Special Features
60-480 Watts
ADN Series
Electrical Specs
• Power Factor Correction
• Auto Select 115/230 VAC, 50/60 Hz Input
• All Single Phase models meet SEMI F47
Sag Immunity
• Class 1, Div 2 Hazardous Locations
• DC OK Signal
• Adjusable Voltage
• Industrial grade design (no derating to 60°C)
• User-friendly front panel
• Single and three phase inputs available
• Highly efficent >90% switching technology
• High MTBF and reliability
• Peak current capability 2x rated current
for 2 seconds
• Three year warranty
• NEC Class 2 on models <100W
Input
Nominal voltage 115/230 VAC auto select
Power factor (PFC) EN61000-3-2
AC Input range 85-123 / 176-264VAC
DC Input range 210-375VDC
Frequency 47-63 Hz, 500 Hz
Output
Nominal voltage 24V (22.5-28.5VDC Adj.)
Holdup time > 20ms at full load (25°C)
Tolerance < ±2 % overall
(combination line/load/time/temp)
Tolerance < ±2 % overall
Line regulation <0.5%
Load regulation <0.5%
Time & temp. drift <1%
Initial voltage setting 24.5V ± 1%
Ripple < 50mVpp
Power back immunity > 35V
Parallel Operation
ADN20-24-1PM Switch selectable
All others Jumper selectable via front panel
Over voltage protection < 33VDC
Storage/Shipment -25°C to +85°C
Operating (convection) -10° C to +60° C (derate
to 50% at +70° C)
Humidity <90% RH noncondensing per
IEC 68-2-2, 68-2-3
IP20 (EN60529), protection
from moisture & condensation
EMC
Emissions EN 61000-6-3, Class B EN55011, EN55022 Radiated
Conducted including Annex A
Immunity EN 61000-6-2, EN61000-4-2 Level 4, EN61000-4-3
Level 3, EN61000-4-6 Level 3, EN61000-4-4 Level 4
input and level 3 output. EN61000-4-5 Isolation class
4, EN61000-4-11, Transient protection according to
VDE 0160/W2 over entire load range.
Approvals EN60950, UL508 Listed, cULus, UL 60950, cURus, CE
(LVD 73/23 & 93/68/EEC), (EMC 89/336 & 93/68/EEC).
EN61000-3-2, EN60079-15 (Class 1, Division 2
hazardous location, Groups A, B, C, D w/ T3 temp
class up to 60°C Ambient.) SEMIF47 Sag Immunity.
For models <100W, UL60950 testing to include
approval as NEC Class 2 power supply acc. To NFPA 70
art. 725-41 (a)(2).
Protection Class 1 (IEC536), degree of protection
SELV rated per EN60950
Environmental
Safety
Total Power: 60 - 480 Watts
Input Voltage: 115/230 VAC
# of Outputs: One