Emerson Fisher 1098-EGR, Fisher 1098H-EGR Instruction Manual

Instruction Manual Form 5084
February 2016
Types 1098-EGR and 1098H-EGR
Types 1098-EGR and 1098H-EGR Pressure Reducing Regulators
WARNING
Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion,

causing property damage and personal injury or death.
Fisher® regulators must be installed, operated and maintained in accordance with federal, state and local codes, rules and regulations and Emerson Process Management Regulator Technologies, Inc. (Emerson™) instructions.
If the regulator vents gas or a leak develops in the system, service to the unit may be required. Failure to correct trouble could result in a hazardous condition.
Installation, operation and maintenance

personnel may result in improper adjustment and unsafe operation. Either condition may result in equipment

personnel when installing, operating and maintaining the Types 1098-EGR and 1098H-EGR pressure reducing regulator.
W6956
Figure 1. Type 1098-EGR
valve is also covered when a 61 Series pilot is used. Instructions and parts lists for monitoring pilots and other equipment used with this regulator are found in separate manuals.
Description
Introduction
Scope of the Manual
This manual describes and provides instructions and parts list for Type 1098-EGR or 1098H-EGR regulator complete with a standard P590 Series
 lter and either a 6350 Series regulator, a 61 Series
pilot or a Type Y600AM pilot. The Type 1806 check
Types 1098-EGR and 1098H-EGR regulators provide economical and accurate pressure control in a wide variety of applications: natural gas distribution
systems; fuel gas supply to industrial boilers, furnaces,
ovens and mixers; and large commercial/industrial establishments such as shopping centers and schools. They are also used in plant air service and in liquid service where a slow stroking time (approximately 30 to 90 seconds) is desired on both opening and closing the main valve.
D100339X012
www.fisherregulators.com
Types 1098-EGR and 1098H-EGR

The Specications section lists pressure limitations and other specications for various Types 1098-EGR and 1098H-EGR constructions. Specications for a given regulator as it originally comes from the factory are stamped on nameplates located on both the actuator and main valve body, while the pilot control spring range is displayed on the pilot spring case and the pilot restriction code is stamped on the pilot body (S = standard gain, L = low gain and H = high gain). To determine maximum pressure ratings, the individual ratings for the main valve, actuator and
pilot must all be considered.
Body Sizes and End Connection Styles
See Table 1
Main Valve Maximum Inlet Pressure
(1)
400 psig / 27.6 bar or body rating limit whichever is lower
Maximum Pilot Supply Pressure
(1)(2)
600 psig / 41.4 bar
Outlet Pressure Ranges
See Table 2
Main Valve Flow Direction
In through the seat ring and out through the cage
Pressure Registration
External
Temperature Capabilities
Nitrile (NBR):
-20 to 180°F / -29 to 82°C
Fluorocarbon (FKM):
0 to 300°F / -18 to 149°C,
Water is limited to 0 to 200°F / -18 to 93°C
Actuator Sizes and Maximum Pressures
See Table 3
Maximum and Minimum Differential Pressures
See Table 4
Main Valve Flow Characteristic
Linear (standard), Whisper Trim
or
Quick opening
1. The pressure/temperature limits in this Instruction Manual or any applicable standard limitation should not be exceeded.
2. For stability or overpressure protection, a reducing regulator may be installed upstream of the pilot according to the Installation section.
Table 1. Body Sizes and End Connection Styles
Ethylenepropylene (EPDM):
-20 to 275°F / -29 to 135°C
Options
• NACE Construction
• Boiler Fuel Construction
• Aqueous Service Construction
• Monitor Conguration
• Noise Abatement Trim
(1)
BODY SIZE
NPS DN
1 or 2 25 or 50 NPT, CL125 FF or CL250 RF NPT, CL150 RF, CL300 RF, CL600 RF, BWE, SWE or PN 16/25/40
3, 4 or 6 80, 100 or 150 CL125 FF or CL250 RF CL150 RF, CL300 RF, CL600 RF, BWE or PN 16/25/40
8 x 6 or 12 x 6 200 x 150 or 300 x 150 - - - - CL150 RF, CL300 RF, CL600 RF or BWE
2
CAST IRON STEEL OR STAINLESS STEEL
PILOT TYPE
6351
6352
6353
(1)
6354L
(2)
6354M
(2)
6354H
61L 61LD 61LE
61H 10 to 65 0.69 to 4.5 Green Stripe 0Y066427022
61HP
Y600AM
1. Without diaphragm limiter.
2. With diaphragm limiter.
Types 1098-EGR and 1098H-EGR
Table 2. Outlet Pressure Ranges
OUTLET PRESSURE RANGE
psig bar
3 to 20 5 to 35
35 to 100
14 in. w.c. to 2 psig
2 to 10
3 to 40
35 to 125
0.21 to 1.4
0.35 to 2.4
2.4 to 6.9
35 mbar to 0.1 bar
0.14 to 0.69
0.21 to 2.8
2.4 to 8.6
85 to 200 5.9 to 13.8 Blue 1L346127142
175 to 220 12.1 to 15.2 Blue 1L346127142
200 to 300 13.8 to 20.7 Green 15A9258X012
7 in. w.c. to 2 psig
1 to 5 2 to 10 5 to 15
10 to 20
15 to 45
35 to 100
100 to 300
4 to 8 in. w.c.
7 to 16 in. w.c.
15 in. w.c. to 1.2 psig
1.2 to 2.5
2.5 to 4.5
4.5 to 7
17 mbar to 0.1 bar
0.07 to 0.3
0.14 to 0.69
0.35 to 1.0
0.69 to 1.4
1.0 to 3.1
2.4 to 6.9
6.9 to 20.7
10 to 20 mbar 17 to 40 mbar
37 mbar to 0.08 bar
0.08 to 0.17
0.17 to 0.31
0.31 to 0.48
SPRING COLOR SPRING PART NUMBER
Green
Unpainted
Red
Yellow
Black
Yellow
Red
Red
Yellow
Blue
Brown
Green
Yellow
Blue
Red
Red
Unpainted
Yellow Green
Light Blue
Black
1B986027212 1B788327022
1K748527202
14A9672X012 14A9673X012
1E392527022 1K748527202
1B886327022
1J857827022
1B886427022
1J857927142
1B886527022
1E392527022 1D387227022 1D465127142
1B653827052 1B653927022 1B537027052 1B537127022 1B537227022 1B537327052
Table 3. Actuator Sizes and Maximum Pressures
ACTUATOR TYPE ACTUATOR SIZE
1098
30
40 (standard)
70
1098H 30 350 24.1 400 27.6
OUTLET CONTROL PRESSURE EMERGENCY CASING PRESSURE
psig bar psig bar
100
75 50
6.9
5.2
3.4
115
82 65
7.9
5.6
4.5
Table 4. Maximum and Minimum Differential Pressures for Main Valve Selection
BODY SIZE
SPRING PART
NUMBER
SPRING
COLOR
MAXIMUM ALLOWABLE
DIFFERENTIAL PRESSURE
(1)
Size 30 Actuator Size 40 Actuator Size 70 Actuator
NPS DN psig bar psig bar psig bar psig bar
14A9687X012 Green 60 4.1 3.5 0.24 2.5 0.17 1 0.07
1 25
14A9680X012 Blue 125 8.6 5 0.34 3 0.21 1.5 0.10
14A9679X012 Red 400
(3)
27.6
(3)
7 0.48 5 0.34 2.5 0.17
14A6768X012 Yellow 20 1.4 - - - - - - - - 2 0.14 1 0.07
2 50
14A6626X012 Green 60 4.1 4 0.28 3 0.21 1.5 0.10
14A6627X012 Blue 125 8.6 6 0.41 5 0.34 2 0.14
14A6628X012 Red 400
(3)
27.6
(3)
11 0.76 10 0.69 3 0.21
14A6771X012 Yellow 20 1.4 - - - - - - - - 2.5 0.17 1 0.07
3 80
14A6629X012 Green 60 4.1 5 0.34 4 0.28 2 0.14
14A6630X012 Blue 125 8.6 8 0.55 6 0.41 2.5 0.17
14A6631X012 Red 400
(3)
27.6
(3)
14 0.97 11 0.76 4 0.28
14A6770X012 Yellow 20 1.4 - - - - - - - - 3.5 0.25 1.3 0.09
4 100
14A6632X012 Green 60 4.1 10 0.69 5 0.34 2.5 0.17
14A6633X012 Blue 125 8.6 13 0.90 8 0.55 3 0.21
14A6634X012 Red 400
(3)
27.6
(3)
22 1.5 13 0.90 5 0.34
15A2253X012 Yellow 20 1.4 - - - - - - - - 6 0.42 2.2 0.15
6, 8 x 6
or 12 x 6
1. Maximum inlet pressure is equal to set pressure plus maximum differential.
2. Requires special 6300 Series pilot construction without integral check valve and with external Type 1806H 40 psid / 2.8 bar d check valve.
3. Should not exceed the body rating limit. Use this pressure value or the body rating limit, whichever is lower.
150, 200 x 150
or 300 x 150
14A9686X012 Green 60 4.1 13 0.90 9.5 0.66 4 0.28
14A9685X012 Blue 125 8.6 19 1.3 14 0.97 6 0.41
15A2615X012 Red 400
(3)
27.6
(3)
(2)
28
MINIMUM DIFFERENTIAL PRESSURE
REQUIRED FOR FULL STROKE
(2)
1.9
19 1.3 8 0.55
3
Types 1098-EGR and 1098H-EGR
Table 5. Recommended Type MR95H Pressure Settings for Use with the Type Y600AM Pilot
SUPPLY PRESSURE
BODY SIZE
NPS DN psig bar psig bar psig bar psig bar psig bar psig bar
1 25
2 50
3 80
4 100
6 or 8 x 6
1. The pressures shown in the table are the minimum supply pressures required by the pilot. If the inlet pressure is less than shown, an external pilot supply is necessary.
150 or
200 x 150
TYPE EGR
SPRING COLOR
Green
Blue
Red
Green
Blue
Red
Green
Blue
Red
Green
Blue
Red
Green
Blue
Red
Red Unpainted Yellow Green Light Blue Black
6
0.41
7
0.48
8
0.55
6
0.41
8
0.55
13
0.90
7
0.48
9
0.62
14
0.97
8
0.55
11
0.76
16
1.1
13
0.90
17
1.2
22
1.5
6
0.41
7
0.48
8
0.55
6
0.41
8
0.55
13
0.90
7
0.48
9
0.62
14
0.97
8
0.55
11
0.76
16
1.1
13
0.90
17
1.2
22
1.5
Principle of Operation
Type Y600AM Spring Color
7
0.48
8
0.55
9
0.62
7
0.48
9
0.62
14
0.97
8
0.55
10
0.69
15
1.0
9
0.62
12
0.83
17
1.2
14
0.97
18
1.2
23
1.6
8 10 11
9 11 16
10 12 17
11 14 19
15 20 25
0.55
0.69
0.76
0.62
0.76
1.1
0.69
0.83
1.2
0.76
0.97
1.3
1.0
1.4
1.7
11
0.76
13
0.90
14
0.97
12
0.83
14
0.97
19
1.3
13
0.90
15
1.0
20
1.4
14
0.97
17
1.2
22
1.5
18
1.2
23
1.6
28
1.9
13
0.90
14
0.97
15
1.0
13
0.90
15
1.0
20
1.4
14
0.97
16
1.1
21
1.5
15
1.0
18
1.2
23
1.6
20
1.4
24
1.7
29
2.0
The pilot-operated Types 1098-EGR and 1098H-EGR regulators both use inlet pressure as the operating
medium, which is reduced through pilot operation to
load the actuator diaphragm. Outlet or downstream pressure opposes loading pressure in the actuator and also opposes the pilot control spring. The Type 1098- EGR regulator operation schematic is shown in Figure 2.
In operation, assume that outlet pressure is below
the pilot control setting. Control spring force on the pilot diaphragm opens the pilot valve plug providing additional loading pressure to the actuator diaphragm. This loading pressure forces the actuator stem
forward, opening the main valve plug via a bump
connection. The upward motion of the plug allows gas
to ow through the cage into the downstream system.
When downstream demand has been satised, outlet pressure tends to increase, acting on the pilot and
actuator diaphragms. This pressure exceeds the pilot
control spring setting, moving the pilot diaphragm away and letting the valve plug spring (Type 6351,
61 Series or Type Y600AM pilots) or bellows
(Types 6352 through 6354M pilots) close the pilot valve plug (unbalanced in the Type 6351 or 61 Series pilots but balanced in the Types 6352 through 6354M pilots). Excess loading pressure on the actuator diaphragm escapes downstream through the bleed
hole (Type 6351 pilot), bleed orice (61 Series pilot), restriction (Types 6352 through 6354M pilots) or xed
restrictor (Type Y600AM pilot).
Reduced actuator loading pressure permits the main valve to close. The combination of main valve spring force and valve plug imbalance provides positive valve plug shutoff against the port and upper seals.
To protect the Type 1098 or 1098H actuator diaphragm
from excessive differential pressure, the 6350 Series
pilots have an integral check valve that allows loading pressure to bleed downstream at approximately 25 psig / 1.7 bar differential across the actuator diaphragm. An external check valve (Type 1806) is required when differential is higher than 25 psi /
1.7 bar or when using the 61 Series or Y600AM pilots. with the normal operation of the regulator.
4
TYPE 6351
TYPE 6352, 6353 OR 6354
Types 1098-EGR and 1098H-EGR
TYPE 1098-EGR
A6563
INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE LOADING PRESSURE
TYPE 1098-EGR WITH 6350 SERIES PILOT
TYPE 1098-EGR
TYPE 1806
TYPE 61LD
A6641
INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE LOADING PRESSURE
TYPE 1098-EGR WITH TYPE 61LD PILOT
Figure 2. Operational Schematics
5
Types 1098-EGR and 1098H-EGR
TYPE MR95H
TYPE 1098-EGR
OPTIONAL:
TYPE 112 RESTRICTOR
TYPE Y600AM
M1008
INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE LOADING PRESSURE PILOT SUPPLY PRESSURE
TYPE 1098-EGR WITH TYPE Y600AM PILOT AND TYPE MR95H PRESSURE SUPPLY REGULATOR
Installation and Startup
WARNING
Personal injury, equipment damage or leakage due to escaping accumulated gas or bursting of pressure-containing parts may result if this regulator is overpressured or is installed where service conditions could exceed the limits given

appropriate nameplate or where conditions exceed any ratings of the adjacent piping or piping connections. To avoid such injury or damage, provide pressure­relieving or pressure-limiting devices to prevent service conditions from exceeding those limits.
FIXED RESTRICTOR
Figure 2. Operational Schematics (continued)
Additionally, physical damage to the regulator may result in personal injury and property damage due to escaping accumulated gas. To avoid such injury and damage, install the regulator in a safe location.
Standard Single-Pilot Regulator (Figure 3)
Installations
A Type 1098-EGR or Type 1098H-EGR regulator
bleeds no gas to the atmosphere, making it suitable for
installation in pits or other enclosed locations without elaborate venting systems. This regulator can also be
installed in pits subject to ooding by venting the pilot spring case above the expected ood level so that the
pilot diaphragm is exposed to atmospheric pressure.
6
Types 1098-EGR and 1098H-EGR
48A6566-A
B1622
4 MAIN PIPE
DIAMETERS
 PIPE
PILOT SUPPLY LINE
FILTER
VENT
10 MAIN PIPE DIAMETERS
TYPE 1098-EGR OR 1098H-EGR REGULATOR WITH STANDARD 6350 SERIES PILOT
Figure 3. Standard Single-Pilot Installation
CONTROL LINE
TO PILOT LIGHT (IF USED FOR BOILER FUEL INSTALLATION)
N 13 mm PIPE
 I 13 mm PIPE
FILTER
TYPE Y600AM AUXILIARY PILOT
48A6566-A
B1622
4 MAIN PIPE DIAMETERS
VENT
PILOT SUPPLY LINE
VENT
10 MAIN PIPE DIAMETERS
CONTROL LINE
TYPE 1098-EGR SIZE 70 REGULATOR WITH QUICK OPENING CAGE AND STANDARD TYPE 6352 WORKING PILOT
Figure 4. Typical Dual-Pilot Boiler Fuel Installation
TO PILOT LIGHT
N. 13 mm PIPE
7
Types 1098-EGR and 1098H-EGR
Note
Normal pressure drop assists shutoff. Therefore, leakage may result during any reverse pressure drop condition.
1. Use qualied personnel when installing, operating and maintaining regulators. Before installing, inspect the main valve, pilot and tubing for any
shipment damage or foreign material that may have collected during crating and shipment. Make certain the body interior is clean and the pipelines are free of foreign material. Apply pipe compound only to the external pipe threads with a screwed body or use suitable line gaskets and good bolting
practices with a anged body.
With a weld end body, be sure to remove the trim package, including the gasket, according to the
Maintenance section before welding the body into the line. Do not install the trim package until any post-weld heat treatment is completed. If heat
treating, prevent scale buildup on all machined
guiding and sealing surfaces inside the body and
at the bonnet ange/body joint.
2. The regulator maybe installed in any orientation, as long as ow through the regulator matches the direction of the ow arrow attached to the valve body. However, mounting the main valve with the
valve stem in a horizontal position may experience stem wear on units with a size 70 actuator or
NPS 4 and larger.
3. Install a three-valve bypass around the regulator if continuous operation is necessary during
maintenance or inspection. The pilot may be eld-
changed to the opposite-side mounting position by swapping the pilot pipe nipple to the opposite bonnet tapping.
WARNING
A regulator may vent some gas to the atmosphere. In hazardous or

accumulate and cause personal injury,

explosion. Vent a regulator in hazardous gas service to a remote, safe location away from air intakes or any hazardous location. The vent line or stack opening must be protected against condensation or clogging.
4. To keep the pilot spring case vent from being
plugged or the spring case from collecting moisture, corrosive chemicals or other foreign material, point
the vent down or otherwise protect it. To remotely
vent the standard pilot, remove the vent and install obstruction-free tubing or piping into the 1/4 NPT
vent tapping. Provide protection on a remote vent by installing a screened vent cap into the remote end of the vent pipe.
5. Run a 3/8 in. / 9.5 mm outer diameter or larger pilot supply line from the upstream pipeline to
the lter inlet as shown in Figure 3. Do not make
the upstream pipeline connection in a turbulent
area, such as near a nipple, swage or elbow. If
the maximum pilot inlet pressure could exceed the
pilot rating, install a separate reducing regulator in
the pilot supply line. Install a hand valve in the pilot supply line and provide vent valves to properly isolate and relieve the pressure from the regulator.
6. Attach a 1/2 NPT downstream pressure control line downstream of the regulator in a straight run
of pipe, as shown in Figure 3. Do not make the tap near any elbow, swage or nipple that might cause
turbulence. Connect the other end of the control line to the bonnet connection. Install a hand valve in the control line to shut off the control pressure when the bypass is in use.
7. If a quick acting solenoid is to be installed
downstream of the regulator, the regulator
and solenoid should be located as far apart as practical. This maximizes the gas piping volume between the regulator and solenoid and improves the regulator response to quick-changing
ow rates.
8. Consult the appropriate instruction manual for installation of an optional Type 662 pneumatic or electric remote control drive unit. For optional remote pneumatic loading of a 6350 or 61 Series
pilot, make the loading piping connections to the 1/4 NPT vent connection.
Pre-startup Considerations
Before beginning the startup procedures in this section,
make sure the following conditions are in effect:
• Block valves isolate the regulator.
Vent valves are closed.
Hand valves are closed.
8
Types 1098-EGR and 1098H-EGR
CAUTION
Introduce pilot supply pressure into the regulator before introducing any downstream pressure or internal damage may occur due to reverse pressurization of the pilot and main valve components.
Always use pressure gauges to monitor downstream pressure during startup. Procedures used in putting this regulator into operation must be planned accordingly if the downstream system is pressurized by another regulator or by a manual bypass.
Note
For proper operation, pilot supply pressure must exceed control pressure

the actuator nameplate as minimum differential pressure.
The only adjustment necessary on a Type 1098-EGR or 1098H-EGR regulator is the pressure setting of the pilot control spring. Turning the adjusting screw clockwise into the spring case increases the spring compression and pressure setting. Turning the adjusting screw counterclockwise decreases the spring compression and pressure setting.
Pilot Adjustment
To adjust standard 6350 Series pilots: Loosen the locknut and turn the adjusting screw. Then tighten the locknut to maintain the adjustment position.
On a standard Types 6352 through 6354M pilots,
closing cap must be removed before adjustment and replaced afterward.
WARNING
To avoid possible personal injury from a pressure-loaded pilot, carefully vent the spring case before removing the closing cap. Otherwise, trapped loading pressure could forcefully eject the freed closing cap.
To adjust the 61 Series or Type Y600AM pilots:
Remove the closing cap and turn the adjusting screw. Any adjustments made should set the controlled pressure within the appropriate spring range shown in the Table 2.
Startup
1. Slowly open the pilot supply line hand valve.
2. Slowly open the upstream block valve and partially open the downstream block valve for minimum ow. Slowly open the hand valve in the control line.
3. Adjust the pilot setting, if necessary.
4. Completely open the downstream block valve.
5. Slowly close the bypass valve, if any.
Dual-Pilot Boiler Fuel Control
Applications
To enhance proper operation and adequate response to negative pressure shock condition in low differential
pressure boiler fuel control applications, use the Type 1098-EGR boiler fuel conguration:
Type 1098-EGR with Type 6352 pilot
Size 70 Actuator
Quick Opening Cage
Yellow Main Spring
Type Y600AM or 627M Auxiliary Pilot mounted in
parallel with the Type 6352 pilot
To provide faster response, two pilots mounted
in parallel sense the downstream pressure. The Type 6352 pilot is the primary controlling pilot and the Type Y600AM or 627M auxiliary pilot stands by until it senses a negative pressure shock condition.
The auxiliary pilot opens, allowing additional ow into the actuator, increasing the stroking speed and
providing faster response. See Figure 4 for schematic. The quick-opening cage allows maximum capacity at shorter travels to decrease stroking time in opening and closing directions. The service conditions should not exceed 20 psig / 1.4 bar maximum inlet pressure and 10 psi / 0.69 bar maximum differential pressure.
If a pilot light is present, supply it gas with the
Type 1098- EGR. The pilot light gas supply line should branch off the main fuel line downstream of the Type 1098-EGR and include a separate regulator to
control the nal pilot light gas pressure, if required (see
Figure 5). This allows the Type 1098-EGR to have its main valve plug just off the seat waiting for the sudden negative shock created when the boiler solenoid
valve is opened to light the boiler to the high re load. This installation practice signicantly increases the
stroking speed of the Type 1098-EGR. See Figure 5 for schematic.
9
Types 1098-EGR and 1098H-EGR
Note
Modulating solenoid load valves provide

one position to the other, effectively preventing sudden pressure changes in the system. Alternately, a snap-acting solenoid valve can be furnished with a characterized valve plug that, by allowing maximum capacity to be reached at a greater proportion of total travel, slows the action slightly. This action does not control shock as effectively as modulating solenoid valves.
Installation
1. Perform the Standard Single-Pilot Regulator
Installation section through step 4, making sure
that the regulator is installed with the actuator below the main valve as shown in Figure 4.
2. Run a 1/2 in. / 13 mm or larger pilot supply line
from the upstream pipeline to the 1/2 NPT supply
connection in the pipe tee as shown in Figure 4. Do
not make the connection in a turbulent area, such as near a nipple, swage or elbow. If the maximum pilot inlet pressure could exceed the pilot rating, install
a separate regulator in the pilot supply line and provide vent valves so that pressure can be properly isolated and relieved from the regulator.
GAS SUPPLY
TYPE 1098-EGR
PILOT
SUPPLY
E0710
Figure 5. Boiler Fuel Conguration Installation Guide
SAFETY SHUT-OFF VALVE
GAS
PILOT GAS
REGULATOR
FAST-ACTING LOAD VALVE
TO PILOT LIGHT
TO BOILER
3. Slowly open the hand valve in the control line and make sure that the standby pilot is set far enough below the working pilot so that the standby pilot remains closed during normal operation. For
example, with nal desired settings of 11 in. w.c. /
27 mbar for the working pilot and 10 in. w.c. /
25 mbar for the standby pilot, begin by reducing
the working pilot setting far enough below 10 in. w.c. / 25 mbar for the working pilot to shut off. Then set the standby pilot for an outlet
pressure of 10 in. w.c. / 25 mbar. Finally, set the
working pilot for an outlet pressure of 11 in. w.c. / 27 mbar. Table 6 shows how close the standby pilot can be set to the working pilot setting.
4. Completely open the downstream block valve.
3. Attach a 1/2 NPT downstream pressure control line ten pipe diameters downstream of the regulator in a straight run of pipe. Do not make
the tap near any elbow, swage or nipple, which
might cause turbulence. Connect the other end of
the control line to the 1/4 NPT connection in the
control pipe tee as shown in Figure 4. Install a hand valve in the control line to shut off the control pressure when the bypass is in use. Also use the
hand valve to dampen out pulsations, which may
cause instability or cycling of the regulator.
4. Consult the appropriate instruction manual for installation of an optional pneumatic or electric remote control drive unit. For optional remote
pneumatic loading of 6350 or 61 Series pilots,
make the loading piping connections to the
1/4 NPT vent connection.
Startup
1. Slowly open the pilot supply line hand valve.
2. Slowly open the upstream block valve and partially
open the downstream block valve for minimum ow.
5. Slowly close the bypass valve, if any.
Working Monitor (Figure 6)
Installation
1. For both working monitor regulator and working
regulator, perform the Standard Single-Pilot
Regulator Installation section through step 7.
2. Connect another downstream pressure control line and hand valve (Figure 6) to the monitoring pilot according to the monitoring pilot instruction manual.
Attach a 1/2 NPT pressure control line and hand
valve from the intermediate pressure pipeline to the working monitor regulator. Pipe supply pressure between the monitoring pilot and the working monitor regulator according to the monitoring pilot manual.
For two typical monitoring pilots, Table 7 gives
the spread between normal distribution pressure and the minimum pressure at which the working monitor regulator can be set to take over if the working regulator fails to open.
10
Types 1098-EGR and 1098H-EGR
Type 1098-EGR
1098-EGR Working Monitor
6350 SERIES PILOT
6350 SERIES PILOT
March 2007
Type 1098-EGR
TYPE Y600M OR 627-109 MONITORING PILOT
6350 SERIES PILOT
A6788
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
LOADING PRESSURE
INTERMEDIATE PRESSURE
TYPE Y600M OR 627-109 MONITORING PILOT
Figure 6. Typical Working Monitor Installation
Startup
On a working monitor installation (Figure 6), be sure that
the second-stage working regulator is set to operate at a pressure lower than the Type 1098-EGR or 1098H-EGR
working monitor regulator. To do this, increase the setting
of the monitoring pilot until the working pilot is in control of the intermediate pressure and the second-stage working regulator is in control of the downstream pressure. If this
is not done, the monitoring pilot tries to take control of the
downstream pressure.
1. Slowly open the upstream block valve and the hand valves in both pilot supply lines. This energizes both pilots so that their setpoints can be adjusted. Partially open the downstream block
valve for minimum ow.
2. To enable intermediate pressure adjustment with
the working monitor regulator, slowly open the
hand valve in the intermediate pressure control line.
3. To enable downstream pressure adjustment with
the second-stage working regulator, slowly open
the hand valve in the control line to this regulator.
4. Adjust the setting of the monitoring pilot to establish the desired emergency downstream
pressure, which is to be maintained in the event
of open failure of the second-stage working regulator. The emergency downstream pressure should exceed the desired downstream pressure by at least the amount listed in Table 7. The steps
a. Increase the outlet pressure setting of the
b. Install special piping (not shown in Figure 6) so
5. Slowly open the downstream block valve.
6. Slowly close the bypass valve, if any.
6350 SERIES PILOT
followed to set the monitoring pilot may vary with
each piping situation; however, the basic method
remains the same. The following sub steps a and b may be used as examples for setting the monitoring pilot:
second-stage working regulator until the monitoring pilot takes control of the downstream pressure. Adjust the monitoring pilot setting until the desired emergency downstream pressure
is achieved. Then, readjust the second-stage
working regulator to establish the desired downstream pressure.
that the monitoring pilot senses the intermediate pressure. The intermediate pressure then appears to the monitoring pilot as if it was increased downstream pressure and the monitoring pilot controls and reduces the intermediate pressure. Adjust the monitoring pilot setting until the desired emergency downstream pressure is achieved at the intermediate pressure stage. Then slowly close the special piping and open up the monitoring downstream control line for normal service.
11
Types 1098-EGR and 1098H-EGR
Table 6. Auxiliary Pilot Selection (Fast Stroke Dual Pilot)
SIZE CONSTRUCTION
Type Y600AM 1/4 6.4
3/4
NPT
Type 627M 1/2 13 5 to 10 0.34 to 0.69 10B3076X012 Yellow
Construction
Type 161AYW pilot and 150 psig /
10.3 bar maximum allowable pilot inlet pressure
Type 627-109 pilot and 1000 psi /
69 bar maximum allowable pilot
inlet pressure
ORIFICE SPRING RANGE
In. mm psi bar
4 to 8 in. w.c. 10 to 20 mbar 1B653827052 Red
7 to 16 in. w.c. 17 to 40 mbar 1B653927022 Unpainted
15 in. w.c. to 1.2 psi 37 mbar to 0.08 bar 1B537027052 Yellow
1.2 to 2.5 0.08 to 0.17 1B537127022 Green
2.5 to 4.5 0.17 to 0.31 1B537227022 Light Blue
4.5 to 7 0.31 to 0.48 1B537327052 Black
Table 7. Working Monitor Performance
MONITORING PILOT INFORMATION
Spring Range
psig bar
3 to 12 in. w.c.
11 to 25 in. w.c.
25 in. w.c. to 2.5 psi
2.5 to 4.5 psi
4.5 to 7 psi
5 to 20 15 to 40 35 to 80
70 to 150
130 to 200
7 to 30 mbar
27 to 62 mbar
62 mbar to 0.17 bar
0.17 to 0.31
0.31 to 0.4
0.34 to 1.4
1.0 to 2.8
2.4 to 5.5
4.8 to 10.3
9.0 to 13.8
SPRING
NUMBER
Spring Part Number
1B653927022 1B537027052
1B537127022 1B537227022 1B537327052
10B3076X012 10B3077X012 10B3078X012
10B3079X012
SPRING
COLOR
MINIMUM PRESSURE AT WHICH
WORKING MONITOR REGULATOR
normal distribution pressure
14 in. w.c. / 34 mbar over
normal distribution pressure
normal distribution pressure
normal distribution pressure
MINIMUM PRESSURE AT WHICH AUXILIARY
PILOT CAN BE SET
1 in. w.c. / 2 mbar
Under working
pilot setpoint
6 in. w.c. / 14 mbar
Under working
pilot setpoint
8 in. w.c. / 21 mbar
Under working
pilot setpoint
CAN BE SET
3 in. w.c. / 7 mbar over
3.0 psig / 0.21 bar over
5.0 psig / 0.34 bar over
Wide-Open Monitor (Figure 7)
Either the upstream or downstream regulator can be
the monitor regulator. During normal operation, the
monitoring regulator is standing wide open with the reduction to distribution pressure being taken across the working regulator. Only in case of open failure of the working regulator does the wide open monitoring regulator take control at its slightly higher setting.
Note that if using a downstream monitor setup, the
upstream worker regulator actuator must be rated to the application’s full inlet pressure or be protected from it in case it fails wide-open.
Regardless of which regulator is used as the monitor, it
should be equipped with a pilot supply regulator set to 5 psig / 0.34 bar plus the monitor minimum differential presure above the working regulator pressure setting. Since the pilot on the monitoring regulator is wide open
during normal operation, the pilot supply regulator
prevents differential check valve chatter on the monitoring regulator pilot.
Adjustment Recommendations for Monitor Applications
Low amplitude/high frequency monitor trim oscillations can occur if the monitor regulator pressure setting is adjusted too closely to the working regulator pressure setting and/or if the monitor pilot supply regulator pressure setting is adjusted too closely to the monitor regulator pressure setting. The monitor pressure setting should be adjusted so it is at minimum two times the pilot proportional band pressure above the working regulator pressure setting. These adjustments must be made such that other governing
pressure limits, such as casing ratings, pilot maximum differential pressures or regulatory limits, are
not exceeded.
Installation
1. For both the wide-open monitoring regulator
and the working regulator, perform the Standard
Single-Pilot Regulator Installation section through step 7.
12
A6789
INLET PRESSURE
OUTLET PRESSURE
LOADING PRESSURE
PILOT SUPPLY PRESSURE
ATMOSPHERIC PRESSURE
INTERMEDIATE PRESSURE
FILTER
FILTER
Types 1098-EGR and 1098H-EGR
PILOT SUPPLY REGULATOR
6350 SERIES PILOT
Figure 7. Typical Wide-Open Monitor Installations
6350 SERIES PILOT
2. Connect the control line of the wide-open monitoring regulator (Figure 7) to downstream piping near the working regulator control line connection. During normal operation the wide- open monitoring regulator stands wide-open with the pressure reduction being taken across the working regulator. Only in case of working regulator failure does the wide-open monitoring regulator take control at its slightly higher setting.
Startup
Repeat this procedure in turn for each regulator in the installation.
1. Slowly open the pilot supply line hand valve.
2. Slowly open the upstream block valve and partially open the downstream block valve for
minimum ow.
3. Slowly open the hand valve in the control line and adjust the pilot setting if necessary. Set the monitoring regulator at a slightly higher control pressure than the working regulator.
4. Completely open the downstream block valve.
5. Slowly close the bypass valve, if any.
Shutdown
Installation arrangements vary, but in any installation it
is important that the valves be opened or closed slowly and that the outlet pressure be vented before venting inlet pressure to prevent damage caused by reverse pressurization of the pilot or main valve. The following steps apply to the typical installation as indicated.
Single-Pilot, Dual-Pilot Regulator or Wide-Open Monitor
As well as applying to a single-pilot regulator (Figure 3),
the steps in this procedure are also valid for a dual- pilot regulator (Figure 4) or a wide-open monitoring installation (Figure 7) and just need to be repeated for each regulator in such an installation.
1. Slowly close the downstream block valve. If the
control line is downstream of the block valve, also
close the hand valve in the control line.
2. Slowly close the upstream block valve and the hand valve in the pilot supply line.
3. Slowly open the vent valve in the downstream pipeline. If the control line is downstream of the
block valve, also open the vent valve in the control
line. Permit all pressure to bleed out.
4. Slowly open the upstream pipeline vent valve. Allow all pressure to bleed out of both the piping and the pilot.
13
Types 1098-EGR and 1098H-EGR
Working Monitor
1. Slowly close the downstream block valve and the hand valve in the downstream pressure control line.
2. Slowly close the upstream block valve and the hand valves in both pilot supply lines.
3. Slowly open all vent valves and permit all pressures to bleed out of the piping and regulators.
Maintenance
Regulator parts are subject to normal wear and must be inspected and replaced as necessary. The frequency of inspection and replacement of parts depends upon the severity of service conditions or the requirements
of local, state and federal regulations. Due to the
care Emerson™ takes in meeting all manufacturing
requirements (heat treating, dimensional tolerances, etc.), use only replacement parts manufactured or
furnished by Emerson.
The stem O-rings (key 6, Figure 13) on the Type 1098
or 1098H actuator should be lubricated during regularly
scheduled maintenance, using the grease  tting (key 28, Figure 13). Stem O-rings can be checked
for damage during normal operation by line pressure leakage or unexpected grease extrusion from the
actuator vent (key 27, Figure 13). Unless otherwise speci ed, all O-rings, gaskets and seals should be
lubricated with a good grade of general-purpose grease and installed gently rather than forced into
position. Be certain that the nameplates (key 13, Figure 13) are updated to accurately indicate any  eld changes in equipment, materials, service conditions or
pressure settings.
WARNING
To avoid personal injury resulting from sudden release of pressure, isolate the regulator from all pressure and cautiously release trapped pressure from the regulator before attempting disassembly.
Type EGR Main Valve
Replacing Quick-Change Trim Package
Perform this procedure if the entire trim package is replaced. Key numbers for both the complete main valve and its trim package are referenced in Figures 11 and 12. Some replacement trim package assembly numbers are listed in a table in the parts list.
SEAT RING SCREWS INTO CAGE
P1507
All disassembly, trim change and reassembly steps in this section may be performed with the regulator in the main line and without disconnecting the pilot supply or control lines.
1. Remove the cap screws (key 3) with a cast iron
body or remove the stud bolt nuts (key 29, not shown) with a steel body. Pry the body  ange
(key 2) from the valve body (key 1) and lift out the trim package.
2. Perform any required inspection, cleaning or maintenance on the exposed surfaces of the valve body (key 1) or trim package. Replace the gasket (key 4) or cage O-ring (key 17) as necessary.
3. On a pre-built replacement trim package, check indicator zeroing by unscrewing the indicator
protector (key 19) and seeing if the  ange of the
indicator nut (key 22) lines up evenly with the bottom marking on the indicator scale (key 18).
If not, remove the indicator scale and separate
the indicator nut and hex nut (key 8). Hold the
indicator scale against the indicator  tting (key 5)
with the scale base resting against the shoulder of
the  tting and turn the indicator nut until its  ange
is aligned with the bottom scale marking. Then lock both nuts against each other and install the indicator scale and protector.
4. Coat the cage seating surface of the valve body
(key 1) web and the body  ange (key 2) seating
surfaces of the valve body neck with a good grade of general-purpose grease. Install the trim package and secure it evenly with the cap screws
(key 3) or stud bolt nuts (key 29, not shown).
No particular trim package orientation in the body
is required.
Figure 8. Trim Package Removal
Note
BODY FLANGE
CAGE SCREWS INTO BODY FLANGE
14
Loading...
+ 30 hidden pages