Installation and Maintenance Manual For IntelliGear Plus™ MD and BW1/BW2 Variable Speed Drives
Emerson Industrial Automation
7120 New Bufngton Road
Florence, KY 41042
Application Engineering: 800 626 2093
www.emerson-ept.com
F O R M
9178E
Revised
April 2012
®
c
UL Listed E211799 Ind. Cont EQ. 54 DN
UL is believed to be a registered trade name and/or trademark of Underwriters Laboratories, Inc. and is NOT owned or controlled by Emerson Power Transmission.
Emerson Power Transmission Corporation cannot and does not represent or warrant the accuracy of this information.
Emerson, Emerson Industrial Automation, Intelligear and Intelligear Plus & Design are trademarks of Emerson Electric Co. or one of its affiliated companies. ©2004, 2008, 2012 Emerson Power Transmission Corp., All Rights Reserved.
MCIM12003E • 9178E • Printed in USA
ce
us
IntelliGear Plus Variable Speed MD Gearmotors
Thank you for choosing an IntelliGear Plus Gearmotor.
General Safety Instructions
• Read and follow all instructions carefully.
• Disconnect and lock-out power before installation and maintenance. Working on or
near energized equipment can result in severe injury or death.
• Disconnect power at least 2 minutes prior to servicing to allow capacitors to discharge. Handling wires sooner than this could result in electric shock, severe injury, or death.
• Do not operate equipment without guards in place. Exposed equipment can result in severe injury or death.
• Any eyebolts that have been supplied with the breakmotor or gearmotor are designed for lifting only these components. Lifting additional weight attached to theses components may break the eyebolt and result in personal injury or death, and product damage.
• All electrical work should be performed by qualified personnel and compliant with local and national electrical codes.
• Periodic inspections should be performed. Failure to perform proper maintenance can result in premature product failure and personal injury.
• IntelliGear Plus contains parts sensitive to static electricity. Care should be taken to discharge static prior to handling these components to avoid damage to them.
• Contact Emerson Power Transmission for recommendations for units running at slow speeds or unusual conditions.
2
IntelliGear Plus Variable Speed MD Gearmotors
Contents
1 General Information ................................................................................................................................4
1.1 General operating principle .......................................................................................................................4
1.2 Product name ............................................................................................................................................4
1.3 Environmental characteristics ...................................................................................................................4
1.4 Radio-frequency interference ....................................................................................................................5
1.4.1 General .....................................................................................................................................................5
1.4.2 Standards (Emissions) ..............................................................................................................................5
1.4.3 Standards (Immunity) ................................................................................................................................5
1.5 Description of cables and protection devices (Customer Supplied) ..........................................................5
1.6 UL conformity ............................................................................................................................................5
1.6.1 Specified mains supply .............................................................................................................................5
1.6.2 Cables .......................................................................................................................................................5
1.6.3 Fuses ........................................................................................................................................................5
1.8 Dimensions ............................................................................................................................................6-7
2 Installation ...............................................................................................................................................8
2.1 General .....................................................................................................................................................8
3 Connections ............................................................................................................................................8
3.1 Control T erminal Blocks ............................................................................................................................8
3.2 Power terminal blocks ...............................................................................................................................8
3.3 Wiring diagram based on standard configuration .....................................................................................9
3.4 Terminal Block Assignments and MD Functionality ................................................................................10
4 Commissioning .....................................................................................................................................10
5 Faults - Diagnostics ..............................................................................................................................11
5.1 Troubleshooting Guide ............................................................................................................................11
6 Gear Lubrication ...................................................................................................................................12
7 Gear Parts List ......................................................................................................................................13
8 Motor Parts List .....................................................................................................................................14
3
IntelliGear Plus Variable Speed MD Gearmotors
General Information
1 - General Information
1.1 - General operating principle
The IntelliGear Plus is a combination of a 3-phase induction motor and an integrated open loop vector variable speed drive. The motor can be combined with many gear types from Emerson Power Transmission’s range.
In the standard product version, the integrated drive does not require any connection other than the power supply. The options may be used to broaden the application range of the IntelliGear Plus.
IntelliGear Plus motors meet the requirements of the Low Voltage Directive 73/23/EEC, modified by 93/68/EEC. The harmonized standards of the DIN VDE 0160 series in connection with standard VDE 0660, part 500 and EN 60146/VDE 0558 are also applicable.
1.2 - Product name 115V Single Phase Power Supply 230V Single Phase Power Supply
Rating Power (HP) Rating Power (HP)
310 M 050 0.50 31 M 050 0.50
32 M 075 0.75 31 M 075 0.75
Designation Description
RP1 4-20 mA follow or local Start/Stop/10 Turn Potentiometer
Designation Description
KEYPAD LCD Parameter setting console w/cable to locally reprogram to customize parameters
VMA30SOFT CD w/cable and USB to locally reprogram to customize parameters
1.3 - Environmental Characteristics
Characteristics Level - IntelliGear PLUS Degree of protection TEFC V ersion TEFC motor and NEMA 4/12 Controller Storage temperature -40
Transport temperature -40 oC to +70 oC
Ambient operating temperature -20
Altitude Up to 3000 feet above sea level without derating
Ambient humidity 95% non-condensing
Humidity during storage 93%, 40
Vibration
Shocks
IntelliGear PLUS Controlling Options
IntelliGear PLUS Accessories
o
C to +70 oC
o
C to +40 oC (above 40 oC requires derating 1% per oC
o
C, 4 days
Immunity Conforming to EN61000-6-2
Radiated and conducted
Conforming to EN500081-2 with internal filters
emissions
UL (USA) Conforming to UL 508 C (E211799)
CUL (CANADA)
4
IntelliGear Plus Variable Speed MD Gearmotors
1.4 - Radio-frequency interference:
1.4.1 - General
V ariable speed drives use high-speed s witches (transistors , semi-conductors) which switch high voltages (around 660V for 3-phase drives) at high frequencies (several kHz). This provides better efficiency and a low level of motor noise. As a result, they generate radio-frequency signals which may disturb operation of other equipment or distort measurements taken by sensors:
•duetohigh frequency leakage currentswhichescape
to ground via the stray capacity of the drive/motor cable and that of the motor via the metal structures which support the motor
•byconductionorfeedbackofR.F.signalsonthepower
supply cable; conducted emissions
•bydirectradiationneartothemainsupplypowercable
or the drive/motor cable: radiated emissions
1.5 - Description of cables and protection devices (Customer Supplied) NOTICE: When using a circuit-breaker, it must be a motor circuit-breaker (D curve).
• Complywiththesizeofprotectionfuses.
• Thecablesizemayvaryaccordingtolegislationapplicableinthecountry,whichwilltakeprecedenceoverthevalues
given in the table below without exception.
These phenomena are of direct interest to the user. The frequency range concerned (radio-frequency) does not affect the energy distribution company.
1.4.2 - Standards (Emission)
The maximum emission level is set by (EN 50081-2) and (EN 50081-1). IntelliGear Plus conforms to:
•EN50081-2asstandard
•EN50081-1withlteroption
1.4.3 - Standards (Immunity)
The maximum immunity level is set by (EN 50082-2) and (EN 50082-1). IntelliGear Plus conforms to:
•EN50082-2andEN50082-1asstandard
Motor 115V Single Phase Power Supply 230V Single Phase Power Supply
HP Rating
0.50 I 310M 050 5 14AWG 10 A I 31M 050 2.5 14AWG 8A
0.75 I 32M 075 8.5 14AWG 14A I 31M 075 4 14AWG 8A
1.6 - UL conformity
1.6.1 Special mains supply
The drive can be incorporated in an installation with short circuit capacity of 5000 A rms maximum at voltage 264 VAC rms maximum for 230 V (TL) drives or 528 VAC rms maximum for 400 V (T) drives.
1.6.2 Cables
Only class 1 copper cables 60/70° C (140/167° F) should be used.
1.6.3 Fuses
UL conformity is adhered to if the fuses are UL-listed, fast-blow fuses (class CC up to 30 A) with a rating as indicated in the above table and if the short-circuit symmetrical current does not exceed 5 kA.
IntelliGear
Plus Number
Input Amps Wire Gauge Fuse Size IntelliGear
Plus Number
Input Amps Wire Gauge Fuse Size
5
1.8 - Dimensions
8.52
5.90
IntelliGear Plus Variable Speed MD Gearmotors
11.23
3.50
1.40
5.50
.39
.12
Ø 3.94
Ø 4.72
Ø 3.1500
3.1493
Ø .280 HOLES
4 @ 90º AS SHOWN
6.30
Ø .344 + .007 / -.002 HOLES
CCI 109-G
CCI NUMBER
5.00
CATALOG NUMBER
CBN3001BSCB524.556 CCI 109
6
IntelliGear Plus Variable Speed MD Gearmotors
CATALOG NUMBER CCI NUMBER
SEEPEXBW2+TS1LS80B14 CCI0109G
7
IntelliGear Plus Variable Speed MD Gearmotors
2 - Installation
After connection, ensure that the seals are firmly in place, and that the screws and cable glands are watertight to ensure drive protection. Clear any condensation from the drain holes at the bottom of the motor.
2.1 - General
The IntelliGear Plus is usually fitted to the gear and mounted to the machine with flange or foot mounting. The motor fan cools the whole assembly. Make sure that the ventilation air inlet is free of obstruction. The positions of the potentiometer/cable gland supports are specified at the time of ordering. However they may be reversed if
necessary.
3 - Connections
Connection with copper conductor only.
3.1 - Control Terminal Blocks
• Remove the terminal block from it’s fixed holder (unplugged) before making any connections , to avoid putting pressure on the card.
CAUTION: The IntelliGear Plus has a positive logic configuration. Using a drive with a control system which has a different control logic may cause unw anted starting of the motor.
• The control circuits in the driv e are isolated from the power circuits by single insulation (IEC 664-1).
• The installer must ensure that the external control circuits are isolated against any human contact.
• If the control circuits need to be connected to circuits conforming to SELV safety requirements, additional insulation must be inserted to maintain the SELV classification.
Removable screws in terminal block:
• Tightening torque = 2.62 in. lbs.
• Maximum cross section = 17 AWG
3.2 Power terminal blocks
3.2.1 Terminal block for power supply PB1 (marked L&N)
This terminal block is used to connect the 3 phase power supply when the RFI filter is not used in an IntelliGear Plus. Otherwise, the RFI filter output is screwed onto this connector and the power supply should be attached to the terminals located on top of the filter. (See table below)
Screw terminal blocks Frame 310M
Tightening Torque 7.1 in. lbs.
Max. cross-section AWG 14
Numbered Controller
Terminal Blocks
8
Terminal Block
for Power Supply
IntelliGear Plus Variable Speed MD Gearmotors
3.3 Wiring diagram based on standard configuration
NOTE:
IF AUTO MODE RUN/STOP CONTACT IS NOT USED, 4-20mA INPUT
CONNECTOR PINS 5 & 6 MUST BE JUMPERED TO RUN IN AUTO
MODE.
User supplied male Turck connectors can be secured locally using the
following information -
4 pin connector with 4 meter cable attached = Turck # SB4T - 4
5 pin connector with 4 meter cable attached = Turck # SB5T - 4
6 pin connector with 4 meter cable attached = Turck # SB6T - 4
9
IntelliGear Plus Variable Speed MD Gearmotors
3.4 Terminal block assignments and MD functionality
Controller Terminal Number Designation Function Characteristics
1 10V +10V analog internal source Accuracy ± 2%
Maximum output current 30 mA Voltage input
2 ADI1 Hand Mode Speed Reference Full scale voltage 10 V ± 2%
** Input Impedance 95 kΩ
3 0V Logic circuit common 0V
Current input Current range 0 to 20 mA ± 5%
4 ADI2 Auto Mode Speed Reference Input impedance 500 Ω
Resolution 10 bits Sampling 6 ms
Logic input (if connected to the +24 V
6 ADIO3 Fault Signal Input Threshholds “0”:<5V-”1”; >10V
From Pump Operation Voltage range 0 to +24V
Run Dry and/or High Pressure Load 95 kΩ
Input threshold 7.5V Characteristics Digital output 1
7 DIO1 Alarm LED Threshholds “0”:<5V-”1”; >10V
Voltage range 0 to +24V
Sampling/refreshment 2 ms
5 Output current 10 mA in total
Overload current 33 = 150mA, 31/32 = 50mA
24V +24V internal source Accuracy ± 5%
11 Protection Current limiting and overload
fault trip
Logic input 2 Characteristics Logic input (positive logic)
8 DI2 Run/Stop Threshold “0”:<5V-”1”; >10V
Voltage range 0 to +24V
Logic input 3
9 DI3 Absolute maximum voltage 0 to +35V
10 DI4 Input threshold 7.5V
12 ENA Enable Impedance 820 Ω 13 RL1 Drive Healthy Contact 14 RL2 4 A, resistive load
** Performs scaling function when drive is programmed for full PI mode of operation
Motor Thermal Input
Logic input 4
Hand Mode Selectior
N/C after start-up if OK
Sampling/refreshment 2 ms
range Load 15 kΩ
Voltage range 9 to + 35V
Characteristics
250VAC maximum contact
current
NO single pole contact
2 A inductive load
4. Commissioning
WARNING! Before switching on the IntelliGear Plus unit, check that the electrical
connections are correct, and that any moving parts are mechanically guarded. WARNING! F or the saf ety of personnel, the IntelliGear Plus must not be s witched on
with any protective covering removed.
10
IntelliGear Plus Variable Speed MD Gearmotors
5. Faults - Diagnostics
Information relating to the status of the IntelliGear Plus is provided by an indicator lamp (see photo bottom right) on the control and by the internal LED in 310M.
seepex Inc. Tel +1(937)864-7150 Fax +1(937)864-7157 sales@seepex.net
CAUTION :RISK OF ELECTRIC SHOCK
DESCONECTAR EL APPARATO
Y ESPERAR AL MENOS
2 MINUTOS ANTES
DE INTERVENIR
RED
ROJO
ROUGE
DISCONNECT POWER AT LEAST 2 MINUTES
BEFORE MAKING
ADJUSTMENTS
POTENTIAL FAULT
Falla potencial / Defaut potentiel
PUMP
Bomba
Pompe
OVER TEMP
Temperatura excesiva
Température élevée
LOW FLOW
Bajo flujo Débit bas
HIGH PRESURE
Alta presión
Haute pression
METTRE L’APPAREIL HORS
TENSION ET ATTENDRE 2 MINUTES AU MOINS AVANT
TOUTE INTERVENTION
DRIVE & POWER
Impulsion & Potencia
Entrainement & puissance
OVER/UNDER VOLTAGE
Alto/Bajo Voltage
sur/sous tention
WINDING FAILURE
falla en el bobinado
Défaut d’enroulement
DRIVE FAILURE
Falla en el impulsor
Défaut d’uentrainement
5. 1 MD Gearmotor Troubleshooting Guide
Symptom Probable Cause(s) Actions Required
Not running in AUTO or HAND mode-
Alarm Light not lit
Not running in AUTO mode - HOA switch not in “AUTO” position Put HOA switch in “AUTO” position Alarm light not lit Pins “5” and “6” of the six pin Turck
Unit runs at only Low Speed in AUTO mode
Unit in AUTO mode will not achieve
high RPM output at 20 mA
Power to drive is not on Check power supply and cord HOA switch is in “OFF” position Move switch to HAND or AUTO
• Connect Auto Mode Run/Stop contact to
connector are not “connected”
pins “5”and “6” of six pin Turck connector.
• Make sure Auto Mode Run/Stop contact is
closed.
• Jumper pins “5” and “6” if Auto Mode Run/ Stop contact is not being utilized
4-20 mA signal is not present at drive Check incoming 4-20 mA signal 4-20 mA to drive installed in reverse into pins
Reverse 4-20 mA connection polarity
“1” and “2” of six pin Turck connector
4-20 mA signal does not achieve full scale Check incoming 4-20 mA signal Signal to drive is not reaching full 20 mA Repair signal
Red LED “Alarm” light is on ­Unit has stopped
Potentiometer is not in “10” position Turn potentiometer to “10” position Refer to “badge” below and on top of unit
for mechanical/pump and electrical/ motor causes
Check these causes to determine the
root cause for fault. Once cleared, un­plug and re-install main power plug with
power source
11
IntelliGear Plus Variable Speed MD Gearmotors
6 - Gear Lubrication
Series 3000 CbN gearing is shipped with one of the following synthetic lubricants per the table below. The gear reducer has been filled to accommodate any mounting position. In the case of synthetic oil, the lubricant does not require changing, but it is recommended that proper oil level be checked periodically.
Synthetic
No Backstop
Manufacturer
®
Fuchs
®
Mobil
®
Shell
-25˚ F to 125˚ F
(-30˚ C to 50˚ C)
Sintogear® 125
SHC 629
Omala® Fluids HD 150
With Backstop
Manufacturer
Shell Omala RL 100
Acceptable Mineral Oil Lubricants
Ambient Range of Installation
-4
˚ F to 14˚ F
(-20˚C to 10˚C)
ISO VG 68 ISO VG 100 ISO VG 150 ISO VG 220 ISO VG 150 ISO VG 320
14˚F to 122˚F (-10˚C to 50˚C)
No Backstop With Backstop
122˚F and Above
(50 ˚C+)
Input Opening
Primary
Gear
-25˚ F to 125˚ F
(-30˚ C to 50˚ C)
Orient the gear head vertically and fill to mid-point of the Pri­mary Gear
Fuchs is a registered trademark of Fuchs Petrolub; Shell is a registered trademark of Shell Petroleum Incorporated. Omala is a registered trademark of Shell Trademark Management.
12
Diagram for
Size 30
Oil Level
052
097
255
001
282
284
062
080
031
077
061
130
090
009
187
257
256
258
128
042
7.0 - Gear Parts List CBN 3001
IntelliGear Plus Variable Speed MD Gearmotors
Rep Description Quantity
001 Housing 1 009 Output flang ring 1 031 Output shaft 1 042 Pinion 1 052 Gear 1 061 Bearing front 1 062 Bearing back 1 077 Output shaft key 1 080 Gear Key 1
* Not illustrated on diagram
Typical Maintenance Items - Bearings and Seals
Gear
Frame
Item Description By Location
Bearings Seal (mm)
61 62 90
30 6205 ZZ 6005 25 x 52 x 7 DL nitrile
Rep Description Quantity
090 Oil seal 1 097 Input o-ring 1 127 Gearing snap ring* 1 130 Gearing snap ring 1 175 Input bracket screw 4 185 Washer for gear* 1 186 Screw washer* 1 187 Bolt 4 282 Nameplate 1
13
IntelliGear Plus Variable Speed MD Gearmotors
3
2
1
5
6
4
9
8
10
11
183
184
254
7
CbN 30 (Quantity Per Unit)
Rep Description Quantity
1 Motor adapter 1 2 Input shaft 1 3 Pinion 1 4 Internal snap ring 1 6 Bearing 1 8 External snap ring 1 9 Seal 1
10 Pinion pin 1 183 Stud 4 184 Nut 4
Gear
Frame
Bearing Seal (mm)
6 9
30 6005 2RS 47 x 25 x 7
Part # Description Qty.
FRAME 56
1 Fan Cover 1 2 Self T apping Screw 3 3 Hex Nut 1 5 Retaining Snap Ring 1 6 Fan 1 7 Bracket 1 8 Screw 4
9 Bushing 4 10 Plastic Plug 4 11 Ball Bearing 1 12 Rotor Assembly (includes items 13 & 14) 1 13 Shaft 1 14 Rotor Core 1 15 Wound Stator Assembly 1 16 Gasket 1 17 Outlet Box Base 1 18 Self Tapping Screw 2 19 Outlet Box Cover 1 20 Self Tapping Screw 2
14
Notes
15
Emerson, Emerson Industrial Automation, Intelligear and Intelligear Plus & Design are trademarks of Emerson Electric Co. or one of its affiliated companies. ©2004, 2008, 2012 Emerson Power Transmission Corp., All Rights Reserved.
MCIM12003E • 9178E • Printed in USA