Edwards and the Edwards logo are trademarks of Edwards Limited.
B800-00-880 Issue A
CAUTION
WARNING
1Introduction
1.1Scope and definitions
This manual provides installation, operation, maintenance and storage instructions for the Edwards nEXT
Turbomolecular Pumps. You must use the nEXT pumps as specified in this manual. If you do not, the protection
provided by the nEXT pumps may be impaired.
Read this manual before you install and operate the nEXT pump. Important safety information is highlighted as
WARNING and CAUTION instructions; you must obey these instructions. The use of WARNINGS and CAUTIONS is defined
below.
Warnings are given where failure to observe the instruction could result in injury or death to
people.
Cautions are given where failure to observe the instruction could result in damage to the equipment, associated
equipment and process
Introduction
The units used throughout this manual conform to the SI international system of units of measurement; where
appropriate US equivalent units of measurement are also given. When flow rates are specified, the abbreviation
‘sccm’ is used to mean standard cubic centimetres per minute. This is a flow of 1 cm
of 0 ºC and a pressure of 1013 mbar (1.013 x 10
In accordance with standard EN61010, the following warning label appears on the nEXT pump:
Improper use of the equipment could cause damage to it or injury to people. The user is
responsible for the safe operation, installation and monitoring of the system.
The Drive contains electrolytic capacitors and, under certain fault conditions, may emit dangerous
fumes. Ensure that the Drive is operated in a well-ventilated area.
Do not attempt to separate the Controller from the pump since this will cause damage to the electrical
connections.
The nEXT pumps consist of the turbomolecular pump with a permanently attached controller containing drive
electronics.
The controller controls the electrical supply to the pump with the exception of standby speed control. It has no
manual controls and can only be operated through the logic interface. To operate the nEXT pump you must connect
it to your own control equipment and power supply or alternatively use the Edwards TIC Turbo Instrument Controller
or TIC Turbo Controller.
The controller drives the brush-less d.c. motor in the pump.
There are three main variants of the nEXT pump,
The “S” or “Simplex” variant contains only turbomolecular blades.
The “D” or “Duplex” variant contains turbomolecular blades and a Siegbahn drag mechanism allowing
operation at higher backing pressures than pure turbomolecular pumps.
The “T” or “Triplex” variant contains turbomolecular blades, a Siegbahn drag mechanism and a regenerative
mechanism. The regenerative stage offers the option to utilise “boost” mode.
Also available is an “iD” or “iT” interstage variant, which provides an interstage port between the turbomolecular
blades and Siegbahn drag mechanism.
nEXT pumps are supplied with an inlet-screen fitted into the centering O-ring for ISO version pumps and into envelope
for CF version pumps. nEXT pumps with an NW25 interstage port are supplied with an inlet-strainer that fits into the
interstage-port. The inletscreen and inlet-strainer protect the pump against damage that would be caused by debris
entering the pump.
The nEXT pumps have a vent-port for venting the pump and vacuum system to atmospheric pressure. The pump is
supplied with a manual vent-valve fitted; this can be replaced with a TAV5 or TAV6 solenoid-operated vent-valve
(available as accessories – see Section 7). The TAV valve can be directly controlled by the on-board controller.
The nEXT pumps have a purge-port: an inert purge gas can be introduced to protect the bearing and motor from
corrosion. An optional vent-port adapter and purge restrictor can be fitted to the purge-port to control the flow rate
of the purge gas and to filter the gas supply. (Refer to Section 7).
Air-coolers and a water-cooling block are available as optional accessories to cool the nEXTpumps. (Refer to
Edwards and the Edwards logo are trademarks of Edwards Limited.
B800-00-880 Issue A
1.3Pump controller
The pump controller contains the drive electronics that control the pump operation and the TAV vent valve. There
is a connector socket on the side of the controller where the TAV vent valve can be plugged-in. (Refer to Section 2.9)
The controller has three indicator LEDs that signal the general status, operation and service status of the pump, that
can also be used for fault finding if a problem should occur. (Refer to Section 2.10)
The drive electronics system has a number of built-in safety features to protect the nEXT pumps from damage in the
event of sustained high pressure or temperature:
The electronics constantly monitors the temperature inside the controller and the temperature of the motor
within the pump. If either part becomes too hot, the controller reduces the power supplied to the pump
motor and the pump speed will drop. If the pump rotational speed falls below 50% full speed, the electronics
may trip into a Fail condition, depending on how you have configured the system. (Refer to Section 1.4.3).
If the nEXT pump's inlet pressure increases, the power supplied to the pump-motor increases to counteract
the gas frictional load. However, when the built-in maximum power limit is reached, the speed of the pump
will start to drop. If the pump rotational speed falls below 50% full speed, the electronics may trip into Fail
condition, depending on how the system has been configured. (Refer to Section 1.4.3).
In the event of an electrical supply failure, the drive electronics uses the motor within the pump as a
generator. This means the nEXT pumps have their own regenerative supply and do not require a separate
battery for emergency power back-up. The regenerated energy is used to maintain the electrical supply to
the vent valve until the pump speed falls to below 50% of full rotational speed: this will ensure that the vent
valve remains shut until below 50% of full rotational speed and will prevent the pump from venting at full
speed.
Introduction
1.4Operational features
In addition to the basic start and stop commands, the nEXT pumps have several other features which allow you to
tailor the pump operation to your particular application. Refer to Table 14 for factory default settings of the
parameters discussed in the following Sections.
1.4.1Power limit setting
You can select the maximum power that will be drawn by the pump (refer to Section 4.1.1). The more power you
supply, the quicker the pump will accelerate to reach full speed. Therefore if your application requires fast cycling,
you should set the power limit to the maximum value. If ramp time is not important in your application, you can use
a lower power limit, down to a minimum value, refer to Table 1.
Tab l e 1 - Pow er li mi ts
PumpStandard default setting
nEXT240, nEXT300 & nEXT400160 W200 W50 W
You must make sure that the power supply you use is capable of delivering sufficient power to the nEXT pump. By
choosing a lower power limit setting, you could use a smaller power supply. For more information, refer to
Section 2.7.
1.4.2Standby speed
Maximum value
setting
Minimum value setting
In Standby mode the pump rotational speed is lower than the full rotational speed. The default setting for standby
speed is 70% of full speed. Note that in order for standby speed to be selected, the pump must also be in the start
condition.
If your application does not require the pump to be running at maximum speed at all times, you can use the Standby
speed feature rather than switching the pump off. This feature can be used for vacuum system tuning or as a system
power saving option.
The Standby speed is a user-selectable value (refer to Section 4.1.4).
1.4.3Timer
When the pump is started, an internal timer is automatically started within the drive electronics. The default timer
setting is 8 minutes. If the pump fails to reach 50% of full rotational speed within the timeout period, the controller
will signal a Fail and will decelerate the pump to rest. This feature prevents the controller from driving the pump at
maximum power for a long time. The pump may fail to reach 50% speed if the gas load is too high (for example if
there is a leak in the system), if the backing pump fails, or if the pump is too hot.
The timeout period is a user-selectable feature (refer to Section 4.1.6), so if your application requires the pump to
ramp up slowly, you can extend the timeout period. The Timer is permanently enabled for ramp-up.
The Timer has an additional function: if the pump rotational speed drops below 50% full speed for any reason, you
may wish to allow the pump time to recover rather than trigger a Fail condition. The Timer starts as soon as the speed
drops to below 50% full speed. If, during the timeout period, the pump recovers to above 50% full speed then the
Timer will be reset. If the pump rotational speed fails to recover by the end of the timeout period, the controller
will trigger a Fail condition and will decelerate the pump to rest. When you receive the pump, the Timer function
will be enabled, however you can disable it if you wish to. With the Timer disabled, the pump will Fail and decelerate
to rest as soon as pump rotational speed falls below 50%.
1.4.4Analogue output
The pump controller produces an analogue output that allows you to monitor four different system parameters:
The analogue output signal ranges from 0 to 10 V and is directly proportional to the system parameter (refer to
Section 2.8).
Connect the analogue output to a suitable meter or indicator to display the appropriate system parameter or connect
to your control equipment (for example, to operate other components in the pumping system at preset values).
You can only monitor one system parameter at a time using the analogue output. However, it is easy to configure the
controller to monitor a different system parameter (refer to Section 4.1.7).
1.4.5Automatic vent options
An Edwards TAV vent valve can be connected directly to the nEXT pump’s controller. The controller is capable of
providing a number of different venting options.
The drive electronics can control the rate of venting. Using this feature the pump can be vented from full rotational
speed in a controlled manner that will not damage the pump bearings. Once the pump rotational speed has dropped
to below 50% of maximum speed, it is safe to hard vent (open the vent valve fully.)
There are many venting options available to you, such as:
Hard vent when rotational speed drops below 50%
Controlled vent when above 50% speed and hard vent below 50% speed
Hard vent immediately through a suitable restrictor
Edwards and the Edwards logo are trademarks of Edwards Limited.
B800-00-880 Issue A
A full list of the venting options is given in Section 3.8
In addition there is a feature that allows a delayed start of the nEXT pump. With this feature you can close the vent
valve before you start the nEXT pump. This allows the backing pump to reduce the pressure in the vacuum system
before starting the nEXT pump.
If you do not wish to use the controller to control a TAV vent valve, you could use it to run a fan instead. You can
configure the controller so that the fan is permanently enabled.
1.4.6Normal speed setting
The Normal Speed is a user-selectable parameter that can be set anywhere from 50% to 100% of full rotational speed.
When the pump reaches Normal Speed, a signal is available on the Normal pin of the logic interface connector. You
can use this signal to control your application since it shows that pump speed, and therefore vacuum performance,
has reached a specific minimum level. The default setting is 80% of full rotational speed. Refer to Section 4.1.5 for
instructions on altering the Normal Speed setting.
1.5Logic interface
The pump controller can only be operated through the logic interface. The signals on the logic interface are of three
types:
Introduction
Control inputs: these are switch-type signals that are used to control the pump
Status outputs: these outputs identify the status of the system
Analogue output: this provides a 0 – 10 V output for a number of pump parameters.
The logic interface has been designed to support both serial and parallel control and monitoring, operating through
one connector. For serial control either RS232(default) or RS485 can be selected using a slide switch located on the
controller (see Section 3.7).
The logic interface can be plugged directly into the Edwards TIC Turbo Controller or TIC Turbo Instrument Controller
and then use the functionality that they provide. Alternatively, the logic interface can be connected to a customers
own control system. The most useful arrangements are described in the sections below.
For more information about the logic interface, refer to Section 2.8.
1.5.1Parallel control and monitoring
The simple parallel interface is a quick and easy way to control the pump; this is the same interface used on existing
24V Edwards Turbo Pumps. The controls that are available to use are Start and Standby. You can monitor the system
status using the Normal, Fail and Analogue output signals.
Note:The Serial Enable switch MUST be open (no connection) and the slide switch must be in the RS232 position
(see Section 3.7).
Refer to Section 3.6 for more detailed instructions of how to use the parallel interface.
A system operating with only a parallel connection has no facility to adjust the configuration settings stored in the
controller(for example, power limit setting or controlled venting options). This would place a restriction in that all
these features would be at their factory default settings. It is possible to manually adjust the standby speed if standby
mode is selected. However, the Controller could be configured separately before fitting the nEXT pump to the
system. This is covered in more detail in Section 1.5.5.
1.5.2Serial control and monitoring
The serial communications link provides complete control and monitoring by using just three signal lines. The Serial
data lines share the same connector pins as the parallel signals Standby and Fail. The serial data lines can be
configured to provide an RS485 compliant or RS232 compatible interface by setting the position of the slide switch
(see Section 3.7)
Th e S erial En a ble signa l M UST be li n k ed to 0 V f o r t he syst e m to accep t c ommands f r o m the ser i a l link. T h i s is a safe t y
feature and acts as an interlock. For pure serial control the parallel start signal will be left unconnected.
The controller will still provide the Normal and Analogue signals on the logic interface connector even when operating
under serial control. The status of the Normal signal and the value of the system parameter on the analogue output
can also be obtained by interrogating the system status via the Serial link.
For more information about the Serial interface, refer to Section 3.7.
1.5.3Serial control with parallel monitoring
Since Normal and Analogue signals remain available even using Serial control, it is possible to control the pump via
the Serial link whilst monitoring these signals in the parallel interface.
The serial link uses the same connector pins as the parallel signals Standby and Fail respectively so these parallel
control and monitoring signals are not available. The Serial Enable signal MUST be linked to 0 V and the parallel start
signal will be left unconnected.
1.5.4Parallel control with serial monitoring or serial configuration
This method of control is best for users who normally wish to operate the pump in parallel mode but occasionally
want to adjust the configuration settings stored in the Controller or to monitor operational status of the pump via
the serial link.
Whilst operating under parallel control with the serial link active, the start control signal is available (as described
in Section 1.5.1.) but the standby control line is not since it is used as a serial data line.
The Serial Enable signal must be linked to 0 V for serial communications to take place. We suggest that you make a
special cable for serial communications that includes a link between Serial Enable and 0 V. This way, Serial Enable
is automatically activated when the cable is connected and then deactivated when the cable is removed.
1.5.5Controller configuration (serial set-up)
All the configuration settings stored within the Controller are retained even when power to the nEXT pump is
removed. This means that it is possible to use a separate system to configure the Controller before fitting the nEXT
pump to your application. This gives the benefit of tailoring the pump functionality to a customer application and
allows the pump to be operated using a simple parallel interface system.
To configure the nEXT pump, either use your own simple serial system or use the Edwards TIC Turbo Controller or
Turbo Instrument Controller. The TICs have a feature which allows storage of a nEXT pump’s configuration. The
configuration can then be downloaded to another nEXT pump. This is useful when configuring a number of nEXT
pumps with the same settings before they are fitted to a system.
Note:The RS485/RS232 slide switch must be in the (default) RS232 position if the TIC is to be used to configure
the nEXT pump. Refer to Section 3.7.1.
TM
The TIC is supplied with a Windows
PC. The program has a simple user interface which means that it is not necessary to use the ASCII message protocol
described in Section 3.7. The TIC PC Program has a facility to save multiple nEXT pump configurations which can then
be downloaded into other nEXT pumps.
based PC program which allows the nEXT pump to be configured from a single
Edwards and the Edwards logo are trademarks of Edwards Limited.
2Technical data
WARNING
WARNING
WARNING
WARNING
2.1General
Tab l e 2 - G ene r al da ta
General itemsReference data
PerformanceRefer to Table 3, 4 and Figure 1
DimensionsRefer to Figure 3, 4 and 5
Maximum inlet-flange temperature
nEXT24075°C
nEXT300 80°C
nEXT400 70°C
Maximum permitted external magnetic field5mT Radial*
B800-00-880 Issue A
Technical data
Pollution degreeEN61010 Polution degree 2
Equipment typeFixed equipment, for indoor use only
Enclosure protection (installed)IP40
*Reduce gas load when operating in magnetic field
2.2Pumping media
Vent dangerous gases and gas mixtures safely, do not expose people to these gases. If pumping
hazardous gases or vapours, observe the safety recommendations of the supplier of the gas/
vapour.
Do not use the nEXT pump to pump pyrophoric or explosive gas mixtures, as it is not suitable for
this purpose. The pump and its connections are not designed to contain an explosion.
In the interstage and booster versions of the nEXT pumps, gas pumped through the interstage port
will mix with gas pumped through the pump inlet. Ensure that the gases will not react or combine
to form dangerous gases and substances.
Do not exceed the maximum continuous operating pressure. Doing so can result in dangerous rotor
temperatures and will shorten the life of the pump.
Do not expose any part of the human body to vacuum.
Do not use a nEXT pump to pump mercury vapour and do not allow mercury (for example, from a McLeod gauge)
to come into contact with the pump. If you do, the pump rotor may corrode and fail.
Note:Concentrations of gases may be modified by the compression of the pump.
The pumps are designed to pump the following residual gases normally used in high-vacuum systems:
You can use the pump to pump oxygen and water vapour, subject to the following conditions:
Oxygen – when the pump is purged by an inert gas, oxygen can be pumped at concentrations above 20% by
volume. Refer to Section 2.4 for Purge gas specification. However, if the pump is not purged, the oxygen
concentration must be less than 20% by volume.
Water vapour - you must ensure that vapour does not condense inside the pump; refer to Section 3.9.3.
If you wish to pump a gas not in the list above, contact your supplier for advice. If you do not contact your supplier,
you may invalidate the warranty on the pump. The pump is not suitable for pumping aggressive or corrosive gases.
Table 3 - nEXT 240 pumps technical data
Parameter
nEXT240D
ISO100
nEXT240D
CF100
nEXT240T
ISO100
nEXT240T
CF100
Mass5.7kg8.8kg6kg9.1kg
Inlet FlangeDN100ISO-KDN100CFDN100ISO-KDN100CF
Outlet FlangeDN25NWDN25NWDN25NWDN25NW
Vent Port1 / 8 inch BSPP1 / 8 inch BSPP1 / 8 inch BSPP1 / 8 inch BSPP
Purge Port1 / 8 inch BSPP1 / 8 inch BSPP1 / 8 inch BSPP1 / 8 inch BSPP
Operation attitudeVertical and upright to horizontal ±2
o
Normal Rotational Speed60,000 revolutions per minute
Starting Time to 90% Speed
‡
125 sec150 sec160 sec190 sec180 sec210 sec
Sound Pressure Level (1 metre away)< 45 dB(A) ± 3dB(A) Declared dual number noise emission values in accordance with ISO4871
*
Values for maximum continuous inlet pressure obtained using a RV12 backing pump at sea level in negligible magnetic field. Values for maximum
continuous backing pressure obtained under no flow conditions at sea level in negligible magnetic field. Refer to Section 3.9 for cooling conditions.
Above these pressures, rotational speed drops below nominal.
†
Cooling water temperature 15oC at a flow rate of 30l hr-1.
Edwards and the Edwards logo are trademarks of Edwards Limited.
B800-00-880 Issue A
2.3Vent gas specification and vent control data
Although the pump may be vented to atmosphere, high relative humidity of the air may greatly increase the
subsequent pump-down time. To reduce pump-down times you should vent with dry, clean gases. Refer to Section 3.8
for a description of the vent options and the vent valve connection refer to Section 4.1.3 for configuring the venting
options.
Table 8 - Vent gas specification and vent control
Vent gas specification and controlReference data
Vent gasDry air, nitrogen, argon or other inert gases
Maximum dew point at atmospheric pressure-22 °C
Maximum size of particulates1
Maximum concentration of oil0.1 parts per million
Recommended time for rotational speed to reach 50%> 15 seconds
Maximum allowed rate of pressure riseRefer to Figure 5
Figure 6 - Maximum allowed rate of pressure rise during venting: pressure against time (with pump initially at
Purge gasDry air, nitrogen, argon or other inert gases
Maximum dew point at atmospheric pressure-22 °C
Maximum size of particulates1
Maximum concentration of oil0.1 parts per million
Allowable purge gas flow (when required)20 to 50 sccm (0.33 to 0.84 mbar l s
Recommended purge gas flow25 sccm (0.42 mbar l s-1, 42 Pa l s-1)
Maximum allowable purge gas supply pressure1 bar (gauge); 14.5 psig, 2 x 105 Pa
Table 10 - Cooling water specification
Cooling water specificationReference data
QualityMechanically clean and optically clear with no deposits
pH value6.0 to 8.0
Maximum calcium carbonate concentration75 parts per million
Maximum chloride concentration100 parts per million
Minimum oxygen concentration4 parts per million
Minimum cooling water flow rate (at 15 °C)15 l hr
Water temperature10 to 20°C
Maximum water pressure5 bar (gauge), 73.5 psig, 6 x 10
Materials exposed to cooling-waterNickel plated brass
µm
or turbidity
-1
-1
or 33 to 84 Pa l s-1)
5
Pa
2.5Cooling water
Refer to Table 7 for the cooling water specification corresponds to a typical high-quality drinking water specification.
Check with your water supply authority if you are in doubt about the quality of your supply.
2.6Materials exposed to gases pumped
The following materials and component types are exposed to the gases pumped:
Aluminium alloys, stainless steels, fluoroelastomer and nitrile O-rings, hydrocarbon lubricant, rare earth
magnets, silicon nitride, carbon-fibre reinforced epoxy resin, fire retardant polypropylene, polyamide, PVC,
Titanium, Silicon, Torlon and Ceramic.