Installation Guide
English – May 2002
Type 1367
Introduction
This installation guide provides instructions for installation,
startup, and adjustment. To receive a copy of the instruction
manual, contact your local Fisher Sales
Office or Sales Representative or view a copy at
www.FISHERregulators.com. For further information refer to:
Type 1367 Instruction Manual, form 5220, D100343X012.
This installation guide provides basic information on the
Type 1367 high-pressure instrument supply system. For
complete adjustment, maintenance, and parts information on the individual components of this system, refer to
separate manuals for the Type 67CF and 1301F regulators, Type 252 filter, and Type H800 relief valve.
The Type 1367 high-pressure instrument supply system
takes a pressure of up to 138 bar (2000 psig) and reduces it to a controlled pressure to be used for supplying
a pneumatic instrument. This system consists of the following:
• A Type 252 aluminum extended body filter.
• A first-stage Type 1301F regulator, with bracket for mounting on an actuator yoke or casing.
• A Type H120 relief valve, elbow-mounted in the side
outlet of the Type 1301F regulator.
• A second-stage Type 67CF filter-style regulator, nipplemounted in the outlet of the Type 1301F regulator.
• A Type H800 relief valve, nipple-mounted in the outlet of
the Type 67CF regulator
P.E.D. Categories
This product may be used as a safety accessory with
pressure equipment in the following Pressure Equipment
Directive 97/23/EC categories. It may also be used outside of the Pressure Equipment Directive using sound
engineering practice (SEP) per table below.
EZISTCUDORPSEIROGETACEPYTDIULF
)hcni-4/1(6NDPES1
Proof Test Pressure
All Pressure Retaining Components have been
proof tested per Directive 97/23/EC - Annex 1,
Section 7.4
Temperature Capabilities
-29 to 66°C (-20 to 150°F)
(1)
Installation
Only qualified personnel should install or service
a regulator. Regulators should be installed,
operated, and maintained in accordance with
international and applicable codes and
regulations, and Fisher instructions.
If the regulator vents fluid or a leak develops in
the system, it indicates that service is required.
Failure to take the regulator out of service
immediately may create a hazardous condition.
Personal injury, equipment damage, or leakage
due to escaping fluid or bursting of pressurecontaining parts may result if this regulator is
overpressured or is installed where service
conditions could exceed the limits given in the
Specifications section, or where conditions
exceed any ratings of the adjacent piping or piping
connections.
To avoid such injury or damage, provide pressurerelieving or pressure-limiting devices (as required
by the appropriate code, regulation, or standard)
to prevent service conditions from exceeding
limits.
Additionally, physical damage to the regulator
could result in personal injury and property
damage due to escaping fluid. To avoid such injury
and damage, install the regulator in a safe
location.
Specifications
Connection Size
Inlet and Outlet: DN 6 (1/4-inch) NPT screwed
Type H800 Vent: DN 15 (1/2-inch) NPT screwed
with removable screen
Maximum Inlet Pressure
138 bar (2000 psig)
Outlet (Supply) Pressure Range
0,34 to 2,4 bar (5 to 35 psig)
Maximum Outlet (Supply) Pressure with Type
67CF Regulator Failed Wide-Open and Type H800
Relief Valve Relieving
3,4 bar (50 psig)
1. The pressure/temperature limits in this installation guide and any applicable
standard or code limitation should not be exceeded.
(1)
(1)
(1)
www.FISHERregulators.com
Clean out all pipelines before installation of the regulator
and check to be sure the regulator has not been damaged
or has collected foreign material during shipping. For NPT
bodies, apply pipe compound to the male pipe threads. For
flanged bodies, use suitable line gaskets and approved
piping and bolting practices. Install the regulator in any
position desired, unless otherwise specified, but be sure
flow through the body is in the direction indicated by the
arrow on the body.
Note
It is important that the regulator be installed so that
the vent hole in the spring case is unobstructed at all
times. For outdoor installations, the regulator should
be located away from vehicular traffic and positioned
so that water, ice, and other foreign materials cannot
enter the spring case through the vent. Avoid placing
the regulator beneath eaves or downspouts, and be
sure it is above the probable snow level.
D100343XENG
Type 1367
Overpressure Protection
The recommended pressure limitations are stamped on
the regulator nameplate. Some type of overpressure
protection is needed if the actual inlet pressure exceeds the
maximum operating outlet pressure rating. Overpressure
protection should also be provided if the regulator inlet
pressure is greater than the safe working pressure of the
downstream equipment.
Regulator operation below the maximum pressure limitations
does not preclude the possibility of damage from external
sources or debris in the line. The regulator should be inspected
for damage after any overpressure condition.
Startup
The regulator is factory set at approximately the midpoint of
the spring range or the pressure requested, so an initial
adjustment may be required to give the desired results. With
proper installation completed and relief valves properly
adjusted, slowly open the upstream and downstream shutoff
valves.
Adjustment
To change the outlet pressure, remove the closing cap or
loosen the locknut and turn the adjusting screw clockwise
to increase outlet pressure or counterclockwise to decrease
pressure. Monitor the outlet pressure with a test gauge
during the adjustment. Replace the closing cap or tighten
the locknut to maintain the desired setting.
Taking Out of Service (Shutdown)
To avoid personal injury resulting from sudden
release of pressure, isolate the regulator from all
pressure before attempting disassembly.
Parts List
Key Description
1 Type 252 Filter
2 Type 1301F Regulator
For yoke mounting
For casing mounting
3 Type H120 Relief Valve
4 Type 67CF Regulator
5 Type H800 Relief Valve
6 Pipe Nipple
7 Street Elbow
A7035
Figure 1. Type 1367 Instrument Supply System
©Fis her C ontro ls Inte rnati onal, I nc., 2002; All R ights Rese rved
Fisher and Fisher Regulators are marks owned by Fisher Controls International, Inc. The Emerson logo is a trade mark and service mark of Emerson Electric Co.
All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express
or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
For information, contact Fisher Controls, International:
Within USA (800) 588-5853 – Outside USA (972) 542-0132
France – (33) 23-733-4700
Singapore – (65) 770-8320
Mexico – (52) 57-28-0888
Printed in U.S.A.
www.FISHERregulators.com