Emerson C471, C477 Instruction Manual

Instruction Manual MCK-2287
September 2014
Types C471, C477 and C486
Types C471, C477 and C486 Internal Valves
WARNING
!
Failure to follow these instructions or to properly install and maintain this equipment
could result in an explosion and/or re
causing property damage and personal injury or death.
Fisher® equipment must be installed, operated and maintained in accordance with federal, state and local codes and Emerson Process Management Regulator Technologies, Inc. (Emerson™) instructions. The installation in most states must also comply with NFPA No. 58 and ANSI Standard K61.1.
Only personnel trained in the proper procedures, codes, standards and regulations of the LP-Gas industry should install and service this equipment.
The internal valve must be closed except during product transfer. A line break downstream of a pump may not actuate the
excess ow valve. If any break occurs in the system or if the excess ow valve closes, the
system should be shut down immediately.
Introduction
P1197
TYPE C477
TYPE C486
TYPE C471
Scope of the Manual
This manual covers instructions for the Types C471, C477 and C486 internal valves.
Description
The valves are typically used on the inlets and outlets of bobtail and transport trucks and on large stationary storage tanks. They can also be installed in-line. Designed for propane, butane or NH3 at ambient temperatures, the valves can be used on other compressed gases, but the user should check with the factory to make sure the valves are suitable for the particular service.
Figure 1. C471, C477 and C486 Series Internal Valves
Specications
The Specications section on the following page shows specications for Types C471, C477 and C486 internal valves.
DOT Internal Self-Closing Stop Valve Requirement—
U.S. Department of Transportation (DOT) regulations 49CFR§178.337-8(a)(4) require each liquid or vapor discharge outlet on cargo tanks (except for cargo tanks used to transport chlorine, carbon dioxide, refrigerated liquid and
certain cargo tanks certied prior to January 1, 1995) to be tted with an internal self-closing stop valve. Fisher “C” Series
internal valves comply with the internal self-closing stop valve requirement under the DOT regulations.
D450229T012
Types C471, C477 and C486
Specications (continued)
Body Size and End Connection Styles Types C471 and C477 Inlet: 2 or 3-inch MNPT / DN 50 or 80 Outlet: 2 or 3-inch FNPT / DN 50 or 80 Type C486 Inlet: 3-inch CL300 RF Flange / DN 80 Outlet: 3-inch FNPT / DN 80
Number of Outlets Type C471: 2 (side and straight through) Types C477 and C486: 1 (straight through)
Excess Flow Springs Type C470 Half Coupling and Type C486 Flows: 2-inch Sizes / DN 50: 105, 150 and 250 GPM / 397, 567
and 946 L/min
3-inch Sizes / DN 80: 160, 265, 375 and 460 GPM / 605,
1003, 1419 and 1741 L/min
Type C470 Full Coupling Flows:
2-inch Sizes / DN 50: 60, 80 and 130 GPM / 227, 302 and 492 L/min
3-inch Sizes / DN 80: 120, 230, 320 and 380 GPM / 454,
870, 1211 and 1438 L/min
Maximum Allowable Inlet Pressure
400 psig / 27.6 bar WOG
Temperature Capabilities
-20 to 150°F / -29 to 66°C
(1)(2)
(1)
Approximate Weights 2-inch Sizes / DN 50:
Type C471: 11 pounds / 5.0 kg Type C477: 9 pounds / 4.1 kg
3-inch Sizes / DN 80:
Type C471: 21 pounds / 10 kg Type C477: 16 pounds / 7.3 kg Type C486: 20 pounds / 9.1 kg
Construction Materials Ductile Iron: Body (Types C471 and C477)
Stainless steel: Stem Assembly, Excess Flow Spring,
Spring Seat, Closing Spring, Disc Holder, Disc Retainer, Screw, O-ring Seat, O-ring Retainer, Cotter Pin, Spring,
Shaft, Screen, Travel Stop, Screen Cap, Bolt, Gasket
and Lock Washer Steel: Body (Type C486), Cap Screw and
Operating Lever
Plated steel: Nut, Washer, Bonnet Nut, Guide Bracket
and Cap Screw Polyurethane (PU): Rod Wiper Polytetrauoroethylene (PTFE): Bushing, Packing
Adaptor and Packing Ring Nitrile (NBR) (Standard Construction): Main Disc,
Bleed Disc and O-ring Other Disc Material Available from Factory: PTFE,
Fluorocarbon (FKM), Neoprene (CR), Ethylene- Propylene (EPDM) and Kalrez®
1. The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.
2. Product has passed Fisher® testing for leakage down to -40ºF / -40ºC.
Principle of Operation
Refer to the schematic drawing, Figure 2. In view #1, the valve is held closed by both tank pressure and the valve’s closing spring. There is no leakage past the resilient seats in the poppet to the valve outlet.
The valve is opened by moving the operating lever to
approximately mid-point in its 70° travel (view #2). This
allows the cam to place the rapid equalization portion of the valve stem in the pilot opening, permitting a larger amount of product to bleed downstream than if the operating lever were moved to the full open position.
When tank and downstream pressure are nearly equal
after a few seconds, the excess ow spring pushes open
the main poppet (view #3) and the operating lever can be moved to the full open position.
If tank pressure is greater than the valve’s outlet pressure, the main poppet will remain in the closed position. If valve outlet piping is closed off by other valves, however, product bleeding through the pilot will increase until it nearly equals tank pressure and the main poppet opens.
Kalrez® is a mark owned by E.I. du Pont de Nemours and Co.
The main poppet will not open if valve outlet piping is not closed off so that the outlet pressure can approach tank pressure.
Once the main poppet opens, a flow greater than the valve’s excess flow spring rating or a sufficient surge in flow forces the main poppet closed against the excess flow spring (view #4). The pilot valve allows a small amount of product to bleed, but much less than view #2 where the rapid equalization portion of the stem is placed in the pilot opening. When the operating lever is moved to the closed position, the valve closes completely and seals tightly (view #1).
Installation
Mounting and Piping
The internal valves can be installed in either a half or full
coupling. Excess ow spring closing ow rates vary in half and full couplings, refer to the Specication section.
Note
2
Types C471, C477 and C486
M1170
JET
BLEED
1 2 3 4
VALVE CLOSED
LIMITED BLEED
VALVE OPEN FLOW
JET BLEED EQUALIZATION
JET BLEED OPEN VALVE OPEN EXCESS FLOW VALVE
JET BLEED
Figure 2. Operational Schematic
CAUTION
Excess ow valve closing ow rates are not
the same for half and full couplings. Verify
the coupling for the desired excess ow rate.
Do not install the valve in any piping tending to restrict the valve inlet because this may
prevent the excess ow valve from closing.
Do not install the valve with such extreme torque that the coupling can cut threads into the valve. This could cause valve distortion and affect the internal working parts.
Do not use PTFE tape as it may cause thread galling to occur.
Use an appropriate pipe compound, on the male threads of the internal valve and pipeline. Pull the valve into the coupling hand tight and then wrench tighten it for approximately two additional turns. Larger size valves may require an additional amount of torque to obtain a leak-free connection.
Keep piping from the valve outlet to the pump full size and as short as possible with a minimum number of bends. Reduction in pipe size to suit smaller pump inlets should be made as close to the pump as possible using forged reducers (swage nipples) or venturi tapers rather than bushings. This assures minimum flow resistance and efficient pump operation.
FLOW
FLOW
LIMITED
BLEED
CLOSED
LIMITED BLEED
The valves have a break off section below the inlet pipe thread which is intended to permit the lower valve body to shear off in an accident, leaving the valve seat in the tank. The break off section is designed for container
installations and will probably not provide shear protection if the valve is installed in a pipeline.
A hydrostatic relief valve does not need to be installed adjacent to the valve since the internal valve relieves excessive line pressure into the tank.
Selectively Filling Manifolded Tanks
Fisher® internal valves provide positive shutoff only in one direction, from out of the tank to downstream of the valve. The
internal valves are designed to allow gas to ow into a tank
when the downstream line pressure exceeds tank pressure. If
you want to selectively ll one or more of the other tanks in a
tank manifold system, you must place a positive shutoff valve downstream of the internal valve, otherwise, all tanks will be
lled at the same time and at about the same rate.
Actuators
The remote operating control system for the valve is extremely important and it must be installed to conform with the applicable codes. DOT MC331, for example, most generally applies for trucks.
Fisher offers both cable controls and pneumatic actuator systems to operate the C470 and C486 Series internal
3
Types C471, C477 and C486
valves. It may also be possible to use cable controls from other manufacturers or to fabricate a linkage mechanism.
Any control system requires thermal protection (fuse links) at the valve, at the remote control point and, if necessary, near the hose connections. The Instruction Manuals for Emerson™ actuator systems show how to install the fuse links.
Installation instructions on Fisher® Types P650, P163A and
P164A cable controls, are in Document D450012T012.
Pneumatic actuator installation is covered in Document
D450162T012. Type P340 latch/remote release instructions are on Document D450123T012.
The operating linkage must allow the operating lever to
move from the fully closed position to within 2° of the fully
open position. The linkage should not apply strong force to the lever past the fully open position or the valve could be damaged.
Warranty Note
The use of non-Fisher actuators will void internal valve warranty and may result in leakage of the gland packing caused by premature wear. In addition to premature wear, the use of non- Fisher actuators may
result in lower than expected ow rates and
possible leakage across the valve seats.
CAUTION
The internal valve’s closing spring is not designed to overcome drag in the control linkage in order to close the valve. Depending upon the control system used, an external spring (such as Fisher drawing number 1K4434) or positive closing linkage may be needed. Be sure the control system is installed to prevent binding that could cause the valve to stick in the open position.
Excess Flow Operation
The internal valve contains an excess ow function or “integral excess ow valve”, that will close when the ow exceeds the ow rating established by Fisher. Fisher integral excess ow valve installed on a bobtail truck or transport
can provide protection against the discharge of hazardous materials during an unloading operation of a bobtail truck or transport in the event that a pump or piping attached directly
to the internal valve is sheared off before the rst valve, pump or tting downstream of the internal valve, provided that the cargo tank pressure produces a ow rate greater than the valve’s excess ow rating.
Likewise, if the internal valve is installed on a stationary tank or in the related downstream piping system, the
integral excess ow valve can provide protection against an
unintentional release of hazardous materials in the event
that a pump or piping attached directly to the internal valve is
sheared off before the rst valve, pump or tting downstream of the internal valve, provided that the ow of product through
the internal valve reaches the rated ow specied by Fisher.
EXPLOSION HAZARD
!
Restrictions incorporated in the discharge system of a bobtail truck or transport or of a stationary tank (due to pumps, pipe and hose length and dimensions, branching, elbows, reductions in pipe diameter or a
number of other in-line valves or ttings),
low operating pressure as a result of ambient temperature or a partially closed valve downstream from the integral excess
ow valve, can restrict the rate of ow
through the internal valve below the level necessary to actuate the integral excess
ow valve. Therefore, DO NOT USE the excess ow function of the internal valve for
the purpose of providing protection against the discharge of hazardous materials in the event of a rupture of hose or piping at a point in the discharge system downstream
from the rst valve, pump or tting
downstream of the internal valve.
The internal valve is designed with an internal bleed feature for equalization of
pressure. After the integral excess ow valve
closes, the leakage through the bleed must be controlled or a hazard can be created. For this reason the operator must be familiar with the closure controls for the internal valve and must close the internal valve immediately
after the integral excess ow valve closes.
Failure to follow this warning could result in serious personal injury or property damage
from a re or explosion.
DOT Passive Shutdown Equipment Requirement—DOT
regulations 49CFR§173.315(n)(2) require certain cargo
tanks transporting propane, anhydrous ammonia and
other liqueed compressed gases to be equipped with
passive emergency discharge control equipment that will
automatically shutoff the ow of product without human
intervention within 20 seconds of an unintentional release caused by complete separation of a delivery hose. The design
for each passive shutdown system must be certied by a Design
Certifying Engineer (DCE) and all components of the discharge system that are integral to the design must be included in the
DCE certication. The DCE certication must consider any specications of the original component manufacturer.
In the case of downstream ruptures in hose or piping, a variety of operating conditions routinely encountered during
an unloading operation restrict the rate of ow through the integral excess ow valve and make such a valve unsuitable
to serve as the means of passive shutdown required under
49CFR§173.315(n) (2). Such variables include restrictions
4
Types C471, C477 and C486
incorporated in the discharge system (due to pumps, pipe and hose length and dimensions, branching, elbows, reductions in pipe diameter or a number of other in-line
valves or ttings), low operating pressure as a result of
ambient temperature or a partially closed valve downstream
from the excess ow valve. Due to the variety of conditions,
in the case of a hose separation, that can restrict the rate of
ow below the level necessary to activate the excess ow valve, the integral excess ow function of Fisher® “C” Series internal valves or “F” Series excess ow valves cannot be
used to satisfy the passive shutdown equipment requirement
under/in 49CFR§173.315(n)(2). Also, a Design Certifying Engineer cannot include the integral excess ow valve of a Fisher “C” Series internal valve or “F” Series excess ow
valve as a component of the discharge system in any DCE
certication under 49CFR§173.315(n)(2).
EXPLOSION HAZARD
!
DO NOT USE the excess ow function incorporated into Fisher “C” Series internal
valves or “F” Series excess ow valves to
satisfy the passive shutdown equipment requirement in 49CFR§173.315(n)(2). DO NOT
include the excess ow function incorporated
into Fisher “C” Series internal valves or
“F” Series excess ow valves in a DCE certication under 49CFR§173.315(n)(2). The
cargo tank manufacturer must install some
other equipment that satises the requirement
for passive shutdown capability under 49CFR§173.315(n)(2).
Failure to follow this warning could result in serious personal injury or property damage
from a re or explosion in the event of an
unintentional release of product during an unloading operation.
Operation
Since the C470 and C486 Series will not open unless the downstream pressure can build-up to equal the inlet pressure, an operating sequence that assures equalization is important.
Follow these points:
1. C470 and C486 Series on bobtails and transports should never be open when the truck is in motion. If the control system is not interlocked to prevent this, the operator is responsible to see that the valves are closed.
2. Always open the internal valve before opening any other valves in the line or starting the pump.
3. Move the lever to the half-open position (Operational Schematic, view #2) to equalize pressure. When the main poppet clicks open, move the operating lever fully open.
4. Open other line valves slowly to avoid sudden surges which could slug the excess flow valve shut.
5. If the excess flow valve does close, stop the
pump and close the nearest downstream valve. Move the internal valve’s operating lever back to the rapid equalizing position and wait for the valve to click open. Then move the operating lever fully open and slowly open the downstream valve.
6. All valves should be completely open when pumping. (Throttling type valves could prevent the excess flow valve from closing when required.)
7. The operator must always be aware of where the remote closure controls are located and know how to operate the controls if an emergency requires valve closure. When pumping is finished, make a habit of closing the internal valve from the remote closure point, thus checking to see that the control actually is capable of closing the valve.
8. The valve should be open when backfilling through the valve to fill the tank.
Troubleshooting
Internal Valve Will Not Open—This could be due to leakage
downstream, engaging the pump too soon or from excessive wear in the internal valve. If excessive volume is in the downstream system, a longer time is required to equalize the pressures (tank and downstream) before the pump can be engaged. To determine if the valve pilot seat is opening, install a gauge downstream of the valve, operate the valve actuator; if pressure does not build up to the tank pressure, the valve pilot seat is not open. This test should be done with pump off. If the pilot is not opening, it may be plugged with dirt or some internal part may be broken. If by operating the lever manually it can be rotated past the fully open position, there is something wrong internally and the valve must be disassembled.
Premature Valve Closure—This can be caused from engaging
the pump too soon, by an underrated excess ow valve spring
or by an improperly connected internal valve operating lever which does not fully open the valve. The trouble could also be from a valve that has its inlet port obstructed or from sudden line surges. In order to check the valve opening travel, operate the lever manually to the full travel, wait until valve opens,
then engage the pump. If the excess ow closes, the points
mentioned above should be investigated.
Internal Valve Will Not Close—The stub shaft could be binding or the stem could be bent in the valve. Before disassembling the valve, check the actuator mechanism to see that it operates freely by disconnecting it from the valve lever and cycling it several times. Also, operate the valve lever manually. If it sticks in the open position, the packing and bushings should be replaced. This should free the operating mechanism if the valve has not been damaged internally. Refer
to the “Maintenance” section.
Low Flow Capacity—This could be caused by too small an internal valve, too small or long downstream piping, plugged screens, some other restriction in the downstream system or by the bypass valve sticking in the open position. The bypass valve could also be set too low and be opening prematurely.
5
Types C471, C477 and C486
the internal valve. If piping is cold allow it to warm to ambient temperature.
b. Refer to CFR 49 Section 180 Appendix B for Meter
Creep Test Methods.
3. All operating controls should be inspected and cleaned
and oiled. The controls should be checked to see that they fully open—but not over-travel—the internal valve operating lever and operate freely to close the valve.
4. Standard construction internal valves must
be removed if the container is to be steam cleaned. Heat can damage the valve’s seats and seals.
5. Standard construction internal valves are not designed
for water service. Immediately after a container is hydrostatically tested, remove all water and allow the container to thoroughly dry out.
Disassembly
Figure 3. Use Tool Provided or Spring Seat (key 4) and Stem
Assembly (key 2) to Align Disc Retainer (key 8)
Maintenance
CAUTION
Do not use these internal valves if they leak, fail to work properly or have been damaged or have missing parts. Prompt repairs should be made by a properly trained service person. Continued use without repair can create a hazardous or injurious situation.
A simple preventative maintenance program for the valve and its controls will eliminate a lot of potential problems.
Fisher® recommends these steps be conducted once a month. Also refer to the Department of Transportation (DOT) CFR 49 Sections 180.416 and 180 Appendix A and B which specify monthly maintenance and inspections tests for cargo tank service internal valves and their actuation controls.
1. Inspect the operating lever to see that it operates freely and that there is no leakage around the retainer nut. If there is sticking or leakage, replace the packing and bushings. Refer to Replacing Packing.
2. Check for tight closure of the seat discs. Any detected
leakage, which is normally caused by disc wear or dirt, scale or debris embedded in the disc, requires that the internal valve be removed from service and repaired. Repair most often requires the replacement of valve discs. To check for leakage:
a. Close the internal valve and exhaust downstream
pressure. Close the rst valve downstream from the
internal valve and note any pressure buildup, using a pressure gauge, between the closed valve and
WARNING
!
Tank pressure must be released before removing the valve from the container. Failure to do so could result in personal injury.
Numbers in parenthesis refer to key numbers in Figures 3 to 7.
To Replace Packing or Install Gland Hardware
WARNING
!
Downstream pressure must be released before removing the screws holding the gland assembly to the internal valve body. Failure to do so could result in personal injury.
1. The packing (keys 15F, G and H) can be replaced with product in the tank by closing the operating lever (key 18) and blowing down the downstream pressure in the system.
2. If using Screw-Type hardware, remove the three cap screws (key 17) holding the bonnet assembly to the body. If using the current Stud-Type hardware, remove the
nuts (key 59) and washers (key 55) holding the bonnet
assembly to the body.
Note
If working on a valve equipped with a pneumatic actuator, please refer to the corresponding actuator Instruction Manual for proper removal procedures.
3. Rotate the entire bonnet assembly slightly to remove it from the body.
4. Unscrew the cap screw (key 15R) from the stub shaft
(key 15J) and remove the operating lever by taking out
the cotter pin (key 19).
6
17
55
Types C471, C477 and C486
A
CAM PROFILE UP
A
BACK VIEW WITHOUT
BOLT AND WASHER
T11555
T11545
T11546
T11547
C
*45°
CAM PROFILE POINTED LEFT
T11549 MULTI-PURPOSE PTFE LUBRICANT
T11550 MULTI-PURPOSE PTFE LUBRICANT
1H9416 MULTI-PURPOSE PTFE LUBRICANT
GLAND WING
* DRILLED PIN HOLE MUST BE 45° TO CL OF CAM
T11551
T11552
T20431
HOLE B ORIENTATION NE TO SW
T11559 LEVER
GLAND WING
1B8480
1C2256
T20380
T11548
TORQUE: 90 to 100 inch-lbs /
10 to 11 N•m
T11548
SECTION A-A
(WITHOUT LEVER)
T11553
T20431
B
58
59
55
TORQUE: 90 to 100 inch-lbs /
10 to 11 N•m
SCREW-TYPE HARDWARE
STUD-TYPE HARDWARE
Figure 4. Stub Shaft Orientation
7
Types C471, C477 and C486
5. Unscrew the retaining nut (key 15M) from the bonnet. Pushing on the stub shaft (key 15J) will expose the bonnet
parts including the packing.
6. Besides the packing, the liner bushings (keys 15B and 15K) should be replaced. Lubricate the packings with Multi­purpose PTFE lubricant.
7. Reassemble in reverse order. Replace cap screw (key 15R)
using 30 to 35 inch-pounds / 3.4 to 4.0 N•m torque.
8. Before replacing the gland assembly, replace the O-ring (key 16) with the proper material matching the main seals. The standard Types C471 and C477 material is Nitrile (NBR).
9. Orient Cam and stub shaft (See Figure 4)
Before reassembling the gland assembly into the body,
make sure the operating lever can move freely with the new parts installed. Then, correctly orient the cam to the stub shaft. Incorrect orientation will result in either:
a. Not being able to open the internal valve or
b. Only being able to partially open the internal valve
which will cause the valve’s excess ow feature to
close prematurely
Refer to Figure 4. Looking at the end of the stub shaft (C)
that the lever or actuator attaches to:
1. The cam prole on the opposite end of the shaft should
be up and the cam pointing to the left.
2. The hole (B) through the stub shaft that the lever/
actuator attaches to should be oriented in a NE to SW position with N being at the top.
3. The 2 gland wings should be at the top as shown
in Figure 4.
4. The lever should be oriented as shown and the cotter pin
run through hole (B).
4. Unscrew the screws (keys 9 and 4 for 2-inch / DN 50,
6 for 3-inch / DN 80) holding the disc retainer (key 8) to replace the main seat disc.
5. Examine both seat discs (keys 7 and 11) and replace if necessary.
6. If the excess ow spring (key 3) is changed, replace the
nameplate or stamp the body with the new type number.
7. Always replace the sealing washer (key 23).
8. a. Reassemble in reverse order. Tighten the screws
(key 9) using 20 inch-pounds / 2.2 N•m torque to
install the disc retainer (key 8) properly.
CAUTION
Failure to properly center the disc retainer to the disc holder may result in improper function of the valve.
Important
During replacement of the seat disc, use P/N GE45079X012 provided to center the disc retainer to the disc holder (See Figure 3). Line up holes and insert screws. Keep the alignment tool inserted until all of the screws
are tightened to specication.
Alternately, the stem assembly (key 2) and spring seat (key 4) may be used as shown in Figure 3 to perform this alignment. After assembly, check to make sure there is no interference of the spring seat and disc retainer
when the valve is in the excess ow position.
b. Apply Medium-Strength Threadlocker on the stem
threads before installing the hex nut (key 13).
10. Once proper orientation of the cam is conrmed:
a. Reinstall the washers (key 55) and nuts (key 59) and
torque to 90 to 100 inch-lbs / 10 to 11 N•m. Reinstall
actuator or latch if applicable.
b. If reusing the cap screws, reinstall the actuator or latch if
applicable before installing the cap screws and washers.
Torque to 90 to 100 inch-lbs / 10 to 11 N•m.
c. If installing new studs, install the long studs (key 57) in
the top-most hole locations and the short stud (key 58) in
the bottom-most location. Secure the gland to the body
with the rst set of washers (key 12) and nuts. Reinstall
actuator or latch if applicable or cover two long studs with protective cap (key 60) if available.
To Replace Seat Discs
1. Remove the valve from the tank.
2. Remove the cotter pin (key 14, Figure 5) and unscrew
the hex nut (key 13).
3. Remove both disc holders (keys 6 and 12) from the stem (key 2).
8
Parts Ordering
Important
Use only genuine Fisher® replacement parts. Components that are not supplied by Emerson™ should not, under any circumstances, be used in any Fisher valve, because they will void your warranty, might adversely affect the performance of the valve and could give rise to personal injury and property damage.
When corresponding about this equipment, always reference the equipment type number found on the nameplate.
When ordering replacement parts, reference the complete 11-character part number for each needed part.
Types C471, C477 and C486
TORQUE: 50 to 75 inch-lbs /
5.6 to 8.5 N•m
13
14
1
L
57
55
59
60
B
15P
22
A
6
3
15R
15S
15J
4
36
2
5
33
TORQUE: 50 to 75 inch-lbs /
5.6 to 8.5 N•m
13
19
57
L
55
59
60
B
A
C
SECTION A - A
STEM
7
8
9
35
34
58
TORQUE:
59
90 to 100 inch-lbs /
55
10 to 11 N•m
18
L
15F
L
15G
L
15H
15E
15M
15L
SECTION B - B
GLAND
APPLY LUBRICANT L = MULTI-PURPOSE PTFE LUBRICANT
1. Lubricants must be selected such that they meet the temperature requirements.
(1)
Figure 5. Type C477 Assemblies
15A
15B
15C
15D
16
15E
15K
10
11
12
23
SECTION C
9
Types C471, C477 and C486
Parts List
Types C471, C477 and C486 Internal Valves
Key Description Part Number
Repair Kit
2 inch NPT / DN 50 RC47016T012
3 inch NPT / DN 80 RC47024T012
1 Body Type C471, Ductile Iron
2 inch / DN 50 T40195T0012
3 inch / DN 80 T80119T0012 Type C477, Ductile Iron
2 inch / DN 50 T40132T0012
3 inch / DN 80 T80089T0012 Type C486
3-inch / DN 80 Flange by FNPT ERAA00979A0 2 Stem Assembly
†2-inch / DN 50, Steel/Stainless steel GE41520T012 *3-inch / DN 80, Steel GE41522T012
2A Stem
2-inch / DN 50, Steel/Stainless steel GE35309T012 3-inch / DN 80, Steel GE35311T012
2B Follower Assembly, Steel/Stainless steel T11880000A2
2C Groove Pin, Steel/Stainless steel IJ1560T0012
3 Excess Flow Spring, Stainless steel
2 inch / DN 50 105 GPM / 397 L/min, Green GE42498X012 150 GPM / 567 L/min, Yellow T1153537022 250 GPM / 946 L/min, Pink T1200537022
3 inch / DN 80
160 GPM / 605 L/min, Blue GE42499X012 265 GPM / 1003 L/min, Black GE42500X012 375 GPM / 1419 L/min, Yellow GE42851X012 460 GPM / 1741 L/min, Red GE42501X012
4 Spring Seat, Stainless steel
2 inch / DN 50 GE35317T012 3 inch / DN 80 GE35318T012 5 Closing Spring, Stainless steel T1153737022
6 Disc Holder, Stainless steel
2 inch / DN 50 GE35315T012 3 inch / DN 80 GE35316T012
7 Main Disc 2 inch / DN 50
Nitrile (NBR) T1154003202
PTFE T1214006242
Fluorocarbon (FKM) T12533T0012
Neoprene (CR) T12879T0012 Kalrez® T12877T0012 Ethylene Propylene (EPDM) T13474T0012 *3 inch / DN 80 Neoprene (CR) T12914T0012 Nitrile (NBR) T1177403032 PTFE T1217306242
Fluorocarbon (FKM) T12535T0012
Kalrez® T12921T0012 Ethylene Propylene (EPDM) T13476T0012 8 Disc Retainer
2-inch / DN 50, Steel/Stainless steel GE35313T012 3-inch / DN 80, Steel GE35314T012
9 Screw
2-inch / DN 50, Steel/Stainless steel (4 required) 13B3513X022 3-inch / DN 80, Steel (6 required) 13B3513X022 10 Bleed Disc seat, Steel/Stainless steel ERAA00325A0
11* Bleed Disc Nitrile (NBR) ERAA00328A0 PTFE ERAA00328A1 Fluorocarbon (FKM) ERAA00328A2 Kalrez® ERAA00328A3 Neoprene (CR) ERAA00328A4 Ethylene Propylene (EPDM) ERAA02202A0
Key Description Part Number
12 Bleed Disc Retainer, Stainless steel ERAA00324A0 13* Hex Nut, Plated steel GE04678T012 14* Cotter Pin, Stainless steel T1241338992
15 Gland Assembly, Nitrile (NBR) 2 inch / DN 50 T20377000B2
3 inch / DN 80 T20430000B2
15A Gland
Steel T2038022012
Stainless steel T2052033092 15B†*Liner Bushing, PTFE T1154506992 15C*Washer Steel T1154625072
Stainless steel T1220236152 15D Spring, Stainless steel T1154737022 15E*Washer (2 required) Steel T1154825072 Stainless steel T1220336152 15F*Male Packing Adaptor, PTFE T1154901012 15G†*Packing, PTFE (3 required) T1155001012
15H*Female Packing Adaptor, PTFE 1H941601012 15J Stub Shaft 2-inch / DN 50, Stainless steel T2037835072 3-inch / DN 80, Stainless steel T2043135072 15K†*Liner Bushing, PTFE T1155106992 15L†*Rod Wiper, Polyurethane (PU) T1155206992 15M Bonnet Nut, Steel T1155324102 15P Cam Steel T1155521992 Stainless steel T1220535072 15R Cap Screw Steel 1B848024052
Stainless steel T12206T0022
15S Washer Steel 1C225628982 Stainless steel T1220736152
16* O-ring
Nitrile (NBR) T1155706562 PTFE T1214206522 Fluorocarbon (FKM) T12577T0012
Kalrez® T1214206522
Neoprene (CR) T1214206522
Ethylene Propylene (EPDM) T13477T0012 17 Cap screw, Steel (3 required) T12499T0012
18 Operating Lever, Steel T1155919312
19* Cotter pin, Carbon-plated Steel (not shown) 1H837128982 20 Nameplate (not shown) - - - - - - - - - - ­ 21 Drive Screw, Stainless steel (2 required) (not shown) 1A368228982 22 Pipe plug, Zinc (not shown) T13718T0012 23* Washer Steel T1188228982 Stainless steel T1221006242
30 Fusible Link (not shown) 1J157443992
33 Travel stop, Stainless steel T1240838072
35* Bushing, PTFE T1221306992 36 Guide, Iron
Type C471
2 inch / DN 50 T12918T0012 3 inch / DN 80 T12511T0012
Type C477
2 inch / DN 50 T12918T0022 3 inch / DN 80 T12511T0012 55 Lock washer, Stainless steel (3 required) 1C2257K0012 57 Stud, Long (2 required) ERAA02623A0 58 Stud, Short ERAA02652A0 59 Nut 1A309338992
60 Thread Cap (2 required) (not shown) ERAA02691A0
†Recommended spare part for 2-inch / DN 50 body size.
*Recommended spare part for 3-inch / DN 80 body size. Kalrez® is a mark owned by E.I. du Pont de Nemours and Co.
10
Types C471, C477 and C486
TORQUE: 50 to 75 inch-lbs /
5.6 to 8.5 N•m
1
14
A
13
C
L
15P
6
3
57
55
59
60
A
19
57
L
55
59
60
BB
4
36
2
5
33
7
8
9
35
34
58
TORQUE:
59
90 to 100 inch-lbs /
55
10 to 11 N•m
18
SECTION A - A
STEM
TORQUE: 50 to 75 inch-lbs /
5.6 to 8.5 N•m
15R
22
L
15F
L
15G
L
15H
15E
15M
15L
15S
15J
15A
15B
15C
15D
16
15E
15K
SECTION B - B
13
10
11
12
23
SECTION C
GLAND
PARTS NOT SHOWN: 20 AND 21
APPLY LUBRICANT L = MULTI-PURPOSE PTFE LUBRICANT
1. Lubricants must be selected such that they meet the temperature requirements.
(1)
Figure 6. Type C471 Assemblies
11
A
Types C471, C477 and C486
14
1
TORQUE: 90 to 100 inch-lbs /
10 to 11 N•m
59
19
55 57
15P
B
A
22
L
15F
L
15G
L
15H
15E
15M
15L
15K
15R
15S
15J
15A
15C
15E
B
15B
15D
16
SECTION B - B SECTION C
PARTS NOT SHOWN: 20 AND 21
APPLY LUBRICANT L = MULTI-PURPOSE PTFE LUBRICANT
1. Lubricants must be selected such that they meet the temperature requirements.
(1)
Figure 7. Type C486 Assemblies
TORQUE:
50 to 75 inch-lbs /
5.6 to 8.5 N•m
13
6
3
9
36
35
34
33
5
2
TORQUE: 50 to 75 inch-lbs /
5.6 to 8.5 N•m
13
10
11
SEE DETAIL C
SECTION A - A
7
8
4
58
59
TORQUE: 90 to 100 inch-lbs /
55
10 to 11 N•m
18
12
23
LP-Gas Equipment
Emerson Process Management Regulator Technologies, Inc.
USA - Headquarters McKinney, Texas 75070, USA Tel: +1 800 558 5853 Outside U.S.: +1 972 548 3574
For further information visit www.fisherregulators.com
The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher® is a mark owned by Fisher Controls International LLC, a business of Emerson Process Management.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or
guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specications of such
products at any time without notice.
Emerson Process Management Regulator Technologies, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson Process Management Regulator Technologies, Inc. product remains solely with the purchaser.
©Emerson Process Management Regulator Technologies, Inc. 2002, 2014; All Rights Reserved
Loading...