Fisher® regulators must be installed,
operated, and maintained in accordance
with federal, state, and local codes, rules
and regulations, and Emerson Process
Management Regulator Technologies,
Inc., instructions.
For LP-Gas service, an approved
regulator (such as one listed by U.L.)
should be used. The installation,
in most states, must comply with
NFPA standards.
If the regulator vents gas or a leak
develops in the system, service to
the unit may be required. Failure
to correct trouble could result in a
hazardous condition.
Call a gas service person to service
the unit. Only a qualied person must
install or service the regulator.
Introduction
Scope of the Manual
This instruction manual provides instructions for
installation, adjustment, maintenance, and parts
ordering information for Types S201, S201H, S201K,
S202, and S202H gas service regulators.
Description
S201 and S202 Series regulators are typically
installed on industrial and commercial applications.
The Types S202 and S202H regulators contain an
internal relief valve. Units with an “H” or “K” sufx
are similar to the basic regulators but deliver a higher
outlet pressure of 1 to 5 psig (69 mbar to 0,35 bar) and
2 to 10 psig (0,14 to 0,69 bar), respectively.
Specications
The Specications section lists the specications for
the regulators. The following information is stamped
on the regulator at the factory: type number, date of
manufacture, spring range, orice size, maximum inlet
pressure, maximum operating outlet pressure, and
outlet pressure which may damage regulator parts.
www.emersonprocess.com/regulators
D400007X012
S201 and S202 Series
TypeS202
Specications
Available Congurations
See Figure 3
Body Size and End Connection Styles
1-1/2 or 2 NPT inlet and outlet and
NPS 2 (DN 50) CL125 FF anged
Maximum Allowable Inlet Pressures
(1)
See Table 1
Maximum Emergency Outlet Pressure
15 psig (1,0 bar)
Outlet Pressure Range
(1)
Orice Size
1/4, 3/8, 1/2, 3/4, 1, and 1-3/16-inches
(6,4; 9,5; 13; 19; 25; and 30 mm)
Temperature Capabilities
-20° to 150°F (-29° to 66°C)
Pressure Registration
Internal
Approximate Weight
22 pounds (10 kg)
2.0-inches w.c. to 10 psig (5 mbar to 0,69 bar)
1. The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation for valve should not be exceeded.
CONTROL
SPRING
VALVE DISK
DIAPHRAGM
RELIEF VALVE
SPRING
VALVE DISK
DIAPHRAGM
PUSHER POST
A6197A6198
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
ORIFICE
TYPE S201TYPE S202
Figure 2. Operational Schematics
Principle of Operation
Refer to Figure 2. When downstream demand
decreases, the pressure under the diaphragm
increases. This pressure overcomes the regulator
setting (which is set by the control spring). Through
the action of the pusher post assembly, lever, and
valve stem, the valve disk moves closer to the orice
and reduces gas ow. If demand downstream
increases, pressure under the diaphragm decreases.
Spring force pushes the pusher post assembly
downward, and the valve disk moves away from the
orice, and the gas ow increases.
The Types S202 and S202H regulators include an
internal relief valve. Internal relief is used to help
minimize overpressure. Any outlet pressure above
the start-to-discharge point of the non-adjustable relief
spring moves the diaphragm off of the relief seat,
allowing excess pressure to discharge through the vent.
Typical start-to-discharge values are 7-inches w.c. to
2 psi (17 to 138 mbar) above the outlet pressure
setting, depending on control spring used.
PUSHER POST
ORIFICE
2
S201 and S202 Series
TYPE NUMBER
S20
REGULATOR TYPE
1Regulator, 2 to 30-inches w.c. (5 to 75 mbar) outlet range
2Regulator, 2 to 30-inches w.c. (5 to 75 mbar) outlet range with Internal Relief
PRESSURE OUTLET RANGE
HHigh-Pressure Regulator, 1 to 5 psi (0,07 to 0,34 bar) outlet range with heavy diaphragm plate
KHigh-Pressure Regulator with external adjusting screw, 2 to 10 psi (0,14 to 0,69 bar) outlet range (Not an option for S202)
Installation
WARNING
!
Personal injury or system damage
may result if this regulator is installed,
without appropriate overpressure
protection, where service conditions
could exceed the limits given on the
Specications section and regulator
nameplate. Regulator installations
should be adequately protected from
physical damage.
All vents should be kept open to permit
free ow of gas to the atmosphere.
Protect openings against entrance of
rain, snow, insects, or any other foreign
material that may plug the vent or vent
line. On outdoor installations, point the
spring case vent downward to allow
condensate to drain (see Figure 4). This
minimizes the possibility of freezing and
of water or other foreign materials from
entering the vent and interfering with
proper operation.
Under enclosed conditions or indoors,
escaping gas may accumulate and be
an explosion hazard. In these cases,
the vent should be piped away from the
regulator to the outdoors.
OPTIONS
Figure 3. Available Congurations
AJ4698
A1121
Figure 4. Type S201 Regulator Installed with the Vent
Pointed Downward and with a Type 289H Relief Valve for
any portion of the regulators beyond the
limits in the Specications section and
Table 1 may cause leakage, damage to
regulator parts, or personal injury due to
bursting of pressure-containing parts.
Some type of external overpressure
protection should be provided if inlet
pressure will be high enough to damage
downstream equipment. Common
methods of external overpressure
protection include relief valves,
monitoring regulators, shutoff devices,
and series regulation.
TYPE S201
REGULATOR
PROTECT VENT PIPE
WITH RAIN CAP
High Capacity Relief
NPS 2 (DN 50)
TYPE 289H
RELIEF VALVE
CAUTION
S201 and S202 Series regulators have
an outlet pressure rating lower than
their inlet pressure rating. If actual inlet
pressure can exceed the outlet pressure
rating, outlet overpressure protection
is necessary. However, overpressuring
If the regulator is exposed to an
overpressure condition, it should be
inspected for any damage that may
have occurred. Regulator operation
below these limits specied in the
Specications section and Table 1 does
not preclude the possibility of damage
from external sources or from debris in
the pipeline.
3
Loading...
+ 5 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.