Emerson 2100, 2100E Instruction Manual

Page 1
www.Fisher.com
D200119X012
Type 2100 Pneumatic and Type 2100E Electric Liquid Level Switches
Contents
Introduction 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scope of Manual 1. . . . . . . . . . . . . . . . . . . . . . . . .
Specifications 3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Educational Services 3. . . . . . . . . . . . . . . . . . . . . .
Installation
3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Procedures 3. . . . . . . . . . . . . . . . . . . .
Common Procedures for Either Switch 4. . . . .
Additional Procedures for Type
2100 Switch 4. . . . . . . . . . . . . . . . . . . . . . . . . .
Additional Procedures for Type
2100E Switch 5. . . . . . . . . . . . . . . . . . . . . . . . .
Calibration Check 5. . . . . . . . . . . . . . . . . . . . . . . . .
Principle of Operation 5
. . . . . . . . . . . . . . . . . . . . . . .
Maintenance 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operational Test 8. . . . . . . . . . . . . . . . . . . . . . . . . .
Type 2100 Switch Maintenance Procedure 8. . . Type 2100E Switch Maintenance Procedure 10
Parts Ordering 11
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts Kits 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts List 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Type 2100E Electrical Switch Component
Hazardous Area Classification information 15.
CSA 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FM 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ATEX 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UL 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction
Scope of Manual
This instruction manual includes installation, maintenance, and parts information for the Type 2100 pneumatic and Type 2100E electric liquid level switches. Refer to separate instruction manuals when you require information regarding related valves, actuators, positioners, and accessories.
APPROXIMATE SWITCHING POINT
W6102-1*/IL
Figure 1. Type 2100 Pneumatic Liquid Level Switch
APPROXIMATE SWITCHING POINT
W6103-1*/IL
Figure 2. Type 2100E Electric Liquid Level Switch
Instruction Manual
Form 5039 December 2005
2100 and 2100E Liquid Level Switches
Page 2
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039
December 2005
2
Table 1. Specifications
Input Signal
(1)
Liquid level
Minimum Process Liquid Specific Gravity
0.5 (consult your Emerson Process Managementt sales office for specific gravity below this value)
Output Signal
(1)
Type 2100 Switch: Output equal to supply
pressure when the switch is in the normal position (flapper against nozzle). Output reduced to approximately atmospheric pressure, depending upon size of the bleed orifice and piping configuration, when the switch is activated
Type 2100E Switch: Same as supply signal
Supply Signal
Type 2100 Switch: J 2.1 to 4.1 bar (30 to 60
psig), J 4.1 to 6.9 bar (60 to 100 psig), or J 6.9 to 10.3 bar (100 to 150 psig)
Type 2100E Switch: 11 amperes, 1/4
horsepower at 125/250 volts ac; 5 amperes resistive, 3 amperes inductive at 28 volts dc
Supply Medium (Type 2100 Switch)
Air or natural gas
(4)
Steady-State Air Consumption
(1,2)
(Type 2100
Switch)
Less than 0.03 normal m
3
/hr (1.0 scfh) for all supply pressures when the liquid level is 25.4 mm (1 inch) below the normal switch position (flapper against nozzle) for high-level switching or
25.4 mm (1 inch) above the normal switch position for low-level switching
Maximum Working Pressure
J 2220 WOG
(3)
except J 350 WOG is the maximum working pressure for sight window construction
Operative Temperature Range
(1)
Type 2100 Switch: 29 to 204_C (20 to
400_F)
Type 2100E Switch: 29 to 82_C (20 to
180_F)
Displacer Diameter
102 mm (4 inches)
Process Connection Size
2220 WOG
(3)
: J 1-inch NPT female,
J 50.8 mm (2-inch) Schedule 80 buttwelding ends, or J 50.8 mm (2-inch) Schedule 160 buttwelding ends
Type 2100 Switch Supply Pressure Connection Size
1/4-inch NPT female
Type 2100E Switch Electrical Connection Size
1/2-inch NPT male
Hazardous Area Classification
The Type 2100 and 2100E switches have no hazardous area approvals.
Approvals on the electrical switch component in the Type 2100E, supplied by ITT NEO-DYN are as follows:
APPROVED
EXP Class I Division 1 Groups A,B,C,D DI Class II Division I Groups E,F,G
Class I Groups A,B,C,D Class II Groups E,F, G
UL
Class I Groups A,B,C,D Class II Groups E,F, G
ATEX
EEx d IIC
Refer to figures 7, 8, 9, and 10 for specific hazardous classification information. Contact your Emerson Process Management sales office if additional information is required.
Shipping Weights
2220 WOG
(3)
Construction: 17.2 kg (38 pounds)
1. These terms are defined in ISA Standard S51.1.
2. Normal m
3
/hr—normal cubic meters per hour (0_C and 1.01325 bar, absolute); scfh—standard cubic feet per hour (60_F and 14.7 psia)
3. Water, Oil, Gas maximum working pressure rating designation in psi. Corresponds to Cold Working Pressure: the maximum pressure rating allowed under normal ambient temperature conditions, which are usually understood to be − 29_C to 38_ C (− 20_F to 100_F). Refer to MSS SP-25.
4. Natural gas to contain no more than 20 ppm of H
2
S.
Page 3
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039 December 2005
3
No person may install, operate or maintain a Type 2100 pneumatic or a Type 2100E electric liquid level switch without first D being fully trained and qualified in valve, actuator and accessory installation, operation and maintenance, and D carefully reading and understanding the contents of this manual. If you have any questions about these instructions, contact your Emerson Process Management sales office.
Description
The on-off Type 2100 pneumatic switch (figure 1) and the Type 2100E electric switch (figure 2) operate shutdown valves or alarm systems when liquid in a vessel reaches a predetermined level. The Type 2100 switch uses an externally mounted displacer that operates a nozzle-flapper to vent the supply pressure when the switch is activated. The nozzle-flapper has a soft seat for tight shutoff when the switch is in its normal position (flapper against the nozzle). The Type 2100E switch uses the displacer torque to activate and deactivate an electric switch for positive on-off service. The displacer on each type can withstand up to 1-1/2 times the maximum working pressure, allowing it to remain in the cage during hydrostatic testing.
Unless otherwise noted, all NACE references are to NACE MR01752002.
Specifications
Specifications for the Type 2100 and 2100E switches are shown in table 1.
WARNING
This product is intended for a specific current range, temperature range and other application specifications. Applying different current, temperature and other service conditions could result in malfunction of the product, property damage or personal injury.
Educational Services
For information on available courses for Type 2100 pneumatic and Type 2100E electric liquid level switches, as well as a variety of other products, contact:
Emerson Process Management Educational Services, Registration P.O. Box 190; 301 S. 1st Ave. Marshalltown, IA 501582823 Phone: 8003388158 or Phone: 6417543771 FAX: 6417543431 e-mail: education@emersonprocess.com
Note
Neither EmersonR, Emerson Process Management, Fisher
R
, nor any of their affiliated entities assumes responsibility for the selection, use, and maintenance of any product. Responsibility for the selection, use, and maintenance of any product remains with the purchaser and end-user.
Installation
Installation Procedures
The installation procedures include those common to both the Type 2100 pneumatic and Type 2100E electric liquid level switches and additional ones for each switch.
WARNING
Always wear protective clothing, gloves, and eyewear when performing any installation operations to avoid personal injury.
Check with your process or safety engineer for any additional measures that must be taken to protect against process media.
If installing into an existing application, also refer to the WARNING at the beginning of the Maintenance section in this instruction manual.
Page 4
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039
December 2005
4
A3619-1/IL
1/4-INCH NPT OUTPUT PRESSURE CONNECTION
1/4-INCH NPT SUPPLY PRESSURE CONNECTION
BACK PLATE (KEY 10)
STREET TEE (KEY 34)
BLEED ORIFICE (KEY 35)
Figure 3. Detail of Optional Street Tee and Bleed Orifice
Common Procedures for Either Switch
The horizontal line forged on the displacer cage indicates the approximate switching point (figures 1 and 2). When you mount the Type 2100 or Type 2100E switch, position it so that the horizontal line corresponds to the horizontal level at which switching is desired.
Before you install the Type 2100 or Type 2100E switch, remove the plastic plugs from the process connections. One of these plugs retains a paper tube that protects the displacer and torque tube during handling and shipping. This paper tube must also be removed.
There are two process connections, one at the top and one at the bottom of the cage. To mount the switch, connect the appropriate top and bottom process connections to the vessel using the required size pipe. The pipe must be capable of supporting the assembly and of withstanding the pressure involved. Use accepted piping and welding practices when making connections. Install isolating valves between the vessel and cage. Plugs are furnished for the unused process connections. However, one of the plugs can be removed, and a bleed valve or drain can be installed in one of the unused connections.
Additional Procedures for Type 2100 Switch
If using natural gas as the pneumatic supply medium, natural gas will be used in the pressure connections of the unit to any connected equipment. The unit will vent natural gas into the surrounding atmosphere, unless it is remote vented.
WARNING
Personal injury or property damage may occur from an uncontrolled process if the Type 2100 switch supply medium is not clean, dry air or noncorrosive gas. If clean, dry air, or noncorrosive gas is not used, the switch may become inoperative and allow the level in a process vessel to exceed safe limits. Install a 40 micron filter and suitable equipment to dry the supply medium and establish a maintenance cycle to check the filter and equipment.
If the existing supply medium is corrosive, make sure the tubing and instrument components that contact the corrosive medium are suitable corrosion-resistant materials, or use a noncorrosive medium.
WARNING
Personal injury or property damage may result from fire or explosion if natural gas is used as the supply medium and preventative measures are not taken. Preventative measures may include: Remote venting, re-evaluating the hazardous area classification, ensuring adequate ventilation, and the removal of any nearby ignition sources.
Refer to figure 5 except as noted.
1. Connect a supply pressure line to the 1/4-inch NPT female connection located in the back plate (key 10).
2. Install an output line between the supply pressure line and the equipment to be operated by the switch.
3. Install a street tee and bleed orifice (keys 34 and 35, figure 3) or other fixed restriction in the supply pressure line between the supply source and the output signal line.
4. If a remote vent is required, remove the vent assembly (key 23) from the 1/4-inch NPT female vent connection and install a vent line to an area where the operating medium can be safely exhausted.
Note
The vent line should have as large a diameter as possible with a minimum
Page 5
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039 December 2005
5
number of bends and elbows. The vent line should be as short as possible. Protect the end of the vent pipe from the entrance of rain, snow, insects, or any other foreign material that may plug the vent line. Inspect the vent line opening periodically to ensure that it is not plugged.
If necessary to change to a different supply pressure, install a different nozzle according to steps 1 through 4 and 15 through 18 of the Type 2100 switch maintenance procedure.
To change switch action from low-level to high-level switching or vice versa, reverse the positions of the nozzle, flapper, and magnet according to steps 1 through 7 and 10 through 18 of the Type 2100 switch maintenance procedure.
To change switch mounting from right-hand to left-hand or vice versa, perform steps 1 through 7 and 9 through 18 of the Type 2100 switch maintenance procedure.
Additional Procedures for Type 2100E Switch
Refer to figure 6.
To install for standard action, connect electrical wires as shown in table 2.
To change switch action from low-level to high-level switching, or vice versa, perform steps 1 through 4 and 13 through 17 of the Type 2100E maintenance procedure.
To reverse action of the Type 2100E switch, refer to table 2 and reinstall wiring for normally open (NO) switches to normally closed (NC) and vice versa.
To change switch mounting from right-hand to left-hand or vice versa, perform steps found in the Type 2100 switch maintenance procedure.
Calibration Check
For either type of switch, calibration can be checked by varying the level of the process liquid in the cage and observing the switch operation.
If the process connection directly on top of the cage is not piped to the tank, close the isolating valves
Table 2. Type 2100E Wiring Codes
Wire
Color
SPDT DPDT Switch 1 DPDT Switch 2
Red
Brown
Blue
Green
Black Yellow Purple
Normally Closed
Common
Normally Open
Ground
Normally Closed Common Normally Open Ground
Ground Normally Closed Common Normally Open
and fill the cage with process liquid through the top connection. Verify that the switch operates as the cage is being filled. Repeat the calibration procedure if necessary.
Calibration can also be checked on the work bench. Connect a flexible hose from one of the bottom process connections to the bottom of a bucket. The top process connection should be open. Fill the bucket with process liquid. As the bucket is raised or lowered, the liquid level in the displacer cage rises or falls. Verify that the switch operates as the level is varied. Repeat the calibration procedure if necessary.
Dry calibration can be performed on the Type 2100E using the following procedure:
Refer to figure 6.
1. Position the cage and displacer assembly (key 1) so that the displacer is hanging downward.
2. Level the switch arm (key 40), if required.
3. Loosen the locknut (key 33) and adjust the machine screw (key 31) until it contacts the switch.
4. For low-level dry calibration, tighten the locknut. For high-level dry calibration, turn the machine screw one additional full turn, then tighten the locknut.
Principle of Operation
The Type 2100 switch (figure 4) is an external, cage-mounted, pneumatic liquid level switch. When the switch is in the normal position with the flapper against the nozzle, output pressure cannot bleed off and remains the same as full supply pressure. Rising liquid level exerts a buoyant force on the displacer, producing a torque in the torque tube. When this torque exceeds the torque exerted on the flapper by the magnet, the flapper snaps away from the nozzle. This action allows output pressure to bleed through the nozzle faster than supply pressure can enter through the bleed orifice.
Page 6
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039
December 2005
6
A3619-2/IL
Figure 4. Principle of Operation for High-Level Type 2100 Switch
The reduced pressure in the output signal line activates the shutdown or alarm system. When the liquid level lowers, the falling displacer forces the flapper into the field of the magnet, letting the magnet snap the flapper against the nozzle and causing output pressure to build to full supply pressure.
On applications where low-level switch operation is required, the nozzle, flapper, and magnet are positioned on the opposite side of the torque tube so that downward displacer travel moves the flapper away from the nozzle.
The Type 2100E switch is an external, cage-mounted, electric liquid level switch. Rising liquid level exerts a buoyant force on the torque tube that either activates or deactivates an electrical SPDT (single-pole, double-throw) or DPDT (double-pole, double-throw) switch depending on the required switching action. Falling liquid level deactivates or activates the same switch depending on the required action.
Maintenance
Switch parts are subject to normal wear and must be inspected and replaced when necessary. The frequency of inspection and replacement depends on the severity of service conditions.
Refer to figure 5 for maintenance of the Type 2100 switch and figure 6 for maintenance of the Type 2100E switch.
WARNING
Always wear protective clothing, gloves, and eyewear when performing any maintenance procedures to avoid personal injury.
The displacer is a sealed container inside the cage. A displacer penetrated by process fluid may retain pressure or hazardous fluid for an extended period. Such a displacer may contain pressure as a result of being in a pressurized vessel, or it may contain fluid that becomes pressurized due to changes in temperature and/or it may contain fluid that is hazardous or flammable. The sudden release of pressure, contact with hazardous fluid, fire, or explosion resulting in personal injury can occur if a displacer that is retaining pressure or process fluid is punctured or subjected to heat. Handle the cage (with displacer inside) with care in removing, storing, or disposing, taking into consideration the characteristics of the process fluid.
To avoid personal injury and damage to the process system caused by the sudden release of pressure, contact with hazardous fluid, fire, or explosion, isolate and drain the displacer cage.
Page 7
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039 December 2005
7
Table 3. Type 2100 Troubleshooting Guide
Fault Possible Cause Correction
1. Nozzle-flapper throttles (flapper moves in response to change in liquid level but does not completely cap or uncap nozzle).
1.1 Nozzle adjusted too high. 1.1 If nozzle prevents flapper from coming in full contact with magnet, repeat the Calibration procedure.
Perform the Calibration Check procedure to ensure that the unit operates properly.
1.2 Verify that the top surface of the magnet is parallel with the flapper and that the magnet is in full contact with the flapper when the flapper is against the magnet. If the above conditions do not exist, repeat the Calibration procedure.
Perform the Calibration Check procedure to ensure that the unit operates properly.
2. Nozzle-flapper fails to snap open. 2.1 Liquid level not changing in the expected direction.
2.1 Be certain liquid level in the displacer cage is changing in the expected direction.
3. Nozzle-flapper leaks when shut off. 3.1 Surface of nozzle seat or nozzle worn or damaged.
3.2 Nozzle adjusted too low.
3.3 Incorrect alignment of nozzle and flapper.
3.1 Inspect surface of flapper seat (key 11, figure 5), and nozzle (key 6, figure 5); replace parts if necessary.
3.2 Inspect nozzle-flapper when flapper is being held by magnet. If nozzle is not seated on flapper seat, loosen locknut (key 33, figure
5) and rotate nozzle counterclockwise until it is seated.
3.3 Inspect surface of nozzle seat (key 11, figure 5). This surface should be parallel with the opening in the end of the nozzle (key 6, figure 5). Correct as necessary.
4. Switch fails to activate upon high or low
level depending on action selected.
4.1 Foreign material in cage.
4.2 Clamp and shaft assembly loose on torque tube assembly.
4.3 Torque tube assembly failure.
4.1 Flush cage to remove foreign material.
4.2 Perform step 4 of reassembly procedure in maintenance section. Tighten clamp nut on clamp and shaft assembly to between 20 and 27 NSm (15 and 20 lbSft).
4.3 Perform operational test procedure Replace torque tube assembly if it fails operational test.
For Type 2100, shut off and bleed supply pressure from the switch before attempting any maintenance procedures. For Type 2100E, shut off the power to the electric switch assembly before attempting any maintenance procedures.
Check with your process or safety engineer for any additional measures that must be taken to protect against process media.
The displacer cage should be flushed periodically to remove deposits or sludge that may affect proper operation. The frequency of flushing depends on the
nature of the process liquid. Before flushing, close the isolating valves and drain the cage. Flush from one of the top connections to one of the bottom connections. Also, remove the pipe plug (key 2) or the bushing and sight window (keys 4 and 5), and flush from a top connection through the pipe plug or sight window connection.
Inspect the vent or vent screen (key 23) or vent line periodically to ensure that the vent or vent line is not plugged.
Table 3 lists various Type 2100 switch problems and possible solutions for them. The table is valid for either high-level or low-level switching action and for any supply pressure range. If a correction step requires replacement of worn or damaged parts,
Page 8
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039
December 2005
8
refer to the appropriate maintenance procedure in this manual for disassembly and reassembly instructions.
Type 2100E switch problems are solved through common electrical troubleshooting procedures. Fault 4 of table 3 is also pertinent for the Type 2100E.
Operational Test (Types 2100 and 2100E)
Establish a periodic operational test of the switch to ensure that:
a. the torque tube is functioning as a continuous spring element;
b. there is an absence of excessive friction;
c. there is no contact with the mechanical stops, and;
d. the torque tube is still effectively transmitting force and motion to the Type 2100 flapper and clamp assembly, or to the Type 2100E switch arm assembly.
This test should be conducted with no process fluid in the cage using the following procedures:
1. Make sure the Type 2100 switch flapper and clamp assembly (key 12, figure 5) or the Type 2100E switch arm (key 40, figure 6) is tight on the shaft of the torque tube assembly (key 7).
2. Grasp and lift, then immediately release, the following:
D The Type 2100 switch flapper and clamp
assembly (key 12, figure 5), 10 to 13 mm (0.375 to
0.5 inch) from the nozzle (key 6, figure 5), or
D The Type 2100E switch arm (key 40, figure 6), 10 to 13 mm (0.375 to 0.5 inch) from the contact of the electric switch assembly (key 49, figure 6).
3. The torque tube spring system is functional if the Type 2100 switch flapper and clamp assembly, or the Type 2100E switch arm, bounces at least two cycles in a reversing rotary motion.
Type 2100 Switch Maintenance Procedure
WARNING
Refer to the WARNING at the beginning of the Maintenance section.
WARNING
When disconnecting any of the pneumatic connections, natural gas, if used as the supply medium, will seep from the unit and any connected equipment into the surrounding atmosphere. Personal injury or property damage may result from fire or explosion if preventative measures are not taken, such as adequate ventilation and the removal of any nearby ignition sources.
Refer to figure 5.
1. Drain the liquid from the cage and displacer assembly (key 1), then isolate it from the process. Shut off the supply pressure and bleed any trapped supply and output pressure from the nozzle block assembly (key 8).
2. Loosen the cover screws (key 17) and remove the cover (key 15). Replace the cover gasket (key 16) and the cover screw gaskets (key 20) if necessary.
Note
Magnetic attraction between the magnet (key 14) and the flapper (key
12) can be adversely affected by the presence of foreign material between the magnet and flapper. Before performing any inspection or correction step, inspect the magnet. If necessary, clean the magnet thoroughly. If cleaning requires removing the magnet or magnet bracket (key 13), perform step 17 of the maintenance procedure; then perform the calibration check procedure to ensure that the unit operates properly.
3. Loosen the nut holding the flapper and clamp assembly (key 12) to the shaft of the torque tube assembly (key 7). Remove the flapper and clamp
Page 9
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039 December 2005
9
assembly and, if necessary, replace the flapper seat (key 11) or magnet (key 14). The magnet is attached to the magnet bracket (key 13) with a machine screw (key 27).
4. Loosen the locknut (key 33), remove the nozzle (key 6), and if necessary, replace the nozzle O-ring (key 26). If changing supply pressure is the only other maintenance performed, skip to step 15.
5. Remove the pressure plug (key 9) and, if necessary, replace the pressure plug O-ring (key 24).
6. Unscrew the pipe plug (key 2) or the bushing and sight window assembly (keys 4 and 5). With a 13 mm (0.5 inch) hex nut driver, loosen the locknut on the displacer rod end of the cage and displacer assembly (key 1).
7. Remove the torque tube assembly (key 7) and the bearing (key 32) from the body block (key 3). If necessary, replace the torque tube O-ring (key 25).
8. If it is necessary to replace the nozzle block assembly (key 8) or the nozzle block gasket (key 18), these parts are attached to the back plate (key 10) with cap screws (key 30) and lock washers (key 28).
9. If changing mounting position from right-hand to left-hand or vice versa, remove the cap screws (key 30) and lock washers (key 28) that hold the back plate (key 10) to the body block (key 3). Then rotate the body block 180 degrees on the cage and displacer assembly (key 1). Install a new body block gasket (key 19) if necessary, and secure the back plate (key 10) to the body block with lock washers and cap screws so that the greatest back plate overlap points are toward the bottom cage connection.
10. If changing from low-level to high-level switching or vice versa, remove the machine screws (key 31), flat washers (key 29), and magnet bracket (key 13). Install the magnet bracket on the opposite side of the nozzle block assembly (key 8) and secure it with flat washers and machine screws.
11. Replace the torque tube O-ring (key 25) if necessary. Install the bearing (key 32) and torque tube assembly (key 7) into the body block (key 3), making sure the shaft of the torque tube assembly goes through the hole in the displacer rod end of the cage and displacer assembly (key 1).
12. With a tool inserted through the bottom process connection of the cage and displacer assembly (key 1), move the displacer to its upward travel limit
and then tighten the locknut on the displacer rod end to between 20 and 27 NSm (15 and 20 lbfSft).
13. Install the pipe plug (key 2), or the bushing and sight window assembly (keys 4 and 5), into the body block (key 3). Torque the pipe plug, or the bushing and sight window assembly, to between 68 and 136 NSm (50 and 100 lbfSft).
14. Install the pressure plug (key 9) with the attached O-ring (key 24) into the nozzle block assembly (key 8) on the opposite side from the magnet (key 14) and magnet bracket (key 13).
15. Install a nozzle (key 6) of the correct supply pressure range with attached O-ring (key 26) and locknut (key 33) into the nozzle block assembly (key 8) on the same side as the magnet (key 14) and magnet bracket (key 13).
16. Install the flapper and clamp assembly (key 12) on the shaft of the torque tube assembly (key 7) with the flapper seat (key 11) centered over the nozzle (key 6), with the flapper at a 90-degree angle to the center line of the nozzle, and with the end of the flapper flat and fully on the magnet (key 14).
D For low-level switching, tighten the nut of the
flapper and clamp assembly (key 12) just enough to allow the flapper to rotate on the shaft of the torque tube assembly when light force is applied to the flapper.
D For high-level switching, tighten the nut of
the flapper and clamp assembly (key 12) and the machine screws (key 31) to secure the magnet bracket and magnet (keys 13 and 14).
17. Adjust the nozzle (key 6) and flapper (key 12) as follows:
D For low-level switching, rotate the nozzle
(key 6) counterclockwise (up) until it is in contact with the flapper seat (key 11). Rotate the nozzle an additional 1.5 turns in the counterclockwise direction, and fully tighten the flapper clamp. Rotate the nozzle
1.5 turns clockwise (down). Tighten the locknut (key 33).
D For high-level switching, rotate the nozzle
(key 6) counterclockwise (up) until it is in contact with the flapper seat (key 11). Tighten the locknut (key 33).
18. Install the cover (key 15) with the attached cover gasket (key 16) and secure it with the cover screws (key 17) and attached cover screw gaskets.
Page 10
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039
December 2005
10
Type 2100E Switch Maintenance Procedure
WARNING
Refer to the WARNING at the beginning of the Maintenance section.
Refer to figure 6.
1. Drain the liquid from the cage and displacer assembly (key 1) and isolate it from the process. Shut off the power to the electric switch assembly (key 49).
2. Remove the cover screws (key 44) and the cover (key 39) from the switch housing (key 38). Replace the cover gasket (key 43) if necessary.
3. Loosen the locknut (key 33) on the shaft clamp screw (key 41); then remove the switch arm (key 40) with the attached machine screw (key 31), and locknut (key 33).
4. If changing from high-level to low-level switching or vice versa, from right- to left-hand mounting or vice versa, or a combination of both, loosen the set screws (key 45) and remove the electric switch assembly (key 49) and plastic plug (key 51).
5. Unscrew the pipe plug (key 2) or the bushing and sight window assembly (keys 4 and 5). With a 13 mm (1/2-inch) socket, loosen the locknut on the displacer rod end of the cage and displacer assembly.
6. Remove the torque tube assembly (key 7) and bearing (key 32) from the body block (key 3).
7. For changing from right- to left-hand mounting or vice versa, remove the cap screws (key 30) and lock washers (key 28) that hold the switch housing (key
38) to the body block (key 3).
8. Rotate the body block (key 3) 180 degrees on the cage and displacer assembly (key 1).
9. Install a new body block gasket (key 42), if necessary. Secure the switch housing (key 38) to the body block (key 3), with the switch mounting ports pointing down, using cap screws (key 30) and lock washers (key 28).
10. Replace the torque tube O-ring (key 25) if necessary. Install the bearing (key 32) and torque tube assembly (key 7) into the body block (key 3), making sure the shaft of the torque tube assembly goes through the hole in the displacer rod end of the cage and displacer assembly (key 1).
11. With a tool inserted through the bottom process connection of the cage and displacer assembly (key
1), move the displacer to its upward travel limit and then tighten the locknut on the displacer rod end to between 20 and 27 NSm (15 and 20 lbfSft).
12. Install the pipe plug (key 2), or the bushing and sight window assembly (keys 4 and 5), into the body block (key 3). Torque the pipe plug, or bushing and sight window, to between 68 and 136 NSm (50 and 100 lbfSft).
13. Select a switch mounting port that will provide the desired switching action. Screw the electric switch assembly into the selected port until the switch assembly groove aligns with the threaded hole for the set screw (key 45). Position the electric switch contact directly below the machine screw (key 31). Install and tighten the set screw (key 45) to anchor the electric switch assembly.
14. Insert the cap plug (key 51) in the unused switch mounting port. Install the set screw (key 45) in the mounting port of the switch housing (key 38).
15. Install the switch arm (key 40) on the shaft of the torque tube assembly (key 7) with the head of the shaft clamp screw (key 41) pointing toward the top process connection and the switch arm parallel to the top of the electric switch assembly (key 49). Tighten the locknut (key 33) on the shaft clamp screw to secure the switch arm.
16. Thread the machine screw (key 31) in or out of the switch arm (key 40) until it touches the contact of the electric switch assembly (key 49), then tighten the locknut (key 33).
17. Secure the cover (key 39) to the switch housing (key 38) with the two cover screws (key 44).
Page 11
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039 December 2005
11
Parts Ordering
When corresponding with your Emerson Process Management sales office about this equipment, always mention the unit’s serial number. When ordering replacement parts, refer to the part number of each required part as found in the following parts list.
Note
Use only genuine Fisher replacement parts. Components that are not supplied by Emerson Process Management should not, under any circumstances be used in any Fisher instrument. The use of components not manufacture by Emerson Process Management will void your warranty, might adversely affect the performance of the instrument, and might jeopardize worker and workplace safety.
Note
Neither Emerson, Emerson Process Management, Fisher, nor any of their affiliated entities, assumes responsibility for the selection, use, and maintenance of any product. Responsibility for the selection, use, and maintenance of any product remains with the purchaser and end-user.
Parts Kits
Key Description Part Number
Type 2100 Repair Kit (included are keys
7, 11, 12, 14, 16, 18, 19, 20, 24, 25,
26, and 32) R2100X00012
Type 2100E Retrofit Kit (included are the
switch arm assy and keys 21, 28, 30, 38, 39, 42, 44, 45, 46, 49, 50, and 51)
SPDT Switch R2100EX0SP2 DPDT Switch R2100EX0DP2
Parts List
Key Description Part Number
Type 2100 Switch (figure 5)
1 Cage & Displacer Assembly
To comply with NACE MR0175-2002, heat-treated steel and
stainless steel
w/o sight window
For 2220 WOG max working pressures w/1-inch NPT process connections 32B8089X082 w/2-inch Sch 80 BWE process connection 32B8089X132 w/2-inch Sch 160 BWE process connections 32B8089X182
For other than NACE applications, carbon steel
w/sight window
For 350 WOG max working pressure
w/1-inch NPT process connection 32B8089X042
w/o sight window
For 2220 WOG max working pressures
w/1-inch NPT process connection 32B8089X032
w/2-inch Sch 80 BWE process conns 32B8089X112
w/2-inch Sch 160 BWE process conns 32B8089X172
2 Pipe Plug
(2 req’d w/sight window; 3 req’d w/o
sight window) 1A7947X0162
3 Body Block
To comply with NACE MR0175-2002,
NACE steel 31A8610X022
For other than NACE applications, steel 31A8610X012
4 Bushing (for use only w/sight window), steel 1L5019X0052
5 Sight Window, glass and alloy steel 11A8615X012 6 Nozzle, S30300 (303) stainless steel
2.1 to 4.1 bar (30 to 60 psig) supply pressure 11A8616X012
4.1 to 6.9 bar (60 to 100 psig) supply pressure 1V1545X0012
6.9 to 10.3 bar (100 to 150 psig) supply pressure 11A8617X012
7* Torque Tube Assembly, N04400 26A3197X022 8 Nozzle Block Assembly, aluminum
& stainless steel 11A8626X012
9 Pressure Plug, S30300 (303) stainless steel 11A8628X012 10 Back Plate, steel 21A8629X012 11* Flapper Seat, fluoroelastomer 11A8630X012 12* Flapper and Clamp Assembly, stainless steel 18A5221X012
13 Magnet Bracket, stainless steel 11A8637X012 14* Magnet, sintered
Alnico 12A1578X012
15 Cover, plastic 35A2028X012 16* Cover Gasket, chloroprene 15A2837X012
17 Cover Screw, stainless steel (2 req’d) 15A2029X012 18* Nozzle Block Gasket, silicone rubber 11A8641X012 19* Body Block Gasket, silicone rubber 11A8642X012 20* Cover Screw Gasket, silicone rubber (2 req’d) 11A8643X012
21 Nameplate, aluminum
Right-hand mounting 21A8644X0A2 Left-hand mounting 21B1700X0A2
23 Vent Assembly, plastic 27A5516X012
*Recommended spare parts
Page 12
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039
December 2005
12
51A8650-E/DOC
Figure 5. Type 2100 Switch Assembly Drawing
Key Description Part Number
24* O-Ring, fluoroelastomer 1N463906382 25* O-Ring, fluoroelastomer 1N571406382 26* O-Ring, fluoroelastomer 1V826806382 27 Machine Screw, stainless steel 14B8626X012 28 Lock Washer, stainless steel (4 req’d) 1F128035022
Key Description Part Number
29 Flat Washer, stainless steel (2 req’d) 1P752438982
30 Cap Screw, stainless steel (4 req’d) 1A4078X0052 31 Machine Screw, stainless steel (2 req’d) 19A9687X012 32* Bearing, glass-filled PTFE 11A8619X012 33 Locknut, stainless steel 1A680335252
*Recommended spare parts
Page 13
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039 December 2005
13
Key Description Part Number
34 Street Tee (figure 4), STC/PL steel 1P3123X0032
Street Tee, STL/PL 1P3123x0042
35 Bleed Orifice (figure 4),
S31600 (316) stainless steel 1D4835X0012 36 NACE Tag (not shown) 18-8 stainless steel 19A6034X012 37 Tag Wire (not shown), 303 stainless steel 1U7581X0022
Type 2100E Switch (figure 6)
1 Cage & Displacer Assembly
To comply with NACE MR0175-2002, heat-treated
steel and stainless steel
w/o sight window
For 2220 WOG max working pressures w/1-inch NPT process connections 32B8089X082 w/2-inch Sch 80 BWE process connections 32B8089X132 w/2-inch Sch 160 BWE process connections 32B8089X182
For other than NACE applications, carbon steel
w/sight window
For 350 WOG max working pressure
w/1-inch NPT process connection 32B8089X042
w/o sight window
For 2220 WOG max working pressures
w/1-inch NPT process connections 32B8089X032 w/2-inch Sch 80 BWE process connections 32B8089X112 w/2-inch Sch 160 BWE process
connections 32B8089X172
2 Pipe Plug
(2 req’d w/sight window; 3 req’d w/o
sight window) 1A7947X0162
3 Body Block,
To comply with NACE MR0175-2002,
NACE steel 31A8610X022
For other than NACE applications, steel 31A8610X012
Key Description Part Number
4 Bushing (for use only w/sight window), steel 1L5019X0052 5 Sight Window, glass and alloy steel 11A8615X012 7* Torque Tube Assembly, N04400 26A3197X022
21 Nameplate, aluminum, For
right or left-hand mtg 10B5071X0A2
25* O-Ring, fluoroelastomer 1N571406382 28 Lock Washer, stainless steel (2 req’d) 1F128035022 30 Cap Screw, stainless steel (2 req’d) 1A4078X0052 31 Machine Screw, stainless steel 10B5078X012
32* Bearing, glass-filled PTFE 11A8619X012 33 Locknut, stainless steel (2 req’d) 1L286338992 36 NACE Tag (not shown), 18-8 stainless steel 19A6034X012 37 Tag Wire (not shown), 303 stainless steel 1U7581X0022
38 Switch Housing, stainless steel 22B4537X012 39 Cover and Gasket Assembly,
acrylic and chloroprene 12B4538X012 40 Switch Arm, stainless steel 10B5070X012 41 Shaft Clamp Screw, stainless steel 16A3198X012
42* Body Block Gasket, silicone 11A8642X012 43* Cover Gasket, cellulose/nitrile 22B4535X012 44 Cover Screw, stainless steel (2 req’d) 15A2029X012 45 Set Screw, 18-8 stainless steel (2 req’d) 10B5079X012
47 Thread locking adhesive, medium strength
(not furnished with switch) 46 Drive Screw, 18-8 stainless steel (2 req’d) 1A368228982
49* Electric Switch Assembly, stainless steel
Single pole double throw (SPDT) 20B5075X012
Double pole double throw (DPDT) 20B5076X012 50* O-Ring, nitrile 1H2926G0012 51 Cap Plug, polyethylene 12B4599X012
*Recommended spare parts
Page 14
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039
December 2005
14
40B6593-D SHT 1/DOC
Figure 6. Type 2100E Switch Assembly Drawing
Page 15
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039 December 2005
15
Type 2100E Electrical Switch Component Hazardous Area Classification Information
This section contains the hazardous area classification certificates for CSA, FM, ATEX, and UL. Inspect the electrical switch component in your 2100E electric liquid level switch to determine the part number of the switch component. Contact your Emerson Process Management sales office if additional information is needed.
Figure 7. CSA Certificate of Compliance
Page 16
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039
December 2005
16
Figure 7. CSA Certificate of Compliance (continued)
Page 17
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039 December 2005
17
Figure 8. FM Certificate of Compliance
Page 18
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039
December 2005
18
Figure 8. FM Certificate of Compliance (continued)
Page 19
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039 December 2005
19
Figure 9. ATEX Examination Certificate
Page 20
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039
December 2005
20
Figure 9. ATEX Examination Certificate (continued)
Page 21
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039 December 2005
21
Figure 9. ATEX Examination Certificate (continued)
Page 22
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039
December 2005
22
Figure 10. UL Certification
Page 23
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039 December 2005
23
Page 24
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039
December 2005
24
Fisher
Marshalltown, Iowa 50158 USA Cernay 68700 France Sao Paulo 05424 Brazil Singapore 128461
Emerson Process Management
www.Fisher.com
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Neither Emerson, Emerson Process Management, Fisher, nor any of their affiliated entities assumes responsibility for the selection, use and maintenance of any product. Responsibility for the selection, use and maintenance of any product remains with the purchaser and end-user.
EFisher Controls International LLC 1974, 2005; All Rights Reserved Printed in USA
Fisher is a mark owned by Fisher Controls International LLC, a member of the Emerson Process Management business division of Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
Loading...