L
2
L 1
N
OUTPUT INPU T
60 Amp Max B r anch
Overcur r ent P r ot ect i on
L2 L1N L2 L1N
®
Liebert GXT2-10KIPPCBL
Quick-Start Guide
™
Disconnect the Liebert GXT2-10000RT208™ from all electri-1.
cal inputs.
Remove the top cover from the terminal block cover on the 2.
rear of the UPS. Set all screws aside for reinstallation.
Use a screwdriver or similar tool to remove the knockout.3.
Slip the locknut onto the input power cable.4.
Thread the input power cable through the knockout hole.5.
Slip the fixed ring onto the input power cable.6.
Connect the wires of the input power cable to the input 7.
power terminal block of the UPS according to the labels on
the wires (see Connect cable wires, below).
Each wire must be connected to the corresponding location 8.
on the input side of the terminal block.
Reattach the terminal block cover to the Liebert GXT2-9.
10000RT208 using screws removed in Step 2.
Leave a small amount of slack in the input power cable 10.
inside the terminal block and secure the cable to the
terminal block with the fixed ring and locknut (see Secure
cable to back cover, below).
Reattach the top cover to the terminal block using screws 11.
removed in Step 2.
Check the voltage of the input power supply to ensure that 12.
it matches the power requirements of the Liebert GXT210000RT208.
If the input power is correct, shut off power to the supply 13.
socket and mate the UPS to the socket.
Warnings
& Cautions
This input power cable
must be installed only
by properly trained and
qualified personnel.
Opening or removing
the cover of the UPS
may expose you to lethal
voltages within this unit
even when it is apparently not operating and
the input wiring is disconnected from the electrical source. Observe all
cautions and warnings
in this quick-start guide
and in the user manual
for the UPS, available
at the Liebert Web site,
www.liebert.com
Failure to do so may result in serious injury or
death.
L2
N
Wires are labeled
Connect cable wires
G
L1
Secure cable to back cover
Reattach terminal
block cover
Proper Input Power Connection
The GXT2-10KIPPCBL is an IEC 309-60A, L1-L2-N-G configuration, input power cable and plug
designed to work with the Liebert GXT2-10000RT208. This input plug should be connected to a
power outlet with an IEC 309-60A, L1-L2-N-G configuration.
Miswiring power to the input terminal block or connecting to single-phase voltages (L-N-G only)
may damage the UPS.
NOTE
For startup instructions, refer to the user manual for the Liebert GXT2-10000RT208,
SL-23444, available at the Liebert Web site, www.liebert.com
Emerson Network Power
Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability
through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical
systems.
Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit
from greater IT system availability, operational flexibility and reduced capital equipment and operating costs.
Technical Support / Service
Web Site
www.liebert.com
Monitoring
800-222-5877
Liebertmonitoring@emerson.com
Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877
upstech@emersonnetworkpower.com
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
powertech@emersonnetworkpower.com
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Emerson Network Power.
The global leader in enabling Business-Critical Continuity.
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson
Electric Co. EmersonNetworkPower.com
While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all
liability for damages resulting from use of this information or for any errors or omissions.
© 2008 Liebert Corporation. All rights reserved throughout the world. Specications subject to change without notice.
All names referred to are trademarks or registered trademarks of their respective owners.
® Liebert is a registered trademark of the Liebert Corporation.
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
852 2572220
Fax: 852 28029250
SL-23458_REV0_08-08