0 = None (pXH)
1 = 100
2 = 200
3 = 300
4 = r
5 = r
6 = r
7 = r
TMS System
0 = Standard
1 = T-Variant
2 = T-Variant
+ heated
booster
3 = r
4 = r
5 = r
Gas Module
0 = None (pXH) 6 = Single Mode +
1 = Loadlock (44 slm flow)
(4 slm flow)
2 = Single Mode 7 = Single Mode +
(44 slm flow) (96 slm flow)
3 = Single Mode 8 = Single Mode +
(96 slm flow) (133 slm flow)
4 = Single Mode 9 = Single Mode +
(133 slm flow) (204 slm flow)
5 = Single Mode A = Multi Mode
(204 slm flow) (44 slm flow)
B = Multi Mode
(96 slm flow)
C = Multi Mode
(133 slm flow)
D = Multi Mode
(204 slm flow)
Exhaust
0 = r
1 = Standard
without
check valve.
2 = r
3 = Standard with
check valve.
Seals
0 = r
1 = r
2 =Standard
Pump
Motor
0 = None
1 = 4.5 kW
2 = 7.5 kW
3 = 11 kW
Booster
Motor
0 = None
1 = 1.9 kW
2 = 4.5 kW
3 = 7.5 kW
4 = r
High Voltage
A = None
B = 600G
C = r
D = 1200
E = 1800
F = 3000
G = 4500
H = 6000
Harsh
A = 100
B = 200
C = 300
D = 450
E = 500
Where r = reserved for future use
Special
Features
0 = None
1 = Application Specific
2 = Application Specific
3 = Application Specific
4 = Application Specific
5 = Application Specific
6 = Application Specific
7 = Application Specific
8 = Application Specific
9 = Application Specific
iXL Dry Pumping Systems
ASXXXXXXXX00
Where r = reserved for future use
Booster Size
Low Voltage
0 = None
1 = r
2 = r
3 = r
4 = 1800
5 = 3000
High Voltage
A = None
B = r
C = r
D = r
E = 1800
F = 3000
TMS System
0 = Standard
1 = r
Exhaust
0 = r
1 = Standard
without
check valve.
2 = r
3 = r
Seals
0 = r
1 = r
2 = Standard
3 = EES
Pump
Motor
0 = None
1 = 4.5 kW
2 = 7.5 kW
3 = 11 kW
Booster
Motor
0 = None
1 = r
2= 4.5 kW
3 = 7.5 kW
4 = r
Gas Module
0 = None
1 = Loadlock (4 slm flow)
2 = r
3 = r
4 = r
Dry Pump
0 = None
1 = r
2 = r
3 = 250
4 = r
5 = 500
6 = 750
d
Declaration of Conformity
We, Edwards Limited,
Crawley Business Quarter,
Manor Royal,
Crawley,
West Sussex RH10 9LW, UK
declare under our sole responsibility, as manufacturer and person within the EU authorised to assemble the
technical file, that the product(s)
Low Volt Systems High Volt Systems
(200 - 230V) (380 - 460V)
Where x = 1, 2, 3, 4, 5, 6, 7, 8, 9, A, B, C or D depending on gas module type
Where y=1 means 'no check valve' and y=3 means 'check valve supplied'
to which this declaration relates is in conformity with the following standard(s) or other normative document(s):
EN1012-2: 1997 Compressor and Vacuum Pumps Safety Requirements; Part 2 - Vacuum Pumps.
EN61010-1: 2010 Safety Requirements for Electrical Equipment for Measurement, Control and
Laboratory Use; Part 1 – General Requirements.
EN 61326-1: 2006 Electrical equipment for measurement, control and laboratory use -
EMC requirements (Industrial Location Immunity – Class A Emissions)
EN50581:2012 Technical Documentation for the Assessment of Electrical and Electronic Products
with respect to the Restriction of Hazardous Substances
ANSI/UL 61010-1 and CAN/CSA-C22.2 No. 61010-1, 2
Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory Use, Part 1: General
Requirements
SEMI S2-0709 - Environmental, Health, and Safety Guideline for Semiconductor Manufacturing Equipment
when installed in accordance with the instruction manual supplied with the pump, following the provisions of:
2011/65/EU* Restriction of Certain Hazardous Substances (RoHS) Directive
* i.e. The product(s) contain less than - 0.1wt% for hexavalent chromium, lead, mercury, PBB and PBDE; 0.01wt%
for cadmium - in homogeneous materials (subject to the exemptions allowed by the Directive ). The RoH S
Directive does not legally apply to industrial vacuum equipment until July 2019 (July 2017 for instruments).
Note: This declaration covers all product serial numbers from the date this Declaration was signed
onwards.
22.10.2013, Burgess Hill
Mr Mark Hope, Global Technical Support Manag er Date and Place
nd
Edition July 12, 2004, including revision July 22, 2005 -
This product has been manufactured under a quality system certifie
to ISO9001:2008
P200-02-320 Issue J
Declaration of Conformity
We, Edwards Limited,
Crawley Business Quarter
Manor Royal,
Crawley,
West Sussex RH10 9LW, UK
declare under our sole responsibility, as manufacturer and person within the EU authorised to assemble the
technical file, that the product(s)
Where y = 1 means 'no check valve' and y=3 means 'check valve supplied'
Where z = 1, 2, 3, 5, A or B depending on gas module type for iXL
EN 61326-1: 2006 Electrical equipment for measurement, control and laboratory use - EMC requirements
(Industrial Location Immunity – Class A Emissions)
22.10.2013, Burgess Hill
Mr Mark Hope, Global Technical Support Manager Date and Place
iXL500R AS550zy23300 ASF50zy23300
Where x = 1, 2, 3, 4, 5, 6, 7, 8, 9, A, B, C or D depending on gas module type
to which this declaration relates is in conformity with the following standard(s)
or other normative document(s)
EN1012-2: 1997 Compressor and Vacuum Pumps Safety Requirements. Part 2 - Vacuum Pumps
EN61010-1: 2010 Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory
EN50581:2012 Technical Documentation for the Assessment of Electrical and Electronic Products
ANSI/UL 61010-1 and CAN/CSA-C22.2 No. 61010-1, 2
Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory Use, Part 1: General
Requirements
SEMI S2-0709 - Environmental, Health, and Safety Guideline for Semiconductor Manufacturing Equipment
when installed in accordance with the instruction manual supplied with the pump,
following the provisions of:
2006/95/EC Low Voltage Directive
2004/108/EC Electromagnetic Compatibility Directive
2006/42/EC Machinery Safety Directive
2011/65/EU* Restriction of Certain Hazardous Substances (RoHS) Directive
* i.e. The product(s) contain less than - 0.1wt% for hexavalent chromium, lead, mercury, PBB and PBDE; 0.01wt% for
cadmium - in homogeneous materials (subject to the exemptions allowed by the Directive). The RoHS Directive does
not legally apply to industrial vacuum equipment until July 2019 (July 2017 for instruments).
Note: This declaration covers all product serial numbers from the date this Declaration was signed onwards.
This product has been manufactured under a quality system certified to ISO9001:2008
Use. Part 1 – General Requirements.
with respect to the Restriction of Hazardous Substances
nd
Edition July 12, 2004, including revision July 22, 2005 -
P200-02-720 Issue K
Declaration of Conformity
We, Edwards Limited,
Crawley Business Quarter,
Manor Royal,
Crawley,
West Sussex, RH10 9LW, UK
declare under our sole responsibility, as manufacturer and person within the EU authorised to assemble the
technical file, that the product(s)
Low Volt Systems High Volt Systems
(200-230V) (380-460V)
Where x = 1, 2, 3, 4, 5, 6, 7, 8, 9, A, B, C or D depending on gas module type
to which this declaration relates is in conformity with the following standard(s) or other normative document(s)
EN1012-2:1996, A1: 2009 Compressors and Vacuum Pumps. Safety Requirements.
Part 2 - Vacuum Pumps.
EN61010-1: 2010 Safety Requirements for Electrical Equipment for Measurement,
EN 61326-1: 2006 Electrical equipment for measurement, control and laboratory
EN50581:2012 Technical Documentation for the Assessment of Electrical and Electronic Products
ANSI/UL 61010-1 and CAN/CSA-C22.2 No. 61010-1, 2nd Edition July 12, 2004, including revision July 22, 2005 – Safety
Requirements for Electrical Equipment for Measurement, Control and Laboratory Use - Part 1: General Requirements
and fulfils all the relevant provisions of
2006/42/EC Machinery Directive
2006/95/EC Low Voltage Directive
2004/108/EC Electromagnetic Compatibility (EMC) Directive
2011/65/EU* Restriction of Certain Hazardous Substances (RoHS) Directive
* i.e. The product(s) contain less than - 0.1wt% for hexavalent chromium, lead, mercury, PBB and PBDE; 0.01wt% for
cadmium - in homogeneous materials (subject to the exemptions allowed by the Directive). The RoHS Directive does
not legally apply to industrial vacuum equipment until July 2019 (July 2017 for instruments).
Note: This declaration covers all product serial numbers from the date this Declaration was signed onwards.
22.10.2013, Burgess Hill
Where y = 1 means ‘no check valve’ and y = 3 means ‘check valve supplied’
Control and Laboratory Use. Part 1 - General Requirements.
Use - EMC requirements. (Industrial Location Immunity
- Class A Emissions)
with respect to the Restriction of Hazardous Substances
Mr Mark Hope, Global Technical Support Manager Date and Place
This product has been manufactured under a quality system certified to ISO9001:2008
P200-06-000 Issue C
Declaration of Conformity
We, Edwards Limited,
Crawley Business Quarter,
Manor Royal,
Crawley,
West Sussex RH10 9LW, UK
declare under our sole responsibility, as manufacturer and person within the EU authorised to assemble the
technical file, that the product(s)
Where x = 2 means 'standard booster oilbox evacuation' and x=3 means 'external booster oilbox evacuation'
EN 61326-1: 2006 Electrical equipment for measurement, control and laboratory use - EMC requirements
(Industrial Location Immunity – Class A Emissions)
iXL750R AS56001x4300 ASF6001x4300
to which this declaration relates is in conformity with the following standard(s) or other normative document(s)
EN1012-2: 1997 Compressor and Vacuum Pumps Safety Requirements. Part 2 - Vacuum Pumps
EN61010-1: 2010 Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory
ANSI/UL 61010-1 and CAN/CSA-C22.2 No. 61010-1, 2
Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory Use, Part 1: General
Requirements
when installed in accordance with the instruction manual supplied with the pump,
following the provisions of:
Note: This declaration covers all product serial numbers from the date this Declaration was signed onwards.
Mr Mark Hope, Global Technical Support Manager Date and Place
This product has been manufactured under a quality system certified to ISO9001:2008
Use. Part 1 – General Requirements.
nd
Edition July 12, 2004, including revision July 22, 2005 -
22.10.2013, Burgess Hill
P200-06-620 Issue B
P601-01-100
2020
NWNW
Issue C Original
The Chinese regulatory requirement on the Control of Pollution Caused by Electronic Information Products No. 39
(also known as ‘China RoHS’) mandates that manufacturers of certain categories of electronic products sold in Ch ina
after 1st March 2007 –
Mark the product and packaging
Define the Product’ s Environment Protection Use Period (EPUP)
Provide a Materials Content Declaration.
Product Labels
ProductProduct LabelMeaning
All iXH, iXL500 and
pXH models
Indicates toxic or hazardous substance contained in at least
one of the homogeneous materials used for this part is
above the limit requirement in SJ/T11363-2006.
Environmental Protection Use Period is 20 years.
This is the period in years during which the toxic or hazardous substances or elements contained in this product will
not leak or mutate under normal operating conditions so that the use of such electronic information products will
not result in any severe environmental pollution, any bodily injury or damage to any assets.
The Environmental Protection Use Period is 20 years for this product.
For the purposes of EPUP, normal operating conditions are considered to be use in accordance with the product’s
instruction manual.
Materials Content Declaration for all iXH, iXL & pXH models
Toxic or Hazardous Substances and Elements
Part name
Motor (Mechanical
Booster)
Motor (pump)OOOOOO
Pump & BoosterOOOOOO
Electronics and ControlsOOXOOO
Cooling SystemOOOOOO
Purge SystemOOOOOO
O: Indicates that this toxic or hazardous substance contained in all of the homogeneous materials for this part is below the limit requirement in
SJ/T11363-2006.
X: Indicates that this toxic or hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit
requirement in SJ/T11363-2006.
A20Inverter diagnostic display text ......................................................................................73
Associated publications
Publication titlePublication number
Vacuum Pump and Vacuum System SafetyP400-40-100
Semiconductor Pumping Application GuideP411-00-090
Trademark Credits
Han® is a registered trademark of Harting Electric GmbH
EtherCon® is a registered trademark of Neutrik® AG
Fomblin® is a registered trademark of Solvay Solexis SpA
Edwards and the Edwards logo are trademarks of Edwards Limited.
M561-00-880 Issue C
CAUTION
WARNING
1Introduction
1.1Scope and definitions
This manual provides installation, operation and maintenance instructions for the Edwards iXH, iXL and pXH dry
pumping systems. You must use your pumping system as speci fied i n th is man ual otherw is e the protecti on provided
by the equipment may be impaired.
Read this manual before you install and operate your pump. Important safety information is highlighted as WARNING
and CAUTION instructions; you must obey these instructions. The use of WARNINGS and CAUTIONS is defined below.
Warnings are given where failure to observe the instruction could result in injury or death to
people.
Cautions are given where failure to observe the instruction could result in damage to the equipment, associated
equipment and/or process.
Introduction
The units throughout this manual conform to the SI international system of units of measurement.
The following warning labels are on the pump:
Warning - Refer to accompanying documentation.
Warning - Risk of electric shock.Warning - Heavy object.
Warning - Hot surfaces.Protective earth (ground).
Warning - Moving parts present.
Warning - Maximum angle between
paired slings
Warning - use protective equipment.RF earth (ground).
The following warnings only appear in this manual:
Warning - Risk of explosion.Warning - pressurised.
Material Safety Data Sheets for chemicals supplied by Edwards can be obtained by contacting Edwards, or on
www.edwardsvacuum.com.
1.2Applications
iXH, iXL and pXH pumping systems are intended for use on the Semiconductor, Solar and FPD processes shown in
Figure 1.
Figure 1 - Applications
iXH, iXL and pXH applications
ALDMetal EtchRTP
HDP-CVDMetrologySACVD
Implant SourceOxide etchSilicon Etch
LithographyPECVDStrip/Ashing
Load lockPVD Pre-CleanTransfer
LPCVDPVD Process
MOCVDRTA
The iXL systems are intended for use on clean duty applications.
If you use the system on an application for which it is not suitable, you may invalidate your warranties. If in doubt,
contact Edwards who will advise you as to the suitability of the system for any particular application.
1.3Description
The iXH dry pump range has been developed to m ee t the demanding requirements for process pumping solutions in
the Semiconductor, Flat Panel and Solar industries. The range se ts new standards for harsh process capability,
reliability and reduced cost of ownership in lo w footprint packages.
The iXL pump range has been developed to meet cyclic loadlock duty applications used in the flat panel and solar
industries.
The pXH booster systems are not intended for use as stand-alone units. Each system must be backed using a suitable
Edwards dry pump selected to match process and performance specifications.
1.4Priority of control
The pumping system can be controlled by a number of modules: the front control panel (refer to Figure 2), a Pump
Display Terminal (PDT), the Edwards System Controller or by the tool through the MicroTIM or one of the serial
interfaces. Only one of these can have control of the system at any one time. That is, once one of these has control
of the system, control requests from the others are denied.
In addition to the control modules listed above, the pXH proximity booster can control or be controlled by the
Edwards backing pump. C ontact Edwards for more information on how to control a pXH using an iXH or other Edwards
pumping system.
The PDT indicates who is in control. LEDs are also provided on the rear pane l, front panel or PDT, which illuminate
to indicate 'in control'.
Edwards and the Edwards logo are trademarks of Edwards Limited.
M561-00-880 Issue C
Item
Control/connector
identification
1EMS button
2Running LED (green)
3Start button
4Stop button
5Local control button
6Local control LED (green)
7Power LED (green)
8Warning LED (amber)
9Alarm LED (red)
10Green Mode LED (green)
11PDT (Pump Display Terminal)
connection
Item
Control/connector
identification
1Front panel control
2Levelling feet (4 off)
3Castors (4 off)
4Seismic bracket (4 off if
fitted)
5Pumped gas inlet connection
6RF Earth (ground) cable
7Extraction port
8Lifting eyebolts (4 off)
1.5Active utility control
The Active Utility Control (Green Mode) function reduces utility consumption of the system while on stand-by. The
Green Mode functionality is controlled by the on/off process signal from the Tool Interface Module. Contact Edwards
for advice on application and activation.
Figure 2 - The front panel controls
Introduction
Figure 3 - Front view of pumping system
Note:iXH 100, iXH 200H and iXH 610 variants have only two eyebolts provided for lifting.
1Ethernet LAN LED (green)
2Ethernet link LED (yellow)
3Ethernet connection
4Power LED (green)
5System interface
6Warning LED (yellow)
7Running and Alarm LEDs (2 colours,
either green or red)
8Accessory interface
9MicroTIM in control LED (green)
Edwards and the Edwards logo are trademarks of Ed wards Limited.
2Technical data
2.1General technical data
Table 1 - General technical data
Characteristics
Body dimensions
Pump
UnitsmmkgdB(A)mm/skg forcekg forcemm
iXH100784 x 390 x 526260< 70< 1.5< 20< 4ISO63NW40105
iXH200H901 x 390 x 526287< 70< 1.5< 20< 4ISO63NW40105
iXH450H1000 x 517 x 650455< 70< 1.5< 20< 10ISO63NW40105
iXH500H1000 x 517 x 650490< 70< 1.5< 20< 10ISO63NW40105
iXH610784 x 390 x 780355< 70< 1.5< 20< 4ISO100NW40105
iXH1210/H784 x 390 x 780413 - 430< 70< 1.5< 20< 4ISO100NW40105
iXH1220H/T901 x 390 x 780455 - 460< 70< 1.5< 20< 4ISO100NW40105
iXH1820/H/T901 x 390 x 780471 - 487< 70< 1.5< 20< 4ISO160NW40105
iXH3030/T915 x 517 x 966619 - 624< 70< 1.5< 20< 10ISO160NW40105
iXH3045H1000 x 517 x 96677670< 1.5< 20< 10ISO160NW40105
iXH3050H1000 x 517 x 96681170< 1.5< 20< 10ISO160NW40105
iXH4545HT1000 x 517 x 96681470< 1.5< 20< 10ISO200NW40105
iXH4550HT1000 x 517 x 96684970< 1.5< 20< 10ISO200NW40105
iXH6045H/T1080 x 517 x 966860 - 86574< 1.5< 20< 10ISO250NW40105
iXH6050H/T1080 x 517 x 96689970< 1.5< 20< 10ISO250NW40105
pXH45001086 x 517 x 531400< 70< 1.5< 20< 10ISO200ISO160-
pXH60001086 x 517 x 531435< 70< 1.5< 20< 10ISO250ISO160-
iXL250Q1092 x 390 x 830515<64<1.5<20<10ISO160NW40105
iXL500Q1186 x 517 x 966860< 70< 1.5< 20< 10ISO160NW50105
iXL500R1186 x 517 x 966874< 70< 1.5< 20< 10ISO160NW50105
iXL750Q1622 x 517 x 1031918<70<1.522<10ISO160NW50105
iXL750R1622 x 517 x 1031976<70<1.522<10ISO160NW50105
*
Contact Edwards for installation drawings
†
Measured in laboratory on level concrete surface
Edwards and the Edwards logo are trademarks of Edwards Limited.
ItemDescriptionRatingUnits
Operating conditions
Materials in contact with process gas
Degree of protection provided by
enclosure
Length x Width x
Height
(excludes exhaust
enclosure)
*
Mass
(excluding
packaging)
Intended useIndoor
Ambient temperature range:
Operating5 to 40°C
Storage-45 to 55°C
Maximum relative humidity: 80% for temperatures up to 31 °C decreasing linearly to 50% relative
Maximum operating altitude2000m
Pollution degree2 (IEC 61010)
Pump, shaft and rotorsCa st Iron, Steel
SealsPTFE and fluoroelastomer
Gas systemStainless steel, aluminium, brass, PTFE and fluoroelastomer
Enclosure protection when installed IP21D (IEC60529)
Edwards and the Edwards logo are trademarks of Ed wards Limited.
2.2Performance data
Table 3 - Performance data
Characteristics
Pump
Unitsm
Typical peak pumping speed
3
/hmbarmbar
iXH100100< 3 x 10
iXH200H215< 3 x 10
iXH450H500< 3 x 10
iXH500H500< 3 x 10
iXH610665< 5 x 10
iXH1210/H1025 - 1065< 5 x 10
iXH1220H/T1200 - 1250< 5 x 10
iXH1820/H/T1700 - 1900< 5 x 10
iXH3030/T2750 - 2900< 5 x 10
iXH3045H3225< 5 x 10
iXH3050H3200< 5 x 10
iXH4545HT4450< 5 x 10
iXH4550HT4220< 5 x 10
iXH6045H/T5000 - 5200< 5 x 10
iXH6050H/T5000 - 5200< 5 x 10
pXH4500N/A< 5 x 10
pXH6000N/A< 5 x 10
iXL250Q1900< 1 x 10
iXL500Q2150< 5 x 10
iXL500R3100< 5 x 10
iXL750Q2300< 1 x 10
iXL750R3450< 1 x 10
*
Speed may be limited
†
Ultimate achieved when pXH used in conjunction with an appropriate backing pump. Please contact Edwards to discuss your application. The pXH does not
have a shaft seal purge.
Edwards and the Edwards logo are trademarks of Edwards Limited.
Note:If you are not sure which gas module is fitted to your system, find the product code number on the label on the rear of the pump and then refer to the
product configurators at the start of this manual.
Table 6 - Gas module types and flows
For iXH systems:
Gas module
type
LoadlockShaft seal only44-----
Single mode
Single mode +
Multi mode
*
Contact Edwards
Note:H variant pumps fitted with Single Mode+ modules include the innovative Gas Buster
Description
Gas ballast purge with harsh/medium
manually selected
Gas ballast purge with harsh/medium
manually selected + inlet purge
Gas ballast purge with electronically selected
harsh/medium + inlet purge + exhaust purge
Module
sizes
available
444428---slm
969656---slm
13313388---slm
204204133---slm
44442860--slm
969656122--slm
13313388173--slm
204204133264--slm
4444226094110slm
969634122146172slm
13313365173183223slm
204204
Total fl ow,
harsh
setting
Total flow,
medium
setting
*
TM
inlet purge for improved powder handling.
Total flow
with inlet
purge
264254314slm
Total fl ow
with
exhaust
purge
Total flow
with inlet
and exhaust
purge
Units
M561-00-880 Issue C
For iXL systems:
iXL systems are designed for use on clean applications only.
Dry pump motor rating7.511112222kW
Mechanical booster motor rating4.57.57.57.5705kW
Current rating (200 - 230 V systems)387563140135A
Current rating (380 - 460 V systems)2040327874A
Recommended branch circuit fuse UL (200 - 230 V
systems)
Recommended branch circuit fuse IEC (200 - 230 V
systems)
Recommended branch circuit fuse UL (380 - 460 V
systems)
Recommended branch circuit fuse IEC (380 - 460 V
systems)
Min cable size for 200 - 230 V systems (or corresponding
AWG size)
Min cable size for 380 - 460 V systems (or corresponding
AWG size)
Mains connector for 200 - 230 V systemsHan
Mains connector for 380 - 460 V systemsHan® K 4/4Han® 100 A
†
The minimum geometric wire gauge for Han® 100A module is 10mm² and minimum AWG size is 6 AWG
Supply voltage 3-phaseeither 200 - 230 or 380 - 460 (see rating plate)V a.c.
Frequency50/60 Hz
Wiring configuration3 wire plus earth (ground)
Branch circuit protection requirementCurrent rating, refer to Table 7Fuse Class gG (IEC 60269), UL class T, class J or class RK5, Bussmann type JJS or equivalent
Voltage tolerance range+/- 10%
Installation categoryII (IEC 60664)
Input supply voltage unbalanceShould not exceed 2% when assessed over any one minute period
Short circuit current rating (when installed with
Edwards and the Edwards logo are trademarks of Edwards Limited.
class T or class J fuses)
Second protective earth (ground) conductorMust be fitted with cross-sectional area at least equal to phase conductor size up to 16 mm
Maximum permitted overcurrent protection for
systems with the Han
for 200 - 230 V systems60A
for 380 - 460 V systems35A
Typical earth leakage
For 200 - 230 V systems
- for iXL750Q and iXL750R
- for all other systems
For 380 - 460 V systems
- for iXL750Q and iXL750R
- for all other systems
*
If you use overcurrent protection above the ra tings in Table 7 for systems with the Han® K 4/4, the minimum cable sizes no longer apply and you must
ensure that the pump cable size is appropriately rated and in accordance with local legislation and electrical regulations. Ensure that cable size is
compatible with the mains connector, refer to Table 9.
†
Typical earth leakage values were measured at steady-state conditions.
Note that higher leakage currents ma y occur:
i) under transient conditions such as power on or pump acceleration or
ii) with abnormal supply configurations such as a missing or earthed phase or unbalanced supply voltages.
®
K 4/4 mains connector
†
2
t characteristic rate d to 600 V
I
200kA
*
9
<5
18
<10
Table 8 - General electrical data
2
mA
mA
mA
mA
M561-00-880 Issue C
Contact Edwards for more information about configuration requirements for earth leakage reduction.