Emerson Fisher 161 Series, 161AY, 161EB Instruction Manual

Instruction Manual D103232X012
August 2018
161 Series
161 Series Pilots for Pilot-Operated Pressure Reducing Regulators
WARNING
!
Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion,
re and/or chemical contamination
causing property damage and personal injury or death.
Fisher™ regulators must be installed, operated and maintained in accordance with federal, state and local codes, rules and regulations and Emerson Process Management Regulator Technologies, Inc. (Emerson) instructions.
If the regulator vents gas or a leak develops in the system, service to the unit may be required. Failure to correct trouble could result in a hazardous condition.
procedures performed by unqualied
personnel may result in improper adjustment and unsafe operation. Either condition may result in equipment damage or personal injury. Only a
qualied person shall install or service
the 161 Series regulator.
W7430
TYPE 161AY
W6505
TYPE 161EB
Introduction
Scope of the Manual
This manual provides installation, startup, maintenance and parts ordering information for the 161 Series Pilots used together with pilot-operated pressure reducing regulators in low and high-pressure applications. For information on mounting on
Figure 1. 161 Series Pilot
pilot-operated regulators, monitoring systems and installations, refer to full product literature:
Type EZR: D102600X012 Type EZL: D103091X012
161 Series
Specications
The Specications section lists pressure limitations and other specications for all models of 161 Series pilots.
Please note that the pilot control spring range is marked on the spring case of 161 and 161EB Series pilots and on the nameplate of 161AY Series pilots.
Outlet (Control) Pressure Ranges
See Table 1
Proportional Bands
See Table 1
Maximum Inlet Pressure
(1)
See Table 2
1. The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.
Pilot Flow Coefcients
See Table 3
Options
Type 252 Pilot supply lter
Pilot Sping Case Vent
1/4 NPT (internal)
Table 1. Outlet (Control) Pressure Ranges, Proportional Bands and Pilot Control Spring Information
OUTLET (CONTROL)
PILOT TYPE
161 or 161M
161AY, 161AYM
or 161AYW
161EB or
161EBM
161EBH or
161EBHM
1. Proportional band includes outlet pressure drop plus hysteresis (friction), but does not include lockup.
2. Proportional band was determined with a pressure drop ranging from 50 to 150 psig / 3.4 to 10.3 bar. Approximately double the proportional band if the pressure drop is less than 50 psig / 3.4 bar.
3. With Type 112 restrictor set on 2.
4. The spring ranges for the Type 161AYW is 3 to 12 in. w.c. / 7.5 to 30 mbar.
5. The spring ranges for the Type 161AYW is 11 to 25 in. w.c. / 27 to 62 mbar.
6. The spring ranges for the Type 161AYW is 0.9 to 2.5 psig / 0.06 to 0.17 bar.
7. Proportional band was determined with a pressure drop ranging from 100 to 300 psig / 6.9 to 20.7 bar. Approximately double the proportional band if the pressure drop is less than 100 psi / 6.9 bar
PRESSURE RANGE
psig bar psig bar In. mm In. mm
5 to 15 0.34 to 1.03 2 0.14 1E392527022 Yellow 0.148 3.76 2.00 50.8
10 to 125 0.69 to 8.62 2 0.14 1K748527202 Red 0.192 4.88 2.19 55.6
120 to 300 8.3 to 20.7 6 0.41 15A9258X012 Green 0.243 6.17 1.88 47.8
6 to 15 in. w.c.
0.5 to 1.2
1.2 to 2.5
130 to 200 8.96 to 13.8 1.5 0.10 17B1263X012 Blue 0.262 6.66 3.85 97.8
200 to 350 13.8 to 24.1 3 0.21 17B1264X012 Red 0.294 7.47 4.22 107
250 to 450 17.2 to 31.0 3.5 0.24
400 to 700 27.6 to 48.2 7 0.48
(4)
15 to 37 mbar
(5)
0.03 to 0.08
(6)
0.08 to 0.17
2.5 to 4.5 0.17 to 0.31 0.5 0.03 1B537227022 Light Blue 0.187 4.75 3.94 100
4.5 to 7 0.31 to 0.48 0.5 0.03 1B537327052 Black 0.218 5.54 3.98 101
5 to 15 0.34 to 1.03 0.5 0.03 17B1260X012 White 0.120 3.05 3.75 95.2
10 to 40 0.69 to 2.76 0.5 0.03 17B1262X012 Yellow 0.148 3.76 3.75 95.2
30 to 75 2.07 to 5.17 0.6 0.04 17B1259X012 Black 0.187 4.75 4.00 102
70 to 140 4.83 to 9.65 1.3 0.09 17B1261X012 Green 0.225 5.71 3.70 94.0
(4)
(5)
1 in. w.c 2 mbar 1B537027052 Yellow 0.114 2.90 4.31 109
(6)
0.5 0.03 1B537127022 Green 0.156 3.96 4.06 103
PROPORTIONAL
(1)(2)(3)
BAND
1 in. w.c 2 mbar 1B653927022 Olive Green 0.105 2.67 3.75 95.2
Part Numbers Color Code
(7)
17B1263X012 Blue 0.262 6.66 3.85 97.8
(7)
17B1264X012 Red 0.294 7.47 4.22 107
PILOT CONTROL SPRING INFORMATION
Wire Diameter Free Length
TYPE
161 1500 103 1200 82.7
161AY 150 10.3 150 10.3
161EB and 161EBH 1500 103 1200 82.7
161M 1500 103 1200 82.7 1500 103
161AYM or 161AYW 150 10.3 150 10.3 150 10.3
161EBM and 161EBHM 1500 103 1200 82.7 1500 103
1. Maximum pressure to prevent the casings from bursting during abnormal operation (leaking to atmosphere and internal parts damage may occur).
MAXIMUM INLET PRESSURE
psig bar psig bar psig bar
2
Table 2. Pilot Pressure Ratings
MAXIMUM EMERGENCY OUTLET PRESSURE OR MAXIMUM EMERGENCY SENSE PRESSURE
MAXIMUM BLEED (EXHAUST) PRESSURE
(1)
FOR MONITOR PILOTS
- - - -
Orice Size C
3/32 in. / 2.4 mm 1/8 in. / 3.2 mm 1/4 in. / 6.4 mm
Table 3. Pilot Flow Coefficients
161AY SERIES 161EB SERIES
6.9
12.3 50
g
C
0.20
0.35
1.43
v
C
1
35 35 35
Orice Size C
1/8 in. /
3.18 mm
g
8.5 0.28 30.4
161 Series
C
v
C
1
Product Description
The 161 Series pilots are mainly used in natural gas, air or other non-corrosive gas applications. For applications that have high pressure drops, using a Type 161AYM, 161EBM or 161EBHM monitor pilot will increase the accuracy of the regulator.
161 Series pilot models are the following:
Type 161—Downstream pressure range from 5 to
300 psig / 0.34 to 20.7 bar. Pilot bleed exhausts downstream through the sense (control) line.
Type 161M—Downstream pressure range from 5 to 300 psig / 0.34 to 20.7 bar. A static sensing (control) line is isolated from pilot bleed (exhaust). The Type 161M is used in working monitor and other application that require a sense (control) line isolated from pilot bleed (exhaust).
Type 161AY—Low-pressure pilot with an outlet pressure range from 6 in. w.c. to 7 psig / 15 mbar to
0.48 bar. Pilot bleeds (exhausts) downstream through the sense (control) line.
Type 161AYM—The monitor version of the Type 161AY pilot. The pilot bleed (exhaust) is isolated from the sense (control) line. This pilot is used in monitoring systems requiring an isolated pilot bleed (exhaust).
Type 161AYW- A version of the Type 161AY used solely as the upstream monitor pilot on a working monitor setup.
Type 161EB—High accuracy pilot with an outlet pressure range from 5 to 350 psig / 0.34 to 24.1 bar. Pilot bleeds (exhausts) downstream through the sense (control) line.
Type 161EBM—The monitor version of the Type 161EB pilot. The pilot bleed (exhaust) is isolated from the sense (control) line. This pilot is used in monitoring systems requiring an isolated pilot bleed (exhaust).
Type 161EBH—The high pressure version of the Type 161EB pilot with an outlet pressure range from 250 to 700 psig / 17.2 to 48.3 bar.
Type 161EBHM—The high pressure version of the Type 161EBM pilot with an outlet pressure range from 250 to 700 psig / 17.2 to 48.3 bar.
Principle of Operation
As long as the outlet (control) pressure is above the outlet pressure setting, the pilot valve plug or disk remains closed. Force from the main spring, in addition to inlet pressure bleeding through the Type 112 restrictor, provides downward loading pressure to keep the main valve diaphragm and plug assembly tightly shutoff. When the outlet pressure decreases below the pilot outlet pressure setting, the pilot plug or disk assembly opens. Loading pressure bleeds downstream through the pilot faster than it can be replaced through the Type 112 restrictor. This reduces loading pressure on top of the main valve diaphragm and plug assembly and lets the unbalanced force between inlet and loading pressure overcome the main spring force to open the regulator diaphragm and plug assembly.
As the outlet pressure rises toward the outlet pressure setting, it compresses the pilot diaphragm against the pilot control spring and lets the pilot valve plug close. Loading pressure begins building on the regulator diaphragm and plug assembly. The loading pressure, along with force from the main spring, pushes the diaphragm and plug assembly onto the knife-edged seat, producing tight shutoff.
Installation
WARNING
!
Personal injury or equipment damage, due to bursting of pressure-containing parts may result if this regulator is overpressured or is installed where service conditions could exceed any rating of the adjacent piping of piping connections. To avoid such injury or damage, provide pressure-relieving or pressure-limiting devices to prevent service conditions from exceeding those limits. Also, be sure the installation is in compliance with all applicable codes and regulations. Additionally, physical damage to the regulator could break the pilot off the main valve, causing
3
161 Series
personal injury and property damage due to bursting of pressure-containing parts. To avoid such injury and damage, install the regulator in a safe location.
1. Use qualied personnel when installing, operating and maintaining pilots. Before installing, inspect pilot and tubing, for any shipment damage or foreign material that may have collected during crating and shipment. Make certain that body is clean and the pipelines are free of foreign material.
WARNING
!
In hazardous or ammable gas service,
vented gas may accumulate and cause personal injury, death or property
damage due to re or explosion. Vent
a regulator in hazardous gas service to a remote, safe location away from air intakes or any hazardous location. The vent line or stack opening must be protected against condensation or clogging.
2. Pilots have a 1/4 NPT vent connection in the spring case. To remotely vent gas from the spring case, remove the screened vent and connect 1/4 in. / 6.4 mm piping or tubing. It should vent to a safe location, have as few elbows as possible and have a screened vent on its exhaust. Install the regulator and any remote vent spring or tubing so that the vent is protected from condensation, freezing or substance that may clog it.
CAUTION
To avoid freeze-up because of pressure drop and moisture in the gas, use anti-freeze practices, such as heating the supply gas or adding a de-icing agent to the supply gas.
3. Run a 3/8 in. / 9.5 mm outer diameter or larger pilot supply line from the upstream pipeline to the
lter inlet, bushing the line down to t the 1/4 NPT lter connection. Do not make the upstream
pipeline connection in a turbulent area, such as near a nipple, swage or elbow. If the maximum pilot inlet pressure could exceed the pilot rating, install a separate pressure reducing regulator in the pilot supply line. Install a hand valve in the pilot
supply line and provide vent valves to properly isolate and relieve the pressure from the regulator.
4. Attach a 1/2 in. / 13 mm piping or tubing downstream control line to the 1/2 NPT control line connection on the actuator casings. Connect the other end of the control line to the pipeline downstream of the regulator. Do not attach the control line near any elbow, swage, block valve or any other location that might cause turbulence. Install a full port ball valve in the control line to shut off the control pressure when using the bypass.
Startup and Adjustment
Pre-Startup Considerations
Each regulator is factory-set for the outlet pressure
specied on the order. If no setting was specied,
outlet pressure was factory-set at the mid-range of the pilot control spring. Before beginning the startup procedure in this section, make sure the following conditions are in effect:
• Block valves isolate the regulator
• Vent valves are closed
• A bypass, if any, is in operation
In all cases, check the control spring setting to make sure it is correct for the application.
CAUTION
Be sure to slowly introduce pressure into the system to prevent downstream overpressure due to potential rapid pressure increase. Pressure gauges should always be used to monitor downstream pressure during startup. Procedures used in putting this regulator into operation must be planned accordingly if the downstream system is pressurized by another regulator or by a manual bypass.
Pilot Adjustment
For 161 Series pilots, remove the pilot closing cap
(key 16, Figures 4 through 6 or key 22, Figure 7) and, on 161EB Series only, loosen the locknut (key 12, Figure 4). Turn the adjusting screw (key 11, Figures 4 through 6 or key 35, Figure 7) into the
4
Loading...
+ 8 hidden pages