Loose-leaf version: Part Number D301080X012
Bound version: Contact FAS
FloBoss 407 Instruction Manual
Revision Tracking Sheet
May 2000
This manual may be revised periodically to incorporate new or updated information. The date revision
level of each page is indicated at the bottom of the page opposite the page number. A major change in
the content of the manual also changes the date of the manual which appears on the front cover. Listed
below is the date revision level of each page.
PageRevision
All5/00
Previous Editions:
November 1998 - Added changes for 1.05/1.06 firmware and added references to ROCLINK.
Fisher Controls International, Inc. 1995-2000. All rights reserved.
FloBoss is a trademark of Fisher Controls International, Inc.
HART is a registered trademark of the HART Communication Foundation.
Printed in the U.S.A.
While this information is presented in good faith and believed to be accurate, Fisher Controls does not guarantee satisfact ory results from
reliance upon such information.
performance, merchantability, fitness or any other matter with respect to the products
process in conflict with any patent. Fisher Controls reserves the right, without notice, to alter or improve the desi gns or specifications of the
products described herein.
iiRev 5/00
Nothing contained herein is to be construed as a warranty or guarantee, express or implied, regarding the
, nor as a recommendation to use any product or
FloBoss 407 Instruction Manual
Table of Contents
(For a more detailed listing, see the Section Contents at the front of each section.)
SECTION 1 — GENERAL INFORMATION ............................................................1-1
1.1 Scope of Manual...............................................................................................................................1-1
B.4 Field Wiring.....................................................................................................................................B-7
C.2 Analog Outputs to Analog Inputs.................................................................................................... C-1
C.3 Analog Outputs to a meter...............................................................................................................C-2
C.4 Discrete Outputs to Discrete Inputs................................................................................................. C-3
C.5 Discrete Outputs to Pulse Inputs......................................................................................................C-4
C.6 Potentiometer to Analog Inputs....................................................................................................... C-5
C.7 Switch to Discrete Inputs.................................................................................................................C-6
C.8 Switch to Pulse Inputs .....................................................................................................................C-7
GLOSSARY OF TERMS.............................................................................................G-1
INDEX ..............................................................................................................................I-1
Rev 5/00v
FloBoss 407 Instruction Manual
[This page is intentionally left blank.]
viRev 5/00
FloBoss 407 Instruction Manual
SECTION 1 — GENERAL INFORMATION
1.1 SCOPE OF MANUAL
This manual describes the FloBoss™ 407 Flow Manager (also called the ROC407), part of the family of
FloBoss Flow Managers manufactured by Fisher Controls. Both the Standard version and the
Measurement Canada version of the FloBoss 407 are covered in this manual. Included are the
following sections:
♦ Section 1General Information
♦ Section 2FloBoss 407 Base Unit
♦ Section 3Input/Output Modules
♦ Section 4Communications Cards
♦ Section 5Display and Keypad
♦ Appendix ALightning Protection Module
♦ Appendix BMulti-Variable Sensors
♦ Appendix CI/O Simulation
♦ GlossaryGlossary of Terms
♦ IndexTopical Index
Section 1 describes this and related manuals. Section 1 also provides a summary of the FloBoss 407
hardware, installation guidelines, and information on power consumption, startup, and keypad
operation.
Section 2 provides information and specifications concerni ng the tw o ma in com ponen ts of the FloBoss
407, the p r o cessor board and the te r minat i o n boar d.
Section 3 provides information and specifications for t he op tio nal I/O modules available for the FloBoss
407.
Section 4 provides information and specifications for the communications card options available for the
FloBoss 407.
Section 5 describes the operation of the keypad and the display.
Appendix A describes t he op tional lig htn ing pro tectio n m odu le.
Appendix B describ es the M u lti-Varia b le Sensors a v ailable fo r t h e F loBoss 407.
Appendix C shows various ways to set up I/O simulation for troubleshooting I/O components and
configurations.
Rev 5/001-1
FloBoss 407 Instruction Manual
1.2 SECTION CONTENTS
This section contains the following information:
InformationSectionPage Number
Product Overview1.31-2
Related Documents and Compatibility1.3.11-4
Installation Guidelines1.41-5
Environmental Requirements1.4.11-5
Site Requirements1.4.21-5
Compliance with Hazardous Area Standards1.4.31-6
Power Installation Requirements1.4.41-7
Grounding Installation Requirements1.4.51-7
I/O Wiring1.4.61-8
Power Consumption Calculation1.51-9
Determining I/O Channel Power Consumption1.5.11-9
Determining Radio Power Consumption1.5.21-12
Totaling Power Requirements1.5.31-12
Startup and Operation1.61-13
Startup1.6.11-13
Operation1.6.21-13
Keypad Operation1.71-14
Service Bulletins1.81-15
1.3 PRODUCT OVERVIEW
The FloBoss 407 is a microprocessor-based flow computer (see Figure 1-1) that provides functions
required for gas flow measurement and custody transfer in accordance with standards such as AGA
1985 or 1992 orifice metering. More generally, the unit provides on-site functionality for applications
where there is a need for remote monitoring, measurement, data archival, communications, and control.
The design allows the user to configure the FloBoss 407 for specific applications including those
requiring calculations, logic, and sequencing control using function sequence tables, as well as PID
loop control.
The FloBoss 407 is available in two versions based on the type of approval: the standard hazardous
area version, and the Measurement (Industry) Canada custody transfer version, which includes
hazardous area approval. These versions have a number of differences both in firmware and hardware.
Both of these versions are further subdivided by the type of orifice metering calculations (either AGA
1992 or AGA 1985) included in the firmware.
1-2Rev 5/00
FloBoss 407 Instruction Manual
Figure 1-1. FloBoss 407 Flow Manager
Physically, the FloBoss 407 consists of two printed circuit cards, a keypad, and a display housed in a
compact weather-tight case. The printed circuit cards are the processor board and the termination
board.
Built into the termination board are two analog input (AI) channels. Moving a jumper on the
termination board changes one of the built-in analog inputs to a pulse input (PI). The pulse input can be
wired either as a FloBoss-powered or a device-powered, medium-speed pulse counter. The pulse
circuitry is optically coupled to isolate the termination board from the input signal.
In addition, the termination board has slots for four plug-in input/output (I/O) modules (also called
modular I/O). The plug-in I/O modules allow any combination of discrete inputs, discrete outputs,
analog inputs, analog outputs, or pulse inputs an application requires.
NOTE
I/O modules must not be used as flow inputs for Industry Canada approved
FloBoss 407 units.
The built-in Liquid Crystal Display (LCD) and membrane keypad provide the ability to look at data and
configuration parameters while on site. The keypad also permits limited editing of parameter values.
The FloBoss 407 can have up to four Multi-Variable Sensor (MVS) devices connected to it. The MVS
provides the differential pressure, static pressure, and temperature inputs needed for performing orifice
flow calculations. As many as four MVS devices (one of which can be an integral MVS) can be used
with a FloBoss 407. The integral MVS is factory-mounted to the bottom of the enclosure with a
coupler and further secured with a stiffening plate. For detailed information on the MVS, refer to
Appendix B.
Rev 5/001-3
FloBoss 407 Instruction Manual
The FloBoss has two communication ports built in: a local operator interface port and an EIA-232
serial port. A variety of optional plug-in communication cards are available that allow you to add
another communications channel: EIA-232 serial, EIA-422/485 serial, dial-up modem, radio modem,
or leased-line modem communications.
The FloBoss 407 is packaged in a NEMA 4X windowed enclosure that can mount on a wall or a
pipestand. The enclosure, which protects the electronics from physical damage and harsh environments, is fabricated of die-cast, low-copper aluminum alloy. It consists of four pieces: the body, the
electronics cover, the keypad cover, and the lower cover. Silicone-rubber gaskets seal the unit when the
covers are closed. All covers are secured by captive screws.
Note that for the Measurement Canada version of the FloBoss 407, the electronics cover, and the lower
cover are secured by special captive screws. These screws have holes through the heads for adding
security wire seals according to Measurement (Industry) Canada requirements.
For the standard version of the FloBoss 407, an optional padlock adapter can be added in the field. This
adapter is installed on the captive screw that secures the electronics cover. With the shank (up to 0.25
inch diameter) of the padlock running through the adapter, the screw is inaccessible and the cover
cannot be opened. Refer to Section 2.3 for adapter installation instructions.
The FloBoss 407 unit can be mounted either on a wall or on a 2-inch pipestand (U-bolt mounting kit is
supplied). For installation information, refer to Section 1.4 and Section 2.3.
Configuration of the FloBoss 407, including installing user programs (special versions may be needed
for the Measurement Canada FloBoss), requires a personal computer and ROCLINK Configuration
Software. See Section 1.3.1 for compatible configuration software and its documentation.
For a more details about the FloBoss 407, refer to Section 2.
1.3.1 Related Documents and Compatibility
For software aspects such as configuration, refer to the following manual:
♦ Type RL101 ROCLINK Configuration Software User Manual (Form A6051) – ROCLINK
Version 2.1 or greater is required for all Measurement Canada FloBoss 407 units as well as
standard FloBoss units with Version 1.05 firmware or greater. ROCLINK Version 2.1 also
works with standard FloBoss units that have an earlier version of firmware. ROCLINK
Version 2.0 can be used for standard FloBoss units with Version 1.04 or earlier firmware.
For FST information, refer to the following manual:
♦ Function Sequence Table User Manual (Form A4625) – Provides information on setting up
an FST to run in the FloBoss, including how to use the FST Editor supplied with the
configuration software.
1-4Rev 5/00
FloBoss 407 Instruction Manual
For accessories, refer to the following manual:
♦ ROC/FloBoss Accessories Instruct ion M anua l (Form A 4637) – Provides information
concerning accessories such as RTD sensors for the MVS.
1.4 INSTALLATION GUIDELINES
This manual provides generalized guidelines for successful installation and operation of the FloBoss
407. Planning helps to ensure a smooth installation. Be sure to consider location, ground conditions,
climate, and site accessibility as well as the suitability of the FloBoss 407 application while planning an
installation.
The variety of application firmware (software) in the FloBoss 407 allows it to be used in many types of
installations. For additional information concerning a specific installation, contact your Fisher
Representative.
1.4.1 Environmental Requirements
The FloBoss 407 case is classified as a NEMA 4X enclosure. This provides the level of protection
required to keep the units operating under conditions such as harsh weather and corrosive atmospheres.
NOTE
In salt spray environments, it is especially important to ensure that the enclosure is
sealed properly, including all entry and exit points. If salt is allowed to enter, it can
shorten the life of the lithium battery in the FloBoss 407 and cause the battery to
leak corrosive chemicals.
The FloBoss 407 is designed to operate over a wide range of temperatures, as detailed in the
Environmental specifications (see Section 2.6). Outside of this range, it may be necessary to moderate
the temperature in which the unit operates.
1.4.2 Site Requirements
Careful consideration in locating the FloBoss 407 on the site can help prevent future operational
problems. The following items should be considered when choosing a location:
♦ Local, state, and federal codes often place restrictions on monitoring locations and dictate
site requirements. Examples of these restrictions are fall distance from a meter run, distance
from pipe flanges, and hazardous area classifications.
Rev 5/001-5
FloBoss 407 Instruction Manual
♦ Locate the FloBoss 407 to minimize the length of signal and power wiring. By Code, line
power wiring must not cross meter runs.
♦ Orient solar panels used with solar-powered FloBoss 407s to face True South (not magnetic)
in Northern hemispheres. Orient solar panels used with solar-powered FloBoss 407s to face
True North (not magnetic) in Southern hemispheres. Make sure nothing blocks the sunlight
from 9:00
to 4:00 PM.
AM
♦ Antennas for FloBoss 407s equipped for radio communications must be located with an
unobstructed signal path. If possible, locate antennas at the highest point on the site and
avoid aiming antennas into storage tanks, buildings, or other tall structures. Allow sufficient
overhead clearance to raise the antenna.
♦ To minimize interference with radio communications, locate the FloBoss 407 away from
electrical noise sources such as engines, large electric motors, and utility line transformers.
♦ Locate FloBoss 407s away from heavy traffic areas to reduce the risk of being damaged by
vehicles. However, provide adequate vehicle access to aid in monitoring and maintenance.
1.4.3 Compliance with Hazardous Area Standards
The FloBoss 407 has hazardous location approval for Class I, Division 2, Groups A, B, C, and D
exposures. The class, division, and group terms are defined as follows:
Class defines the general nature of the hazardous material in the surrounding atmosphere. Class
I is for locations where flammable gases or vapors may be present in the air in quantities
sufficient to produce explosive or ignitable mixtures.
Division defines the probability of hazardous material being present in an ignitable
concentration in the surrounding atmosphere. Division 2 locations are presumed to be
hazardous only in an abnormal situation.
Group defines the hazardous material in the surrounding atmosphere. Groups A to D are
defined as follows:
♦ Group A - Atmosphere containing acetylene.
♦ Group B - Atmosphere containing hydrogen, gases or vapors of equivalent hazards.
♦ Group C - Atmosphere containing ethylene, gases or vapors of equivalent hazards.
♦ Group D - Atmosphere containing propane, gases or vapors of equivalent hazards.
For the FloBoss 407 to be approved for hazardous locations, it must be installed according to the
National Electrical Code (NEC) Article 501.
CAUTION
1-6Rev 5/00
FloBoss 407 Instruction Manual
When installing units in a hazardous area, make sure components selected are
labeled for use in such areas. Installation and maintenance must be performed
only when the area is known to be non-hazardous.
NOTE
Measurement Canada approved units normally require a sealed installation. Refer
to your local codes for specifics.
1.4.4 Power Installation Requirements
Typical sources of primary power for FloBoss 407 installations are line power and solar power. Care
must be taken to route line power away from hazardous areas, sensitive monitoring devices, and radio
equipment. Local and company codes generally provide guidelines for line power installations.
Adhere rigorously to all local and National Electrical Code (NEC) requirements for line power
installations.
Solar power allows installation of the FloBoss 407 in locations where line power is not available. The
two important elements in a solar installation are solar panels and batteries. Each must be properly
sized for the application and geographic location to ensure continuous, reliable operation. Information
contained in the accessories manual can help you determine the solar panel and battery requirements to
fit your installation.
As a site may have additional power requirements for radios, repeaters, and other monitoring devices,
Fisher Controls Field Automation Systems offers power supply and converter accessories to minimize
the number of separate power sources required for an installation.
1.4.5 Grounding Installation Requirements
Grounding wiring requirements for line-powered equipment are governed by the National Electrical
Code (NEC). When the equipment uses line power, the groundi ng system must terminate at the ser vice
disconnect. All equipment ground ing conductors must provide an unin terrupted electr ical path to the
service disconnect.
The National Electrical Code Article 250-83 (1993), paragraph c, defines the material and
installation requirements for grounding electrodes.
The National Electrical Code Article 250-91 (1993), paragraph a, defines the material
requirements for grounding electrode conductors.
The National Electrical Code Article 250-92 (1993), paragraph a, provides installation
requirements for grounding electrode conductors.
Rev 5/001-7
FloBoss 407 Instruction Manual
The National Electrical Code Article 250-95 (1993) defines the size requirements for equipment
grounding conductors.
Proper grounding of the FloBoss 407 helps to reduce the effects of electrical noise on the units
operation and protects against lightning. Lightning Protection Modules (LPM) are available to provide
additional lightning protection for field wiring inputs and outputs. A surge protection device installed at
the service disconnect on line-powered sy stems offers l ightni ng and power surge protect ion for t he
installed equipmen t.
All earth grounds must have an earth to g round ro d or g rid im pedance of 2 5 ohm s or le ss as measured with
a ground system tester. The g roundi ng conductor sho uld have a resis tance of 1 oh m or less between the
FloBoss 407 case ground lug and the earth g r ound ro d or gr id .
The grounding installation met hod f or t he F loBoss 407 depend s on whether the pipeline has cathodic
protection. On pipelines wi th cathod ic pro tectio n, the FloB os s 4 07 must be elec trical ly isolated from the
pipeline.
Electrical isolation can be accomplished by using insulating flanges upstream and downstream on the
meter run. In this case, the F loBoss 407 c oul d be f lang e moun ted or sadd le-clamp mou nted directly on the
meter run and grounded with a ground rod or g rid system.
Another way of providing electrical iso lation wo uld be t o moun t the FloBoss 407 on a pipe stand and use a
remote Multi-Variable Sensor instal led w ith non-con duct ive condu it. Groun d t he case of the Fl oB oss 407
to a ground rod or grid system.
On pipelines without cathod ic pro tection, the p ipel ine it self may provide an adequate earth ground and the
FloBoss 407 could mount direct ly on the meter run. Test with a ground sy stem tes ter to make sure t he
pipeline to earth impedance is less than 25 o hms . If an adequate ground is provided by the pipeline, do not
install a separate ground rod or g rid system. All grounding shou ld termina te at a si ng le poi nt.
If the pipeline to earth impedance is g reater than 25 o hms, t he FloB os s 40 7 installation should be
electrically isolated and a ground r od or g rid g roundi ng system installed.
1.4.6 I/O Wiring
I/O wiring requirements are site and application dependent. Local, state, or NEC requirements
determine the I/O wiring installation methods. Direct burial cable, conduit and cable, or overhead
cables are options for I/O wiring installations. Sections 2 and 3 contain detailed information on
connecting I/O wiring to the FloBoss 407.
1-8Rev 5/00
FloBoss 407 Instruction Manual
1.5 POWER CONSUM PTION CALCULATION
A ROC/FloBoss system’s power consumption determines power supply and battery sizing for both line
and solar power supplies. Table 1-1 and Table 1-2 provide information to assist in determining power
requirements. For non-analog I/O, size the I/O module scaling resistors (see Section 3) for optimal
current to minimize current drain on the power supply.
1.5.1 Determining I/O Channel Power Consumption
In estimating total I/O power requirements, the “duty cycle” of each I/O channel (built-in I/O or
modular I/O) must be estimated. For a non-analog I/O channel, the duty cycle is essentially the
percentage of time that the I/O channel is active (maximum power consumption). For example, if a
discrete output is active for 15 seconds out of every 60 seconds, the duty cycle is:
Duty Cycle = Active time/(Active time + Inactive time) = 15 sec/60 sec = 0.25
For an analog I/O channel, the duty cycle is approximated by estimating the percentage of time the
channel spends in the upper half of its range (span) of operation. For example, if an analog input wired
as a current loop (4 to 20 mA) device operates in the upper half of its range 75% of the time, then 0.75
would be used as the duty cycle. If the analog channel generally operates around the midpoint of its
span, use 0.5 as the duty cycle.
To calculate the total power consumed by an I/O channel, first select either the 12 or 24 volt column in
Table 1-1 or Table 1-2. Then, read the minimum (P
) and maximum (P
min
) power consumption value
max
from the table for the desired I/O channel. Use the following equation to calculate the power
consumption for a channel with the duty cycle taken into account:
Power = (P
x Duty Cycle) + [P
max
(1 - Duty Cycle)]
min
Multiply this value by the quantity (Qty) of I/O channels with the same duty cycle and enter the
calculated value in the Subtotal column. Repeat the procedure for all other I/O channels used. For a
FloBoss 407, total the values in the Subtotal column in Table 1-2, and enter the value in the I/O
Modules row of Table 1-1.
Rev 5/001-9
FloBoss 407 Instruction Manual
Table 1-1. Power Consumption of the FloBoss 407 and Powered Devices
POWER CONSUMPTION (mW)
DUTYSUB-
DEVICE12V System24V SystemQTYCYCLETOTAL
Processor and I/O Termination Board
(includes minimum built-in I/O power
P
min
N/A800N/A12001N/A
P
max
P
min
P
max
consumption)
Built-in Analog Input — ROC/FloBoss -
130440130440
Powered Current Loop
Built-in Analog Input — Externally-
0650275
Powered Voltage Signal
Built-in Pulse Input — ROC/FloBoss-
012024
Powered
Built-in Pulse In put — Externally-Powered0000
Serial Communications Card135135N/A
Dial-up Modem Communications Card395395N/A
Leased-Line Communications Card110110N/A
Radio Modem Communications Card110110N/A
(mW)
MVS (Integral or Remote)N/A240N/A480N/A
I/O Modules Total from Table 1-2N/AN/AN/A
Radio (from Section 1.4.2)N/AN/AN/A
TOTAL
NOTE: 1. For the Analog Input, the Duty Cycle is the percent of time spent in the upper half of the operating range.
1-10Rev 5/00
FloBoss 407 Instruction Manual
Table 1-2. Power Consumption of the I/O Modules
POWER CONSUMPTION (mW)
I/O MODULE12V System24V S ys temQTYCYCLETOTAL
P
min
P
max
P
min
P
max
AI Loop170495170495
AI Differential75757575
AI Source110305130470
AO Source145585145585
RTD Input (P
P
is at 100° C)
max
is at -50° C;
min
240475475930
DI Isolated110110
DI Source1551205
PI Isolated130130
PI Source1701230
SPI Isolated110110
SPI Source1551205
DUTYSUB-
(mW)
Low-Level PI145145
DO Isolated125125
DO Source (P
is at 57 mA)
max
30815301585
DO Relay 12V15375N/AN/A
DO Relay 24VN/AN/A20470
HART Interface Module85685851285
TOTAL
NOTES: 1. For analog I/O channels, the Duty Cycle is the percent of time spent in the upper half of the operating range.
2. The P
amount includes any power drawn by a ROC/FloBoss-powered field device, such as a transmitter.
max
Rev 5/001-11
FloBoss 407 Instruction Manual
1.5.2 Determining Radio Power Consumption
In determining power requirements for radios, the duty cycle for the radio must be estimated. The duty
cycle is the percentage of time the radio is transmitting (TX). For example, if a radio is transmitting 1
second out of every 60 seconds, and for the remaining 59 seconds the radio is drawing receive (RX)
power, the duty cycle is:
To calculate the total power consumed by a radio, obtain the power (P) consumption values for transmit
and receive from the radio manufacturer’s literature, then use the following equation to calculate the
power consumption for a particular duty cycle:
Power = (PTX x Duty Cycle) + [PRX (1 - Duty Cycle)]
Determine the power consumption for all radios that use power from the ROC/FloBoss, and enter the
total calculated value in Table 1-1.
1.5.3 Totaling Power Requirements
To adequately meet the needs of the ROC/FloBoss system, it is important to determine the total power
consumption, size solar panel, and battery backup requirements accordingly. For total power
consumption, add the device values in Table 1-1. Although Table 1-1 and Table 1-2 take into account
the power supplied by the ROC/FloBoss to its connected devices, be sure to add the power consumption
(in mW) of any other devices used with the ROC/FloBoss in the same power system, but not accounted
for in the tables.
Convert the total value (in mW) to Watts by dividing it by 1000.
mW / 1000 = Watts
For selecting an adequate power supply, use a safety factor (SF) of 1.25 to account for losses and other
variables not factored into the power consumption calculations. To incorporate the safety factor,
multiply the total power consumption (P) by 1.25.
= P x 1.25 = _____ Watts
P
SF
To convert P
24 volts.
to current consumption in amps (ISF), divide PSF by the system voltage (V), either 12 or
SF
ISF = PSF / V = _____ Amps
1-12Rev 5/00
FloBoss 407 Instruction Manual
1.6 STARTUP AND OPERATION
Before starting the FloBoss 407, perform the following checks to ensure the unit is properly installed.
♦ Make sure the enclosure has a good earth ground con nected to the eart h gr ound bus inside the
enclosure.
♦ Seat and secure all I/O modules in the ir s ockets .
♦ Check the field wiring for proper insta llat ion .
♦ Make sure the input power is fused a t the power source.
♦ Make sure the input power has the correct polar ity .
♦ Make sure the input power is at least 12.5 volts (unless Switch S1 on the ter mination board of
newer FloBoss units—see Section 2—is depre ssed du ring power-up ).
CAUTION
Check the input power polarity before turning on the power. Incorrect polarity can
damage the ROC/FloBoss.
CAUTION
When installing units in a hazardous area, ensure components selected are labeled
for use in such areas.
1.6.1 Startup
Observe cautions above, and then apply power to the FloBoss 407. After the FloBoss completes startup diagnostics of Random Access Memory (RAM) and other internal checks, the STATUS LED on the
processor board turns on. This LED should turn on, and stay on, to show that the FloBoss 407
completed a valid reset sequence. If the LED indicator does not come on, refer to the Troubleshooting
and Repair paragraphs in Section 2 of this manual for possible causes.
1.6.2 Operation
Once startup is successful, it is necessary to configure the FloBoss 407 to meet the requirements of the
application. The manual that comes with the configuration software describes in detail the procedures
for configuring the FloBoss and calibrating the I/O. Once the FloBoss is configured and calibrated, it
can be placed into operation.
CAUTION
Configuration of the FloBoss must be performed only in an area known to be nonhazardous.
Rev 5/001-13
FloBoss 407 Instruction Manual
1.7 KEYPAD OPERATION
Table 1-3 provides a brief description of the keypad functions and the expected displays. For a detailed
description, refer to Section 5 of this manual.
To activate the display, press any key, for example
I/O SUMMARY
the display. Enter the numeric password with the keypad and press
. This returns a password prompt to
ENTER.
A date and time message
shows on the LCD. Refer to Section 5.5 concerning password security.
Select one of the categories to view from the keypad. The information scrolls on the LCD. Press
DISPLAY
display until the
to stop the list from scrolling on the LCD. The FloBoss 407 continuously updates the current
HOLD DISPLAY
key is pressed again to return the list to the scroll mode.
Table 1-3. FloBoss 407 Keypad Functions
KEYDISPLAY
Log OnPress Any KeyPassword prompt
Enter PasswordDate and time
I/O SUMMARYTag, value, and alarm for each I/O point
ALT,I/O DETAILParameters for selected I/O point
FLOW RATESFlow parameters for selected meter run
ALT,COMM PORTSParameters for selected communications port
FLOW COMPGas composition for selected meter run
ParameterALT,SYS PARAMSystem parameters: address, contract hour, etc.
ListsMETER CONFIGMeter configuration for selected meter run
ALT,TIMEDate and time
CONTROLParameters for selected PID loop
ALT,FSTParameters for selected FST
USER LIST 1,2,3User defined parameter list 1, 2, or 3
ALT,CALIBRATECalibration procedure
HOLD
ALARMSAlarm log
ALT,MIN/MAXMinimum and maximum history log
HistoryALT,MINUTE HISTMinute history log
FunctionsALT,HOURS HISTHours history log
ALT,DAY HISTDay history log
DisplayUP, DOWN Manually scrolls parameter list
ControlALT,PREV/NEXT SETSelects previous or next set of parameters
HOLD DISPLAYStops scroll; updates value; press again to resume
EDITAllows edit of current parameter; enter to save
KeypadBACKSPACEEdit mode backspace erase
ControlCANCELStops edit mode; resumes list display
ALT,CANCELCancels the operation in progress
QUITALT,PASSWORDLogs out current user; displays password prompt
ALT,DISPLAY OFFLogs out current user; shuts the display off
1-14Rev 5/00
FloBoss 407 Instruction Manual
The
DOWN ARROW
The
UP ARROW
key displays the next parameter in the list or changes the display to the next point.
key displays the previous parameter in the list or changes the display to the previous
point.
The
“7” key would activate the
selected I/O point.
key activates the key functions labeled below each key. For example, pressing
ALT
function which would display the entire set of parameters for the
activates the
DISPLAY OFF
function and turns off the LCD. Press
ALT
I/O DETAIL
and
ENTER
ALT
and the
any key to reactivate the LCD.
The
key activates the functions labeled in red on each key. This includes the numeric digits, the
EDIT
“-”, the “.”, and the backspace (←) key. The backspace key is an edit-only function. Those parameters
that allow editing can be changed if the edit mode is selected. The
CANCEL
key stops the edit mode and
resumes list display.
1.8 SERVICE BULLETINS
Fisher issues service bulletins periodically to provide information related to hardware and software
products. Fisher Representatives are responsible for local distribution of service bulletins to customers
as required. Contact your Fisher Representative for more information.
Rev 5/001-15
FloBoss 407 Instruction Manual
[This page intentionally left blank.]
1-16Rev 5/00
FloBoss 407 Instruction Manual
SECTION 2 — THE FLOBOSS 407 BASE UNIT
2.1 SCOPE
This section describes the FloBoss 407 and its main components: the processor board and termination
board. For options, refer to the remaining sections of this manual. Topics covered in this section are:
Installing the FloBoss 407 Unit2.3.12-11
Installing FloBoss 407 Options and Accessories2.3.22-12
Connecting the FloBoss 407 to Wiring2.42-14
Connecting Ground Wiring2.4.12-14
Connecting Main Power Wiring2.4.22-14
Built-in Analog Input Wiring2.4.32-15
Built-in Pulse Input Wiring2.4.42-16
Connecting Communications Wiring2.4.52-17
Multi-Variable Sensor Wiring2.4.62-19
Troubleshooting and Repair2.52-19
LED Indicators2.5.12-19
Backup Procedure Before Removing Power2.5.22-21
After Installing Components2.5.32-22
Warm Start2.5.42-23
Cold Start2.5.52-23
Fuses2.5.62-24
RAM Backup and Real-Time Clock Battery2.5.72-25
Calibrating the Board Temperature Input2.5.82-26
Testing the Built-in Analog Input Channels2.5.92-26
Testing the Built-in Pulse Input Channel2.5.102-27
Replacing the Processor Board2.5.112-28
Replacing the Termination Board2.5.122-29
Replacing the Flash ROM2.5.132-31
Keypad and Display Replacement2.5.142-32
Integral MVS Replacement2.5.152-32
Specifications2.62-32
Rev 5/002-1
FloBoss 407 Instruction Manual
2.2 PRODUCT DESCRIPTION
This section describes the functionality of the FloBoss 407, as well as its processor and termination
boards. The processor board has the microprocessor, memory components, the keypad, display
interfaces, and the connectors for mounting the communications board. The termination board has the
power supply circuitry, the communications ports, I/O ports, and the on-board monitoring circuitry.
2.2.1 Functionality
This section describes the functions of the FloBoss 407, most of which are determined by its firmware,
programmed by the factory into flash memory (see Section 2.2.2). The features and applications
provided by the firmware, which must be configured by using ROCLINK Configuration Software, are:
♦ Either 1985 or 1992 AGA3 flow calculations for an orifice meter, plus AGA7 flow
calculations for a turbine meter.
♦ Archival of data for up to 50 history points.
♦ Memory logging of 240 alarms and 240 events (plus audit log events for the Measurement
Canada version).
♦ Logic and sequencing control using a user-defined FST program.
♦ Closed loop control (PID) capability.
♦ Power cycling control for a radio (not available in Measurement Canada version).
♦ Report-by-exception (RBX) alarming capability (Version 1.05 and greater).
♦ Capability to load and run user programs, such as the Modbus Protocol Emulation Program.
2.2.1.1 Flow Measurement
One of the primary functions of the FloBoss 407 is to measure the flow of natural gas in accordance
with the 1985 or 1992 American Petroleum Institute (API) and American Gas Association (AGA)
standards. The FloBoss performs either 1985 or 1992 AGA3 orifice calculations, depending on which
was ordered (firmware Version 1.04 and earlier contains both). In addition, all versions of FloBoss 407
firmware contain the AGA7 turbine meter flow calculation function.
The primary inputs used for the orifice metering flow measurement function are differential pressure,
static pressure, and temperature. These inputs typically come from the Multi-Variable Sensor (MVS).
The temperature input typically comes from an RTD probe, whether connected to the MVS or not.
The 1985 flow calculation is in accordance with AGA Report No. 3 1985 and AGA Report No. 8 1985
(ANSI/API 2530-85 and API Chapter 14.2), and API Chapter 21.1. The 1985 flow calculation may be
configured for either Metric or English units.
The 1992 flow calculation is in accordance with AGA Report No. 3 1992 (ANSI/API 2530-92), AGA
Report No. 8 1992 2nd printing 1994 (API Chapter 14.2), and API Chapter 21.1. The 1992 flow
calculation may be configured for either Metric or English units.
2-2Rev 5/00
FloBoss 407 Instruction Manual
The primary inputs used for the turbine metering flow measurement function are meter pulse input,
static pressure, and temperature. These inputs typically come through I/O modules installed on the
FloBoss 407. The flow calculation is in accordance with AGA Report No. 7. The flow calculation may
be configured for either Metric or English units.
2.2.1.2 History Points
A total of 50 history points may be set up and accessed in the FloBoss 407. The first six or eight are
pre-configured for flow history on Meter Run #1 (required for EFM reporting). These points can be
changed if needed. The time stamp for periodic logging consists of the month, day, hour, and minute.
The exception is for FST Second logging, in which the time stamp consists of the day, hour, minute,
and second.
The FloBoss has a minute historical log for every history point. The Minute Historical Log stores the
last 60 minutes of data from the current minute. Each history point has Minute Historical Log entries
unless the history point is configured for FST-controlled logging.
The FloBoss has a total of 840 hourly historical logs available for every history point. The Hourly
Historical Log is also called the Periodic Log. Normally, the Hourly Log is recorded every hour at the
top of the hour. The exception is for FST-controlled logging.
The FloBoss has a total of 35 daily historical logs for every history point. The Daily Log is recorded at
the configured contract hour every day with a time stamp that is the same as the Hourly Log. Each
history point has daily historical log entries unless the history point is configured for FST-controlled
logging.
2.2.1.3 Alarm and Event Lo gs
Alarm and event logs are stored in non-volatile RAM in the FloBoss. Note that they are not stored to
flash ROM when the Save Configuration function is used in the ROCLINK Configuration Software.
The Alarm Log records instances when exceptions from field inputs and calculations occur. The
system Alarm Log has the capacity to maintain and store up to 240 alarms in a “circular” log. The
alarm log has information fields which include time and date stamp, alarm clear or set indicator, and
either the tag name of the point which was alarmed with the current value or a 14 ASCII character
description.
In addition to providing functionality for appending new alarms to the log, it allows host packages to
request the index of the most recently logged alarm entry. Alarm logging is available internally to the
system, to external host packages, to FSTs, and to User C programs. Alarm Logs are not stored to the
flash ROM during the ROCLINK Save Configuration function. The Alarm Log operates in a circular
fashion with new entries overwriting the oldest entry when the buffer is full. The alarm log provides an
Rev 5/002-3
FloBoss 407 Instruction Manual
audit history trail of past operation and changes. The Alarm Log is stored separately to prevent
recurring alarms from overwriting configuration audit data.
Event logs contain a record of operator changes and system events such as power-downs. The event log
operates in a circular fashion, with new entries overwriting the oldest entry when the buffer is full. The
event log provides a history of past operation and changes. The event log is stored separate from the
alarm log to prevent recurring alarms from overwriting configuration change events.
In addition to providing functionality for appending new events to the log, it allows host packages to
request the index of the most recently logged event entry. Event logging is available internally to the
system, to external host packages, and to the FST.
The Audit Log is a specialized type of event log set up only for the Measurement/Industry Canada
version of the FloBoss. It contains changes to any flow-related parameter made through the protocol.
The Audit Log has the capacity to maintain and store up to 240 events. Once the Audit Log fills up, a
flag must be cleared by saving the log to a disk file; then the FloBoss will allow parameter changes and
resume recording audit events. The log has information fields which include point type, parameter
number, time and date stamp, point number if applicable, the operator identification, and either the
previous and current parameter values or a 14-byte ASCII description.
2.2.1.4 Function Sequence Tables (FSTs)
The FloBoss supports FST user programmability. The FST program can be as many as 300 lines of
code, depending upon the FST. The FST code resides in static RAM and is backed up to flash memory
when the “save configuration” function is issued through the ROCLINK Configuration Software. See
the configuration software user manual and the Function Sequence Table (FST) User Manual (Form
A4625).
2.2.1.5 PID Control
The PID Control functionality is used to provide control of a process variable to a user-entered setpoint
by automatically adjusting the output to a regulating device, such as a control valve. PID Control can
only be implemented if I/O modules are installed in the FloBoss to provide a control output. This
output can be achieved either through an Analog Output or a through a pair of Discrete Outputs for
open/close control. Override Control of a secondary variable may also be set up.
2.2.1.6 Power Control
The Power Control function (available in Standard firmware only) is used with communications port to
provide power savings when using a radio or cell phone for communications. Three cycling “zones”
are provided, but zones can be disabled as desired. Either a Discrete Output module (for COM1 or
COM2) or the DTR signal (for COM2 only) provides the switching mechanism.
2-4Rev 5/00
FloBoss 407 Instruction Manual
The Power Control function calculates which zone should be currently active. The Power Control
begins in the ON state and continues with a full On Time and then goes to the OFF state for the full Off
Time.
2.2.1.7 Report By Exception ( R BX) Alarming
The RBX Alarming function (added for Version 1.05 and greater) allows a communications port to be
set up to enable the FloBoss to contact the host computer when specified alarm conditions exist.
2.2.2 Processor Board Description
The processor board components define the functionality of the FloBoss 407. The processor board
provides the following:
♦ NEC V25+ microprocessor
♦ On-board static RAM
♦ Flash memory for program storage
♦ Keypad port
♦ Display port
♦ Communications card port
♦ Real-time clock
♦ Battery backup power
♦ Status indicator
♦ Reset switch
Figure 2-1 shows a view of the processor board mounted on the door of the FloBoss 407 case and the
termination board mounted in the FloBoss 407 case.
The FloBoss 407 derives processing power from a NEC V25+ microprocessor. The NEC V25+ is a 16bit CMOS microprocessor featuring dual 16-bit internal data buses and a single 8-bit external data bus.
The unit can address up to one megabyte of memory and features high-speed direct memory access.
The processor board has 512 Kbytes of static random access memory (SRAM) for storing interrupt
vectors, Function Sequence Tables (FSTs), ROC displays, alarms, events, user program data, and
history data.
The processor board also has a 512 Kbyte flash memory chip for storing firmware such as the operating
system, factory code, user programs, and configuration parameters. A protected 64K block of flash
memory contains the operating system kernel (boot block). There are four different flash chips, which
determine the 407 version as follows:
♦ W68044 – Standard AGA92 Version 1.05 or greater (same part number as earlier FloBoss versions)
♦ W68073 – Standard AGA85 Version 1.05 or greater
♦ W68057 – Measurement Canada AGA92 Version 1.05 or greater
♦ W68074 – Measurement Canada AGA85 Version 1.05 or greater
Table 2-1 shows how the FloBoss 407 memory is allocated. Each memory location range (such as
00000 to 0FFFF) represents 64 Kbytes of memory.
A two-line LCD panel mounts on the display connector on the rear of the processor board. This
positions the display for viewing through the main door of the enclosure.
2-6Rev 5/00
FloBoss 407 Instruction Manual
Table 2-1. FloBoss 407 Memory Map
MEMORY LOCATIONUSE
00000 to 003FFInterrupt Vectors
00400 to 0FFFFBoot Block Data
10000 to 1FFFFEvents, Alarms, ROC Displays,
20000 to 2FFFFScratch Pad/Flash Program Buffer
30000 to 3FFFFHistory Data
40000 to 4FFFFHistory Data
50000 to 5FFFFHistory Data
RAM
FST Data, Audit Log (Measure-
ment Canada version only), and
other Flash Program Data
60000 to 6FFFFUser Program Data
70000 to 7FFFFUser Program Data
FLASH MEMORY
80000 to 87FFF
88000 to 8FFFF
Configuration Save Area
Factory Program
90000 to 9FFFFFactory Program
A0000 to AFFFFUser Program
B0000 to BFFFFUser Program
C0000 to CFFFFUser Program
D0000 to DFFFFFactory Code
E0000 to EFFFFFactory Code
F0000 to FFFFFBoot Block
A membrane keypad mounts on the main door of the enclosure and provides a local operator interface
with the FloBoss 407. A gasketed door mounted on the main door of the enclosure protects the keypad
from the elements. The keypad connects to the processor board with a ribbon cable.
Rev 5/002-7
FloBoss 407 Instruction Manual
The communications connectors on the processor board provide the FloBoss 407 with electrical access
and mounting provisions for the optional communications boards. The communication board mounts
directly on the connectors on the processor board and is held in place with a screw passing through the
communications board to a standoff on the processor board. The communications boards available for
the FloBoss 407 allow the options of serial data communication, modem, radio modem, or leased-line
modem communications.
A 3.6 volt lithium battery provides backup power for the RAM and the real-time clock. The backup
battery mounts on the processor board with a spring clip to hold it in place. The processor board has
provisions for mounting a second backup battery. This provision allows the user to replace the battery
without losing backup power to the FloBoss 407.
The real-time clock provides the FloBoss 407 with the time of day date, month, year, and day of the
week. The time chip automatically switches to battery power when the board loses primary input
power.
An LED indicator on the processor board shows the system status. The system status indicator, when
on, indicates the unit is normal; when blinking, indicates the processor board is not running; and when
off, it means a missing or out-of-tolerance input voltage.
The RESET switch permits a special type of cold start from the factory default configuration (contained
in the boot block of flash memory) rather than from the configuration saved to permanent memory (as
in a normal Cold start). Hold the RESET switch down during power-up to initiate this cold hard start;
otherwise, the switch has no effect. Perform the RAM backup procedure before performing a Cold
start. Refer to Section 2.5.2, Backup Procedure Before Removing Power on page 2-21.
2.2.3 FloBoss 407 Termination Board Description
Refer to Figure 2-1. The termination board provides the following functionality to the FloBoss 407:
♦ 11 to 30 volts dc input power supply
♦ Board temperature and voltage monitor inputs
♦ Built-in field input terminals
♦ Expansion I/O module terminals
♦ External modem port
♦ Communications board port
♦ MVS port
♦ Operator interface serial port
The FloBoss 407 operates with an 11 to 30 volt dc power input to the termination board. A power
indicator LED lights when an input voltage with the proper polarity and level is applied to the power
terminal block if the power input fusing/protection is operational.
2-8Rev 5/00
FloBoss 407 Instruction Manual
The FloBoss 407 power supply circuitry provides supply voltages of +5, -5, and +8.5 volts. In addition,
+12/24 volts (+T) is provided for transmitter power by means of a switching regulator.
The +T voltage is used by the built-in field I/O and the plug-in I/O modules to provide power for looppowered instruments such as transmitters. The +T voltage depends on the setting of a jumper on the
termination board (P15 or W1--see Figure 2-1 on page 2-6). If Jumper P15 is set to 24V or if the W1
pins are not connected (factory default), then the +T voltage is 24 volts or greater (if the input power
voltage to the FloBoss 407 exceeds 24 volts, the switching regulator shuts down and the +T voltage
follows the input voltage). If Jumper P15 is set to 12V or if the W1 pins are connected (by the supplied
jumper plug), then the switching regulator no longer operates, so that the +T voltage is 12 volts,
provided the input power is 12 volts. This setting should only be used when all the I/O loops for this
FloBoss 407 require a 12-volt source.
For Revision D or later of the termination card, the +T voltage can be software-switched. This feature
allows the +T supply to be turned on or off for field devices not requiring continuous +T power. To
control the +T voltage, use the Aux Out #1 or Transmitter flag in the Configuration Software.
The FloBoss 407 termination board provides a +B voltage for the plug-in field I/O modules that require
it. For example, the discrete output (DO) relay modules can have either a 12 volt or a 24 volt coil. The
+B voltage is the same as the input voltage applied to the FloBoss 407 and the relay module used needs
to match the power supply input.
One over-current device and a soldered fuse on the termination board provide input power protection.
The over-current device protects the fuse. Another over-current device on the termination board
protects the +T outputs.
The LV START switch (Switch S1, found on Revision E or later or the termination card) allows the
FloBoss to power up under low-voltage conditions. Normally, the FloBoss will not start up below 12.5
volts; this is a cut-off feature designed to avoid draining down the power supply battery. Hold the LV
START switch down during power-up to initiate this startup. Refer to Figure 2-1 on page 2-6 to see the
location of this switch.
Three diagnostic analog inputs monitor input power voltage, +T voltage, and board temperature. These
values can be observed with the Configuration Software (as Analog Input points E1, E2, and E5) or
with the local display panel.
The on-board (built-in) field I/O channels provide two analog inputs (AIs); one of which you can
configure as a pulse input (PI). These I/O channels are suitable for use as flow inputs, including flow
measurement in the Measurement Canada version of the FloBoss 407.
Two plug-in terminal blocks provide termination for the built-in I/O channels. Jumper P4 on the
termination board provides the input type selection for the AI/PI channel. With P4 set to “PI,” the
channel becomes pulse input. The pulse input can be connected as either a sourced or an isolated input.
An LED indicator (PI IND) shows when the field input to the pulse input channel is active. Refer to
Figure 2-1, Processor and Termination Boards, on page 2-6.
Rev 5/002-9
FloBoss 407 Instruction Manual
The FloBoss 407 termination board has four I/O module connectors (also called slots) to accommodate
a variety of I/O modules. The four plug-in I/O modules allow any combination of discrete inputs (DIs),
discrete outputs (DOs), analog inputs (AIs), analog outputs (AOs), or pulse inputs (PIs) an application
requires. I/O modules should not be used for flow inputs on a Measurement Canada FloBoss 407.
When installed, optional surge protection devices (lightning protection modules) protect the built-in and
modular input channels from voltage transients. These devices replace the field wiring terminal blocks,
providing terminations for connecting the I/O wiring to the FloBoss 407. See Appendix A for more
information about the lightning protection modules.
The COM1 terminal block on the termination board provides wiring access to a built-in EIA-232 serial
interface.
If the FloBoss 407 processor board has an optional communications card installed, the COM2 terminal
block on the termination board provides wiring access for the communications card. Depending on the
type of card, this port allows the FloBoss 407 to connect to a radio, to public, leased, or customerowned telephone lines, to another device via serial communications. The termination board has a
bracket to hold an RJ11 connector for communications cards that provide a telephone line hook-up.
For installations using radio communications, battery power can be conserved by cycling power to the
radio. The radio power is controlled by either the DTR signal (COM2 only) or a discrete output
module. Radio power cycling can be implemented for COM1 and COM2. Refer to the ROCLINK
Configuration Software User Manual for detailed information.
The MVS port on the termination board allows the FloBoss 407 to communicate directly with a MultiVariable Sensor (MVS). The MVS is a flow monitoring device that collects temperature and pressure
data, making it available to the FloBoss 407 through this specialized serial port. This port can function
as a multi-drop port for installations with as many as four MVS units connected to the FloBoss 407.
Refer to Appendix B for details on the MVS.
The operator interface connector provides direct communications between the FloBoss 407 and the
serial port of an operator interface device such as a notebook computer. The interface allows you
access to the FloBoss 407 for configuration (using the ROCLINK software) and for transferring stored
data.
2-10Rev 5/00
FloBoss 407 Instruction Manual
2.3 INSTALLATION
Before installing the FloBoss 407 or any of its options or accessories, be sure to read Section 1.3, which
describes installation guidelines.
2.3.1 Installing the FloBoss 407 Unit
CAUTION
Take precautions to make sure the unit is handled properly to prevent equipment
damage, and ensure that personnel are aware of any site hazards.
The FloBoss 407, with or without an integral MVS, can be mounted either on a wall or on a 2-inch
pipestand. When mounting the FloBoss 407 on a wall or panel, fasten with 5/16-inch bolts (8 mm)
through each of the four mounting holes. See Figure 2-2 for outline and mounting dimensions. If the
FloBoss 407 has an integral MVS, refer to Appendix B for outline and mounting dimensions.
To mount the FloBoss 407 on a pipestand, with or without an integral MVS, use the U-bolt mounting
kit supplied (contains 5/16-inch U-bolts). For further information on dimensions, as well as other
specifications, refer to Section 2.6.
NOTE
To prolong hinge life, the FloBoss 407 should be mounted vertically. If it is
necessary to mount the FloBoss 407 horizontally, make sure the hinges are located
on top.
Rev 5/002-11
FloBoss 407 Instruction Manual
.38 DIA MTG
HOLES
9.32
2.81
4.36
11.15 12.00
DOC0205A
Figure 2-2. FloBoss 407 Outline and Mounting Dimensions
2.3.2 Installing FloBoss 407 Options and Accessories
To install a Remote MVS, refer to the instructions in Appendix B. To install I/O Modules in the
FloBoss 407, refer to Section 3.3. To install a communications card in the FloBoss 407, refer to
Section 4.3.
To install a padlock adapter on the FloBoss 407, follow the procedure below. Installation of other
accessories for the FloBoss 407, such as solar panels and battery enclosures, is discussed in the
ROC/FloBoss Accessories Instruction Manual (Form A4637).
The optional padlock adapter (not available for the Measurement Canada FloBoss 407) installs on the
captive screw that secures the electronics cover. With the shank of the padlock (purchased separately)
running through the stainless steel adapter, the screw is inaccessible and the cover cannot be opened.
The padlock shank can be up to 0.25 inch in diameter, and the body of the padlock can be up to 1.5
inches wide.
To install the padlock adapter:
1. Open the main (electronics) cover of the FloBoss 407.
2. Remove the old retaining washer from the screw and discard the washer.
3. Position the screw, adapter, and new washer as displayed in Figure 2-3.
4. Thread the screw through the washer and into the enclosure using a screwdriver.
2-12Rev 5/00
FloBoss 407 Instruction Manual
5. Rotate the adapter as required using a padlock shank.
6. Install the padlock.
PADLOCK
COVER
SCREW
PADLOCK
ADAPTOR
FRONT VIEW
SHOWN WITH ADAPTOR
AND PADLOCK INSTALLED
Figure 2-3. Padlock Adapter Installation
RETAINING
WASHER
MAIN
COVER
SIDE VIEW
MAIN COVER SHOWN
OFFSET FOR CLARITY
Rev 5/002-13
FloBoss 407 Instruction Manual
2.4 CONNECTING THE FLOBOSS 407 TO WIRING
The following paragraphs describe how to connect the FloBoss 407 to power, ground, I/O devices, and
communications devices. Use the recommendations and procedures described in the following
paragraphs to avoid damage to equipment or injury to personnel. The FloBoss 407 terminal blocks
can accommodate up to 12 AWG wire.
CAUTION
Always turn the power to the F loBoss o ff before you attem pt any t ype o f wirin g.
2.4.1 Connecting Ground Wiring
Equipment Required: Small flat-blade screwdriver
The FloBoss 407 and related components must be connected to earth ground. The National Electrical
Code (NEC) governs the ground wiring requirements for all line-powered devices.
The FloBoss 407 has a ground bus bar located in the lower section of the enclosure. The ground bus
bar is electrically bonded to the enclosure and provides space to connect ground wires from I/O devices,
power input, and grounding conductors from devices used in the installation. For line-powered devices,
the grounding conductor must end at the service disconnect. The grounding conductor can be wire or
metallic conduit as long as the circuit provides a low impedance ground path.
With stand-alone units, a grounding terminal on the outside of the housing allows you to ground the
FloBoss 407 directly to an earth ground. It is recommended that 12 AWG wire be used for theground wiring. Make sure the installation has only one ground point to prevent creation of a ground
loop circuit. A ground loop circuit could cause erratic operation of the system.
2.4.2 Connecting Main Power Wiring
Equipment Required: Small flat-blade screwdriver
It is important that good wiring practice be used when sizing, routing, and connecting power wiring.
All wiring must conform to state, local, and NEC codes. The terminal blocks can accommodate up to
12 AWG wire. Use 18 AWG wire or larger for all power wiring.
Connect power to the FloBoss 407 through the plug-in PWR terminal block on the termination board.
Connect the DC power source to the “+” and “-” terminals. Make sure the polarity is correct. Figure
2-4 shows the location of the power indicator and the power wiring terminal block.
The analog input channels have three field terminals per channel. The “+T” terminal provides +24
volts dc for loop-powered devices. Each channel has a current regulator in series with the “+T”
terminal to provide short-circuit protection. The maximum output of each terminal is 25 milliamps.
The FloBoss 407 is shipped with a 250-ohm scaling resistor between the “+” and “-” analog input
terminals.
The “+” terminal is the positive signal input and the “-” terminal is the negative signal input. These
terminals accept a voltage signal in the 1 to 5 volt range. Since the “-” terminal is internally connected
to common, the analog input channels function as a single-ended input only.
For use with a 4 to 20 milliamp current signal, leave the 250-ohm resistor installed between the “+” and
“-” terminals. Wire the device “+” lead to the FloBoss 407 “+T” terminal and the device “-” lead to the
FloBoss 407 “+” terminal. Figure 2-5 shows the wiring for a typical current signal.
For use as a voltage input, remove the 250-ohm resistor from the analog input terminal block.
Figure 2-6 shows a typical voltage signal analog input.
Rev 5/002-15
FloBoss 407 Instruction Manual
AI
ROC-POWERED
CURRENT LOOP
DEVICE
EXTERNAL/
SELF-POWERED
DEVICE
+
-
Vs = 11 TO 30 VDC
+T = 24 VDC
+SIGNAL = 4 TO 20 mA
250 OHM
+T
+
-
Figure 2-5. Current Signal on Built-in Analog Input
AI
+
-
Vs = 11 TO 30 VDC
+T = 24 VDC
+SIGNAL = 1 TO 5 VDC
+T
+
-
Figure 2-6. Voltage Signal on Built-in Analog Input
Changing the P4 jumper to the “PI” position allows the built-in AI/PI input channel to be used as either
an isolated or a sourced pulse input. This pulse input signal is optically isolated from the FloBoss 407
circuit board. The pulse input can operate at up to 10 kHz, with a maximum 50% duty cycle.
The AI/PI channel has three field terminals. Terminal “+T” is a positive source voltage, either +24
volts or a level that follows the voltage of the FloBoss 407 input power. Terminal “+” is the positive
signal input; terminal “-” is the negative signal input. Be sure to remove the supplied 250-ohm resistor
from the terminal block when using the AI/PI channel as a pulse input.
To use the channel as an isolated input shown in Figure 2-7, connect the “+” and “-” field wires to
terminals “+” and “-” on the FloBoss 407 Pulse Input channel. When the field device sends a voltage
through terminal “+” on activation, the PI indicator LED on the termination board lights to show an
active circuit and the signal triggers the optical circuitry to signal the FloBoss 407.
For use as a sourced input shown in Figure 2-8, connect the field device positive wire to terminal “+T”
and the field negative lead to terminal “+”. When the discrete field device conducts, the source power
flows through the LED to show an active circuit and triggers the optical circuitry to signal the FloBoss
407.
AI/PI
2.5K
+T
DOC0210A
ROC-POWERED
PULSE DEVICE
+
-
+T
+
-
Figure 2-8. FloBoss-Powered Built-in Pulse Input
2.4.5 Connecting Communications Wiring
Equipment Required: None
The FloBoss 407 has the flexibility to communicate to external devices using several different formats
and protocols. A special 3-pin connector provides a port for an operator interface device. Terminal
blocks located on the termination board provide connections to the COM1 and COM2 ports. Figure 2-9
shows the COM1, COM2, and Operator Interface port locations.
The Operator Interface port provides connections for a built-in EIA-232 communications interface to a
configuration and monitoring device. The configuration and monitoring device typically is a notebookstyle PC. A null modem cable (transmit and receive wires cross-connected, plus ground) must be used
Rev 5/002-17
FloBoss 407 Instruction Manual
between the operator interface connector and the PC. A prefabricated operator interface cable is
available as an accessory.
The FloBoss 407 has a built-in EIA-232 serial interface accessible through the COM1 communications
port. The port is an 8-terminal connector located on the termination board. Refer to Table 2-2 for a
description of the signals available at each terminal.
COM1
COM2
OPERATOR
INTERFACE
PORT
DOC0217A
Figure 2-9. Operator Interface, COM1, and COM2 Ports
Table 2-2. COM1 Port Signals
TERMINAL12345678
COM1 SignalRXDTXDRTSCTSDCDDTR*DSRCOM
*This signal is permanently enabled (connected to +10 Vdc).
The COM2 port provides communications access to an optional plug-in communications card. Section
4 details the types of communications cards available for the FloBoss 407 and has information on
connecting wiring to the COM2 connector.
2-18Rev 5/00
FloBoss 407 Instruction Manual
2.4.6 Multi-Variable Sensor Wiring
For information on MVS wiring, refer to Appendix B.
2.5 TROUBLESHOOTING AND REPAIR
Troubleshooting and repair procedures are designed to help the technician identify and replace faulty
boards and modules. Return faulty boards and modules to your Fisher Representative for repair or
replacement. To troubleshoot I/O modules and communications cards, refer to Sections 3.5 and 4.5,
respectively.
The following tools are required for troubleshooting:
♦ IBM-compatible personal computer
♦ ROCLINK Configuration Software
♦ Battery-powered digital multi-meter, Fluke 8060A or equivalent.
The configuration software runs on the personal computer and is required for a majority of the
troubleshooting performed on the FloBoss 407. Refer to the configuration software manual as needed.
2.5.1 LED Indicators
The FloBoss 407 has three LED indicators to verify operational functionality. Figure 2-10 shows the
location of the indicators and Table 2-3 gives the indicator functions.
When lit, the POWER LED shows that power is applied to the FloBoss 407.
The STATUS LED, located on the processor board, gives a first-level indication of the operation of the
FloBoss 407. After the power is switched on, the STATUS indicator should come on, and remain on to
indicate normal operation. If the STATUS indicator does not remain on, check Table 2-3 for possible
causes.
The PI LED located on the termination board shows the state of the Pulse Input channel. When the
LED is on, the PI channel is active.
Rev 5/002-19
FloBoss 407 Instruction Manual
PULSE INPU T IN D ICATOR
LV START SWITCH
POWER INDICATOR
DOC0207A-mod
STATUS INDICATOR
Figure 2-10. FloBoss 407 Indicator Locations
Table 2-3. Indicator Functions
INDICATORSTATUSDESCRIPTION
STATUSONSuccessful startup and the processor is running.
STATUSBLINKINGProcessor is not running and is attempting to restart.
Can result from bad clock battery (see Section 2.5.7).
overloaded, insufficient voltage available to power up
(see Section 2.5.3), or input power polarity reversed.
POWERON
Power is connected. Must be minimum of 12.5 volts,
unless LV START switch is used (see Figure 2-10
and Section 2.5.3).
POWEROFFPower not applied.
PI INDONInput active.
PI INDOFFInput not active.
2-20Rev 5/00
FloBoss 407 Instruction Manual
2.5.2 Backup Procedure B efore Removing Power
Use the following backup procedure when removing or adding FloBoss 407 components. This
procedure preserves the current FloBoss 407 configuration and data held in RAM.
Before removing power to the FloBoss for repairs, troubleshooting, or enhancements, perform the
backup procedure to avoid losing the FloBoss configuration and other data held in RAM. The
procedure assumes you are using ROCLINK Configuration Software Revision 2.10 or greater.
User programs cannot be saved out of the FloBoss. You need to reload user programs from their
original disk files as instructed in Section 8 of the ROCLINK User Manual.
CAUTION
There is a possibility of losing the FloBoss configuration and historical data
held in RAM while performing the following procedure. As a precaution, save
the current configuration and historical data to permanent memory as follows.
CAUTION
When installing devices in a hazardous area, make sure each device is labeled
for use in such areas. Procedures involving switching power on or off, or
procedures for installing or removing any wiring or components, must be
performed only when the area is known to be non-hazardous.
CAUTION
To avoid circuit damage when working with the unit, use appropriate
electrostatic discharge precautions, such as wearing a grounded wrist strap.
1. Save the current configuration data to internal configuration memory as instructed in the
ROCLINK User Manual for the ROC Flags display. This action saves most of the FloBoss
configuration into the permanent memory accessed when a cold hard start is performed.
2. Save the current configuration data to disk by using the Download/Save ROC Configuration
To Disk function described in Section 2.10 of the ROCLINK User Manual. When replacing
or physically upgrading a Flash memory chip, the only way to preserve configuration data
is to save the data to disk and then retrieve the information after the chip is installed.
3. Save all historical database logs (Minute, Hourly, and Daily) to disk as explained in Section
7 (or Section 2.9) of the ROCLINK User Manual.
Rev 5/002-21
FloBoss 407 Instruction Manual
4. Save the Event and Alarm logs to disk as explained in Section 7 (or Section 2.9) of the
ROCLINK User Manual. If you have a Measurement Canada FloBoss, also save the Audit
Log to disk. This action clears the audit flags but not the entries, enabling 240 new entries
to come into the Audit Log. The AGA Reports utility also clears the flags when reports are
saved to disk.
5. Save each Function Sequence Table (FST) program (up to four possible) to disk using the
“Write FST” function in the FST Editor utility of the ROCLINK software. See Section 4.2
of the FST User Manual (Form A4625) for more information.
2.5.3 After Installing Compon ents
After removing power to the FloBoss and installing components as needed, perform the following steps
to start your FloBoss and reconfigure your data. You must use configuration software that is
compatible with the firmware version of the FloBoss 407, as described in Section 1.3.
NOTE
For Measurement Canada units, maintenance and resealing of the FloBoss
must be performed by authorized personnel only.
CAUTION
Ensure all input devices, output devices, and processes remain in a safe state
upon restoring power.
1. Connect the PWR terminal block to restore power.
Due to a cut-out feature designed to avoid draining down the power supply
NOTE
battery, the FloBoss 407 normally requires a minimum of 12.5 volts to start up.
However, this feature can be bypassed on newer FloBoss 407s by depressing the
LV START switch (see Figure 2-10 on page 2-20) while applying power.
2. Using the configuration software, check the configuration data (including ROC displays) and
FSTs. If the configuration contained in RAM was lost or corrupted, the configuration contained
in flash memory will automatically be used.
3. Load or modify the configuration and FSTs as required.
4. Load and start any user programs as needed. User programs need to be reloaded from their
original disk files as instructed in Section 8 of the ROCLINK User Manual.
2-22Rev 5/00
FloBoss 407 Instruction Manual
5. Verify the FloBoss performs as required.
6. If you changed the configuration, save the current configuration data to permanent configuration
memory.
7. If you changed the configuration or any FSTs, save them to disk. See Section 2.5.2 for more
information on performing these saves.
2.5.4 Warm Start
A warm start temporarily suspends all input/output (I/O) scanning. I/O processes are restarted from
their last calculated values. A warm start clears and restarts all user-enabled flags. A warm start also
starts all FSTs to the first instruction.
NOTE
If your FloBoss is semi-functional, perform the RAM Backup Procedure
before removing power from your FloBoss. Refer to Section 2.5.2, Backup
Procedure Before Removing Power, on page 2-21.
To perform a warm start, remove power from your FloBoss and reapply power.
2.5.5 Cold Start
A cold start reloads all configuration data from electrically erasable read only memory (EEPROM),
clears all history, events, and alarm logs, disables all user program tasks, and disables all user data
types. The RESET switch permits a restart from the boot block of the flash memory (cold hard start)
rather than from RAM (warm start). Hold the RESET switch down during power-up to initiate a cold
hard start; otherwise, the switch has no effect.
NOTE
If your FloBoss is semi-functional, perform the previously described RAM
Backup Procedure before removing power from your FloBoss. Refer to
Section 2.5.2, Backup Procedure Before Removing Power on page 2-21.
Rev 5/002-23
FloBoss 407 Instruction Manual
CAUTION
The cold hard start reloads all restart configuration data from programmable ROM (flash memory). Generally, a Cold Hard Start should not be
used on a FloBoss that is actively gathering data and performing control.
Save or document all data and parameter values that could be affected
before performing the cold hard start. Refer to Section 2.5.2, Backup
Procedure Before Removing Power on page 2-21.
The following list shows the values that are saved to memory and restored after a Cold Hard Start.
♦ Device Address and Group.
♦ Station name.
♦ Number of history points in each module.
♦ Contract hour.
♦ User program enable flags – COM1, COM2, and USER/CALC
♦ All communication port settings, including power control settings.
♦ History point configuration.
♦ Discrete input parameters.
♦ Discrete output parameters.
♦ Analog input parameters.
♦ Analog output parameters.
♦ Pulse input parameters.
♦ AGA parameters.
♦ PID parameters.
♦ Configurable Opcode parameters.
♦ AI Calibration.
♦ FST tags.
♦ FST registers.
♦ FST run flag is cleared.
♦ FST instruction pointer is reset to the first instruction.
♦ Softpoints tags are set to their default values and all registers are set to zero.
2.5.6 Fuses
The FloBoss 407 uses the overload protection devices listed in Table 2-4. The overload protection
devices are not field replaceable.
2-24Rev 5/00
FloBoss 407 Instruction Manual
Table 2-4. Overload Protection Devices
IDRATINGUSE
F13A100 VA power limiting fuse.
PTR11.25AInput power protection.
PTR20.30AAnalog input 24 volts dc power (“+T” terminal).
2.5.7 RAM Backup and Real-Time Clock Battery
There is a battery on the processor board (installed in position B1 or B2) that provides power to the
real-time clock and backup power for the RAM. If this battery fails, the clock will stop running andthe FloBoss 407 will stop operating (the STATUS LED should be blinking). The battery is a 3.6volt lithium type and is secured with a hold-down clip. Under normal usage, this battery should last 5
to 10 years. However, if the FloBoss 407 is powered down for long periods of time, battery life will be
shortened.
To check the condition of the clock battery, install a new battery (see the following procedure) in the
unused battery socket location on the processor board, remove the existing battery, and use a multimeter to measure the voltage at the terminals of the removed battery. Leave the new battery installed if
the voltage of the old battery is less than 3.2 volts. If the old battery is still good, you can re-install it
into its socket and remove the new battery.
To install a clock battery into a functioning FloBoss 407 (if power is applied, it can remain applied):
NOTE
For Measurement Canada units, maintenance and resealing of the FloBoss
must be performed by authorized personnel only.
CAUTION
To avoid circuit damage when working with the unit, use appropriate
electrostatic discharge precautions, such as wearing a grounded wrist strap.
1. Locate the unused battery socket (typically B2) on the processor board. Insert the new battery
in this position.
2. Remove the old battery from the other battery socket (typically B1) by sliding the hold-down
clip to one side and lifting the battery from the board. If the clip does not readily rotate, you
may need to loosen the screw that secures it.
3. Move the hold-down clip to the new battery (tighten the clip screw if you loosened it in Step 2).
Rev 5/002-25
FloBoss 407 Instruction Manual
If the old battery was too weak to power the clock (the STATUS LED blinks when power is applied),
you need to reset the clock and reload the configuration. Refer to Section 2.5.3.
2.5.8 Calibrating the Board T e mper ature Input
The board temperature input (diagnostic analog input E5) normally does not need to be calibrated. If
you want to calibrate it, consult the factory.
2.5.9 Testing the Built-in Anal og Input Channels
Equipment Required: Multimeter
1K ohm resistor
0-5K ohm potentiometer
Personal computer with ROCLINK software installed
If a built-in analog input does not function correctly, first determine if problem is with the field device
or the FloBoss 407 I/O circuitry.
1. Disconnect the I/O terminal block to isolate the field device from the FloBoss 407 I/O.
2. If the FloBoss 407 provides loop power source, measure the voltage between terminal “+T”
and “-” of the AI channel under test. The loop power should be 23 volts dc minimum with
jumper P15 in the 24V position (W1 open in older units), or near to input power voltage
with jumper P15 in the 12V position (W1 installed).
3. Disconnect the battery terminal block. With an ohmmeter check between terminals “+T”
and “-” of the AI channel under test. If 0 ohms, the input has a shorted diode.
4. With an ohmmeter, check between terminals “+” and “-” of the AI channel under test. If 0
ohms, the input has shorted components.
5. Replace the termination board if the above tests indicate a fault. Refer to Section 2.5.10.
6. Connect a lead of a 250 ohm resistor and a 5K ohm potentiometer to the “+” terminal of the
AI channel. Connect the other resistor lead to terminal “-” and the potentiometer to terminal
“+T” of the AI channel under test.
7. Connect the FloBoss 407 to a computer running the ROCLINK configuration software.
Power up the FloBoss 407.
2-26Rev 5/00
FloBoss 407 Instruction Manual
8. Turn the potentiometer to vary the input to simulate a transmitter. Use the ROCLINK
software to confirm the input value changes.
A positive result on the above tests would show the FloBoss 407 input is operational. Check the field
wiring and transmitters for a fault.
2.5.10 Testing the Built-in Pulse Input Channel
Equipment Required: Multimeter
Jumper wire
Personal computer with ROCLINK software installed
Use the following tests to verify operation of the AI/PI channel when it is configured as a pulse input
(AI/PI jumper in the PI position).
1. Isolate the field device from the FloBoss 407 by disconnecting the AI/PI terminal block.
2. If the FloBoss 407 provides power to the field device, measure the voltage between terminal
“+T” and “-” of the AI/PI channel. This voltage should be 23 volts dc minimum with
jumper P15 in the 24V position (W1 open in older units), or near to input power voltage
with jumper P15 in the 12V position (W1 installed).
3. Connect a jumper from terminal “+T” to terminal “+” on the AI/PI connector. The LED
labeled PI IND on the termination board should light.
4. Connect the FloBoss 407 to a computer running the ROCLINK configuration software.
5. Again connect a jumper from terminal “+T” to terminal “+” on the pulse input connector.
The PI LED on the termination board should light. Use the ROCLINK software to confirm
that the input value changes for point A7.
Replace the termination board if the above tests indicate failure. Refer to Section 2.5.12. A positive
result on the above tests would show that the input is operational. Check the field wiring and
transmitters for a fault.
Rev 5/002-27
FloBoss 407 Instruction Manual
2.5.11 Replacing the Process o r Board
Equipment Required: Hex nut driver
Personal computer with ROCLINK software installed
Refer to Figure 2-1. Proceed as follows to replace the FloBoss 407 processor board:
NOTE
For Measurement Canada units, maintenance and resealing of the FloBoss must
be performed by authorized personnel only.
CAUTION
There is a possibility of losing the configuration and historical data held in RAM
while performing the following procedure. As a precaution, save the current
configuration and historical data to permanent memory. Refer to Section 2.5.2.
CAUTION
When installing devices in a hazardous area, make sure each device is labeled for
use in such areas. Procedures involving switching power on or off, or procedures
for installing or removing any wiring or components, must be performed only when
the area is known to be non-hazardous.
CAUTION
To avoid circuit damage when working with the unit, use appropriate electrostatic
discharge precautions, such as wearing a grounded wrist strap.
CAUTION
During this procedure, all power will be removed from the FloBoss and devices
powered by the FloBoss. Ensure that all connected input devices, output devices,
and processes will remain in a safe state when power is removed from the FloBoss
and also when power is restored to the FloBoss.
1. Perform the RAM backup procedure. Refer to Section 2.5.2, Backup Procedure
Before Removing Power on page 2-21.
2. Disconnect the PWR input connector from the termination board.
2-28Rev 5/00
FloBoss 407 Instruction Manual
The FloBoss 407 requires a minimum of 12.5 volts to start up. However, a newer
FloBoss 407 can be restarted below 12.5 volts by depressing the LV START switch
(see Figure 2-10 on page 2-20) while applying power.
3. Unplug the processor board power supply cord on the termination board at P1.
4. Disconnect the ribbon cable at P3 on the processor board.
5. Disconnect the keypad ribbon connector at P4 on the processor board.
6. Remove the communications card if present by removing its retaining screw and unplugging
the card from its mating connectors.
7. Remove the six nuts securing the processor board, and lift the board out of the case.
8. Remove the LCD from the processor board.
9. Install the LCD on the new processor board.
10. Place the new processor board in the case. Install the screws to secure the board to the case.
11. Install the keypad ribbon connector at P4 on the processor board.
NOTE
12. Install the ribbon cable at P3 on the processor board.
13. Install the communications card if required.
14. Plug the processor board power supply cord into P1 on the termination board.
15. Refer to Section 2.5.3, After Installing Components on page 2-22.
2.5.12 Replacing the Termination Board
Equipment Required:Small Philips screwdriver
Personal computer with ROCLINK software installed
Refer to Figure 2-1. Proceed as follows to replace the termination board:
CAUTION
There is a possibility of losing the configuration and historical data held in RAM
while performing the following procedure. As a precaution, save the current
configuration and historical data to permanent memory. Refer to Section 2.5.2.
CAUTION
When installing devices in a hazardous area, make sure each device is labeled for
use in such areas. Procedures involving switching power on or off, or procedures
for installing or removing any wiring or components, must be performed only when
the area is known to be non-hazardous.
Rev 5/002-29
FloBoss 407 Instruction Manual
To avoid circuit damage when working with the unit, use appropriate electrostatic
discharge precautions, such as wearing a grounded wrist strap.
During this procedure, all power will be removed from the FloBoss and devices
powered by the FloBoss. Ensure that all connected input devices, output devices,
and processes will remain in a safe state when power is removed from the FloBoss
and also when power is restored to the FloBoss.
For a Measurement Canada FloBoss 407, resealing of the case must be performed
by authorized personnel only.
1. Perform the RAM backup procedure. Refer to Section 2.5.2 on page 2-21.
2. Disconnect the PWR input connector (terminal block) from the termination board.
CAUTION
CAUTION
NOTE
NOTE
The FloBoss 407 requires a minimum of 12.5 volts to start up. However, a newer
FloBoss 407 can be restarted below 12.5 volts by depressing the LV START switch
(see Figure 2-10 on page 2-20) while applying power.
3. Disconnect all connected field wiring, including MVS, built-in inputs, and I/O
modules. This can be done by unplugging the terminal blocks.
4. Disconnect all communication card and RJ11 wiring if necessary.
5. Disconnect the ribbon cable at P3 on the termination board.
6. Disconnect operator interface port wiring on the termination board at P2.
7. Disconnect the processor board power connector from the termination board at P1.
8. Remove the five screws securing the termination board, and lift the board out of the case.
9. Place the new termination board in the case and install the securing screws to the case.
10. Connect the ribbon cable at P3 on the processor board.
11. Connect the communication card wiring if required.
12. Connect the field wiring.
13. Connect the operator interface port wiring on the termination board at P2.
14. Connect the processor board power connector to the termination board at P1.
15. Plug the processor board power supply cord into P1 on the termination board.
16. Refer to Section 2.5.3, After Installing Components on page 2-22.
2-30Rev 5/00
FloBoss 407 Instruction Manual
2.5.13 Replacing the Flash ROM
Equipment Required: Flash ROM extractor
Personal computer with ROCLINK software installed
Note that a firmware upgrade can also be performed without removing the flash chip; see the Update
Firmware procedure described in Section 2 of the ROCLINK user manual. Proceed as follows to
physically replace the FloBoss 407 flash ROM chip (refer to Figure 2-1):
CAUTION
During the following procedure, configuration data held in Flash ROM will be lost.
There is also a possibility of losing the configuration and historical data held in
RAM. Therefore, save the current configuration and historical data to permanent
memory. Refer to Section 2.5.2.
CAUTION
When installing devices in a hazardous area, make sure each device is labeled for
use in such areas. Procedures involving switching power on or off, or procedures
for installing or removing any wiring or components, must be performed only when
the area is known to be non-hazardous.
CAUTION
To avoid circuit damage when working with the unit, use appropriate electrostatic
discharge precautions, such as wearing a grounded wrist strap.
CAUTION
During this procedure, all power will be removed from the FloBoss and devices
powered by the FloBoss. Ensure that all connected input devices, output devices,
and processes will remain in a safe state when power is removed from the FloBoss
and also when power is restored to the FloBoss.
NOTE
For a Measurement Canada FloBoss 407, resealing of the case must be performed
by authorized personnel only.
1. Perform the RAM backup procedure. Refer to Section 2.5.2, Backup Procedure
Before Removing Power on page 2-21.
2. Disconnect the PWR input connector from the processor board.
Rev 5/002-31
FloBoss 407 Instruction Manual
The FloBoss 407 requires a minimum of 12.5 volts to start up. However, a newer
FloBoss 407 can be restarted below 12.5 volts by depressing the LV START switch
(see Figure 2-10 on page 2-20) while applying power.
3. Using a Flash ROM Extractor, remove the flash ROM chip located at U2 on the
termination board.
4. Gently press the new flash ROM chip into the socket located at U2 on the
termination board. The flash ROM chip should fit securely into the socket.
5. Connect the PWR input connector to the processor board.
6. Refer to Section 2.5.3, After Installing Components on page 2-22.
7. Refer to the ROCLINK Configuration Software User Manual, which explains how to
load updated firmware and user programs into the flash ROM (if required).
NOTE
2.5.14 Keypad and Display Replacement
To replace a damaged or faulty keypad or display, contact your Fisher Representative.
2.5.15 Integral MVS Replac ement
If an MVS that is integral with a FloBoss 407 needs to be replaced or repaired, contact your Fisher
Representative.
2.6 SPECIFICATIONS
The following pages provide a table of specifications for the FloBoss 407.
2-32Rev 5/00
FloBoss 407 Instruction Manual
FloBoss 407 Specifications
PROCESSOR
NEC V25+ running at 10 MH z.
MEMORY
Program:
programmable) for firmware, configuration, etc.
Data:
Memory R es e t :
switch enables a cold start from factory defaults.
TIME FUNCTIONS
Clock Type:
supply, battery-backed. Year/Month/Day and
Hour/Minute/Second.
Clock Accuracy:
Watchdog Timer:
1.2 seconds and resets the processor. Processor
restart is automatic.
DIAGNOSTICS
These values are monitored and alarmed: RAM
validity/operation, analog input mid-scale voltage,
power input voltage, and board tem per atur e.
COMMUNICATIONS PORTS
Operator Interface:
Software configured; 300 to 9600 BPS baud rate
selectable. Screw-cap protected connecto r.
COM1:
Software configured; 300 to 9600 BPS baud rate
selectable. Eight-terminal connector provided on I/O
board.
COM2:
communications card. Nine-terminal connector
provided on I/O board.
POWER
Input:
for input sourcing, I/O modules, MVS, and communications card.
Loop/Source:
for transmitter power at the “+T” terminals (25 mA
maximum) and at the “A” terminals on the modular
I/O channels.
ANALOG INPUTS (BUILT-IN)
Quanti ty/Type:
(current loop if scaling resistor is used).
Terminals:
negative input ( common) .
Voltage:
mA, with a 250 ohm resistor install ed across ter minals
“+” and “-”.
when tested per SAMA PMC 33.1 in field classified
as 3-abc with field strength of 30 V/m, circuit board
properly mounted, and doors closed.
0.1% over operating temperature range.
One megohm.
Double-pole, low-pass.
12 bits.
30 microseconds.
50 ms mi ni mu m.
1 high-speed source or isolated
“+T” source power, “+” positive input, “-”
8 to 30 Vdc (ON st ate) ; 0 t o 4 V d c (O FF
10 kHz ma xi mu m.
50 ms mi ni mu m.
High-speed, multi-drop, serial interface with
“A” and “B” for data; “+” and “-” for power.
1 sec max.
2 line by 20 chara cte r LCD. Ove rall siz e is
15 multi-function, membrane keys. Keys
-40 to 75 °C (- 40 to 167
-50 to 85 °C (-58 to
To 95% non-condensing.
Less than 0.1% effect on overall accu-
Meets IEC 801-2, Level 3.
Meets IEC 801-4, Level 4.
No effect on operation of unit
Rev 5/002-33
FloBoss 407 Instruction Manual
Specifications (Continued)
DIMENSIONS
Overall, FloBoss 407 only:
by 4.4 in. D (305 mm by 236 mm by 112 mm).
Overall, with Integral MVS:
by 5.1 in. D (457 mm by 236 mm by 130 mm).
Wall Mounting:
mm) between mounting hole centers. Mounting hole
diameter is 0.37 in. (9.4 mm).
Pipestand Mounting:
U-bolt mounting kit (included).
ENCLOSURE
Die-cast low-copper aluminum alloy with three 0.75 in.
NPT holes in bottom. Single-piece gasketed doors.
Coated with ANSI 61 gray polyurethane paint. Meets
CSA Type 4X rating.
2.8 in. W by 12.1 in. H (71 mm by 308
12.0 in. H by 9.3 in. W
18.0 in. H by 9.3 in. W
Mounts on 2-inch pipe with
WEIGHT
FloBoss 407:
With Integral MVS:
APPROVALS
Standard Version:
hazardous locations Class I, Division 2, Groups A,
B, C, and D.
Measurement Canad a Ver sio n:
Measurement (Industry) Canada for gas custody
transfer, in addition to app roval by CSA for hazardou s
locations (see Standard Version). Note that I/O
Modules must not be used to supply flow inputs to
the FloBoss in a Measurement Canada installation.
7 lb. (3.2 kg).
17 lb. (7.7 kg).
Approved by CSA for
Approved by
2-34Rev 5/00
FloBoss 407 Instruction Manual
SECTION 3 — INPUT/OUTPUT MODULES
3.1 SCOPE
This section describes the I nput/Ou tpu t (I/O) Modules used with the FloBoss™ 407 Flow Manager and
ROC300-Series products (except RO C30 6). This section contains the following information:
InformationSectionPage Number
Product Descriptions3.23-2
Analog Input Loop and Differential Modules3.2.13-3
Analog Input Source Module3.2.23-4
Analog Output Source Module3.2.33-4
Discrete Input Source and Isolated Modules3.2.43-4
Discrete Output Source and Isolated Modules3.2.53-4
Discrete Output Relay Module3.2.63-5
Pulse Input Source and Isolated Modules3.2.73-5
Slow Pulse Input Source and Isolated Modules3.2.83-5
Low-Level Pulse Input Module3.2.93-6
RTD Input Module3.2.103-6
HART Interface Module3.2.113-6
Removal, Addition, and Replacement Procedures3.63-37
Impact on I/O Point Configuration3.6.13-37
Removing/Installing an I/O Module3.6.23-38
I/O Module Specifications3.73-40
3.2 PRODUCT DESCRIPTIONS
The I/O modules plug into the I/O module sockets and accommodate a wide range of process inputs and
outputs. Units used in Measurement/Industry Canada installations must not employ I/O modulesfor flow measurement. The following modules are available:
♦ AI Loop
♦ AI Differential
♦ AI Source
♦ AO Source
♦ DI Source
♦ DI Isolated
♦ DO Source
♦ DO Isolated
♦ DO Relay
♦ PI Source
♦ PI Isolated
♦ Slow Pulse Input Source
♦ Slow Pulse Input Isolated
♦ Low-Level Pulse Input
♦ RTD Input
♦ HART® Interface
3-2Rev 5/00
FloBoss 407 Instruction Manual
Adjacent to each I/O module socket is a plug-in terminal block for field wiring connections. The plugin terminal blocks permit removal and replacement of the modules without the need to disconnect field
wiring. The ROC/FloBoss accommodates any number of modules in any combination up to the limit of
the I/O module rack or board. Figure 3-1 shows a typical I/O module.
STATIC
SENSITIVE
DOC0034C
Figure 3-1. Typical I/O Module
3.2.1 Analog Input Loop and Differential Modules
The Analog Input Loop (AI Loop) and Analog Input Differential (AI Differential) modules are used for
monitoring current loop and voltage output devices. Each AI module uses a scaling resistor for scaling
loop current to achieve the proper input voltage.
The AI Loop module provides a source voltage for powering current loop devices and can also be used
as a single-ended voltage output. The AI Differential module monitors loop current or voltage input
from externally-powered devices and provides electrical isolation from the ROC/FloBoss power
supplies.
Rev 5/003-3
FloBoss 407 Instruction Manual
3.2.2 Analog Input Source Module
The Analog Input Source (AI Source) module monitors current loop or voltage output devices. The
module provides a regulated 10-volt source for powering a device, usually a low power transmitter, and
uses a scaling resistor for converting loop current to input voltage.
3.2.3 Analog Output Source Module
The Analog Output Source (AO Source) module provides both a current and a voltage output for
powering analog devices. These outputs are isolated from each other and can be used simultaneously.
A scaling resistor is provided for setting the minimum loop resistance of the current loop to 0 ohms
(installed) or 220 ohms (removed).
3.2.4 Discrete Input Source and Isolated Modules
The Discrete Input Source (DI Source) and Discrete Input Isolated (DI Isolated) modules monitor the
status of relays, solid-state switches, or other two-state devices. Each module can accommodate one
discrete input.
Both types of modules provide an LED that lights when the input is active and use a scaling resistor for
scaling the input range. Functions supported by both modules are: discrete latched input, discrete
status input, and time-duration input.
The source module provides a source voltage for dry relay contacts or for an open-collector solid-state
switch. The isolated module accepts an external voltage from a powered two-state device and provides
electrical isolation from the ROC power supplies.
3.2.5 Discrete Output Source and Isolated Modules
The Discrete Output Source (DO Source) and Discrete Output Isolated (DO Isolated) modules provide
two-state outputs to energize relays and power small electrical loads. Each module provides one
discrete output.
Both types of modules use an LED to show the status of the output and are fused for protection against
excessive current. Functions supported by both modules are: sustained discrete output, momentary
discrete output, slow pulse-train output, and time-duration discrete output.
The source module supplies switched current-limited power to small loads. The isolated module acts as
a solid-state normally-open switch for activating externally powered devices. The solid-state switch is
optically isolated from the power supplies in the ROC/FloBoss.
3-4Rev 5/00
FloBoss 407 Instruction Manual
3.2.6 Discrete Output Relay Module
The Discrete Output Relay (DO Relay) module provides two sets of “dry” relay contacts to switch
voltages of up to 250 volts ac. One set of contacts is normally open and the other set is normally
closed. Two types of relay modules are available, one with a 12 volts dc energizing coil and the other
with a 24 volts dc energizing coil.
An LED shows the status of the output. Functions supported by the module include: sustained discrete
output, momentary discrete output, slow pulse-train output and time-duration discrete output. The
module contacts are isolated from the ROC/FloBoss power supplies.
3.2.7 Pulse Input Source and Isolated Modules
The Pulse Input Source (PI Source) and Pulse Input Isolated (PI Isolated) modules count pulses from
pulse-generating devices. Each module can accommodate one pulse input.
Both types of modules use an LED to show when the input is active and use a scaling resistor for
scaling the input range. Input pulses are counted by a 16-bit counter capable of storing up to 6.5
seconds of pulse counts for a 10-KHz input signal. Functions supported by both modules are:
slow-counter input, slow rate input, fast counter input, and fast rate input.
The source module provides a source voltage for dry relay contacts or for an open-collector solid-state
switch. The isolated module accepts an external voltage from a powered device and provides electrical
isolation from the ROC/FloBoss power supplies.
3.2.8 Slow Pulse Input Source and Isolated Modules
The Slow Pulse Input Source (SPI Source) and Slow Pulse Input Isolated (SPI Isolated) modules count
the changes in the status of relays, solid-state switches, or other two-state devices. Each module can
accommodate one pulse input.
The modules provide an LED that lights when the input is active and use a scaling resistor for scaling
the input range. Functions supported are controlled by the ROC/FloBoss firmware. For example: raw
pulse accumulation, rate in engineering units (EUs), today’s total in EUs, or rate alarm.
The source module provides a source voltage for dry relay contacts or for an open-collector solid-state
switch. The isolated module accepts an external voltage from a powered two-state device and provides
electrical isolation from the ROC/FloBoss power supplies.
Rev 5/003-5
FloBoss 407 Instruction Manual
3.2.9 Low-Level Pulse Input Module
The Low-Level Pulse Input module counts pulses from pulse-generating devices having a voltage range
of 30 millivolts to 3 volts peak-to-peak. The module can accommodate one pulse input.
Input pulses are counted by a 16-bit counter that is capable of storing up to 22 seconds of pulse counts
for a 3 KHz input signal. The module provides electrical isolation between the input pulses and the
ROC/FloBoss power supplies.
3.2.10 RTD Input Module
The Resistance Temperature Detector (RTD) module monitors the temperature signal from an RTD
source. The module can accommodate one input from a two-, three-, or four-wire RTD source.
The active element of an RTD probe is a precision, temperature-dependent resistor, made from a
platinum alloy. It has a predictable positive temperature coefficient, meaning its resistance increases
with temperature. The RTD input module works by supplying a small current to the RTD probe and
measuring the voltage drop across it. Based on the voltage curve of the RTD, the signal is converted to
temperature by the ROC/FloBoss firmware.
3.2.11 HART Interface Module
The HART Interface Module provides communications between a ROC/FloBoss and other devices
using the Highway Addressable Remote Transducer (HART) protocol. The module has its own
microprocessor and mounts in the I/O module sockets of a ROC/FloBoss.
The HART Interface Module communicates digitally to HART devices through the I/O termination
blocks associated with the module position. Each HART module contains two separate channels. Each
channel polls all HART devices connected to it before the other channel is polled. Each channel can be
configured to operate in either the point-to-point mode or the multi-drop mode. In the point-to-point
mode, each module channel supports one HART device.
In the multi-drop mode, each channel can support up to five HART devices for a total of ten devices for
each module. By using the multi-drop mode with multiple HART modules, up to 32 HART devices
(limited by the software) can be supported by a single ROC/FloBoss.
3-6Rev 5/00
FloBoss 407 Instruction Manual
3.3 INITIAL INSTALLATION AND SETUP
Each I/O module installs in the ROC/FloBoss in the same manner. Any I/O module can be installed
into any I/O module socket. To install a module on a ROC/FloBoss that is not in service, perform the
following steps. For an in-service ROC/FloBoss, refer to Section 3.6.
CAUTION
Failure to exercise proper electrostatic discharge precautions (such as wearing a
grounded wrist strap) may reset the processor or damage electronic components,
resulting in interrupted operations.
CAUTION
When preparing a unit for installation into a hazardous area, change components in
an area known to be non-hazardous.
CAUTION
Units used for Measurement Canada installations must not employ I/O modules to
supply flow measurement inputs.
1. Install I/O module by aligning the pins with the desired I/O module socket and pressing
gently, but firmly straight down.
2. Tighten the module retaining screw.
3. Make sure a field wiring terminal block is installed in the socket adjacent to where the I/O
module was installed. If a Lightning Protection Module is to be installed for this I/O
channel, refer to Appendix A.
3.3.1 Calibrating an I/O Module
After an I/O module is installed, configure and calibrate the associated I/O channel as needed by using
the ROCLINK Configuration Software.
Rev 5/003-7
FloBoss 407 Instruction Manual
3.4 CONNECTI NG THE I/O MODULES TO WIRING
Each I/O module is electrically connected to field wiring by a separate plug-in terminal block. In
addition, the ROC/FloBoss enclosures provide a ground bus bar for terminating the sheath on shielded
wiring. The following paragraphs provide information on wiring field devices to each type of I/O
module.
CAUTION
The sheath surrounding shielded wiring should never be connected to a signal
ground terminal or to the common terminal of an I/O module. Doing so makes the
I/O module susceptible to static discharge, which can permanently damage the
module. Connect the shielded wiring sheath to a suitable earth ground only.
3.4.1 Analog Input Loop Module
The Analog Input Loop module monitors either loop current or output voltage from field devices. The
module provides source power at terminal A for the loop. The AI Loop module operates by measuring
the voltage at terminals B and C. For current loop monitoring, scaling resistor R1 generates a voltage
across terminals B and C that is proportional to the loop current (I). A 250-ohm scaling resistor (R1) is
supplied by the factory (0.1%, 1/8W) to accommodate either 0-to-20 milliamp or 4-to-20 milliamp
current loop transmitters. This translates to a maximum operating input voltage of 5 volts dc, which is
the upper limit of the module.
When using a transmitter with a maximum current requirement different than 20 milliamps, R1 should
be scaled to achieve full scale deflection at 5 volts dc. The formula for determining a new value of R1
is given in Figure 3-2, where “I Maximum” is the upper end of the operating current range (such as
0.025 amps for a 0 to 25 milliamp device).
ROC-POWERED
CURRENT LOOP
DEVICE
+
-
TO SELECT PROPER VALUE OF R1:
= SOURCE VOLTAGE FROM MODULE = 11 TO 30 VDC, 25 mA MAX
V
S
5 VOLTS
R1 =
I MAXIMUM
I
A
B
C
R1=250
+T
+
–
AI LOOP
I LIMIT
DOC0153J
V
S
Figure 3-2. AI Loop Module Field Wiring for Current Loop Devices
3-8Rev 5/00
FloBoss 407 Instruction Manual
A
Figure 3-3 shows a typical voltage signal input. Terminal B is the “+” signal input and terminal C is the
“-” signal input. These terminals accept a voltage signal in the 0 to 5 volt range. Since terminal C
connects to a signal ground (non-isolated), the analog input must be a single-ended. Ensure that noscaling resistor (R1) is installed when the module is used to sense a voltage signal.
SELF-POWERED
VOLTAGE DEVI CE
Figure 3-3. AI Loop Module Field Wiring for Voltage Devices
SIGNAL = 1 TO 5 VDC
+
-
R1=OPEN
AI LOOP
+T
+
B
I LIMIT
V
S
C
DOC0153A
(modified)
Rev 5/003-9
FloBoss 407 Instruction Manual
3.4.2 Analog Input Differential Module
A schematic representation of the field wiring connections to the input circuit of the Analog Input
Differential module is shown in Figure 3-4, Figure 3-5, and Figure 3-6.
The Analog Input Differential module measures either output voltage (V
or loop current (I) from
)
o
externally-powered devices only. The module operates by measuring the voltage between field wiring
terminals B and C. The module input is semi-isolated from the ROC/FloBoss power supply and signal
commons.
When connecting voltage devices, the 5-volts input voltage limit of the module must not be exceeded.
If the output of the field device is in the range of 0 to 5 volts dc, do not use a scaling resistor; ensure
that the supplied 250-ohm scaling resistor is removed. Refer to Figure 3-4 for connecting field devices
with outputs of 5 volts dc or less.
For field devices with output voltages that exceed 5 volts dc, two scaling resistors, R1 and R2, are
required (not supplied). Figure 3-5 shows how to connecting field devices with outputs exceeding 5
volts dc and where to install scaling resistors (at least 1%, 1/8W). The equation for determining values
of scaling resistors R1 and R2 is given in Figure 3-5. For example, if VO = 10 volts, and R1 = 250
ohms, then R2 = 250 ohms. Note that R1 must be less than 4.5K ohms.
SELF-POWERED
ANALOG VOLTAGE
DEVICE
R1 = OPEN
N/C
+
V
o
-
V = VOLTAGE FROM ANALOG DEVICE = 0 TO 5 VDC
o
A
+
B
-
C
AI DIFF
200K
200K
DOC0155A
Figure 3-4. AI Differential Module Field Wiring for Low Voltage Devices
SELF-POWERED
ANALOG VOLTAGE
DEVICE
+
V
o
-
TO SCALE R1 AND R2 FOR:
V = VOLTAGE FROM ANALOG DEVICE = 5 TO 100 VDC
o
R1 MUST BE LESS THAN 4.5K OHM (1.0K OHM TYPICAL)
R2 =
R1(V - 5)
o
5
R1
N/C
A
+
B
R2
-
C
AI DIFF
200K
200K
DOC0156A
Figure 3-5. AI Differential Module Field Wiring for Higher Voltage Devices
3-10Rev 5/00
FloBoss 407 Instruction Manual
For current loop devices, scaling resistor R1 generates a voltage across terminals B and C that is
proportional to the loop current. When connecting current loop devices, the value of R1 must be
selected such that the 5-volt input limit of the module is not exceeded under maximum operating
current conditions. For 0 to 20 milliamp or 4 to 20 milliamp devices, the value of R1 would be 250
ohms. In this case, you can use the 250-ohm (0.1%, 1/8W) scaling resistor supplied by the factory. The
formula for determining the value of R1 is given in Figure 3-6, where “I Maximum” is the upper end of
the operating current range (such as 0.025 amps for a 0 to 25 milliamp device).
N/C
SELF-POWERED
CURRENT LOOP
DEVICE
+
V
o
–
TO SELECT PROPER VALUE FOR R1:
V = VOLTAGE FROM ANALOG DEVICE = 0 TO 5 VDC
o
5 VOLTS
R1 =
I MAXIMUM
I
A
+
B
–
C
Figure 3-6. AI Differential Module Field Wiring for Current Loop Devices
R1
AI DIFF
200K
200K
DOC0154A
Rev 5/003-11
FloBoss 407 Instruction Manual
–
–
A
–
–
A
3.4.3 Analog Input Source Module
A schematic representation of the field wiring connections to the input circuit of the Analog Input
Source module is shown in Figure 3-7 and Figure 3-8. The AI Source module is normally used to
monitor the voltage output of low-voltage transmitters, but it can be used for monitoring loop current.
The module provides source power at terminal A for the loop. The Analog Input Source module
operates by measuring the voltage across terminals B and C. The module accepts a maximum input
voltage of 5 volts dc, which is the upper operating limit of the module.
Figure 3-7 shows a typical voltage signal input. Terminal B is the positive (+) signal input and terminal
C is the negative (-) signal input. These terminals accept a voltage signal in the 0 to 5 volt range. Since
terminal C connects to common, the analog input can only be a single-ended input. Make sure no
scaling resistor is installed when wiring the module for a voltage signal.
I SRC
ROC-POWERED
VOLTAGE DEVICE
+10Vdc
+
SIGNAL = 0 TO 5 Vdc
A
B
C
+10Vdc
+
V SRC
Vs
Figure 3-7. AI Source Module Field Wiring for Voltage Devices
The AI Source module can be used for monitoring loop current as shown in Figure 3-8. For current
loop monitoring, scaling resistor R1 generates a voltage across terminals B and C that is proportional to
the loop current (I). For example, a 250-ohm scaling resistor would accommodate either 0 to 20
milliamp, or 4 to 20 milliamp current loop transmitters (the transmitter must be able to operate on 10
volts dc or be powered from another source). This translates to a maximum operating input voltage of 5
volts dc, which is the upper limit of the module. When using a transmitter with a maximum operating
current requirement different than 20 milliamps, R1 should be sized to achieve full scale deflection at 5
volts. The formula for determining a new value of R1 is given in Figure 3-8.
ROC-POWERED
CURRENT LOOP
DEVICE
+
TO SELECT PROPER VALUE OF R1:
Vs = SOURCE VOLTAGE FROM MODUL E = 10 Vdc, 20 mA MAX
5 VOLTS
R1 =
I MAXIMUM
I
A
B
C
R1
+10 Vdc
+
V SRC
I SRC
Vs
Figure 3-8. AI Source Module Field Wiring for Current Loop Devices
3-12Rev 5/00
FloBoss 407 Instruction Manual
3.4.4 Analog Output Source Module
A schematic representation of the field wiring connections to the output circuit of the Analog Output
Source module is shown in Figure 3-9 and Figure 3-10. The AO Source module can provide either loop
current or output voltage to non-powered field devices. The Analog Output Source module provides
a 0- to 5.5-Volt output at terminal A, and a 0 to 30 milliamp current source output at terminal B.
Terminal C is referenced to the ROC/FloBoss common.
Resistor R1 (0-ohm resistor supplied) helps keep the loop resistance within the operating range of the
module. Remove the 0-ohm resistor when the loop resistance between terminals B and C is less than
100 ohms.
Terminals A and B are both active at the same time. Figure 3-9 shows wiring for a ROC/FloBosspowered current loop device, and Figure 3-10 shows wiring for an output voltage to non-powered field
devices.
AO SRC
LEVEL
DOC0158A
(Modified)
R1=0
220
+V
A
+I
COM
REMOVE RESISTOR R1 WHEN LOOP
RESISTANCE IS LESS THAN 100 OHMS
I = 30 mA MAX
+
B
C
-
I
ROC-POWERED
LOOP DEVICE
Figure 3-9. Analog Output Source Module Field Wiring for Current Loop Devices
AO SRC
LEVEL
DOC0159A
R1=0
+V
A
+I
220
COM
V = OUTPUT VOLTAGE FROM MODULE = 0 TO 5 VDC, 5 mA
o
+
V
o
B
-
C
ROC-POWERED
VOLTAGE DEVICE
Figure 3-10. Analog Output Source Module Field Wiring for Voltage Devices
Rev 5/003-13
FloBoss 407 Instruction Manual
V
3.4.5 Discrete Input Source Module
A schematic representation of the field wiring connections to the input circuit of the Discrete Input
Source module is shown in Figure 3-11.
CAUTION
The Discrete Input Source module is designed to operate only with non-powered
discrete devices such as “dry” relay contacts or isolated solid-state switches.
Use of the module with powered devices may cause improper operation or
damage.
The Discrete Input Source module operates by providing a voltage across terminals B and C that is
derived from internal voltage source Vs. When a field device, such as a set of relay contacts, is
connected across terminals B and C, the closing of the contacts completes a circuit which causes a flow
of current between Vs and ground at terminal C. This current flow is sensed by the DI module, which
signals the ROC/FloBoss electronics that the relay contacts have closed. When the contacts open,
current flow is interrupted and the DI module signals the ROC/FloBoss electronics that the relay
contacts have opened.
A 10-ohm scaling resistor (R1) is supplied by the factory and accommodates a source voltage (Vs)
of 11 to 30 volts dc. The source voltage is the input voltage to the ROC/FloBoss. However, it is
desirable to optimize the value of R1 to reduce the current drain from the source or reduce the heat
generated in the module due to high source voltage. The formula for determining the value of R1 is
given in Figure 3-11. For optimum efficiency, R1 should be scaled for a loop current (I) of 3
milliamps.
R1=10
DI SRC
ROC-POWERED
PULSE DEVICE
I
R
W
TO OPTIMIZE SCALING RESISTOR R1:
VS – 1
R1 =
R1 + R
I = LOOP CURRENT = 3 mA TYPICAL
R
W
VS = SOURCE VOLTAGE FROM MODULE = 11 TO 30 VDC
I
+ 3.3K = LOOP RESISTANCE = 4.5K OHMS MAX
W
= RESISTANCE OF FIELD WIRING
– R
– 3.3K
W
N/C
A
+
B
–
C
3.3K
DOC0143A
Modified
Figure 3-11. Discrete Input Source Module Field Wiring
3-14Rev 5/00
FloBoss 407 Instruction Manual
–
–
3.4.6 Discrete Input Isolated Module
A schematic representation of the field wiring connections to the input circuit of the Discrete Input
Isolated module is shown in Figure 3-12.
NOTE
The Discrete Input Isolated module is designed to operate only with discrete
devices having their own power source such as “wet” relay contacts or
two-state devices providing an output voltage. The module is inoperative
with non-powered devices.
The Discrete Input Isolated module operates when a field device provides a voltage across terminals B
and C of the module. The voltage sets up a flow of current sensed by the module which, in turn, signals
the ROC/FloBoss electronics that the field device is active. When the field device no longer provides a
voltage, current stops flowing and the DI module signals the ROC/FloBoss electronics that the device is
inactive.
A 10-ohm scaling resistor (R1) is supplied by the factory and accommodates an external voltage (Vo) of
11 to 30 Volts dc. However, it is desirable to optimize the value of R1 to reduce the current drain from
the source or reduce the heat generated in the module due to high source voltage. The formula for
determining the optimum value of R1 is given in Figure 3-12. For best efficiency, R1 should be scaled
for a loop current (I) of 3 milliamps.
SELF-POWERED
DISCRETE DEVICE
VO – 1
I
I
R
W
RW – 3.3KR1 =
+
V
O
–
TO OPTIMIZE SCALING RES ISTOR R1:
R1 + RW + 3.3K = LOOP RESISTAN CE = 4.5K OHMS MAX
I = LOOP CURRENT = 3 m A TY PICAL
R
= RESISTANCE OF FIELD WI RI NG
W
= VOLTAGE FROM DISCRETE DEVICE = 11 TO 30 VDC
V
O
R1=10
N/C
A
+
B
C
DI ISO
3.3K
DOC0144A
Figure 3-12. Discrete Input Isolated Module Field Wiring
Rev 5/003-15
FloBoss 407 Instruction Manual
3.4.7 Discrete Output Source Module
A schematic representation of the field wiring connections to the output circuit of the Discrete Output
Source module is shown in Figure 3-13.
CAUTION
The Discrete Output Source module is designed to operate only with non-powered
discrete devices such as relay coils or solid-state switch inputs. Using the module
with powered devices may cause improper operation or damage to occur.
The Discrete Output Source module provides a switched voltage across terminals B and C that is
derived from internal voltage source Vs. A field device, such as a relay coil, is energized when the
ROC/FloBoss electronics provides a voltage at terminals B and C. When Vs is switched off by the
ROC/FloBoss electronics, the field device is no longer energized.
CAUTION
When using the Discrete Output Source module to drive an inductive load such as a
relay coil, a suppression diode should be placed across the input terminals to the
load. This protects the module from the reverse EMF spike generated when the
inductive load is switched off.
1 Amp
N/C
+
–
A
+
B
C
–
ROC-POWERED
DISCRETE DEVICE
V
S
DO SRC
+5V
CONTROL
I LIMIT
DOC0145A
Figure 3-13. Discrete Output Source Module Field Wiring
3-16Rev 5/00
FloBoss 407 Instruction Manual
3.4.8 Discrete Output Isolated Module
A schematic representation of the field wiring connections to the output circuit of the Discrete Output
Isolated module is shown in Figure 3-14.
NOTE
The Discrete Output Isolated module is designed to operate only with discrete
devices having their own power source. The module is inoperative with
non-powered devices.
The Discrete Output Isolated module operates by providing a low or high-output resistance to a field
device. When the field device provides a voltage across terminals A and B of the module, current
either flows or is switched off by the DO Isolated module. The switching is controlled by the
ROC/FloBoss electronics.
DO ISO
+5V
CONTROL
DOC0146A
(Modified)
1 Amp
+
–
N/C
A
B
C
VO = VOLTAGE FROM DISCRETE DEVICE = 11 TO 30 VDC, 1.0 A MAX
+
V
O
SELF-POWERED
DISCRETE DEVICE
–
Figure 3-14. Discrete Output Isolated Module Field Wiring
Rev 5/003-17
FloBoss 407 Instruction Manual
–
3.4.9 Discrete Output Relay Module
A schematic representation of the field wiring connections to the output circuit of the Discrete Output
Relay module is shown in Figure 3-15.
NOTE
The Discrete Output Relay module is designed to operate only with discrete
devices having their own power source. The module will be inoperative with
non-powered devices.
The Discrete Output Relay module operates by providing both normally-closed and normally-open
contacts to a field device. Normally-closed contacts use terminals B and C, and normally-open contacts
use terminals A and B. The status of the contacts (open or closed) is controlled by the ROC/FloBoss
software.
There are two versions of the relay module. The 12-volt version (which has a 12-volt energizing coil)
must be used when the ROC/FloBoss input voltage is a nominal 12 volts dc, and the 24-volt version
(which has a 24-volt energizing coil) must be used when the ROC/FloBoss input voltage is a nominal
24 volts dc.
V
S
DO RLY
CONTROL
DOC0147A
NO
A
COM
B
NC
C
TERMINAL A CONNECTION TO BE MADE FOR NORMALLY OPEN APPLICATIONS
TERMINAL B IS COMMON
TERMINAL C CONNECTION TO BE MADE FOR NORMALLY CLOSED APPLICATIONS
= VOLTAGE FROM DISCRETE DEVICE = 0 TO 30 VDC OR 0 TO 115 VAC, 5 A MAX
V
O
+
V
O
Figure 3-15. Discrete Output Relay Module Field Wiring
SELF-POWERED
DISCRETE DEVICE
3-18Rev 5/00
FloBoss 407 Instruction Manual
V
3.4.10 Pulse Input Source Module
A schematic representation of the field wiring connections to the input circuit of the Pulse Input
Source module is shown in Figure 3-16.
CAUTION
The Pulse Input Source module is designed to operate only with non-powered
discrete devices such as “dry” relay contacts or isolated solid-state switches. Use of
the module with powered devices may cause improper operation or damage to
occur.
The Pulse Input Source module provides a voltage across terminals B and C that is derived from
internal voltage source Vs. When a field device, such as a set of relay contacts, is connected across
terminals B and C, the opening and closing of the contacts causes current to either flow or not flow
between Vs and ground at terminal C.
This interrupted, or pulsed current flow is counted and accumulated by the PI Source module which
provides the accumulated count to the ROC/FloBoss electronics upon request.
A 10-ohm scaling resistor (R1) is supplied by the factory and accommodates a source voltage (Vs)
of 11 to 30 volts dc and a pulse source with a 50% duty cycle. The source voltage is the input voltage
to the ROC/FloBoss. However, it is desirable to optimize the value of R1 to reduce the current drain
from the source or reduce the heat generated in the module due to high source voltage. The formula for
determining the value of R1 is given in Figure 3-16. For optimum efficiency, R1should be scaled
for a loop current (I) of 5 milliamps.
R1=10
PI SRC
ROC-POWERED
PULSE DEVICE
I
R
W
TO OPTIMIZE SCALING RESISTOR R1:
VS – 1
R1 =
R1 + R
I = LOOP CURRENT = 5 mA TYPICAL
R
W
VS = SOURCE VOLTAGE FROM MODULE = 11 TO 30 VDC
I
+ 2.2K = LOOP RESISTANCE = 3.4K OHMS MAX
W
= RESISTANCE OF FIELD WIRING
– R
– 2.2K
W
N/C
A
+
B
–
C
2.2K
Figure 3-16. Pulse Input Source Module Field Wiring
Rev 5/003-19
FloBoss 407 Instruction Manual
–
3.4.11 Pulse Input Isolated Module
A schematic representation of the field wiring connections to the input circuit of the Pulse Input
Isolated module is shown in Figure 3-17.
NOTE
The Pulse Input Isolated module is designed to operate only with discrete
devices having their own power source such as “wet” relay contacts or
two-state devices providing an output voltage. The module is inoperative with
non-powered devices.
The Pulse Input Isolated module operates when a field device provides a voltage across terminals B and
C of the module. The voltage sets up a flow of current sensed by the module. When the field device no
longer provides a voltage, current stops flowing.
This interrupted, or pulsed current flow is counted and accumulated by the PI module which provides
the accumulated count to the ROC/FloBoss electronics upon request.
A 10-ohm scaling resistor (R1) is supplied by the factory, which accommodates a field device with
pulse amplitude (Vo) of 11 to 30 volts dc and a duty cycle of 50%. However, it is desirable to optimize
the value of R1 to reduce the current drain from the source or reduce the heat generated in the module
due to amplitudes greater than 30 volts dc. The formula for determining the value of R1 is given in
Figure 3-17. For optimum efficiency, R1 should be scaled for a loop current (I) of 5 milliamps.
SELF-POWERED
PULSE DEVICE
+
V
O
TO OPTIMIZE SCALING RESISTOR R1:
R1 =
R1 + R
I = LOOP CURRENT = 5 mA TYPICAL
RW = RESISTANCE OF FIELD WIRING
= VOLTAGE FROM PULSE DEVICE = 11 TO 30 VDC
V
O
R
W
VO – 1
I
+ 2.2K = LOOP RESISTANCE = 3.4K OHMS MAX
W
– R
– 2.2K
W
R1=10
N/C
A
+
B
–
C
PI ISO
2.2K
DOC0149A
Figure 3-17. Pulse Input Isolated Module Field Wiring
3-20Rev 5/00
FloBoss 407 Instruction Manual
3.4.12 Slow Pulse Input Source Module
A schematic representation of the field wiring connections to the input circuit of the Slow Pulse Input
Source module is shown in Figure 3-18.
CAUTION
The Slow Pulse Input source module is designed to operate only with
non-powered discrete devices such as “dry” relay contacts or isolated
solid-state switches. Use of the module with powered devices may cause
improper operation or damage to occur.
The Slow Pulse Input source module operates by providing a voltage across terminals B and C
that is derived from internal voltage source Vs. When a field device, such as a set of relay contacts,
is connected across terminals B and C, the closing of the contacts completes a circuit, which causes a
flow of current between Vs and ground at terminal C.
This current flow is sensed by the SPI module, which signals the ROC/FloBoss electronics that the
relay contacts have closed. When the contacts open, current flow is interrupted and the SPI module
signals the ROC/FloBoss electronics that the relay contacts have opened. The ROC/FloBoss software
counts the number of times the contacts switch from open to closed, and stores the count. The software
checks for the input transition every 50 milliseconds.
A 10-ohm scaling resistor (R1) is supplied by the factory that accommodates a source voltage (Vs) of
11 to 30 volts dc. The source voltage is either the input voltage to the ROC/FloBoss or the output
voltage of the I/O converter card if one is installed (ROC364 only). However, it is desirable to
optimize the value of R1 to reduce the current drain from the source or reduce the heat generated in the
module due to high source voltage. The formula for determining the value of R1 is given in Figure 3-
18. For optimum efficiency, R1 should be scaled for a loop current (I) of 3 milliamps.
R1=10
SPI SRC
ROC-POWERED
DISCRETE DEVICE
I
R
w
TO OPTIMIZE SCALING RESISTOR R1:
V - 1
R1 =
R1 + Rw + 3.3K = LOOP RESISTANCE = 4.5K OHMS
I = LOOP CURRENT = 3 mA TYPICAL
R = RESISTANCE OF FIELD
w
V = SOURCE VOLTAGE FROM MODULE = 11 TO 30 VDC
s
s
- R - 3.3K
I
w
N/C
A
+
B
-
C
3.3K
V
DOC0151
Modified
Figure 3-18. Slow Pulse Input Source Module Field Wiring
s
Rev 5/003-21
FloBoss 407 Instruction Manual
3.4.13 Slow Pulse Input Isolated Module
A schematic representation of the field wiring connections to the input circuit of the Slow Pulse Input
Isolated module is shown in Figure 3-19.
NOTE
The Slow Pulse Input isolated module is designed to operate only with discrete
devices having their own power source such as “wet” relay contacts or two-state
devices providing an output voltage. The module is inoperative with non-powered
devices.
The Slow Pulse Input isolated module operates when a field device provides a voltage across terminals
B and C of the module. The voltage sets up a flow of current sensed by the module, which signals the
ROC/FloBoss electronics that the field device is active. When the field device no longer provides a
voltage, current stops flowing and the SPI module signals the ROC/FloBoss electronics that the device
is inactive. The ROC/FloBoss software counts the number of times the current starts flowing, and
stores the count. The software checks for the input transition every 50 milliseconds.
A 10-ohm scaling resistor (R1) is supplied by the factory, which accommodates an external voltage
(Vo) of 11 to 30 volts dc. However, it is desirable to optimize the value of R1 to reduce the current
drain from the source or reduce the heat generated in the module due to high source voltage. The
formula for determining the value of R1 is given in Figure 3-19. For optimum efficiency, R1 should be
scaled for a loop current (I) of 3 milliamps.
SELF-POWERED
DISCRETE
DEVICE
+
V
O
-
TO OPTIMIZE SCALING RESISTOR R1:
V - 1
R1 =
R1 + R + 3.3K = LOOP RESISTANCE = 4.5K OHMS MAX
I = LOOP CURRENT = 3 mA TYPICAL
R = RESISTANCE OF FIELD
w
V = VOLTAGE FROM DISCRETE DEVICE = 11 TO 30 VDC
o
o
w
R1=10
N/C
I
R
W
- R - 3.3K
I
w
A
+
B
-
C
SPI ISO
3.3K
DOC0152A
Figure 3-19. Slow Pulse Input Isolated Module Field Wiring
3-22Rev 5/00
FloBoss 407 Instruction Manual
–
–
3.4.14 Low-Level Pulse Input Module
A schematic representation of the field wiring connections to the input circuit of the Low-Level Pulse
Input module is shown in Figure 3-20. The field wiring connections are made through a separate
terminal block that plugs in next to the module allowing replacement of the module without
disconnecting field wiring.
NOTE
The Low-Level Pulse Input module is designed to operate only with pulsegenerating devices having their own power source. The module does not work with
non-powered devices.
The low-level pulse input module operates when a field device provides a pulsed voltage between
30 millivolts and 3 volts peak-to-peak across terminals B and C of the module. The pulsed voltage is
counted and accumulated by the module, which provides the accumulated count to the ROC/FloBoss
electronics on request.
SELF-POWERED
PULSE DEVICE
Figure 3-20. Low-Level Pulse Input Module Field Wiring Schematic
PI LL
N/C
+
A
+
B
C
200K
200K
DOC0150A
Rev 5/003-23
FloBoss 407 Instruction Manual
3.4.15 RTD Input Module
The RTD input module monitors the temperature signal from a resistance temperature detector (RTD)
sensor or probe. The RTD module is isolated, reducing the possibility of lightning damage. A lightning
protection module (LPM) will not protect the RTD, but it helps protect the rack in which the module is
installed.
The RTD module needs to be calibrated while disconnected from the RTD probe; therefore, it may be
more convenient to perform calibration before connecting the field wiring. However, if the field wiring
between the ROC/FloBoss and the RTD probe is long enough to add a significant resistance, then
calibration should be performed in a manner that takes this into account.
3.4.15.1 Calibrating the RTD Module
The following instructions describe how to manually calibrate an RTD input channel for use with an
RTD probe having an alpha value of either 0.00385 or 0.00392 ohms/ohm/degree C. This procedure
requires a resistance decade box with 0.01 ohm steps and an accuracy of ±1%. You also need a
personal computer running the ROCLINK Configuration Software.
NOTE
For a more automated procedure, you may instead use the Calibrate pushbutton
associated with the Analog Input configuration, as described in Section 4 of the
ROCLINK user manual.
WHTC
WHT
A4464821
RTD
RED
A
B
1
DECADE BOX
ABC
Figure 3-21. Calibration Setup
3-24Rev 5/00
FloBoss 407 Instruction Manual
Table 3-1. Calibration Resistance Values
ALPHA-50º C100º C
0.0038580.31 OHMS138.50 OHMS
0.0039279.96 OHMS139.16 OHMS
Note: Resistance values for RTD probes with other alpha values can be found in the temperature-to-resistance conversion
table for that probe.
1. Connect the decade box as shown in Figure 3-21 on Page 3-24.
2. Set the decade box to the -50° C resistance value corresponding to the RTD alpha value in
Table 3-1.
3. Enter the value displayed for “Raw A/D Input” as the value for “Adj. A/D 0%” using the
Analog Inputs configuration screen for the RTD input (in ROCLINK, see the Advanced
Features for these parameters).
4. Set the decade box to the 100° C resistance value given in Table 3-1.
5. Enter the value displayed for “Raw A/D Input” as the value for “Adj. A/D 100%” using the
Analog Inputs configuration screen for the RTD input.
6. Enter “-50” for “Low Reading EU”.
7. Enter “100” for the “High Reading EU”.
8. Press F8 to save the changes.
3.4.15.2 Connecting RTD Module Field Wiring
The RTD sensor connects to the RTD module with ordinary copper wire. To avoid a loss in accuracy,
sensor wires should be equal in length, of the same material, and the same gauge. To avoid possible
damage to the RTD module from induced voltages, sensor wires should be kept as short as possible
(typically 100 feet or less). A schematic representation of the field wiring connections to the input
circuit of the RTD input module is shown in Figure 3-22, Figure 3-23, Figure 3-24, and Figure 3-25.
Two-wire RTDs are connected to module terminals A and B. Terminal B must be connected to
terminal C, as shown in Figure 3-22.
Rev 5/003-25
FloBoss 407 Instruction Manual
RTD
ROC-POWERED
2-WIRE, 100 OHM
RTD PROBE
RED
WHT
RED
A
WHT
B
WHT
C
I SRC
+
-
DOC4007A
Modified
Figure 3-22. RTD Input Module Field Wiring for Two-Wire RTDs
Three-wire RTDs have an active element loop and a compensation loop. The active element loop
is connected across terminals A and B. The compensation loop is connected across B and C. The
compensation loop helps increase the accuracy of the temperature measurement by allowing the
RTD module to compensate for the resistance of hookup wire used between the probe and RTD
module.
In operation, the RTD module subtracts the resistance between terminals B and C from the resistance
between terminals A and B. The remainder is the resistance of only the active element of the probe.
This compensation becomes more important as the resistance of the hookup wire increases with
distance between the probe and the ROC/FloBoss. Of course, in order to perform properly, the
compensation loop must use the same type, size, and length of hookup wire as the active element loop.
The RTD module is designed for only one compensation loop, and this loop is not isolated from the
active element loop because terminal B is common to both loops. In the 3-wire RTD, the wires are
connected to module terminals A, B, and C, as shown in Figure 3-23.
It is important to match the color coding of the RTD probe wires to the proper module terminal,
because the probe wire colors vary between manufacturers. To determine which leads are for the
compensation loop and which are for the active element, read the resistance across the probe wires with
an ohmmeter. The compensation loop reads 0 ohms, and the RTD element reads a resistance value
matching the temperature curve of the RTD.
RTD
RED
A
WHT
B
WHT
C
I SRC
DOC0161A
Modified
3-WIRE,100-OHM,
RTD PROBE
RED
WHT
WHT
Figure 3-23. RTD Input Module Field Wiring for Three-Wire RTDs
3-26Rev 5/00
FloBoss 407 Instruction Manual
RTDs with 4 wires normally have the compensation loop separate from the active element loop to
increase the accuracy of the probe. Various colors are used for the probe wires. For example, some
probes have wire colors of red and white for the RTD element loop and black leads for the
compensation loop, while other probes use two red leads for the active element loop and two white
leads for the compensation loop.
The connections in Figure 3-24 connect a 4-wire RTD with compensation loop to the 3-wire RTD
module. The RTD module designed for 3-wire use does not permit a 4-wire RTD to provide any
additional accuracy over a 3-wire RTD.
RTD
RED
A
WHT
B
WHT
C
I SRC
DOC4008A
4-WIRE RTD
WITH COMPENSATION LOOP
RED
RED
WHT
WHT
Figure 3-24. RTD Input Module Field Wiring for 4-Wire RTD With Compensation Loop
Figure 3-25 shows the connections for a single-element, 4-wire RTD. The two leads for one side of the
RTD are both red, and for the other side they are both white.
RTD
DOC4009A
4-WIRE RTD
WITH SINGLE
ELEMENT
RED
RED
WHT
WHT
RED
A
WHT
B
WHT
C
I SRC
Figure 3-25. Field Wiring for 4-Wire, Single Element RTD
Rev 5/003-27
FloBoss 407 Instruction Manual
3.4.16 HART Interface Module
The HART Interface module allows the ROC/FloBoss to interface with up to 10 HART devices per I/O
slot. The HART module provides “loop source” power (+T) on terminal A and two channels for
communications on terminals B and C. The +T power is regulated by a current limit. If the power
required by all connected HART devices exceeds 40 milliamps (more than an average of 4 milliamps
each), the total number of HART devices must be reduced.
The HART module polls one channel at a time. If more than one device is connected to a channel in
a multi-drop configuration, the module polls all devices on that channel before it polls the second
channel. The HART protocol allows one second per poll for each device, so with 5 devices per channel
the entire poll time for the module would be ten seconds.
In a point-to-point configuration, only one HART device is wired to each HART module channel.
In a multi-drop configuration, two to five HART devices are connected to a channel. In either case,
terminal A (+T) is wired in parallel to the positive (+) terminal on all of the HART devices, regardless
of the channel to which they are connected. Channel 1 (terminal B) is wired to the negative (-) terminal
of a single HART device, or in parallel to the negative terminals of two to five devices. Likewise,
channel 2 (terminal C) is wired to the negative (-) terminal of a single HART device, or in parallel to
the negative terminals of a second group of two to five devices. Refer to Figure 3-26.
ROC-POWERED
HART DEVICE 1
ROC-POWERED
HART DEVICE 2
ROC-POWERED
HART DEVICE 5
CHANNEL 1, MULTI-DROP MO DECHANNEL 2, POINT-TO-POINT MODE
+
-
+
-
+
-
A
B
C
+
ROC-POWERED
-
HART DEVICE
Figure 3-26. Field Wiring for a HART Interface Module
MUX
HART MODULE
I LIMIT
MODEM
DOC0295A
+T
3-28Rev 5/00
FloBoss 407 Instruction Manual
3.5 TROUBLESHOOTING AND REPAIR
The troubleshooting and repair help the technician identify and replace faulty modules. Faulty modules
must be returned to your Fisher Representative for repair or replacement.
If an I/O point does not function correctly, first determine if the problem is with the field device or the
I/O module as follows:
CAUTION
Failure to exercise proper electrostatic discharge precautions (such as wearing a
grounded wrist strap) may reset the processor or damage electronic components,
resulting in interrupted operations.
1. Isolate the field device from the ROC/FloBoss by disconnecting it at the I/O module
terminal block.
2. Connect the ROC/FloBoss to a computer running the ROCLINK configuration software.
3. Perform the appropriate test procedure described in the following paragraphs.
A module suspected of being faulty should be checked for a short circuit between its input or output
terminals and the ground screw on the termination card. If a terminal not directly connected to ground
reads zero (0) when measured with an ohmmeter, the module is defective and must be replaced.
3.5.1 Analog Input Modules
Equipment Required:Multimeter
To determine if an Analog Input module is operating properly, its configuration must first be known.
Table 3-2 shows typical configuration values for an analog input:
Rev 5/003-29
FloBoss 407 Instruction Manual
Table 3-2. Analog Input Module Typical Configuration Values
PARAMETERVALUECORRESPONDS TO:
Adj. A/D 0 %800 1 volt dc across Rs (scaling resistor R1)
Adj. A/D 100 %4000 5 volts dc across R
Low Reading EU0.0000 EU value with 1 volt dc across R
High Reading EU100.0 EU value with 5 volts dc across R
s
s
s
Filtered EUsxxxxx Value read by AI module
When the value of Filtered Engineering Units (EU) is -25% of span as configured above, it is an
indication of no current flow (0 mA), which can result from open field wiring or a faulty field device.
When the value of Filtered EUs is in excess of 100% of span as configured above, it is an indication of
maximum current flow, which can result from shorted field wiring or a faulty field device.
When the value of Filtered EUs is between the low and high readings, you can verify the accuracy of
the reading by measuring the voltage across scaling resistor Rs (Vrs) with the multimeter. To convert
this reading to the filtered EUs value, perform the following:
Filtered EUs = [((Vrs - 1)/4) × Span] + Low Reading EU,
where Span = High Reading EU - Low Reading EU
This calculated value should be within one-tenth of one percent of the Filtered EUs value measured by
the ROC/FloBoss. To verify an accuracy of 0.1 percent, read the loop current with a multimeter
connected in series with current loop. Be sure to take into account that input values can change rapidly,
which can cause a greater error between the measured value and the calculated value.
If the calculated value and the measured value are the same, the AI module is operating correctly.
3.5.2 Analog Output Modules
The Analog Output module is a source for current loop or voltage devices. Two test procedures are
provided to verify correct operation. Use the first procedure to check current loop source installations
and the second procedure to check voltage source installations.
3-30Rev 5/00
FloBoss 407 Instruction Manual
3.5.2.1 Check Current Loop Source Installations
Equipment Required:Multimeter
Personal Computer running ROCLINK Software
1. Taking appropriate precautions, disconnect the field wiring going to the AO module terminations.
2. Connect a multimeter between the B and C terminals of the module and set the multimeter to
measure current in milliamps.
3. Using the ROCLINK software, put the AO point associated with the module under test in Manual
mode (scanning disabled).
4. Set the output to the high EU value.
5. Verify a 20-milliamp reading on the multimeter.
6. Calibrate the analog output high EU value as needed by increasing or decreasing the “Adj D/A
100% Units”.
7. Set the output to the low EU value.
8. Verify a 4-milliamp reading on the multimeter.
9. Calibrate the analog output low EU value by increasing or decreasing the “Adj D/A 0% Units” as
needed.
10. Enable scanning for the AO point, remove the test equipment, and reconnect the field device.
11. If possible, verify the correct operation of the AO module by setting the high and low EU values as
before (scanning disabled) and observing the field device.
3.5.2.2 Check Voltage Source Installations
Equipment Required:Multimeter
Personal Computer running ROCLINK Software
To check operation of the Analog Output module powering a voltage device, use the following
procedure.
1. If the resistance value (R) of the field device is known, measure the voltage drop (V)
across the device and calculate the output EU value using the following formula.
EU value = [((1000V/R - 4)/16) × Span] + Low Reading EU,
where Span = High Reading EU - Low Reading EU
2. Compare the computed value to the output EU value measured by the ROC/FloBoss with the
ROCLINK software. It is normal for the reading to be several percent off, depending on the
accuracy tolerance of the device and how rapidly changes occur in the output value.
3. Calibrate the analog output EU values by increasing or decreasing the “Adj D/A % Units” as
needed.
Rev 5/003-31
FloBoss 407 Instruction Manual
4. If the analog output is unable to drive the field device to the 100% value, confirm the +V (1 to 5
volts) voltage is present at the field device.
♦ If the voltage is present and the device is not at the 100% position, the resistance value of the
device is too large for the +V voltage. A field device with a lower internal resistance should
be used.
♦ If the voltage is not present at the field device, but it is present at field wiring terminal B,
there is excessive resistance or a break in the field wiring.
3.5.3 Discrete Input Source Module
Equipment Required:Jumper wire
Place a jumper across terminals B and C. The LED on the module should light and the status as read by
the ROCLINK software should change to “1”. With no jumper on terminals B and C, the LED should
not be lit and the status should be “0”. If the unit fails to operate, make sure a correct value for the
module resistor is being used.
3.5.4 Discrete Input Isolated Module
Equipment Required:Voltage generator capable of generating 11 to 30 V dc
Personal Computer running ROCLINK Software
Supply an input voltage across terminals B and C. The LED on the module should light and the status
as read by the ROCLINK software should change to “1”. With no input on terminals B and C, the LED
should not be on and the status should be “0”. If the unit fails to operate, make sure a correct value for
the module resistor is being used.
3-32Rev 5/00
FloBoss 407 Instruction Manual
3.5.5 Discrete Output Source Module
Equipment Required:Multimeter
Personal Computer running ROCLINK Software
Place the Discrete Output in manual mode using the ROCLINK configuration software. With the
output status set to “0”, less than 0.5 volts dc should be measured across pins B and C. With the output
status set to “1”, approximately 1.5 volts dc less than the system voltage (Vs-1.5) should be measured
across terminals A and B. If these values are not measured, check to see if the module fuse is open,
verify the module is wired correctly, and verify the load current requirement does not exceed the 57milliamp current limit value of the module.
3.5.6 Discrete Output Isolated Module
Equipment Required:Multimeter
Personal Computer running ROCLINK Software
Place the Discrete Output in manual mode using the ROCLINK configuration software. Set the output
status to “0” and measure the resistance across terminals A and B. No continuity should be indicated.
Set the output status to “1” and measure the resistance across terminals A and B. A reading of 15K
ohms or less should be obtained.
3.5.7 Discrete Output Relay Module
Equipment Required:Multimeter
Personal Computer running ROCLINK Software
Place the Discrete Output in manual mode using the ROCLINK configuration software. Set the output
status to “0” and measure the resistance across terminals B and C. A reading of 0 ohms should be
obtained. Measure the resistance across terminals A and B. No continuity should be indicated. Set the
output status to “1” and measure the resistance across terminals B and C. No continuity should be
indicated. Measure the resistance across terminals A and B. A reading of 0 ohms should be obtained.
Rev 5/003-33
FloBoss 407 Instruction Manual
3.5.8 Pulse Input Source and Isolated Modules
Equipment Required:Pulse Generator
Voltage Generator
Frequency Counter
Jumper wire
For both types of modules, there are two methods of testing. One method tests high-speed operation,
and the other method tests low-speed operation.
NOTE
When checking the operation of the Pulse Input Source and Isolated modules,
ensure the scan rate for the pulse input is once every 6.5 seconds or less as set by the
ROCLINK software.
To verify high-speed operation, connect a pulse generator having sufficient output to drive the module
to terminals B and C. Connect a frequency counter across terminals B and C. Set the pulse generator
to a value equal to, or less than 10 KHz, and set the frequency counter to count pulses. Verify the count
read by the counter and the count read by the ROC/FloBoss are the same using the ROCLINK software.
To verify low-speed operation of the source module, alternately jumper across terminals B and C. The
module LED should cycle on and off, and the accumulated count should increase.
To verify low-speed operation of the isolated module, alternately supply and remove an input voltage
across terminals B and C. The module LED should cycle on and off, and the total accumulated count
should increase.
3.5.9 Slow Pulse Input Source Module
Equipment Required:Jumper wire
To verify low-speed operation of the source module, connect and remove a jumper across terminals B
and C several times to simulate slow switching. The module LED should cycle on and off and the
accumulated count should increase.
3-34Rev 5/00
FloBoss 407 Instruction Manual
3.5.10 Slow Pulse Input Isolated Module
Equipment Required:Jumper wire
To verify low-speed operation of the isolated module, alternately supply and remove an input voltage
across terminals B and C. The module LED should cycle on and off and the total accumulated count
should increase.
3.5.11 Low-Level Pulse Input Module
Equipment Required:Pulse Generator
Frequency Counter
Personal Computer running ROCLINK software
NOTE
When checking the operation of the Low-Level Pulse Input module, ensure that the
scan rate for the pulse input is once every 22 seconds or less as set by the ROCLINK
software.
To verify operation, connect a pulse generator, with the pulse amplitude set at less than 3 volts, to
terminals B and C. Then, connect a frequency counter across terminals B and C. Set the pulse
generator to a value equal to, or less than 3 KHz, and set the frequency counter to count pulses. Verify
that the count read by the counter and in the count read by the ROC/FloBoss are the same using the
ROCLINK software.
Rev 5/003-35
FloBoss 407 Instruction Manual
3.5.12 RTD Input Module
The RTD module is similar in operation to an AI module and uses the same troubleshooting and repair
procedures. The RTD module can accommodate two-wire, three-wire, or four-wire RTDs. If two-wire
RTDs are used, terminals B and C must be connected together. If any of the input wires are broken or
not connected, the ROCLINK software indicates the “Raw A/D Input” value is either at minimum (less
than 800) or maximum (greater than 4000) as follows:
♦ An open at terminal A gives a maximum reading.
♦ An open at terminal B gives a minimum reading.
♦ An open at terminal C gives a minimum reading.
To verify the operation of the RTD module, disconnect the RTD and connect a jumper between
terminals B and C of the RTD module. Next, connect either an accurate resistor or decade resistance
box with a value to give a low end reading across terminals A and B. The resistance value required can
be determined by the temperature-to-resistance conversion chart for the type of RTD being used. Use
ROCLINK software to verify that the “Raw A/D Input” value changed and reflects the 0% A/D value.
Change the resistance to reflect a high temperature as determined by the temperature-to-resistance
conversion chart. Verify that the “Raw A/D Input” value changed and reflects the 100% A/D value.
3.5.13 HART Interface Module
The HART Interface Module provides the source for the HART devices and uses two test procedures to
verify correct operation. Use the first procedure to check the integrity of the loop power and the second
to verify communications.
3.5.13.1 Verify Integrity of Loop Power
Equipment Required:Multimeter
1. Measure voltage between terminals A and B to verify channel 1.
2. Measure voltage between terminals A and C to verify channel 2.
The voltage read in both measurements should reflect the value of +T less the voltage drop of the
HART devices. Zero voltage indicates an open circuit in the I/O wiring, a defective HART device, or a
defective module.
3-36Rev 5/00
FloBoss 407 Instruction Manual
3.5.13.2 Verify Communications
Equipment Required:Dual-trace Oscilloscope
In this test, the HART module and the ROC/FloBoss act as the host and transmit a polling request to
each HART device. When polled, the HART device responds. In this test, you use the oscilloscope to
observe the activity on the two HART communication channels. Note that there is normally one second
from the start of one request to the start of the next request.
1. Attach one input probe to terminal B of the HART module and examine the signal for a polling
request and response for each HART device connected to this channel.
2. Attach the other input probe to terminal C and examine the signal for a polling request and response
for each HART device connected.
3. Compare the two traces; signal bursts should not appear on both channels simultaneously.
Keep in mind that each device on one channel is polled before the devices on the other channel are
polled. If a channel indicates no response, this could be caused by faulty I/O wiring or a faulty device.
If the HART module tries to poll both channels simultaneously, this could be caused by a defective
module, in which case the module must be replaced.
3.6 REM OV AL, ADDITION, AND REPLACEMENT PROCEDURES
3.6.1 Impact on I/O Point Configuration
When an I/O module is replaced with the same type of I/O module, it is not necessary to reconfigure
the ROC/FloBoss. Modules which are treated as the same type are:
♦ Discrete input isolated and source modules
♦ Discrete output isolated, source, and relay modules
♦ Analog input loop, differential, and source modules, and RTD input modules
♦ Pulse input isolated and source modules
♦ Slow pulse input isolated and source modules
If a module is to be replaced with one of the same type (see above), but some of its configuration
parameters need to be changed, you can use the ROCLINK software to make the changes off-line or
on-line. If you want to minimize “down time,” before you replace the module, you can make the
needed changes (except for ROC display and FST changes) off-line by first saving the ROC/FloBoss
configuration to disk. Modify the disk configuration, replace the module, and then load the
configuration file into the ROC/FloBoss.
Rev 5/003-37
FloBoss 407 Instruction Manual
To make changes on-line, replace the module, proceed directly to the configuration display for the
affected point, and modify parameters as needed. Remember to consider the impact on FSTs and other
points that reference the affected point.
Any added modules (new I/O points) start up with default configurations. Even though adding a
module, removing a module, or moving a module to a new position in the ROC/FloBoss does not
directly affect the configuration of other I/O points, it can affect the numbering of I/O points of thesame type. This, in turn, can impact an FST or higher-level point because the referencing of I/O points
is done by a sequence-based point number. For example, if you have AI modules installed in slots A7,
A10, and A11, adding another AI module in slot A8 changes the point numbers of the analog inputs for
modules in slots A10 and A11.
CAUTION
If one or more FSTs, or higher level points such as a PID loop or AGA Flow, have
been configured in the ROC/FloBoss, be sure to reconfigure them according to the
changes in I/O modules. Operational problems will occur if you do not reconfigure
the ROC/FloBoss.
3.6.2 Removing/Installing an I/O Module
Use the following procedure to remove/install an I/O module. The procedure is performed using the
ROCLINK Configuration Software.
CAUTION
There is a possibility of losing the configuration and historical data held in RAM
while performing the following procedure. As a precaution, save the current
configuration and historical data to permanent memory as instructed in Section
2.5.2.
CAUTION
When working on units labeled for service in hazardous areas, ensure that the
working environment is currently non-hazardous.
NOTE
For a Measurement Canada FloBoss 407, resealing of the case must be performed
by authorized personnel only.
3-38Rev 5/00
FloBoss 407 Instruction Manual
Failure to exercise proper electrostatic discharge precautions (such as wearing a
grounded wrist strap) may reset the processor or damage electronic components,
resulting in interrupted operations.
During this procedure all power will be removed from the ROC/FloBoss and devices
powered by the ROC/FloBoss. Ensure that all connected input devices, output
devices, and processes remain in a safe state when power is removed from the
ROC/FloBoss and when power is restored.
1. Refer to Section 2.5.2 concerning RAM backup procedures.
2. Disconnect the input power, such as by unplugging the 5-terminal connector.
3. Perform one of the following steps, depending on whether the module is to be removed or
installed:
CAUTION
CAUTION
a) If removing the module, loosen the module retaining screw and remove the module by
lifting straight up. It may be necessary to rock the module gently while lifting.
b) If installing the module, insert the module pins into the module socket. Press the module
firmly in place. Tighten the module retaining screw.
4. After the module is removed/installed, reconnect the input power.
5. Check the configuration data (including ROC displays) and FSTs, and load or modify them
as required. Load and start any user programs as needed.
6. Read Section 3.6.1 on I/O point configuration. If you increased or reduced the number of
HART modules or changed their relative position, perform a warm start to cause the HART
program to recognize the changes. Configure the HART points accordingly.
7. Verify that the ROC/FloBoss performs as required.
8. If you changed the configuration, save the configuration data to permanent memory.
9. If you changed the configuration, including the history database, FSTs, and ROC displays,
save them to disk. See Section 2.5.2 for more information on saving files.
Rev 5/003-39
FloBoss 407 Instruction Manual
3.7 I/O MODULE SPECIFICATIONS
The specifications for the various I/O modules are given in the following order in sections 3.7.1 through
3.7.11:
♦ Analog Input Modules—Loop and Differential
♦ Analog Input Source Module
♦ Analog Output Source Module
♦ Discrete Input Modules—Source and Isolated
♦ Discrete Output Modules—Source and Isolated
♦ Discrete Output Relay Module
♦ Pulse Input Modules—Source and Isolated
♦ Slow Pulse Input Modules—Source and Isolated
♦ Pulse Input Module—Low Level
♦ RTD Input Module
♦ HART Interface Module
3.7.1 Analog Input Modules—Loop and Differential
Loop Module Specifications
FIELD
WIRING
TERMINALS
INPUT
Loop Power (+T)
A:
Analog Input (+)
B:
Common (-)
C:
Single-ended, voltage sense.
Type:
Current loop with scaling resistor (R1).
Loop Current:
mum range. Actual range depends
on scaling resistor used.
Voltage Sensing:
software configured.
Accuracy:
30 °C). 0.5% of full scale (-40 to
70 °C).
0 to 25 mA maxi-
0 to 5 Volts dc,
0.1% of full scale (20 to
INPUT
(CONTINUED)
POWER
REQUIREMENTS
ISOLATION
Impedance:
ohms (without scaling resistor).
Normal Mode Rejection:
@ 60 Hz.
Loop Source:
from ROC power supply or I/O
converter card (V
Module:
maximum; -4.5 to -5.5 Volts dc, 2
mA maximum (supplied by ROC).
Not isolated. Terminal C tied to
power supply common.
Greater than 400K
50 dB
25 mA maximum,
= 11 to 30 Vdc).
s
4.9 to 5.1 Volts dc, 6 mA
3-40Rev 5/00
FloBoss 407 Instruction Manual
Differential Module Specifications
FIELD WIRING
TERMINALS
INPUT
SCALING
RESISTOR
SURGE
WITHSTAND
RESOLUTION
Not used.
A:
Positive Analog Input (+)
B:
Negative Analog Input (-)
C:
Voltage sense. Externally-
Type:
powered current loop sensing with
scaling resistor (R1).
Voltage:
configured.
Accuracy:
to 30 °C). 0.5% of full scale (-40 to
70 °C).
0 to 5 Volts dc, software
0.1% of full scale (20
Common Specifications
250 ohm (supplied) for 0 to 20 mA
full scale. 100 ohm for 0 to 50 mA
(externally-powered only).
Meets IEEE 472/ANSI C37.90a.
12 bits.
INPUT
(CONTINUED)
POWER
REQUIREMENTS
INPUT
ISOLATION
MECHANICAL
SHOCK
CASE
Normal Mode Rejection:
60 Hz.
Impedance:
ohms (without scaling resistor).
4.9 to 5.1 Volts dc, 6 mA maximum;
-4.5 to -5.5 Volts dc, 2 mA maximum
(supplied by ROC).
Greater than 400K ohms input to
power supply common.
1500 Gs 0.5 mS half sine per MILSTD-202 method 213, condition F.
Solvent-resistant thermoplastic
polyester, meets UL94V-0. Dimensions are 0.60 in. D by 1.265 in. H by
1.69 in. W (15 mm by 32 mm by 43
mm), not including pins.
Greater than 400K
50 dB @
FILTER
CONVERSION
TIME
VIBRATION
WEIGHT
Rev 5/003-41
Single pole, low-pass, 40 millisecond time constant.
30 microseconds typical.
20 Gs peak or 0.06 in. double
amplitude, 10 to 2,000 Hz, per
MIL-STD-202 method 204
condition F.
1.3 ounces (37 grams).
ENVIRONMENTAL
APPROVALS
Meets the Environmental specifications of the ROC or FloBoss in
which the module is installed,
including Temperature and Transient
Protection specifications.
Approved by CSA for hazardous
locations Class I, Division 2, Groups
A, B, C, and D.
FloBoss 407 Instruction Manual
3.7.2 Analog Input Source Module
Specifications
FIELD WIRING
TERMINALS
INPUT
SOURCE
POWER
POWER
REQUIREMENTS
INPUT
ISOLATION
SURGE
WITHSTAND
A:
10 Vdc
B:
Analog Input
C:
Common
Type:
Single-ended, voltage sense;
can be current loop if scaling resistor
(not supplied) is used.
Voltage:
configurable.
Resolution:
Accuracy:
C); 0.5% of full scale (-40 to 65 °C).
°
Impedance:
(without scaling resistor).
Normal Mode Rejection:
Hz.
9.99 to 10.01 Vdc, 20 mA maximum.
4.9 to 5.1 Vdc, 6 mA maximum; -4.5 to -
5.5 Vdc, 2 mA maximum (all supplied by
ROC).
Not isolated. Terminal C is tied to
power supply ground.
Meets IEEE 472 / ANSI C37.90a.
0 to 5 Vdc, software
12 bits.
0.1% of full scale (20 to 30
Greater than 400 kil-ohms
50 db @ 60
FILTER
CONVERSION
TIME
VIBRATION
MECHANICAL
SHOCK
CASE
ENVIRONMENTAL
WEIGHT
APPROVALS
Single pole, low-pass, 40 msec time
constant.
30 microseconds typical.
20 Gs peak or 0.06 in. double
amplitude, 10 to 2,000 Hz, per MILSTD-202 method 204 condition F.
1500 Gs 0.5 mS half sine per MIL-STD202, method 213, condition F.
0.6 in. D by 1.265 in. H by 1.690 in. W
(15 mm by 32 mm by 43 mm), not
including pins.
Meets the Environmental specifications
of the ROC or FloBoss in which the
module is installed, including
Temperature and Transient Protection
specifications.
1.3 ounces (37 grams).
Approved by CSA for hazardous
locations Class I, Division 2, Groups A,
B, C, and D.
3.7.3 Analog Output Source Module
Specifications
FIELD WIRING
TERMINALS
VOLTAGE
OUTPUT
3-42Rev 5/00
A:
Voltage Output
B:
Current Output
C:
Common
Type:
Voltage source.
Range:
overranging. 25 mA maximum.
Resolution:
1 to 5 Vdc with 0 to 5.25 Vdc
12 bits.
VOLTAGE
OUTPUT
(CONT’D)
Accuracy:
from 20 to 30 °C. 0.5% of full-scale
output for -40 to 65 °C.
Settling Time:
Reset Action:
percent output or last value (software
configurable) on power-up (warm start) or
on watchdog timeout.
0.1% of full-scale output
100 µs maximum.
Output goes to zero
FloBoss 407 Instruction Manual
Specifications (Cont’d)
CURRENT
OUTPUT
POWER
REQUIREMENTS
Current loop.
Type:
Range:
overranging, adjusted by scaling
resistor. A 0-ohm resistor is
supplied.
Loop Source:
supplied by ROC for “+T” power
(typically 24 Vdc).
Loop Resistance at 12 Vdc:
ohms minimum, 250 ohms
maximum.
Loop Resistance at 24 Vdc:
ohms minimum, 750 ohms
maximum.
Resolution:
Accuracy:
from 20 to 30 °C. 0.5% of full-scale
output for -40 to 65 °C.
Settling Time:
maximum.
Reset Action:
percent output or last value (software
configurable) on pow er-up (warm
start) or on watchdog timeout.
Module Alone:
Module w/Current Loop:
@ 4 mA output to 590 mW @ 20 mA
output.
4 to 20 mA with 0 to 22 mA
11 to 30 Vdc, as
0
200
12 bits.
0.1% of full-scale output
100 microseconds
Output goes to zero
24 mW typical.
400 mW
OUTPUT
ISOLATION
SURGE
WITHSTAND
VIBRATION
MECHANICAL
SHOCK
WEIGHT
CASE
ENVIRONMENTAL
APPROVALS
Not isolated. Terminal C tied to power
supply common.
Meets IEEE 472/ANSI C37.90a.
20 Gs peak or 0.06 in. double
amplitude, 10 to 2,000 Hz, per MILSTD-202 method 204 condition F.
1500 Gs 0.5 ms half sine per MILSTD-202, method 213, condition F.
1.3 ounces (37 grams) typical.
Solvent-resistant thermoplastic
polyester, meets UL94V-0.
Dimensions are 0.6 in. D by 1.265 in.
H by 1.69 in. W (15 mm by 32 mm by
43 mm), not including pins.
Meets the Environmental specifications of the ROC or FloBoss in
which the module is installed,
including Temperature and Transient
Protection specifications.
Approved by CSA for h a zardous
locations Class I, Division 2, Groups
A, B, C, and D.
Rev 5/003-43
FloBoss 407 Instruction Manual
3.7.4 Discrete Input Modules—Source and Isolated
Source Module Specifications
Not used
FIELD WIRING
TERMINALS
INPUT
A:
Discrete device source/signal
B:
Common
C:
Contact sense.
Type:
Range:
Active, 2 to 9 mA.
Source Voltage:
Source Current:
source voltag e (Vs), loop resistance
(Rl), and scaling resistor (Rs, 10
ohm supplied):
I = (Vs - 1)/(3.3K + Rl + Rs)
Inactive, 0 to 0.5 mA.
11 to 30 Vdc.
Determined by
POWER
REQUIREMENTS
INPUT
ISOLATION
SURGE
WITHSTAND
Source Input:
maximum from ROC power supply
or I/O converter card.
Module:
maximum (supplied by ROC).
Not isolated. Terminal C tied to
power supply common.
Meets IEEE 472/ANSI C37.90a.
11 to 30 Vdc, 9 mA
4.9 to 5.1 Vdc, 1 mA
FIELD WIRING
TERMINALS
INPUT
Isolated Module Specifications
Not used
A:
Positive discrete input
B:
Negative discrete input
C:
Type:
Range:
Active; 2 to 9 mA.
Current:
voltage (Vi), loop resistance (Rl),
and scaling resistor (Rs, 10 ohm
supplied):
I = (Vi - 1)/(3.3K + Rl + Rs)
Maximum Voltage:
forward, 5 Vdc reverse.
Two-state current sense.
Inactive; 0 to 0.5 mA.
Determined by input
30 Vdc
POWER
REQUIREMENTS
INPUT
ISOLATION
4.9 to 5.1 Vdc, 1 mA maximum
(supplied by ROC).
Isolation:
input to output, and input or output to
case.
Voltage:
minimum, input to output.
Capacitance:
output.
100 megohm minimum,
4,000 Vac (RMS)
6 pF typical, input to
3-44Rev 5/00
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.