NOTICE: The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment meets certain telecommunications network
NOTICE: The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment meets certain telecommunications network
protective, operational and safety requirements. The Department does not guarantee the equipment will operate to the user's satisfaction.
protective, operational and safety requirements. The Department does not guarantee the equipment will operate to the user's satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be
installed using an acceptable method of connection. In some cases, the company's inside wiring associated with a single line individual service may be extended by means of certified
installed using an acceptable method of connection. In some cases, the company's inside wiring associated with a single line individual service may be extended by means of certified
connector assembly (telephone extension cord). The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
connector assembly (telephone extension cord). The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this
equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
User should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are
User should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are
connected together. This precaution may be particularly important in rural areas.
connected together. This precaution may be particularly important in rural areas.
CAUTION:
CAUTION:
Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection authority, or electrician, as appropriate.
Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection authority, or electrician, as appropriate.
The Load Number
The Load Number
overloading. The termination on a loop may consist of any combination of devices subject only to the requirement that the total of the Load Numbers of all the devices does not
overloading. The termination on a loop may consist of any combination of devices subject only to the requirement that the total of the Load Numbers of all the devices does not
exceed 100.
exceed 100.
The Load Number of this device is 42.
The Load Number of this device is 42.
AVIS:
AVIS:
L'étiquette du ministère des Communications du Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme à certaines normes de
L'étiquette du ministère des Communications du Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme à certaines normes de
protection, d'exploitation et de sécurité des réseaux de télécommunications. Le Ministère n'assure toutefois pas que le matétiel fonctionnera à la satisfaction de l'utilisateur.
protection, d'exploitation et de sécurité des réseaux de télécommunications. Le Ministère n'assure toutefois pas que le matétiel fonctionnera à la satisfaction de l'utilisateur.
Avant d'installer ce matériel, l'utilisateur doit s'assurer qu'il est permis de le raccorder aux installations de l'entreprise locale de télécommunication. Le matériel doit également être
Avant d'installer ce matériel, l'utilisateur doit s'assurer qu'il est permis de le raccorder aux installations de l'entreprise locale de télécommunication. Le matériel doit également être
installé en suivant une méthod acceptée de raccordement. Dans certains cas, les fils intérieurs de l'entreprise utilisés pour un service individuel a ligne unique peuvent être prolongés
installé en suivant une méthod acceptée de raccordement. Dans certains cas, les fils intérieurs de l'entreprise utilisés pour un service individuel a ligne unique peuvent être prolongés
au moyen d'un dispositif homologué de rassordement (cordon prolongateur tèlèphonique interne). L'abonné ne doit pas oublier qu'il est possible que la conformité aux conditions
au moyen d'un dispositif homologué de rassordement (cordon prolongateur tèlèphonique interne). L'abonné ne doit pas oublier qu'il est possible que la conformité aux conditions
énoncées ci-dessus n'empechent pas la dégradation du service dans certaines situations. Actuellement, les entreprises de télécommunication ne permettent pas que l'on raccorde leur
énoncées ci-dessus n'empechent pas la dégradation du service dans certaines situations. Actuellement, les entreprises de télécommunication ne permettent pas que l'on raccorde leur
matériel a des jacks d'abonné, sauf dans les cas précis prévus par les tarrifs particuliers de ces entreprises.
matériel a des jacks d'abonné, sauf dans les cas précis prévus par les tarrifs particuliers de ces entreprises.
Les réparations de matériel homologué doivent etre effectuées par un centre d'entretien canadien autorisé désigné par le fournisseur. La compagnie de télécommunications peut
Les réparations de matériel homologué doivent etre effectuées par un centre d'entretien canadien autorisé désigné par le fournisseur. La compagnie de télécommunications peut
demander à l'utilisateur de débrancher un appareil à la suite de réparations ou de modifications effectuées par l'utilisateur ou à cause de mauvais fonctionnement.
demander à l'utilisateur de débrancher un appareil à la suite de réparations ou de modifications effectuées par l'utilisateur ou à cause de mauvais fonctionnement.
Pour sa propre protection, l'utilisateur doit s'assurer que tous les fils de mise à la terre de la source d'énergie électrique, des lignes téléphoniques et des canalisations d'eau métalliques,
Pour sa propre protection, l'utilisateur doit s'assurer que tous les fils de mise à la terre de la source d'énergie électrique, des lignes téléphoniques et des canalisations d'eau métalliques,
s'il y en a, sont raccordés ensemble. Cette précaution est particulièrement importante dans les régions rurales.
s'il y en a, sont raccordés ensemble. Cette précaution est particulièrement importante dans les régions rurales.
AVERTISSEMENT:
AVERTISSEMENT:
selon le cas.
selon le cas.
L'indice de charge
L'indice de charge
bouclé utilisé par ce dispositif. La terminaison du circuit bouclé peut etre constituée de n'import quelle combinaison de dispositifs, pourvu que la somme des indices de charge de
bouclé utilisé par ce dispositif. La terminaison du circuit bouclé peut etre constituée de n'import quelle combinaison de dispositifs, pourvu que la somme des indices de charge de
l'ensemble des dispositifs ne dépasse pas 100.
l'ensemble des dispositifs ne dépasse pas 100.
L'indice de charge de cet dispositif est 42.
L'indice de charge de cet dispositif est 42.
(LN) assigned to each terminal device denotes the percentage of the total load to be connected to a telephone loop which is used by the device, to prevent
(LN) assigned to each terminal device denotes the percentage of the total load to be connected to a telephone loop which is used by the device, to prevent
L'utilisateur ne doit pas tenter de faire ces raccordements lui-meme; il doit avoir recours a un service d'inspection des installations électriques, ou a electricien,
L'utilisateur ne doit pas tenter de faire ces raccordements lui-meme; il doit avoir recours a un service d'inspection des installations électriques, ou a electricien,
(IC) assigné a chaque dispositif terminal indique, pour éviter toute surcharge, le pourcentage de la charge totale qui peut etre raccordée a un circuit téléphonique
(IC) assigné a chaque dispositif terminal indique, pour éviter toute surcharge, le pourcentage de la charge totale qui peut etre raccordée a un circuit téléphonique
Configuring the Printer _____________________________________________________ 12
Programming the Panel for Use with a Printer _________________________________ 12
• 16 fully programmable supervised zones (EOL resistors)
• Supervised fire zone
• 1 auxiliary normally open zone
• 3 keypad activated zones
Audible alarm output:
• Bell output
700 mA, fused at 5 Amps, 12 V
• Steady or pulsed output
EEPROM memory:
• Does not lose codes or system status on complete AC
and battery failure
Programmable output:
• Transistor switch sinks 50 mA to ground
• Operation controllable through program options
Powerful 1.5 amp regulated power supply:
• 400 mA auxiliary supply, 12 V
• Separately fused for battery, keypad/auxiliary supply and
bell output
• Supervision for loss of AC power, low battery
• Internal clock locked to AC power frequency
Switched Smoke Detector Supply Output:
• Controlled from keypad [Q][4] command
Battery required:
• 12 volt 4 Ah minimum rechargeable gel-cell or sealed
lead-acid battery
DC unregulated
DC unregulated
Remote Keypad Specifications
(PC3000RK)
• Four wire (QUAD) hook-up and up to 3 keypads per
system
• Built-in piezoelectric buzzer
• Full annunciation of zones and system status
• Nominal current draw 60 mA
• Dimensions 5.5” x 4.5” x 1” deep (140 x 114 x 25 mm)
Output Voltage Specification
Typically, with normal AC in and a fully charged battery, the
output voltage will be 13.8 V
discharged battery, the voltage will go to 10 volts. Devices
that require power from the control panel should be capable
of normal operation over the voltage range of 10 to 14 V
DC. With AC off and a
DC.
Digital Communicator Specifications
• 94 reporting codes
• Transmits all 10BPS and 20BPS single line and extended
formats
• Radionics Rounds and Radionics Parity formats
• Sescoa Superfast format
• 3/1, 4/2 and hexadecimal numbers
• DTMF and Pulse dialing
• DPDT line seizure
• True dial tone detection
• Anti-jam feature
• Two telephone numbers and two account codes
• Split reporting of selected transmissions to each
telephone number
Transformer required:
• 16.5 VAC, 40VA
Dimensions:
• 11” x 11.8” x 3.3” deep (279 x 300 x 84 mm)
Weight:
• 6.5 lbs (3 kg)
1
FEATURES
Keypad Programming
The PC3000 comes with a default program so it is
operational with a minimum of programming. It is completely
programmable from the keypad. The panel uses EEPROM
memory so that all information is retained even if the panel
loses both AC and battery power.
Multiple Level Static/Lightning
Protection
The PC3000 has been carefully designed and tested to
provide reliable service. It is built to take static and lightning
induced surges and keep on working. Multiple level surge
filters are on all zone inputs, the power supply, the keypad
connections, the bell output, the auxiliary power supply and
the telephone interface. A special “ZAP-TRAC” circuit
board configuration catches high voltage impulses right at
the wiring terminals. Protective ground planes surround
sensitive areas preventing the spread of damaging voltage
surges. Metal Oxide Varistors (MOV’s) are placed in all the
critical areas to further reduce impulses to safe levels.
”WATCHDOG MONITOR” Circuit
Even when all precautions are taken so that voltage surges
do not cause damage to the control panel, it is possible to
cause temporary disruption to the operation of the
microprocessor causing it to lose track of the program
sequence. The PC3000 is equipped with an external
“Watchdog Monitor” circuit which continually checks the
microprocessor program execution.
Advanced Features
The PC3000 has many advanced features. Features which
provide the security system design flexibility and selling
advantage necessary to win those demanding jobs and
make them profitable.
Some of these features include:
• EEPROM memory retains all data even on complete AC
and battery failure. Panel powers up in last armed or
disarmed state before power loss.
• All programmable zones may be selected as one of 10
different types including; delay, double delay, quadruple
delay, instant, follower, follower with home-away, delay
with home-away, and 4 types of 24 hour emergency and
supervisory circuits.
• Keypad programming of up to sixteen security codes.
• Zone bypassing from the keypad.
• Individual zone and system function indicators on keypad.
• A keypad activated utility output function for operating
lights, door openers, cameras or other devices.
Although the PC3000 has many features, it is not difficult to
use. All keypad commands are similar and are assisted by
audible and visual cues.
System Supervision Features
The PC3000 continuously monitors a number of possible
trouble conditions including:
• An active battery supervision circuit that periodically tests
the battery under load.
• A loss of the AC power supply.
• A supervised circuit trouble condition.
• A telephone line monitoring circuit.
• A bell circuit failure indicates open circuit or fuse failure.
• A test code feature which transmits a communicator test
code to the monitoring station at a selected time
everyday. The test code can be sent at intervals from 1 to
99 days.
• A bell/siren/communicator test feature which can be
activated from the keypad.
• TLM (Telephone Line Monitoring) restoral transmission.
2
INSTALLATION
Bench Testing
The PC3000 contains a factory default program. Any
additional programming required can be done through the
keypad. For many applications all that will be required is to
enter the telephone number and alarm codes with keypad
entries that are as straight forward as dialing a telephone
number. If you need help talk to your DSC equipment
distributor.
Connect 1K ohm 1/2 watt end of line resistors from each
zone (Z1 to Z16) input to the closest common “COM”
terminal. Connect an end of line resistor between the “Fire”
input terminal and the “COM” terminal between “Z1” and
“Z2”. Unless all zone are properly terminated with end of
line resistors the “Ready” light will not be on and the panel
will not arm unless the “Ready” light is on.
Connect the four keypad wires to the control panel as
shown in the connection drawing.
To completely test the PC3000 including the communicator
data, it is necessary to connect the panel to a digital
receiver through a telephone line connection or by
connecting the telephone terminals on the PC3000 to a
digital communicator test set such as the DSC DTS-1. The
DSC DTS-1 digital communicator test set is an inexpensive
unit which can simulate the telephone system dial tone and
the receiver hand shake and kiss-off tones as well as
display the data sent out by a digital communicator. Also,
the DTS-1 has a “listen-in” feature which makes it ideal for
monitoring the transmission between communicator and
receiver when the PC3000 is connected to the telephone
line.
If you are using a DTS-1, connect the green and red
telephone clips to the “TIP” and “RING” terminals and
connect the red and black power clips to the “AUX [+]” and
“AUX [-]” terminals on the PC3000. When power is applied
to the panel press the red local-line button on the DTS-1
and observe the display window area. The “local-line”
indicator should be in the local position.
For testing purposes, so that the sound level is not too loud,
connect a small buzzer to the “BELL [+]” and “BELL [-]”
terminals to indicate when the panel is in alarm.
Connect a 16.5 VAC, 40 VA transformer to the “AC”
terminals. Before plugging in the transformer be sure the
circuit board is not resting on anything metallic which may
cause a short.
Note: The PC3000 will not start up is “AC” is off and
the battery is low. The panel will display trouble #1
under these conditions.
When the transformer is plugged in there should be lights
on the keypad and the buzzer connected to the bell
terminals may go on for a few seconds. The “Armed” light
may be on or off the first time the panel is powered. The
last armed/disarmed condition is stored in the EEPROM
memory so the panel will always power up in the last
armed/disarmed state. If the “Armed” light is on, enter the
default master code [1234] to disarm the panel. If the
keypad is not active, check for the presence of AC power
at the “AC” terminals, check the keypad connections and
check the panel fuses.
If all the zones are properly connected with end of line
resistors all of the zone lights will be off. Note that the panel
will arm only if all zones are properly connected with end of
line resistors (including FIRE zone) so that the “Ready” light
is on. The keypad should beep several times to indicate
acceptance of the master code. Enter the master code to
arm or disarm the panel.
Read the “Keypad Commands” section of this manual or the
Instruction Manual and enter commands on the keypad to
become familiar with the different commands.
Turn to the “Programming Guide” in this manual and enter a
sample program into the panel through the keypad to
become familiar with the programming commands.
Mounting Panel
Select a dry location close to an unswitched AC source, a
ground connection and the telephone connection.
Remove printed circuit board, mounting hardware and
keypad from cardboard retainer inside panel. Before
attaching cabinet to wall, press the five white nylon printed
circuit board mounting studs and the ground connection
screw into cabinet from the back.
Pull all cables into cabinet and prepare them for connection
before mounting the circuit board to the back of the cabinet.
Press circuit board down onto mounting studs.
Hook-up Procedure
DO NOT connect transformer or battery until all other wiring
has been connected. See power-up procedure.
Connect a ground cable from the cabinet ground
connection by the shortest and most direct route to a
grounding rod.
Connect zone cables to zone inputs and put end of line
resistors on any unused zones. Connect wires supplying
power to motion detectors to auxiliary supply.
Install keypads and connect wires to keypad terminals on
panel. Connect RJ31-X cord to telephone terminals. Do not
insert plug into RJ31-X jack.
Warning: Do not use this equipment on a telephone
line equipped with “call holding” feature because the
tone generated may interfere with the communicator
operation.
Connect bell or siren to “BELL [+]” and “BELL [-]” terminals.
Observe correct polarity for sirens and polarized bells.
Connect 1K ohm 1/2 watt resistor across terminals to
eliminate trouble condition if bell circuit is not being used.
3
Terminal Connections
“AC” Power Terminals
Use a 16.5 VAC transformer with a minimum 40 VA rating to
supply AC power to the PC3000. The transformer should not
be connected to an outlet that is controlled by a switch. If
AC failure occurs it is displayed as a trouble on the keypad
(see “Keypad Functions [Q][2] Trouble Conditions”). It can
also be transmitted to the monitoring station as a trouble
condition (see “Programming Guide [Q][8]” sections [09]
and [10] for alarm and restore codes and section [20] for
AC transmission delay).
switch to ground. A 100 ohm current limiting resistor is
connected in series. A small relay, a buzzer or other DC
operated device may be connected between the 12 V
“AUX” (positive) terminal and the “PGM OUT” (switched
negative) terminal on the main board.
DC
Auxiliary Power Terminals “AUX” and “GND”
The auxiliary power supply can be used to power motion
detectors and other devices requiring 12 V
DC is available from the “AUX” (positive) and “GND”
V
DC. 400 mA 12
(negative) terminals when the PC3000 is used with one
keypad. For each additional keypad the auxiliary supply
rating must be reduced by 60 mA. The auxiliary supply is
fused with the keypad supply at 1 amp. Auxiliary fuse failure
transmission can be sent (see [Q][8] sections [09] and
[10]).
Switched Auxiliary Power Terminals
“SW AUX” and “GND”
The switched auxiliary supply can be switched off
momentarily from the keypad (see “Keypad Commands
[Q][4]”). The “SW AUX” terminal is positive and the “GND”
terminal negative. The 400 mA auxiliary supply rating must
be reduced by any current taken from the switched auxiliary
supply. The switched supply shares the same fuse as the
auxiliary supply.
Bell/Siren Terminals “BELL [+]” and “BELL [-]”
These terminals are for powering bells or other devices
requiring a steady output voltage on alarm. The bell output
is fused for 5 amps. When connecting sirens (speakers with
siren driver already built-in), be sure to observe the correct
polarity. Connect the positive lead to the “BELL [+]” terminal
and the negative lead to the “BELL [-]” terminal.
If no siren or bell is used, connect a 1000 ohm resistor
between “BELL [+]” to “BELL [-]”. The bell/siren alarm
output is pulsed (1 second on 1 second off) when an alarm
is created by the [F] keypad zone, by the FIRE zone, or
when the Bell Pulse option is enabled in section [19] light 1.
Keypad Terminals “RED”, “BLK”, “YEL” and “GRN”
Connect the four coloured wires from the keypads to these
terminals. When connecting more than one keypad, connect
in parallel across the keypad terminals at the control panel
(i.e. all reds wires together, all blacks together, all yellows
together and all greens together). The keypad red and black
power supply terminals are fused through the auxiliary fuse.
Programmable Output Terminal “PGM OUT”
The operation of the Programmable Output depends upon
which option is selected in the programming table. See the
“Programming Guide” section [28] for a list of options for the
“PGM OUT” output. The “PGM OUT” is a 50 mA maximum
The “AUX IN” input terminal is a normally open 24 hour
zone. It can be programmed from the keypad to be silent or
audible. There is no display on the keypad for the “AUX IN”
input. An alarm on this input is created by applying a
positive voltage or by closing a contact between the “AUX
IN” terminal and the positive auxiliary supply. See
“Programming Guide [Q] [8]” sections [09] and [10] for
programming the alarm and restoral codes.
The “AUX IN” terminal can also be used as a momentary
key arming/disarming input. See “Programming Guide”
section [28] for a list of options for the “AUX IN” terminal.
”FIRE” Zone Input
The “FIRE” zone is a supervised (normally open alarm
initiating contact) end-of-line resistor circuit designed to
accept “Latching” four-wire smoke detectors.
(See “Fire Circuit Installation Diagram”.)
On alarm, (fire zone shorted) the bell output will pulse the
signal to indicate that the fire zone has been activated.
Alarm memory and transmission by the digital
communicator is delayed 30 seconds. If the alarm is
acknowledged, by pressing the [#] key before the 30
second delay has expired the signals will silence and the
transmission will be aborted. If the alarm is not
acknowledged and the 30 second delay expires, the fire
memory latches and the transmission cannot be aborted.
If after signal silence, the smoke detector is not restored to
normal, the signals will resound after 90 seconds, and 30
seconds after that, the communicator will transmit. If the
signals resound, they may again be silenced, [#] key, and
the communicator will be aborted if silence occurs within the
30 second delay period.
To restore the smoke detector to normal, clear all products
of combustion from the detector and reset the detector by
pressing [Q] and then holding down [4] for 2 or 3 seconds.
This action will remove power from the smoke detector and
if it is clear of smoke, the detector will return to normal. If the
detector is still in alarm, the signals will sound immediately
and the above sequence will repeat.
For an open on the FIRE zone, the keypad sounder will beep
twice every 10 seconds and the “Trouble” light will show on
the keypad. The communicator will transmit the trouble
condition if programmed for trouble transmission. The
audible “Trouble” signal may be silenced by pressing the [#]
key. To determine the nature of the trouble, press [Q][2].
(see the “Trouble Display” section.)
4
Zone Input Terminals “Z1” to “Z16”
Zone inputs “Z1” to “Z16” are supervised end of line (E.O.L.)
resistor circuits. Each input must be terminated with a 1K
ohm E.O.L. resistor. An alarm condition will be created if a
normally open contact is used to short across the E.O.L.
resistor. An alarm is also created if normally closed
contacts, wired in series with the E.O.L. resistor, are
opened. See the wiring diagram for normally open and
normally closed contact connection. The type of circuit or
zone definition (delay, instant, 24 hour etc.) is programmed
from the keypad using the [Q][8] Installer’s Programming
commands ("Programming Guide" sections [16] and [17]).
Telephone Terminals “TIP”, “RNG”, “T-1” and “R-1”
The wires from the RJ31-X telephone jack are connected to
these terminals in the following way.
TIPGreen wireIncoming line from
RNGRed wiretelephone company
T-1Brown wire
Outgoing line to
R-1Grey wirehouse telephone(s)
Note: For proper operation there must be no other
telephone equipment connected between the control
panel and the telephone company's facilities.
Battery Connections
Do not connect the battery or the transformer until the wiring
is complete. Connect the red battery lead to the positive
battery terminal and the black lead to the negative battery
terminal. If the connection is made in the reverse the battery
fuse will fail. The battery charging voltage is factory adjusted
and normally needs no adjustment.
Keypad Installation
Mount the keypads near the exit-entry doors. The
PC3000RK keypad has a red, a black, a green and a yellow
wire on the back. Connect these four wires to the four
keypad terminals on the control panel using four conductor
(quad) telephone wire. Up to three keypads may be
connected to one PC3000. Connect all green wires from the
keypads to the “GRN” terminal on the panel. Connect all
yellow wires from the keypads to the “YEL” terminal on the
panel. Connect all red wires from the keypads to the “RED”
terminal. Connect all black wires from the keypads to the
“BLK” terminal.
Power-up Procedure
If the keypads are located a distance from the panel, install
an extra keypad temporarily at the panel during power up
testing. An extra keypad with a short length of cable and
alligator clips attached is helpful for testing and
programming PC3000 systems.
Connect the transformer, wait approx. 5 seconds.
Enter a few keypad commands and open a zone to be sure
that the panel and keypad are responding to signals. If the
keypad does not respond and there are no indicators on,
check for AC voltage at the “AC” terminals. If there is 16
VAC present, check that the keypad wiring is correct and
check the keypad/auxiliary supply fuse. If the keypad/
auxiliary supply fuse is blown check for a short between the
keypad red and black wires before replacing the fuse.
If the keypad is responding normally, connect the battery.
The red battery lead attaches to the positive battery post
and the black battery lead attaches to the negative battery
post.
Note: The PC3000 will not start up is “AC” is off and
the battery is low. The panel will display trouble #1
under these conditions.
Testing The System
See Installer’s test - [Q] [6] [Master Code] [0] (page 9), or
do the following. Contact the monitoring station to request a
transmission test. Plug the telephone cord into the RJ31-X
jack. If a DTS-1 is being used to monitor communicator
transmissions, connect as described in “Bench Testing”
section and place the DTS-1 in the line mode by pressing
the red “LINE/LOCAL” button. Arm the panel, wait for the
exit delay to expire and trip a detector on an instant circuit.
Wait for the communication to complete. Disarm panel and
check with the monitoring station to confirm the
transmission. Perform additional transmissions required by
the monitoring station.
Check the “Trouble” light on the keypad. If it is on, press [Q]
then [2] to determine if there is a system trouble. The
“Trouble Display” section in “Keypad Commands” gives a
description of the different trouble conditions.
Instructing End-User
Fill out the system reference guide in the PC3000 Instruction
Manual. Check off sections in the manual which apply to the
user’s system and make additional notes if necessary.
Describe the system to an authorized user. Describe arming
and disarming procedures. Describe the basic keypad
functions. Assist the user in working through examples of
each type of command.
Provide user with the Instruction Manual and instruct them to
read the manual to become familiar with the system
operation.
Instruct the user to test the system on a regular basis as
described in the Instruction Manual. The Master Code
should be changed from the default setting and recorded in
the Instruction Manual.
5
GUIDELINES FOR SMOKE
DETECTOR LOCATION
Experience has shown that all hostile fires in family living
units generate smoke to a greater or lesser extent.
Experiments using typical fires in family living units indicate
that detectable quantities of smoke precede detectable
levels of heat in most cases. For these reasons, smoke
detectors should be installed outside of each sleeping area
and on each additional story of the family unit.
The following information is for general guidance only and it
is recommended that the smoke detector manufacturer's
literature be used for detailed installation instructions.
It is recommended that additional smoke detectors beyond
those required be installed for increased protection. The
added areas include: basement, bedrooms, dining rooms,
furnace room, utility room and hallways not protected by
the required detectors.
BedroomBedroom
Living
Room
Basement
Hall
Dining
Room
BedroomBedroom
Bathroom
Kitchen
A smoke detector should be located between
FIG. 1:
Bedroom
Living
Room
the sleeping area and the rest of the family unit.
Living
Room
Dining
Room
Family
Room
Bedroom
FIG. 2:
Bedroom
Bedroom
Kitchen
In the family living units with more than one
sleeping area, a smoke detector should be located to
protect each sleeping area.
FIG. 3:
A smoke detector should be located on each
story of the living unit.
4 in.
Ceiling
Acceptable here
Note:
Measurements shown are to the
closest edge of the detector.
FIG. 4:
Smoke Detector mounting - “Dead” Air Space.
(0.1m)
Never here
Top of detector
acceptable here
4 in.
(0.1m)
minimum
Side wall
12 in.
(0.3m)
maximum
The smoke from a fire generally rises to the ceiling,
spreads out across the ceiling surface and begins to
bank down from the ceiling. The corner where the
ceiling and wall meet is an air space into which the
smoke may have difficulty penetrating. In most fires,
this “dead” air space measures about 4 in. (0.1m)
along the ceiling from the corner and about 4 in.
(0.1m) down the wall as shown in Figure 4. Detectors
should not be placed in the dead air space.
6
KEYPAD FUNCTIONS
Introduction
The PC3000RK remote keypad provides complete
information and control of the PC3000 control panel. The
panel can be fully programmed from the keypad. The 16
zone lights and the fire alarm light provide alarm and status
indication for the alarm circuits. The 6 function lights guide
the user in operating the system. The built-in buzzer lets the
user hear correct key entries and other alert signals. The 12
digit keypad is used for code entry and other programming
functions. All keypad entries are made by pressing one key
at a time.
The keypad is normally resting in the arm-disarm mode. In
this condition the zone lights are indicating the opening and
closing of zones. The “Ready” light comes on when all zones
are closed. The system can be directed to perform other
functions such as zone bypassing, displaying trouble
conditions, displaying alarm memory and programming by
entering one of the various [Q] commands described below.
Pressing the [#] key or not making any key entry for 2
minutes always returns the keypad to the arm-disarm mode.
Master Code
A default Master Security Code “1234” is programmed into
the PC3000 at the factory. The Master Security Code is used
for arming and disarming the control panel, for
programming up to fifteen additional security codes using
the [Q][5] command and for entering other user functions
using the [Q][6] command. The Master Code can be
reprogrammed if the installer leaves section [19] light 2 off.
Because the PC3000 uses EEPROM memory the codes and
other data are retained even after complete AC and battery
failure.
Installer’s Programming Code
A default Installer’s Programming Code “3000” is
programmed into the PC3000. This code is used with the
[Q][8] command by the installer to gain access to the
system in order to enter panel or communicator program
information. The Installer’s Programming Code may be
changed by the installer.
Arming
Check to see if the “Trouble” or “Bypass” light is on before
arming the PC3000. Close all protected doors and windows
and stop movement in areas covered by motion detectors.
Check to see that the “Ready” light is on (all zones are
closed). The system cannot be armed unless the “Ready”
light is on. Enter a [4 Digit Security Code]. As each digit is
entered the keypad buzzer will beep. If the security code
was entered incorrectly, the sounder will beep steadily for 2
seconds. If the code was entered correctly but the “Ready”
light was not on, the keypad will beep quickly followed by a
steady tone. When the correct code is entered, the “Armed”
light will come on and the keypad buzzer will beep quickly.
Exit the premises through the designated exit-entry door. At
the end of the allowed exit time all lights on the keypad will
go out except the “Armed” light. See the “Installer’s
Programming [Q][8] Command” section for instructions on
how to change the exit time. Also see, “Quick Arm” and “At
Home Arming”.
Disarming
Enter the premises through the designated exit-entry door.
The keypad buzzer will be on. Go to the keypad and enter
the [4 digit security code]. If an error is made in entering the
code, press the [#] key and enter the code again. The
“Armed” light will go out and the keypad sounder will stop.
The correct security code must be entered before the
allowed entry time expires. To change the entry time see
“Installer’s Programming Command”, [Q][8]. If an alarm
occurred while the panel was armed, the “Memory” light and
the “Zone” light which caused the alarm will start to flash
and stay flashing for 2 minutes when the panel is disarmed.
Pressing the [#] key returns the panel to the normal armdisarm mode.
Auto-bypass/Home-Away Arming
If a correct security code is entered, and you do not exit the
premises, the system will, at the end of the Exit delay time,
arm with interior zones automatically bypassed if those
interior zones have been programmed as “Home-Away”
zones. The “Bypass” light will come on immediately following
the arming code being entered until a delay zone is tripped
or [Q] [1] is entered to reactivate bypassed home-away
zones. (See programming sections [16] and [14], zone
definitions for programming zones as “Home-Away”.)
This is a convenience feature for the user who wishes to
remain at home with the system armed. The user does not
have to manually bypass the home-away zones.
To reactivate the home-away zones that have been
automatically bypassed, press [Q] [1]. The “Bypass” light
will go out. This command is a quick method of fully arming
the system before going to bed.
Zone Bypassing
[Q]+[1]
A bypassed zone will not cause an alarm. If a zone is
bypassed the panel may be armed (“Ready” light will be on)
even if the zone is open. Use zone bypassing when access
is needed to part of the protected area. Also, damaged
wiring or contacts on a zone may be temporarily bypassed
until repairs can be made so that the panel can be armed.
To bypass zones, enter [Q] [1] and the zone number(s) to
be bypassed. Press [#] to return to “Ready” (arm-disarm
mode). When bypassing zones, two digits must be entered
for the zone number(s) to be bypassed (e.g. [Q] [1]
[01]....[16]). To remove all bypasses, enter [Q] [1] [00] [#].
The “Zone” lights which are on, while the “Bypass” light is
flashing, indicate the bypassed zones. Remember that if no
keypad entry is made for more than 2 minutes the keypad
will return to the arm-disarm mode. Then, in order to bypass
a zone the complete command must be re-entered. Once
7
the bypass command is entered, pressing [99] recalls the
last zone or group of zones which was bypassed. If the
same group of zones is bypassed each time, this bypass
recall feature can be used instead of having to bypass
zones individually.
When the PC3000 is programmed, the ability to bypass
certain zones may be eliminated. In this case, the “Zone”
lights for those zones will not come on in response to the
bypass command. See the “Zone Bypass Mask” instruction
in the [Q][8] Installer’s programming section. If the “Bypass”
light is on when arming the panel, the [Q][1] command
should be used to see which zones are bypassed so that
zones are not unintentionally bypassed. Zone bypasses are
automatically cancelled when the panel is disarmed.
If light 8 in section [19] is on then a code must be entered
with [Q]+[1] to bypass zones. Only the zones assigned to
the same side of the system as the user code can be
bypassed. The ability to bypass using certain access codes
can be eliminated. See the “Access Bypass Mask”
instruction in the [Q] [8] Installer’s Programming section.
Note: At no time can any armed zone be bypassed.
Trouble Display
[Q]+[2]
The PC3000 continuously monitors a number of possible
trouble conditions. If one of these conditions occurs, the
keypad “Trouble” indicator will light and the audible
indication will sound (two short beeps every 10 seconds).
When the [#] key is pressed the audible indication will stop
but the “Trouble” indicator light will remain on until the
trouble is cleared. Trouble conditions can also be
transmitted to the monitoring station (see “Programming
Guide” sections [09] and [10] for alarm and restoral trouble
codes). Press the [Q] then [2] keys to display the type of
trouble. The “Zone” lights indicate the type of trouble
condition.
1 Low stand-by battery
2 AC power failure
3 Day zone trouble
4 Telephone line trouble
5 Unsuccessful communication attempt with monitoring
station
6 Bell circuit failure
7 Smoke detector zone trouble
8 Loss of time on internal clock
Press [#] to return to “Ready”.
1 Low Battery...A battery trouble will be displayed and can
be reported if the battery is weak, disconnected or the
battery fuse is blown. Only one low battery alarm or restoral
transmission takes place per arming period. Low battery
trouble display is latching and can only be cleared by
battery restoration, arming and disarming panel then
accessing trouble indication.
2 AC Power Failure...There is no audible annunciation on
AC power failure. The system “Trouble” light will come on but
the audible indication will not sound until there is a low
battery condition. Transmission delay can be programmed
for 1 to 99 minutes. See “Programming Guide” section [22].
3 Day Zone Trouble...This trouble applies only to zones
which have been programmed as day zones.
(“Programming Guide” section 16 & 17). A day zone creates
a trouble signal when the panel is disarmed and an alarm
signal when the panel is armed.
4 Telephone Line Trouble...A telephone line trouble is
generated when the line voltage drops below 3 volts for
more than 30 seconds. It generates a keypad trouble when
the system is disarmed and rings a local alarm when the
panel is armed if section [19] light 5 is off.
5 Unsuccessful Communication...If the digital
communicator is unsuccessful communicating with the
monitoring station after eight attempts, a trouble is
generated.
If a later attempt to communicate is successful the trouble is
cleared.
6 Bell Circuit Failure...If the bell fuse is blown or the bell
circuit is open, a keypad trouble and a trouble transmission
are generated.
7 Smoke Detector Zone Trouble...If a FIRE zone is open
circuit, a keypad trouble and a trouble transmission are
generated. A trouble on the FIRE zone will unconditionally
initiate an audible indication on the keypad. This means that
even if any other previous trouble has been silenced, a FIRE
zone trouble will restart the keypad buzzer.
8 Loss of Internal Time...When the PC3000 is powered up
or reset, the internal time of day clock needs to be set to the
correct time. This trouble is cleared when the trouble display
is viewed and exited or when an attempt is made to reset
the internal time of day clock. See “[Q][6] User’s Function
Command” for resetting time of day clock.
If the [9] is pressed while in the trouble display mode the
most recent trouble will be displayed on the zone LEDs. This
trouble memory feature is useful as a diagnostic aid when
installing and servicing the PC3000.
Alarm Memory Display
[Q]+[3]
Press [Q] then [3] to enter the alarm memory mode. The
“Memory” light will flash and any alarm caused during the
last armed period will be displayed on the zone lights. In
addition to the last alarm memory there are 2 history levels.
After entering the memory mode (pressing [Q] then [3]),
pressing [9] will cause the keypad to display the two other
levels of alarm history. Each time [9] is pressed the keypad
will beep 1, 2 or 3 times to indicate which level of history is
being viewed. When the panel is armed, the last alarm
memory is cleared and the contents moves to the 1st history
level. The “Memory” light will only be on when there was an
alarm during the last armed period.
Press [#] to return to “Ready”.
Switched Auxiliary Supply Control
[Q]+[Hold Down 4]
To interrupt the switched auxiliary power supply press [Q]
then hold down [4] for the desired interrupt time. When the
[4] is released the system returns to the “Ready” mode and
the switched auxiliary supply is restored.
8
User’s Programming Commands
[Q]+[5]+[MASTER CODE]
The [Q][5] user’s programming command is used to
program additional access codes. Up to 16 user arm-disarm
codes may be programmed. The 1st code is the master
code (factory default [1234]). The 16th code is optionally a
“One Time Use” or maid code. The 16th code may be
changed from a “One Time Use” code to a regular code
using an installer’s programming command (section
[18]...1st system option code). Remember if no keypad entry
is made for more than 2 minutes the keypad will return to the
normal arm-disarm display and the complete command will
have to be re-entered to program a new access code.
Programming Additional Access Codes
1 Press the [Q] and [5] keys then enter the Master Security
Code (default [1234]) to enter the additional code
programming mode. The “Program” light and “Zone 1” light
will be on to show that the first code (the Master Code) is
already programmed with the factory default code [1234].
The Master Code may be changed but do not try to erase
the Master Code. The installer can disable user changing of
the Master Code by turning on light 2 in section [19].
2 15 additional codes may be programmed. The zone lights
are used to indicate which of these codes are already
programmed (zone light on steady) and the one which is
currently being programmed (zone light is flashing).
3 To program the second code, press [02] then enter a 4
digit code. Zone 2 light will flash and sounder will beep three
times and zone light 2 will come on steady after the 4 digit
code is entered.
4 To remove the second code, press [02] - the buzzer will
beep three times and zone light 2 will flash. Enter [Q] [Q] [Q]
[Q], the buzzer will beep three times and zone 2 light will go
out to show that the code has been removed.
5 Follow the instructions in 3 or 4 for programming or
removing any of the other additional codes.
6 Do not try to remove the Master Code (1st code). The
Master Code may be changed but it must not be removed.
When changing the Master Code be sure to enter a valid 4
digit number (use only number keys 0 to 9). Do not enter [#]
or [Q] as one of the digits. If the Master Code is forgotten
and the panel is left disarmed, program a new Master Code
using the [Q][8][Installer’s Code][25] command. If the
Master Code is forgotten and the panel is left armed, the
entire programming can be reset to factory default by using
the “Hardware Reset” method described on page 22.
7 To successfully program or remove additional codes, the
panel must be put into the code program mode by following
step 1 followed by steps 3 or 4. Note that if no key entry is
made for 2 minutes the panel will go back to the normal
arm/disarm mode, after which step 1 must be repeated to
get back into the code program mode.
8 To exit the code program mode press [#].
To review:
programming a new code;
enter [Q] [5] [Master Code] [01 to 16] [4 digit code]
eliminating an existing code;
enter [Q] [5] [Master Code] [02 to 16] [Q Q Q Q].
Note: The access code, numbers must be entered as
two digits. E.g. 02, 03,......, 15, 16.
User’s Functions Command
[Q]+[6]+[MASTER CODE]
This command is used to set the system clock time and to
set the Auto-arm time. It is also used to turn on and off a
number of system functions. The command is used by
entering [Q], [6], [Master Code] then a number from the
following list to select the item to be changed.
[0] Installer’s test
[1] System 24 hour clock (enter HH:MM)
[2] Auto-arming time (enter HH:MM)
[3] DO NOT USE
[4] Quick arm enable/disable
[5] Auto-arm enable/disable
[6] Door chime enable/disable
[7] DO NOT USE
[8] Bell test function
[9] User Initiated Callup
Note: The system clock is a 24 hour clock and times
must be entered as two digit numbers.
e.g.HH - 00, 01,.....10,11,.....22, 23
MM - 00, 01,.....35,36.....58,59
If a printer is attached
Day - 01.....31, Month - 01.....12, Year - XX (two digits)
e.g. HH: MM: DAY: MONTH: YEAR.
Items 1 & 2 are time setting functions. Enter 4 digits
representing the time in hours and minutes (HH:MM) based
on the 24 hour or military clock. Always enter a leading zero
where only one digit is required, 8:05 am would be entered
as 0805, 1:30 pm would be entered as 1330. Items [0], [4],
[5] and [6] turn on and off various features. When the item
key is pressed, the feature is turned on if the keypad beeps
quickly 3 times. The feature is turned off if the keypad
sounds one long beep. Pressing item [8] gives a 2 second
bell and keypad light test. Pressing [9] makes the panel call
the Downloading computer if enabled in section [47].
If a printer is attached to the panel (see section [28]) and is
enabled (see section [49]) the clock data entry will be
automatically extended to include the day (two digits
01.....31), the month (two digits 01.....12) and the year (two
digits...e.g. 91, 92, 93....etc.).
9
Installer’s Test
[Q]+[6]+[MASTER CODE]+[0]
This feature is designed to assist the installer in testing the
system. In this mode, the bell or siren will operate for two
seconds each time a device is tripped and the zone alarm
will be put into the first level memory. The feature is
automatically disabled when the panel is armed and
disarmed. Each time a zone is tripped or restored in this
mode, a signal, if programmed, will be transmitted to the
monitoring station. If this is not desired, it is possible to
disable the communicator during the test (see section [18]
“1st System Option Code”). A printer, if attached, will not
function if the communicator is disabled.
Notes: Do not use the PC16OUT module during the
installer’s test.
Do not use the installer’s test when the panel is
partially armed.
Quick Arm
[Q]+[6]+[MASTER CODE]+[4]
The “Quick Arm” feature is enabled by pressing the [4] key
while in the “User Functions Command” section. When
enabled (enabled 3 beeps....disabled one long beep) the
panel can be armed by entering [Q][0]. The closing code
transmitted for “Quick Arm” is the same as the code which
is programmed for the Master Code.
Auto-arm Enable
[Q]+[6]+[MASTER CODE]+[5]
Entering [Q] [6] [Master Code] [5] will enable/disable the
Auto-arming feature. When the feature is being Enabled, the
keypad buzzer will sound 3 beeps and when being Disabled
the buzzer will sound one long beep.
Setting the Clock
[Q]+[6]+[MASTER CODE]+[1]
Setting the “System 24 Hour Clock” (item [1]) tells the
system the correct time of day. If the system is without
battery and AC power it cannot continue to keep time.
Therefore when the panel is first powered up or when it has
been without AC power long enough to completely
discharge the stand-by battery, the “System 24 Hour Clock”
must be reset. If the time needs to be reset a “Trouble #8”
will be indicated on the keypad (see [Q][2] “System Trouble
Command”). If a printer is attached to the panel, setting the
clock must include the day, month and year. e.g. HH: MM:
DAY: MONTH: YEAR.
Auto-arm Time of Day
[Q]+[6]+[MASTER CODE]+[2]
The PC3000 can be programmed to arm at the same time
each day. Programming item [2] sets this time and the
feature must be enabled as shown in item [5] (see “Autoarm Enable” on this page).
At the selected auto-arm time the keypad beeper begins to
sound and the Bell/Siren will pulse once every 10 seconds to
alert anyone on the premises that the system is about to
arm. The Bell/Siren pulse can be silenced in section [51] by
turning light 1 on.
The keypad beeper will sound for one minute before autoarming unless one of the following two methods is used to
abort the auto-arm.
• Auto-arm abort: Any key can be pressed to abort the
auto-arm sequence and silence the keypad during the
one minute pre-alert (this is the default condition). If
section [51] light 2 is on, then a valid 4 digit access code
is required to abort the auto-arm sequence. The auto-arm
will be attempted at the same time the following day.
• Auto-arm abort with transmission: Any time an auto-
arm is aborted using one of the above methods, the
reporting code programmed in section [53] will be
transmitted to the central station.
Door Chime
[Q]+[6]+[MASTER CODE]+[6]
The “Door Chime” feature is enabled by pressing the [6] key
while in the “User’s Functions Command” section. When
enabled the keypad buzzer will beep quickly 5 times each
time any zone defined as a delay or instant circuit opens or
closes. The “Door Chime” feature does not operate on other
zone definitions. Zone bypass may be used to eliminate
“beeping” on doors where it is not wanted. This feature
operates only while the panel is disarmed.
System Test
[Q]+[6]+[MASTER CODE]+[8]
The system test feature sounds the bell or siren, lights the
keypad indicators and beeps the keypad buzzer for 2
seconds. If a code is programmed in section [54] it will be
transmitted at the same time.
User Callup
[Q]+[6]+[MASTER CODE]+[9]
This function is enabled in section [47]. When activated,
the panel will call the downloading computer. The
downloading computer must be waiting for the panel to
call before downloading can be performed.
Utility Output Command
[Q]+[7] OR [Q]+[7]+[ACCESS CODE]
The programmable output (PGM terminal) on the PC3000
can be made to activate by a command from the keypad.
This output can be used for operating other devices such
as; garage door opener, special lighting or door strikes.
The programmable output must be selected for keypad
utility using the [Q][8][Installer’s Code][28] command and
programming a [2], [3], [4] or [5].
Depending on the option chosen in the programming
section, the programmable output is activated by pressing
the [Q] then [7] keys followed by a Group A access code.
10
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.