Duke SWFM Installation Manual

0 (0)

BY

WATER

WASH

VENTILATOR

OWNER’S

MANUAL

Please read this manual completely before attempting to install, operate or service this equipment.

This manual is Copyright © 2010 Duke Manufacturing Co. All rights reserved. Reproduction without written permission is prohibited. Duke is a registered

trademark of the Duke Manufacturing Co.

Southern Engineering

A Division of Duke Manufacturing Co.

2305 N. Broadway

St. Louis, MO 63102 Phone: 314-231-1130 Toll Free: 1-800-735-3853 Fax: 314-231-5074 www.dukemfg.com

P/N 0058619

Water Wash Ventilator Owner’s Manual

IMPORTANT WARNING AND SAFETY INFORMATION

POST IN A PROMINENT LOCATION instructions to be followed in the event the user smells gas. This information shall be obtained by consulting the local gas supplier.

FOR YOUR SAFETY:

Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance.

WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.

INSTALLATION INSTRUCTIONS

Units shall be installed by qualified personnel in accordance with all local and municipal codes.

Wiring Diagrams are provided with equipment as supplied.

Exhaust and supply air flow rates shall be in accordance with NFPA96-UL requirements.

Exhaust and supply (if provided) air flow rates were established under controlled laboratory conditions, and greater and/or lesser air supply may be required for complete vapor and smoke removal in specific installations.

THIS MANUAL MUST BE RETAINED FOR FUTURE REFERENCE

2

Water Wash Ventilator Owner’s Manual

TABLE OF CONTENTS

 

LIMITED WARRANTY..........................................................................................................................

5

OWNER’S REGISTRATION REFERENCE SHEET............................................................................

6

INSTALLER: FILL OUT THIS FORM, DETACH AND PUT WITH THE

 

START-UP REPORT TO BE SENT TO SOUTHERN ENGINEERING................................................

7

GENERAL INFORMATION..................................................................................................................

9

PRINCIPLES OF OPERATION............................................................................................................

9

CONTAMINANT CAPTURE.........................................................................................................

9

GREASE EXTRACTION..............................................................................................................

9

AUTOMATIC CLEANING...........................................................................................................

10

FIRE PROTECTION CYCLE......................................................................................................

11

Standard Push Button Control............................................................................................

11

SEQUENCE OF OPERATION...........................................................................................................

12

STANDARD CONTROL PANEL.................................................................................................

12

Wash Cycle Procedure.......................................................................................................

12

Fan Cycle...........................................................................................................................

12

MODE COMMANDER................................................................................................................

13

FIRE SUPPRESSION SYSTEMS......................................................................................................

13

APPLIANCE PROTECTION.......................................................................................................

13

DRY AND WET CHEMICAL SYSTEMS.....................................................................................

13

WATER FOG SYSTEM..............................................................................................................

14

WATER WASH FIRE SUPPRESSION.......................................................................................

14

COMPONENT IDENTIFICATION AND ACCESS..............................................................................

16

STANDARD CONTROL CABINET ............................................................................................

16

Push Button Control...........................................................................................................

16

ELECTRICAL COMPARTMENT................................................................................................

17

PLUMBING COMPARTMENT....................................................................................................

19

EXTERNALLY MOUNTED COMPONENTS......................................................................................

22

VENTILATOR MOUNTED COMPONENTS AND ACCESS PANELS................................................

23

WATER WASH MAINTENANCE PROCEDURES.............................................................................

26

DETERGENT SYSTEM.............................................................................................................

26

Water Wash Detergent Pump Replacement.......................................................................

26

Start-up of the Detergent Pump Assembly.........................................................................

28

Care and Adjustments........................................................................................................

28

Gaskets and Check Valves.................................................................................................

29

Detergent Reservoir...........................................................................................................

29

3

Water Wash Ventilator Owner’s Manual

 

Service and Repairs...........................................................................................................

30

Pump Head Assembly or Diaphragm.................................................................................

30

Ball Check and Valve Seat Replacement...........................................................................

31

Approved Detergents.........................................................................................................

31

Water Wash Hood Detergent/Water Consumption Chart...................................................

32

EXTERNALLY MOUNTED COMPONENTS......................................................................................

33

REMOTE FIRE PULL.................................................................................................................

33

VACUUM BREAKER..................................................................................................................

33

WASH SOLENOID VALVES.......................................................................................................

34

DAMPER MOTOR......................................................................................................................

35

WASH NOZZLES.......................................................................................................................

35

TROUBLESHOOTING.......................................................................................................................

36

WIRING SCHEMATICS.....................................................................................................................

41

MODE COMMANDER FOR ONE VENTILATOR.......................................................................

41

MODE COMMANDER FOR TWO VENTILATORS....................................................................

42

MODE COMMANDER FOR THREE VENTILATORS................................................................

43

MODE COMMANDER FOR FOUR VENTILATORS..................................................................

44

STANDARD WIRING DIAGRAM FOR VENTILATOR (OLD STYLE).........................................

46

PREVENTIVE MAINTENANCE CHART............................................................................................

47

SERVICE AND ORDERING INFORMATION.....................................................................................

48

WATER WASH VENTILATOR REPLACEMENT PARTS LIST..........................................................

49

CUSTOMER ASSISTANCE...............................................................................................................

51

4

Water Wash Ventilator Owner’s Manual

LIMITED WARRANTY

Southern Engineering Systems products are warranted to be free from defects in material or workmanship for a period of one year from the date of start-up or 18 months from the date of shipment (whichever comes first) when installed, operated and serviced in accordance with the Southern Engineering Systems recommendations, when used under normal conditions for their intended purposes; and when evidence of such installations, proper and acceptable to Southern Engineering Systems, are recorded at the factory. Southern Engineering Systems reserves the right to void this warranty for operations of its product outside of these terms.

Southern Engineering shall further warrant motorized conveyor drive components (consisting of motor, gear reduction unit, track glide wear surfaces, speed controller, bearings, shaft(s)) for an additional 48 months after the expiration of the above described one-year warranty. This additional warranty does not apply to renewable parts such as drive chains or gears, or the belting; and is for parts replacement only if these motorized conventional conveyor drive components become inoperative due to a defect in factory workmanship or a failure in material utilized in its original operation and maintenance instructions, labor not included.

Any request for repair or replacement must be made to the Service Department of Duke Manufacturing Co., 2305 N. Broadway, St. Louis, MO 63102. Southern Engineering Systems’ warranty shall be limited to repair or replacement (at Duke Manufacturing Co's.option)ofanypartofsaidequipmentthatprovestobedefectiveafteranexaminationbyitsServiceDepartmentordesignate. The labor required to make repairs or replacement under this warranty shall be furnished by Duke Manufacturing Co. or its authorized representative between the hours of 8:00AM and 400 PM Monday through Friday, and is limited to the actual repairs or replacements of the warranty item. Labor and cost of such labor to inspect and/or determine the origin of the problem involving theexaminationofequipmentorsystemsnotfurnishedormanufacturedbySouthernEngineeringSystemsisspecificallyexcluded. Thiswarrantyisonlyforapplicationswhichtheequipmentwasoriginallyinstalled,andonlycoversoriginalequipmentcomponents.

This warranty does not cover routine maintenance (such as but not limited to tightening belts, adjustment of linkage or controls, cleaning, etc.) or replacement of renewable items such as belts, chains, detergent, filters, etc. Malfunctions caused by improper water pressure, electrical power variances, exhaust fan performance (ventilators only), or restricted drainage systems are also excluded from warranty protection. Warranty claims will not be honored unless the manufacturer is advised in advance of the work being performed by an authorized and approved representative of Duke Manufacturing Co.

This warranty does not cover loss of food, other products, or other consequential damage resulting from any equipment failure.

THIS WARRANTY IS THE ONLY WARRANTY; THERE BEING NO OTHER WARRANTY EITHER EXPRESSED OR IMPLIED.

5

Water Wash Ventilator Owner’s Manual

OWNER’S REGISTRATION REFERENCE SHEET

FOR SOUTHERN ENGINEERING SYSTEMS BY DUKE WATER WASH VENTILATORS

(fill out at time of installation)

DO NOT REMOVE FROM THIS MANUAL

Model No._______________________________ Serial No. _______________________________

Customer’s Name:_________________________________________________________________

_________________________________________________________________________________

Address:__________________________________________________________________________

Installer’s Name:___________________________________________________________________

Address:__________________________________________________________________________

Installed At:_______________________________________________________________________

Installation Date:___________________________________________________________________

Remarks:_________________________________________________________________________

_________________________________________________________________________________

_________________________________________________________________________________

6

Water Wash Ventilator Owner’s Manual

INSTALLER: FILL OUT THIS FORM, DETACH AND PUT WITH THE START-UP REPORT TO BE SENT TO SOUTHERN ENGINEERING

WARRANTY REGISTRATION for

SOUTHERN ENGINEERING SYSTEMS BY DUKE WATER WASH VENTILATORS

Model No._______________________________ Serial No. _______________________________

Customer’s Name:_________________________________________________________________

_________________________________________________________________________________

Address:__________________________________________________________________________

Installer’s Name:___________________________________________________________________

Address:__________________________________________________________________________

Installed At:_______________________________________________________________________

Installation Date:___________________________________________________________________

Remarks:_________________________________________________________________________

_________________________________________________________________________________

_________________________________________________________________________________

For Factory Use Only S/O#___________________________________________________________

_________________________________________________________________________________

_________________________________________________________________________________

7

Water Wash Ventilator Owner’s Manual

8

Water Wash Ventilator Owner’s Manual

GENERAL INFORMATION

TO ENSURE PROPER OPERATION AND MAINTENANCEOFTHESOUTHERNENGINEERING BY DUKE WATER WASH VENTILATION SYSTEM, PLEASE READ AND UNDERSTAND THIS MANUAL THOROUGHLY.

When necessary, the following information will be indented and paraphrased.

NOTE: Information pertaining to special instructions regarding the care and use of the Mode Commander.

CAUTION: Information intended to indicate situations which may cause immediate or future damage to the Mode Commander.

WARNING: Advice against improper use or procedures which may result in bodily injury for which Southern Engineering will accept no responsibility.

Allinformation,illustrationsandspecificationscontained inthismanualarebasedonthelatestproductinformation available at the time of printing. Southern Engineering by Duke reserves the right to make changes at any time,withoutnotice,inspecifications,andmodels,also to discontinue models. Southern Engineering by Duke also reserves the right to change any specifications or parts at any time without incurring obligation to equip the same on models manufactured prior to the date of such change.

The continuing accuracy of this manual cannot be guaranteed.

All illustrations used in this manual may not depict modelsorequipmentandareintendedasrepresentative views for reference only.

Future supplement sheets will be added or deleted as necessary.

Prints or system details located in this manual are for instructionalpurposesonlyanddonotrepresentactual or scale drawings.

PRINCIPLES OF OPERATION

CONTAMINANT CAPTURE

The primary purpose of any kitchen ventilator system is to take objectionable odors, grease, steam and dust particles from the cooking surface and transfer them to an un-objectionable area.

The two most important considerations in achieving contaminant capture are air velocity and volume. Becauseonedirectlyaffectstheother,eachwilldetermine how well the ventilator captures contaminants and will be fully explained in a following section of this manual.

GREASE EXTRACTION

Becauseofenvironmentalconcernsandregulations,it is more important than ever before to remove as much grease and unwanted contaminants as possible from the air stream being expelled from the system. The Water Wash Ventilator is one of the most effective in grease removal on the market.

This is accomplished by centrifugal force as the air is drawn through a series of baffles and forced to make turnsduringwhichthegreaseparticlesimpingeuponthe

baffleplates.Thegreasewillremaininsidetheventilator through the duration of the normal cooking cycle.

Centrifugal Grease Extraction

9

Water Wash Ventilator Owner’s Manual

Centrifugal grease extraction is the removal of grease and dust from the air stream by means of centrifugal action without any removable parts, moving parts, or continuous, wasteful water spray.

At the termination of this cycle, the equipment is shut down, and the ventilator will automatically clean the greasefromthesystem.Thisextractionisaccomplished without the use of filter media or moving parts to clog with grease.

Because of this type of extraction, the Water Wash Ventilator is well suited for commercial and industrial applicationsandremovesgreasemuchmoreefficiently than baffle or mesh filter systems.

Extraction Chamber

Thorough cleaning of the extraction chamber interior is achieved by means of a pressurized hot detergent water spray.

Model SWFM Hi-Velocity Wall Style Water

Wash Ventilator With “Lazy Air” Make-up

Chamber

AUTOMATIC CLEANING

The grease and dust that accumulate within the extraction chamber during operation of the ventilator must be removed regularly. If allowed to accumulate for long periods of time, the grease will “bake on” to the interior of the ventilator forming a combustible and difficult to remove coating. To prevent this build up, the Water Wash Ventilator features an automatic cleaning cycle this is initiated each time the exhaust fan is turned off, or at the preset time during which the Water Wash Mode Commander calls for a wash cycle.Wheneitherofthissituationsoccur,theexhaust fan will stop. The ventilator damper will close and the ventilator will be sprayed with a pressurized hot water and detergent combination. The waste water will flow fromthesystemintoanapprovedplumbingdrain.This willbeexplainedindetailintheSequenceofOperations section of the manual.

Spray

Nozzles

Primary

Diverter

Baffle

Southern Wash Extraction Chamber

10

Spray Manifold

Spray Manifold

FIRE PROTECTION CYCLE

STANDARD PUSH BUTTON CONTROL

In the event of a fire in the cooking area under the ventilator, the exhaust ductwork should be protected to prevent the exhaust fan from spreading the fire to the ductwork and the building roof. The Water Wash Ventilatorfeaturesanautomaticfireprotectioncycleto contain fires under the canopy to prevent their spread. The fire protection cycle is automatically initiated by thermostats located in the exhaust air path at the duct collars of the ventilator.

Water Wash Ventilator Owner’s Manual

CoverÊPlate

Thermostat

Mounting

Plate

J-Box

Duct

Collar

Location of Fire Detection Thermostats

As a back up, there is a remote fire pull furnished near a door. When pulled, this device will provide the same results as the automatic fire cycle.

Remote Fire Pull

In case of fire, pull for the instant activation of the Ventilator Fire Cycle.

11

Water Wash Ventilator Owner’s Manual

SEQUENCE OF OPERATION

STANDARD CONTROL PANEL

Contaminantsaccumulatedduringthenormalcooking cycles are washed from the system at the end of each operating cycle. This can be achieved automatically (throughtheusedoftheModeCommander)ormanually by turning OFF the exhausts fans using the Standard Control Panel.

CAUTION: Always turn cooking equipment off 15 minutes prior to shutting down the exhaust system.

This will prevent accidental tripping of the appliance fire suppression system due to heat build-up when the exhaust system is terminated.

WASH CYCLE PROCEDURE

Spray

Nozzles

Damper Door

Extraction

Chamber

Inlet Damper Location

1. Turn off all cooking appliances and allow to cool

• Thewashsolenoidvalvewillopenandthedetergent

for minimum of 15 minutes.

pump will start.

2.

Press the STOP & WASH button.

• Hotdetergentwater(120°F@40psi)willbeinjected

 

 

through the spray nozzles for a predetermined

 

 

period of time.

 

 

• When the wash cycle ends, the wash solenoid

 

 

closes terminating water flow, and the detergent

 

 

pump stops. The inlet damper will remain closed

 

 

awaiting the next fan cycle.

 

 

• When the Mode Commander is furnished, up to

 

 

four wash sequences may be run consecutively.

 

 

FAN CYCLE

Water Wash Ventilator Controller

Push the START button on the Control Panel.

 

The exhaust fan will coast to a stop

• The supply fan (if required) will stop.

• The inlet damper will close.

Water Wash Ventilator Controller

12

The Inlet damper will open.

The Exhaust fan will start.

Ventilatormake-upairsupplywillstart(ifrequired).

Turn on cooking appliances as needed.

CAUTION: Do not turn on cooking appliances if inlet damper is closed or exhaust fan is not running. Failure to comply my result in an accidental fire suppression discharge.

MODE COMMANDER

MANUAL MODE:

VENT #1

ON

Damper opens, fan starts

VENT #1

STOP

Fan stops, damper closes,

 

 

timed wash begins. Wash ends

 

 

after elapsed time, fan remains

 

 

OFF.

VENT #1

WASH

Same sequence as stop

 

 

sequence

VENT #1

FIRE

Upon manual or thermal

 

 

activation, fan stops, damper

 

 

closes, continuous suppressive

 

 

spray initiates. Remains in this

 

 

state until manual deactivated

 

 

by depressing the FIRE

 

 

RESET button.

NOTE: In order to deactivate fire suppression, the temperature in the extraction chamber must be below 325°F.

NOTE: When multiple ventilators are supplied with single fan systems, all sequences are simultaneous with the exception of fire status, which remains individual.

VENT #1: Fan sequence is automatically initiated at programmed times.

NOTE: May be repeated up to three cycles in a 24-hour timeframe.

FIRE SUPPRESSION SYSTEMS

Water Wash Ventilator Owner’s Manual

All Water Wash systems have two separate means of fire suppression built in to protect the ventilator and duct system should a fire occur.

APPLIANCE PROTECTION

This is the first line of defense in the event of a fire. Basically,therearethreetypeswhichwillbediscussed in detail in separate sections of this manual. They are water mist, dry chemical and wet chemical. Each type is designed for one purposes, suppression of out of

control cooking fires.

DRY AND WET CHEMICAL SYSTEMS

The dry chemical and wet chemical systems make use of remote fire pulls, usually located near an exit, which when pulled will activate the chemical solution.

Typical Remote Fire Pull

Theyalsoemployfusiblelinkswhicharelocateddirectly above the cooking equipment.

Fusible Links above Appliances

When one of these links melt, the fire suppression system activates. When activated, wet or dry powder

13

Duke SWFM Installation Manual

Water Wash Ventilator Owner’s Manual

will be sprayed directly on the fire through strategically placed nozzles located above the appliances. Once the chemicals are discharged, the gas valve will be electricallyormechanicallyclosedandtheexhaustand supply fans can be shut down or remain in operations dependent upon local jurisdictional authority. Once these systems are activated, the chemicals must be replaced along with all fusible links which have been affected. Once this is accomplished the gas valve can be reset and normal operation resumed.

WATER FOG SYSTEM

Whenwaterfogsystemsarespecified,therearesome basic differences which that should be noted. The sprinkler nozzles are point of use and do not utilize remote pulls or fusible links.

WATER FOG

NOZZLES

Typical Water Fog System

When a nozzle vial is heated to the designated temperature and breaks, a continuous water spray begins. Unlike chemical systems, all nozzles do not open unless each/all are heated. Water continues to flow until it is manually stopped. As with chemical systems, the gas or electric appliances will be shut down along with the exhaust system as required. All systemsmaybeincorporatedwithautomaticsignaling devices for alarms.

WATER WASH FIRE SUPPRESSION

All Water Wash Ventilators utilize built in methods of fire suppression acting separately of appliance protection.Intheeventafirehasnotbeensuppressed and is drawn into the extraction chamber causing a temperature rise above 325°F (275°F on down draft models), fire-stat contacts will close, sending a signal to the ventilator control panel. The following sequences will occur.

1.The exhaust fan shuts off, stopping the induced draft over the cooking equipment and preventing fire from being pulled into the ductwork.

2.The UL rated damper door at the inlet to the extraction chamber closes and provides a barrier to the fire, preventing a heat induced draft from rising up the exhaust shaft.

3.The water-detergent wash system is activated, releasing its water spray within the ventilator to quench any fire, wash away grease and dust that could support combustion, and cool the damper and extraction chamber, protecting the ventilator from heat damage.

4.The water spay continues until the thermostat(s) cool below 325°F and the FIRE RESET button on the ventilator control panel is reset,

Fire Reset Button on Standard Control

14

Water Wash Ventilator Owner’s Manual

Fire Reset Button on Mode Commander

5. A remote manual fire pull switch is provided for mounting in the exit path of the kitchen area. This switch activates the fire protection cycle. The fire switch (fiber disc or glass bar) must be replaced and the FIRE RESET button pushed before the ventilation system can be restarted. If a remote manual fire switch or other device (such as a fire suppression system) activates the fire protection cycle, this device must also be reset to normal or supervisory status before the FIRE RESETbutton on the control panel will have any effect.

6. The START button on the Control Panel may then be pushed to restart the ventilation system.

15

Water Wash Ventilator Owner’s Manual

COMPONENT IDENTIFICATION AND ACCESS

STANDARD CONTROL CABINET

 

Hot Water Outlet

1/4" Detergent Outlet

 

Solenoid Valve

Hot Water

Terminal

Supply

 

Strip

 

 

Circuit

Board (See separate drawing)

N H H1 7 N1 9

WST

 

SOUTHERN

 

WATER WASH

WSR

VC1

 

12

 

11

 

WT

 

10

 

9

 

38

WR

8

 

7

 

6

 

5

 

4

TR

30

 

20

 

1

 

H1

FR

H

 

G

 

Shutoff Valve

Pressure/Temp.

Gauge

Line Strainer

Shock

Arrestor

Detergent

Pump

DIR

 

Detergent

Pump Test

MPA-3

Container

Switch

Miniature

Detergent Tube Assembly

Pilot

Actuator

w/Foot Valve Strainer

 

This enclosure serves as the fixture for the major electrical and plumbing components utilized by the ventilator system. Basically the cabinet is divided into twosections:Theelectricalcompartmentontheleftside and the plumbing components on the right. For ease in identification the components will be discussed in separate sections: Electrical Compartment, Plumbing Compartment, Externally Mounted Components, and Ventilator Mounted Components.

PUSH BUTTON CONTROL

All system functions are controlled by the Push Button

Control.

START: The green start button is a normally open switch. Momentary contact close the electrical circuit to the damper interlock relay energizing the exhaust fan and blower pilot light.

NOTE: The system must have water pressure to complete the start sequence.

STOP:TheredstopbuttonisaSPDTswitchproviding maintained contact with the start button when not depressed. When depressed, the stop button will stop the exhaust fans, close the inlet damper and initiate the wash cycle.

RESET: The black fire reset button is normally closed. Whenpressed,thefirecyclerelayisopenedterminating a fire cycle.

NOTE: When a fire cycle is initiated the STOP and WASH function will be bypassed

NOTE: All Southern Engineering by Duke fire devicessuchastheremotefirepullandthermostats must be in normal operating condition before the termination of a fire cycle may be achieved.

EXHAUSTFANPILOT(EFP):Illuminatesgreenwhen the exhaust fan is operating, indicating power to the damper interlock relay.

16

Loading...
+ 36 hidden pages