Control Panel Specifications
Flexible Zone Configuration:
• Six fully programmable zones
• Seven Access Codes: five User, one Master and a
second Master code
• Normally Closed, Single EOL, Double EOL
• 23 Zone Types, 6 Programmable Zone Options
Audible Alarm Output:
• Supervised Bell Output (current limited at 3 amps), 12 V
• Steady or Pulsed Output
EEPROM Memory: Does not lose programming or
system status on complete AC and Battery failure
Programmable Outputs:
• Two Programmable Voltage Outputs, 20
programmable options
- One High Current (300 mA) PGM output on main
panel
- One Low Current (50 mA) PGM output on main
panel
Powerful 1.5 Amp Regulated Power Supply:
• 550 mA Auxiliary Supply, 12 V
• Positive Temperature Coefficient (PTC) components
replace fuses
• Supervision for loss of AC Power, Low Battery
• Internal Clock Locked to AC Power Frequency
Power Requirements:
• Transformer = 16.5 VAC, 40VA
• Battery = 12 volt 4 Ah minimum rechargeable sealed
lead acid
Remote Keypad Specifications:
• Three Different Keypads Available:
- PC5506T 6 Zone LED Keypad
- LCD5500T Alphanumeric Keypad
- PC1575RK 6 Zone LED Keypad
• The PC5506T and LCD5500T keypads have 5 Fully
Programmable Function Keys and Tampers
• Connect up to 8 Keypads
• Four Wire (Quad) Connection to KEYBUS
• Built in Piezoelectric Buzzer
Digital Communicator Specifications:
• Supports Major Formats including SIA, Scantronics 4-8-1
Slot and Contact ID
• Event Initiated Personal Paging
• Three Programmable Phone Numbers
• Two Account numbers
• DTMF and Pulse Dialing
• DPDT Line Seizure
• Anti-jam Feature
• Split Reporting of Selected Transmissions to Each
Telephone Number
DC
System Supervision Features
The PC1580 continuously monitors a number of possible
trouble conditions including:
• AC Power Failure
• Trouble by Zone
• Tamper by Zone
• Fire Trouble
• Telephone Line Trouble
• Failure to Communicate
DC
• Low Battery Condition
• Bell Output Trouble
• Module Fault (Supervisory or Tamper)
• Loss of Internal Clock
• AUX Power Supply Fault
False Alarm Prevention Features
• Audible Exit Delay
• Audible Exit Fault
• Communication Delay
• Urgency on Entry Delay
• Quick Exit
Additional Features
• Auto Arm at Specified Time
• Keypad Activated Alarm Output and Communicator
Test
• All modules connect to the system via a four wire
KEYBUS up to 1000’/330m from main panel
• Event Buffer can be printed using PC5400 RS232 Serial
Interface module
• Supports the ESCORT 5580 Voice Prompt Module with
Automation/Lighting Control
• An Event Buffer which records the past 100 events with
both the time and date at which they occured
• Uploading and Downloading capability
• Local Downloading capability with the use of the
PC-LINK Adaptor
• Time compensation feature
1.2 Additional Devices
1.2.1 Keypads
A maximum of eight keypads can be connected to the
control panel and can be any combination of the following
listed.
• PC5506T 6 zone LED keypad with function keys and
tamper
• LCD5500T LCD keypad with function keys and tamper
• PC1575RK 6 zone LED keypad
1.2.2 ESCORT5580 Module
There are many benefits to adding the ESCORT5580 module
to a security system. The ESCORT5580 module will turn any
touch tone phone in the world into a fully functional keypad.
Imagine the security a customer would feel if they had the
ability to arm, disarm and check status of their alarm system
while at the office or on vacation.
1
SYSTEMVINTRODUCTION
All touch tone phones in the home also become system
keypads. For example, at bedtime, the phone beside the bed
can be used to arm the system. The addition of the
ESCORT5580 may reduce the cost of the overall installation,
eliminating the need for additional keypads and the labour of
running wires.
The ESCORT5580 will also act
as a tutor for the system. By
using clear, easy to understand
sentences, the voice module
helps guide the user through
functions they may otherwise
find difficult to navigate. Programmable zone labels (up to
6 words each from our library of over 240 words) makes the
system even easier to use.
The module also has a built-in power line control interface
and can control up to 32 power line control devices for
lighting and temperature control, giving you the power to
add home automation in a very cost effective manner.
Devices can be activated individually, as a group, by
schedule or can be activated when an event occurs on the
system, such as an alarm.
These are just a few of the applications available with the
addition of the ESCORT5580 module. For more information,
please refer to the ESCORT5580 Installation Manual.
1.2.3 PC5400 Printer Module
This module will give you the
added advantage for the
commercial customers who
like the idea of a permanent
record of openings and
closing but are put off by the
additional monthly
monitoring charge. In addition, as reports are generated in
real-time, the customer will not have to wait for a monthly
report form the monitoring station.
The PC5400 Printer Module will allow the panel to print out
all events that occur on the system to any serial printer. The
printout will contain the time, date and the event that occurred
(see Section – 5.25 “On-site Printer”).
1.2.4 Downlook Video Transmission Module
The Downlook Still-Frame Video Transmission Module (DLM1/DLM-4) is the ideal solution for all business and residential
environments which require visual surveillance but where
the presence of on-site security personnel is impossible,
undesirable or unaffordable.
Downlook is the smart and inexpensive way to add visual
backup to your regular remote alarm signalling system,
meeting your demand for tighter security on a tight budget.
The added visual protection will reduce the incidence of
false alarms as well as surveillance costs, thus improving
the overall security protection.
For more information regarding the Downlook Video
Transmission Module, please consult the DLM-1/DLM-4
Installation Manuals.
1.2.5 Cabinets
Several different cabinets are available for the PC1580
modules. They are as follows:
PC5003C Cabinet
Control cabinet for the PC1580 main panel. Dimensions
288mm x 298mm x 78mm / 11.3” x 11.7” x 3” approximately.
PC5004C Cabinet
Cabinet to house the Escort5580 Module or the PC5400
Printer Module. Dimensions 229mm x 178mm x 65mm / 9”
x 7” x 2.6” approximately.
1.3 Out of the Box
Please verify that each of the following components is
included in your system:
• one PC1580 control cabinet
• one PC1580 control circuit board
• one keypad (LED keypad or LCD keypad)
• one Installation Manual including Programming
Worksheets
• one Instruction Manual for the end user
• one hardware pack consisting of:
-four plastic circuit board standoffs
-twelve 5600Ω (5.6K) resistors
-one 2200Ω (2.2K) resistors
-one 1000Ω (1K) resistor
-EGND Assembly
-one cabinet door plug
• 220V to16.5V AC transformer with fuseblock
• two yellow safety hazard warning labels to be applied by the
installer
Enclosed 240V AC Warning Labels
The Health & Safety (Signs and Signals) Regulations state
that warning signs must be displayed to warn people to be
careful to take precautions where a hazard exits.
These signs also comply to the Electricity at Work Regulation
1989 and BS5378.
The Regulations for Electrical Installation (16 Edition) Section
514-10 Warning Notice Voltage.
Every Item of Equipment or enclosure within which a voltage
exceeding 250 Volts exists, and where the presence of such
a voltage would not normally be expected, shall be so
arranged that before access is gained to a live part, a
warning of the maximum voltage present is clearly visible.
It is recommended that one of the enclosed warning stickers
be attached to the external area of the control panel housing
to give indication of voltage before access is gained to the
transformer area. The second enclosed warning sticker
should be placed on the front plate of the unswitched fuse
unit to give indication of mains connection within.
DSC accepts no responsibility for the non use of these
warning labels and can confirm that it is the responsibility of
the installation engineers to attach them to the required
devices during the installation process. The warning labels
are enclosed to be used in accordance with the Health and
Safety regulations and also the electricity at work act 1989.
2
Getting Started
SECTION2
The following Sections provide a thorough description of how to
wire and configure devices and zones.
2.1 Installation Steps
The following steps are provided to assist you with installing
the panel. We suggest that you read this section in its entirity
before you begin. Once you have an overall understanding of
the installation process, carefully work through each step.
Working in this manner will reduce the number of problems as
well as the amount of time required for a complete installation.
Step 1 Create a Layout
Draw a rough sketch of the building to get an idea of where
all alarm detection devices, keypads and other modules
are to be located.
Step 2 Mounting the Panel
Locate the panel in a dry area close to an unswitched AC
power source and the incoming telephone line. Before
attaching the cabinet to the wall, be sure to press the four
circuit board mounting studs into the cabinet from the back.
After you have attached the cabinet to the wall, stick the
provided DSC logo sticker on the front of the cabinet.
You must complete all wiring before applying AC or
connecting the battery to the panel.
Step 3 Wiring the KEYBUS (Section 2.3)
Wire the KEYBUS to each of the modules following the
guidelines provided in Section 2.3 of this manual.
Step 4 Zone Wiring (Section 2.8)
You must power down the control panel to complete all
zone wiring. Please refer to Section 2.8 when connecting
zones using normally closed loops, single EOL resistors,
double EOL resistors, Fire zones and Keyswitch Arming
zones.
Step 5 Complete Wiring (Section 2.2)
Complete all other wiring including bells or sirens, phone
line connections, and ground connections following the
guidelines provided in Section 2.2 (“Terminal
Descriptions”).
Step 6 Power up the Control
Once all zone and KEYBUS wiring is complete, power up
the control panel.
The panel will not power up on the battery connection alone.
Step 7 Keypad Assignment (Section 2.5)
In order for keypads to be properly supervised, each must
be assigned to a different slot. Please follow the guidelines
provided in Section 2.5 when assigning keypads.
Step 8 Supervision (Section 2.6)
The supervision of every module by the panel is
automatically enabled upon power up. Please verify that
all modules appear on the system according to the
instructions in Section 2.6.
Step 9 Programming the System (Sections 4 and 5)
Section 4 explains how to program the panel. Section 5
contains a complete description of the various
programmable features, which options are available and
how they function. The Programming Worksheets (pages
25-33) should be filled out completely before attempting
to program the system.
Step 10 Testing the System
The panel must be thoroughly tested to ensure that all
features and functions are operating as programmed.
2.2 Terminal Descriptions
AC Terminals – AC (50Hz)
The panel requires a 16.5 volt, 40 VA transformer. Connect
the transformer to an unswitched AC source and connect
the transformer to these terminals.
Do not connect the transformer until all other wiring
is complete.
The panel must have a power line frequency of
50Hz.
Battery Connection
A 12V 4Ah rechargable gel-cell battery is used as a back up
source of power in the event of an AC power failure. The
battery also provides additional current when the panel’s
demands exceed the power output of the transformer, such
as when the panel is in alarm.
Do not connect the battery until all other wiring is
complete.
Connect the RED battery lead to the positive battery terminal;
connect the BLACK lead to negative.
Auxiliary Power Terminals – AUX+ and AUX-
These terminals provide up to 550 mA of additional current
DC for devices requiring power. Connect the positive
at 12 V
side of any device requiring power to the AUX+ terminal, the
negative side to AUX- (ground). The AUX output is protected.
This means that if too much current is drawn from these
terminals (such as a wiring short), the panel will temporarily
shut off the output until the problem is corrected.
Bell Output Terminals – BELL+ and BELL- (Section 3.4)
These terminals provide up to 700 mA of continuous current
at 12 V
DC for powering bells, sirens, strobes or other warning-
type equipment. Connect the positive side of any alarm
warning device to BELL+, the negative side to BELL–.
Please note that the Bell output is protected: if too much
current is drawn from these terminals (such as a wiring
short), the Bell fuse will open. Three Amps can be drawn for
short periods only.
The Bell output is supervised. If no alarm warning devices
are in use, connect a 1000 ohm resistor across BELL+ and
BELL– to prevent the panel from displaying a trouble
condition. For more information, please refer to Section 3.4
✱] [2] Trouble Display”).
(“[
The bell is programmed by default to terminate after four
minutes. The Bell Cutoff time can be adjusted in
programming section [02] (“System Times”).
The KEYBUS is used by the panel to communicate with
modules and vice versa. Each module has four KEYBUS
terminals that must be connected to the four KEYBUS
terminals on the panel. For more information, see Section
2.3 (“KEYBUS Operation and Wiring”).
3
G E T T I N G S T A R T E D
Programmable Outputs – PGM1 and PGM2
Each PGM output is designed so
that when activated by the panel, the
terminal will switch to ground.
PGM2 can sink up to 50 mA of current
to activate LEDs or a small buzzer.
Connect the positive side of the LED
+AUXPGM1
RED
or buzzer to AUX+, the negative side
to PGM2. If more than 50 mA of
current are required, a relay must be
used. Please study PGM wiring in
the accompanying diagram.
PGM1 is a high current output which
COM NC
operates similar to PGM2. PGM1 is
used for high current output (300mA).
Zone Input Terminals – Z1 to Z6
Each detection device must be connected to a zone on the
control panel. We suggest that one detection device be
connected to each zone; wiring multiple detection devices
to a single zone, however, is possible. For zone wiring
specifics, please see Section 2.8 (“Zone Wiring”).
If a telephone line is
required for central
station communication or
downloading, connect an
RJ-31X telephone jack in
the following manner:
• TIP - Green Wire incoming line from
RING TIP R-1
RED
GRN
EGND
T-1
GRY
BRN
RJ31X
TELEPHONE
PLUG
• RING - Red Wire telephone company
• R-1 - Grey Wireoutgoing line to
• T-1 - Brown Wire house telephone(s)
Please ensure that all plugs and jacks meet the
correct dimension, tolerance and metallic plating
requirements.
For proper operation, no other telephone equipment
should be connected between the control panel and
the telephone company facilities.
Do not connect the alarm panel communicator to
telephone lines intended for use with a fax machine.
These lines may incorporate a voice filter which
disconnects the line if anything other than fax
signals are detected, resulting in incomplete
transmissions.
2.3 KEYBUS Operation and Wiring
The KEYBUS is used by the panel to communicate with all
connected modules and vice versa. The red (AUX+) and
black (AUX-) terminals are used to provide power, while the
yellow (YEL) and green (GRN) terminals are clock and data
respectively.
The four KEYBUS terminals of the panel must be
connected to the four KEYBUS terminals or wires of
all modules.
(ANY OUTPUT
TERMINAL)
BLK
DSC
RM-1
YEL
WHT
GRN
NO
PREMISE
TELEPHONE
TELEPHONE
The following restrictions apply to KEYBUS wiring:
• KEYBUS should be run in minimum 22 gauge quad
(0.5mm); two pair twist is preferred.
• The modules should be home run to the panel but can
be connected in series or T-tapped .
• Any module can be connected anywhere along the
KEYBUS. You do not need to run a separate KEYBUS
wire for keypads, etc.
• No module can be more than 1,000'/330m (in wire
length) from the panel.
• Shielded wire should not be used unless wires are run
in an area that presents excessive RF noise or other
such interference.
Example of KEYBUS Wiring
NOTE:
Module (A) is correctly
wired within 1,000'/330m
of wire from the panel.
Module (B) is correctly
wired within 1,000'/330m
of wire from the panel.
Module (C) is NOT wired
correctly as it is further
than 1,000'/330m from the
panel, in wire distance.
TO
2.4 Current Ratings – Modules and
Accessories
In order for the PC1580 system to operate properly, the
power output capabilities of the main control and the
expansion devices must not be exceeded. Use the data
TO
presented below to ensure that no part of the system is
overloaded and cannot function properly.
PC1580 (12 V
DC)
VAUX: 550 mA. Includes one keypad. Subtract for each
additional keypad, expansion module and accessory connected to VAUX or KEYBUS.
BELL: 700 mA. Continuous Rating. 3.0 A. Short Term.
Available only with stand-by battery connected.
PC1580 Device Ratings (@ 12 V
• LCD5500T Keypad: 50 mA
• PC5400 Serial Module: 65 mA
• PC5506T Keypad: 45 mA
• PC1575RK Keypad: 50 mA
• DLM-4: 160 mA standing / 180 mA transmitter
• Escort: 65 mA standing / 130 mA on-line
Other Devices
Please read the manufacturer’s literature carefully to
determine the maximum current requirements for each
device—during activation or alarm—and include the proper
values for loading calculations. Connected devices must
not exceed system capabilities during any possible
operational mode.
2.5 Keypad Assignment
There are eight available slots for keypads. LED keypads by
default are always assigned to slot 1; the LCD5500T is
always assigned to slot 8. Whereas the PC1575 LED keypad
must always be assigned to slot 1, the PC5506T and
DC)
4
G E T T I N G S T A R T E D
DOUBLE EOL CIRCUIT
1 NORMALLY CLOSED
LCD5500T keypads can each be assigned to a different slot
(1 to 8). Keypad enrollment is required since the panel must
know which slots are occupied in order to generate a fault
when a supervisory is not present.
How to Assign Keypads
Each keypad must be assigned one at a time. After
assigning all keypads, a supervisory reset should
be performed.
To assign a keypad to a slot, enter the following:
1. Enter Installer’s Programming.
2. Press [00] for Keypad Programming.
3. Press [0] for Slot Assignment.
4. Enter a two digit number (11-18) to specify which
supervisory slot the keypad will occupy.
Press the [#] key twice to exit programming. Continue this
procedure at each keypad until they have all been assigned
to the correct slot.
When using more than one LCD keypad, be sure
that only one is assigned to slot number 8.
2.6 Supervision
By default, all modules are supervised upon installation.
Supervision is enabled at all times so that the panel can
indicate a trouble if a module is removed from the system.
A connected module which does not show as being present
will appear as a trouble condition and the Trouble light on the
keypad will turn ON. This condition may be due to one or more
of the following reasons:
• the module is not connected to the KEYBUS
• there is a KEYBUS wiring problem
• the module is more than 1,000'/330m from the panel
• the module does not have enough power
For more information regarding module supervision troubles,
please refer to Section 3.4 (“[
✱] [2] Trouble Conditions”).
Modules will not be automatically supervised if
connected while in installers mode.
2.7 Removing Modules
The panel must be instructed to no longer supervise a module
being removed from the system. To remove the module,
disconnect it from the KEYBUS and reset the supervision
field by entering [92] in the installer’s programming. The
panel will be reset to recognize and supervise all existing
modules on the system.
2.8 Zone Wiring
For a complete description of the operation of all zone types,
please refer to Section 5.2 (“Zone Definitions”).
There are several different ways in which zones may be
wired, depending on which programming options have
been selected. Please refer to the following diagrams to
study each type of individually supervised zone wiring.
Any zone defined as Fire will automatically require a
single End of Line (EOL) resistor regardless of which
type of zone wiring supervision is selected. (See Section
5.2 “Zone Definitions.”) Reconfiguring the zone supervision from a non-default setting—from DEOL to EOL or
from NC to DEOL—may disable zones 1-6 while open or
in trouble. To prevent this situation, the system should be
powered down completely and powered up again.
2.8.1 Normally Closed (NC) Loops
ANY Z
TERMINAL
ANY COM
TERMINAL
2 NORMALLY CLOSED
CONTACTS WITH
NO END OF LINE
RESISTOR
ANY Z
TERMINAL
ANY COM
TERMINAL
NORMALLY CLOSED
CONTACT WITH
NO END OF LINE
RESISTOR
This option should only be selected if Normally Closed
(NC) detection devices or contacts are being used.
2.8.2 Single End Of Line (EOL) Resistors (5600W)
ANY Z
TERMINAL
ANY Z
TERMINAL
ANY COM
TERMINAL
NORMALLY
CLOSED
CONTACT WITH
END OF LINE
RESISTOR
ANY COM
TERMINAL
1 NORMALLY OPEN
CONTACT AND
1 NORMALLY CLOSED
CONTACT WITH
END OF LINE
RESISTOR
ANY Z
TERMINAL
ANY Z
TERMINAL
ANY COM
TERMINAL
NORMALLY OPEN
CONTACTS WITH
END OF LINE
RESISTOR
ANY COM
TERMINAL
2 NORMALLY OPEN
CONTACTS AND
2 NORMALLY CLOSED
CONTACTS WITH
END OF LINE
RESISTOR
This option should be selected if either Normally
Closed (NC) or Normally Open (NO) detection
devices or contacts are being used.
2.8.3 Double End of Line (DEOL) Resistors
Double End of Line resistors allow the panel to determine if
the zone is in alarm, tampered or faulted.
ANY Z
ANY COM
TERMINAL
TERMINAL
ALARM
CONTACT
CONTACT WITH
5600 END OF LINE
Ω
RESISTORS
This option can only be selected if Normally Closed
(NC) detection devices or contacts are being used
(ie: Do not use DEOL resistors for Fire zones.
Only one NC contact can be connected to each
zone. Multiple detection devices or contacts on a
single loop is not allowed.
The following chart shows zone status under certain
conditions:
• Loop Resistance ................................ Loop Status
The PC1580 alarm panel can be accessed, controlled and
completely programmed via any keypad on the system. The
LED keypad uses function and zone indicator lights to represent alarm functions and status. The LCD keypad provides a
written description on the liquid crystal display and uses
function indicator lights to communicate alarm status to the
user.
The following sections describe how to arm and disarm the
system from each type of keypad, and how to perform other
keypad functions.
3.1 Arming and Disarming
The system cannot be armed unless the Ready light is ON.
In order for the system to be in the Ready state, all protected
doors and windows must be secured and all movement in
areas covered by motion detectors must cease. When the
Ready light is ON, enter any valid access code. As each
digit is pressed, the keypad will beep. If the correct code is
entered when the system is not in the Ready state, the panel
will sound six quick beeps followed by a long two-second
beep to indicate that the system is not secured.
If an incorrect code is entered, the keypad will emit a steady
two second beep to indicate the invalid access code. When
the correct code is entered and the system is Ready, the
panel will emit six short beeps and the Armed light will turn
ON. Exit the premises through the designated entry/exit
door. For other methods of arming, please refer to section
✱] [0] Quick Exit” and “[✱] [9] Arming Without Entry
3.4 (“[
Delay”) and section 3.5 (“Function Keys”).
In an attempt to prevent false alarms, the Audible Exit Fault is
designed to notify the user of an improper exit when they arm
their system. If a non force-arming Delay 1 or Delay 2 type zone
is left open at the end of the exit delay, the entry delay will begin
immediately and the bell or siren will sound a steady alarm for
the entry delay period. At the end of the entry delay period, if
the system has not been disarmed it will go into alarm.
When you enter the premises through a designated entry/
exit door while the system is armed, the keypad will emit a
steady beep to remind you to disarm the system. Enter a
valid access code from any keypad to disarm the system. If
an error is made, press the [#] key and enter the code again.
When a correct code is entered, the Armed light will turn
OFF and the keypad will stop beeping. During the last 10
seconds of entry delay, the panel will pulse the keypad
beeper ON and OFF rapidly to warn you that the entry delay
is about to expire.
If an alarm occurred while the panel was armed, the Memory
light and the zone indicator lights corresponding to the
zones which went into the alarm will be flashing. Press the
[#] key to return the keypad to the Ready state.
3.2 Auto Bypass – Stay Arming
Stay arming allows the user to arm the system without
leaving the premises. All interior zones can be programmed
to be bypassed during Stay arming so that the user does not
have to bypass interior zones manually.
When the system is armed using a valid user code, if any
zones on the system have been programmed as Stay/Away
zones, the Bypass light will turn ON. The panel will then
monitor all zones programmed as Delay 1 and Delay 2
zones, such as designated entry/exit doors. If no delay type
zone is violated by the end of the exit delay, the panel will
bypass all Stay/Away type zones. The Bypass light will
remain ON to inform the user that the interior protection has
been automatically bypassed by the panel. If a delay zone
is violated during the exit delay, the Stay/Away zones will be
active after the exit delay expires.
The user can add the Stay/Away zones back into the system
at any time by entering the [
section 3.4 “[
Zones”).
Stay arming can also be initiated by pressing and holding
the Stay function key for two seconds on the PC5506T and
LCD5500T keypads, if programmed by the installer. For
more information regarding Stay arming, please see section
3.5 (“Function Keys”).
✱] [1] Bypassing and Reactivating Stay/Away
✱] [1] keypad command (see
3.3 Automatic Arming
The system can be programmed to Auto-Arm at a specific
time every day if it is in the disarmed condition.
In order for the Auto-Arm function to work properly, the
correct Time of Day must be programmed. To program the
clock and Auto-Arm times, see Section 3.4 ([
Functions)
When the system’s internal clock matches the Auto-ArmTime, the panel will check the system status. If armed, the
panel will do nothing until the next day at the Auto-ArmTime, when it will check the system again. If disarmed, the
panel will sound the buzzer of all keypads for one minute. If
a valid User Code is entered, the Auto-Arming will be
aborted.
If no code is entered, the panel will Auto-Arm. If a zone is
violated, the panel will transmit a Partial Closing ReportingCode – if programmed – to indicate to the central station that
the system is not secure. If the zone is restored, the panel
will add the zone back into the system (see Section 5.7
“Communicator – Reporting Codes”).
3.4 [✱] Commands
The [✱] key commands provide an easy way for the user to
access basic system programming – such as entering user
codes or bypassing zones. The user can also use the [
commands to check on the system’s status, including viewing
trouble conditions and displaying the event buffer on the LCD
keypad.
The [
✱] key commands can be performed from both LCD
and LED keypads. The LED keypad uses the zone indicator
lights to display command information. The LCD display
provides written information, guiding the user through each
command. The commands in this section are explained as
viewed from an LED keypad. When using an LCD keypad,
use the arrow keys (< >) to scroll through information
provided. Otherwise, the functions remain the same for both
keypad types.
[✱] [1]Bypassing and Reactivating Stay/
Away Zones
The [✱] [1] keypad command can be used to bypass
individual zones. A bypassed zone will not cause an alarm.
The user can bypass zones to gain access to an area while
arming the rest of the system or to override a defective
zone—due to a bad contact or damaged wiring—until
service can be provided.
✱] [6] User
✱] key
7
KEYPADVCOMMANDS
If the Code Required for Bypass option is enabled, only
user codes with the Bypass attribute enabled will be able to
bypass zones (see section 5.1 “Programming Security
Codes”).
If the Bypass Status Displayed While Armed is chosen,
the Bypass light will be ON while the system is armed to
indicate any bypassed zones (see section 5.15 “Arming /
Disarming Options”).
Zones can only be bypassed when the system is
disarmed.
To bypass a zone:
1. Enter [
✱] [1] (and an access code, if required).
2. The keypad will flash the Bypass light and the zone
indicator lights corresponding to any zones already
bypassed will turn ON.
3. Enter the number corresponding to the zone you wish
to bypass. The corresponding zone indicator light will
turn ON.
4. Press [#] to exit the function.
All zones whose indicator lights are ON when the [#]
key is pressed will be bypassed. The Bypass light will
turn ON, indicating that zones are bypassed.
To reactivate a bypassed zone:
1. Enter [
✱] [1] (and an access code if required).
2. The keypad will flash the Bypass light. The zone
indicator lights corresponding to any zones already
bypassed will turn ON.
3. Enter the number corresponding to the bypassed zone
you wish to reactivate. The corresponding zone
indicator light will turn OFF.
4. Press [#] to exit the function.
All zones whose indicator lights are ON when the [#]
key is pressed will be bypassed. If no zone indicator
lights were ON, the Bypass light will be OFF and no
zones will be bypassed.
When the system is disarmed, all manually-bypassed zones will be unbypassed.
Reactivate Interior
If the system is armed in the Stay mode, the [
✱] [1] command
can be used to reactivate the Stay/Away zones.
Reactive Stay/Away cannot be used with an alarm in
memory.
Please ensure all force-armed zones are restored
before reactivating the Stay/Away zones (See
Section 5.3 “Zone Attributes”).
[✱] [2]Trouble Display
The panel constantly monitors itself for several different
trouble conditions. If a trouble condition is present, the
Trouble light will be ON and the keypad will beep twice
every 10 seconds. The trouble beep can be silenced by
pressing any key on any keypad.
To view trouble conditions from an LED keypad:
1. Press [✱] [2].
2. The keypad will flash the Trouble light. The zone indicator
lights corresponding to the present trouble conditions
will be ON.
When using an LCD keypad, the trouble conditions will be
listed on the display; the user must simply use the arrow (< >)
keys to scroll through the list of present trouble conditions.
The various troubles are described below:
Trouble [1] – Service Required
If zone indicator light [1] is ON, a “service required” trouble
is present. Press [1] to determine the specific trouble. The
following is a list of “service required” trouble conditions:
• Light [1] – Low Battery
The main panel backup battery is low. The trouble will
be generated if the battery drops below 11.5 volts
under load and will be restored when the battery
charges to over 12.5 volts.
• Light [2] – Bell Circuit Trouble
The panel will indicate this trouble if the Bell fuse is
blown or if the panel senses an open condition on the
bell circuit (see Section 5.12 “Siren Supervision”).
• Light [3] – General System Trouble
This trouble will be present if the printer connected to
the PC5400 Printer module has a fault and is off-line, or
if the ESCORT module does not detect the Power Line
Interface Module.
• Light [4] – General System Tamper
This trouble will be indicated if any peripheral module
tamper is detected.
• Light [5] – General System Supervisory
This trouble will be indicated if the panel loses
communication with any module connected to the
KEYBUS (see Section 2.6 “Supervision”). The event
buffer will log a detailed description of the event.
Trouble [2] – AC Failure
This trouble indicates that AC power is no longer being
supplied to the control unit. The reporting codes in sections
[43] and [44] can be programmed to communicate a power
failure to the monitoring station. To avoid reporting short power
failures to the monitoring station, an AC FailureCommunication Delay from 000-255 minutes can be
programmed in section [62].
Trouble [3] – Communication Troubles
There are two types of telephone line trouble conditions. Press
[3] to display which type of trouble is present:
• [1] – Telephone Line Monitoring Trouble (TLM)
The telephone connection to the control unit is monitored
every 10 seconds. If the voltage drops below one to three
volts for the number of consecutive checks programmed
in section [62], a telephone line trouble is generated.
• [2] – Failure to Communicate (FTC)
This trouble will be generated if the communicator fails
to communicate with any of the programmed telephone
numbers. If a later attempt is successful, the FTC
reporting code(s) programmed in section [45] will be
transmitted along with the unreported events from an
earlier unsuccessful communication.
8
KEYPADVCOMMANDS
Trouble [4] – Zone Fault (including Fire Zone)
This trouble will be generated if any zone on the system is
experiencing trouble, meaning that a zone could not provide
an alarm to the panel if required to do so. When a zone fault
trouble condition occurs, the keypad(s) on the system will
start to beep.
Press [4] while in Trouble mode to view the affected zones.
A Fire zone trouble will be generated and displayed
in the armed state. A Fire zone trouble will also
restart the trouble beeps from all keypads.
Trouble [5] – Zone Tamper
This trouble is only generated by zones configured for
Double End Of Line Resistor Supervision when a tamper
condition is present. When a tamper condition occurs, the
keypad(s) will start to beep. Press [5] while in the Trouble
mode to view the affected zones.
Trouble [6] – Loss of System Time
This trouble occurs when the control unit is powered up and
the internal clock has not been set. Setting the time with User
Function [
✱][6][Master Code][1] will clear this trouble.
[✱] [3]Alarm Memory
The ‘Memory’ light will be on if any alarm occurred during the
last armed period or – in the case of 24 hour zones – if an
alarm occurred while the panel was disarmed.
To view alarm memory:
Press [✱] [3]. The keypad will flash the Memory light and the
zone indicator lights corresponding to the alarm or tamper
conditions which occurred during or since the last armed
period. To clear the Memory light, arm and disarm the
system.
[✱] [4]Door Chime On/Off
The door chime feature is used to sound a tone from the
keypad whenever a zone programmed as a chime zone is
activated (see Section 5.3 – “Zone Attributes”). If the door
chime feature is enabled, the keypad will emit five short
beeps whenever a chime zone is activated. Designated
entry/exit doors are often defined as chime zones; when the
feature is enabled, the keypads will sound when an entry/exit
door is opened.
To turn Door Chime ON or OFF:
1. Press [
✱] [4].
2. The keypad will emit three short beeps if the Door
Chime feature is enabled and one long beep when
disabled.
The function can also be peformed by pressing and holding
the Chime function key for two seconds on any PC5506T or
LCD5500T keypad.
[✱] [5]Programming Access Codes
There are 6 access codes available to the user. They are as
follows:
Access codes (2) to (6)..................Five User Codes
All access codes have the ability to arm or disarm the
system and can activate the PGM Outputs using the [
[1] [Access Code] and [
✱] [7] [2] commands.
✱] [7]
Master Code – Access Code (1)
By default, the Master Code is enabled to perform any
keypad function. This code can be used to program all User
Codes. If the Master Code Not Changeable option is
enabled, the Master Code can only be changed by the
Installer.
User Codes – Access Codes (2) to (6)
User codes can arm and disarm the system. By selecting
the No Code Required for Bypassing option, each user
can also have the ability to bypass zones without entering
an access code.
Duress Code – Access Code (6)
If the Sixth Code is Duress Code option is enabled, the
sixth code can be programmed by the user as a Duress
Code which will send a Duress reporting code to the central
station when entered.
For more information regarding access code options, please
see Section 5.1 – “Programming Security Codes.”
How to program User Codes:
1. Enter [
✱] [5] [Master Code]. The keypad will flash the
Program light. The zone indicator lights corresponding to
access codes already programmed will turn ON.
2. Enter the number corresponding to the code you wish to
program. The corresponding zone light will flash.
3. Enter a 4 digit code. The zone light will turn ON.
4. Continue from step 2 until all codes are programmed.
Once the process is complete, press the [#] key to return
to the Ready state.
Do not press [✱] or [#] when programming the 4 digit
code.
How to erase an Access Code:
✱] [5] [Master Code], select the code to be erased
Enter [
and press [
✱].
[✱] [6]User Functions
This keypad command can be used to program several
different functions. The programmable items are listed and
described below.
To program User Functions:
1. Press [
2.Press the number [0] to [9] for the item to be
• [1] – Time and Date
• [2] – Auto-Arm Enable/Disable
✱] [6] [Master Code]. The Program light will
flash.
programmed.
The time and date must be accurate for the Auto-Arm
or Test Transmission functions to work properly and for
the event buffer to time and date stamp all events.
- Enter the time (hour and minute) using military format
[HH MM] from 00:00 to 23:59.
- Enter the date by month, day and year [MM DD YY].
Auto-Arming will not work unless it is enabled for the
system. To enable or disable auto-arming, press [2]. The
keypad will emit three short beeps if the Auto-Arm feature
is enabled and one long beep when disabled. For more
information, see Section 3.3 – “Auto-Arming”.
9
KEYPADVCOMMANDS
• [3] – Auto-Arm Time
The system can be programmed to Auto-Arm at a
certain time. When programming the auto-arming time,
enter the time (hour and minute) using military format
[HH MM]. For more information, see Section 3.3 –
“Auto-Arming”.
• [4] – System Test
When [4] is pressed the panel will test the bell output,
keypad lights and the communicator for two seconds.
The panel will also send a System Test Reporting
code, if programmed (see Section 5.7 – “Communicator – Reporting Codes”).
• [5] – Enable DLS (Downloading)
When [5] is pressed, the panel will enable the downloading option for one hour. During this time the panel
will answer incoming downloading calls (see Section
5.9 “Downloading”).
• [6] – User Initiated Call-Up
When [6] is pressed, the panel will initiate call-out to
the downloading computer.
• [7] – Last Code to Disarm and Arm
Pressing [7] will display the last code to disarm the
system. Then, pressing [9] will display the last code to
arm the system.
• [0] – Walk Test Enable / Disable
The Installer Walk Test can be used to verify that each
zone of the panel is functioning properly. Any zone
violated during a walk test will cause the panel to
activate the Bell Output for two seconds, log the event
to the Event Buffer and communicate the alarm to
central station. Do not tamper or fault zones while in
walk test. You can exit walk test with zones open. You
can cancel walk test by arming with all zones restored.
Additional Features using the LCD Keypad
Additional features, including access to the Event Buffer, are
available using the LCD keypad. Use the arrow keys (< >) to
scroll through the [
✱] [6] menu and press the [✱] key to select
the following commands:
Viewing the Event Buffer from an LCD Keypad
Select “View Event Buffer” from the [
✱] [6] menu. The
keypad will display the event, event number, time and date
along with the zone number and user code, if applicable.
Press [
✱] to toggle between this information and the event
itself. Use the arrow keys (<>) to scroll through the events
in the buffer. When you have finished viewing the Event
Buffer, press the [#] key to exit.
Brightness Control
The LCD keypad will allow you to select from 10 different
backlighting levels. Use the arrow keys (< >) to scroll to the
desired backlighting level and press the [#] key to exit.
Contrast Control
The LCD keypad will allow you to select from 10 different
display contrast levels. Use the arrow keys (< >) to scroll to
the desired contrast level and press the [#] key to exit.
Keypad Beeper Control
The LCD keypad will allow you to select from 21 different
keypad beeper tones. Use the arrow keys (< >) to scroll to
the desired keypad beeper level and press the [#] key to
exit. This featured can be accessed on LED keypads by
holding the [
✱] key.
[✱] [7]Output Functions
There are two output functions available to the user: Utility
Output and Sensor Reset.
To activate Utility Output:
✱] [7] [1][Access Code].
Press [
The panel will activate all PGM Outputs programmed as
utility outputs for five seconds (see Section 5.10 – “PGM
Outputs”).
To activate Sensor Reset:
✱] [7] [2].
Press [
The panel will activate all PGM Outputs programmed as
Sensor Reset for five seconds.
This function can also be performed by pressing and
holding the Reset function key for two seconds on any
PC5506T or LCD5500T keypad.
[✱] [8]Installer’s Programming
Enter [✱] [8] followed by the Installer’s Code to enter this
function. Installer’s Programming is outlined in detail in
Sections 4 and 5 of this manual.
[✱] [9]Arming Without Entry Delay
When the system is armed with the [✱] [9] command, the
panel will cancel the entry delay. Once the exit delay has
expired, Delay 1 and Delay 2 type zones will be instant and
Stay/Away zones will be bypassed (see Section 5.2 – “Zone
Definitions”). A valid access code must be entered after
pressing [
✱] [9].
[✱] [0]Quick Arm
If the Quick Arm option is enabled, the panel can be armed
without a user code by entering [
✱] [0] (See Section 5.15
“Arming / Disarming Options”).
Quick Arm cannot be used to cancel Auto Arm.
Quick Exit
The Quick Exit function, if enabled, will allow someone to
leave an armed premises through a Delay type zone without
having to disarm and rearm the system (See Section 5.15
“Arming / Disarming Options”).
When [
✱] [0] is entered, the panel will provide a two minute
window for the user to exit the premises. During this time, the
panel will ignore only one activation of a Delay zone. When
the Delay zone is secured, the panel will end the two minute
quick exit delay.
If a second Delay zone is tripped or if the zone is not restored
after two minutes, the panel will begin the entry delay.
If the Exit Delay is in progress, performing a Quick
Exit will not extend the Exit Delay.
3.5 Function Keys
The function keys only appear on the PC5506T and
LCD5500T keypads
There are five function keys on the PC5506T and LCD5500T
keypads located to the right of the number pad labelled
Stay, Away, Chime, Reset and Exit. Each of these keys are
programmed by default to perform one of the functions
10
KEYPADVCOMMANDS
[06] – [
described below. A function is activated by pressing and
holding the appropriate key for two seconds.
“Stay” – Stay Arm
Pressing this key will arm the system in the Stay mode,
meaning that all Stay/Away type zones will be automatically
bypassed. Delay type zones will provide entry and exit
delay. The Quick Arm feature must be enabled in order for
this key to function (programming section [10], option [6]).
“Away” – Away Arm
Pressing this key will arm the system in the Away mode. All
Stay/Away type zones and all other non-bypassed zones
will be active at the end of the exit delay. Delay type zones
will provide entry and exit delay. The Quick Arm feature must
be enabled in order for this key to function.
“Chime” – Door Chime On / Off
Pressing this key will toggle the Door Chime feature ON or
OFF. One solid beep means that the feature has been
disabled and three short beeps means that it has been
enabled (see Section 3.4 – “[
✱] [4] Door Chime”).
“Reset” – Reset Smoke Detectors
Pressing this key will cause the panel to activate for five
seconds all PGM outputs programmed as Sensor Reset.
“Exit” – Activate Quick Exit
Pressing this key will cause the panel to activate the Quick Exit
feature (See Section 3.4 – “[
✱] [0] Quick Exit”).
3.5.1 Function Key Options
The following is a list of Function Key options available.
Each option is listed according to their programming code,
followed by their corresponding [
✱] key command. For more
information regarding each function, please refer to the
appropriate segment in section 3.4 (“[
✱] Commands”)
[00] – Null Key
The key is not used and will perform no function when
pressed.
[01]-[02]– Not Used
[03] – Stay Arm
Same as described in Function Keys – Section 3.5.
[04] – Away Arm
Same as described in Function Keys – Section 3.5.
✱] [9] No-Entry Delay Arm
[05] – [
Once this function key is pressed the user must enter a valid
✱] [4] Door Chime On / Off
Same as described in Function Keys – Section 3.5.
✱] [6] [----] [4] System Test
[07] – [
This function key provides the user with a simple method for
testing the system.
✱] [1] Bypass Mode
[08] – [
This function key provides the user with a simple method for
entering the Bypass Mode. If a user code is required, it must
be entered before zone bypassing can be performed.
✱] [2] Trouble Display
[09] – [
This function key provides the user with a simple method for
entering the Trouble Display Mode.
✱] [3] Alarm Memory
[10] – [
This function key provides the user with a simple method for
entering the Alarm Memory Display Mode.
✱] [5] Programming Access Codes
[11] – [
This function key provides the user with a simple method for
programming user codes. Once this key is pressed, a valid
master code must be entered before the panel will allow
programming to be performed.
[12] – [
✱] [6] User Functions
This function key provides the user with a simple method for
programming user functions. Once this key is pressed, the
Master code must be entered before the panel will allow user
functions to be performed.
[13] – [
✱] [7] [1] Utility Output
This function key provides the user with a simple method for
activating a PGM Output programmed as utility output (see
section 5.10 – “PGM outputs”). Once this key is pressed, a
valid user code must be entered.
[14] – [
✱] [7] [2] Sensor Reset
Same as described in Function Keys – Section 3.5.
[15] – Not Used
✱] [0] Quick Exit
[16] – [
Same as described in Function Keys – Section 3.5.
✱] [1] Reactivate Stay/Away Zones
[17] – [
This function key provides the user with a simple method for
adding Stay/Away zones back into the system at night-time
(see Section 3.4 – “[
✱] [1] Bypassing and Reactivating Stay/
Away Zones”).
user code. The system will arm and remove the entry delay
from the system when the exit delay expires (see Section 3.4
– “[
✱] [9] Arming Without Entry Delay”).
11
G E T T I N G S T A R T E D
How to Program
SECTION4
The following section of the manual describes the Installer’s
Programming function and how to program the various sections.
You must read the following section of the manual
very carefully before you begin programming. We
also recommend filling out the Programming
Worksheets before you program the panel.
For your reference, the corresponding programming sections for
the functions listed are highlighted in text boxes such as this one.
4.1 Installer’s Programming
Installer’s Programming is used to program all communicator
and panel options. The Installer’s Code is [1575] by default
but may be changed to prevent unauthorized access to
programming.
Step 2 Enter the two digit Section number corresponding
Step 3 Enter the information required to complete
If the two digit Section numbered entered is invalid,
or if the module which pertains to the section is not
present, the keypad will sound a two second error
tone.
From an LCD Keypad:
Step 1 From any keypad, enter [
Step 2 Enter the two digit number corresponding to
Step 3 Enter the information required to complete
If you enter information into a section and make a mistake,
press the [#] key to exit the section. Select that section again
and re-enter the information correctly.
✱] [8] [Installer’s Code].
• The Program light will flash to indicate you are
in programming mode.
• The Armed light will turn ON to indicate that the
panel is waiting for the two digit programming
section number.
to the section you wish to program.
• The Armed light will turn OFF.
• The Ready light will turn ON to indicate that the
panel is waiting for the information required to
complete programming the selected section.
section programming (ie: numbers, HEX data, or
ON/OFF options).
✱] [8] [Installer’s
Code]. The Keypad will display ‘Enter
Section’ followed by two dashes.
the programming section number you wish to
program. The keypad will now display the
information required to complete
programming the selected section.
section programming (ie: numbers, HEX
data, or ON/OFF options).
4.2 Programming Decimal Data
A set number of programming boxes are allotted for each
section requiring decimal data (e.g.: codes, telephone
numbers). If a digit is entered for each program box, the
panel will automatically exit from the selected programming
section. The Ready light will turn OFF and the Armed light
will turn ON.
You can also press the [#] key to exit a programming section
without entering data for every box. This is handy if you only
need to change digits in the first few programming boxes.
All other digits in the programming section will remain
unchanged.
4.3 Programming HEX Data
On occasion, hexadecimal (HEX) digits may be required. To
program a HEX digit press the [
HEX programming and Ready light will begin to flash.
The following are the numbers which should be pressed to
enter the appropriate HEX digit:
1 = A2 = B3 = C4 = D5 = E6 = F
After the correct HEX digit is entered, the Ready light will
continue to flash. If another HEX digit is required, press the
corresponding number. If a decimal digit is required, press
the [
✱] key again. The Ready light will turn ON and the panel
will return to regular decimal programming.
Example:
To enter ‘C1’ for a closing by user 1, you would enter
[
✱] to enter Hexadecimal mode (Ready light flashes)
[
[3] to enter C
✱] to return to decimal mode (Ready light is solid);
[
[1] to enter digit 1
If Ready light is flashing, any number you enter will
be programmed as the HEX equivalent.
If you are using a pulse format, a decimal zero [0] does not
transmit. Programming a zero [0] tells the panel not to send
any pulses for that digit. Decimal zero [0] is a filler digit. To
make a zero [0] transmit, it must be programmed as a
Hexadecimal ‘A’.
Example:
For the three digit account number ‘403’, you would enter
[4], [
[4] to enter the digit 4;
✱] to enter Hexadecimal mode (Ready light flashes)
[
[1] to enter A
✱] to return to decimal mode (Ready light is solid);
[
[3] to enter the digit 3;
[0] to enter the digit 0 as a filler digit.
✱] key. The panel will enter
✱] [3] [✱] , [1]
✱] [1] [✱] [3], [0].
4.4 Programming Toggle Option Sections
Some Sections contain several toggle options. The panel
will use zone lights 1 through 6 to indicate if the different
options are enabled or disabled. Press the number
corresponding to the option to turn it ON or OFF. Once all the
toggle options have been selected correctly, press the [#]
key to exit the section and save the changes. The Ready
12
HOWVTOVPROGRAM
light will turn OFF and the Armed light will turn ON.
Refer to Section 5 in this manual to determine what each
option represents and whether the light should be ON or
OFF for your application.
4.5 Viewing Programming
LED Keypads
Any programming section can be viewed from an LED
keypad. When a programming section is entered, the keypad
will immediately display the first digit of information
programmed in that section.
The keypad displays the information using a binary format,
where
Zone Light 1 = 1Zone Light 2 = 2
Zone Light 3 = 4Zone Light 4 = 8
Add up the values for the zone lights to determine the
number displayed (for example, no zone lights = 0, all 4
zone lights = 15 HEX ‘F’).
Press any of the Emergency Keys (Fire, Auxiliary or Panic)
to advance to the next digit. When all the digits in a section
have been viewed, the panel will exit the section; the Ready
Light will turn OFF and the Armed light will turn ON, waiting
for the next two digit programming section number to be
entered. Press the [#] key to exit the section
LCD Keypad
When a programming section is entered, the keypad will
immediately display all the information programmed in that
section.
Use the arrow keys (< >) to scroll through the data being
displayed.
Scroll past the end of the data displayed or press the [#] key
to exit the section.
13
G E T T I N G S T A R T E D
Program Descriptions
SECTION5
The following section explains the operation of all programmable
features and options and provides a summary of all corresponding
programming locations.
5.1 Programming Security Codes
There are three codes which can be programmed by the
installer in the Installer’s Programming function: the Master
Code, a Second Master Code, and the Installer’s Code. All
other access codes can be programmed through the [
command (see Section 3.4).
The Master Code can also be programmed by the user as
access code (1). If the Master Code Not Changeable
option is enabled, the System Master Code can only be
changed by the Installer.
User codes can arm and disarm the system. By selecting
the No Code Required for Bypassing option, each user
code can also have the ability to bypass zones without
entering the Master Code.
If the Sixth Code is Duress Code option is enabled, the
sixth code can be programmed by the user as a Duress
Code which will send a Duress Reporting Code to the
central station when entered.
If the 6-Digit User Access Codes option is enabled, all the
access codes may be programmed with six digits instead of
four, with the exception of the Panel ID code and the
Downloading Access Code.
Second Master Code.............................................. Section [05]
Master Code Not Changeable ............. Section [09], option [1]
No Code Required for Bypassing........Section [09], option [2]
Sixth Code is Duress Code..................Section [09], option [3]
6-Digit User Access Codes .................. Section [81], option [4]
When enabling 6-digit access codes, if the master
code is anything other than default, the last two
digits will be [00].
✱] [5]
5.2 Zone Definitions
These sections will allow you to select how each of the 6
zones will operate. Each zone requires a two digit entry. In
addition to zone definitions, six different attributes may be
programmed by zone (see Section 5.3 – “Zone Attributes”).
[00] Null Zone
The zone is vacant. Unused zones should be programmed
as Null zones.
[01] Delay 1
This zone type, normally used for entry/exit doors, can be
violated during the exit delay time without causing an alarm.
Once the exit delay has expired, opening the zone will start
the entry delay timer. During the entry delay time, the
keypad buzzer will sound steadily to advise the user that the
system should be disarmed. If the panel is disarmed before
the entry time expires, no alarm will be generated.
[02] Delay 2
The Delay 2 entry delay time can be set independent of Delay
1 in programming section [02] (System Times).
[03] Instant Zone
This zone type will cause an instant alarm if it is violated
when the panel is armed. Typically, this zone is used for
windows, patio doors or other perimeter zones.
[04] Interior Zone
This zone will not cause an alarm if violated during the entry
delay. If the zone is violated before the entry delay has
begun, it will cause an instant alarm. Typically, this zone is
used for interior protection devices, such as motion detectors.
[05] Interior Stay/Away Zone
This zone type works similar to the Interior zone type except
that it will be automatically bypassed under the following
conditions:
• When the panel is armed in the Stay Mode (see Section
3.5 – “Function Keys”).
• When the panel is armed without entry delay (see
Section 3.4 – “[✱] [9] Arming Without Entry Delay”).
• When the panel is armed with a user code and a Delay
type zone is NOT tripped during the exit delay.
The automatic bypass prevents the user from having to
manually bypass interior type zones when arming at home.
This zone is typically used for interior protection devices,
such as motion detectors.
[06] Delay Stay/Away Zone
This zone type will operate similar to Interior Stay/Away zones
except that it will always provide an entry delay. Typically, this
zone is used for interior protection devices, such as motion
detectors. This zone option will help prevent false alarms
since it always provides an entry delay time for the user to turn
off the panel.
[07] Delayed 24 Hour Fire Zone
When this zone is violated, the alarm output will be
immediately activated but the communicator will be delayed
for 30 seconds. If the user presses any key on any keypad
during this delay, the alarm output and the communicator
will be delayed an additional 90 seconds, giving the user
time to correct the problem. If the zone is still violated after
the 90 second delay, the panel will sound the alarm ouput
and delay the communicator for 30 seconds.
If the user does not press a key during the 30 second delay,
the alarm output will latch and the panel will communicate
the alarm to the central station. The alarm will sound for the
Bell Cutoff time programmed in Section [02] (“System
Times”).
If a second Fire type zone is violated or if the Fire
keys are pressed during the delay period, the panel
will latch the alarm output and will immediately
communicate the alarm.
A violated Fire zone will be displayed on all keypads and
can be delayed at any keypad. Typically this zone is used
for latching smoke detectors.
[08] Standard 24 Hour Fire Zone
When this zone is violated, the panel will immediately latch
the alarm output and communicate to the central station.
The alarm will sound for the Bell Cutoff time programmed in
Section [02] (“System Times”).
A violated Fire zone will be displayed on all keypads.
Typically this zone is used for pull stations.
14
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.