Emerson Fisher P520L Instruction Manual

Page 1
Instruction Manual D450013T012
August 2016
Type P520L Reamer
Type P520L
DRILL MARKS
P2114_1
P2115_1
REAMER TIP
MARKINGS
REAMER TIP EXTENDS AT THIS END
Figure 1. Type P520L Reamer
Introduction
The Type P520L tapered reamer is calibrated for propane vapor by drill size. Refer to the NATIONAL FUEL GAS CODE, NFPA 54-2006, Table F.1 (b) and Table F.1 (c) for BTU/hour for
a specic orice and gas size. Use Type P520L to enlarge or clean out orices on LP-Gas appliances ranging from drill size
no. 52 to 30 (0.0635 to 0.125 in.).
Use the reamer as follows:
The reamer is designed with knurls on the handle for better grip. Make sure reamer is held in vertical position while doing the following steps.
To enlarge orices:
1. Loosen the reamer by twisting the knurls against the slide rule.
2. Push the slide rule towards the end of the reamer body
until the cursor points to the desired orice or drill size.
3. Once the cursor is aligned with the desired drill size, lock position by twisting the knurl in opposite directions.
4. Hold the orice with one hand and the reamer with the other.
5. Insert the tip of the reamer into the orice as far as it
can go.
6. Start reaming until the orice contacts the end of the reamer body.
7. Remove the reamer from the orice.
8. Unlock the reamer and retract the slide rule to the fully closed position.
9. Lock handle.
SLIDE RULE
CURSOR
HANDLE WITH KNURLS
P2116_1
To check orice sizes:
1. Loosen the reamer.
2. Extend the reamer tip fully.
3. Lock the reamer.
4. Insert the reamer tip into the orice until it sits
quite snugly.
5. Unlock the reamer and allow the handle to drop and
contact the tip of the orice.
6. Lock position.
7. Read the indicated drill size
8. Remove the reamer and retract the slide rule to the fully closed position.
9. Lock handle.
CAUTION
Always retract the reamer to the fully closed position and tighten the handle before placing the reamer into pocket. Failure to do so may result in personal injury.
This reamer can also be used on appliance orices where gas other than propane is used. The following chart shows the BTU Orice Capacity by Gas and Orice
Sizes. (Tables are from NATIONAL FUEL GAS CODE, NFPA 54-2006, 2006 edition.)
Page 2
Type P520L
Table F.1 (b). LP-Gases (BTU/hour at Sea Level) Table F.1 (b). LP-Gases (BTU/hour at Sea Level) (continued)
ORIFICE OR DRILL SIZE PROPANE BUTANE
0.008
0.009
0.010
0.011
0.012
80 79 78 77 76
75 74 73 72 71
70 69 68 67 66
65 64 63 62 61
60 59 58 57 56
55 54 53 52 51
50 49 48 47 46
519 656 812 981
1169
1480 1708 2080 2629 3249
3581 4119 4678 5081 5495
6375 6934 7813 8320 8848
9955 10,535 11,125 11,735 12,367
13,008 13,660 14,333 15,026 17,572
21,939 24,630 28,769 32,805 36,531
39,842 43,361 46,983 50,088 53,296
589 744
921 1112 1326
1678 1936 2358 2980 3684
4059 4669 5303 5760 6230
7227 7860 8858 9433
10,031
11,286 11,943 12,612 13,304 14,020
14,747 15,486 16,249 17,035 19,921
24,872 27,922 32,615 37,190 41,414
45,168 49,157 53,263 56,783 60,420
ORIFICE OR DRILL SIZE PROPANE BUTANE
45 44 43 42 41
40 39 38 37 36
35 34 33 32 31
30 29
Notes:
1. BTU per cubic foot
2. Specic gravity
3. Pressure at orice, inches w.c.
4. Orice coefcient
Propane
2516
1.52 11
0.9
54,641 60,229 64,369 71,095 74,924
78,029 80,513 83,721 87,860 92,207
98,312 100,175 103,797 109,385 117,043
134,119 150,366
Butane
3280
2.01 11
0.9
Table F.1 (c). Multipliers for Utility Gases of
Another Specic Gravity
SPECIFIC
GRAVITY
0.45
0.50
0.55
0.60
0.65
0.70
0.75
0.80
0.85
0.90
MULTIPLIER
1.155
1.095
1.045
1.000
0.961
0.926
0.894
0.866
0.840
0.817
SPECIFIC
GRAVITY
0.95
1.00
1.05
1.10
1.15
1.20
1.25
1.30
1.35
1.40
61,944 68,280 72,973 80,599 84,940
88,459 91,215 94,912 99,605
104,532
111,454 113,566 117,672 124,007 132,689
152,046 170,466
MULTIPLIER
0.795
0.775
0.756
0.739
0.722
0.707
0.693
0.679
0.667
0.655
Webadmin.Regulators@emerson.com
Fisher.com
Emerson Process Management Regulator Technologies
Americas
McKinney, Texas 75070 USA T +1 800 558 5853 +1 972 548 3574
Europe
Bologna 40013, Italy T +39 051 419 0611
- continued -
Facebook.com/EmersonProcessManagement
LinkedIn.com/company/emerson-process-management
Twitter.com/emersonprocess
Asia Pacic
Singapore 128461, Singapore T +65 6770 8337
Middle East and Africa
Dubai, United Arab Emirates T +971 4 811 8100
D450013T012 © 1971, 2016 Emerson Process Management Regulator Technologies, Inc. All rights reserved. 07/16. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher™ is a mark owned by Fisher Controls International LLC, a business of Emerson Process Management.
The contents of this publication are presented for information purposes only, and while effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the
designs or specications of our products at any time without notice.
Emerson Process Management Regulator Technologies, Inc does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson Process Management Regulator Technologies, Inc. product remains solely with the purchaser.
Loading...