DSC PC1580BABT Installation Manual

System Introduction
SECTION1
1.1 Specifications
Control Panel Specifications Flexible Zone Configuration:
• Six fully programmable zones
• Seven Access Codes: five User, one Master and a second Master code
• Normally Closed, Single EOL, Double EOL
Audible Alarm Output:
• Supervised Bell Output (current limited at 3 amps), 12 V
• Steady or Pulsed Output
EEPROM Memory: Does not lose programming or
system status on complete AC and Battery failure
Programmable Outputs:
• Two Programmable Voltage Outputs, 20
programmable options
- One High Current (300 mA) PGM output on main panel
- One Low Current (50 mA) PGM output on main panel
Powerful 1.5 Amp Regulated Power Supply:
• 550 mA Auxiliary Supply, 12 V
• Positive Temperature Coefficient (PTC) components replace fuses
• Supervision for loss of AC Power, Low Battery
• Internal Clock Locked to AC Power Frequency
Power Requirements:
• Transformer = 16.5 VAC, 40VA
• Battery = 12 volt 4 Ah minimum rechargeable sealed lead acid
Remote Keypad Specifications:
• Three Different Keypads Available:
- PC5506T 6 Zone LED Keypad
- LCD5500T Alphanumeric Keypad
- PC1575RK 6 Zone LED Keypad
• The PC5506T and LCD5500T keypads have 5 Fully Programmable Function Keys and Tampers
• Connect up to 8 Keypads
• Four Wire (Quad) Connection to KEYBUS
• Built in Piezoelectric Buzzer
Digital Communicator Specifications:
• Supports Major Formats including SIA, Scantronics 4-8-1 Slot and Contact ID
• Event Initiated Personal Paging
• Three Programmable Phone Numbers
• Two Account numbers
• DTMF and Pulse Dialing
• DPDT Line Seizure
• Anti-jam Feature
• Split Reporting of Selected Transmissions to Each Telephone Number
DC
System Supervision Features
The PC1580 continuously monitors a number of possible trouble conditions including:
• AC Power Failure
• Trouble by Zone
• Tamper by Zone
• Fire Trouble
• Telephone Line Trouble
• Failure to Communicate
DC
• Low Battery Condition
• Bell Output Trouble
• Module Fault (Supervisory or Tamper)
• Loss of Internal Clock
• AUX Power Supply Fault
False Alarm Prevention Features
• Audible Exit Delay
• Audible Exit Fault
• Communication Delay
• Urgency on Entry Delay
• Quick Exit
Additional Features
• Auto Arm at Specified Time
• Keypad Activated Alarm Output and Communicator Test
• All modules connect to the system via a four wire KEYBUS up to 1000’/330m from main panel
• Event Buffer can be printed using PC5400 RS232 Serial Interface module
• Supports the ESCORT 5580 Voice Prompt Module with Automation/Lighting Control
• An Event Buffer which records the past 100 events with both the time and date at which they occured
• Uploading and Downloading capability
• Local Downloading capability with the use of the PC-LINK Adaptor
• Time compensation feature
1.2 Additional Devices
1.2.1 Keypads
A maximum of eight keypads can be connected to the control panel and can be any combination of the following listed.
• PC5506T 6 zone LED keypad with function keys and
tamper
• LCD5500T LCD keypad with function keys and tamper
• PC1575RK 6 zone LED keypad
1.2.2 ESCORT5580 Module
There are many benefits to adding the ESCORT5580 module to a security system. The ESCORT5580 module will turn any touch tone phone in the world into a fully functional keypad. Imagine the security a customer would feel if they had the ability to arm, disarm and check status of their alarm system while at the office or on vacation.
1
SYSTEMV INTRODUCTION
All touch tone phones in the home also become system keypads. For example, at bedtime, the phone beside the bed can be used to arm the system. The addition of the ESCORT5580 may reduce the cost of the overall installation, eliminating the need for additional keypads and the labour of running wires.
The ESCORT5580 will also act as a tutor for the system. By using clear, easy to understand sentences, the voice module helps guide the user through functions they may otherwise find difficult to navigate. Programmable zone labels (up to 6 words each from our library of over 240 words) makes the system even easier to use.
The module also has a built-in power line control interface and can control up to 32 power line control devices for lighting and temperature control, giving you the power to add home automation in a very cost effective manner. Devices can be activated individually, as a group, by schedule or can be activated when an event occurs on the system, such as an alarm.
These are just a few of the applications available with the addition of the ESCORT5580 module. For more information, please refer to the ESCORT5580 Installation Manual.
1.2.3 PC5400 Printer Module
This module will give you the added advantage for the commercial customers who like the idea of a permanent record of openings and closing but are put off by the additional monthly monitoring charge. In addition, as reports are generated in real-time, the customer will not have to wait for a monthly report form the monitoring station.
The PC5400 Printer Module will allow the panel to print out all events that occur on the system to any serial printer. The printout will contain the time, date and the event that occurred (see Section – 5.25 “On-site Printer”).
1.2.4 Downlook Video Transmission Module
The Downlook Still-Frame Video Transmission Module (DLM­1/DLM-4) is the ideal solution for all business and residential environments which require visual surveillance but where the presence of on-site security personnel is impossible, undesirable or unaffordable.
Downlook is the smart and inexpensive way to add visual backup to your regular remote alarm signalling system, meeting your demand for tighter security on a tight budget. The added visual protection will reduce the incidence of false alarms as well as surveillance costs, thus improving the overall security protection.
For more information regarding the Downlook Video Transmission Module, please consult the DLM-1/DLM-4 Installation Manuals.
1.2.5 Cabinets
Several different cabinets are available for the PC1580 modules. They are as follows:
PC5003C Cabinet
Control cabinet for the PC1580 main panel. Dimensions 288mm x 298mm x 78mm / 11.3” x 11.7” x 3” approximately.
PC5004C Cabinet
Cabinet to house the Escort5580 Module or the PC5400 Printer Module. Dimensions 229mm x 178mm x 65mm / 9” x 7” x 2.6” approximately.
1.3 Out of the Box
Please verify that each of the following components is included in your system:
• one PC1580 control cabinet
• one PC1580 control circuit board
• one keypad (LED keypad or LCD keypad)
• one Installation Manual including Programming
Worksheets
• one Instruction Manual for the end user
• one hardware pack consisting of:
-four plastic circuit board standoffs
-twelve 5600 (5.6K) resistors
-one 2200 (2.2K) resistors
-one 1000 (1K) resistor
-EGND Assembly
-one cabinet door plug
• 220V to16.5V AC transformer with fuseblock
• two yellow safety hazard warning labels to be applied by the
installer
Enclosed 240V AC Warning Labels
The Health & Safety (Signs and Signals) Regulations state that warning signs must be displayed to warn people to be careful to take precautions where a hazard exits.
These signs also comply to the Electricity at Work Regulation 1989 and BS5378. The Regulations for Electrical Installation (16 Edition) Section
514-10 Warning Notice Voltage. Every Item of Equipment or enclosure within which a voltage
exceeding 250 Volts exists, and where the presence of such a voltage would not normally be expected, shall be so arranged that before access is gained to a live part, a warning of the maximum voltage present is clearly visible.
It is recommended that one of the enclosed warning stickers be attached to the external area of the control panel housing to give indication of voltage before access is gained to the transformer area. The second enclosed warning sticker should be placed on the front plate of the unswitched fuse unit to give indication of mains connection within.
DSC accepts no responsibility for the non use of these warning labels and can confirm that it is the responsibility of the installation engineers to attach them to the required devices during the installation process. The warning labels are enclosed to be used in accordance with the Health and Safety regulations and also the electricity at work act 1989.
2
Getting Started
SECTION2
The following Sections provide a thorough description of how to wire and configure devices and zones.
2.1 Installation Steps
The following steps are provided to assist you with installing the panel. We suggest that you read this section in its entirity before you begin. Once you have an overall understanding of the installation process, carefully work through each step. Working in this manner will reduce the number of problems as well as the amount of time required for a complete installation.
Step 1 Create a Layout
Draw a rough sketch of the building to get an idea of where all alarm detection devices, keypads and other modules are to be located.
Step 2 Mounting the Panel
Locate the panel in a dry area close to an unswitched AC power source and the incoming telephone line. Before attaching the cabinet to the wall, be sure to press the four circuit board mounting studs into the cabinet from the back. After you have attached the cabinet to the wall, stick the provided DSC logo sticker on the front of the cabinet.
You must complete all wiring before applying AC or connecting the battery to the panel.
Step 3 Wiring the KEYBUS (Section 2.3)
Wire the KEYBUS to each of the modules following the guidelines provided in Section 2.3 of this manual.
Step 4 Zone Wiring (Section 2.8)
You must power down the control panel to complete all zone wiring. Please refer to Section 2.8 when connecting zones using normally closed loops, single EOL resistors, double EOL resistors, Fire zones and Keyswitch Arming zones.
Step 5 Complete Wiring (Section 2.2)
Complete all other wiring including bells or sirens, phone line connections, and ground connections following the guidelines provided in Section 2.2 (“Terminal Descriptions”).
Step 6 Power up the Control
Once all zone and KEYBUS wiring is complete, power up the control panel.
The panel will not power up on the battery connec­tion alone.
Step 7 Keypad Assignment (Section 2.5)
In order for keypads to be properly supervised, each must be assigned to a different slot. Please follow the guidelines provided in Section 2.5 when assigning keypads.
Step 8 Supervision (Section 2.6)
The supervision of every module by the panel is automatically enabled upon power up. Please verify that all modules appear on the system according to the instructions in Section 2.6.
Step 9 Programming the System (Sections 4 and 5)
Section 4 explains how to program the panel. Section 5 contains a complete description of the various programmable features, which options are available and how they function. The Programming Worksheets (pages 25-33) should be filled out completely before attempting to program the system.
Step 10 Testing the System
The panel must be thoroughly tested to ensure that all features and functions are operating as programmed.
2.2 Terminal Descriptions
AC Terminals – AC (50Hz)
The panel requires a 16.5 volt, 40 VA transformer. Connect the transformer to an unswitched AC source and connect the transformer to these terminals.
Do not connect the transformer until all other wiring is complete. The panel must have a power line frequency of 50Hz.
Battery Connection
A 12V 4Ah rechargable gel-cell battery is used as a back up source of power in the event of an AC power failure. The battery also provides additional current when the panel’s demands exceed the power output of the transformer, such as when the panel is in alarm.
Do not connect the battery until all other wiring is complete.
Connect the RED battery lead to the positive battery terminal; connect the BLACK lead to negative.
Auxiliary Power Terminals – AUX+ and AUX-
These terminals provide up to 550 mA of additional current
DC for devices requiring power. Connect the positive
at 12 V side of any device requiring power to the AUX+ terminal, the negative side to AUX- (ground). The AUX output is protected. This means that if too much current is drawn from these terminals (such as a wiring short), the panel will temporarily shut off the output until the problem is corrected.
Bell Output Terminals – BELL+ and BELL- (Section 3.4)
These terminals provide up to 700 mA of continuous current at 12 V
DC for powering bells, sirens, strobes or other warning-
type equipment. Connect the positive side of any alarm warning device to BELL+, the negative side to BELL–. Please note that the Bell output is protected: if too much current is drawn from these terminals (such as a wiring short), the Bell fuse will open. Three Amps can be drawn for short periods only.
The Bell output is supervised. If no alarm warning devices are in use, connect a 1000 ohm resistor across BELL+ and BELL– to prevent the panel from displaying a trouble condition. For more information, please refer to Section 3.4
] [2] Trouble Display”).
(“[ The bell is programmed by default to terminate after four
minutes. The Bell Cutoff time can be adjusted in programming section [02] (“System Times”).
KEYBUS Terminals – AUX+, AUX-, YEL, GRN (Section 2.3)
The KEYBUS is used by the panel to communicate with modules and vice versa. Each module has four KEYBUS terminals that must be connected to the four KEYBUS terminals on the panel. For more information, see Section
2.3 (“KEYBUS Operation and Wiring”).
3
G E T T I N G S T A R T E D
Programmable Outputs – PGM1 and PGM2
Each PGM output is designed so that when activated by the panel, the terminal will switch to ground.
PGM2 can sink up to 50 mA of current to activate LEDs or a small buzzer. Connect the positive side of the LED
+AUX PGM1
RED
or buzzer to AUX+, the negative side to PGM2. If more than 50 mA of current are required, a relay must be used. Please study PGM wiring in the accompanying diagram.
PGM1 is a high current output which
COM NC
operates similar to PGM2. PGM1 is used for high current output (300mA).
Zone Input Terminals – Z1 to Z6
Each detection device must be connected to a zone on the control panel. We suggest that one detection device be connected to each zone; wiring multiple detection devices to a single zone, however, is possible. For zone wiring specifics, please see Section 2.8 (“Zone Wiring”).
Telephone Connection Terminals – TIP, RING, T-1, R-1
If a telephone line is required for central station communication or downloading, connect an RJ-31X telephone jack in the following manner:
• TIP - Green Wire incoming line from
RING TIP R-1
RED
GRN
EGND
T-1
GRY
BRN
RJ31X TELEPHONE PLUG
• RING - Red Wire telephone company
• R-1 - Grey Wire outgoing line to
• T-1 - Brown Wire house telephone(s)
Please ensure that all plugs and jacks meet the correct dimension, tolerance and metallic plating
requirements. For proper operation, no other telephone equipment should be connected between the control panel and the telephone company facilities. Do not connect the alarm panel communicator to telephone lines intended for use with a fax machine. These lines may incorporate a voice filter which disconnects the line if anything other than fax signals are detected, resulting in incomplete transmissions.
2.3 KEYBUS Operation and Wiring
The KEYBUS is used by the panel to communicate with all connected modules and vice versa. The red (AUX+) and black (AUX-) terminals are used to provide power, while the yellow (YEL) and green (GRN) terminals are clock and data respectively.
The four KEYBUS terminals of the panel must be connected to the four KEYBUS terminals or wires of all modules.
(ANY OUTPUT
TERMINAL)
BLK
DSC
RM-1
YEL
WHT
GRN
NO
PREMISE
TELEPHONE
TELEPHONE
The following restrictions apply to KEYBUS wiring:
• KEYBUS should be run in minimum 22 gauge quad
(0.5mm); two pair twist is preferred.
• The modules should be home run to the panel but can
be connected in series or T-tapped .
• Any module can be connected anywhere along the
KEYBUS. You do not need to run a separate KEYBUS wire for keypads, etc.
• No module can be more than 1,000'/330m (in wire
length) from the panel.
• Shielded wire should not be used unless wires are run
in an area that presents excessive RF noise or other such interference.
Example of KEYBUS Wiring NOTE:
Module (A) is correctly
wired within 1,000'/330m of wire from the panel.
Module (B) is correctly wired within 1,000'/330m of wire from the panel.
Module (C) is NOT wired correctly as it is further than 1,000'/330m from the panel, in wire distance.
TO
2.4 Current Ratings – Modules and Accessories
In order for the PC1580 system to operate properly, the power output capabilities of the main control and the expansion devices must not be exceeded. Use the data
TO
presented below to ensure that no part of the system is overloaded and cannot function properly.
PC1580 (12 V
DC)
VAUX: 550 mA. Includes one keypad. Subtract for each
additional keypad, expansion module and acces­sory connected to VAUX or KEYBUS.
BELL: 700 mA. Continuous Rating. 3.0 A. Short Term.
Available only with stand-by battery connected.
PC1580 Device Ratings (@ 12 V
• LCD5500T Keypad: 50 mA
• PC5400 Serial Module: 65 mA
• PC5506T Keypad: 45 mA
• PC1575RK Keypad: 50 mA
• DLM-4: 160 mA standing / 180 mA transmitter
• Escort: 65 mA standing / 130 mA on-line
Other Devices
Please read the manufacturer’s literature carefully to determine the maximum current requirements for each device—during activation or alarm—and include the proper values for loading calculations. Connected devices must not exceed system capabilities during any possible operational mode.
2.5 Keypad Assignment
There are eight available slots for keypads. LED keypads by default are always assigned to slot 1; the LCD5500T is always assigned to slot 8. Whereas the PC1575 LED keypad must always be assigned to slot 1, the PC5506T and
DC)
4
G E T T I N G S T A R T E D
DOUBLE EOL CIRCUIT 1 NORMALLY CLOSED
LCD5500T keypads can each be assigned to a different slot (1 to 8). Keypad enrollment is required since the panel must know which slots are occupied in order to generate a fault when a supervisory is not present.
How to Assign Keypads
Each keypad must be assigned one at a time. After assigning all keypads, a supervisory reset should be performed.
To assign a keypad to a slot, enter the following:
1. Enter Installer’s Programming.
2. Press [00] for Keypad Programming.
3. Press [0] for Slot Assignment.
4. Enter a two digit number (11-18) to specify which supervisory slot the keypad will occupy.
Press the [#] key twice to exit programming. Continue this procedure at each keypad until they have all been assigned to the correct slot.
When using more than one LCD keypad, be sure that only one is assigned to slot number 8.
2.6 Supervision
By default, all modules are supervised upon installation. Supervision is enabled at all times so that the panel can indicate a trouble if a module is removed from the system.
A connected module which does not show as being present will appear as a trouble condition and the Trouble light on the keypad will turn ON. This condition may be due to one or more of the following reasons:
• the module is not connected to the KEYBUS
• there is a KEYBUS wiring problem
• the module is more than 1,000'/330m from the panel
• the module does not have enough power
For more information regarding module supervision troubles, please refer to Section 3.4 (“[
] [2] Trouble Conditions”).
Modules will not be automatically supervised if connected while in installers mode.
2.7 Removing Modules
The panel must be instructed to no longer supervise a module being removed from the system. To remove the module, disconnect it from the KEYBUS and reset the supervision field by entering [92] in the installer’s programming. The panel will be reset to recognize and supervise all existing modules on the system.
2.8 Zone Wiring
For a complete description of the operation of all zone types, please refer to Section 5.2 (“Zone Definitions”).
There are several different ways in which zones may be wired, depending on which programming options have been selected. Please refer to the following diagrams to study each type of individually supervised zone wiring.
Any zone defined as Fire will automatically require a single End of Line (EOL) resistor regardless of which type of zone wiring supervision is selected. (See Section
5.2 “Zone Definitions.”) Reconfiguring the zone supervi­sion from a non-default setting—from DEOL to EOL or from NC to DEOL—may disable zones 1-6 while open or in trouble. To prevent this situation, the system should be powered down completely and powered up again.
2.8.1 Normally Closed (NC) Loops
ANY Z
TERMINAL
ANY COM
TERMINAL
2 NORMALLY CLOSED CONTACTS WITH NO END OF LINE RESISTOR
ANY Z
TERMINAL
ANY COM
TERMINAL
NORMALLY CLOSED CONTACT WITH NO END OF LINE RESISTOR
This option should only be selected if Normally Closed (NC) detection devices or contacts are being used.
2.8.2 Single End Of Line (EOL) Resistors (5600W)
ANY Z
TERMINAL
ANY Z
TERMINAL
ANY COM
TERMINAL
NORMALLY CLOSED CONTACT WITH END OF LINE RESISTOR
ANY COM
TERMINAL
1 NORMALLY OPEN CONTACT AND 1 NORMALLY CLOSED CONTACT WITH END OF LINE RESISTOR
ANY Z
TERMINAL
ANY Z
TERMINAL
ANY COM
TERMINAL
NORMALLY OPEN CONTACTS WITH END OF LINE RESISTOR
ANY COM
TERMINAL
2 NORMALLY OPEN CONTACTS AND 2 NORMALLY CLOSED CONTACTS WITH END OF LINE RESISTOR
This option should be selected if either Normally Closed (NC) or Normally Open (NO) detection devices or contacts are being used.
2.8.3 Double End of Line (DEOL) Resistors
Double End of Line resistors allow the panel to determine if the zone is in alarm, tampered or faulted.
ANY Z
ANY COM
TERMINAL
TERMINAL
ALARM
CONTACT
CONTACT WITH 5600 END OF LINE
RESISTORS
This option can only be selected if Normally Closed (NC) detection devices or contacts are being used (ie: Do not use DEOL resistors for Fire zones. Only one NC contact can be connected to each zone. Multiple detection devices or contacts on a single loop is not allowed.
The following chart shows zone status under certain conditions:
• Loop Resistance ................................ Loop Status
• 0 (shorted wire, loop shorted) ....... Fault
• 5600 (contact closed) .................... Secure
• Infinite (broken wire, loop open)....... Tamper
• 11200 (contact open) ..................... Violated
5
G E T T I N G S T A R T E D
2.8.4 Fire Zone Wiring — Four-Wire Smoke Detectors
All fire zones must be wired according to the following diagram:
4-WIRE SMOKE DETECTOR CONNECTION WITH RESET
TO ZONE "Z"
AUX++ BELL -1 PG M 2
ALARM CONTACT
ININOUT
OUT
TERMINAL PROGRAMMED FOR "FIRE"
TO ANY "COM" TERMINAL
OUT
IN
ALARM CONTACT
OUT
IN
MINIMUM 18 AWG WIRING IS REQUIR
FOR RESIDENTIAL FIRE ALARM SYST
BLK
RED
5600
END OF LINE RESISTOR
(EOLR-2)
2.8.5 Keyswitch Zone Wiring
If PGM2 has been
PGM2
AUX+
programmed for keyswitch operation (momentary or maintained), the keyswitches must be wired according to this diagram:
NORMALLY CLOSED CONTACT WITH 5600 END OF LINE
RESISTOR
WHT
POWER SUPERVISORY RELAY (DSC RM-1)
GRN
2.9 Wiring Gauge Conversion Table
North American Gauges Metric Wire Diameter
(AWG) (mm) AWG-14 1.62mm AWG-16 1.29mm AWG-18 1.02mm AWG-19 0.91mm AWG-20 0.81mm AWG-21 0.72mm AWG-22 0.64mm AWG-24 0.50mm
6
Keypad Commands
SECTION3
The PC1580 alarm panel can be accessed, controlled and completely programmed via any keypad on the system. The LED keypad uses function and zone indicator lights to repre­sent alarm functions and status. The LCD keypad provides a written description on the liquid crystal display and uses function indicator lights to communicate alarm status to the user. The following sections describe how to arm and disarm the system from each type of keypad, and how to perform other keypad functions.
3.1 Arming and Disarming
The system cannot be armed unless the Ready light is ON. In order for the system to be in the Ready state, all protected doors and windows must be secured and all movement in areas covered by motion detectors must cease. When the Ready light is ON, enter any valid access code. As each digit is pressed, the keypad will beep. If the correct code is entered when the system is not in the Ready state, the panel will sound six quick beeps followed by a long two-second beep to indicate that the system is not secured.
If an incorrect code is entered, the keypad will emit a steady two second beep to indicate the invalid access code. When the correct code is entered and the system is Ready, the panel will emit six short beeps and the Armed light will turn ON. Exit the premises through the designated entry/exit door. For other methods of arming, please refer to section
] [0] Quick Exit” and “[] [9] Arming Without Entry
3.4 (“[ Delay”) and section 3.5 (“Function Keys”).
In an attempt to prevent false alarms, the Audible Exit Fault is designed to notify the user of an improper exit when they arm their system. If a non force-arming Delay 1 or Delay 2 type zone is left open at the end of the exit delay, the entry delay will begin immediately and the bell or siren will sound a steady alarm for the entry delay period. At the end of the entry delay period, if the system has not been disarmed it will go into alarm.
When you enter the premises through a designated entry/ exit door while the system is armed, the keypad will emit a steady beep to remind you to disarm the system. Enter a valid access code from any keypad to disarm the system. If an error is made, press the [#] key and enter the code again. When a correct code is entered, the Armed light will turn OFF and the keypad will stop beeping. During the last 10 seconds of entry delay, the panel will pulse the keypad beeper ON and OFF rapidly to warn you that the entry delay is about to expire.
If an alarm occurred while the panel was armed, the Memory light and the zone indicator lights corresponding to the zones which went into the alarm will be flashing. Press the [#] key to return the keypad to the Ready state.
3.2 Auto Bypass – Stay Arming
Stay arming allows the user to arm the system without leaving the premises. All interior zones can be programmed to be bypassed during Stay arming so that the user does not have to bypass interior zones manually.
When the system is armed using a valid user code, if any zones on the system have been programmed as Stay/Away zones, the Bypass light will turn ON. The panel will then monitor all zones programmed as Delay 1 and Delay 2 zones, such as designated entry/exit doors. If no delay type zone is violated by the end of the exit delay, the panel will
bypass all Stay/Away type zones. The Bypass light will remain ON to inform the user that the interior protection has been automatically bypassed by the panel. If a delay zone is violated during the exit delay, the Stay/Away zones will be active after the exit delay expires.
The user can add the Stay/Away zones back into the system at any time by entering the [ section 3.4 “[ Zones”).
Stay arming can also be initiated by pressing and holding the Stay function key for two seconds on the PC5506T and LCD5500T keypads, if programmed by the installer. For more information regarding Stay arming, please see section
3.5 (“Function Keys”).
] [1] Bypassing and Reactivating Stay/Away
] [1] keypad command (see
3.3 Automatic Arming
The system can be programmed to Auto-Arm at a specific time every day if it is in the disarmed condition.
In order for the Auto-Arm function to work properly, the correct Time of Day must be programmed. To program the clock and Auto-Arm times, see Section 3.4 ([ Functions)
When the system’s internal clock matches the Auto-Arm Time, the panel will check the system status. If armed, the panel will do nothing until the next day at the Auto-Arm Time, when it will check the system again. If disarmed, the panel will sound the buzzer of all keypads for one minute. If a valid User Code is entered, the Auto-Arming will be aborted.
If no code is entered, the panel will Auto-Arm. If a zone is violated, the panel will transmit a Partial Closing Reporting Code – if programmed – to indicate to the central station that the system is not secure. If the zone is restored, the panel will add the zone back into the system (see Section 5.7 “Communicator – Reporting Codes”).
3.4 [] Commands
The [✱] key commands provide an easy way for the user to access basic system programming – such as entering user codes or bypassing zones. The user can also use the [ commands to check on the system’s status, including viewing trouble conditions and displaying the event buffer on the LCD keypad.
The [
] key commands can be performed from both LCD
and LED keypads. The LED keypad uses the zone indicator lights to display command information. The LCD display provides written information, guiding the user through each command. The commands in this section are explained as viewed from an LED keypad. When using an LCD keypad, use the arrow keys (< >) to scroll through information provided. Otherwise, the functions remain the same for both keypad types.
[] [1] Bypassing and Reactivating Stay/ Away Zones
The [✱] [1] keypad command can be used to bypass individual zones. A bypassed zone will not cause an alarm. The user can bypass zones to gain access to an area while arming the rest of the system or to override a defective zone—due to a bad contact or damaged wiring—until service can be provided.
] [6] User
] key
7
KEYPADV COMMANDS
If the Code Required for Bypass option is enabled, only user codes with the Bypass attribute enabled will be able to bypass zones (see section 5.1 “Programming Security Codes”).
If the Bypass Status Displayed While Armed is chosen, the Bypass light will be ON while the system is armed to indicate any bypassed zones (see section 5.15 “Arming / Disarming Options”).
Zones can only be bypassed when the system is disarmed.
To bypass a zone:
1. Enter [
] [1] (and an access code, if required).
2. The keypad will flash the Bypass light and the zone indicator lights corresponding to any zones already bypassed will turn ON.
3. Enter the number corresponding to the zone you wish to bypass. The corresponding zone indicator light will turn ON.
4. Press [#] to exit the function. All zones whose indicator lights are ON when the [#] key is pressed will be bypassed. The Bypass light will turn ON, indicating that zones are bypassed.
To reactivate a bypassed zone:
1. Enter [
] [1] (and an access code if required).
2. The keypad will flash the Bypass light. The zone indicator lights corresponding to any zones already bypassed will turn ON.
3. Enter the number corresponding to the bypassed zone you wish to reactivate. The corresponding zone indicator light will turn OFF.
4. Press [#] to exit the function. All zones whose indicator lights are ON when the [#] key is pressed will be bypassed. If no zone indicator lights were ON, the Bypass light will be OFF and no zones will be bypassed.
When the system is disarmed, all manually-by­passed zones will be unbypassed.
Reactivate Interior
If the system is armed in the Stay mode, the [
] [1] command
can be used to reactivate the Stay/Away zones.
Reactive Stay/Away cannot be used with an alarm in memory.
Please ensure all force-armed zones are restored before reactivating the Stay/Away zones (See Section 5.3 “Zone Attributes”).
[] [2] Trouble Display
The panel constantly monitors itself for several different trouble conditions. If a trouble condition is present, the Trouble light will be ON and the keypad will beep twice every 10 seconds. The trouble beep can be silenced by pressing any key on any keypad.
To view trouble conditions from an LED keypad:
1. Press [✱] [2].
2. The keypad will flash the Trouble light. The zone indicator lights corresponding to the present trouble conditions will be ON.
When using an LCD keypad, the trouble conditions will be listed on the display; the user must simply use the arrow (< >) keys to scroll through the list of present trouble conditions.
The various troubles are described below:
Trouble [1] – Service Required
If zone indicator light [1] is ON, a “service required” trouble is present. Press [1] to determine the specific trouble. The following is a list of “service required” trouble conditions:
• Light [1] – Low Battery
The main panel backup battery is low. The trouble will be generated if the battery drops below 11.5 volts under load and will be restored when the battery charges to over 12.5 volts.
• Light [2] – Bell Circuit Trouble
The panel will indicate this trouble if the Bell fuse is blown or if the panel senses an open condition on the bell circuit (see Section 5.12 “Siren Supervision”).
• Light [3] – General System Trouble
This trouble will be present if the printer connected to the PC5400 Printer module has a fault and is off-line, or if the ESCORT module does not detect the Power Line Interface Module.
• Light [4] – General System Tamper
This trouble will be indicated if any peripheral module tamper is detected.
• Light [5] – General System Supervisory
This trouble will be indicated if the panel loses communication with any module connected to the KEYBUS (see Section 2.6 “Supervision”). The event buffer will log a detailed description of the event.
Trouble [2] – AC Failure
This trouble indicates that AC power is no longer being supplied to the control unit. The reporting codes in sections [43] and [44] can be programmed to communicate a power failure to the monitoring station. To avoid reporting short power failures to the monitoring station, an AC Failure Communication Delay from 000-255 minutes can be programmed in section [62].
Trouble [3] – Communication Troubles
There are two types of telephone line trouble conditions. Press [3] to display which type of trouble is present:
• [1] – Telephone Line Monitoring Trouble (TLM)
The telephone connection to the control unit is monitored every 10 seconds. If the voltage drops below one to three volts for the number of consecutive checks programmed in section [62], a telephone line trouble is generated.
• [2] – Failure to Communicate (FTC)
This trouble will be generated if the communicator fails to communicate with any of the programmed telephone numbers. If a later attempt is successful, the FTC reporting code(s) programmed in section [45] will be transmitted along with the unreported events from an earlier unsuccessful communication.
8
KEYPADV COMMANDS
Trouble [4] – Zone Fault (including Fire Zone)
This trouble will be generated if any zone on the system is experiencing trouble, meaning that a zone could not provide an alarm to the panel if required to do so. When a zone fault trouble condition occurs, the keypad(s) on the system will start to beep.
Press [4] while in Trouble mode to view the affected zones.
A Fire zone trouble will be generated and displayed in the armed state. A Fire zone trouble will also restart the trouble beeps from all keypads.
Trouble [5] – Zone Tamper
This trouble is only generated by zones configured for Double End Of Line Resistor Supervision when a tamper condition is present. When a tamper condition occurs, the keypad(s) will start to beep. Press [5] while in the Trouble mode to view the affected zones.
Trouble [6] – Loss of System Time
This trouble occurs when the control unit is powered up and the internal clock has not been set. Setting the time with User Function [
][6][Master Code][1] will clear this trouble.
[] [3] Alarm Memory
The ‘Memory’ light will be on if any alarm occurred during the last armed period or – in the case of 24 hour zones – if an alarm occurred while the panel was disarmed.
To view alarm memory:
Press [✱] [3]. The keypad will flash the Memory light and the zone indicator lights corresponding to the alarm or tamper conditions which occurred during or since the last armed period. To clear the Memory light, arm and disarm the system.
[] [4] Door Chime On/Off
The door chime feature is used to sound a tone from the keypad whenever a zone programmed as a chime zone is activated (see Section 5.3 – “Zone Attributes”). If the door chime feature is enabled, the keypad will emit five short beeps whenever a chime zone is activated. Designated entry/exit doors are often defined as chime zones; when the feature is enabled, the keypads will sound when an entry/exit door is opened.
To turn Door Chime ON or OFF:
1. Press [
] [4].
2. The keypad will emit three short beeps if the Door Chime feature is enabled and one long beep when disabled.
The function can also be peformed by pressing and holding the Chime function key for two seconds on any PC5506T or LCD5500T keypad.
[] [5] Programming Access Codes
There are 6 access codes available to the user. They are as follows:
Access code (1)..............................One Master Code
Access codes (2) to (6)..................Five User Codes
All access codes have the ability to arm or disarm the system and can activate the PGM Outputs using the [ [1] [Access Code] and [
] [7] [2] commands.
] [7]
Master Code – Access Code (1)
By default, the Master Code is enabled to perform any keypad function. This code can be used to program all User Codes. If the Master Code Not Changeable option is enabled, the Master Code can only be changed by the Installer.
User Codes – Access Codes (2) to (6)
User codes can arm and disarm the system. By selecting the No Code Required for Bypassing option, each user can also have the ability to bypass zones without entering an access code.
Duress Code – Access Code (6)
If the Sixth Code is Duress Code option is enabled, the sixth code can be programmed by the user as a Duress Code which will send a Duress reporting code to the central station when entered.
For more information regarding access code options, please see Section 5.1 – “Programming Security Codes.”
How to program User Codes:
1. Enter [
] [5] [Master Code]. The keypad will flash the
Program light. The zone indicator lights corresponding to access codes already programmed will turn ON.
2. Enter the number corresponding to the code you wish to program. The corresponding zone light will flash.
3. Enter a 4 digit code. The zone light will turn ON.
4. Continue from step 2 until all codes are programmed. Once the process is complete, press the [#] key to return to the Ready state.
Do not press [✱] or [#] when programming the 4 digit code.
How to erase an Access Code:
] [5] [Master Code], select the code to be erased
Enter [ and press [
].
[] [6] User Functions
This keypad command can be used to program several different functions. The programmable items are listed and described below.
To program User Functions:
1. Press [
2.Press the number [0] to [9] for the item to be
• [1] – Time and Date
• [2] – Auto-Arm Enable/Disable
] [6] [Master Code]. The Program light will
flash.
programmed.
The time and date must be accurate for the Auto-Arm or Test Transmission functions to work properly and for the event buffer to time and date stamp all events.
- Enter the time (hour and minute) using military format [HH MM] from 00:00 to 23:59.
- Enter the date by month, day and year [MM DD YY].
Auto-Arming will not work unless it is enabled for the system. To enable or disable auto-arming, press [2]. The keypad will emit three short beeps if the Auto-Arm feature is enabled and one long beep when disabled. For more information, see Section 3.3 – “Auto-Arming”.
9
KEYPADV COMMANDS
• [3] – Auto-Arm Time
The system can be programmed to Auto-Arm at a certain time. When programming the auto-arming time, enter the time (hour and minute) using military format [HH MM]. For more information, see Section 3.3 – “Auto-Arming”.
• [4] – System Test
When [4] is pressed the panel will test the bell output, keypad lights and the communicator for two seconds. The panel will also send a System Test Reporting code, if programmed (see Section 5.7 – “Communica­tor – Reporting Codes”).
• [5] – Enable DLS (Downloading)
When [5] is pressed, the panel will enable the down­loading option for one hour. During this time the panel will answer incoming downloading calls (see Section
5.9 “Downloading”).
• [6] – User Initiated Call-Up
When [6] is pressed, the panel will initiate call-out to the downloading computer.
• [7] – Last Code to Disarm and Arm
Pressing [7] will display the last code to disarm the system. Then, pressing [9] will display the last code to arm the system.
• [0] – Walk Test Enable / Disable
The Installer Walk Test can be used to verify that each zone of the panel is functioning properly. Any zone violated during a walk test will cause the panel to activate the Bell Output for two seconds, log the event to the Event Buffer and communicate the alarm to central station. Do not tamper or fault zones while in walk test. You can exit walk test with zones open. You can cancel walk test by arming with all zones restored.
Additional Features using the LCD Keypad
Additional features, including access to the Event Buffer, are available using the LCD keypad. Use the arrow keys (< >) to scroll through the [
] [6] menu and press the [✱] key to select
the following commands:
Viewing the Event Buffer from an LCD Keypad
Select “View Event Buffer” from the [
] [6] menu. The
keypad will display the event, event number, time and date along with the zone number and user code, if applicable. Press [
] to toggle between this information and the event
itself. Use the arrow keys (<>) to scroll through the events in the buffer. When you have finished viewing the Event Buffer, press the [#] key to exit.
Brightness Control
The LCD keypad will allow you to select from 10 different backlighting levels. Use the arrow keys (< >) to scroll to the desired backlighting level and press the [#] key to exit.
Contrast Control
The LCD keypad will allow you to select from 10 different display contrast levels. Use the arrow keys (< >) to scroll to the desired contrast level and press the [#] key to exit.
Keypad Beeper Control
The LCD keypad will allow you to select from 21 different keypad beeper tones. Use the arrow keys (< >) to scroll to the desired keypad beeper level and press the [#] key to exit. This featured can be accessed on LED keypads by holding the [
] key.
[] [7] Output Functions
There are two output functions available to the user: Utility Output and Sensor Reset.
To activate Utility Output:
] [7] [1][Access Code].
Press [ The panel will activate all PGM Outputs programmed as
utility outputs for five seconds (see Section 5.10 – “PGM Outputs”).
To activate Sensor Reset:
] [7] [2].
Press [ The panel will activate all PGM Outputs programmed as
Sensor Reset for five seconds. This function can also be performed by pressing and
holding the Reset function key for two seconds on any PC5506T or LCD5500T keypad.
[] [8] Installer’s Programming
Enter [✱] [8] followed by the Installer’s Code to enter this function. Installer’s Programming is outlined in detail in Sections 4 and 5 of this manual.
[] [9] Arming Without Entry Delay
When the system is armed with the [✱] [9] command, the panel will cancel the entry delay. Once the exit delay has expired, Delay 1 and Delay 2 type zones will be instant and Stay/Away zones will be bypassed (see Section 5.2 – “Zone Definitions”). A valid access code must be entered after pressing [
] [9].
[] [0] Quick Arm
If the Quick Arm option is enabled, the panel can be armed without a user code by entering [
] [0] (See Section 5.15
“Arming / Disarming Options”).
Quick Arm cannot be used to cancel Auto Arm.
Quick Exit
The Quick Exit function, if enabled, will allow someone to leave an armed premises through a Delay type zone without having to disarm and rearm the system (See Section 5.15 “Arming / Disarming Options”).
When [
] [0] is entered, the panel will provide a two minute
window for the user to exit the premises. During this time, the panel will ignore only one activation of a Delay zone. When the Delay zone is secured, the panel will end the two minute quick exit delay.
If a second Delay zone is tripped or if the zone is not restored after two minutes, the panel will begin the entry delay.
If the Exit Delay is in progress, performing a Quick Exit will not extend the Exit Delay.
3.5 Function Keys
The function keys only appear on the PC5506T and LCD5500T keypads
There are five function keys on the PC5506T and LCD5500T keypads located to the right of the number pad labelled Stay, Away, Chime, Reset and Exit. Each of these keys are programmed by default to perform one of the functions
10
KEYPADV COMMANDS
[06] – [
described below. A function is activated by pressing and holding the appropriate key for two seconds.
“Stay” – Stay Arm
Pressing this key will arm the system in the Stay mode, meaning that all Stay/Away type zones will be automatically bypassed. Delay type zones will provide entry and exit delay. The Quick Arm feature must be enabled in order for this key to function (programming section [10], option [6]).
“Away” – Away Arm
Pressing this key will arm the system in the Away mode. All Stay/Away type zones and all other non-bypassed zones will be active at the end of the exit delay. Delay type zones will provide entry and exit delay. The Quick Arm feature must be enabled in order for this key to function.
“Chime” – Door Chime On / Off
Pressing this key will toggle the Door Chime feature ON or OFF. One solid beep means that the feature has been disabled and three short beeps means that it has been enabled (see Section 3.4 – “[
] [4] Door Chime”).
“Reset” – Reset Smoke Detectors
Pressing this key will cause the panel to activate for five seconds all PGM outputs programmed as Sensor Reset.
“Exit” – Activate Quick Exit
Pressing this key will cause the panel to activate the Quick Exit feature (See Section 3.4 – “[
] [0] Quick Exit”).
3.5.1 Function Key Options
The following is a list of Function Key options available. Each option is listed according to their programming code, followed by their corresponding [
] key command. For more
information regarding each function, please refer to the appropriate segment in section 3.4 (“[
] Commands”)
[00] – Null Key
The key is not used and will perform no function when pressed.
[01]-[02]– Not Used [03] – Stay Arm
Same as described in Function Keys – Section 3.5.
[04] – Away Arm
Same as described in Function Keys – Section 3.5.
] [9] No-Entry Delay Arm
[05] – [
Once this function key is pressed the user must enter a valid
] [4] Door Chime On / Off
Same as described in Function Keys – Section 3.5.
] [6] [----] [4] System Test
[07] – [
This function key provides the user with a simple method for testing the system.
] [1] Bypass Mode
[08] – [
This function key provides the user with a simple method for entering the Bypass Mode. If a user code is required, it must be entered before zone bypassing can be performed.
] [2] Trouble Display
[09] – [
This function key provides the user with a simple method for entering the Trouble Display Mode.
] [3] Alarm Memory
[10] – [
This function key provides the user with a simple method for entering the Alarm Memory Display Mode.
] [5] Programming Access Codes
[11] – [
This function key provides the user with a simple method for programming user codes. Once this key is pressed, a valid master code must be entered before the panel will allow programming to be performed.
[12] – [
] [6] User Functions
This function key provides the user with a simple method for programming user functions. Once this key is pressed, the Master code must be entered before the panel will allow user functions to be performed.
[13] – [
] [7] [1] Utility Output
This function key provides the user with a simple method for activating a PGM Output programmed as utility output (see section 5.10 – “PGM outputs”). Once this key is pressed, a valid user code must be entered.
[14] – [
] [7] [2] Sensor Reset
Same as described in Function Keys – Section 3.5.
[15] – Not Used
] [0] Quick Exit
[16] – [
Same as described in Function Keys – Section 3.5.
] [1] Reactivate Stay/Away Zones
[17] – [
This function key provides the user with a simple method for adding Stay/Away zones back into the system at night-time (see Section 3.4 – “[
] [1] Bypassing and Reactivating Stay/
Away Zones”).
user code. The system will arm and remove the entry delay from the system when the exit delay expires (see Section 3.4 – “[
] [9] Arming Without Entry Delay”).
11
G E T T I N G S T A R T E D
How to Program
SECTION4
The following section of the manual describes the Installer’s Programming function and how to program the various sections.
You must read the following section of the manual very carefully before you begin programming. We also recommend filling out the Programming Worksheets before you program the panel.
For your reference, the corresponding programming sections for the functions listed are highlighted in text boxes such as this one.
4.1 Installer’s Programming
Installer’s Programming is used to program all communicator and panel options. The Installer’s Code is [1575] by default but may be changed to prevent unauthorized access to programming.
Installer Code ......................................................... Section [03]
From an LED Keypad: Step 1 Enter [
Step 2 Enter the two digit Section number corresponding
Step 3 Enter the information required to complete
If the two digit Section numbered entered is invalid, or if the module which pertains to the section is not present, the keypad will sound a two second error tone.
From an LCD Keypad:
Step 1 From any keypad, enter [
Step 2 Enter the two digit number corresponding to
Step 3 Enter the information required to complete
If you enter information into a section and make a mistake, press the [#] key to exit the section. Select that section again and re-enter the information correctly.
] [8] [Installer’s Code].
• The Program light will flash to indicate you are in programming mode.
• The Armed light will turn ON to indicate that the panel is waiting for the two digit programming section number.
to the section you wish to program.
• The Armed light will turn OFF.
• The Ready light will turn ON to indicate that the panel is waiting for the information required to complete programming the selected section.
section programming (ie: numbers, HEX data, or ON/OFF options).
] [8] [Installer’s
Code]. The Keypad will display ‘Enter Section’ followed by two dashes.
the programming section number you wish to program. The keypad will now display the information required to complete programming the selected section.
section programming (ie: numbers, HEX data, or ON/OFF options).
4.2 Programming Decimal Data
A set number of programming boxes are allotted for each section requiring decimal data (e.g.: codes, telephone numbers). If a digit is entered for each program box, the panel will automatically exit from the selected programming section. The Ready light will turn OFF and the Armed light will turn ON.
You can also press the [#] key to exit a programming section without entering data for every box. This is handy if you only need to change digits in the first few programming boxes. All other digits in the programming section will remain unchanged.
4.3 Programming HEX Data
On occasion, hexadecimal (HEX) digits may be required. To program a HEX digit press the [ HEX programming and Ready light will begin to flash.
The following are the numbers which should be pressed to enter the appropriate HEX digit:
1 = A 2 = B 3 = C 4 = D 5 = E 6 = F
After the correct HEX digit is entered, the Ready light will continue to flash. If another HEX digit is required, press the corresponding number. If a decimal digit is required, press the [
] key again. The Ready light will turn ON and the panel
will return to regular decimal programming.
Example:
To enter ‘C1’ for a closing by user 1, you would enter
[
] to enter Hexadecimal mode (Ready light flashes)
[ [3] to enter C
] to return to decimal mode (Ready light is solid);
[ [1] to enter digit 1
If Ready light is flashing, any number you enter will be programmed as the HEX equivalent.
If you are using a pulse format, a decimal zero [0] does not transmit. Programming a zero [0] tells the panel not to send any pulses for that digit. Decimal zero [0] is a filler digit. To make a zero [0] transmit, it must be programmed as a Hexadecimal ‘A’.
Example:
For the three digit account number ‘403’, you would enter
[4], [
[4] to enter the digit 4;
] to enter Hexadecimal mode (Ready light flashes)
[ [1] to enter A
] to return to decimal mode (Ready light is solid);
[ [3] to enter the digit 3; [0] to enter the digit 0 as a filler digit.
] key. The panel will enter
] [3] [] , [1]
] [1] [] [3], [0].
4.4 Programming Toggle Option Sections
Some Sections contain several toggle options. The panel will use zone lights 1 through 6 to indicate if the different options are enabled or disabled. Press the number corresponding to the option to turn it ON or OFF. Once all the toggle options have been selected correctly, press the [#] key to exit the section and save the changes. The Ready
12
HOWV TOV PROGRAM
light will turn OFF and the Armed light will turn ON. Refer to Section 5 in this manual to determine what each
option represents and whether the light should be ON or OFF for your application.
4.5 Viewing Programming
LED Keypads
Any programming section can be viewed from an LED keypad. When a programming section is entered, the keypad will immediately display the first digit of information programmed in that section.
The keypad displays the information using a binary format, where
Zone Light 1 = 1 Zone Light 2 = 2 Zone Light 3 = 4 Zone Light 4 = 8
Add up the values for the zone lights to determine the number displayed (for example, no zone lights = 0, all 4 zone lights = 15 HEX ‘F’).
Press any of the Emergency Keys (Fire, Auxiliary or Panic) to advance to the next digit. When all the digits in a section have been viewed, the panel will exit the section; the Ready Light will turn OFF and the Armed light will turn ON, waiting for the next two digit programming section number to be entered. Press the [#] key to exit the section
LCD Keypad
When a programming section is entered, the keypad will immediately display all the information programmed in that section.
Use the arrow keys (< >) to scroll through the data being displayed.
Scroll past the end of the data displayed or press the [#] key to exit the section.
13
G E T T I N G S T A R T E D
Program Descriptions
SECTION5
The following section explains the operation of all programmable features and options and provides a summary of all corresponding programming locations.
5.1 Programming Security Codes
There are three codes which can be programmed by the installer in the Installer’s Programming function: the Master Code, a Second Master Code, and the Installer’s Code. All other access codes can be programmed through the [ command (see Section 3.4).
The Master Code can also be programmed by the user as access code (1). If the Master Code Not Changeable option is enabled, the System Master Code can only be changed by the Installer.
User codes can arm and disarm the system. By selecting the No Code Required for Bypassing option, each user code can also have the ability to bypass zones without entering the Master Code.
If the Sixth Code is Duress Code option is enabled, the sixth code can be programmed by the user as a Duress Code which will send a Duress Reporting Code to the central station when entered.
If the 6-Digit User Access Codes option is enabled, all the access codes may be programmed with six digits instead of four, with the exception of the Panel ID code and the Downloading Access Code.
Installer’s Code ....................................................... Section [03]
Master Code............................................................ Section [04]
Second Master Code.............................................. Section [05]
Master Code Not Changeable ............. Section [09], option [1]
No Code Required for Bypassing........Section [09], option [2]
Sixth Code is Duress Code..................Section [09], option [3]
6-Digit User Access Codes .................. Section [81], option [4]
When enabling 6-digit access codes, if the master code is anything other than default, the last two digits will be [00].
] [5]
5.2 Zone Definitions
These sections will allow you to select how each of the 6 zones will operate. Each zone requires a two digit entry. In addition to zone definitions, six different attributes may be programmed by zone (see Section 5.3 – “Zone Attributes”).
[00] Null Zone
The zone is vacant. Unused zones should be programmed as Null zones.
[01] Delay 1
This zone type, normally used for entry/exit doors, can be violated during the exit delay time without causing an alarm. Once the exit delay has expired, opening the zone will start the entry delay timer. During the entry delay time, the keypad buzzer will sound steadily to advise the user that the system should be disarmed. If the panel is disarmed before the entry time expires, no alarm will be generated.
[02] Delay 2
The Delay 2 entry delay time can be set independent of Delay 1 in programming section [02] (System Times).
[03] Instant Zone
This zone type will cause an instant alarm if it is violated when the panel is armed. Typically, this zone is used for windows, patio doors or other perimeter zones.
[04] Interior Zone
This zone will not cause an alarm if violated during the entry delay. If the zone is violated before the entry delay has begun, it will cause an instant alarm. Typically, this zone is used for interior protection devices, such as motion detectors.
[05] Interior Stay/Away Zone
This zone type works similar to the Interior zone type except that it will be automatically bypassed under the following conditions:
• When the panel is armed in the Stay Mode (see Section
3.5 – “Function Keys”).
• When the panel is armed without entry delay (see Section 3.4 – “[] [9] Arming Without Entry Delay”).
• When the panel is armed with a user code and a Delay type zone is NOT tripped during the exit delay.
The automatic bypass prevents the user from having to manually bypass interior type zones when arming at home. This zone is typically used for interior protection devices, such as motion detectors.
[06] Delay Stay/Away Zone
This zone type will operate similar to Interior Stay/Away zones except that it will always provide an entry delay. Typically, this zone is used for interior protection devices, such as motion detectors. This zone option will help prevent false alarms since it always provides an entry delay time for the user to turn off the panel.
[07] Delayed 24 Hour Fire Zone
When this zone is violated, the alarm output will be immediately activated but the communicator will be delayed for 30 seconds. If the user presses any key on any keypad during this delay, the alarm output and the communicator will be delayed an additional 90 seconds, giving the user time to correct the problem. If the zone is still violated after the 90 second delay, the panel will sound the alarm ouput and delay the communicator for 30 seconds. If the user does not press a key during the 30 second delay, the alarm output will latch and the panel will communicate the alarm to the central station. The alarm will sound for the Bell Cutoff time programmed in Section [02] (“System Times”).
If a second Fire type zone is violated or if the Fire keys are pressed during the delay period, the panel will latch the alarm output and will immediately communicate the alarm.
A violated Fire zone will be displayed on all keypads and can be delayed at any keypad. Typically this zone is used for latching smoke detectors.
[08] Standard 24 Hour Fire Zone
When this zone is violated, the panel will immediately latch the alarm output and communicate to the central station. The alarm will sound for the Bell Cutoff time programmed in Section [02] (“System Times”). A violated Fire zone will be displayed on all keypads. Typically this zone is used for pull stations.
14
Loading...
+ 30 hidden pages