Chapter 2: Installation and configuration
20 LaserSense Nano Aspirating Smoke Detector Installers Handbook
The Alarm and Pre-Alarm contacts are connected as normally open and change state upon
alarm conditions.
The NO/NC (normally open/closed) terminal legends for this relay refer to the contact state in
the power‐off/fault condition, not to the “normal operation” condition. Fault relay contacts will
also change over on power‐down.
Use screened cable with screen connected to the detector EARTH terminal.
(3) Remote control input
DIP Switch 7 OFF: connect to PSU fault relay Normally Closed contacts for PSU monitoring.
Note: The INPUT terminals are set by default to monitor the power supply. If power supply
monitoring and ClassiFire Override are not required, fit a wire link across the two terminals to
prevent a fault condition on power-up.
DIP Switch 7 ON: ClassiFire Override will reduce detector sensitivity by 50% while the input
terminals are shorted together, e.g. by a key switch.
Use screened cable with screen connected to the detector EARTH terminal.
(4) External communications terminals
Optional communications card fitted (RS-485 serial communications mode):
Connect Command Module or detector RS-485 (SenseNet)
serial bus to A and B.
Set communications card address switches to identify detector.
Use screened cable. Connect screen to SCREEN terminal. Earth the screen at one end
ONLY (if using a chain of detectors connected to a Command Module, earth the cable screen
at the Command Module only).
Optional APIC card fitted (addressable communications mode):
Connect + and – IN and + and – OUT terminals to fire panel with a communications protocol
compatible with the APIC. Set APIC address switches to identify detector.
In a chain of detectors linked to a Command Module, use a serial communications card in
each detector, each set to an individual address, and communicate with the fire panel via a
single APIC in the Command Module.
Use screened cable with screen connected to the detector EARTH terminal.
WARNING: Electrocution hazard. All connections should be made with the
power turned off.
Power supply connections
The grounded power supply cable should be routed through the metal cable
gland provided, leaving about 1-
1/4
inch (35 mm) of the cable extending from
the bottom of the cable gland. Depending on the type of cable used, it may
be necessary to increase the diameter of the cable with sleeving or insulating
tape to ensure that the cable is firmly held when the cable gland is fully tightened.
Note: If this equipment is part of a fire detection system, power should be
supplied from a supervised UL Listed power supply, designed for fire system use.
To connect the power supply:
1. Remove the Nano detector front cover, and then locate the power supply
terminal block.