Elkhart Brass 8294-02 User Manual

INSTRUCTIONS FOR ELKHART 8294-02
DUAL HANDWHEEL MONITOR
INSTALLATION
Warning: When installing monitor on a raised face companion flange or butterfly valve, it is critical that bolts be tightened uniformly to prevent cocking of the monitor relative to the flange or valve. If the monitor becomes cocked, the monitor cast flange base will fracture and fail when the bolts on the "high" side are tightened.
OPERATION
The left/right hand wheel remains fixed while the up/down hand wheel will rotate with the monitor. Turn the up/down hand wheel clockwise to lower nozzle or counterclockwise to raise nozzle. Turn the left/right hand wheel clockwise to move nozzle left or counterclockwise to move nozzle right. (See drawing 98031010 for possible up/down and left/right travel stop positions.)
MAINTENANCE & INSPECTION
The monitor should be inspected regularly. Careful inspection for damage to the monitor or nozzle is especially important after use in emergency operations. Flow water to check nozzle pattern. If pattern is disrupted, remove nozzle and check for debris lodged between the nozzle stem and body, or in the stream shaper inlet. During nozzle flow test, inspect monitor swivel joints for leaks.
Note: Although grease fittings are provided for the up-down and left-right gear cases, routine greasing should not be necessary. If the monitor is exposed to a high level of radiant heat for a prolonged period, it may be possible for the factory grease to thin and run out of the gear cases. In such an event, fresh grease should be applied.
98031020 (Rev-REL)
Elkhart Brass Mfg. Co., Inc. 1302 W. Beardsley Avenue • Elkhart, Indiana 46514 • 1-574-295-8330 • 1-800-346-0250
www.elkhartbrass.com