Emerson Active Tracking User Manual

Liebert
®
Interceptor®Active Tracking®Filter Series
The Ultimate Solution To Power Disturbance Problems
AC Power Systems f
or Business-Critical Continuity
When You Require The Ultimate In Surge Protection
In today's world, almost every business depends on sensitive microprocessor-based electronics to conduct their day to day operations. This means that electric power line disturbances can disrupt or cripple equipment causing a major loss in productivity — and money. Liebert understands this problem and offers a way to keep these power problems from getting into your facility in the first place.
The answer is the Liebert Interceptor®Series Active Tracking provide the highest level of protection with the lowest UL 1449 clamping ratings available.
the sinewave, our Active Tracking filter technology protects sensitive electronic equipment from the potentially damaging effects of low-energy voltage transients and the ringwaves that follow. The filter also stores and releases energy to fill and reduce sinewave spikes and notches.
Pr
Interceptor's sophisticated parallel system of computer­m modul exact current sharing and prevent component degr Lis yet allow surge current capability to be attenuated.
1449, UL 1283 and C facility is ISO 9001 Registered. Surge current ratings are inde pr Liebert Interceptor Series filter with the industry's only fi
®
Filter. These series-connected systems
By closely controlling voltage at every location along
en Performance
v
o
y current diversion is handled by the
g
r
ne
-e
gh
Hi
tched MOV (metal-oxide varistor) arrays. Each array
a
sulated and screened to provide
p
a
nc
e is sand
dation. Our patented, coordinated fusing is UL
a
or 200kAIC a
ed f
t
The In
-e
C to ensure absolute safety,
A
t 600V
terceptor Series Active Tracking Filter is UL
. Our manufacturing
ed
t
A Lis
S
pendently tested, so you can specify a Liebert
ete confidence. And we back every
pl
om
t with c
oduc
ve-year warranty for on-site labor.
Features That Make The Difference
The Industry's Best Attenuation Of Voltage
Transients Proprietary Active Tracking sinewave correction filter continuously provides close voltage control at any location on the sinewave.
The Industry's Best Attenuation Of 100 kHz Ringwaves
The Active Tracking filter system minimizes the aftershocks of voltage transients and the inherent energy storage system smoothes the sinewave by filling notches and reducing spikes.
Stringent, Independent Testing For Performance
UL 1449, UL 1283 and CSA Listed.
ANSI/IEEE C62.11, C62.41, C62.45 Categories A, B,
and C3 tested.
Independently tested surge current ratings from 100kAmps
to 300kAmps.
Life cycle tested: will survive in excess of 12,000 10kAmp
surges per IEEE Category C3.
Engineered For Superior Surge Current Ratings And Long Life
Computerized "smart" array technology for surge protection.
Unique sand-packed silver fuse network allows rated surge
current to pass through without fuse operation.
Unprecedented redundancy offers expanded mean-time-
between-failure (MTBF).
wave tracking EMI/RFI filtering.
Sine
Fast response time — less than .5 nanoseconds.
All modes of protection.
Compatible With All Linear Loads
vides flexibility for a wide range of applications.
o
Pr
Modular Design For Ease Of Customization And Service
Enables you to specify an Interceptor system to match the
needs of a specific application. Also allows easy replacement
of surge modules if required.
Sophisticated User-Friendly Diagnostics
On-line system monitoring/testing for all suppression
components in all modes of protection.
Standard features include: audible alarm, transient
r, door LEDs indicating unit status, individual
e
t
un
o
c
module status LEDs, and Form C dry contacts for
remote system integrity monitoring and indication
f undervoltage, phase and/or power loss.
o
Optional features include: additional seven-digit transient
counter for normal mode, additional Form C dry contacts.
ed To The Most Stringent ISO Quality Standards
tur
c
a
f
u
an
M
ISO 9001 registration for design, manufacturing and service.
cated Service Network Protects You Too
i
ed
A D
icated service network with over 400 Liebert-trained
ed
D
and authorized technicians.
Toll-free service hotline manned 24 x 7.
2
Specifications
A
D
F
E
B
- Diameter
C
- Optional Features
2.0” MAX
- Standard Features .50” MAX
onnection Type Series connected
C
gency Listings UL 1449, UL 1283, CSA
A
otection Modes All modes standard (Line to Neutral,
Pr
EMI/RFI Filtering Normal mode — 60 dB maximum from
Response Time less than .5 nanoseconds Load Regulation 1% no load to full load Enclosure NEMA 12 standard; options include
o Ground, Neutral to Ground,
Line t
o Line); any combination optional
Line t
10 kHz to 500 MHz; Common mode 50 dB maximum from 10 kHz to 500 MHz
NEMA 3R, 4, 4X and caseless for switchgear applications
requency 47 to 63 Hz
Line F
oltage ±15% nominal
Line V
emperature -40 to +60°C
T
perating Humidity 0 to 95% noncondensing
O
ude 0 to 18,000 feet
Altit Audible Noise Less than 45 dBa Operational Crest Factor 3.0 Warranty 10-Years Parts and
5-Years On-Site Labor
How To Specify The Appropriate Model:
Go to Chart A
1)
2) Follow column two across to column three to determine your Model Number.
3) Refer to se the first three digits of the Voltage Code for split phase and three phase configurations).
(U
4) Finally, to complete your model number, go to the last column or (Monitoring Options) and choose the suffix for Standard Features (-06) or
Optional Features (-03).
hoose your Current Rating from column one and corresponding Configuration from column two.
, c
Chart B to determine the Voltage Code from the available choices. Substitute the Voltage Code for “XXX.”
Chart A - Active Tracking®Filter Systems
Current Model Number Surge Current Capability Dimensions
Rating Configuration (xxx=voltage code) per phase (L-N or L-L+L-G) (inches) Weight
A BCDE FLbs. 30A Single Phase L-L FXXXL30 100kA 24.0 20.0 9.0 21.25 10.0 .44 40 30A Single Phase L-N FXXXN30 100kA 24.0 20.0 9.0 21.25 10.0 .44 35 30A Split Phase FXXXS30 100kA 24.0 20.0 9.0 25.25 14.0 .44 45 30A Three Phase Delta FXXXD30 100kA 24.0 20.0 9.0 25.25 14.0 .44 50 30A Three Phase Wye FXXXY30 100kA 24.0 20.0 9.0 25.25 14.0 .44 60 60A Single Phase L-L FXXXL60 100kA 24.0 20.0 9.0 21.25 10.0 .44 40 60A Single Phase L-N FXXXN60 100kA 24.0 20.0 9.0 21.25 10.0 .44 35 60A Split Phase FXXXS60 100kA 24.0 20.0 9.0 25.25 14.0 .44 45 60A Three Phase Delta FXXXD60 100kA 24.0 20.0 9.0 25.25 14.0 .44 50 60A Three Phase Wye FXXXY60 100kA 24.0 20.0 9.0 25.25 14.0 .44 60
100A Single Phase L-L FXXXL100 150kA 30.0 24.0 9.0 31.25 18.0 .44 65 100A Single Phase L-N FXXXN100 150kA 30.0 24.0 9.0 31.25 18.0 .44 60 100A Split Phase FXXXS100 150kA 30.0 24.0 9.0 31.25 18.0 .44 70 100A 100A 125A Single Phase L-L FXXXL225 150kA 30.0 24.0 9.0 31.25 18.0 .44 65 125A Single Phase L-N FXXXN225 150kA 30.0 24.0 9.0 31.25 18.0 .44 60 225A Split Phase FXXXS225 150kA 30.0 24.0 9.0 31.25 18.0 .44 70 225A Three Phase Delta FXXXD225 150kA 30.0 24.0 9.0 31.25 18.0 .44 70 225A Three Phase Wye FXXXY225 150kA 30.0 24.0 9.0 31.25 18.0 .44 80 400A 400A 800A Three Phase Delta FXXXD800 choose 200 or 300 kA 60.0 48.0 12.0 - - - 500
800A 1200A Three Phase Delta FXXXD1200 choose 200 or 300 kA 60.0 48.0 20.0 - - - 700 1200A Three Phase Wye FXXXY1200 choose 200 or 300 kA 60.0 48.0 20.0 - - - 750 2000A 2000A Three Phase Wye FXXXY2000 choose 200 or 300 kA 60.0 48.0 20.0 - - - 950 4000A Three Phase Delta FXXXD4000 choose 200 or 300 kA 60.0 48.0 20.0 - - - 1175 4000A
t B - N
ar
h
C
(substitute for “xxx” to complete model number) Single Phase, 2 wire plus ground 100, 110, 120, 230, 240, 277, 346, 400, 480, 600 Split Single Phase, 3 wire plus ground 100/173, 110/190, 120/208 or 240, 230/400, 277/480, 346/600 Three Phase Delta, 3 wire plus ground 208, 240, 380, 400, 480, 600 Three Phase Delta Hi-Leg, 4 wire plus ground 120/240
hase Wye, 3 or 4 wire plus ground
ee P
Thr
ase Delta FXXXD100 150kA 30.0 24.0 9.0 31.25 18.0 .44 70
h
ee P
Thr
Thr
ee Phase Wye FXXXY100 150kA 30.0 24.0 9.0 31.25 18.0 .44 80
se Delta FXXXD400 150kA 48.0 36.0 12.0 49.25 30.0 .44 275
a
h
ee P
Thr
hase Wye FXXXY400 150kA 48.0 36.0 12.0 49.25 30.0 .44 300
ee P
Thr
FXXXY800 choose 200 or 300 kA 60.0 48.0 12.0 - - - 530
e
y
e W
s
a
h
ee P
Thr
Three Phase Delta FXXXD2000 choose 200 or 300 kA 60.0 48.0 20.0 - - - 875
se Wye FXXXY4000 choose 200 or 300 kA 60.0 48.0 20.0 - - - 1300
a
h
ee P
Thr
minal Voltage Codes
o
100/173, 110/190, 120/208, 230/400, *277/480, 346/600
Standard Features Include:
•Audible Alarm, Transient Counter
• Door LEDs indicating unit status
• Individual Module Status LEDs, and -06 Form C Dry Contacts for Remote System Integrity Monitoring and Indication of Under Voltage, Phase and/or Power Loss.
Optional Features Include:
ditional Seven-
d
• A Digit Transient Counter for Normal Mode -03
• Additional Form C Dr
y C
ontacts
S: For configurations not
TE
O
N mentioned, including caseless units for switchgear applications and ungrounded delta units, consult factory. For different levels of surge current capacity mode and/or phase, consult factory.
CODE: L - N = Line t L - G = Line t N - G = Neutral to Ground L - L = Line to Line
*Valid for 220/380 and 240/415 per IEC.
am
Ex
Monitoring
Options
utral
e
o N
und
o
o Gr
l Numbe
ode
e M
pl
F120Y30-03
:
r
3
Ensuring The High Availability Of Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies — including Liebert power and cooling technologies — that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility, and reduced capital equipment and operating costs.
Liebert Corporation
1050 Dearborn Drive P.O. Box 29186 Columbus, Ohio 43229 800 877 9222 Phone (U.S. & Canada Only) 614 888 0246 P 614 841 6022 FAX
Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy 39 049 9719 111 Phone 39 049 5841 257 FAX
Emerson Network Power Asia Pacific 7/F., Dah Sing Financial Centre 108 Gloucester Rd, Wanchai Hong Kong 852 25722201 Phone 852 28029250 FAX
hone (Outside U.S.)
liebert.com
Technical Support
607 724 2484 Phone 800 288 6169 Toll-Free 607 722 8713 Fax
e every precaution has been taken to ensure accuracy and
l
Whi completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting
om use of this information or for any errors or omissions.
r
f
© 2005 Liebert Corporation. All rights reserved throughout the w
All names referred to are trademarks or registered trademarks of their respective owners.
® Liebert and the Liebert logo are registered trademarks
f the Li
o
SL-22006 (R9/05) Printed in USA
ifications subject to change without notice.
pec
. S
ld
or
ebert Corporation.
Emerson Network Power.
The global leader in enabling business-critical continuity.
AC Power Systems
onnectivity
C DC Power Systems
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2005 Emerson Electric Co.
Embedded Power
bound Power
In Integrated Cabinet Solutions
Outside Plant
ecision Cooling
Pr Site Monitoring and Services
rsonNetworkPower.com
e
Em
Loading...