Emerson 1305 Installation Guide

Installation Guide English – May 2002
1305 Series
Introduction
This installation guide provides instructions for installation, startup, and adjustment. To receive a copy of the instruction manual, contact your local Fisher Sales Office or Sales Representative or view a copy at www.FISHERregulators.com. For further information refer to:
1305 Series Instruction Manual (form 1095, D100342X012).
P.E.D. Category
This product may be used as a safety accessory with pressure equipment in the following Pressure Equipment Directive 97/23/EC categories. It may also be used outside of the Pressure Equipment Directive using sound engineering practice (SEP) per table below.
EZISTCUDORPSEIROGETACEPYTDIULF
)hcni-1(52NDPES1
Specifications
Available Constructions
Type 1305C: DN25 (1-inch) NPT inlet and DN 8 (1/4-
inch) NPT outlet connections; 2 mm (5/64-inch) orifice diameter. Three springs provide 0 to 15,51 bar (0 to 225 psig) reduced pressure ranges.
Type 1305D: same as 1305C, with larger spring case and one heavy spring for reduced pressure range of 13,79 to 34,47 bar (200 to 500 psig).
Piping Connections
Inlet: DN 25 (1-inch) NPT Outlet: DN 6 (1/4-inch) NPT
Maximum Emergency Outlet (casing) Pressure
Type 1305C: 17,25 bar (250 psig) Type 1305D: 37,92 bar (550 psig)
Outlet Pressure Ranges
Type 1305C: 0 to 5,17 bar (0 to 75 psig), 0 to 10,34 bar
(0 to 150 psig), and 0 to 15,51 bar (0 to 225 psig)
Type 1305D: 13,79 to 34,47 bar (200 to 500 psig)
Maximum Allowable Inlet Pressures
275,8 bar (4000 psig)
(1)
(1)
(1)
Proof Test Pressure
All Pressure Retaining Components have been proof tested per Directive 97/23/EC - Annex 1, Section 7.4
Temperature Capabilities
-29 to 93°C (-20 to 200°F)
(1)
Installation
Only qualified personnel should install or service a regulator. Regulators should be installed,
operated, and maintained in accordance with international and applicable codes and regulations, and Fisher instructions.
If the regulator vents fluid or a leak develops in the system, it indicates that service is required. Failure to take the regulator out of service immediately may create a hazardous condition.
Personal injury, equipment damage, or leakage due to escaping fluid or bursting of pressure­containing parts may result if this regulator is overpressured or is installed where service conditions could exceed the limits given in the Specifications section, or where conditions exceed any ratings of the adjacent piping or piping connections.
To avoid such injury or damage, provide pressure­relieving or pressure-limiting devices (as required by the appropriate code, regulation, or standard) to prevent service conditions from exceeding limits.
Additionally, physical damage to the regulator could result in personal injury and property damage due to escaping fluid. To avoid such injury and damage, install the regulator in a safe location.
Clean out all pipelines before installation of the regulator and check to be sure the regulator has not been damaged or has collected foreign material during shipping. For NPT bodies, apply pipe compound to the male pipe threads. For flanged bodies, use suitable line gaskets and approved piping and bolting practices. Install the regulator in any position desired, unless otherwise specified, but be sure flow through the body is in the direction indicated by the arrow on the body.
Note
It is important that the regulator be installed so that the vent hole in the spring case is unobstructed at all times. For outdoor installations, the regulator should be located away from vehicular traffic and positioned so that water, ice, and other foreign materials cannot enter the spring case through the vent. Avoid placing the regulator beneath eaves or downspouts, and be sure it is above the probable snow level.
Overpressure Protection
The recommended pressure limitations are stamped on the regulator nameplate. Some type of overpressure protection is needed if the actual inlet pressure exceeds the maximum operating outlet pressure rating. Overpressure protection should also be provided if the regulator inlet pressure is greater than the safe working pressure of the downstream equipment.
Regulator operation below the maximum pressure limitations does not preclude the possibility of damage from external sources or debris in the line. The regulator should be inspected for damage after any overpressure condition.
1. The pressure/temperature limits in this installation guide and any applicable standard or code limitation should not be exceeded.
www.FISHERregulators.com
D100342XENG
1305 Series
Startup
The regulator is factory set at approximately the midpoint of the spring range or the pressure requested, so an initial adjustment may be required to give the desired results. With proper installation completed and relief valves properly adjusted, slowly open the upstream and downstream shutoff valves.
Adjustment
To change the outlet pressure, remove the closing cap or loosen the locknut and turn the adjusting screw clockwise to increase outlet pressure or counterclockwise to decrease pressure. Monitor the outlet pressure with a test gauge during the adjustment. Replace the closing cap or tighten the locknut to maintain the desired setting.
Parts List
Key Description
1 Lower Casing 2 Spring Case 3 Inlet Adaptor 4 Orifice 5 Valve Disk Assembly 6 Valve Stem 7 O-Ring 8 Union Nut 9 Split Ring 10 Valve Lever Assembly 10A Valve Lever 10B Valve Lever Pin 11 Pusher Post Assembly 11A Pusher Post 11B Roll Pin 12 Lever Support Pin 14 Diaphragm 15 Diaphragm Head 16 Hex Nut 17 Spring 18 Upper Spring Seat 19 Set Screw 20 Hex Nut 21 Machine Screw 23 O-Ring 24 Pipe Plug 27 Vent Screen 28 Baffle 30 O-Ring
Taking Out of Service (Shutdown)
To avoid personal injury resulting from sudden release of pressure, isolate the regulator from all pressure before attempting disassembly.
CR1399-A
Figure 1. 1305 Series Regulator
©Fis her C ontro ls Inte rnati onal, I nc., 2002; All R ights Rese rved
Fisher and Fisher Regulators are marks owned by Fisher Controls International, Inc. The Emerson logo is a trade mark and service mark of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.