Emerson Fisher S201PK, Fisher S202, Fisher S202P, Fisher S203H, Fisher S203P1-P3 Installation Manual

...
Page 1
S200 Series
D400007XENG
Installation Guide English – May 2002
www.FISHERregulators.com
Introduction
This installation guide provides instructions for installation, startup, and adjustment. To receive a copy of the instruction manual, contact your local Fisher Sales Office or Sales Representative or view a copy at www.FISHERregulators.com. For further information refer to:
• Type S201 and S202 Instruction Manual, form 5171,
D400007X012
• Type S201P, S201PK, and S202P Instruction Manual,
form 5172, D400009X012
• Type S203, S203H, and S203P1-P3 Instruction Manual,
form 2216, D400010X1012
• Types S204 and S206 Instruction Manual, form 1749,
D400011X012
• Types S208 and S209 Instruction Manual, form5412,
D102247X012
P.E.D. Categories
This product may be used as a safety accessory with pressure equipment in the following Pressure Equipment Directive 97/23/EC categories. It may also be used out­side of the Pressure Equipment Directive using sound engineering practice (SEP) per table below.
EZISTCUDORPSEIROGETACEPYTDIULF
05,05x04,04,23ND
)2,2x2/1-1,2/1-1,4/1-1(
I1
Specifications
Available Constructions (See table 1)
S201: Basic construction without internal relief for
5 to 75 mbar (2 to 30-inches w.c.) outlet pressures S201H: S201 with a heavy diaphragm plate for 0,069 to 0,34 bar (1 to 5 psig ) outlet pressures S201K: S201 with a heavy diaphragm plate for 0,14 to 0,69 bar (2 to 10 psig) outlet pressures S201P: S201 with downstream control line connec­tion and O-ring stem seal for external pressure registration
S201PK: Combination of S201K and S201P S202, S202H, S202P: S201, S201H, and S201P
constructions with internal relief S203, S203H, S203P: S201, S201H, and S201P constructions with “True” monitor regulator to provide overpressure protection. Available in Cast iron body only. S204, S204H: S201 and S201H constructions with a low outlet pressure shutoff. Available in Cast iron body only. S206, S206H: S202 and S202H constructions with a low outlet pressure shutoff with internal relief.
Available in Cast iron body only. S208, S208H, S208P, S208K, S208PK: S201, S201H, S201P, S201K, and S201PK constructions with a Type VSX-2 slam-shut device to provide over­pressure (OPSO) or over and underpressure (UPSO) protection. Available in Ductile iron body only. S209, S209H, S209P: S202, S202H, and S202P constructions with a Type VSX-2 slam-shut device to provide overpressure (OPSO) or over and under­pressure (UPSO) protection. Available in Ductile iron body only.
Body Sizes and End Connection Styles
(1)
See table 2
Minimum and Maximum Inlet Pressures
(1)
Maximum Emergency (Body Rating) Inlet Pressure: 12 bar (175 psig) Maximum Operating Inlet Pressure: See table 4 Types S204 and S206 Minimum Inlet Pressure Required to Prevent Shutoff: See figure 1
Maximum Outlet Pressure (Casing)
(1)
1,0 bar (15 psig)
Maximum Operating Outlet Pressure to Avoid Internal Part Damage
(1)
Light Diaphragm Plate: 0,14 bar (2 psi) above outlet pressure setting Heavy Diaphragm Plate: 0,21 bar (3 psi) above
outlet pressure setting
Outlet Pressure Ranges
(1)
See table 3
Integral Monitor Performance
(1)
See table 5
Internal Relief Performance
(1)
Internal relief valve opens at 20 to 69 mbar (7 to 28-inches w.c.) above outlet setting, depending on control spring
Type VSX-2 Trip Pressure Ranges
(1)
See table 6
Proof Test Pressure
All Pressure Retaining Components have been proof tested per Directive 97/23/EC - Annex 1, Section 7.4
Maximum Temperature Capabilities
(1)
Nitrile (NBR): –29° to 66°C (–20° to 150°F) Fluoroelastomer (FKM): –18° to 93°C (0° to 200°F)
(Upper temperature limitation due to nylon flappers)
Type VSX-2: –29° to 60°C (–20° to 140°F)
1. The pressure/temperature limits in this installation guide and any applicable standard or code limitation should not be exceeded.
SLAIRETAMYDOB
REBMUNEPYT
norItsaC XXXXXXXXXXXXXXX
norIelitcuD XXXXXXXX XXXXXXXX
leetS XXXXXXXX
S201
S201H
S201K
S201P
S201PK
S202
S202H
S202P
S203
S203H
S203P
S204
S204H
S206
S206H
S208
S208H
S208K
S208P
S208PK
S209
S209H
S209P
Table 1. Available Constructions
Page 2
S200 Series
2
)SEHCNI(ND,EZISYDOB
ELYTSNOITCENNOCDNE
norItsaCnorIelitcuDleetS
)4/1-1(23 )2/1-1(04
)2x2/1-1(05x04
PSB,TPN PSB,TPN
---
--­PSB,TPN PSB,TPN
--­PSB,TPN
---
)2(05
FF521ssalCISNAro;PSB;TPN
)1(
,
degnalfFR052
roFF521ssalCISNA;PSB;TPN
degnalf61-01NPro;degnalfFR052
roFR051ssalCISNA;PSB;TPN
degnalf61-01NPro;degnalfFR003
.)sehcni-01(mm452ro)sehcni-5.7(mm191foecaf-ot-ecafahtiwelbaliavasiegnalfsihT.1
Table 2. Body Sizes and End Connection Styles
REBMUNEPYT
GNIRPS
REBMUN
EGNARERUSSERPTELTUO
GNIRPSLORTNOC
EDOCROLOC
302S,202S,102S
)1(
902S,802S,
,P302S,P202S,P102S
P902S,P802S
--­1 2 3 4
rabm11ot5
)3,2(
rabm61ot9 rabm22ot21 rabm54ot12 rabm57ot53
().c.wsehcni-2/1-4ot2
)3,2(
().c.wsehcni-5.6ot5.3
).c.wsehcni-9ot5(
).c.wsehcni-81ot5.8(
).c.wsehcni-03ot41(
nworB
deR
kcalB
yarG
neergkraD
602S,402S
---
---
---
---
---
rabm21ot9
)2(
rabm71ot21 rabm32ot61 rabm54ot12 rabm57ot53
).c.wsehcni-5ot5.3(
)2(
).c.wsehcni-7ot5(
).c.wsehcni-5.9ot5.6(
).c.wsehcni-81ot5.8(
).c.wsehcni-03ot41(
nworB
deR
kcalB
yarG
neergkraD
H302S,H202S,H102S
)1(
,H902S,H802S,
P102S
)4(
P202S,
)4(
P302S,
)4(
,
P802S,H602S,H402S
)4(
P902S,
)4(
5 6 7
rab41,0ot960,0 rab22,0ot01,0
rab43,0ot41,0
)5(
gisp2ot1()
)gisp52.3ot5.1(
)gisp5ot2(
)5(
eulbkraD
egnarO
wolleY
,KP102S,K102S
KP802S,K802S
8 9
rab83,0ot41,0 rab96,0ot82,0
)gisp5.5ot2(
)gisp01ot4(
epirtsneerG
detniapnU
H602S,H402S
---
---
rab41,0ot960,0 rab22,0ot01,0
gisp2ot1()
)gisp52.3ot5.1(
eulbkraD
egnarO
.noitamrofnieromrof5elbaTeeS.)desustaesgnirpsforebmunehtdnagnirpsrotinom(noitcurtsnocrotinomehtfonoitcnufaerasegnarerusserpteltuoH302Sdna302SsepyT.1
hcni-1(rabm5,2ybdecuderebnacegnarerusserpteltuofodnerewol,mottobnosignirpslortnocosdellatsnifI.mgarhpaidfopotnosignirpslortnocosdellatsnirotalugerhtiW.2
.etalpmgarhpaidyvaehhtiwrotalugerrof).c.wsehcni-2(rabm0,5roetalpmgarhpaidthgilhtiwrotalugerrof).c.w
.902Sdna802SsepyThtiwelbaliavatoN.3
.)gisp1(rab960,0revoserusserpteltuorofetalpmgarhpaidyvaeheriuqerP902Sdna,P802S,P302S,P202S,P102SsepyT.4
.H602Sdna,H402S,P302SsepyTrofelbaliavatoN.5
Table 3. Outlet Pressure Ranges
REBMUNEPYT
ERUSSERPTELTUO
GNITTES
,EZISECIFIROmm)HCNI(
OTERUSSERPTELNIGNITAREPOMUMIXAM
,ECNAMROFREPMUMITPONIATBOrab)GISP(
,P102S,102S ,P202S,202S
,P302S,302S
,P802S,802S
P902S,902S
rabm57ot5
).c.wsehcni-03ot2(
4,6 5,9 7,21
1,91 4,52 2,03
)4/1( )8/3( )2/1(
)4/3(
)1(
)61/3-1(
6,8 6,8 9,6 1,4 7,1 09,0
)521( )521(
)001( )06( )52( )31(
,P102S,H102S ,P202S,H202S ,P302S,H302S ,P802S,H802S
P902S,H902S
rab22,0ot960,0
)gisp52.3ot1(
4,6 5,9 7,21
1,91 4,52 2,03
)4/1( )8/3( )2/1( )4/3(
)1(
)61/3-1(
6,8 6,8 9,6 1,4 1,2 0,1
)521( )521(
)001( )06( )03( )41(
KP102S,K102S KP802S,K802S
teltuollA
sgnitteserusserp
4,6 5,9 7,21
1,91
4,52
)4/1( )8/3( )2/1( )4/3(
)1(
6,8 6,8 9,6 1,4 1,2
)521(
)521(
)001( )06( )03(
rab83,0ot41,0
)gisp5.5ot2(
2,03)61/3-1(4,1)02(
rab96,0ot82,0
)gisp01ot4(
2,03)61/3-1(7,1)52(
,402S
602S
rabm57ot9
).c.wsehcni-03ot5.3(
5,9 7,21
1,91 4,52 2,03
)8/3( )2/1( )4/3(
)1(
)61/3-1(
9,6 9,6 2,5 1,2 0,1
)001(
)001( )57( )03( )51(
,H402S
H602S
rab22,0ot960,0
)gisp52.3ot1(
5,9 7,21
1,91 4,52 2,03
)8/3( )2/1( )4/3(
)1(
)61/3-1(
9,6 9,6 2,5 1,2 0,1
)001(
)001( )57( )03( )51(
Table 4. Additional Specifications
Page 3
S200 Series
3
Installation
Only qualified personnel should install or service a regulator. Regulators should be installed, operated, and maintained in accordance with international and applicable codes and regulations, and Fisher instructions.
If the regulator vents fluid or a leak develops in the system, it indicates that service is required. Failure to take the regulator out of service immediately may create a hazardous condition.
Personal injury, equipment damage, or leakage due to escaping fluid or bursting of pressure-containing parts may result if this regulator is overpressured or is installed where service conditions could exceed the limits given in the Specifications section, or where conditions exceed any ratings of the adjacent piping or piping connections.
To avoid such injury or damage, provide pressure­relieving or pressure-limiting devices (as required by the appropriate code, regulation, or standard) to prevent service conditions from exceeding limits.
Additionally, physical damage to the regulator could result in personal injury and property damage due to escaping fluid. To avoid such injury and damage, install the regulator in a safe location.
Clean out all pipelines before installation of the regulator and check to be sure the regulator has not been damaged or has collected foreign material during shipping. For NPT bodies, apply pipe compound to the male pipe threads. For flanged bodies, use suitable line gaskets and approved piping and bolting practices. Install the regulator in any position desired, unless otherwise specified, but be sure flow through the body is in the direction indicated by the arrow on the body.
Note
It is important that the regulator be installed so that the vent hole in the spring case is unobstructed at all times. For outdoor installations, the regulator should be located away from vehicular traffic and positioned so that water, ice, and other foreign materials cannot enter the spring case through the vent. Avoid placing the regulator beneath eaves or downspouts, and be sure it is above the probable snow level.
Type VSX-2 Installation
The Type VSX-2 may be shipped separately from the regulator. To install the unit on a regulator, place the new O­rings (keys 2 and 3) on the Type VSX-2 and slide the module into the regulator body. Secure the Type VSX-2 to the regulator body with the four set screws (key 4). The unit may be oriented in any direction with respect to the sensor line connection.
SEGNARTNIOPTESEPYTTUHS-MALS
GNIRPSEVLAVNIAMHTIWESU
REBMUN
)1(
MUMIXAMOTMUMINIM
ERUSSERPPIRT
ffotuhSerusserprevO
)OSPO(
PL
2,1rabm36ot03).c.wsehcni-52ot21(
4,3,2,1rabm031ot05).c.wsehcni-25ot02(
6,5,4,3rabm072ot59)gisp9.3ot4.1(
9,8,7,6,5rabm006ot062)gisp7.8ot8.3(
9rabm0011ot004)gisp61ot8.5(
ffotuhSerusserprednU
)OSPU(
PL
3,2rabm03ot6).c.wsehcni-21ot2(
6,5,4,3rabm57ot01).c.wsehcni-03ot4(
8,7,6,5rabm061ot52)gisp3.2ot63.0(
9,8,7rabm057ot001)gisp8.01ot5.1(
.rebmungnirpsevlavniamrof3elbateeS.1
Table 6. Type VSX-2 High and Low Trip Pressure Ranges
EPYT
REBMUN
GNIRPSLORTNOC
ROLOC
3ELBATEES( )EGNARROF
EGNARERUSSERPTELTUO
MAERTSNWODMUMIXAM
HTIWERUSSERP
NIROTINOMLARGETNI
,NOITAREPOrab)GISP(
FEILER
ROTINOM
ROLOCGNIRPS
FOREBMUN
GNIRPS
STAES
DERIUQER
,302S
P302S
nworBrabm21ot0).c.wsehcni-5ot0(55)gisp8.0(neerG0
kcalB/deRrabm42ot01).c.wsehcni-5.9ot4(neerG1
yarG
rabm53ot02 rabm03ot02 rabm05ot52 rabm25ot72
).c.wsehcni-41ot8( ).c.wsehcni-21ot8(
).c.wsehcni-02ot01( ).c.wsehcni-12ot11(
-­69 421 251
-­)4.1( )8.1( )2.2(
neerG deR deR eulB
2 0
1
0
neergkraD
rabm07ot53 rabm28ot54 rabm07ot53
).c.wsehcni-82ot41( ).c.wsehcni-33ot81(
)gisp0.1ot5.0(
391 702 702
)8.2( )0.3( )0.3(
deR eulB
revliS
2
1
0
,H302S
P302S
eulbkraD
rabm011ot07 rabm011ot25
)gisp6.1ot0.1(
)gisp6.1ot57.0(
262 672
)8.3( )0.4(
eulB
revliS
2
1
egnarO
rabm551ot68 rabm422ot68
)gisp52.2ot52.1( )gisp52.3ot52.1(
543 314
)0.5( )0.6(
revliS
revliS
2 3
Table 5. Integral Monitor Data
Page 4
S200 Series
4
Overpressure Protection
The recommended pressure limitations are stamped on the regulator nameplate. Some type of overpressure protection is needed if the actual inlet pressure exceeds the maximum operating outlet pressure rating. Overpressure protection should also be provided if the regulator inlet pressure is greater than the safe working pressure of the downstream equipment.
Regulator operation below the maximum pressure limitations does not preclude the possibility of damage from external sources or debris in the line. The regulator should be inspected for damage after any overpressure condition.
Startup
The regulator is factory set at approximately the midpoint of the spring range or the pressure requested, so an initial adjustment may be required to give the desired results. With proper installation completed and relief valves properly adjusted, slowly open the upstream and downstream shutoff valves.
Type VSX-2 Startup
The Type VSX-2 is shipped in the tripped position and will need to be reset. If the Type VSX-2 is a high trip only, it can be reset before starting the regulator. If the Type VSX-2 is a high and low trip, the regulator will have to be started and the downstream system pressurized before the Type VSX-2 can be reset.
Adjustment
To change the outlet pressure, remove the closing cap or loosen the locknut and turn the adjusting screw clockwise to increase outlet pressure or counterclockwise to decrease pressure. Monitor the outlet pressure with a test gauge during the adjustment. Replace the closing cap or tighten the locknut to maintain the desired setting.
Type VSX-2 Trip Adjustment
Note
An adjustment tool is included with the Type VSX-2. Use only this tool to make adjustments to the unit. To make adjustments, the overpressure trip spring is found under the outer adjusting screw and the underpressure trip spring is found under the inner adjusting screw.
To adjust the Overpressure Trip Spring:
1. Adjust the overpressure trip setting to its maximum
compression.
2. If present, adjust the underpressure spring to its
minimum compression.
3. Backpressure the unit with the desired trip pressure.
4. Reduce the overpressure trip spring compression until
the Type VSX-2 trips.
To adjust the Underpressure Trip Spring:
1. Adjust the underpressure trip spring back to its minimum
compression.
2. Backpressure the unit with the desired trip pressure.
3. Increase the underpressure trip spring compression until
the Type VSX-2 trips.
Taking Out of Service (Shutdown)
To avoid personal injury resulting from sudden release of pressure, isolate the regulator from all pressure before attempting disassembly.
Figure 1. Minimum Inlet Pressure Required to Prevent Shutoff
on all Sizes of S204, S204H, S206, and S206H Regulators at Indicated Flow
FLOW RATE, SCFH OF 0.6 SPECIFIC GRAVITY NATURAL GAS
FLOW RATE, m3/h(n) OF 0.6 SPECIFIC GRAVITY NATURAL GAS
50
40
30
20
10
0
3.0
2.0
1.0
0
0 1000 2000 3000 4000 5000 6000 7000 8000
MINIMUM INLET PRESSURE, PSIG
MINIMUM INLET PRESSURE, bar
0 26.8 53.6 80.4 107 134 160 188 214
1-INCH (25,4 mm) SEAT RING
1/2-INCH (12,7 mm) SEAT RING
5/8-INCH (15,9 mm) SEAT RING
1-3/16-INCH (30,2 mm) SEAT RING
Page 5
S200 Series
5
50A9455
50A9457
Type S201 and S202 Parts List
Key Description
1 Spring Case 2 Spring 3 Adjusting Screw 4 Closing Cap 5 Closing Cap Gasket 6 Upper/Lower Spring Seat 7A Diaphragm 7B Diaphragm Head 8 Pusher Post 9 Lower Casing Assembly 10 Lever 11 Pin 12 Machine Screw 13 Valve Stem Assembly 14 Cap Screw 15 Hex Nut 16 Disk Holder Assembly 17 Diaphragm Plate 18 Cap Screw 19 O-Ring 20 Seat Ring 21 Body 24 Cap Screw 25 Relief Valve Spring 32 Nameplate 46 Pipe Plug 53 Hex Nut 55 Flapper Stem 56 Lower Flapper 57 Upper Flapper 58 Seat Ring 59 Self-Tapping Screw 60 Spring 61 Screen 62 Snap Ring
Figure 2. Type S202 Assembly
Figure 3. Type S206 Assembly
Type S204 and S206 Parts List
Key Description
1 Spring Case 2 Spring 3 Adjusting Screw 4 Closing Cap 5 Closing Cap Gasket 6 Lower Spring Seat 7 Diaphragm & Head Assembly 7A Diaphragm 8 Pusher Post (S204) 8 Ball Stem Assembly (S206) 9 Lower Casing Assembly 10 Lever 11 Pin 12 Machine Screw 13 Valve Stem Assembly 14 Cap Screw 15 Hex Nut 16 Disk Holder Assembly 18 Cap Screw 19 O-Ring 20 Seat Ring 21 Body 24 Reset Stem 25 Relief Valve Spring (S206) 26 Back Disk Spring 27 Back Disk Holder 28 Disk Spacer 32 Nameplate 33 Valve Stem 34 Gasket 55 Flapper Stem 56 Lower Flapper 57 Upper Flapper 58 Seat Ring 59 Self-Tapping Screw 60 Spring 61 Screen 62 Snap Ring
Page 6
S200 Series
For information, contact Fisher Controls, International:
Within USA (800) 588-5853 – Outside USA (972) 542-0132 Italy – (39) 051-4190-606 Singapore – (65) 770-8320 Mexico – (52) 57-28-0888
©Fis her C ontrols Inte rnati onal, I nc., 2002; All R ights Reser ved
Fisher and Fisher Regulators are marks owned by Fisher Controls International, Inc. The Emerson logo is a trade mark and service mark of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Printed in U.S.A.
www.FISHERregulators.com
T80390-A2 B2517-2
T80388-C B2508-2
T80388-C B2495-2
Figure 4. Type S209 Assembly
Type S208 and S209 Parts List
Key Description
1 Spring Case 2 Spring 3 Adjusting Screw 4 Closing Cap 5 Closing Cap Gasket 6 Lower Spring Seat 7 Diaphragm and Diaphragm Head 8 Pusher Post 9 Lower Casing Assembly 10 Lever 11 Pin 12 Machine Screw 13 Valve Stem Assembly 14 Cap Screw 15 Hex Nut 16 Disk Holder 17 Diaphragm Head 19 O-Ring 20 Orifice 21 Body 24 Stem 25 Relief Valve Spring 32 Nameplate 55 Flapper Stem 56 Lower Flapper 57 Upper Flapper 58 Orifice 59 Self-Tapping Screw 60 Spring 61 Screen 62 Snap Ring 63 Retaining Ring 64 O-Ring 65 O-Ring 67 Stem Adaptor 94 Relief Restriction 121 Insert 122 O-Ring 123 Pipe Plug
Figure 5. Type VSX-2 Assembly
Type VSX-2 Parts List
Key Description
1 VSX-2 Module 2 Upper O-Ring 3 Lower O-Ring 4 Set Screw 6 Vent Assembly 7 High-Pressure Control Spring 8 Low-Pressure Control Spring 10 Machine Screw 11 Gasket 13 Pipe Plug
VIEW A
VIEW A