Emerson 2100, 2100E Instruction Manual

www.Fisher.com
D200119X012
Type 2100 Pneumatic and Type 2100E Electric Liquid Level Switches
Contents
Introduction 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scope of Manual 1. . . . . . . . . . . . . . . . . . . . . . . . .
Specifications 3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Educational Services 3. . . . . . . . . . . . . . . . . . . . . .
Installation
3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Procedures 3. . . . . . . . . . . . . . . . . . . .
Common Procedures for Either Switch 4. . . . .
Additional Procedures for Type
2100 Switch 4. . . . . . . . . . . . . . . . . . . . . . . . . .
Additional Procedures for Type
2100E Switch 5. . . . . . . . . . . . . . . . . . . . . . . . .
Calibration Check 5. . . . . . . . . . . . . . . . . . . . . . . . .
Principle of Operation 5
. . . . . . . . . . . . . . . . . . . . . . .
Maintenance 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operational Test 8. . . . . . . . . . . . . . . . . . . . . . . . . .
Type 2100 Switch Maintenance Procedure 8. . . Type 2100E Switch Maintenance Procedure 10
Parts Ordering 11
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts Kits 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts List 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Type 2100E Electrical Switch Component
Hazardous Area Classification information 15.
CSA 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FM 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ATEX 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UL 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction
Scope of Manual
This instruction manual includes installation, maintenance, and parts information for the Type 2100 pneumatic and Type 2100E electric liquid level switches. Refer to separate instruction manuals when you require information regarding related valves, actuators, positioners, and accessories.
APPROXIMATE SWITCHING POINT
W6102-1*/IL
Figure 1. Type 2100 Pneumatic Liquid Level Switch
APPROXIMATE SWITCHING POINT
W6103-1*/IL
Figure 2. Type 2100E Electric Liquid Level Switch
Instruction Manual
Form 5039 December 2005
2100 and 2100E Liquid Level Switches
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039
December 2005
2
Table 1. Specifications
Input Signal
(1)
Liquid level
Minimum Process Liquid Specific Gravity
0.5 (consult your Emerson Process Managementt sales office for specific gravity below this value)
Output Signal
(1)
Type 2100 Switch: Output equal to supply
pressure when the switch is in the normal position (flapper against nozzle). Output reduced to approximately atmospheric pressure, depending upon size of the bleed orifice and piping configuration, when the switch is activated
Type 2100E Switch: Same as supply signal
Supply Signal
Type 2100 Switch: J 2.1 to 4.1 bar (30 to 60
psig), J 4.1 to 6.9 bar (60 to 100 psig), or J 6.9 to 10.3 bar (100 to 150 psig)
Type 2100E Switch: 11 amperes, 1/4
horsepower at 125/250 volts ac; 5 amperes resistive, 3 amperes inductive at 28 volts dc
Supply Medium (Type 2100 Switch)
Air or natural gas
(4)
Steady-State Air Consumption
(1,2)
(Type 2100
Switch)
Less than 0.03 normal m
3
/hr (1.0 scfh) for all supply pressures when the liquid level is 25.4 mm (1 inch) below the normal switch position (flapper against nozzle) for high-level switching or
25.4 mm (1 inch) above the normal switch position for low-level switching
Maximum Working Pressure
J 2220 WOG
(3)
except J 350 WOG is the maximum working pressure for sight window construction
Operative Temperature Range
(1)
Type 2100 Switch: 29 to 204_C (20 to
400_F)
Type 2100E Switch: 29 to 82_C (20 to
180_F)
Displacer Diameter
102 mm (4 inches)
Process Connection Size
2220 WOG
(3)
: J 1-inch NPT female,
J 50.8 mm (2-inch) Schedule 80 buttwelding ends, or J 50.8 mm (2-inch) Schedule 160 buttwelding ends
Type 2100 Switch Supply Pressure Connection Size
1/4-inch NPT female
Type 2100E Switch Electrical Connection Size
1/2-inch NPT male
Hazardous Area Classification
The Type 2100 and 2100E switches have no hazardous area approvals.
Approvals on the electrical switch component in the Type 2100E, supplied by ITT NEO-DYN are as follows:
APPROVED
EXP Class I Division 1 Groups A,B,C,D DI Class II Division I Groups E,F,G
Class I Groups A,B,C,D Class II Groups E,F, G
UL
Class I Groups A,B,C,D Class II Groups E,F, G
ATEX
EEx d IIC
Refer to figures 7, 8, 9, and 10 for specific hazardous classification information. Contact your Emerson Process Management sales office if additional information is required.
Shipping Weights
2220 WOG
(3)
Construction: 17.2 kg (38 pounds)
1. These terms are defined in ISA Standard S51.1.
2. Normal m
3
/hr—normal cubic meters per hour (0_C and 1.01325 bar, absolute); scfh—standard cubic feet per hour (60_F and 14.7 psia)
3. Water, Oil, Gas maximum working pressure rating designation in psi. Corresponds to Cold Working Pressure: the maximum pressure rating allowed under normal ambient temperature conditions, which are usually understood to be − 29_C to 38_ C (− 20_F to 100_F). Refer to MSS SP-25.
4. Natural gas to contain no more than 20 ppm of H
2
S.
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039 December 2005
3
No person may install, operate or maintain a Type 2100 pneumatic or a Type 2100E electric liquid level switch without first D being fully trained and qualified in valve, actuator and accessory installation, operation and maintenance, and D carefully reading and understanding the contents of this manual. If you have any questions about these instructions, contact your Emerson Process Management sales office.
Description
The on-off Type 2100 pneumatic switch (figure 1) and the Type 2100E electric switch (figure 2) operate shutdown valves or alarm systems when liquid in a vessel reaches a predetermined level. The Type 2100 switch uses an externally mounted displacer that operates a nozzle-flapper to vent the supply pressure when the switch is activated. The nozzle-flapper has a soft seat for tight shutoff when the switch is in its normal position (flapper against the nozzle). The Type 2100E switch uses the displacer torque to activate and deactivate an electric switch for positive on-off service. The displacer on each type can withstand up to 1-1/2 times the maximum working pressure, allowing it to remain in the cage during hydrostatic testing.
Unless otherwise noted, all NACE references are to NACE MR01752002.
Specifications
Specifications for the Type 2100 and 2100E switches are shown in table 1.
WARNING
This product is intended for a specific current range, temperature range and other application specifications. Applying different current, temperature and other service conditions could result in malfunction of the product, property damage or personal injury.
Educational Services
For information on available courses for Type 2100 pneumatic and Type 2100E electric liquid level switches, as well as a variety of other products, contact:
Emerson Process Management Educational Services, Registration P.O. Box 190; 301 S. 1st Ave. Marshalltown, IA 501582823 Phone: 8003388158 or Phone: 6417543771 FAX: 6417543431 e-mail: education@emersonprocess.com
Note
Neither EmersonR, Emerson Process Management, Fisher
R
, nor any of their affiliated entities assumes responsibility for the selection, use, and maintenance of any product. Responsibility for the selection, use, and maintenance of any product remains with the purchaser and end-user.
Installation
Installation Procedures
The installation procedures include those common to both the Type 2100 pneumatic and Type 2100E electric liquid level switches and additional ones for each switch.
WARNING
Always wear protective clothing, gloves, and eyewear when performing any installation operations to avoid personal injury.
Check with your process or safety engineer for any additional measures that must be taken to protect against process media.
If installing into an existing application, also refer to the WARNING at the beginning of the Maintenance section in this instruction manual.
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039
December 2005
4
A3619-1/IL
1/4-INCH NPT OUTPUT PRESSURE CONNECTION
1/4-INCH NPT SUPPLY PRESSURE CONNECTION
BACK PLATE (KEY 10)
STREET TEE (KEY 34)
BLEED ORIFICE (KEY 35)
Figure 3. Detail of Optional Street Tee and Bleed Orifice
Common Procedures for Either Switch
The horizontal line forged on the displacer cage indicates the approximate switching point (figures 1 and 2). When you mount the Type 2100 or Type 2100E switch, position it so that the horizontal line corresponds to the horizontal level at which switching is desired.
Before you install the Type 2100 or Type 2100E switch, remove the plastic plugs from the process connections. One of these plugs retains a paper tube that protects the displacer and torque tube during handling and shipping. This paper tube must also be removed.
There are two process connections, one at the top and one at the bottom of the cage. To mount the switch, connect the appropriate top and bottom process connections to the vessel using the required size pipe. The pipe must be capable of supporting the assembly and of withstanding the pressure involved. Use accepted piping and welding practices when making connections. Install isolating valves between the vessel and cage. Plugs are furnished for the unused process connections. However, one of the plugs can be removed, and a bleed valve or drain can be installed in one of the unused connections.
Additional Procedures for Type 2100 Switch
If using natural gas as the pneumatic supply medium, natural gas will be used in the pressure connections of the unit to any connected equipment. The unit will vent natural gas into the surrounding atmosphere, unless it is remote vented.
WARNING
Personal injury or property damage may occur from an uncontrolled process if the Type 2100 switch supply medium is not clean, dry air or noncorrosive gas. If clean, dry air, or noncorrosive gas is not used, the switch may become inoperative and allow the level in a process vessel to exceed safe limits. Install a 40 micron filter and suitable equipment to dry the supply medium and establish a maintenance cycle to check the filter and equipment.
If the existing supply medium is corrosive, make sure the tubing and instrument components that contact the corrosive medium are suitable corrosion-resistant materials, or use a noncorrosive medium.
WARNING
Personal injury or property damage may result from fire or explosion if natural gas is used as the supply medium and preventative measures are not taken. Preventative measures may include: Remote venting, re-evaluating the hazardous area classification, ensuring adequate ventilation, and the removal of any nearby ignition sources.
Refer to figure 5 except as noted.
1. Connect a supply pressure line to the 1/4-inch NPT female connection located in the back plate (key 10).
2. Install an output line between the supply pressure line and the equipment to be operated by the switch.
3. Install a street tee and bleed orifice (keys 34 and 35, figure 3) or other fixed restriction in the supply pressure line between the supply source and the output signal line.
4. If a remote vent is required, remove the vent assembly (key 23) from the 1/4-inch NPT female vent connection and install a vent line to an area where the operating medium can be safely exhausted.
Note
The vent line should have as large a diameter as possible with a minimum
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039 December 2005
5
number of bends and elbows. The vent line should be as short as possible. Protect the end of the vent pipe from the entrance of rain, snow, insects, or any other foreign material that may plug the vent line. Inspect the vent line opening periodically to ensure that it is not plugged.
If necessary to change to a different supply pressure, install a different nozzle according to steps 1 through 4 and 15 through 18 of the Type 2100 switch maintenance procedure.
To change switch action from low-level to high-level switching or vice versa, reverse the positions of the nozzle, flapper, and magnet according to steps 1 through 7 and 10 through 18 of the Type 2100 switch maintenance procedure.
To change switch mounting from right-hand to left-hand or vice versa, perform steps 1 through 7 and 9 through 18 of the Type 2100 switch maintenance procedure.
Additional Procedures for Type 2100E Switch
Refer to figure 6.
To install for standard action, connect electrical wires as shown in table 2.
To change switch action from low-level to high-level switching, or vice versa, perform steps 1 through 4 and 13 through 17 of the Type 2100E maintenance procedure.
To reverse action of the Type 2100E switch, refer to table 2 and reinstall wiring for normally open (NO) switches to normally closed (NC) and vice versa.
To change switch mounting from right-hand to left-hand or vice versa, perform steps found in the Type 2100 switch maintenance procedure.
Calibration Check
For either type of switch, calibration can be checked by varying the level of the process liquid in the cage and observing the switch operation.
If the process connection directly on top of the cage is not piped to the tank, close the isolating valves
Table 2. Type 2100E Wiring Codes
Wire
Color
SPDT DPDT Switch 1 DPDT Switch 2
Red
Brown
Blue
Green
Black Yellow Purple
Normally Closed
Common
Normally Open
Ground
Normally Closed Common Normally Open Ground
Ground Normally Closed Common Normally Open
and fill the cage with process liquid through the top connection. Verify that the switch operates as the cage is being filled. Repeat the calibration procedure if necessary.
Calibration can also be checked on the work bench. Connect a flexible hose from one of the bottom process connections to the bottom of a bucket. The top process connection should be open. Fill the bucket with process liquid. As the bucket is raised or lowered, the liquid level in the displacer cage rises or falls. Verify that the switch operates as the level is varied. Repeat the calibration procedure if necessary.
Dry calibration can be performed on the Type 2100E using the following procedure:
Refer to figure 6.
1. Position the cage and displacer assembly (key 1) so that the displacer is hanging downward.
2. Level the switch arm (key 40), if required.
3. Loosen the locknut (key 33) and adjust the machine screw (key 31) until it contacts the switch.
4. For low-level dry calibration, tighten the locknut. For high-level dry calibration, turn the machine screw one additional full turn, then tighten the locknut.
Principle of Operation
The Type 2100 switch (figure 4) is an external, cage-mounted, pneumatic liquid level switch. When the switch is in the normal position with the flapper against the nozzle, output pressure cannot bleed off and remains the same as full supply pressure. Rising liquid level exerts a buoyant force on the displacer, producing a torque in the torque tube. When this torque exceeds the torque exerted on the flapper by the magnet, the flapper snaps away from the nozzle. This action allows output pressure to bleed through the nozzle faster than supply pressure can enter through the bleed orifice.
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039
December 2005
6
A3619-2/IL
Figure 4. Principle of Operation for High-Level Type 2100 Switch
The reduced pressure in the output signal line activates the shutdown or alarm system. When the liquid level lowers, the falling displacer forces the flapper into the field of the magnet, letting the magnet snap the flapper against the nozzle and causing output pressure to build to full supply pressure.
On applications where low-level switch operation is required, the nozzle, flapper, and magnet are positioned on the opposite side of the torque tube so that downward displacer travel moves the flapper away from the nozzle.
The Type 2100E switch is an external, cage-mounted, electric liquid level switch. Rising liquid level exerts a buoyant force on the torque tube that either activates or deactivates an electrical SPDT (single-pole, double-throw) or DPDT (double-pole, double-throw) switch depending on the required switching action. Falling liquid level deactivates or activates the same switch depending on the required action.
Maintenance
Switch parts are subject to normal wear and must be inspected and replaced when necessary. The frequency of inspection and replacement depends on the severity of service conditions.
Refer to figure 5 for maintenance of the Type 2100 switch and figure 6 for maintenance of the Type 2100E switch.
WARNING
Always wear protective clothing, gloves, and eyewear when performing any maintenance procedures to avoid personal injury.
The displacer is a sealed container inside the cage. A displacer penetrated by process fluid may retain pressure or hazardous fluid for an extended period. Such a displacer may contain pressure as a result of being in a pressurized vessel, or it may contain fluid that becomes pressurized due to changes in temperature and/or it may contain fluid that is hazardous or flammable. The sudden release of pressure, contact with hazardous fluid, fire, or explosion resulting in personal injury can occur if a displacer that is retaining pressure or process fluid is punctured or subjected to heat. Handle the cage (with displacer inside) with care in removing, storing, or disposing, taking into consideration the characteristics of the process fluid.
To avoid personal injury and damage to the process system caused by the sudden release of pressure, contact with hazardous fluid, fire, or explosion, isolate and drain the displacer cage.
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039 December 2005
7
Table 3. Type 2100 Troubleshooting Guide
Fault Possible Cause Correction
1. Nozzle-flapper throttles (flapper moves in response to change in liquid level but does not completely cap or uncap nozzle).
1.1 Nozzle adjusted too high. 1.1 If nozzle prevents flapper from coming in full contact with magnet, repeat the Calibration procedure.
Perform the Calibration Check procedure to ensure that the unit operates properly.
1.2 Verify that the top surface of the magnet is parallel with the flapper and that the magnet is in full contact with the flapper when the flapper is against the magnet. If the above conditions do not exist, repeat the Calibration procedure.
Perform the Calibration Check procedure to ensure that the unit operates properly.
2. Nozzle-flapper fails to snap open. 2.1 Liquid level not changing in the expected direction.
2.1 Be certain liquid level in the displacer cage is changing in the expected direction.
3. Nozzle-flapper leaks when shut off. 3.1 Surface of nozzle seat or nozzle worn or damaged.
3.2 Nozzle adjusted too low.
3.3 Incorrect alignment of nozzle and flapper.
3.1 Inspect surface of flapper seat (key 11, figure 5), and nozzle (key 6, figure 5); replace parts if necessary.
3.2 Inspect nozzle-flapper when flapper is being held by magnet. If nozzle is not seated on flapper seat, loosen locknut (key 33, figure
5) and rotate nozzle counterclockwise until it is seated.
3.3 Inspect surface of nozzle seat (key 11, figure 5). This surface should be parallel with the opening in the end of the nozzle (key 6, figure 5). Correct as necessary.
4. Switch fails to activate upon high or low
level depending on action selected.
4.1 Foreign material in cage.
4.2 Clamp and shaft assembly loose on torque tube assembly.
4.3 Torque tube assembly failure.
4.1 Flush cage to remove foreign material.
4.2 Perform step 4 of reassembly procedure in maintenance section. Tighten clamp nut on clamp and shaft assembly to between 20 and 27 NSm (15 and 20 lbSft).
4.3 Perform operational test procedure Replace torque tube assembly if it fails operational test.
For Type 2100, shut off and bleed supply pressure from the switch before attempting any maintenance procedures. For Type 2100E, shut off the power to the electric switch assembly before attempting any maintenance procedures.
Check with your process or safety engineer for any additional measures that must be taken to protect against process media.
The displacer cage should be flushed periodically to remove deposits or sludge that may affect proper operation. The frequency of flushing depends on the
nature of the process liquid. Before flushing, close the isolating valves and drain the cage. Flush from one of the top connections to one of the bottom connections. Also, remove the pipe plug (key 2) or the bushing and sight window (keys 4 and 5), and flush from a top connection through the pipe plug or sight window connection.
Inspect the vent or vent screen (key 23) or vent line periodically to ensure that the vent or vent line is not plugged.
Table 3 lists various Type 2100 switch problems and possible solutions for them. The table is valid for either high-level or low-level switching action and for any supply pressure range. If a correction step requires replacement of worn or damaged parts,
2100 and 2100E Liquid Level Switches
Instruction Manual
Form 5039
December 2005
8
refer to the appropriate maintenance procedure in this manual for disassembly and reassembly instructions.
Type 2100E switch problems are solved through common electrical troubleshooting procedures. Fault 4 of table 3 is also pertinent for the Type 2100E.
Operational Test (Types 2100 and 2100E)
Establish a periodic operational test of the switch to ensure that:
a. the torque tube is functioning as a continuous spring element;
b. there is an absence of excessive friction;
c. there is no contact with the mechanical stops, and;
d. the torque tube is still effectively transmitting force and motion to the Type 2100 flapper and clamp assembly, or to the Type 2100E switch arm assembly.
This test should be conducted with no process fluid in the cage using the following procedures:
1. Make sure the Type 2100 switch flapper and clamp assembly (key 12, figure 5) or the Type 2100E switch arm (key 40, figure 6) is tight on the shaft of the torque tube assembly (key 7).
2. Grasp and lift, then immediately release, the following:
D The Type 2100 switch flapper and clamp
assembly (key 12, figure 5), 10 to 13 mm (0.375 to
0.5 inch) from the nozzle (key 6, figure 5), or
D The Type 2100E switch arm (key 40, figure 6), 10 to 13 mm (0.375 to 0.5 inch) from the contact of the electric switch assembly (key 49, figure 6).
3. The torque tube spring system is functional if the Type 2100 switch flapper and clamp assembly, or the Type 2100E switch arm, bounces at least two cycles in a reversing rotary motion.
Type 2100 Switch Maintenance Procedure
WARNING
Refer to the WARNING at the beginning of the Maintenance section.
WARNING
When disconnecting any of the pneumatic connections, natural gas, if used as the supply medium, will seep from the unit and any connected equipment into the surrounding atmosphere. Personal injury or property damage may result from fire or explosion if preventative measures are not taken, such as adequate ventilation and the removal of any nearby ignition sources.
Refer to figure 5.
1. Drain the liquid from the cage and displacer assembly (key 1), then isolate it from the process. Shut off the supply pressure and bleed any trapped supply and output pressure from the nozzle block assembly (key 8).
2. Loosen the cover screws (key 17) and remove the cover (key 15). Replace the cover gasket (key 16) and the cover screw gaskets (key 20) if necessary.
Note
Magnetic attraction between the magnet (key 14) and the flapper (key
12) can be adversely affected by the presence of foreign material between the magnet and flapper. Before performing any inspection or correction step, inspect the magnet. If necessary, clean the magnet thoroughly. If cleaning requires removing the magnet or magnet bracket (key 13), perform step 17 of the maintenance procedure; then perform the calibration check procedure to ensure that the unit operates properly.
3. Loosen the nut holding the flapper and clamp assembly (key 12) to the shaft of the torque tube assembly (key 7). Remove the flapper and clamp
Loading...
+ 16 hidden pages