-L630
UPS
MAITANENCE BYPASS
AVAILABLE
AVAILABLE
UPS
UTILITY
ON
ON
OUTPUT BREAKER 20A 240V~/T
OFF
BREAKER 30A
OFF
OFF
ON
OUTPUT ONLY CB DOES NOT CONNECT BYPASS POWER TO MANUAL BYPASS SWITCH.
OUTPUT BREAKER 20A 240V~/T
INPPUT
Manual Bypass Switch
CONNECTOR PROTECTIVE COVER DO NOT REMOVE SCREWS
PRIOR TO INSTALLATION OF BOX ON UPS
-LOOSEN THREE SCREWS 1 TURN
- SLIDE COVER TO EXPOSE CONNECTOR
-TIGHTEN SCREWS GENTLY
UPON REMOVAL OF BOX FROM UPS
-LOOSEN THREE SCREWS 1 TURN
Wired
connections
to UPS
-SLIDE COVER TO REACH END SCREW AND COVER COMMUNICATION
-TIGHTEN SCREWS GENTLY
9
DISCONTINUED
Page 14
4.0 WHATS INCLUDED
The GXT2-6000RTL630 is shipped with the following items:
• GXT2-6000RTL630 user manual
• Vertical display overlay
• Top bezels - 2
• MultiLink software CD
• MultiLink serial cable, 10 ft (3m)
• Rack mount handles
• Battery retaining brackets and screws - 2 each
• Support base - 2
• Mounting hardware
• Configuration program CD
• DB-9 port cover
What’s Included
Top bezels
(tower use)
Vertical display overlay
Rack mount
handles
Battery retaining brackets and screws
MultiLink
software CD
Mounting hardware
Support Base
with Spacers
MultiLink
serial cable
10 ft (3m)
www.liebert.com
GXT2U ™ Configuration Pr ogram
For use with Liebert GXT2U model UPS systems. Version 1.6 For Windows XP, 2000 NT, 98
Configuration
disk
DB-9 port cover
10
DISCONTINUED
Page 15
5.0 INSTALLATION AND CONFIGURATION
Do NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until instructed to do so in 6.0 - Initial Start-Up and Electrical Checks.
Visually inspect the UPS for freight damage. Report any damage to the carrier and your local dealer or Liebert representative.
CAUTION
!
The UPS is heavy (see 13.0 - Specifications). Take proper precautions when lifting or moving it.
Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place it where air flows unrestricted around the unit. The installation location must be free of water, flam­mable liquids, gases, corrosives and conductive contaminants. Maintain a minimum clearance of 4 inches (100mm) in the front and rear of the UPS. Maintain an ambient temperature range of 32-104°F (0 to 40°C).
NOTE
UPS operation in sustained temperatures above 77°F (25°C) reduces battery life.
5.1 Install the Main Cabinet
Installation and Configuration
The GXT2-6000RTL630 may be installed in either a tower configuration or in a rack, depending on available space and use considerations. Determine the type of installation and follow the appropriate instructions in either 5.1.1 - Tower UPS Installation or 5.1.2 - Rack-Mount UPS Installation.
5.1.1 Tower UPS Installation
When using the GXT2-6000RTL630 in a tower configuration, use the included support base (shown below, left) to stabilize the UPS. If any external battery cabinets are added, they will include spacers to accommodate the additional cabinets (shown below, right).
Attach Bezels to Top
When used as a tower, the GXT2-6000RTL630 requires bezels attached to the top. To connect the bezels:
1. Position the UPS so that the battery compartments are on the right side.
2. Attach the top bezels by placing them on the mounting holes and sliding them toward the rear of the UPS.
Figure 5 Tower-use support bases, spacers for external battery cabinets
3U
3U
3U
2U
2U
2U
2U
5U support base for GXT2 End bases and 3U spacer
11
Spacers added to support base to accommodate additional battery cabinets
DISCONTINUED
Page 16
5.1.2 Rack-Mount UPS Installation
When using the GXT2 in a rack-mount configuration, the UPS must be supported by a slide kit, fixed rails or a shelf.
When using the optional Adjustable Rack Mount Kit, you will use the following instructions. The fig­ures accompanying 5.1.3 - Installing the Adjustable Rack-Mount Kit—Sold Separately shows the positioning of the rack-mounting brackets. Liebert recommends taking the internal batteries out of the UPS during rack installation. This will make the UPS cabinet lighter and easier to handle.
CAUTION
!
Only three (3) M4 screws are used on the side of the GXT2 where the Power Distribution Box is located. The fourth mounting hole is above the Power Distribution Box and is not used.
5.1.3 Installing the Adjustable Rack-Mount Kit—Sold Separately
This kit contains parts needed to mount several different models of UPS and external battery cabi­nets into EIA310-D standard four-post racks that are 18-32" deep (457-813mm). The weight limit per pair of adjustable rack-mounting brackets is 200 lb (91kg).
Parts included are:
Item Quantity
Rear bracket members 2
Front bracket members 2
Inner bracket members 2
M4 x 8mm machine screws 16
M4 locking hex nuts 8
M5 x 16 mm machine screws 12
Grease packet. 1
Installation and Configuration
Tools needed for installation are:
• one Phillips screwdriver
• one 7mm wrench
The adjustable rack-mounting brackets (Part#: RMKIT18-32) feature retaining latches to prevent users from inadvertently sliding the UPS or battery cabinet out of the rack.
To install the rack mount brackets:
1. Unpack two (2) rack-mounting bracket assemblies and mounting hardware from this kit. Bracket assemblies are interchangeable between left-hand or right-hand.
Remove inner member of each bracket assembly as shown at right by extending it to its outermost position, depress­ing the retaining latch and then pulling the inner member out of the bracket assembly.
2. Determine the height position inside the rack enclosure where you want to mount the UPS or battery cabinet.
CAUTION
!
Reduce the risk of tipping the rack enclosure by placing the UPS or battery cabinet in the lowest possible rack position.
Retaining Latches
Inner members
Return flanges
Front members
12
DISCONTINUED
Page 17
Installation and Configuration
M5
3. Install the rear member of each bracket assembly into the rack enclosure with two (2) M5 screws provided in this kit (see figure at right). The return
Front rack mounting rails
screws
flanges on the bracket assembly fit to the inside of rack mounting rails. Insert screws loosely (finger­tight) into the top and bottom holes of the return flange on the rear member. Extend the bracket assembly by sliding the front member forward until it touches the front rack mounting rail. Insert two (2) M5 screws loosely (finger-tight) into the top and bottom holes of the return flange on each front member. Make sure that the bracket assemblies are at the same mounting height on all four (4) rack
M5 screws
Rear rack mounting rails
mounting rails.
4. Get eight (8) M4 screws and eight (8) M4 nuts from the hardware pack in this kit. Each nut has a
M4 nuts
M4 screws
locking, nylon insert that begins gripping the screw when it is halfway tight. Make sure to tighten the nut and screw completely to ensure locking action. Fasten the rear member and the front member together using (4) screws and (4) nuts per bracket assembly as shown in at right. For maximum support, insert fasteners for each bracket assembly as far apart as possible, depending on rack depth, while still joining both members (see figures at right). Check alignment of bracket assemblies and
457mm (18") rack depth
M4 nuts
TIGHTEN ALL SCREWS FROM Steps 2 and 3.
5. Prepare the UPS or battery cabinet (the “equipment”) for rack mounting by following instructions in the equipment’s user manual. The
M4 nuts
M4 screws
equipment may require additional parts to be added or parts to be removed for rack mounting. After it is prepared, lay the equipment in rack­mounting position. Fasten the inner members from Step 1 to the equipment on both sides as shown at right with seven (7) M4 screws provided in the kit. Make sure retaining latch is near the rear of the
813mm (32") rack depth
M4 nuts
equipment as shown (see figure below right).
6. Open the grease packet provided in the kit. Apply a bead of grease 25mm (1") long at four (4) places
M4 screws
Retaining latch
inside the bottom, curved tracks of the front members as shown below right. The grease will allow the equipment to slide into the bracket assemblies more easily.
CAUTION
!
6.
Lifting equipment into the rack may be a two­person job, depending on the weight of the
UPS or battery cabinet
equipment. Liebert recommends taking the internal batteries out of the UPS during rack
Front
installation. This will make the UPS cabinet lighter and easier to handle. The GXT2-
M4 screws
6000RTL630 weighs 151 lb (67kg). For the battery cabinet’s weight, see the unit’s user manual.
13
DISCONTINUED
Page 18
Installation and Configuration
Appl
7. Insert the equipment, with inner members attached in Step 5, into the bracket assemblies by inserting the top and bottom edges of the inner members into the top and bottom curved tracks of the front members and sliding the equipment into the rack (see figure at right). Ends of inner members are tapered to allow the rear of the equipment to be angled upward before insertion, if space allows.
Then the rear, bottom edges of the inner members can be placed into the front edge of the bottom tracks and the front of the equipment can be tipped up so they are level to insert the top edges of the inner members before sliding the equipment into the rack (see figure below right). The equipment should move smoothly into the bracket assemblies. If it does not, recheck the alignment of the front and rear members from Steps 2 and 3.
8. Secure the front of the equipment to the rack mounting rails to prevent the equipment from sliding out of position. If securing holes are provided on the front of the equipment that align with the center holes on the return flange of the front members, you can use the four (4) extra M5 screws provided in the kit to secure the equipment. Otherwise, the equipment should be secured to the front of the rack with four (4) customer-supplied fasteners.
y
grease
UPS or battery cabinet
Apply grease (inside)
... and push it into the rack.
Insert the UPS into the front members, lift the front .. .
5.2 Install the Internal Batteries
For ease of installation and configuration, the GXT2-6000RTL630 is shipped without its internal bat­teries installed. After the UPS is prepared and installed as either a tower or in a rack, install the GXT2-240BATKIT battery packs.
To install the internal batteries:
CAUTION
!
A battery can present a risk of electrical shock and high short circuit current. Observe the following precautions before replacing the batteries:
• Remove rings, watches and other metal objects.
• Use a Phillips (cross-head) screwdriver with insulated grips.
• Do not lay tools or other metal objects on top of the batteries.
• If the battery replacement kit is damaged in any way or shows signs of leakage, contact
your local dealer or Liebert representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
• Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It is
toxic.
14
DISCONTINUED
Page 19
Installation and Configuration
1. Remove the 3U battery access panel on the front of the GXT2-6000RTL630 by loosening the two captive screws located between the bezels (see illustration at left).
Battery Door Captive Screws
!
UPStation GXT
UPStation GXT
AC OUTPUT BATTERY UPS ON BYPASS
!
- +
AC INPUT
BATTERY UPS ON BYPASS
3U Battery Access Door and
Battery Bezel
Battery Connectors
Retaining screw
2. Once the captive screws are loosened, tip the panel forward and lift to remove it from the main cabinet.
3. Unpack the GXT2-240BATKIT battery assembly.
4. Line up and slide in the battery pack while holding the internal connector out of the way.
5. Connect the electrical cables to each battery pack with the two slotted battery connectors.
6. Install the battery retaining brackets supplied in the accessory box.
7. Install the battery access panel and tighten the captive screws.
5.3 Connect the Internal Batteries Using the External Connector
The connector attaches to the UPS in both the open and closed position using two screws. The picture on the left shows the connector in the open position, as shipped.
When the UPS is installed, remove the two screws to release the connector. Plug the connector into the socket. The internal batteries are now connected to the UPS electronics. Install the two screws to secure the connector in the closed position.
Retaining bracket (one of two)
Remove these screws
to release connector
5.3.1 Storage
If the UPS is to be shipped or stored for an extended time, the connector should be removed and attached in the open position, as shown above. This will minimize any standby current drain on the batteries.
5.4 Connect Input/Output Power
The Power Distribution box is shipped separately for easier handling of the UPS while the UPS is being placed in its final position.
15
DISCONTINUED
Page 20
5.4.1 Attach Power Distribution Box
Whenever the power distribution box is not attached to the UPS, the cover must be slid over the elec­trical connections to prevent damage or injury.
To attach the PD-L630 power distribution box to the UPS:
1. Loosen the white cover over the electrical connections by backing out the three screws securing the cover one turn each.
2. Slide the cover open to expose the electrical connectors.
3. Gently retighten the three screws loosened in Step 1.
4. Align the connectors on the box and UPS.
5. Push the box into place.
6. Holding the box firmly against the UPS, tighten the three captive mounting screws until the box is secure. Do not overtighten.
Figure 6 PD-L630 power distribution box
Installation and Configuration
FRONT of PD-L630 power distribution box
These captive screws attach the power distribution box to the UPS
UPS
MAITANENCE BYPASS
AVAILABLE
AVAILABLE
UPS
UTILITY
ON
OFF
BREAKER 30A
OUTPUT BREAKER 20A 240V~/T
OFF
OUTPUT ONLY CB DOES NOT CONNECT BYPASS POWER TO MANUAL BYPASS SWITCH.
ON
OUTPUT BREAKER 20A 240V~/T
OFF
INPPUT
ON
INSIDE FACE of PD-L630 power distribution box
CONNECTOR PROTECTIVE COVER DO NOT REMOVE SCREWS PRIOR TO INSTALLATION OF BOX ON UPS
-LOOSEN THREE SCREWS 1 TURN
- SLIDE COVER TO EXPOSE CONNECTOR
-TIGHTEN SCREWS GENTLY UPON REMOVAL OF BOX FROM UPS
-LOOSEN THREE SCREWS 1 TURN
-SLIDE COVER TO REACH END SCREW AND COVER COMMUNICATION
-TIGHTEN SCREWS GENTLY
Loosen these three Slide the cover over the connectors when the power distribution box is removed from the UPS.
screws to move the
cover. Retighten the
screws after moving
the cover over the
connectors or off the
connectors.
16
DISCONTINUED
Page 21
5.4.2 Distribution Box Electrical Connections
Electrical connections are made through a removable power distribution box that attaches to the rear of the UPS.
The installer must provide a 30A branch circuit breaker, with NEMA L6-30R receptacle. The Input circuit breaker on the distribution box and the Output circuit breaker on the rear fixed-panel of the UPS disconnect all power between the main cabinet and the distribution box.
Models equipped with a manual bypass switch pass bypass power directly to the bypass switch from the input power cord. The input circuit breaker on the distribution box does not disconnect power from the manual bypass switch.
Figure 7 PD-L630 power distribution box electrical connections diagram
Installation and Configuration
Utility Input
30A External 2-Pole Branch Circuit Breaker
Utility
30
Input
CB
30
UPS
UPS
Output
CB
UPS - PFC, Battery, Inverter
Output
17
DISCONTINUED
Page 22
5.5 External Battery Cabinet Installation
Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed on one side of the UPS or stacked beneath the UPS.
CAUTION
!
The external battery cabinet(s) are heavy (see 13.0 - Specifications). External battery cabinets can be used in rack-mount or tower configuration. Take proper precautions when lifting them.
1. Visually inspect the external battery cabinet for freight damage. Report damage to the carrier and your local dealer or Liebert representative.
2. For slide rail installations, first remove the top/side fin. Top/side fin slides forward and then lift up to remove. Optional rack-mount handles are shipped with the external battery cabinet and may be installed at this time if desired.
3. Securing hardware and slide rails are sold separately. Please contact your local dealer or Liebert representative for these additional options and any assistance needed. Fasten the slides into position with the screws per the instructions included with the slide rails.
4. Use the enclosed support bases for the tower option to prevent tip-over. One additional set of support base extensions ships with each external battery cabinet.
5. Connect the supplied external battery cabinet cable to the rear of the external battery cabinet, then to the rear of the UPS.
6. The UPS is now equipped with additional backup battery run time. For approximate battery run times, refer to Table 5.
Installation and Configuration
CAUTION
!
Do not turn on (close) the battery cabinet circuit breaker yet. Complete the installation first.
NOTE
You must use the included configuration program to program the UPS for the number of external battery cabinets connected. Instructions for the configuration program are in
7.0 - Configuration Program.
3U
2U
Spacers added to support base to accommodate additional battery cabinets
2U
INTERNAL BATTERY
CONNECTOR INSTALL
BEFORE OPERATING
ATTACH JUMPER
HERE FOR SHIPPING
AND EXTENDED
STORAGE
+
EXT. BATTERY
240V 25A
-
ON
OUTPUT BREAKER 30A/250V~T
OFF
COMMUNICATION PORT
SEE MANUAL
FOR CONNECTIONS
REPO
ON
OFF
BREAKER 30A
OFF
OUTPUT ONLY CB DOES NOT
CONNECT BYPASS POWER TO
MANUAL BYPASS SWITCH.
ON
INPPUT
RELAY CARD USB/WEB CARD
OUTPUT
BREAKER
20A 240V~/T
ON
OFF
OUTPUT
BREAKER
20A 240V~/T
AVAILABLE
UPS
UPS
MAITANENCE BYPASS
AVAILABLE
UTILITY
18
DISCONTINUED
Page 23
6.0 INITIAL START-UP AND ELECTRICAL CHECKS
1. Verify that the input and output circuit breakers are off (open).
2. During initial system checks, disconnect all loads (open load disconnects).
3. Inspect all wiring, cables, and connection.
4. If external battery cabinets are used, verify that the battery interconnect cables are fully inserted in the sockets.
5. Turn on (close) the battery cabinet circuit breaker.
6. On the power distribution box, place the Manual Bypass Switch in the UTILITY position.
7. Turn on (close) the branch circuit disconnect to apply voltage to the input.
8. Using a voltmeter, verify the expected L1-L2 voltage. Verify the same voltage is measured at the output receptacles. The BYPASS lamp by the Manual Bypass Switch will light.
9. After verifying proper input voltage to the UPS, turn on the Input circuit breaker located on the distribution box. The green AC Input indicator should illuminate on the UPS’ front panel.
10. Press the On button for 1 second. The BYPASS lamp will light for several seconds before the UPS ON lamp turns on continuously. If the batteries are determined to be charged above 80%, an automatic battery test will run for about 15 seconds.
11. Turn on (close) the output circuit breaker on the rear of the UPS. The UPS lamp on the power distribution box by the Manual Bypass Switch will light. Transfer the switch to the UPS position. The output will now be powered by the UPS.
12. Perform a Manual Battery Test - Press the ON button for 1 second. The front BATTERY lamp will light for about 15 seconds and then return to only the UPS ON and AC INPUT lamps being on.
13. Review all setting options provided by the configuration program. Some changes require that the UPS be Off. If this is the case, these should be programmed before powering the loads. The configuration program is described in 7.0 - Configuration Program.
14. Connect all loads for normal operation.
Initial Start-Up and Electrical Checks
19
DISCONTINUED
Page 24
7.0 CONFIGURATION PROGRAM
The final step of installation may require custom configuration of your UPS using the enclosed config­uration program. Some configuration settings may be changed only while the UPS is off. These should be set before the UPS is put into full-time service powering the critical load.
For most users operating with 208VAC and with no external batteries, the factory default settings will be adequate.
The configuration program user manual is included as a PDF on the CD that shipped with the UPS.
7.1 GXT2-6000RTL630 Configuration Program Features
• Select one of four L-L output voltages to match local voltages.
• Enable/Disable Auto-Restart.
• Select frequency converter operation with a fixed output frequency of 50 or 60 Hz.
• Set the Low Battery Warning alarm time from 2 to 30 minutes.
• Enable/Disable the Auto-Battery test.
• Set the Auto-Battery test to 7, 14, 21, or 28 days.
• Specify the number of external battery cabinets connected to the UPS to adjust the remaining run time calculations reported by Liebert software products.
• Modify the shutdown setting of DB-9 pin 6 (for information on pin assignments, see Table 1).
7.1.1 What You Will Need
Configuration Program
In addition to the GXT2 UPS, you will need the configuration program CD and serial cable (beige or
tan, 3-wire: GND, TX, RX; straight through 2-2, 3-3, 5-5) included in the UPS accessory box. A Win­dows 95® or later computer, desktop or laptop, is also required to set up and run the configuration
program.
!
AC OUTPUT BATTERY UPS ON BYPASS
UPStation GXT
www.liebert.com
GXT2U™ C onfiguration Pr ogram
For use with Liebert GXT2U model UPS systems. Version 1.6
GXT2-6000RTL630
For Windows XP, 2000 NT, 98
Configuration Program CD
Serial Cable
Laptop
20
DISCONTINUED
Page 25
8.0 CONTROLS AND INDICATORS
Controls and Indicators
All indicators illuminated for illustration only.
UPStation GXT
BATTERY UPS ON BYPASSAC INPUT
8.1 ON/Alarm Silence/Manual Battery Test Button
This button controls output power to connected load(s) and has three functions:
• ON
• Alarm Silence
• Manual Battery Test
ON - Pressing this button will start up the UPS in order to provide conditioned and
protected power.
Alarm Silence - To silence alarms, press this button for at least one Second. After the alarm is silenced, the GXT2-6000RTL630 will reactivate the alarm system to alert of additional problems.
NOTE
The LOW BATTERY and BYPASS reminder alarms CANNOT be silenced.
Manual Battery Test - To initiate a manual battery test, press the ON button for at least one second while operating from utility power with no alarm conditions present.
• If only three of the five Battery LEDs illuminate, allow the UPS to recharge the batteries for 24
hours.
• After 24 hours, retest the batteries.
• After the batteries have been retested, if only three of the five Battery LEDs illuminate, contact your local dealer, Liebert representative or Liebert Worldwide Support Group.
8.2 Standby/Manual Bypass Button
This button controls output power to connected load(s) and has dual functions:
Standby and Manual Bypass.
CAUTION
!
Pressing the Standby/Manual Bypass button once will transfer the load to bypass power. Pressing the Standby/Manual Bypass button a second time within 4 seconds will cut off power to the output
receptacles and connected loads. Perform all necessary shutdown procedures on connected loads before pressing this button twice.
21
DISCONTINUED
Page 26
8.3 Load Level Indicators (4 Green, 1 Amber)
The load level indicators display the approximate electrical load placed upon the UPS at all times.
8.4 Battery Level Indicators (5 Green)
The battery level indicators display approximate battery capacity at all times.
The GXT2-6000RTL630 is equipped with automatic and remote battery test features. The automatic test occurs every 14 days (this option is user configurable) if utility power has not been interrupted. Should the battery fail this test, the red Fault indicator LED along with the A and C diagnostic LEDs will illuminate and an alarm will sound (refer to 12.0 - Troubleshooting). The remote test feature functions with MultiLink 3.x software and can remotely initiate the battery test.
8.5 Fault Indicator LED (Red)
The Fault indicator LED is illuminated if the UPS has detected a problem. Also, one or more of the battery level indicators may be illuminated (refer to 12.0 - Troubleshooting).
8.6 Bypass Indicator LED (Amber)
The Bypass indicator LED is illuminated when the UPS is operating from bypass power. An alarm will sound indicating the UPS detected a problem, or the manual bypass function has been activated.
Controls and Indicators
8.7 UPS ON Indicator LED (Green)
The UPS ON indicator LED is illuminated when the UPS inverter is operating and supplying power to the connected loads.
8.8 Battery Indicator LED (Amber)
The Battery indicator LED is illuminated when the UPS is operating on battery.
8.9 AC Input Indicator LED (Green)
The AC Input indicator LED is illuminated when utility power is available and within the input spec­ifications.
22
DISCONTINUED
Page 27
9.0 OPERATING INSTRUCTIONS
AC INPUT
9.1 Normal Mode Operation
During normal operation, utility power provides energy to the UPS. The filters, power factor correction circuit and the inverter process this power to provide computer grade power to connected loads. The UPS maintains the batteries in a fully charged state. The four green load level LEDs indicate an approximate level of load in 25% increments. If the UPS becomes loaded beyond full rating, the fifth (amber) LED indicator will illuminate and the UPS will sound an audible alarm. The display template indicates the percentage of load (10% of load shown in example) on the UPS output.
9.2 Battery Mode Operation
Battery mode occurs in event of an extreme input voltage condition or complete utility failure. The battery system supplies power through the DC to DC converter to the inverter to generate power for the connected load. During battery mode an alarm sounds every 10 seconds. This will change to two beeps every 5 seconds when the battery runs low (approximately 2 minutes remaining, but this is user configurable). The AC Input LED will extinguish, and the Battery LED will illuminate to warn that a utility problem has occurred. Each battery level indicator represents a 20% capac­ity level. As capacity decreases, fewer indicators remain illumi­nated. Refer to 12.0 - Troubleshooting. For approximate battery run times, refer to Table 5. These times are approximate, based on resistive load and an ambient temperature of 77°F (25°C). To increase this time, turn off non-essential pieces of equipment (such as idle computers and monitors) or add the optional external battery cabinet.
Operating Instructions
BATTERY UPS ON BYPASSAC INPUT
Normal Mode Operation Batteries at 100% Charge Load at 10%
Battery Mode Operation Batteries at 30% Charge Load at 50%
CAUTION
!
Turning OFF the UPS while in it is battery mode will cut off output power.
9.3 Bypass Mode Operation
Bypass mode occurs when the OFF button is pressed once while the UPS is in Normal Mode. During bypass operation, utility power provides energy to the UPS. The utility power bypasses the inverter and provides power for the connected load.
The four green load level LEDs indicate an approximate level of load in 25% increments. If the UPS becomes loaded beyond full rating, the fifth (amber) LED indicator will illuminate and the UPS will sound an audible alarm. The display template indicates the percentage of load (26-50% of load shown in the example above) on the UPS output.
9.4 Battery Recharge Mode
Once utility power is restored, the UPS resumes normal operation. At this time, the Battery Charger begins recharging.
UPS ON BYPASS
23
DISCONTINUED
Page 28
10.0 COMMUNICATIONS
r
10.1 Communications Interface Port
The GXT2-6000RTL630 has a standard DB-9 serial port female connector located on the rear of the UPS unit. Several signals are provided on this port and are assigned as follows:
Table 1 DB-9 pin assignment
DB-9
Assignment Description
Pin
1 Low Battery (open collector)
2 UPS TxD (typically RS-232 levels)
3 UPS RxD (typically RS-232 levels)
4 Remote Shutdown (5-12VDC, 10-24mA max; battery operation)
5 Common
6 Remote Shutdown (short to pin 5); all modes of operation
7 Low Battery (open emitter)
8 Utility Power Failure (open emitter)
9 Utility Power Failure (open collector)
Communications
Pin Assignment Collector to Emitter*
6789
54321
* Maximum voltage and current on pins 1, 7, 8 and 9 are 60VDC and 10.0 mA
10.2 Pin 4 - Remote Shutdown on Battery
1. This pin is functional only when the UPS is in battery mode. If the UPS is being powered by utility power, Pin 4 will ignore any signal on this pin.
2. Pin 4 requires a 5-12 VDC signal to shutdown. This normally comes from the serial port using Liebert's contact closure cable. It cannot be used with just a contact closure unless the relay is used to switch a voltage source. A 5-12 VDC signal for 1.5 seconds or greater is required to signal a shutdown. Signals for less than 1.5 seconds will be ignored. After Pin 4 receives a shutdown signal for 1.5 seconds, the command cannot be canceled.
3. A battery shutdown signal on Pin 4 will NOT cause an immediate Shutdown. A shutdown signal will start a 2-minute shutdown timer. The timer cannot be stopped. After 2 minutes, the UPS will shut down.
4. If utility power returns during the 2-minute timer countdown, the shutdown timer will continue until the end of 2 minutes and the UPS will turn OFF. The UPS must remain OFF for at least 10 seconds even if AC input power Returns before the UPS turns OFF. This serves to reset and restart the server.
330 Ohms
(+)
(-)
Open Collecto
Open Emitter
Whether the UPS turns back ON when power is restored depends on the auto-restart setting: enabled or disabled.
If the auto-restart is disabled, the UPS will not restart after performing the 2-minute shutdown delay.
24
DISCONTINUED
Page 29
10.3 UPS Intelligent Communications
The GXT2-6000RTL630 is equipped with two Intellislot® ports to provide advanced communication and monitoring options.
The Intellislot port closer to the corner of the UPS chassis is the serial card slot. This Intellislot port is used for the OCWEBCARD and the USBCARD. The other Intellislot port is used for RELAYCARD-INT or the MULTIPORT Card.
Liebert’s OCWEBCARD
Communications
DB9 (RS232) port covered
NOTE
The OCWEBCARD DB9 serial port cable should be used only for the initial card setup. Remove the cable after setup is complete.
When the DB9 OCWEBCARD serial port cable is removed, the OCWEBCARD DB9 connector needs to be covered. The DB9 cover is included with the UPS.
Liebert's MultiLink software continually monitors the UPS and can shut down your computer or server in the event of an extended power failure.
MultiLink can also be configured for use without the serial cable when the Intellislot SNMP/Web card is installed in the UPS. Additionally, MultiLink can be configured to coordinate shutdown across the network with other computers running MultiLink when you purchase a MultiLink License Kit. For more information about the Intellislot SNMP/Web Card and MultiLink license Kits, visit our Web site (www.liebert.com) or contact your local dealer or Liebert representative.
Several option cards are available for use in the Intellislot port of the GXT2-6000RTL630. The Intel­lislot SNMP/Web Card provides SNMP and Web-based monitoring and control of the UPS across the network.
The Intellislot MultiPort 4 Card allows you to install MultiLink software on four computers and coor­dinate shutdown in the event of a power failure.
The Intellislot Relay Card provides dry contact relay outputs for custom wired applications and deliv­ers support for built-in shutdown for AS/400 systems.
CAUTION
!
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should be segregated and run separate from all other power cables, where applicable.
25
DISCONTINUED
Page 30
10.4 Remote Emergency Power Off
The UPS is equipped with a Remote Emergency Power Off (REPO) connector.
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS input feeder breaker to remove all sources of power to the UPS and connected equipment to comply with national and local wiring codes and regulations.
REPO switch connection diagram
UPS ships with REPO jumper installed allowing the UPS to operate
Communications
Opening the REPO connection will disable the UPS. Manual restart using the front panel is required after the REPO connection is closed again.
12
Normally closed switch system (fail-safe)
CAUTION
!
To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should be segregated and run separately from power cables.
12
26
DISCONTINUED
Page 31
11.0 MAINTENANCE
11.1 Internal Battery
The GXT2-6000RTL630 requires very little maintenance. The batteries are valve-regulated, non­spillable, flame retardant, lead acid, and should be kept charged to obtain their designed life. The UPS continuously charges the batteries when connected to the utility supply.
When storing the UPS for any length of time, it is essential to plug the UPS in for at least 24 hours every four to six months to ensure full recharge of the batteries. Failure to recharge the batteries peri­odically will result in permanent degradation of battery capacity.
UPStation GXT
- +
AC INPUT
Maintenance
!
BATTERY UPS ON BYPASS
The GXT2-6000RTL630 is designed to allow the user to safely replace the internal batteries. Read the safety cautions before proceeding. Contact your local dealer or Liebert representative to obtain the appropriate replacement battery kit part number and pricing.
27
DISCONTINUED
Page 32
11.1.1 Internal Battery Replacement
CAUTION
!
A battery can present a risk of electrical shock and high short circuit current. Observe the following precautions before replacing the batteries:
• Remove rings, watches and other metal objects.
• Use a Phillips (cross-head) screwdriver with insulated grips.
• Do not lay tools or other metal objects on top of the batteries.
• If the battery replacement kit is damaged in any way or shows signs of leakage, contact
your local dealer or Liebert representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
• Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It is
toxic.
Maintenance
1. Remove the 3U battery access panel on the front of the UPS by loosening the two captive screws located between the bezels (see illustration at right).
2. Once the captive screws are loosened, tip the panel forward and lift to remove it from the main cabinet.
3. Use a Phillips (cross-head) screwdriver to remove the screw in the battery retaining bracket on each battery pack (see illustration at right). Remove the retaining brackets.
4. Disconnect the battery connectors in the front of each battery pack.
5. Lift the internal connector out of the way and slide the battery out of the UPS. Support the weight of the battery to prevent it from falling.
6. Unpack the new battery assembly, taking care not to destroy the packing. Compare new and old battery assemblies to make sure they are the same. If so, proceed with Step 7; otherwise STOP and contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
7. Line up and slide in the new replacement battery pack while holding the internal connector out of the way.
8. Reconnect the electrical connections for each battery pack.
9. Install the battery retaining brackets using the Phillips removed earlier.
10. Install the battery access panel and tighten the captive screws.
Battery Door Captive Screws
!
3U Battery Access Door and
UPStation GXT
- +
Battery Bezel
AC INPUT
BATTERY UPS ON BYPASS
Retaining screw
!
UPStation GXT
AC OUTPUT BATTERY UPS ON BYPASS
Retaining bracket
!
UPStation GXT
- +
AC INPUT
BATTERY UPS ON BYPASS
NOTE
These are hot-swappable replacement batteries. However, caution should be exercised because during this procedure the load is unprotected from disturbances and power outages.
28
Battery Connectors
DISCONTINUED
Page 33
11.2 AC Power Connections
Power connections may be disconnected from the UPS cabinet via a removable distribution box. This may be a convenient feature if the UPS must be moved a short distance or replaced. This box allows power connections to be conveniently disconnection from the main UPS cabinet. A label is attached to the UPS to describe these procedures.
11.2.1 Disconnect
1. DO NOT turn off the branch circuit breaker feeding power the box unless you intend to disconnect all power to the load.
2. Ensure that the Maintenance Bypass Lamp is ON.
3. Switch to the maintenance bypass position. The load is now unprotected from line disturbances or interruptions.
4. Turn off the UPS using the front panel controls. a. If needed, push the OFF button for one second once to transfer the load to bypass. b. Press the OFF button twice within four seconds to turn the UPS off.
5. Turn off the UPS input circuit breaker on the box at the rear of the UPS. This input circuit breaker cuts off power only from the connector between the box and UPS. The
input circuit breaker does not cut off power from the manual bypass switch.
6. Turn off the output circuit breaker on the rear of the UPS.
7. Remove the distribution box from the UPS a. Loosen all three captive screws until the box releases. b. Pull box away from the UPS and set the box aside on a padded surface.
8. Loosen the cover over the electrical connections by backing out the three screws one turn each.
9. Slide the cover over the electrical connections.
10. Gently retighten the three screws loosened in Step 8. Whenever the power distribution box is not attached to the UPS, the cover must be slid over the
electrical connections to prevent damage or injury.
Maintenance
CAUTION
!
Power is still passing through the power distribution box from the utility supply to the load.
Figure 8 Power distribution box, PD-L630
Protective Cover Over Connectors
CONNECTOR PROTECTIVE COVER DO NOT REMOVE SCREWS
PRIOR TO INSTALLATION OF BOX ON UPS
-LOOSEN THREE SCREWS 1 TURN
- SLIDE COVER TO EXPOSE CONNECTOR
-TIGHTEN SCREWS GENTLY
UPON REMOVAL OF BOX FROM UPS
-LOOSEN THREE SCREWS 1 TURN
-SLIDE COVER TO REACH END SCREW AND COVER COMMUNICATION
-TIGHTEN SCREWS GENTLY
Captive Screws
(attach
box to
UPS)
Rear View
Maintenance
Bypass Lamps
Front View
Maintenance
Bypass Switch
UPS
MAITANENCE BYPASS
AVAILABLE
AVAILABLE
UPS
UTILITY
ON
ON
OUTPUT BREAKER
OUTPUT
20A 240V~/T
BREAKER
OFF
OFF
ON
OUTPUT ONLY CB DOES NOT CONNECT BYPASS POWER TO MANUAL BYPASS SW
20A 240V~/T
INPPUT
ITCH.
OFF
BREAKER 30A
29
DISCONTINUED
Page 34
11.2.2 Reconnect
1. Loosen the cover over the electrical connections by backing out the three screws one turn each.
2. Slide the cover open to expose the electrical connectors.
3. Gently retighten the three screws loosened in Step 1.
4. Align connectors and press the box onto the rear of the UPS.
5. Hold the box firmly against the UPS and tighten the captive screws. Do not overtighten.
6. If the utility branch circuit breaker and load is off, turn the branch breaker on now.
7. Turn on the output circuit breaker on the rear of the UPS.
8. Turn on the input circuit breaker on the power distribution box.
9. Start the UPS according to the startup instructions. Press the ON button for one second.
10. Confirm that the UPS AVAILABLE lamp is lit beside the manual bypass switch.
11. Turn the manual bypass switch to the UPS position.
12. The UPS now protects the load.
Maintenance
30
DISCONTINUED
Page 35
12.0 TROUBLESHOOTING
AC INPUT
The information below indicates various symptoms a user may encounter in the event the GXT2-6000RTL630 develops a problem. Use this information to determine whether external factors caused the problem and how to remedy the situation.
1. The Fault indicator will illuminate, indicating the UPS detected a problem.
2. An alarm will sound, alerting that the UPS requires attention.
3. 3. One or more additional battery level LED indicators will be illuminated to provide a diagnostic aid to the operator, as described below:
Table 2 Indicator meanings
Troubleshooting
Fault
Example shows UPS on bypass because of output overload, signified by amber load indicator.
LED status Diagnosis/Audible alarm
All LEDs On bypass due to output overload; beep every half-second
A LED On bypass due to overtemperature condition; beep every 4 sec.
B LED On bypass due to DC bus overvoltage; beep every 4 sec.
C LED DC-DC failure during battery mode; beep every 4 sec.
D LED On bypass due to PFC failure; beep every 4 sec.
E LED On bypass due to inverter failure; beep every 4 sec.
A&C LEDs UPS failed battery test; long beep every minute
C&E LEDs UPS shutdown due to command from communication port (SNMP); no beep
Battery LED Flashing
A&E LEDs Fan locked
B&C REPO active. UPS cannot run with REPO loop open.
B&D UPS is OFF due to previous REPO shutdown. Autorestart disabled.
D&E Charger Malfunction
Internal Battery source not available (continuous horn). Check Battery connection, completely power down and reboot UPS.
Under fault conditions, the Fault indicators will be illuminated indefinitely while battery charger is operational, or for a maximum of 5 minutes while the battery charger is not operational.
If a problem persists, consult your local dealer, Liebert representative or contact the Liebert World­wide Support Group. Please have the UPS model number and serial number available at the time of your inquiry.
31
DISCONTINUED
Page 36
Table 3 Troubleshooting guide
Problem
UPS fails to start when the ON button is pressed.
Battery indicator LED is illuminated.
UPS has reduced battery time.
Fault and Bypass indicator LEDs and all load level LEDs are illuminated.
Fault and Bypass indicator LEDs and diagnostic LED A are illuminated.
Fault and Bypass indicator LEDs and diagnostic LED B are illuminated.
Fault indicator LED and diagnostic LED C are illuminated.
Fault and Bypass indicator LEDs and diagnostic LED D are illuminated.
Fault and Bypass indicator LEDs and diagnostic LED E are illuminated.
Fault indicator LED and diagnostic LEDs A and C are illuminated.
Fault and Bypass indicator LEDs and diagnostic LED C and E are illuminated.
Fault and LEDs A&E are Illuminated
Fault and LEDs B&C are Illuminated
Fault and LEDs B&D are Illuminated
Cause Solution
UPS is short-circuited or overloaded.
UPS not plugged in.
UPS input protection has opened.
Utility voltage out of UPS input range.
Batteries are not fully charged.
UPS is overloaded. Check load level display and reduce the load on the UPS.
Batteries may not be able to hold a full charge due to age.
UPS overloaded or load equipment is faulty.
UPS internal fan has a problem or UPS shutdown due to temperature condition. Load is on bypass power.
UPS internal DC bus overvoltage.
DC-DC failure during battery mode.
UPS PFC (Power Factor Correction Circuit) fault.
UPS inverter fault.
UPS failed the battery test.
UPS shutdown due to a command from the communications port(s).
Fan locked
REPO active
UPS is OFF due to previous REPO shutdown, but the REPO has been connected or reset. Autorestart disabled.
Troubleshooting
Ensure UPS is OFF. Disconnect all loads and ensure nothing is lodged in output receptacles. Ensure loads are not defective or shorted internally.
UPS is operating from battery mode, make certain UPS is securely plugged into the wall receptacle.
UPS is operating from battery mode. Save data and close applications. Check UPS input circuit breaker, then restart UPS.
UPS is operating from battery mode. Save data and close applications. Ensure utility supply voltage is within acceptable limits for UPS.
Keep UPS plugged in continuously at least 24 hours to recharge batteries.
Replace batteries. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group for replacement battery kit.
Check load level display and remove non-essential loads. Recalculate the load and reduce number of loads connected to UPS. Check load equipment for faults.
Ensure UPS is not overloaded, ventilation openings not blocked, or room ambient temperature is not excessive. Wait 30 minutes to allow UPS to cool, then restart UPS. If UPS does not restart, contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
UPS requires service. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Bus voltage under 315VDC (O/P 220VAC) / 330VDC (O/P 230VAC) / 345VDC (O/P 240VAC). UPS requires service. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
UPS requires service. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
UPS requires service. Contact your local dealer, Liebert Representative or the Liebert Worldwide Support Group.
Replace batteries. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Your UPS has received a signal or command from the attached computer. If this was inadvertent, ensure the communication cable used is correct for your system. For assistance, contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Check for external obstruction entering fan guard. UPS requires service. Contact your local dealer, Liebert representative or Liebert Worldwide Support Group.
REPO circuit loop is open. If not used, a wire jumper must connect the REPO terminals.
Start the UPS using the front panel.
32
DISCONTINUED
Page 37
Troubleshooting
Table 3 Troubleshooting guide (cont’d)
Problem
Fault and LEDs D&E are Illuminated
Battery LED is flashing.
Cause Solution
If the charger is overvoltage, the UPS will shutdown. If the
Charger malfunction
Battery source is not available; continuous horn.
charger is undervoltage and the batteries are nearly depleted, this alarm will give a temporary warning before the UPS shuts down. UPS requires service. Contact your local dealer, Liebert representative or Liebert Worldwide Support Group.
Check battery connections, completely power down and restart UPS. NOTE: If the battery circuit opens while the UPS is running, it will be detected when the next battery test is performed.
Table 4 Alarm conditions
Condition Alarm
Battery Mode (utility failure) One short beep every 10 seconds: more than 2 minutes of run time remaining
Low Battery Two short beeps every 5 seconds: less than 2 minutes of run time remaining
Output Overload (Bypass) One short beep every half second
Overtemperature (Bypass) A one-second beep every 4 seconds
DC Bus Overvoltage (Bypass) A one-second beep every 4 seconds
DC-DC failure during battery mode
PFC Failure (Bypass) A one-second beep every 4 seconds
Inverter Failure A one-second beep every 4 seconds
Battery Test Failure A two-second beep every 1 minute
Fan Locked A one-second beep every 4 seconds
REPO Active A 0.25-second beep every 0.25 seconds
UPS OFF; Autorestart disabled from previous REPO shutdown
Charger Malfunction A one-second beep every 4 seconds
A one-second beep every 4 seconds
A one-second beep every 4 seconds
33
DISCONTINUED
Page 38
Troubleshooting
Table 5 Battery run times
Load% 6000VA
10% 94 20% 46 30% 29 40% 21
Internal Battery (minutes)
Internal Battery + 1 External Battery Cabinet (minutes)
Internal Battery + 2 External Battery Cabinets (minutes)
Internal Battery + 3 External Battery Cabinets (minutes)
Internal Battery + 4 External Battery Cabinets (minutes)
50% 17 60% 13 70% 11 80% 9 90% 8
100% 7
10% 222 20% 124 30% 81 40% 60 50% 49 60% 39 70% 33 80% 28 90% 24
100% 21
10% 350 20% 197 30% 135 40% 105 50% 85 60% 70 70% 58 80% 50 90% 43
100% 38
10% 478 20% 269 30% 185 40% 145 50% 123 60% 101 70% 85 80% 73 90% 63
100% 55
10% 606 20% 341 30% 235 40% 184 50% 156 60% 131 70% 113 80% 97 90% 85
100% 75
Using the configuration program, the user may specify the number of GXT2-240VBATTUL external battery cabinets attached to the UPS. The factory default is programmed for internal batteries only.
Table 5 above shows the estimated run times at different loads.
34
DISCONTINUED
Page 39
12.0.1 Auto-Learning Battery Run Times
As batteries age, the estimated runtimes may become less accurate. The GXT2-6000RTL630 is pro­grammed to “learn” from a full battery discharge and modify the estimated runtime for the measured battery capacity. This can improve accuracy and compensate for aging batteries or batteries that operate at different ambient temperatures.
The UPS will update the anticipated run time calculation only under certain conditions.
• The UPS must have a steady load that is greater than 20%.
• The UPS must be at 100% charge at the start of a battery discharge.
• The battery discharge must continue uninterrupted until the batteries reach their end-of-dis-
charge voltage.
If all conditions are not met, the run time calculation will not be modified.
If the configuration program is used to change the number of battery cabinets, then the values in the battery above table will be restored. This will override any value that is Auto-Learned.
Troubleshooting
35
DISCONTINUED
Page 40
13.0 SPECIFICATIONS
Table 6 UPS specifications
Model Number GXT2-6000RTL630
Dimensions, in. (mm)
Shipping, W x D x H 22.0 x 27.2 x 19.7 (560 x 690 x 500)
Weight, lb (kg)
Input AC Parameters
Nominal Operating Frequency 50 or 60Hz (Factory Default = 60)
Factory Default VAC 208VAC
User Configurable VAC
Operating Voltage Range Without
Battery Operation
Maximum Allowable VAC 276VAC
Input Frequency Without Battery
Input Power Connection L6-30P Plug (on PD-L630 power distribution box)
Output AC Parameters
Factory Default VAC 208VAC
Output Connections
Bypass Protection Limits
Disable Bypass operation If input voltage exceeds ±15% of the nominal voltage
Re-enable Bypass operation If input voltage returns to within ±10% of nominal output voltage
Disable Bypass operation When the input frequency prevents synchronous operation
Environmental
Operating Temperature 32°F to 104° F (0°C to 40°C)
Storage Temperature 5°F to 122° F (-15°C to 50°C)
Relative Humidity 0-95% non-condensing
Operating Elevation
Storage Elevation
Agency
Radiated Susceptibility EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient EN61000-4-4, Level 4, Criteria A
Model Rating 6000VA/4200W
Unit, W x D x H 8.7 x 21.5 x 16.9 (221 x 547 x 430)
Unit 57.2 (26)
Shipping 81.5 (37)
208/220/230/240VAC
(May be modified using configuration program)
176 – 276VAC
Operation
(2) L6-20R and (2) L6-30R on 12" (300mm) cords
(on PD-L630 power distribution box)
Frequency 50Hz or 60Hz, Nominal
Waveform Sinewave
Main Mode
Overload
Audible Noise
Safety UL, C-UL Listed to UL1778
EMI/EMC FCC Class B
ESD EN61000-4-2, Level 4, Criteria A
Surge Immunity EN61000-4-5, Level 3, Criteria A
Transportation ISTA Procedure 1B
>200% for 96 milliseconds; 131 - 199% for 2 seconds;
112- 129% for 10 seconds with transfer to bypass
Up to 6600 ft (2000m) at 104°F (40°C) without derating
50,000 ft. (15,000m) maximum
<55 dBA, at 3 ft. (1m) from the rear
<50 dBA, at 3 ft. (1m) from the front or sides
40 - 70Hz
Specifications
36
DISCONTINUED
Page 41
Table 7 Internal battery specifications
Model Number GXT2-240BATKIT
Dimensions, W x D x H, in. (mm)
Shipping 21.2 x 12.2 x 16.2 (539 x 311 x 412)
Weight, lb (kg)
Unit 44.5 (20.2) each, (2 required)
Shipping 93.9 (42.6), (2 batteries in a single carton
Type Valve-regulated, non-spillable, lead acid
Quantity x V 20 x 12V
Battery Mfr. / Part # Yuasa / REW 28-12FT
Electrical Characteristics
Back-up Time See Table 5 - Battery run times
Recharge Time 3 hrs. to 90% capacity after full discharge into 100% load
Table 8 Output distribution specifications
Model Number PD-L630
Dimensions, W x D x H, in. (mm)
Unit 5.3 x 6.9 x 3.5 (134 x 175 x 88)
Shipping 8.9 x 10.4 x 12.4 (225 x 265 x 315)
Weight, lb (kg)
Unit 30 (13.5)
Shipping 33 (15)
Electrical Specifications
Amp Rating 24 Amps
Input Power Connections L6-30P on 10-foot (3m) cord
Output Power Connection: L1-L2-G
(2) L6-30R on a 12" (300mm) cord (2) L6-20R on a 12" (300mm) cord
Specifications
37
DISCONTINUED
Page 42
Table 9 External battery cabinet specifications
Model Number GXT2-240VBATTUL
Used w/ UPS model GXT2-6000RTL630
Dimensions, W x D x H, in. (mm)
Unit (with bezel) 6.9 x 20.6 x 16.9 (176 x 522 x 430)
Shipping 22.0 x 27.2 x 17.9 (560 x 690 x 455)
Weight, lb (kg)
Unit 145 (65)
Shipping 173.1 (78.5)
Battery Parameters
Type Valve-regulated, non-spillable, flame retardant, lead acid
Qty x V 20 x 12V
Battery Manufacturer, Part # Yuasa / REW 45-12
Backup Time See Table 5 - Battery run times
Environmental
Operating Temp 32°F to 104°F (0°C to 40°C)
Storage Temp 5°F to 122° F (-15°C to 50°C)
Relative Humidity 0-95% non-condensing
Operating Elevation Up to 6600 ft. (2000m) at 104°F (40°C) without derating
Storage Elevation 50,000 ft. (15,000m) maximum
Agency
Safety UL, C-UL Listed to UL1778
Transportation ISTA Procedure 1B
Specifications
38
DISCONTINUED
Page 43
DISCONTINUED
Page 44
Ensuring The High Availability 0f Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility and reduced capital equipment and operating costs.
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2007 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
Technical Support / Service
Web Site
www.liebert.com
Monitoring
800-222-5877
monitoring@emersonnetworkpower.com
Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877
upstech@emersonnetworkpower.com
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
powertech@emersonnetworkpower.com
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
852 2572220
Fax: 852 28029250
SL-23452_REV0_04-07
Emerson Network Power. The global leader in enabling Business-Critical Continuity.
AC Power
Connectivity DC Power
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2007 Emerson Electric Co.
Embedded Computing Embedded Power Power Switching & Controls Monitoring
Outside Plant
Precision Cooling
EmersonNetworkPower.com
Racks & Integrated Cabinets Services Surge Protection
PRO DU C T
DISCONTINUED
Loading...