Emerson CASH A-401 Installation Instructions Manual

CASH TYPE A-401 CRYOGENIC PRESSURE REGULATOR
InstallatIon InstructIons
Before installation, these instructions must be fully read and understood.
DESCRIPTION
The Type A-401 regulator is a fully automatic pressure regulating valve designed for cryogenic service in the pressure build-up circuit. Because it may be used for either cryogenic liquids or gases, it may be installed either before or after the pressure build-up coil.
SPECIFICATION DATA
Service: Cryogenic liquids and gases
(pressure reducing or pressure build-up service)
Sizes: 1/2" Connections: Threaded internal inlet
and outlet.
Body Material: ASTM B62 CA836 Bronze Temperature Rating:
+150°F (339°K) to -320°F (78°K)
Maximum Initial Pressure: 600 psig (41.4 bar) Capacity: For specific capacity information,
consult the factory.
GENERAL INSTALLATION INSTRUCTIONS
The Type A-401 regulator should be installed in the horizontal position with the spring chamber upright or down. For other installation requirements, consult the factory. For easy operation and maintenance, it is suggested that manual shut-off valves be installed upstream and downstream from the valve. Before installing the valve, the piping and valve should be thoroughly flushed out to remove any foreign material. Install the valve with the inlet pipe fitted to the inlet connection identified on the valve body. Use a compatible sealant on the male pipe threads and do not over-tighten the valve connections.
CONSTRUCTION
See component description for materials of construction.
All parts are commercially cleaned for oxygen service.
OPERATING INSTRUCTIONS
Adjusting the Delivery Pressure
The regulator’s delivery pressure setting is adjusted by turning the adjusting screw (1) at the top of the spring chamber (3) after loosening the adjusting screw lock nut (2). To increase the delivery pressure, turn the adjusting screw clockwise (into the spring chamber). To decrease the delivery pressure, turn the adjusting screw counter-clockwise (out of the spring chamber). Tighten the adjusting screw lock nut after the adjustment has been made (and reinstall optional cap).
MAINTENANCE INSTRUCTIONS
CAUTION
Before attempting to replace any spare parts, be sure to shut off all pressure connections to the valve. With the valve closed however, system pressure could still be locked between the shut off valve and the inlet and/or outlet sides of the regulator. Before proceeding with any valve service, be certain to relieve the pressure from both sides of the regulator.
Refer to section view on the following page for parts identification. Repair parts can easily be installed without removing the regulator from the line.
Emerson.com/FinalControl © 2018 Emerson. All rights reserved. VCIOM-10805-EN 18/11
CASH TYPE A-401 CRYOGENIC PRESSURE REGULATOR
InstallatIon InstructIons
BILL OF MATERIALS
Item Quantity Part No. Description Material
1 1 18524 Adjusting Screw SST 2 1 16684 Lock Nut SST 3 1 21500 Spring Chamber Bronze 4 1 08225 Spring Button Brass 5 1 13399 Name Plate Aluminum 6 2 02533 Drive Screw SST 7 1 - - - - Pressure Spring SST 8 1 08243 Diaphragm Stop Brass 9 1 12003 Gasket Teflon 10 1 22048 Diaphragm Sub - - - ­10a 1 07999 Nut SST 10b 1 10993 Washer SST 10c 1 22062 Pressure Plate Brass 10d 4 16586 Diaphragm Bronze 10e 1 12002 Gasket Teflon 10f 1 21956 P-Post Button SST 11 1 22173 Piston Sub - - - ­11a 1 22174 Piston Brass 11b 1 21510 Seat Disc Teflon 12 1 06711 Spring SST 13 1 21518 Gasket Gylon 14 1 21970 Bottom Plug Brass 15 4 21517 Screw SST 16 1 21507 Body Bronze
FIGURE 1
PB INLET
PB OUTLET
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Cash is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.