DANGER is used in this manual to warn of a
hazard situation which, if not avoided, will result in
death or serious injury .
WARNING is used in this manual to warn of a
hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION is used in this manual to warn of a
hazardous situation which, if not avoided, could
result in minor or moderate injury.
An experienced licensed electrician must install the A TS.
100 throu gh 400 ampe re sizes
Series 185
Refer to the outline and wiring drawings provided with
your ASCO Series 185 ATS for all installation details.
ASCO Series 185 Automatic Transfer Switches (ATSs) are
Listed under Underwriter’s Laboratories Standard for
Transfer Switch Equipment, UL–1008. They are intended
for use only in optional standby system s in accordanc e with
the National Electrical Code, NEC/NFPA 70, Article 702.
This ATS is for use with 2–wire automatic–start generator s
only.
Refer to Application Information 381339–292 to confirm
that you have selected the appropriate product for the
intended installatio n .
This automatic transfer switch is intended for standby
power applications in residential / light commercial use
only.
This product is not intended for emergency
or life–support systems.
If you have more stringen t applicatio n requirements contact
ASCO Pow er Technolog ies for other produc ts suitable for
critical applications.
Rating Label
Each automatic transfer switch contains a rating label to
define the loads and fault circuit withstand / closing ratings.
Refer to the label on the transfer switch for specific values.
Do not exceed the values on the rating label.
Exceeding the rating can cause person injury or
serious equipment damage.
TABLE OF CONTENTS
page
INSTALLATION1..........................
CONTROLLER2–5........................
FUNCTIONAL TEST6......................
SEQUENCE OF OPERATION7.............
TROUBLESHOOTING8–9..................
INDEX10.................................
100–230 ampere sizes
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA
For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3
381333–319 E
Series 185
Nameplate
The Transfer Switch nameplate includes data for
each specific ASCO Series 185 ATS. Use the ATS
only within the limits shown on this nameplate.
D 185A2200F4C
Neutral
A –standard
clock battery
Phase Poles
2 –singleØ
AmperesVoltageControllerEnclosure
100
cable spacers
(see INSTALLATION)
200
230
260
400
Catalog Number Identification
A typical Catalog Number is shown below with its
elements explained. The example is for a D–design,
2 pole, 200 A, 220–240 V, in T ype 1 indoor enclosure:
F 220--- 240
4 –standard
4X
–if
accessories
ordered
load power
connections
C –Type1
M –Type3R
emergency
power
connections
neutral
connections
terminals
for optional
switch
position
contacts
(shown
installed)
Transfer
Switch
ground
connections
200 ampere size in typical enclosure with location of customer connections
381333–319 E
membrane
controls
generator
control
connections
Controller
harness plug
utility power
connections
INSTALLATION
Series 185
Installation of the ASCO Series 185 automatic transfer
switch (ATS) must be performed by a licensed electrician.
It must be installed according to the National Electrical
Code (NEC) and all local electrical code requirements.
Remove the enclosure cover and inspect the ATS for
shipping damage. If damage is evident do not install the
ATS .
1 --- M o u n t i n g
Refer to the enclosure outline drawing. Mount the ATS
according to details and instructions shown on this
diagram. Mount the ATS vertically to a rigid supporting
structure. Level all mounting points by using flat washers
behind the holes to avoid distortion of the enclosure.
NOTICE
MALFUNCTION or SHORTENED LIFE
Protect the automatic transfer switch from
construction grit and metal chips to prevent
malfunction or shortened life of the AT S.
2 --- Electrical Power Connections
Refer to the wiring diagram. The ATS must be protecte d
by suitably sized circuit breakers feeding the utility and
generator source terminals. The rating of the circuit
breakers must be based on the requirements of the
National Electrical Code for its nameplate ampere and
short circuit withstand ratings.
ELECTROCUTION HAZARD Turn off utility power
and turn off the generator to prevent electrocution
when wiring the transfer switch.
Cable Spacers for 150, 200, and 230 A
Three cable spacers are included with 150, 200, and 230
ampere transfer switches. Run the copper power cables
throughthecablespacersasshowninFigure2. Position
the cable spacers approximately 1½ inches from the
terminal lugs.
Transfer switches rated 260 and 400 amperes are
mounted on an insulator backing piece (installed behind
the transfer switch). If the transfer switch is removed
from the enclosure and then reinstalled, this insulator
must be placed behind the transfer switch. See Figure 1.
FLASH HAZARD – DAMAGE
Be sure that the insulator piece is installed behind
the 260 and 400 ampere transfer switches.
insulator
backing
piece
NOTICE
CABLE LOOSENING DUE TO SHORT CIRCUIT
Install three cable spacers 1 1/2 inches from the
power terminals to prevent the cables from
loosening during a short–circuit condition on 150,
200, and 230 ampere transfer switches.
cable spacers
1 ½ inch approximate
use copper power
cables only for
200 and 230 A
cable spacer
Figure 2. Cable spacers for 150, 200, an d 230 A.
Figure 1. Insulator for 260 and 400 A.
1
381333–319 E
CONTROLLERSeries 185
The Group 4 digital Controller is used in ASCO Series
185 automatic transfer switches. It provides the sensing,
timing, and control functions for the ATS. This micro–
processor–based controller includes built–in control
buttons and st atus lights for control of the ATS and
generator.
clock
battery
cover
seepage3
Utility
Acceptable
light
Trans fer
Tes t
button
Bypass
Time Delay
button
Set Engine
Exerciser
button
Automatic
Generator
Exerciser
light
Load on
Utility light
Load on
Generator
light
Generator
Acceptable
light
1 --- P u s h B u t t o n s
On the front control display are three push buttons that
control the operation of the generator and the ATS.
Before using the transfer test button, be sure that
conditions are safe for running the generator and
for load transfer.
Transfer Test
Use this button to test the system. This operation starts
the generator and transfers the load. Be sure that
conditions are safe to do this operation.
Bypass Time Delay
Use this button to cancel the active time delay or exercise
period (stops the generator after cooldown).
Set Engine Exerciser
Use this button to set the automatic generator exerciser
(page 3).
2 --- I n d i c a t o r L i g h t s
On the f ront control display are five lights that indicate
the status of the sources and the ATS.
Utility Acceptable
This light i ndicates that the utility voltage is acceptable
for connection to the load.
Generator Acceptable
This light indicates that the generator voltage is
acceptable for connection to the load.
Figure 3. Front view of controller.
381333–319 E
Load on Utility
This light indicates that the load is connected to the
utility.
Load on Generator
This light indicates that the load is connected to the
generator.
Automatic Generator Exerciser
This light i ndicates the status of the generator exerciser:
--- blinks during the exercise period (including cooldown).
--- stays on when the exerciser has been set.
--- is off when the exerciser has not been set.
2