Emerson CASH VALVE Installation Manual

CASH VALVE TYPES FR AND FR-6 BACK PRESSURE OR ECONOMIZER VALVES
CRYOGENIC INSTALLATION INSTRUCTIONS
Before installation, these instructions must be carefully read and understood.
DESCRIPTION
The Types FR and FR-6 are designed to function as Back Pressure or Economizer valves in Cryogenic Circuits. The Back Pressure function is to open at a preset pressure and relieve inlet pressure to the discharge side into a lower pressure. The Economizer's function is to open at a preset pressure above the Pressure Build set pressure, and continue to open as gas head pressure from heat leak builds during non-use periods of the system. The Economizer by-passes gas head pressure directly to the Final Line circuit when system draw resumes, drawing down the excess pressure rapidly and re-closes before the Pressure Build regulator opens. FR Series valves are not emergency relief devices, but are designed for continuous pressure regulation.
SPECIFICATION DATA
Service: Cryogenic liquids and gases Sizes: 1-1/4", 1-1/2" and 2" End Connections:
Threaded internal inlet and outlet
Available Body Materials:
Bronze or Stainless Steel
Temperature Rating:
+150°F (339K) to -320°F (78K)
Maximum Pressure:
FR: 400 psi (27.6 bar) FR-6: 600 psi (41.4 bar)
Capacity:
For specific capacity information, consult the factory.
GENERAL INSTALLATION INSTRUCTIONS
Connect the supply line to either the right or left hand body connection. The remaining right or left hand connection should be connected to the service line or plugged depending on the type of installation. The bottom connection, which is indicated by an arrow on the valve body, should be connected to the by-pass or vaporizer line.
Before installing the valve, the piping and valve should be thoroughly flushed out to remove any foreign material. Use a compatible sealant on the male pipe threads and do not over-tighten the valve connections.
CONSTRUCTION
See component description for materials of construction.
OPERATING INSTRUCTIONS
Adjusting the Delivery Pressure:
The regulator’s back pressure setting is adjusted by turning the adjusting screw (2) at the top of the spring chamber (5) after removing the adjusting screw cap (1) and loosening the adjusting screw lock nut (3). To obtain a higher pressure setting, turn the adjusting screw clockwise (into the spring chamber). To lower the pressure setting, turn the adjusting screw counter-clockwise (out of the spring chamber). Tighten the adjusting screw lock nut after the adjustment has been made and install the closing cap.
MAINTENANCE INSTRUCTIONS
CAUTION
Before attempting to service the valve, be sure to shut off the supply pressure and relieve all pressure from BOTH sides of the valve. Refer to the Type FR section view for parts identification. It is not necessary to remove the valve from the line for servicing.
Emerson.com/FinalControl © 2018 Emerson. All rights reserved. VCIOM-10799-EN 19/06
CASH VALVE TYPES FR AND FR-6 BACK PRESSURE OR ECONOMIZER VALVES
CRYOGENIC INSTALLATION INSTRUCTIONS
No. Content Description Construction
1 Adjusting Screw Cap Brass 2 Adjusting Screw Brass or SST 3 Lock Nut Brass or SST 4 Gasket Teflon 5 Spring Chamber Brass or SST 6 Spring Button Brass or SST 7 Pressure Spring SST 8 Name Plate Aluminum 9 Drive Screw SST 10 Nut SST 11 Washer SST 12 Pressure Plate Brass 13 Screw SST 14 Diaphragm Bronze or SST 15 Gasket Teflon 16 Ring SST
Diaphragm Ring
17
(FR-6 only) 18 O-ring Teflon 19 Ball Seat SST 20 Seat Ring SST 21 Body Seat Brass or SST 22 Body Bronze or SST
Brass
FIGURE 1
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Cash Valve is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.